Loading...
HomeMy WebLinkAboutPLANS Remodel Cabin 5-6 1750 Fall River Rd 2021-10-06PERMIT #21-EP-00468 Field Copy Print out in color and have on site for inspector Bathrooms - 15 & 20 amp circuit installed in bathrooms to be GFCI protected Arc fault protection required at electrical openings - except bathrooms Provide Tamper Resistant Receptacles Replacement of existing receptacles outlets shall comply with NEC 406.4 D 1-6 Cement based substrate or equal on shower/tub walls Glazing installed in hazardous locations as defined in Section R308.4 shall be Tempered Glass Freeze Protect pipes per P2603.5 Provide 50 cfm fan in bathroom - vented to exterior - when no natural ventilation is provided by window Fire Block shall be provided in wood framed walls per locations designated in R302.11 Provide Anti-Scald valves on shower or tub/shower combination valves Toilets & Lavatories & Shower - See Figure R307.1 for clearances Showers shall be finished 72" above floor with non-absorbent material. Shower door min. clear opening 24" SD/CO - SD to be installed inside of each separate sleeping area and outside each door in the immediate vicinity of the bedrooms. (R315.3) CO must be installed outside each bedroom within 15' of each room Air gap required at or within dishwasher - per P2717.1 Appliance and all Equipment Vent Terminations shall be per manufacturers specifications If kitchen hood greater than 400 cfm, must have approx equal make up air on automatically controlled damper - Per M1503.6 Hardwired appliances are required to have a disconnect within sight or a lockable means at circuit breaker APPROVED by SAFEbuilt; 2015 International Codes Subject to inspection and compliance to all Relevant, adopted Building & Municipal Codes 10/06/2021 REVIEWED BY SAFEBUILT - PBLAND