HomeMy WebLinkAboutPLANS 23-362 461 Marcus Ln, PV System 2023-07-17GENERAL NOTES
1.1.1 PROJECT NOTES:
1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC
CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION
INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING
JURISDICTION’S (AHJ) APPLICABLE CODES.
1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM
INSPECTED PRIOR TO PARALLEL OPERATION
1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATED WITH
THE MICROINVERTER IN ACCORDANCE WITH NEC 690.41(B)
1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND
SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN
PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4:
PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE
INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519
COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY
1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT
FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO NEC 690.7.
1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE
CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE
IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLED
ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3].
1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF
EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL
BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.
1.2.1 SCOPE OF WORK:
1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THE
GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE
RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,
SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE
PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.
*NEC2020M
1.3.1 WORK INCLUDES:
1.3.2 PV ROOF ATTACHMENTS - IRONRIDGE FLASH VUE
1.3.3 PV RACKING SYSTEM INSTALLATION - IRONRIDGE XR-100
1.3.4 PV MODULE AND INVERTER INSTALLATION - HANWHA Q-CELLS Q.PEAK DUO G10+ 405W /
ENPHASE IQ8A-72-2-US
1.3.5 PV EQUIPMENT GROUNDING
1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX
1.3.7 PV INSTALLING SYSTEM MONITORING EQUIPMENT
1.3.8 PV LOAD CENTERS (IF INCLUDED)
1.3.9 PV METERING (IF INCLUDED)
1.3.10 PV DISCONNECTS
1.3.11 PV GROUNDING ELECTRODE & BONDING TO (E) GEC
1.3.12 PV FINAL COMMISSIONING
1.3.13 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV
OWNER
NAME:SCOTT MONTGOMERY
AUTHORITIES HAVING JURISDICTION
BUILDING:
ZONING:
UTILITY:
ESTES
ESTES
TOWN OF ESTES PARK UTILITIES
DESIGN SPECIFICATIONS
OCCUPANCY: ІІ
CONSTRUCTION: SINGLE-FAMILY
ZONING:RESIDENTIAL
GROUND SNOW LOAD: 70 PSF
WIND EXPOSURE: C
WIND SPEED: 175 MPH
APPLICABLE CODES & STANDARDS
BUILDING: IBC 2015
RESIDENTIAL:IRC 2015
ELECTRICAL: NEC 2020
FIRE:IFC 2018
PROJECT INFORMATION
PROJECT MANAGER
NAME:CLAY COLE
PHONE:970-401-0391
CONTRACTOR
NAME:AFFORDABLE ALTERNATIVE ENERGY DBA ARE SOLAR
PHONE:720-504-0005
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
T-001.00
COVER PAGE
(SHEET 1)
01 AERIAL PHOTO
NOT TO SCALE
N
EW
S
02 PLAT MAP
NOT TO SCALE
SHEET LIST TABLE
SHEET NUMBER SHEET TITLE
T-001 COVER PAGE
G-001 NOTES
A-101 SITE PLAN
A-102 ELECTRICAL PLAN
A-103 SOLAR ATTACHMENT PLAN
E-601 LINE DIAGRAM
E-602 DESIGN TABLES
E-603 PLACARDS
S-501 ASSEMBLY DETAILS
R-001 RESOURCE DOCUMENT
R-002 RESOURCE DOCUMENT
R-003 RESOURCE DOCUMENT
R-004 RESOURCE DOCUMENT
R-005 RESOURCE DOCUMENT
R-006 RESOURCE DOCUMENT
R-007 RESOURCE DOCUMENT
MA
R
C
U
S
L
N
NEW PV SYSTEM:
11.340 kWp DC /9.772 kWp AC
MONTGOMERY RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
ASSESSOR'S #: 3536421001
SCOPE OF WORK
SYSTEM SIZE:
ATTACHMENT TYPE:
MSP UPGRADE:
STC: 28 X 405W = 11.340KW
PTC: 28 X 383.13W = 10.728KW
(28) HANWHA Q-CELLS Q.PEAK DUO G10+ 405W
(28) ENPHASE IQ8A-72-2-US
IRONRIDGE FLASH VUE
NO
PEAK VIEW DR
PARK
PARK
2.1.1 SITE NOTES:
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY
INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING
ROOF VENTS.
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL
EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH
THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF
COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.
2.2.1 EQUIPMENT LOCATIONS:
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING
TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).
2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC
690.34.
2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN
SIGHT OF THE AC SERVICING DISCONNECT.
2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO
NEC APPLICABLE CODES.
2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN
APPROPRIATE.
2.3.1 STRUCTURAL NOTES:
2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT
INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,
AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE
ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED
CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE
SPECIFIED BY THE RACKING MANUFACTURER.
2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST
THE ROOF FRAMING MEMBERS.
2.4.1 WIRING & CONDUIT NOTES:
2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND
WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT
TO LIMIT UP-SIZING.
2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
2.4.4 VOLTAGE DROP LIMITED TO 1.5%.
2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING SYSTEMS SHALL BE
LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS.
2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION
NEUTRAL- WHITE OR GRAY
IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED
ORANGE [NEC 110.15].
2.5.1 GROUNDING NOTES:
2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING
DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.
2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE
250.122.
2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED
GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45 AND
MICROINVERTER MANUFACTURERS' INSTRUCTIONS.
2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED,
MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES
PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.
2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL
OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.
2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR
MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH
250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE
SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.
2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) THROUGH (3) TO REDUCE
FIRE HAZARDS
2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE
CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE
SIDE” (TYPICALLY THE UPPER TERMINALS).
2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE-BREAK SWITCH
2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN
FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH
690.12(A) THROUGH (D).
2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.
2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN
ACCORDANCE WITH NEC 110.3(B).
2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO
NEC 690.11 AND UL1699B.
2.7.1 INTERCONNECTION NOTES:
2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH NEC 705.12
2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE
RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120
PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE
LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].
2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL
OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE
COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).
2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)
2.7.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCE
CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM
ADDITIONAL FASTENING [NEC 705.12 (E)].
*NEC2020M
*NEC2020M
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
G-001.00
NOTES
(SHEET 2)
A-101.00
SITE PLAN
(SHEET 3)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
01/48" = 1'-0"
SITE PLAN01 24'48'
N
EW
S
N
EW
S
PROPERTY LINE
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
FUSED AC DISCONNECT
ENTRANCE
AREA OF WORK (28) ENPHASE IQ8A-72-2-US
2'-2"
32'-10"
279'-1"
MA
R
C
U
S
L
N
PEAK VIEW DR
01/16" = 1'-0"
SITE PLAN02 8'16'
N
EW
S
N
EW
S
47'-2"
PEDESTAL
UTILITY METER
PV METER
NON-FUSED AC DISCONNECT
08/22/2023
MODULE:
HANWHA Q-CELLS
Q.PEAK DUO G10+ 405W
405 WATTS
41.1"
74"
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
A-102.00
ELECTRICAL PLAN
(SHEET 4)
01/12" = 1'-0"
ELECTRICAL PLAN016'12'
N
EW
S
A MODULE STRINGING
B MODULE STRINGING
C MODULE STRINGING
D MODULE STRINGING
FIRE CLEARANCE
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
(N) (1) JUNCTION
BOX
18" FIRE ACCESS PATH
3' FIRE ACCESS PATH
ARRAY 1 - 9.720 KW
[x24] (N) MODULES
TILT: 17 DEGREES
ROOF PITCH: 4:12
AZIMUTH: 176 DEGREES
3' FIRE ACCESS PATH
EXTERIOR PV EQUIPMENT
(N) (1) AC COMBINER BOX
(N) (1) FUSED AC DISCONNECT
(E) (1) MAIN ELECTRICAL PANEL
INTERIOR PV EQUIPMENT
3' FIRE
ACCESS
PATH
A
ARRAY 2 - 1.620 KW
[x4] (N) MODULES
TILT: 17 DEGREES
ROOF PITCH: 4:12
AZIMUTH: 176 DEGREES
18" FIRE ACCESS PATH
A A A A A A AВ
В В В В В В В С С С
ССССС
D D D D
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH
(N) (1) PV METER
(E) (1) PEDESTAL
(E) (1) UTILITY METER
EXTERIOR PV EQUIPMENT
(N) (1) NON-FUSED AC DISCONNECT
08/22/2023
MODULE:
HANWHA Q-CELLS
Q.PEAK DUO G10+ 405W
405 WATTS
41.1"
74"
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
A-103.00
SOLAR ATTACHMENT PLAN
(SHEET 5)
01/8" = 1'-0"
SOLAR ATTACHMENT PLAN014'8'
ROOF TRUSSES
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
FLUSH MOUNT SOLAR MODULES
ATTACHED TO ROOF SURFACE (SEE
SHEET S-501 FOR MOUNTING DETAILS)
ROOF MATERIAL IS ASPHALT SHINGLE
N
E
W
S
37'-11"
13'-9"
08/22/2023
PV SYSTEM EQUIPPED WITH RAPID
SHUTDOWN DISCONNECT PER NEC 690.12
SYSTEM COMPLIANT WITH NEC 690.13
EQUIPMENT LEFT
OF LINE IS (N) NEW
UNLESS OTHERWISE NOTED.
EQUIPMENT RIGHT
OF LINE IS (E) EXISTING
UNLESS OTHERWISE NOTED.
L1 N L2
ENPHASE ENVOY
COMMUNICATIONS
GATEWAY
G
CB5
15A
CB1
20A
CB2
20A
CB3
20A
CB4
20A
G
SW1
(N) AC DISCONNECT, 60A
2
(E) GROUNDING
ELECTRODE
COLD
WATER PIPE
TO UTILITY
GRID (UG)
L1
L2
N
(Е) MAIN ELECTRICAL PANEL
240/120 V 1Ø, 3W
MAIN BUSS: 200A
GN
TO (E)
LOADS
3
BLACK
RED
G
BLACK
RED
BLACK
RED
BLACK
RED
IN BRANCH
IN BRANCH
IN BRANCH
IN BRANCH
1
(N) (28) HANWHA Q-CELLS
Q.PEAK DUO G10+ 405W
405 WATTS
(N) (28) ENPHASE
IQ8A-72-2-US
RATED POWER: 349W
(N) JUNCTION BOX
A
8
B
8
C
8
D
4
L2
L1
NNN
TAP
125A AC COMBINER BOX
ENPHASE IQ COMBINER 4
(X-IQ-AM1-240-4)
120/240V, 1Ø, 3W
MAX. CONTINUOUS CURRENT: 65A
MAX. OCPD: 90A
DC SYSTEM SIZE: 11.340 KWP
AC SYSTEM SIZE: 9.772 KWP
(E)
MAIN
200A
V
M1
(N) PV METER
4
(E)
UTILITY
METER
(E)
UTILITY
METER
G
SW2F1-2
(N) AC DISCONNECT, 60A
WITH FUSES, 60A
5
CONDUCTOR AND CONDUIT SCHEDULE W/ELECTRICAL CALCULATIONS
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING
CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR.
FACTOR
CONDUIT FILL
FACTOR
CONT.
CURRENT
MAX. CURRENT
(125%)BASE AMP.DERATED
AMP.TERM. TEMP. RATING AMP. @ TERMINAL
1 1 10 AWG THWN-2, COPPER 0.75'' DIA EMT 8 20A 10 AWG THWN-2, COPPER 0.91 (35.3 °C)0.7 11.6A 14.5A 40A 25.48A 75°C 35A
2 1 6 AWG THWN-2, COPPER 0.75'' DIA EMT 2 N/A 6 AWG THWN-2, COPPER 0.91 (35.3 °C)1 40.6A 50.75A 75A 68.25A 75°C 65A
3 1 6 AWG THWN-2, COPPER 0.75'' DIA EMT 2 N/A 6 AWG THWN-2, COPPER 0.91 (35.3 °C)1 40.6A 50.75A 75A 68.25A 75°C 65A
4 1 6 AWG THWN-2, COPPER 0.75'' DIA EMT 2 60A 6 AWG THWN-2, COPPER 0.91 (35.3 °C)1 40.6A 50.75A 75A 68.25A 75°C 65A
5 1 6 AWG THWN-2, COPPER 0.75'' DIA EMT 2 N/A 6 AWG THWN-2, COPPER 0.91 (35.3 °C)1 40.6A 50.75A 75A 68.25A 75°C 65A
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
E-601.00
LINE DIAGRAM
(SHEET 6)
MODULE STRINGING
MODULE STRINGING
A
B
MODULE STRINGINGC
MODULE STRINGINGD
SYSTEM SUMMARY
BRANCH #1 BRANCH #2 BRANCH #3 BRANCH #4
INVERTERS PER BRANCH 8 8 8 4
MAX AC CURRENT 11.6A 11.6A 11.6A 5.8A
MAX AC OUTPUT POWER 2,792W 2,792W 2,792W 1,396W
ARRAY STC POWER 11,340W
ARRAY PTC POWER 10,728W
MAX AC CURRENT 40.60A
MAX AC POWER 9,772W
DERATED (CEC) AC POWER 9,772W
DISCONNECTS
INVERTERS
OCPDS
MODULES
ASHRAE EXTREME LOW -27°C (-16.6°F), SOURCE: FORT COLLINS (AWOS) (40.45°; -105°)
ASHRAE 2% HIGH 35.3°C (95.5°F), SOURCE: FORT COLLINS (AWOS) (40.45°; -105°)
REF.QTY.RATED CURRENT MAX VOLTAGE
CB1-4 4 20A 240VAC
CB5 1 15A 240VAC
F1-2 1-2 60A 240VAC
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 EATON DG222URB OR EQUIV.60A 240VAC
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-28 28 HANWHA Q-CELLS Q.PEAK DUO G10+ 405W 405W 383.13W 11.17A 10.83A 45.34V 37.39V -0.122V/°C (-0.27%/°C)20A
REF.QTY.MAKE AND MODEL AC
VOLTAGE GROUND OCPD
RATING
RATED
POWER
MAX OUTPUT
CURRENT
MAX INPUT
CURRENT
MAX INPUT
VOLTAGE
CEC WEIGHTED
EFFICIENCY
I1-28 28 ENPHASE IQ8A-72-2-US 240V FLOATING 20A 349W 1.45A 15A 60V 97.5%
SW2 1 EATON DG222NRB OR EQUIV.60A 240VAC
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
E-602.00
DESIGN TABLES
(SHEET 7)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
E-603.00
PLACARDS
(SHEET 8)
N
EW
S
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
PV ARRAY
MAIN DISTRIBUTION
UTILITY DISCONNECT
BACK
FRONT
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE,
INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED
BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE
YELLOW BACKGROUND. [ANSI Z535]
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
LABEL 1
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT (2" X 4").
[NEC 690.13].
POWER SOURCE
OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
WARNING
LABEL 2
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE (2" X 4").
[NEC 705.12(B)(2)(3)(B)].
LABEL 3
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS (4" X 3").
[NEC 690.54]
LABEL 4
AT EACH AC DISCONNECTING MEANS
(4" X 1").
[NEC 690.13(B)].
INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SOUTH SIDE OF THE GARAGE
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE
DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV
SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN
BATHROOMS
[NEC 690.4(D),(E)]
PHOTOVOLTAIC POWER SOURCE
LABEL 9
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS (5 3/4" X 1 1/8").
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
SOLAR PV SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
TURN RAPID SHUTDOWN SWITCH TO
THE "OFF" POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE SHOCK
HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 6
AT RAPID SHUTDOWN SYSTEM
(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID
AND PV SOLAR
ELECTRIC SYSTEM
LABEL 7
AT POINT OF INTERCONNECTION
(2 3/4" X 1 5/8").
[NEC 705.12(B)(3)]
WARNING
SOLAR ELECTRIC
CIRCUIT BREAKER
IS BACKFED
LABEL 8
AT POINT OF INTERCONNECTION
(2" X 1").
[NEC 705.12(B)(3)]
CAUTION
MULTIPLE SOURCES OF POWER
LABEL 10
AT UTILITY METER (5 3/4" X 1 1/8")
[NEC 690.56(B)]
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
LABEL 5
AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").
[NEC 690.56(C)(3)].
AC DISCONNECT
PHOTOVOLTAIC SYSTEM
POWER SOURCE
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
AMPS
VOLTS
PHOTOVOLTAIC SYSTEM
DISCONNECT
40.6
240
20
12141315182211
S-501
D5
13
S-501
D4
54
252423
8
27
2 SHEET KEYNOTES
1. ROOF MATERIAL: ASPHALT SHINGLE
2. ROOF STRUCTURE: TRUSS
3. ATTACHMENT TYPE: IRONRIDGE FLASH VUE
4. MODULE MANUFACTURER: HANWHA Q-CELLS
5. MODULE MODEL: Q.PEAK DUO G10+ 405W
6. MODULE LENGTH: 74''
7. MODULE WIDTH: 41.1''
8. MODULE WEIGHT: 48.5 LBS.
9. SEE SHEET A-104 FOR DIMENSION(S)
10. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE
11. TRUSS SPACING: 24 IN. O.C.
12. TRUSS SIZE: 2X4 IN. NOMINAL.
13. LAG BOLT DIAMETER: 3/8".
14. LAG BOLT EMBEDMENT: 4".
15. TOTAL # OF ATTACHMENTS: 65
16. TOTAL AREA: 591.38 SQ. FT.
17. TOTAL WEIGHT: 1573.71 LBS.
18. WEIGHT PER ATTACHMENT: 24.21 LBS.
19. DISTRIBUTED LOAD: 2.66 PSF
20. MAX. HORIZONTAL STANDOFF: 48 IN.
21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULE
MANUFACTURER'S INSTRUCTIONS.
22. STANDOFF STAGGERING: YES
23. RAIL MANUFACTURER (OR EQUIV.): IRONRIDGE
24. RAIL MODEL (OR EQUIVALENT): XR-100
25. RAIL WEIGHT: 0.68 PLF
26. MAX. TRUSS SPAN: N/A.
27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.
1.FIELD VERIFY ALL MEASUREMENTS
2.ITEMS BELOW MAY NOT BE ON THIS PAGE
GENERAL NOTES
RO
O
F
S
L
O
P
E
910
10
6 21
7
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
RACKING DETAIL (TRANSVERSE)D1 SCALE: NOT TO SCALE
RACKING DETAIL (LONGITUDINAL)D2 SCALE: NOT TO SCALE
RACKING DETAIL (TOP)D3 SCALE: NOT TO SCALE
DETAIL (LONGITUDINAL)D5 SCALE: NOT TO SCALE
DETAIL (TRANSVERSE)D4 SCALE: NOT TO SCALE S-501.00
ASSEMBLY DETAILS
(SHEET 9)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-001.00
RESOURCE DOCUMENT
(SHEET 10)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-002.00
RESOURCE DOCUMENT
(SHEET 11)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-003.00
RESOURCE DOCUMENT
(SHEET 12)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-004.00
RESOURCE DOCUMENT
(SHEET 13)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-005.00
RESOURCE DOCUMENT
(SHEET 14)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-006.00
RESOURCE DOCUMENT
(SHEET 15)
B F
A D E
2
3
DESIGN BY:
A C D E G H
B C F G H
1
4
5
6
DATE:
CHECKED BY:
REVISIONS
V.T.
M.M.
06.21.2023
PAPER SIZE: 11" x 17" (ANSI B)
V.1.9
CONTRACTOR
PHONE:
LIC. NO.:
HIC. NO.:
ELE. NO.:
ADDRESS:
AFFORDABLE ALTERNATIVE
ENERGY DBA ARE SOLAR
1155 S TEJON ST
DENVER, CO 80223
720-504-0005
LSVL-001411-2018
ENGINEER OF RECORD
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
11.340 kWp DC / 9.772 kWp AC
MONTGOMERY
RESIDENCE
461 MARCUS LN,
ESTES PARK, CO 80517
APN: 3536421001
R-007.00
RESOURCE DOCUMENT
(SHEET 16)