HomeMy WebLinkAboutPLANS PV System 900 Moraine Ave 2021-11-17Rev
SRU-HP
ASTRO CHSM72M(DG)-F-GH
Structure adjusted to
23.0 kW
56
303-552-7468
ddandeneau@ipoweralliance.com
Colorado, US
900 Moraine, Estes Park
IPA-21032402
ESTES PARK
PRESENTATION
L.A.F.P.
2021-08-12
PV0.0011:40
Revision
DC Size :
agreement with, the above statement.
Notice
document, the client understands, and is in full
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
validity of any roof warranty, ballasting or anchoring of the
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# DateReview
08-12-2021
E-mail : projects@opsun.com
new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
IPA-21032402-PV0.00
Digitally signed by Christopher S
Klinga P.E.
DN: C=US, E=chris@solmotiv.com,
O=SolMotiv LLC, CN=Christopher
S Klinga P.E.
Location: Boulder, CO
Reason: I am the author of this
document
Contact Info: 303 859 5570
Date: 2021.09.01 12:01:38-06'00'
21-ep-00471
I-CODES 2015
PRINT PLANS IN COLOR AND HAVE FOR
INSPECTOR AT TIME OF INSPECTION
SAFEbuilt
APPROVED
Subject to inspection and
compliance to all relevant
Adopted Building and Municipal
codes.
Changes in Plans MUST be
approved.
D.GRAHAM
11/17/2021
PATHWAYS DO NOT MEET CODE REQUIREMENTS. THE
PATHWAYS HAVE BEEN REVIEWED BY THE FIRE DEPARTMENT
AND APPROVED SEE LETTER DATED 10.14.2021
VALID:
-End surfaces fully in contact.
-Lock nut fully inserted.
-Lock nut and screw
assembled the proper way.
INVALID:
End surfaces not fully in contact.
INVALID:
Lock nut not fully inserted.
INVALID:
Lock nut and screw
assembled backwards
PROPER LOCK NUT AND
SCREW ASSEMBLY (BACKSLASH).
INVALID LOCK NUT AND
SCREW ASSEMBLY (SLASH).
08-12-2021
56
SRU-HP
ESTES PARK
01
structure dimensions
Rev
F.P.
NOTES
ddandeneau@ipoweralliance.com
Colorado, US
1
IPA-21032402-PV0.100
PV0.
L.A.
2021-08-12
Revision
IPA-21032402
1:96
900 Moraine, Estes Park
DC Size :
Updated with new
Review
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
23.0 kW
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# Date
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
303-552-7468
ASTRO CHSM72M(DG)-F-GH
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
E-mail : projects@opsun.com
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
10
1.0 GENERAL NOTES
1.1 THE CONTRACTOR(S) MUST VISIT SITE AND COMPARE ALL SITE CHARACTERISTICS WITH OPSUN’S PLANS AND MUST REPORT ANY
DISCREPANCIES TO OPSUN WITHOUT DELAYS BEFORE PROCEEDING WITH THE WORK. ANY DEVIATION FROM OPSUN’S PLANS DURING
INSTALLATION MUST BE REPORTED TO OPSUN.
1.2 THE ENGINEER DOES NOT TAKE ANY RESPONSIBILITY FOR ROOF UPLIFT WHERE THE ROOFS HAVE NOT BEEN ADEQUATELY TIED TO THE
FOUNDATIONS AS REQUIRED BY THE RELEVANT BUILDING CODES.
1.3 OPSUN ASSUMES THAT THE PV SYSTEM IS INSTALLED IN ACCORDANCE WITH REGULATIONS FROM MUNICIPAL AUTHORITIES, AND THAT IT
CONFORMS WITH ALL SUCH REQUIREMENTS OF THE RELEVANT BUILDING CODES AND MUNICIPAL LAWS. OPSUN ALSO ASSUMES THAT THE
BUILDING WAS PREVIOUSLY APPROVED BY THE MUNICIPAL BUILDING DEPARTMENT, AND THAT IT CONFORMS WITH REQUIREMENTS OF THE
RELEVANT BUILDING CODES.
1.4 PROVIDE A MINIMUM SEPARATION BETWEEN THE RACKING SYSTEM AND ROOF EDGE AS NOTED ON THE DRAWING, OR AS REQUIRED BY
LOCAL LAWS AND REGULATIONS.
1.5 REVIEW OF THE STRUCTURAL CAPACITY OF THE EXISTING ROOF TO SUPPORT THE PV SYSTEM IS TO BE DONE BY OTHERS.
1.6 THE RACKING SYSTEM IS DESIGNED TO RESIST UPLIFT, OVERTURNING, AND SLIDING.
1.7 NOTES ON THIS PAGE NOTES ON THIS PAGE APPLY BY DEFAULT. CAN DIFFER WHERE INDICATED IN THIS DOCUMENT
2.0 GENERAL INSTALLATION NOTES
2.1 READ STRUCTURAL DRAWINGS / BUILDING PERMIT DRAWINGS / CONSTRUCTION DRAWINGS IN CONJUNCTION WITH THE
PRODUCT INSTALLATION INSTRUCTIONS (WITHIN THIS DOCUMENT AND/OR OTHER PROVIDED DOCUMENTS).
2.2 ON-SITE POSITIONING OF COMPONENTS, SUB-ASSEMBLIES AND ASSEMBLIES MUST BE DONE USING DIMENSIONS PROVIDED IN THIS
DOCUMENT. IF POSITIONING WITH THE PROVIDED DIMENSIONS IS NOT POSSIBLE, THE INSTALLER SHALL CONTACT AN OPSUN
REPRESENTATIVE. ELEMENTS POSITIONED ELSEWHERE THAN WHERE INDICATED ON PLANS SHALL VOID ALL WARRANTY.
2.3 ANY PERMANENT DEFORMATION (PLASTIC DEFORMATION) DUE TO OVER-TORQUING, HANDLING, SHIPPING OR ANY OTHER
REASON SHALL BE BROUGHT TO THE ATTENTION OF AN OPSUN SYSTEMS REPRESENTATIVE WITHOUT DELAYS.
2.4 1.1 THERE MUST BE A MINIMAL 13MM (0.5IN) THERMAL BREAK FOR ANY CONTINUOUS RAIL LENGTH OF 14.6M (48FT). NO PANEL
SHALL BE INSTALLED OVER SUCH THERMAL BREAK.
2.5 IF THE INSTALLER BREAKS THE ADHESIVE OF THE PROVIDED HEX CAP SCREWS WITH LOCTITE BY TIGHTENING AND UNTIGHTENING
THE FASTENER, THE INSTALLER MUST USE NEW FASTENERS, APPLY LOCTITE 204 OR EQUIVALENT, OR USE AN ADEQUATE LOCK WASHER.
2.6 ALL PV WIRES MUST BE SECURED USING AN APPROPRIATE CABLE TIE OR STAINLESS STEEL CABLE CLIP (WILEY / BURNDY OR EQ. BY
OTHERS) ATTACHED TO THE RACKING STRUCTURE AT EACH 1M (3.28 FT).
2.7 OPSUN'S LOCK NUT (LN1):
2.7.1 END SURFACES OF THE LOCK NUT MUST
BE FULLY IN CONTACT WITH THE INTERIOR
SURFACES OF RAILS.
2.7.2 LOCK NUTS MUST BE FULLY INSERTED INTO
RAIL SLOTS. LOCK NUTS MUST NOT PROTRUDE
AT RAIL ENDS.
2.7.3 LOCK NUTS MUST BE ASSEMBLED TO
LOOK LIKE A BACKSLASH WHEN LOOKING AT
THE FASTENERS’ HEAD.
2.8 REQUIRED FASTENERS TIGHTENING TORQUE:
2.8.1 3/8" HEX CAP SCREWS (BL-SS-3/8-XX) COUPLED TO LOCK NUTS (LN-1) MUST BE TORQUED AT 16 N·m (12 lbf· ft).
2.8.2 3/8" HEX CAP SCREWS (BL-SS-3/8-XX) COUPLED TO HEX NUTS (N-SS-3/8) OR KEPS NUTS (KN-SS-3/8) MUST BE TORQUED AT 27 N·m (20 lbf· ft).
2.8.3 TORX SCREWS (CLICLOCS) MUST BE TORQUED AT 12-14 N·m (9-10 lbf· ft).
2.8.4 M8 SCREWS COUPLED TO FIT NUTS (FN1-AL) MUST BE TORQUED AT 9.0 N·m (80 lbf· in).
2.8.5 1/2"HEX CAP SCREWS (BL-SS-1/2-XX) COUPLED TO HEX NUTS (N-SS-1/2) MUST BE TORQUED AT 58.3 N·m (43 lbf· ft).
2.8.6 1/4"HEX CAP SCREWS (BL-SS-1/4-XX) COUPLED TO HEX NUTS (N-SS-1/4) MUST BE TORQUED AT 8.5 N·m (75.2 lbf· in)
2.8.7 10/32"HEX CAP SCREWS (BL-SS-10/32-XX) COUPLED TO HEX NUTS (N-SS-10/32) MUST BE TORQUED AT 3.6 N·m (32 lbf· in).
3.0 MATERIALS
3.1 RAILS ARE MADE OF ALUMINIUM 6005A-T61.
3.2 FIXTURES ARE MADE OF ALUMINUM 6005A-T61, 6005-T5 AND 6061-T6.
3.3 ALL FASTENERS ARE MADE OF STAINLESS STEEL 304 AND 316 EXCEPT WHERE INDICATED.
3.4 LOCK NUTS (LN1) AND FIT NUTS (FN1) ARE MADE OF ALUMINUM 6061-T6.
4.0 DESIGN/CODES COMPLIANCE AND REFERENCES
4.1 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES [ASCE 7-10]
4.2 ESTES PARK BUILDING CODE
4.2 IBC 2015
4.3 ALUMINUM ASSOCIATION - ALUMINUM DESIGN MANUAL, 2015
4.4 AISC DESIGN GUIDE 27 - STRUCTURAL STAINLESS STEEL
4.5 WIND LOAD ON OPSUN PV MOUNTING SYSTEMS, BLWT-SS36-2010, ALAN DAVENPORT WIND ENGINEERING GROUP, S. FARQUHAR,
G.A. KOPP WIND LOAD ZONING FOR OPSUN ROOF MOUNTED SOLAR ARRAYS, OPSUN ROOF ZONING-MARCH 25, 2014 LETTER
REPORT
4.6 THE BOUNDARY LAYER WIND TUNNEL LABORATORY, «ROOF MOUNTED PV ARRAY - EXPANSION OF WIND TUNNEL STUDY RESULTS»,
WESTERN UNIVERSITY, S. FARQUHAR, G.A. KOPP, FEBRUARY 22 2018 RWDI REPORT #1701352, PV PANEL SNOW ASSESSMENT, A.
BROOKS, E. CHRUSCINSKI, MAY 16 2018.
4.7 THE ADDITION OF THE SOLAR PANELS IS NOT EXPECTED TO RESULT IN SIGNIFICANT CHANGES TO OVERALL ROOF SNOW LOADS
AND PATTERNS. WITH SOLAR PANELS IN PLACE, SNOW LOADS TEND TO CONCENTRATE IN THE SPACES BETWEEN ROWS AND IN THE
GAPS BETWEEN MODULES.THE DESIGN SNOW LOADS FOR THE PV PANEL SURFACES THEMSELVES ARE USUALLY EQUIVALENT TO THE
WORSE SNOW FALL EVENT IN 50 YEARS.
5.0 SPECIFIED COMPONENT CERTIFICATION
5.1 FATH CLICLOC (SOLAR MODULE END AND MID CLAMPS) SHOULD BE IN ACCORDANCE WITH : CSA C22.2#41 GROUNDING AND BONDING EQUIPMENT;
AND ANSI-UL 467 ED.9 STANDARD FOR SAFETY FOR GROUNDING AND BONDING EQUIPMENT.
5.2 PV MODULES (BY OTHERS) SHOULD BE IN ACCORDANCE WITH UL-1703. GROUND LUGS (BY OTHERS) SHOULD BE IN ACCORDANCE WITH ANSI-UL 467 ED.9
STANDARD FOR SAFETY FOR GROUNDING AND BONDING EQUIPMENT.
LATITUDE, LONGITUDE 40.36415,-105.54390
DESIGN CRITERIA
CODE(S)ASCE 7-10
CITY REFERENCE ESTES PARK BUILDING CODE
RISK CATEGORY II
WIND
BASIC WIND SPEED, V 175 MPH
EXPOSURE CATEGORY C
ROOF HEIGHT 17 FT
EXPOSURE COEFFICIENT, Kz 0.87
DIRECTIONALITY FACTOR, Kd 0.85
TOPOGRAPHIC FACTOR, Kzt 1
SNOW
GROUND SNOW LOAD, Pg 70 PSF
IMPORTANCE FACTOR, IS 1
THERMAL FACTOR, Ct 1.2
EXPOSURE FACTOR, Ce 0.9
PV MODULE
MANUFACTURER ASTROENERGY
MODEL CHSM72M(DG)-F-BH
DIMENSIONS 6.69 FT X 3.31 FT
MASS 58 LBS
LATITUDE, LONGITUDE 40.36415,-105.54390
DESIGN CRITERIA
CODE(S)ASCE 7-10
CITY REFERENCE ESTES PARK BUILDING CODE
RISK CATEGORY II
WIND
BASIC WIND SPEED, V 175 MPH
EXPOSURE CATEGORY C
ROOF HEIGHT 17 FT
EXPOSURE COEFFICIENT, Kz 0.87
DIRECTIONALITY FACTOR, Kd 0.85
TOPOGRAPHIC FACTOR, Kzt 1
SNOW
GROUND SNOW LOAD, Pg 70 PSF
IMPORTANCE FACTOR, IS 1
THERMAL FACTOR, Ct 1.2
EXPOSURE FACTOR, Ce 0.9
PV MODULE
MANUFACTURER ASTROENERGY
MODEL CHSM72M(DG)-F-BH
DIMENSIONS 6.69 FT X 3.31 FT
MASS 58 LBS
1.0 GENERAL NOTES
1.1 THE CONTRACTOR(S) MUST VISIT SITE AND COMPARE ALL SITE CHARACTERISTICS WITH OPSUN’S PLANS AND MUST REPORT ANY
DISCREPANCIES TO OPSUN WITHOUT DELAYS BEFORE PROCEEDING WITH THE WORK. ANY DEVIATION FROM OPSUN’S PLANS DURING
INSTALLATION MUST BE REPORTED TO OPSUN.
1.2 THE ENGINEER DOES NOT TAKE ANY RESPONSIBILITY FOR ROOF UPLIFT WHERE THE ROOFS HAVE NOT BEEN ADEQUATELY TIED TO THE
FOUNDATIONS AS REQUIRED BY THE RELEVANT BUILDING CODES.
1.3 OPSUN ASSUMES THAT THE PV SYSTEM IS INSTALLED IN ACCORDANCE WITH REGULATIONS FROM MUNICIPAL AUTHORITIES, AND THAT IT
CONFORMS WITH ALL SUCH REQUIREMENTS OF THE RELEVANT BUILDING CODES AND MUNICIPAL LAWS. OPSUN ALSO ASSUMES THAT THE
BUILDING WAS PREVIOUSLY APPROVED BY THE MUNICIPAL BUILDING DEPARTMENT, AND THAT IT CONFORMS WITH REQUIREMENTS OF THE
RELEVANT BUILDING CODES.
1.4 PROVIDE A MINIMUM SEPARATION BETWEEN THE RACKING SYSTEM AND ROOF EDGE AS NOTED ON THE DRAWING, OR AS REQUIRED BY
LOCAL LAWS AND REGULATIONS.
1.5 REVIEW OF THE STRUCTURAL CAPACITY OF THE EXISTING ROOF TO SUPPORT THE PV SYSTEM IS TO BE DONE BY OTHERS.
1.6 THE RACKING SYSTEM IS DESIGNED TO RESIST UPLIFT, OVERTURNING, AND SLIDING.
1.7 NOTES ON THIS PAGE NOTES ON THIS PAGE APPLY BY DEFAULT. CAN DIFFER WHERE INDICATED IN THIS DOCUMENT
2.0 GENERAL INSTALLATION NOTES
2.1 READ STRUCTURAL DRAWINGS / BUILDING PERMIT DRAWINGS / CONSTRUCTION DRAWINGS IN CONJUNCTION WITH THE
PRODUCT INSTALLATION INSTRUCTIONS (WITHIN THIS DOCUMENT AND/OR OTHER PROVIDED DOCUMENTS).
2.2 ON-SITE POSITIONING OF COMPONENTS, SUB-ASSEMBLIES AND ASSEMBLIES MUST BE DONE USING DIMENSIONS PROVIDED IN THIS
DOCUMENT. IF POSITIONING WITH THE PROVIDED DIMENSIONS IS NOT POSSIBLE, THE INSTALLER SHALL CONTACT AN OPSUN
REPRESENTATIVE. ELEMENTS POSITIONED ELSEWHERE THAN WHERE INDICATED ON PLANS SHALL VOID ALL WARRANTY.
2.3 ANY PERMANENT DEFORMATION (PLASTIC DEFORMATION) DUE TO OVER-TORQUING, HANDLING, SHIPPING OR ANY OTHER
REASON SHALL BE BROUGHT TO THE ATTENTION OF AN OPSUN SYSTEMS REPRESENTATIVE WITHOUT DELAYS.
2.4 1.1 THERE MUST BE A MINIMAL 13MM (0.5IN) THERMAL BREAK FOR ANY CONTINUOUS RAIL LENGTH OF 14.6M (48FT). NO PANEL
SHALL BE INSTALLED OVER SUCH THERMAL BREAK.
2.5 IF THE INSTALLER BREAKS THE ADHESIVE OF THE PROVIDED HEX CAP SCREWS WITH LOCTITE BY TIGHTENING AND UNTIGHTENING
THE FASTENER, THE INSTALLER MUST USE NEW FASTENERS, APPLY LOCTITE 204 OR EQUIVALENT, OR USE AN ADEQUATE LOCK WASHER.
2.6 ALL PV WIRES MUST BE SECURED USING AN APPROPRIATE CABLE TIE OR STAINLESS STEEL CABLE CLIP (WILEY / BURNDY OR EQ. BY
OTHERS) ATTACHED TO THE RACKING STRUCTURE AT EACH 1M (3.28 FT).
2.7 OPSUN'S LOCK NUT (LN1):
2.7.1 END SURFACES OF THE LOCK NUT MUST
BE FULLY IN CONTACT WITH THE INTERIOR
SURFACES OF RAILS.
2.7.2 LOCK NUTS MUST BE FULLY INSERTED INTO
RAIL SLOTS. LOCK NUTS MUST NOT PROTRUDE
AT RAIL ENDS.
2.7.3 LOCK NUTS MUST BE ASSEMBLED TO
LOOK LIKE A BACKSLASH WHEN LOOKING AT
THE FASTENERS’ HEAD.
2.8 REQUIRED FASTENERS TIGHTENING TORQUE:
2.8.1 3/8" HEX CAP SCREWS (BL-SS-3/8-XX) COUPLED TO LOCK NUTS (LN-1) MUST BE TORQUED AT 16 N·m (12 lbf· ft).
2.8.2 3/8" HEX CAP SCREWS (BL-SS-3/8-XX) COUPLED TO HEX NUTS (N-SS-3/8) OR KEPS NUTS (KN-SS-3/8) MUST BE TORQUED AT 27 N·m (20 lbf· ft).
2.8.3 TORX SCREWS (CLICLOCS) MUST BE TORQUED AT 12-14 N·m (9-10 lbf· ft).
2.8.4 M8 SCREWS COUPLED TO FIT NUTS (FN1-AL) MUST BE TORQUED AT 9.0 N·m (80 lbf· in).
2.8.5 1/2"HEX CAP SCREWS (BL-SS-1/2-XX) COUPLED TO HEX NUTS (N-SS-1/2) MUST BE TORQUED AT 58.3 N·m (43 lbf· ft).
2.8.6 1/4"HEX CAP SCREWS (BL-SS-1/4-XX) COUPLED TO HEX NUTS (N-SS-1/4) MUST BE TORQUED AT 8.5 N·m (75.2 lbf· in)
2.8.7 10/32"HEX CAP SCREWS (BL-SS-10/32-XX) COUPLED TO HEX NUTS (N-SS-10/32) MUST BE TORQUED AT 3.6 N·m (32 lbf· in).
3.0 MATERIALS
3.1 RAILS ARE MADE OF ALUMINIUM 6005A-T61.
3.2 FIXTURES ARE MADE OF ALUMINUM 6005A-T61, 6005-T5 AND 6061-T6.
3.3 ALL FASTENERS ARE MADE OF STAINLESS STEEL 304 AND 316 EXCEPT WHERE INDICATED.
3.4 LOCK NUTS (LN1) AND FIT NUTS (FN1) ARE MADE OF ALUMINUM 6061-T6.
4.0 DESIGN/CODES COMPLIANCE AND REFERENCES
4.1 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES [ASCE 7-10]
4.2 ESTES PARK BUILDING CODE
4.2 IBC 2015
4.3 ALUMINUM ASSOCIATION - ALUMINUM DESIGN MANUAL, 2015
4.4 AISC DESIGN GUIDE 27 - STRUCTURAL STAINLESS STEEL
4.5 WIND LOAD ON OPSUN PV MOUNTING SYSTEMS, BLWT-SS36-2010, ALAN DAVENPORT WIND ENGINEERING GROUP, S. FARQUHAR,
G.A. KOPP WIND LOAD ZONING FOR OPSUN ROOF MOUNTED SOLAR ARRAYS, OPSUN ROOF ZONING-MARCH 25, 2014 LETTER
REPORT
4.6 THE BOUNDARY LAYER WIND TUNNEL LABORATORY, «ROOF MOUNTED PV ARRAY - EXPANSION OF WIND TUNNEL STUDY RESULTS»,
WESTERN UNIVERSITY, S. FARQUHAR, G.A. KOPP, FEBRUARY 22 2018 RWDI REPORT #1701352, PV PANEL SNOW ASSESSMENT, A.
BROOKS, E. CHRUSCINSKI, MAY 16 2018.
4.7 THE ADDITION OF THE SOLAR PANELS IS NOT EXPECTED TO RESULT IN SIGNIFICANT CHANGES TO OVERALL ROOF SNOW LOADS
AND PATTERNS. WITH SOLAR PANELS IN PLACE, SNOW LOADS TEND TO CONCENTRATE IN THE SPACES BETWEEN ROWS AND IN THE
GAPS BETWEEN MODULES.THE DESIGN SNOW LOADS FOR THE PV PANEL SURFACES THEMSELVES ARE USUALLY EQUIVALENT TO THE
WORSE SNOW FALL EVENT IN 50 YEARS.
5.0 SPECIFIED COMPONENT CERTIFICATION
5.1 FATH CLICLOC (SOLAR MODULE END AND MID CLAMPS) SHOULD BE IN ACCORDANCE WITH : CSA C22.2#41 GROUNDING AND BONDING EQUIPMENT;
AND ANSI-UL 467 ED.9 STANDARD FOR SAFETY FOR GROUNDING AND BONDING EQUIPMENT.
5.2 PV MODULES (BY OTHERS) SHOULD BE IN ACCORDANCE WITH UL-1703. GROUND LUGS (BY OTHERS) SHOULD BE IN ACCORDANCE WITH ANSI-UL 467 ED.9
STANDARD FOR SAFETY FOR GROUNDING AND BONDING EQUIPMENT.
REVIEWED
BY SAFEBUILT
11/17/2021
900 Moraine, Estes Park
SRU-HP
Updated structure
56
Review
Rev
IPA-21032402
ddandeneau@ipoweralliance.com
Colorado, US
ASTRO CHSM72M(DG)-F-GH
L.A.
ESTES PARK
F.P.
BILL OF MATERIALS
1:50
IPA-21032402-PV0.110
DC Size :
Panel Qty :
Tilt Angle :
Panel Model:
Type of Mounting:
2021-08-12
Rev.#
08-12-2021
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
document, the client understands, and is in full
PV0.
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
23.0 kW
E-mail : projects@opsun.com
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Aliiance (IPA)
Array Information
01
Revision
303-552-7468
with new dimensions
validity of any roof warranty, ballasting or anchoring of the
1
Date
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
11
ITEM NO. PART NUMBER DESCRIPTION
UNIT MASS
(kg)
MASS
(kg)
MASS
(lb)QTY. MATERIAL
6 AST02-Astro CHSM72M(DG)-F-BH AstroTWIN CHSM72M(DG)-F-BH 26.300 1472.8 3247.0 56 STD
7 SRL2-242IN SunRail Lite 2 Beam; Length 242 Inches 6.777 203.3 448.2 30 6005-T5
8 A-ZBC-30 Z Bonding Clamp 30mm 0.080 17.9 39.5 224 STD
9 SRL-RL2-2 SRL Rail Link; Type 2 0.436 13.1 28.9 30 6005A-T61
10 SDS-SS-14-1IN SS Self Drilling Screw; 14 x 1" 0.010 1.0 2.2 100 AISI 304
11 SRL2-81IN SunRail Lite 2 Beam; Length 81 Inches 2.249 22.5 49.6 10 6005-T5
12 PL1-SBJ Plate Type 1, 5/16 Hole 0.020 0.1 0.2 5 6061-T6 (SS)
13 FN3-AL FIT Nut Type 3, 5/16-18 Hole 0.009 1.8 4.0 197 6061-T6
14 SBJ-516-6 Surface Bonding Jumper 0.009 0.0 0.0 5 Material <not specified>
15 BL-SS-5/16-18-0.75IN SS Hex Bolt; 5/16-18 x 0.75" with Loctite 0.016 0.2 0.4 10 AISI 304
16 SR3-14in SunRail3 Beam; Length 14 Inches 0.521 33.3 73.4 64 6005A-T61
17 SR3-21IN SunRail3 Beam; Length 21 Inches 0.781 50.0 110.2 64 6005A-T61
18 SR3-SRU-10D SR3-SRU Clamp; 10 Degrees 0.190 24.4 53.8 128 6005A-T61
19 SR3-SC2 SR3 Side Clamp; Type 2 0.063 8.1 17.9 128 6005A-T61
20 SFB-SS-0.3125-18-0.875IN SS Flanged Hex Bolt; 5/16-18 x 0.875IN 0.017 2.2 4.9 128 AISI 304
21 LN1-AL Aluminum Lock Nut; 0.5" x 0.5" 0.015 4.7 10.4 322 6061-T6 (SS)
22 BL-SS-3/8-16-0.875IN SS Hex Bolt; 3/8-16 x 0.875" with Loctite 0.021 10.8 23.8 514 AISI 304
23 SR3-CC SR3 Corner Clamp 0.153 29.4 64.8 192 6005A-T61
24 SRS3-290IN SRS 2.5 x 3.5; Length 290 Inches 16.954 152.6 336.4 9 6005A-T61
25 SRL2-162IN SunRail Lite 2 Beam; Length 162 Inches 4.555 27.3 60.2 6 6005-T5
26 SRS3-113IN SRS 2.5 x 3.5; Length 113 Inches 6.606 13.2 29.1 2 6005A-T61
27 SRS-RL3 SR3 Rail Linker 0.409 2.0 4.4 5 6005A-T61
28 SDS-SS-12-1IN SS Self Drilling Screw; 12 x 1" 0.007 0.3 0.7 40 AISI 304
29 SRS3-170IN SRS 2.5 x 3.5; Length 170 Inches 9.810 19.6 43.2 2 6005A-T61
30 SRS3-174IN SRS 2.5 x 3.5; Length 174 Inches 10.172 30.5 67.2 3 6005A-T61
31 AA-TA-12IN Anchor Adaptor Top Plate; 12 inches 0.491 1.0 2.2 2 6061-T6 (SS)
32 HBC1-1 Opsun H Beam Clamp type 1 0.062 0.2 0.4 4 6063-T6
33 BL-SS-3/8-16-2IN SS Hex Bolt; 3/8-16 x 2'' with Loctite 0.035 0.1 0.2 4 AISI 304
34 HBC-RW Opsun Round Washer 0.024 0.1 0.2 4 6063-T6
35 FW-SS-3/8 SS Flat Washer; 3/8" 0.004 0.0 0.0 4 AISI 304
36 LW-SS-3/8 SS Lock Washer; 3/8" 0.003 0.0 0.0 2 AISI 304
37 N-SS-3/8-16 SS Nut; 3/8-16 0.007 0.0 0.0 4 AISI 304
38 LW-SS-3/8 SS Lock Washer; 3/8" 0.003 0.0 0.0 2 AISI 304
REVIEWED
BY SAFEBUILT
11/17/2021
N
01
Rev
SRU-HP
ASTRO CHSM72M(DG)-F-GH
Updated structure 12-08-2021
Review
303-552-7468
ddandeneau@ipoweralliance.com
Colorado, US
900 Moraine, Estes Park
IPA-21032402
ESTES PARK
PV PANELS LAYOUT
L.A.F.P.
2021-08-12
PV0.1:40
Revision
IPA-21032402-PV0.200
1
56
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
23.0 kW
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# Date
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
E-mail : projects@opsun.com
with new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
20
337mm
1'-1 1
4 ""2
14'-
1231mm
1135mm
3'-8 5
8 "
"8
767'-2
20495mm
"8
337'-3
11363mm
765mm
30 1
8 "
REVIEWED
BY SAFEBUILT
11/17/2021
PATHWAYS DO NOT MEET CODE REQUIREMENTS. THE
PATHWAYS HAVE BEEN REVIEWED BY THE FIRE DEPARTMENT
AND APPROVED SEE LETTER DATED 10.14.2021
N
ASTRO CHSM72M(DG)-F-GH
Updated structure
SRU-HP
56
with new dimensions
12-08-2021
Review
IPA-21032402-PV0.210
ESTES PARK
ddandeneau@ipoweralliance.com
Colorado, US
IPA-2103402
F.P.
PV0.
Revision
2021-08-13
Rev
303-552-7468
1:40
900 Moraine, Estes Park
1
01
L.A.
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
23.0 kW
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# Date
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
ROOF OBSTACLES
E-mail : projects@opsun.com
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
21
8"
203mm
7264mm
23'-10"
2803mm
110 3
8 "
"4
"1697
2472mm
2457mm
396
5
"4
9144mm
30'-0"
2407mm
394
7417mm
24'-4"
136"
3454mm
"85'-11
1807mm
1
6'-0"
1829mm
6'-0"
1829mm
4020mm
13'-2 1
4 "
REVIEWED
BY SAFEBUILT
11/17/2021
20°SHADING LIMIT
PV PANEL SPECIFICATIONS
MANUFACTURER : ASTROENERGY
MODEL: CHSM72M(DG)/F-BH 410 W
MASS: 26.3 KG ( 58 lb)
MAXIMUM MECHANICAL LOAD PRESSURE: 5.4 kPa /-2.4 kPa
DIMENSION (LxWxH) : 2038x1010x30mm (80.25x39.76x1.18in)
1
SYSTEM DETAILS
ASTRO CHSM72M(DG)-F-GH
SRU-HP
IPA-21032402-PV0.300
08-12-2021
Review
Updated stucture
E-mail : projects@opsun.com
ddandeneau@ipoweralliance.com
Colorado, US
IPA-21032402
2021-08-13
PV0.
56
F.P.
900 Moraine, Estes Park
ESTES PARK
Revision
1:10
Rev
agreement with, the above statement.
23.0 kW
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
document, the client understands, and is in full
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# Date
with new dimensions
validity of any roof warranty, ballasting or anchoring of the
L.A.
01
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
303-552-7468
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
30
DETAIL A
SCALE 1 : 4
533mm
21"
DETAIL D
SCALE 1 : 2
10mm
3
8 "
RECOMMENDED SPACING
BETWEEN PV PANELS
D
"
458mm
16181
1829mm
72"
DETAIL B
SCALE 1 : 4
356mm
14"
1010mm
339 "4
2038mm
180 "4 460mm
18 1
8 "
A
B
725mm
28
8
422mm
2
"
1
1473mm
58"
"
16 5
544mm
21 3
8 "
10°
20°SHADING LIMIT
REVIEWED
BY SAFEBUILT
11/17/2021
SRS3-RL3 INSTALLATION
THERMAL JOINT (JT)
ONCE EVERY 40FT (ONCE EVERY TWO RAIL).
LEAVE A 12mm GAP BETWEEN RAILS AND
SCREW THE SRS-RL3 ON EACH SIDE ONLY TO
ONE OF THE SRS3 RAIL.
[1 2 .7 m m ]
0 .5 i n
SRS3
SRS-RL3
SDS-SS-12-1IN
SRS-RL3 INSTALLATION
NORMAL JOINT (J)
PLACE ONE (1) SRS-RL3 AT EACH SRS3 RAIL JUNCTION.
SCREW ON THE SRS-RL3 ON EACH RAILS WITH THE SDS-SS
01
Rev
SRU-HP
ASTRO CHSM72M(DG)-F-GH
SRU ELECTRICAL
L.A.F.P.
303-552-7468
ddandeneau@ipoweralliance.com
Colorado, US
900 Moraine, Estes Park
IPA-21032402
ESTES PARK
COMPONENTS
Updated structure 08-12-2021
Review
2021-06-08
PV0.1:48
IPA-21032402-PV0.310
1
56
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
23.0 kW
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# Date
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
E-mail : projects@opsun.com
with new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
Revision
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
31
RAIL LINKER SRS3-RL3 INSTALLATION
SBJ ASSEMBLY DETAIL
CROSSRAIL ASSEMBY & ELECTRICAL DETAIL B.2
STRONGLY CLAMPED COMPONENTS.
•
WARNING
MAKE SURE TO HAVE A GAP
OVER A THERMAL JOIN
OVER THERMAL DITALATION JOINTS .
CROSS RAILS CARRY THE CURRENT TO THE GROUND RAILS THROUGH MILL FINISH •
BOUNDING PATH
GROUND RAILS CARRY CURRENT THROUGH STRONGLY CLAMPED MILL FINISH •
GROUNDING IS REQUIRED ONLY AT ONE END OF EACH GROUND RAILS, AND IS •
THERMAL JOINT PANELS INSTALLATION
INSTALLED IN SERIES.
REQUIRED AT EACH 150 FEET IN ALL DIRECTIONS. MAXIMUM 30A PER LUG WHEN
B.1
B.3 B.4
SRU ELECTRICAL DETAIL
ALUMINUM COMPONENTS.
MODULE CLAMPS CARRY CURRENT TO THE CROSS RAILS.•
BURNDY BONDING JUMPERS CARRY THE CURRENT FROM CROSS RAILS TO CROSS RAILS
GROUND LUG
PROVIDED BY OTHERS
ELECTRICAL BONDINGGROUND BEAMS
CROSS RAILS
OF THE SRL-RAILS.
EXPANSION MUST BE ALOWED. LEAVE A 0.5IN GAP
BETWEEN RAILS AND SCREW THE SRL-RL2 ONLY TO ONE
ONCE EVERY 40' (ONCE EVERY TWO RAILS SBJ), THERMAL
SBJ-14-6-CP2
SDS-SS-14-1IN
SRL2
THERMAL JOINT (HT)
SRL-RL2-2
B-SS-1/4-20-0.75IN
KN-SS-1/4-20
NORMAL JOINT (H)
PLACE ONE(1) SRL-RL2 AT EACH
SRL-RAIL INTERSECTION. SCREW
THE SRL-RL2 TO BOTH OF THE
SRL-RAILS.SRL2
SDS-SS-14-1IN
SRL2
SRL-RL2
SRL-RL2
13mm
.50in
SRL-RL2-2
THERMAL JOINT WITH SBJ THERMAL JOINT
REVIEWED
BY SAFEBUILT
11/17/2021
Rev
ASTRO CHSM72M(DG)-F-GH
Updated structure
E-mail : projects@opsun.com
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
ddandeneau@ipoweralliance.com
Colorado, US
900 Moraine, Estes Park
IPA-21032402
ESTES PARK
ANCHORS DETAILS
L.AF.P.
2021-08-13
PV0.1:8
Revision
DC Size :
Panel Qty :
01
IPA-21032402-PV0.320
303-552-7468
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
56
Date
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.#
with new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
1
SRU-HP
23.0 kW
08-12-2021
Review
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
32
2 ANCHORS PER CONNECTION
REVIEWED
BY SAFEBUILT
11/17/2021
PROJECT ITEM NO. PART NUMBER DESCRIPTION
UNIT MASS
(kg)
MASS
(kg)
MASS
(lb)QTY. MATERIAL
03-PV Panels 5 AST02 AstroTWIN CHSM72M(DG)-F-BH 26.300 1472.8 3247.0 56 STD
02-Opsun Rails 6 SRL2-242IN SunRail Lite 2 Beam; Length 242 Inches 6.777 203.3 448.2 30 6005-T5
02-Part
Assemblies 7 A-ZBC-30 Z Bonding Clamp 30mm 0.080 17.9 39.5 224 STD
01-Opsun Parts 8 SRL-RL2 SRL Rail Link; Type 2 0.436 13.1 28.9 30 6005A-T61
Fasteners 9 SDS-SS-14-1IN SS Self Drilling Screw; 14 x 1" 0.010 1.0 2.2 100 AISI 304
02-Opsun Rails 10 SRL2-81IN SunRail Lite 2 Beam; Length 81 Inches 2.249 22.5 49.6 10 6005-T5
Fasteners 11 BL-SS-5/16-18-0.75IN SS Hex Bolt; 5/16-18 x 0.75" with Loctite 0.016 0.2 0.4 10 AISI 304
01-Opsun Parts 12 PL1-SBJ Plate Type 1, 5/16 Hole 0.020 0.1 0.2 5 6061-T6 (SS)
02-Opsun Rails 13 SR3-14IN SunRail3 Beam; Length 14 Inches 0.521 33.3 73.4 64 6005A-T61
02-Opsun Rails 14 SR3-21IN SunRail3 Beam; Length 21 Inches 0.781 50.0 110.2 64 6005A-T61
01-Opsun Parts 15 SR3-SRU-10D SR3-SRU Clamp; 10 Degrees 0.190 24.4 53.8 128 6005A-T61
01-Opsun Parts 16 SR3-SC2 SR3 Side Clamp; Type 2 0.063 8.1 17.9 128 6005A-T61
Fasteners 17 SFB-SS-5/16-18-0.875IN SS Flanged Hex Bolt; 5/16-18 x 0.875IN 0.017 2.2 4.9 128 AISI 304
Fasteners 18 LN1-AL Aluminum Lock Nut; 0.5" x 0.5" 0.015 4.7 10.4 322 6061-T6 (SS)
Fasteners 19 BL-SS-3/8-16-0.875IN SS Hex Bolt; 3/8-16 x 0.875" with Loctite 0.021 10.8 23.8 514 AISI 304
01-Opsun Parts 20 SR3-CC SR3 Corner Clamp 0.153 29.4 64.8 192 6005A-T61
02-Opsun Rails 21 SRS3-283IN SRS 2.5 x 3.5; Length 283 Inches 16.330 98.0 216.1 6 6005A-T61
02-Opsun Rails 22 SRL2-162IN SunRail Lite 2 Beam; Length 162 Inches 4.555 27.3 60.2 6 6005-T5
01-Opsun Parts 23 SRS-RL3 SR3 Rail Linker 0.409 2.0 4.4 5 6005A-T61
Fasteners 24 SDS-SS-12-1IN SS Self Drilling Screw; 12 x 1" 0.007 0.3 0.7 40 AISI 304
02-Opsun Rails 25 SRS3-113IN SRS 2.5 x 3.5; Length 113 Inches 6.606 13.2 29.1 2 6005A-T61
02-Opsun Rails 26 SRS3-170IN SRS 2.5 x 3.5; Length 170 Inches 9.810 19.6 43.2 2 6005A-T61
01-Opsun Parts 27 AA-TA-12IN-M1 Anchor Adaptor Top Plate; 12 inches 0.491 1.0 2.2 2 6061-T6 (SS)
Fasteners 28 HBC1-1 Opsun H Beam Clamp type 1 0.062 0.2 0.4 4 6063-T6
Fasteners 29 BL-SS-3/8-16-2IN SS Hex Bolt; 3/8-16 x 2'' with Loctite 0.035 0.1 0.2 4 AISI 304
Fasteners 30 HBC1-1-RW Opsun Round Washer 0.024 0.1 0.2 4 6063-T6
Fasteners 31 FW-SS-3/8 SS Flat Washer; 3/8" 0.004 0.0 0.0 4 AISI 304
Fasteners 32 LW-SS-3/8 SS Lock Washer; 3/8" 0.003 0.0 0.0 4 AISI 304
Fasteners 33 N-SS-3/8-16 SS Nut; 3/8-16 0.007 0.0 0.0 4 AISI 304
Fasteners 35 FN3-AL FIT Nut Type 3, 5/16-18 Hole 0.009 1.8 4.0 197 6061-T6
ilsco 36 SBJ-516-6 Surface Bonding Jumper 0.009 0.0 0.0 5
Material <not
specified>
02-Opsun Rails 37 SRS3-250IN SRS 2.5 x 3.5; Length 250 Inches 14.426 43.3 95.5 3 6005A-T61
02-Opsun Rails 38 SRS3-228IN SRS 2.5 x 3.5; Length 228 Inches 13.041 39.1 86.2 3 6005A-T61
Review
08-12-2021
BOM PREASSEMBLY
Updated Structure
SRU-HP
1
56
Rev
900 Moraine, Estes Park
F.P.
ddandeneau@ipoweralliance.com
Colorado, US
01
ASTRO CHSM72M(DG)-F-GH
qith new dimensions
Email:
ESTES PARK
Revision
IPA-21032402
2021-08-13
agreement with, the above statement.
Notice
document, the client understands, and is in full
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
validity of any roof warranty, ballasting or anchoring of the
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.# Date
E-mail : projects@opsun.com
IPA-21032402-PV0.340
303-552-7468
23.0 kW
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
L.A
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
PV0.1:45
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
34
REVIEWED
BY SAFEBUILT
11/17/2021
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
responsible for, the longevity or leak-resistance of the roof,
validity of any roof warranty, ballasting or anchoring of the
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
document, the client understands, and is in full
agreement with, the above statement.
Notice
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
E-mail : projects@opsun.com
www.opsun.com
Note
Rev.# DateReview
08-12-2021Updated Structure
qith new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
Revision
1:10 PV0.
2021-08-13
F.P. L.A
SRU PARTS PREASSEMBLY
ESTES PARK
IPA-21032402
900 Moraine, Estes Park
Colorado, US
ddandeneau@ipoweralliance.com
303-552-7468
56
23.0 kW
10
ASTRO CHSM72M(DG)-F-GH
SRU-HP
Rev
01
IPA-21032402-PV0.340
234
SRU ASSEMBLY
SR-CC ASSEMBLY
SRU PREASSEMBLY
SRU PARTS PREASSEMBLY
ZBC PREASSEMBLY
NOTES : FOR EACH LOCK NUTS (LN1-AL),
ONLY BOLT IN 2-3 THREADS .
BL-SS-3/8-16-0.875IN
LN1-AL
SR-CC
SR-CC PREASSEMBLY
FN2-AL
LW-SH-SS-5/16
ZBC 30mm
LW-SS-0.375
ROUND WASHER
N-SS-0.375-16
BL-SS-0.375-16-0.875IN
SRL-AC8-7.5in
H BEAM CLAMP-02
FW-SS-0.375LN1-AL
BL-SS-0.375-16-2IN
SRL-AC8-HBC PREASSEMBLY
SRU-10D
BL-SS-3/8-16-0.875IN
LN1-AL
REVIEWED
BY SAFEBUILT
11/15/2021
0m
m
0"
10
2
m
m
4"
11
0
7
m
m
43
5 8
"
15
7
5
m
m
62
"
25
8
0
m
m
10
1
5 8
"
30
4
8
m
m
12
0
"
40
5
3
m
m
15
9
5 8
"
45
2
1
m
m
17
8
"
55
2
7
m
m
21
7
5 8
"
59
9
4
m
m
23
6
"
70
0
0
m
m
27
5
5 8
"
71
8
8
m
m
28
3
"
0m
m
0"
20
3
m
m
8"
12
0
9
m
m
47
5 8
"
16
7
6
m
m
66
"
26
8
2
m
m
10
5
5 8
"
31
5
0
m
m
12
4
"
41
5
5
m
m
16
3
5 8
"
46
2
3
m
m
18
2
"
56
2
8
m
m
22
1
5 8
"
63
5
0
m
m
25
0
"
0m
m
0"
14
5
m
m
5
3 4
"
11
5
0
m
m
45
1 4
"
16
1
8
m
m
63
3 4
"
26
2
3
m
m
10
3
1 4
"
30
9
1
m
m
12
1
3 4
"
40
9
6
m
m
16
1
1 4
"
45
6
4
m
m
17
9
3 4
"
55
7
0
m
m
21
9
1 4
"
57
9
1
m
m
22
8
"
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
responsible for, the longevity or leak-resistance of the roof,
validity of any roof warranty, ballasting or anchoring of the
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
document, the client understands, and is in full
agreement with, the above statement.
Notice
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
E-mail : projects@opsun.com
www.opsun.com
Note
Rev.# DateReview
08-12-2021Updated Structure
qith new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
Revision
1:15 PV0.
2021-08-13
F.P. L.A
GROUND BEAM ASSEMBLY
ESTES PARK
IPA-21032402
900 Moraine, Estes Park
Colorado, US
ddandeneau@ipoweralliance.com
303-552-7468
56
23.0 kW
10
ASTRO CHSM72M(DG)-F-GH
SRU-HP
Rev
01
IPA-21032402-PV0.340
334
B
C
A GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-5 ROW
QTY: 6
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW
QTY: 3
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW-EXTENDED
QTY: 3
FOR THIS GB
PRE-ASSEMBLY OF CC CLAMPS ONLY
REVIEWED
BY SAFEBUILT
11/17/2021
0m
m
0"
24
6
m
m
9
3 4
"
12
5
2
m
m
49
1 4
"
17
1
9
m
m
67
3 4
"
27
2
5
m
m
10
7
1 4
"
28
7
0
m
m
11
3
"
0m
m
0"
24
6
m
m
9
3 4
"
12
5
2
m
m
49
1 4
"
17
1
9
m
m
67
3 4
"
27
2
5
m
m
10
7
1 4
"
31
9
3
m
m
12
5
3 4
"
41
9
8
m
m
16
5
1 4
"
44
2
0
m
m
17
4
"
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
responsible for, the longevity or leak-resistance of the roof,
validity of any roof warranty, ballasting or anchoring of the
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
document, the client understands, and is in full
agreement with, the above statement.
Notice
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
E-mail : projects@opsun.com
www.opsun.com
Note
Rev.# DateReview
08-12-2021Updated Structure
qith new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
Revision
1:15 PV0.
2021-08-13
F.P. L.A
GROUND BEAM ASSEMBLY
2
ESTES PARK
IPA-21032402
900 Moraine, Estes Park
Colorado, US
ddandeneau@ipoweralliance.com
303-552-7468
56
23.0 kW
10
ASTRO CHSM72M(DG)-F-GH
SRU-HP
Rev
01
IPA-21032402-PV0.340
434
E
D GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-3 ROW
QTY: 2
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-2-BR
QTY: 3
FOR THIS GB
PRE-ASSEMBLY OF CC CLAMPS ONLY
FOR THIS GB
PRE-ASSEMBLY OF CC CLAMPS ONLY
SR3-SRU-
SR3
SRS3
SR3-CC
203mm
8"
380mm
15"
356mm
14"
533mm
21"
REVIEWED
BY SAFEBUILT
11/17/2021
N
1:40 PV0.
IPA-21032402-PV0.500
ESTES PARK
F.P.
Revision
E-mail : projects@opsun.com
DC Size :
303-552-7468
ddandeneau@ipoweralliance.com
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
56
INSTALLATION
2021-08-13
Updated structure
Panel Qty :
Tilt Angle :
Panel Model:
Type of Mounting:
GROUND BEAM
ASTRO CHSM72M(DG)-F-GH
900 Moraine, Estes Park
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
Colorado, US
01
Rev
Phone:
Date
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.#
with new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
IPA-21032402
Email:
IPOWER Alliance (IPA)
Array Information
1
SRU-HP
23.0 kW
L.A
08-12-2021
Review
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
50
F
C
B
B
E
D
A A A A A A
A GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-5 ROW
QTY: 6
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW
QTY: 2
QTY: 3
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW-EXTENDED
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-3 ROW
QTY: 2
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW (CC CLAMPS ONLY)
QTY: 1
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-2 ROW
QTY: 2
F F
C C
E E
DD D
8
2134mm
6'-0"
1829mm
7'-0"
"
6'-6"
1981mm
6'-6"
1981mm
"4
1924mm
36'-3
6'-6"
1981mm
238mm
39
1372mm
4'-6"6'-6"
1981mm
6'-6"
1981mm1676mm
5'-6"
1981mm
6'-6"
BEAMS ARE INSERTED UNDER THE BRACING
(3x)
REVIEWED
BY SAFEBUILT
11/17/2021
N
0m
m
0"
18
2
9
m
m
6'
-
0
"
39
6
2
m
m
13
'
-
0
"
59
4
4
m
m
19
'
-
6
"
79
2
5
m
m
26
'
-
0
"
92
9
6
m
m
30
'
-
6
"
10
9
7
3
m
m
36
'
-
0
"
12
9
5
4
m
m
42
'
-
6
"
14
9
3
5
m
m
49
'
-
0
"
16
9
1
6
m
m
55
'
-
6
"
18
8
9
8
m
m
62
'
-
0
"
F F
CBC
E E
DD D
AA AAA
7188mm
283"
4318mm
170"
2870mm
113"
F
B
C
E
D
A
A
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW
QTY: 2
QTY: 2
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-2 ROW
QTY: 2
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-3 ROW
QTY: 6
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-5 ROW
QTY: 1
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW (CC CLAMPS ONLY)
GB-HP-10D-L-SRL2-SR3-SRS3-58IN-1010-4 ROW-EXTENDED
QTY: 3
Updated structure
L.A
1:40
Panel Qty :
IPA-21032402
08-12-2021
Project Number:
Review
ESTES PARK
INSTALLATION(2)
Date
2021-08-13
Revision
23.0 kW
303-552-7468
56
ASTRO CHSM72M(DG)-F-GH
DC Size :
Tilt Angle :
Type of Mounting:
F.P.
SRU-HP
900 Moraine, Estes Park
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
Colorado, US
www.opsun.com
01
IPA-21032402-PV0.500
2
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
document, the client understands, and is in full
validity of any roof warranty, ballasting or anchoring of the
E-mail : projects@opsun.com
with new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Panel Model:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Rev
GROUND BEAM
ddandeneau@ipoweralliance.com
PV0.
Rev.#
Note
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
50
REVIEWED
BY SAFEBUILT
11/17/2021
N
IPA-21032402-PV0.700
01
Rev
ASTRO CHSM72M(DG)-F-GH
Updated structure
E-mail : projects@opsun.com
56
303-552-7468
ddandeneau@ipoweralliance.com
Colorado, US
900 Moraine, Estes Park
IPA-21032402
ESTES PARK
CROSSRAIL INSTALLATION
L.AF.P.
2021-08-13
PV0.1:40
Revision
Date
agreement with, the above statement.
validity of any roof warranty, ballasting or anchoring of the
racking, and suitability of the roof to support the installation of
such racking. Do not scale this drawing. By accepting this
document, the client understands, and is in full
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
Rev.#
with new dimensions
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Email:
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
DC Size :
1
SRU-HP
23.0 kW
08-12-2021
Review
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
70
H : NORMAL JOINT
HT : THERMAL JOINT
CROSS RAIL LENGTH (IN) QTY.
SRL2-1 242'' 30
SRL2-2 162'' 6
SRL2-3 81'' 10
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-1
SRL2-2
CROSS RAIL LENGTH (IN) QTY.
SRL2-1 242'' 30
SRL2-2 162'' 6
SRL2-3 81'' 10
H
SRL2-3
H
H
HT
H
H
H
H
SRL2-1
H
H
SRL2-3
HT
SRL2-2
H
HT
HT
HT
HT
SRL2-1
SRL2-1
SRL2-1
H
SRL2-1
SRL2-3
H
SRL2-3
SRL2-3
SRL2-2
REVIEWED
BY SAFEBUILT
11/17/2021
Rev
SRU-HP
L.A
08-12-2021
with new dimensions
validity of any roof warranty, ballasting or anchoring of the
900 Moraine, Estes Park
ddandeneau@ipoweralliance.com
Colorado, US
F.P.
Revision
PV PANELS INSTALLATION
303-552-7468
IPA-21032402
PV0.
Email:
ASTRO CHSM72M(DG)-F-GH
1:48
Updated structure
DC Size :
Rev.#
1
document, the client understands, and is in full
such racking. Do not scale this drawing. By accepting this
racking, and suitability of the roof to support the installation of
23.0 kW
agreement with, the above statement.
Notice
responsible for, the longevity or leak-resistance of the roof,
www.opsun.com
Note
56
IPA-21032402-PV0.800
01
Scale: Page:
Check By:Drawn By:
Drawn Date:
Title
Project Info
Project Name:
Project Number:
Project Adress:
Customer Info
Phone:
Review
IPOWER Alliance (IPA)
Array Information
Type of Mounting:
Panel Model:
Tilt Angle :
Panel Qty :
012021-08-13
ESTES PARK
E-mail : projects@opsun.com
Date
All rights reserved. All information contained in this document
remains the sole property of Opsun. This document may not be
copied, photographed or in any way, including by any
electronic mean, reproduced, in whole or in part, without
express written permission from Opsun. Installer and/or
Contractor has to notify in writing Opsun if any changes is
made to the present information, or if any missing information is
detected. Opsun does not offer any warranty concerning the
structural integrity of the building, the integrity of which lies
solely on behalf of the Structural Engineer. Any modifications or
alterations made to the approved design layout and/or
specification herein will nullify any warranty offered by Opsun.
Any and all proposed changes must first be reviewed, and
approved in writing, by Opsun. No warranty is provided or
implied by Opsun with regards to, and Opsun shall not be held
OPSUN SYSTEMS INC.
979 Ave. De Bourgogne, Suite 260
Quebec, Quebec G1W 2L4 Canada
Phone : 1 (418)-651-4040
10
80
PV PANELS INSTALLATION
STEP 1
INSTALL THE PV END CLAMP ( ZBC) ON THE LOWER SRL2 RAIL •
STEP 3
INSTALL THE PANEL ON THE SRL2 RAIL. •
THEN, PLACE THE OTHER END CLAMP ( ZBC) ON THE HIGHER SRL2 RAIL AT THEIR APPROPRIATE PLACES •
TIGHTEN BOLTS TO FIX THE PANEL. (14NM)•
STEP 2
RUN THE WIRE ON THE FRAME OF THE PANLE AND FIX IT WITH THE WILLEY•
MC4-CONNECTOR
E
DETAIL E
SCALE 1 : 2
MAKE SURE THAT THE ZBC TEETH ARE FULLY SEATED
WILEY-ACC-PV
10mm
3
8 "
DETAIL B
SCALE 1.5 : 2
LEAVE A GAP OF 3/8IN (10mm) BETWEEN EACH PANELS •
REPEAT STEP 1 & 2 FOR THE NEXT PANELS AND FOR EACH ROWS •
STEP 4
B
REVIEWED
BY SAFEBUILT
11/15/2021
REV 1 -
STRUCTURAL
UPDATE SHOWING
RAFTERS PER
PLAN CHECK
COMMENTS -
UPDATE BY
SOLMOTIV DESIGN
STRUCTURAL EOR
STRUCTURAL ENGINEER
CHRISTOPHER KLINGA, PE
SOLMOTIV DESIGN
1035 PEARL ST. SUITE 325
BOULDER, CO 80302
1
1
1
11
/
0
2
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
S1 ANCHOR/RAIL PLAN DELI
S2 ANCHOR/RAIL PLAN 201/202
S3 ANCHOR/RAIL PLAN RESTAURANT
S4 ANCHOR CONNECTION DETAILS
S5 DATASHEETS
REV 1, FOR PERMIT
REV 1, FOR PERMIT
REV 1, FOR PERMIT
REV 1, FOR PERMIT
REV 1, FOR PERMIT
1
SAFEbuilt
APPROVED
Subject to inspection and
compliance to all relevant
Adopted Building and Municipal
codes.
Changes in Plans MUST be
approved.
D.GRAHAM
11/17/2021
21-ep-00471
I-CODES 2015
PRINT PLANS IN COLOR AND HAVE FOR
INSPECTOR AT TIME OF INSPECTION
PLAN REVIEWED FOR STRUCTURAL PAGES
ONLY S1-S5
DETAIL CALLOUTS
ADDED
1
1
11
/
0
1
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
DELI - REF. E7 AND S1
201/202 - REF. E8 AND S2
RESTAURANT - REF. E9 AND S3
·
·
·
·
25'0'5'10'
ZONE 3 SHOWN IN RED TYP
1
11
/
0
1
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
·
·
·
·
25'0'5'10'
·
·
·
·
25'0'5'10'
ZONE 3 SHOWN IN RED TYP
1
11
/
0
1
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
25'0'5'10'
INV-01
! WARNING
ELECTRIC SHOCK HAZARD. DO NOT TOUCH
TERMINALS. TERMINALS ON BOTH THE LINE
AND LOAD SIDES MAY BE ENERGIZED IN THE
OPEN POSITION.
! WARNING
PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT: 48.25A
NOMINAL OPERATING AC VOLTAGE: 208V
! WARNING
THIS EQUIPMENT IS FED BY TWO POWER
SOURCES FROM UTILITY AND SOLAR
PHOTOVOLTAIC SYSTEM.
PHOTOVOLTAIC
SYSTEM
DISCONNECT
INV-02
INV-03
INV-04
17.3kW INVERTER DC DISCONNECT-03
DC MAX VOLTAGE/AMPERAGE: 600VDC / 54A
DC WIRE: RED(+) / BLACK(-)
RATED MAX. POWER POINT VOLTAGE/AMPERAGE: 400VDC / 47.2A
AC MAX VOLTAGE/AMPERAGE: 208VAC, 3ɸ / 48.25A
AC WIRE: BLACK (Aɸ), RED (Bɸ),
BLUE (Cɸ), WHITE (N)
17.3kW INVERTER DC DISCONNECT-01
DC MAX VOLTAGE/AMPERAGE: 600VDC / 72A
DC WIRE: RED(+) / BLACK(-)
RATED MAX. POWER POINT VOLTAGE/AMPERAGE: 400VDC /64.8A
AC MAX VOLTAGE/AMPERAGE: 208VAC, 3ɸ / 48.25A
AC WIRE: BLACK (Aɸ), RED (Bɸ),
BLUE (Cɸ), WHITE (N)
17.3kW INVERTER DC DISCONNECT-02
DC MAX VOLTAGE/AMPERAGE: 600VDC / 72A
DC WIRE: RED(+) / BLACK(-)
RATED MAX. POWER POINT VOLTAGE/AMPERAGE: 400VDC / 62.4A
AC MAX VOLTAGE/AMPERAGE: 208VAC, 3ɸ / 48.25A
AC WIRE: BLACK (Aɸ), RED (Bɸ),
BLUE (Cɸ), WHITE (N)
10kW INVERTER DC DISCONNECT-04
DC MAX VOLTAGE/AMPERAGE: 480VDC / 45A
DC WIRE: RED(+) / BLACK(-)
RATED MAX. POWER POINT VOLTAGE/AMPERAGE: 400VDC / 28.7A
AC MAX VOLTAGE/AMPERAGE: 240VAC, 1ɸ /42 A
AC WIRE:BLACK (Aɸ), RED (Bɸ),
WHITE (N)
! WARNING
POWER SOURCE OUTPUT CONNECTION:
DO NOT RELOCATE THIS OVERCURRENT
DEVICE.
10kW INVERTER DC DISCONNECT-05
DC MAX VOLTAGE/AMPERAGE: 480VDC / 45A
DC WIRE:RED(+) / BLACK(-)
RATED MAX. POWER POINT VOLTAGE/AMPERAGE: 400VDC / 28.7A
AC MAX VOLTAGE/AMPERAGE:240VAC, 1ɸ /42 A
AC WIRE:BLACK (Aɸ), RED (Bɸ),
WHITE (N)
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION
TO SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY.
SOLAR ELECTRIC
PV PANELS
PHOTOVOLTAIC POWER
SOURCE
RAPID SHUTDOWN SWITCH
FOR SOLAR PV
SYSTEM
! WARNING
PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT: 84A
NOMINAL OPERATING AC VOLTAGE: 240V
PV
DISCONNECT
PV
DISCONNECT
METER
BANK
TRANSFORMER
PV
DISCONNECT
EXISTING
CT CABINET
PV
DISCONNECT
INV-05
·
·
·
·
25'0'5'10'
A
B
C
D
E
F
A
A
A
A
A
C
C
C
C
ROOF STRUCTURE: T&G PLYWOOD SHEATHING
ON 2x12 WOOD JOISTS @ 24” OC WITH 10” BATT
INSULATION TYP ALL ROOFTOPS ON THIS
BUILDING.
ANCHORS AND K2 CR80 RAIL SHOWN
ALL ANCHORS SHOWN ARE IN LINE WITH ROOF
RAFTERS, ROOF RAFTERS NOT SHOWN
ZONE 3 SHOWN IN RED TYP
1
11
/
0
2
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
S1
AN
C
H
O
R
/
R
A
I
L
P
L
A
N
D
E
L
I
DELI
1B
1B
1B
10
3
5
P
e
a
r
l
S
t
S
t
e
.
3
2
5
Bo
u
l
d
e
r
,
C
O
(3
0
3
)
8
5
9
-
5
5
7
0
ww
w
.
s
o
l
m
o
t
i
v
.
c
o
m
PATHWAYS DO NOT MEET CODE REQUIREMENTS. THE
PATHWAYS HAVE BEEN REVIEWED BY THE FIRE DEPARTMENT
AND APPROVED SEE LETTER DATED 10.14.2021
REVIEWED
BY SAFEBUILT
11/15/2021
·
·
·
·
25'0'5'10'
AAABC
A
A
A
AA
BBBBB
CCC
DE
ZONE 3 SHOWN IN RED TYP
ROOF STRUCTURE: T&G PLYWOOD SHEATHING
ON 2x12 WOOD JOISTS @ 24” OC WITH 10” BATT
INSULATION TYP ALL ROOFTOPS ON THIS
BUILDING.
ANCHORS AND K2 CR80 RAIL SHOWN
ALL ANCHORS SHOWN ARE IN LINE WITH ROOF
RAFTERS, ROOF RAFTERS NOT SHOWN
1
11
/
0
2
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
S2
AN
C
H
O
R
/
R
A
I
L
P
L
A
N
2
0
1
/
2
0
2
201/202
1B
1B
1B
10
3
5
P
e
a
r
l
S
t
S
t
e
.
3
2
5
Bo
u
l
d
e
r
,
C
O
(3
0
3
)
8
5
9
-
5
5
7
0
ww
w
.
s
o
l
m
o
t
i
v
.
c
o
m
REVIEWED
BY SAFEBUILT
11/15/2021
PATHWAYS DO NOT MEET CODE REQUIREMENTS. THE
PATHWAYS HAVE BEEN REVIEWED BY THE FIRE DEPARTMENT
AND APPROVED SEE LETTER DATED 10.14.2021
·
·
·
·
25'0'5'10'
AAAAAAAA
B
ZONE 3 SHOWN IN RED TYP
ROOF STRUCTURE: 2" RIGID INSULATION ON
NOMINAL 3"X6" WESTERN RED CEDAT T&G
DECKING ON 5-1/8" x 16-1/2" GLULAM @ 10FT OC.
TYP ALL ROOFTOPS ON THIS BUILDING.
ANCHORS AND K2 CR80 RAIL SHOWN
ANCHORS MOUNT DIRECT TO DECK, ROOF
GLULAMS NOT SHOWN
1
11
/
0
2
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
S3
AN
C
H
O
R
/
R
A
I
L
P
L
A
N
R
E
S
T
A
U
R
A
N
T
RESTAURANT
1A
1A
10
3
5
P
e
a
r
l
S
t
S
t
e
.
3
2
5
Bo
u
l
d
e
r
,
C
O
(3
0
3
)
8
5
9
-
5
5
7
0
ww
w
.
s
o
l
m
o
t
i
v
.
c
o
m
REVIEWED
BY SAFEBUILT
11/15/2021
PATHWAYS DO NOT MEET CODE REQUIREMENTS. THE
PATHWAYS HAVE BEEN REVIEWED BY THE FIRE DEPARTMENT
AND APPROVED SEE LETTER DATED 10.14.2021
·
·
·
·
25'0'5'10'
AAAAAAAA
B
ZONE 3 SHOWN IN RED TYP
ROOF STRUCTURE: 2" RIGID INSULATION ON
NOMINAL 3"X6" WESTERN RED CEDAT T&G
DECKING ON 5-1/8" x 16-1/2" GLULAM @ 10FT OC.
TYP ALL ROOFTOPS ON THIS BUILDING.
ANCHORS AND K2 CR80 RAIL SHOWN
ANCHORS MOUNT DIRECT TO DECK, ROOF
GLULAMS NOT SHOWN
1
11
/
0
2
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
S4
AN
C
H
O
R
C
O
N
N
E
C
T
I
O
N
D
E
T
A
I
L
S
ROOF STRUCTURE 2: 2" RIGID INSULATION ON
NOMINAL 3"X6" WESTERN RED CEDAT T&G
DECKING ON 5-1/8" x 16-1/2" GLULAM @ 10FT OC.
TYP ALL ROOFTOPS ON THIS BUILDING.
LOCATED ON RESTAURANT
CONNECTION FOR ROOF STRUCTURE 1: T&G
PLYWOOD SHEATHING ON 2x12 WOOD JOISTS @
24” OC WITH 10” BATT INSULATION
LOCATED ON DELI AND 201/202
K2 CR80
RAIL
K2 CR80
RAIL
K2 L-FOOT
ASSEMBLY
K2 L-FOOT
ASSEMBLY
2x12 WOOD
JOIST @ 24" OC
(2) 5/16" GRK SIZED PER
MINIMUM 2.5" EMBEDMENT
K2 L-FOOT ASSEMBLY
(6) #14 TRUFAST DECK SCREWS
SIZED PER MIN 2" T&G EMBEDMENT
3"X6" T&G
DECKING
2" RIGID
INSULATION
DETAIL 1A: T&G CONNECTION DETAIL 1B: RAFTER CONNECTION
2" MIN
EMBEDMENT
INTO T&G
DECKING
10
3
5
P
e
a
r
l
S
t
S
t
e
.
3
2
5
Bo
u
l
d
e
r
,
C
O
(3
0
3
)
8
5
9
-
5
5
7
0
ww
w
.
s
o
l
m
o
t
i
v
.
c
o
m
REVIEWED
BY SAFEBUILT
11/15/2021
·
·
·
·
25'0'5'10'
AAAAAAAA
B
ZONE 3 SHOWN IN RED TYP
ROOF STRUCTURE: 2" RIGID INSULATION ON
NOMINAL 3"X6" WESTERN RED CEDAT T&G
DECKING ON 5-1/8" x 16-1/2" GLULAM @ 10FT OC.
TYP ALL ROOFTOPS ON THIS BUILDING.
ANCHORS AND K2 CR80 RAIL SHOWN
ANCHORS MOUNT DIRECT TO DECK, ROOF
GLULAMS NOT SHOWN
1
11
/
0
2
/
2
1
RC
RC
&
C
K
CS
K
ST
R
U
C
T
U
R
A
L
P
E
R
M
I
T
U
P
D
A
T
E
S5
DA
T
A
S
H
E
E
T
S
CONNECTION FOR ROOF STRUCTURE 1: T&G
PLYWOOD SHEATHING ON 2x12 WOOD JOISTS @
24” OC WITH 10” BATT INSULATION
LOCATED ON DELI AND 201/202
K2 CR80
RAIL
K2 CR80
RAIL
K2 L-FOOT
ASSEMBLY
2x12 WOOD
JOIST @ 24" OC
(2) 5/16" GRK SIZED PER
MINIMUM 2.5" EMBEDMENT
(6) #14 TRUFAST DECK SCREWS
SIZED PER MIN 2" T&G EMBEDMENT
2" RIGID
INSULATION
2" MIN
EMBEDMENT
INTO T&G
DECKING
10
3
5
P
e
a
r
l
S
t
S
t
e
.
3
2
5
Bo
u
l
d
e
r
,
C
O
(3
0
3
)
8
5
9
-
5
5
7
0
ww
w
.
s
o
l
m
o
t
i
v
.
c
o
m
www.roof-tech.us info@roof-tech.us
RT-MINI II
RT-MINI II is suitable for all systems with a conventional L-Foot.
ICC ESR 3575Installation Manual
RT Serrated Hex Flange Bolt/Nut:5/16-18 x 1”
1/4” x 1” Carriage Bolt EMT Accessory
A Self-flashing PV Mount Featuring Roof Tech s AlphaSeal™ Technology
Less Aluminum
Additional Mounting Options
More Efficient Design
Metal, EPDM, TPO, & Asphalt Roofs
b
N
orth Amer i c a ’ M o st Trusted
Se
a
l
a
n
t
100% Ca u l k -F r e e
AlphaSeal ™
PV Mounting
T
e
c
h
n
o
l
o
g
y
s
RT-MINI II
Flexible Flashing Certified by the International Code Council (ICC)
Components
MINI II base : 20 ea.
Screw : 40 ea.
Extra RT-Butyl : 5 ea.
RT-Butyl is Roof Tech s flexible flashing used in one million
residential PV systems for the last 27 years. It is the first PV mounting
system with Flexible Flashing certified by the ICC. Engineered to
withstand wind speeds up to 180 mph and ground snow up to 90 psf.
ICC ESR-3575 ASTM2140 Testing
www.roof-tech.us info@roof-tech.us 10620 Treena Street, Suite 230, San Diego, CA 92131858.935.6064
Roof Tech Inc.
Flexible Flashing
100% Waterproof
Metal Flashing Retrofit
Shedding Water?
Rafter InstallationDeck Installation
’
P.E. Stamped Letters available at www.roof-tech.us/support
Dimensions in (mm)
Optional Items:
5 x 60mm Mounting Screw (RT2-04-SD5-60) : 100 ea./Bag
5/16 X 25MM Flange Bolt & Nut (RT2-04-FBN25) : 100 ea./Bag
RT-Butyl (RT2-04-MNBUTYL) : 10 ea./Box
Paten
t
#
D
8
2
2
4
5
9
S
3.54 inch (90mm).60 inch (15.4mm)
RT2-00-MINIBK2
Offset Rafter Installation
Offset Rafter Attachment Options‘
June 2021
Engineered to ASTM D 1761
(Standard Test Methods for Mechanical Fasteners in Wood)
TAS 100 A on metal and asphalt roof.
We support PV systems
Formerly Everest Solar Systems
We support PV systems
Formerly Everest Solar Systems
k2-systems.com
CrossRail Shared Rail System
PRODUCT SHEET
T High quality, German-engineered system for residential installations
T Beneficial for small 2 row arrays
T 4 rail sizes available to suit all structural conditions
T Universal components for all rail types
T MK3 technology provides highest rail engagement
T 100% code compliant, structural validation for all solar states
T Fast installation with minimal component count result in low total installed cost
T L-Foot provides adjustability and compatibility with common roof types
Part Number Description
4000019 CrossRail 44-X, 166", Mill
4000020 CrossRail 44-X, 166", Dark
4000021 CrossRail 44-X, 180", Mill
4000022 CrossRail 44-X, 180", Dark
CrossRail 44-X
Part Number Description
4000662 CrossRail 48-X, 166", Mill
4000663 CrossRail 48-X, 166", Dark
4000675 CrossRail 48-X, 180", Mill
4000665 CrossRail 48-X, 180", Dark
CrossRail 48-X
Part Number Description
4000695 CrossRail 48-XL, 166", Mill
4000705 CrossRail 48-XL, 166", Dark
CrossRail 48-XL
Part Number Description
4000508 CrossRail 80, 168", Mill
CrossRail 80 CrossRail Mid Clamp
Part Number Description
4000429 CR EC Silver 30-50mm, SR 30-45mm
4000430 CR EC Dark 30-50mm, SR 30-45mm
4000003 SR EC Silver 46-50mm
4000004 SR EC Dark 46-50mm
CrossRail End Clamp
Part Number Description
4000050-H Yeti Hidden EC for CR, Mill, 13mm Hex
Yeti Clamp
Part Number Description
4005344 CrossRail EC Silver, AL 32-33mm
4005169 CrossRail EC Silver, AL 34-36mm
4005290 CrossRail EC Silver, AL 37-38mm
4005170 CrossRail EC Silver, AL 39-41mm
4005291 CrossRail EC Silver, AL 42-44mm
4005171 CrossRail EC Silver, AL 45-47mm
4005292 CrossRail EC Silver, AL 48mm
4005172 CrossRail EC Silver, AL 49-50mm
Aluminum End Clamp
Part Number Description
4000051 Rail Connector CR 44-X, Set, Mill
4000052 Rail Connector CR 44-X, Set, Dark
4000385 RailConn CR48-X,48-XL Struct Set, Mill
4000386 RailConn CR48-X,48-XL Struct Set, Dark
CrossRail Rail Connector
Part Number Description
4000630 L-Foot Slotted Set, Mill
4000631 L-Foot Slotted Set, Dark
4000080 T-Foot X, Set, Mill
L-Foot & T-Foot
Part Number Description
4000015 EverFlash eComp +SR Slide Kit, Mill
4000027 EverFlash eComp +SR Slide Kit, Dark
4000029 EverFlash eComp + SR Slide, LF Mill, Dark Flashing Kit
EverFlash Flashings
Part Number Description
4000016 Standing Seam PowerClamp, Mini
4000017 Standing Seam PowerClamp, Standard
Standing Seam PowerClamps
Part Number Description
4000688-H SR MC Silver, 30-50mm, 13mm Hex
4000689-H SR MC Silver, 30-50mm, 13mm Hex
2
Components
Part Number Description
4000006-H Everest Ground Lug Set, 13mm Hex
Everest Ground Lug
Part Number Description
4000069 TC Wire Management Clip
4000382 Sunrunner Cable Clip
4005394 Omega Wire Mangement Clip
Wire Management
Part Number Description
4000629-H CR Microinverter & Opt Mounting Kit, 13mm
CR Microinverter & Opt Mounting Kit
Part Number Description
4000067 CR 44-X End Cap
4000431 CR 48-X /48-XL Flat End Cap
4000433 CR 48-X/48-XL End Cap
4001221 CR 80 End Cap
End Caps
Part Number Description
4000583 CR 48-X/48-XL 3" Black Sleeve
CR 48-X/48-XL Sleeve
Part Number Description
4000609 Shared Rail Clamp, Add-On, Slide In, 10mm
4000632 Shared Rail Clamp, Add-On, Slide In, 5mm
Add-On
3
REVIEWED
BY SAFEBUILT
11/15/2021