Loading...
HomeMy WebLinkAboutPLANS PV System 704 Moreau Ln 2023-06-12RE:CERTIFICATION LETTER Project Address: DANIEL BARWINSKI 704 MOREAU LANE ESTES PARK, CO 80517 Design Criteria: - Applicable Codes = 2015 IEBC/IBC, 2015 IRC, ASCE 7-16 and 2015 NDS - Risk Category = II - Wind Speed = 173 mph, Exposure Category C, Partially/Fully Enclosed Method - Ground Snow Load = 70 psf - ROOF 1 - 3: 2 x 6 @ 24" OC, Roof DL = 7 psf, Roof LL/SL = 54 psf (Non-PV), Roof LL/SL = 39.5 psf (PV) To Whom It May Concern, June 2, 2023 This document is the property of Barun Corp and cannot be reproduced without prior consent. It is site specific and shall not be transferred to any other property, property owner, person(s), or entity. This document may include an expression of professional opinion by the engineer of record, which is based on his or her best knowledge, information provided by others, and belief. Other professionals may have different opinions. Barun Corp reserves the right to amend and/or supplement this document in the event additional information be uncovered or made available. A structural evaluation of loading was conducted for the above address based on the design criteria listed above. Existing roof structural framing has been reviewed for additional loading due to installation of Solar PV System on the roof. The structural review applies to the sections of roof that is directly supporting the Solar PV System. Based on this evaluation, I certify that the alteration to the existing structure by installation of the Solar PV System meets the prescriptive compliance requirements of the applicable existing building and/or new building provisions adopted/referenced above. specifications and to meet and/or exceed the requirements set forth by the referenced codes. Sincerely, Barun Corp | Design and Engineering | 610.202.4506 | chrisk@baruncorp.com | www.baruncorp.com 1/4 REVIEWED BY SAFEBUILT 06/12/2023 ROOF PITCH 26° Limits of Scope of Work and Liability: MOUNTING PLANE ROOF 1 - 3 STANDOFF HARDWARE EVALUATION FOR WIND UPLIFT WIND UPLIFT DCR 72.5% BARUN CORP RESULTS SUMMARY DANIEL BARWINSKI, 704 MOREAU LANE, ESTES PARK, CO 80517 MOUNTING PLANE STRUCTURAL EVALUATION MOUNTING PLANE ROOF 1 - 3 GOVERNING ANALYSIS MEMBER ANALYSIS RESULT OK The existing structure has been reviewed based on the assumption that it has been originally designed and constructed per appropriate codes. The structural analysis of the subject property is based on the provided site survey data. The calculations produced for this structure's assessment are only for the roof framing supporting the proposed PV installation referenced in the stamped planset and were made according to generally recognized structural analysis standards and procedures. All PV modules, racking and attachment components shall be designed and installed per approved guidelines and specifications. These plans are not stamped for water leakage or existing damage to the structural component that was not accessed during the site survey. Prior to commencement of work, the PV system installer should verify that the existing roof and connections are in suitable condition and inspect framing noted on the certification letter and inform the Engineer of Record of any discrepancies prior to installation. The installer should also check for any damages such as water damage, cracked framing, etc. and inform the Engineer of Record of existing deficiencies which are unknown and/or were not observable during the time of survey and have not been included in this scope of work. Any change in the scope of the work shall not be accepted unless such change, addition, or deletion is approved in advance and in writing by the Engineer of Record. Barun Corp | Design and Engineering | 610.202.4506 | chrisk@baruncorp.com | www.baruncorp.com 2/4 REVIEWED BY SAFEBUILT 06/12/2023 PV Panels Weight = 2.50 psf Hardware Assembly Weight = 0.50 psf PV-DL = 3.00 psf Existing Roofing Material Weight 1 Layer(s) = 2.50 psf Underlayment Weight = 0.50 psf Plywood/OSB Sheathing Weight = 1.50 psf Framing Weight = 1.15 psf No Vaulted Ceiling = 0.00 psf Miscellaneous = 1.50 psf Total Roof Dead Load R-DL = 7.10 psf Roof Live Load Lo = 20.00 psf Member Tributary Area At <200 ft2 ROOF 1 - 3 Pitch 26° or 6/12 Tributary Area Reduction Factor R1 = 1.00 Roof Slope Reduction Factor R2 = 0.90 Reduced Roof Live Load, Lr = Lo (R1) (R2) Lr = 18.00 psf Ground Snow Load pg =70.00 psf Effective Roof Slope 26° Snow Importance Factor Is =1.00 Snow Exposure Factor Ce =1.00 Snow Thermal Factor Ct =1.10 Minimum Flat Roof Snow Load pf-min =0.00 psf Flat Roof Snow Load pf = 53.90 psf Roof Slope Factor Cs-roof = 1.00 Sloped Roof Snow Load on Roof ps-roof = 53.90 psf Roof Slope Factor Cs-PV = 0.73 Sloped Roof Snow Load on PV Panels ps-PV = 39.50 psf SLOPED ROOF SNOW LOAD ON PV PANELS (Unobstructed Slippery Surfaces) ROOF DEAD LOAD (R-DL) Total PV Panels 2 x 6 @ 24 in. O.C. REDUCED ROOF LIVE LOAD (Lr) SNOW LOAD SLOPED ROOF SNOW LOAD ON ROOF (Non-Slippery Surfaces) Composite Shingle Roof BARUN CORP ROOF 1 - 3 LOAD CALCULATION DANIEL BARWINSKI, 704 MOREAU LANE, ESTES PARK, CO 80517 PV PANELS DEAD LOAD (PV-DL) Barun Corp | Design and Engineering | 610.202.4506 | chrisk@baruncorp.com | www.baruncorp.com 3/4 REVIEWED BY SAFEBUILT 06/12/2023 REVIEWED BY SAFEBUILT 06/12/2023 REVIEWED BY SAFEBUILT 06/12/2023 173.00 mph 26° II Gable C 0.90 20.00 ft 1.00 3.00 psf 0.85 3.00 ft 1.00 58.74 psf (0.00256*Kz*Kzt*Kd*Ke*(V^2)) 0.60 1310.00 lbs 1.50 4.00 ft 3.14 ft 4.00 ft 3.14 ft 3.33 ft 3.14 ft ROOF ZONE GCp (-) UPLIFT 1 & 2e -1.50 2n - 3e -2.39 3r -2.92 Max. Y - Spacing (Zone 3r) = -90.87 psf 949.61 lbs UPLIFT PRESSURE PULLOUT FORCE -45.96 psf 576.82 lbs -74.21 psf 931.38 lbs NOTE: Risk Category = Exposure Category = Mean Roof Height = Solar Array Dead Load = DESIGN CALCULATIONS Wind Velocity Pressure, qh = Max. X - Spacing (Zone 2n - 3e) = a = Roof Type = Wind Directionality Factor, Kd = Topographic Factor, Kzt = Velocity Pressure Exposure Coefficient, Kz = Ground Elevation Factor, Ke = Exposed Condition Hardware Type = IRONRIDGE QUICKMOUNT Allowable Load = Effective Wind Area 12.55 ft² 12.55 ft² BARUN CORP WIND UPLIFT CALCULATION ROOF 1 - 3 DANIEL BARWINSKI, 704 MOREAU LANE, ESTES PARK, CO 80517 Ultimate Wind Speed = Roof Pitch = SITE INFORMATION SPF, 5/16" Lag Screw x 2, 2.5" Embedment Max. Y - Spacing (Zone 2n - 3e) = Max. X - Spacing (Zone 3r) = Max. X - Spacing (Zone 1 & 2e) = Max. Y - Spacing (Zone 1 & 2e) = Effective Wind Area Effective Wind Area 10.45 ft² Barun Corp | Design and Engineering | 610.202.4506 | chrisk@baruncorp.com | www.baruncorp.com 4/4 REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 VICINITY MAP AERIAL MAP PV-1 REV #1: REV #2: REV #3: DATE: 6/1/2023 DRAWN BY: AP COVER PAGE BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 BARWINSKI RESIDENCE PHOTOVOLTAIC SYSTEM 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK GOVERNING CODES: ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES: ·2020 NATIONAL ELECTRIC CODE (NEC) ·2015 INTERNATIONAL FIRE CODE ·2015 INTERNATIONAL BUILDING CODE (IBC) ·2015 INTERNATIONAL EXISTING BUILD CODE (IEBC) ·2015 INTERNATIONAL RESIDENTIAL CODE (IRC) ·2015 INTERNATIONAL MECHANICAL CODE ·2015 INTERNATIONAL FUEL GAS CODE ·2015 INTERNATIONAL PLUMBING CODE ·2015 INTERNATIONAL ENERGY CONSERV. CODE ·OSHA 29 CFR 1910.269 ·UNDERWRITERS LABORATORIES (UL) STANDARDS 11. PLUMBING AND MECHANICAL VENTS THROUGH THE ROOF SHALL NOT BE COVERED BY SOLAR MODULES- - NO BUILDING, PLUMBING OR MECHANICAL VENTS TO BE COVERED, CONSTRUCTED OR ROUTED AROUND SOLAR MODULES. 12. ALL FIELD -INSTALLED JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A MODULE SECURED BY REMOVABLE FASTENERS. ELECTRICAL 1. WIRING MATERIALS SHALL COMPLY WITH MAXIMUM CONTINUOUS CURRENT OUTPUT AT 25°C AND MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET RATED AT 90°C. 2. EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON THE ROOF WILL BE USE 2 OR PV-TYPE WIRE. 3. PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR-CODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. 4. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. 5. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. 6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL SIZE THEM ACCORDING TO APPLICABLE CODES. 7. REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BUILDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PV SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR. 8. FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED WITH A GROUND-FAULT PROTECTION DEVICE OR SYSTEM THAT DETECTS A GROUND FAULT, INDICATES THAT FAULT HAS OCCURED AND AUTOMATICALLY DISCONNECTS ALL CONDUCTORS OR CAUSES THE INVERTER TO AUTOMATICALLY CEASE SUPPLYING POWER TO OUTPUT CIRCUITS. 9. FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED WITH GROUND FAULT PROTECTION AND A GFI FUSE PORT FOR GROUND FAULT INDICATION. 10. PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL OR BARE COPPER GEC/GEC PER THE MODULE MANUFACTURER'S LISTED INSTRUCTION SHEET. 11. PV MODULE RACKING RAIL SHALL BE BONDED TO BARE COPPER GEC VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN LUG, OR EQUIVALENT LISTED LUG. 12. THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741 COMPLIANT. 13. RACKING AND BONDING SYSTEM TO BE UL2703 RATED. 14. ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AS BUS BARS WITHIN LISTED EQUIPMENT. 15. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THE BREAKERS SHALL NOT READ "LINE AND LOAD". 16. WHEN APPLYING THE 120% RULE, THE SOLAR BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. 17. THE WORKING CLEARANCE AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE MAINTAINED. GENERAL 1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF PHOTOVOLTAIC SYSTEM. 2. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION 3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO INITIATING CONSTRUCTION. 4. CONTRACTOR SHALL REVIEW ALL MANUFACTURER INSTALLATION DOCUMENTS PRIOR TO INITIATING CONSTRUCTION. 5. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS, ETC, AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED ONLY BY QUALIFIED PERSONNEL. 6. THE CONTRACTOR OR OWNER MUST PROVIDE ROOF ACCESS (LADDER TO ROOF) FOR ALL THE REQUIRED INSPECTIONS. LADDERS MUST BE OSHA APPROVED, MINIMUM TYPE I WITH A 250LB. RATING, IN GOOD CONDITION AND DESIGNED FOR ITS INTENDED USE. 7. CONTRACTOR SHALL VERIFY THAT THE ROOF STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS. 8. LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT EXCEED MANUFACTURER RECOMMENDATIONS FOR FASTENERS INTO ENGINEERED STRUCTURAL MEMBERS. 9. AN ACCESS POINT SHALL BE PROVIDED THAT DOES NOT PLACE THE GROUND LADDER OVER OPENINGS SUCH AS WINDOWS OR DOORS ARE LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION AND IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. 10. WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING, THEY SHALL BE CONTAINED IN A METAL RACEWAY; THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE COVERED BY THE PV MODULES AND EQUIPMENT. PV-1 - COVER PAGE PV-2 - PROPERTY PLAN PV-3 - SITE PLAN PV-3.1 - ROOF PLAN PV-4 - 1-LINE DIAGRAM PV-4.1 - 3-LINE DIAGRAM PV-5 - MOUNTING DETAILS AND BOM PV-6 - LABELS PV-7 - CIRCUITS PV-8 - DATASHEETS PV-9 - PLACARD SHEET INDEX: SYSTEM SIZE: 9.60 kW-DC | 8.38 kW-AC MODULE: (24) SILFAB: SIL-400-HC (400W) INVERTER: (24) ENPHASE IQ8A-72-2-US[240V]MICROINVERTER SAFEbuilt APPROVED Subject to inspection and compliance to all relevant Adopted Building and Municipal codes. Changes in Plans MUST be approved. D.GRAHAM 06/12/2023 I-CODES 2015 23-EP-00286 PRINT PLANS IN COLOR AND HAVE FOR INSPECTOR AT TIME OF INSPECTION PLAN REVIEWED FOR BUILDING AND STRUCTURAL REQUIREMENTS ONLY. INSTALLATION INSTRUCTIONS AND MANUALS MUST BE ON JOB FOR THE INSPECTOR AT THE TIME OF INSPECTION FOR ALL EQUIPMENT. N 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 SCALE: 1/16" = 1'-0" LEGEND: PROPERTY LINE: DATE: 6/1/2023 DRAWN BY: AP PROPERTY PLAN PV-2 DRIVEWAY: APN: 3526415023 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 PROPERTY LINE AHJ: ESTES PARK M A I N H O M E DRIVE W A Y 137'-10" 162'-1" 25'-6" 67'-11"----M O R E A U L A N E . - - - - 14'-2" 13'-4" 40'-4" 35'-10" REVIEWED BY SAFEBUILT 06/12/2023 N 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 SYSTEM LEGEND UM MP AC MAIN UTILITY AND SERVICE POINT MAIN SERVICE PANEL UTILITY AC DISCONNECT SCALE: 1/8" = 1'-0" CONDUIT TO BE RUN IN ATTIC IF POSSIBLE, OTHERWISE CONDUIT BLOCKS MIN. 1"/MAX 6" ABOVE ROOF SURFACE, CLOSE TO RIDGE LINES, AND UNDER EAVES; TO BE PAINTED TO MATCH EXTERIOR/EXISTING BACKGROUND COLOR OF ITS LOCATION; TO BE LABELED AT MAX 10' INTERVALS. CONDUIT RUNS ARE APPROXIMATE AND ARE TO BE DETERMINED IN THE BY THE INSTALLERS CONDUIT RUN FIRE CODE SETBACK (36" MAX) PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 9.60 kW AC SYSTEM SIZE: 8.38 kW ROOF SECTION 1: 10 MODULES AZIMUTH: 242° PITCH: 26° ROOF TYPE: COMPOSITE SHINGLE ROOF SECTION 2: 8 MODULES AZIMUTH: 242° PITCH: 26° ROOF SECTION 3: 6 MODULES AZIMUTH: 242° PITCH: 26° ROOF DETAIL 1 2 3 DATE: 6/1/2023 DRAWN BY: AP SITE PLAN PV-3 JUNCTION BOX AND CONDUIT BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK (24)SILFAB: SIL-400-HC (400W) WITH ENPHASE IQ8A-72-2-US[240V] MICROINVERTERS MOUNTED UNDER EACH MODULE. SP 200A RATED SUB-PANEL CP AC UM MP 1 CP ENPHASE AC COMBINER PANEL(X-IQ-AM1-240-4) SP 3' 3' 3' 3' 3' 3' 3' 2 3 REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 N SYSTEM LEGEND SCALE: 1/8" = 1'-0" ELEVATION DETAIL FIRE CODE SETBACK (36" MAX) ROOF ATTACHMENT POINT DATE: 6/1/2023 DRAWN BY: AP ROOF PLAN PV-3.1 STRUCTURAL ATTACHMENT MODULE COMPOSITE SHINGLE TRUSSES @ 24" O.C: 2"X6" BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 RAFTERS/TRUSS RACKING AHJ: ESTES PARK MODULE MECHANICAL SPECIFICATIONS DESIGN WIND SPEED 173 MPH DESIGN SNOW LOAD 70 PSF # OF STORIES 1 ROOF PITCH 26° TOTAL ARRAY AREA (SQ. FT)459.36 TOTAL ROOF AREA (SQ. FT)2567 ARRAY SQ. FT / TOTAL ROOF SQ. FT 17.89% ROOF SECTION 1: 10 MODULES AZIMUTH: 242° PITCH: 26° ROOF TYPE: COMPOSITE SHINGLE ROOF SECTION 2: 8 MODULES AZIMUTH: 242° PITCH: 26° ROOF SECTION 3: 6 MODULES AZIMUTH: 242° PITCH: 26° ROOF DETAIL 1 2 3 2 3 1 3' 3' 3' 3' 3' 3' 3' 4' TYP.REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 NOTES: 1.MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2.PV DC SYSTEM IS UNGROUNDED 3.PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4.PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5.BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6.BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7.INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. DATE: 6/1/2023 DRAWN BY: AP 1-LINE DIAGRAM & CALCULATIONS PV-4 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 9.60 kW AC SYSTEM SIZE: 8.38 kW INVERTER: (24) ENPHASE IQ8A-72-2-US[240V]MICROINVERTER MODULE: (24) SILFAB: SIL-400-HC (400W) BUSBAR CALCULATIONS - PV BREAKER - 120% RULE MAIN BUS RATING 200 MAIN DISCONNECT RATING 150 PV BREAKER RATING 50 (MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING (200A x 1.2) - 150A >= 50A, OK PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE SILFAB: SIL-400-HC (400W) POWER MAX (PMAX)400W OPEN CIRCUIT VOLTAGE (VOC)43.02V SHORT CIRCUIT CURRENT (ISC)11.58A MAX POWER-POINT VOLTAGE (VMP)36.05V MAX POWER-POINT CURRENT (IMP)11.10A SERIES FUSE RATING 20A AHJ: ESTES PARK CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 6 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 6 - L1 L2 EMT 3/4" 2 THWN-2 EGC #8 1 - GND EMT 3/4" 3 THWN-2 #6 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #8 1 - GND EMT 3/4" 4 THWN-2(AL)#2/0 3 - L1 L2 N EMT 1.5" 4 THWN-2 EGC #6 1 - GND EMT 1.5" NOTES: ALL DC CONNNECTORS TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURE BRAND AND STYLE. DO NOT USE COMPATIBLE’ CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MIS-MATCHED CONNECTOR USEAGE. CIRCUIT 3: 6 MODULES - SILFAB: SIL-400-HC (400W) === 7 NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 2P - 20A 2P - 20A 2P - 15A ENVOY-IQ MONITOR (N) 240V/60A PV ENPHASE PV LOAD CENTER, AC COMBINER(X-IQ-AM1-240-4) WITH INTEGRATED MONITORING, NEMA 3R RATED CIRCUIT 2: 8 MODULES - SILFAB: SIL-400-HC (400W) === 5 THE ENPHASE IQ8A-72-2-US[240V]MICROINVERTER HAVE INTEGRATED GROUND AND DOUBLE INSULATION, SO NO GEC OR EGC IS REQUIRED. THE DC CIRCUIT IS ISOLATED AND INSULATED FROM GROUND AND MEETS THE REQUIREMENTS OF NEC 690.35 ENPHASE IQ8A-72-2-US[240V]MICROINVERTER CIRCUIT 1: 10 MODULES - SILFAB: SIL-400-HC (400W) === 9 2P - 20A (N) AC DISCONNECT 240V/60A NEMA 3R NON-FUSIBLE, VISIBLE-LOCKABLE LABELED UTILITY SERVICE ESTES PARK UTILITY 120/240V SINGLE PHASE FACILITY GROUND (E) GROUND ROD (N) PV OCPD 2P - 50A (N)200A RATED SUB PANEL L1 G N-G G INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE ENPHASE IQ8A-72-2-US[240V] MICROINVERTER MAX INPUT DC VOLTAGE 60V MAX DC SHORT CIRCUIT CURRENT 15A MAXIMUM OUTPUT POWER 349W MAXIMUM CONT. OUTPUT CURRENT 1.45A CEC EFFICIENCY 97% MAX UNITS PER 20A CIRCUIT 13 SYSTEM OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE ENPHASE IQ8A-72-2-US[240V] MICROINVERTER # OF INVERTERS 24 MAX CONTINUOUS OUTPUT CURRENT 1.45 (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING (24 x 1.45A x 1.25)= 43.50A <= 50A, OK (N)150A DISCONNECT (E)INTERIOR DISTRIBUTION PANE G (E)150A RATED MAIN SERVICE PANEL (E)150A MAIN DISCONNECT (E) LOADS (E) LOADS THIS ELECTRICAL INSTALLATION MUST CONFORM TO THE 2020 NEC ELECTRICAL INSPECTIONS AND PLAN REVIEWS (IF REQUIRED) PER THE STATE OF COLORADO. 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP 3-LINE DIAGRAM & CALCULATIONS PV-4.1 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 NOTES: 1.MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2.PV DC SYSTEM IS UNGROUNDED 3.PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4.PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5.BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6.BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7.INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9.CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. AHJ: ESTES PARK PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 9.60 kW AC SYSTEM SIZE: 8.38 kW INVERTER: (24) ENPHASE IQ8A-72-2-US[240V]MICROINVERTER MODULE: (24) SILFAB: SIL-400-HC (400W) NOTES: ALL DC CONNNECTORS TO MODULES OR INVERTERS MUST BE OF MATCHING MANUFACTURE BRAND AND STYLE. DO NOT USE COMPATIBLE’ CONNECTORS WHICH HAVE NOT BEEN UL TESTED FOR COMPATIBILITY. PERFORMANCE AND FIRE DAMAGE MAY RESULT FROM MIS-MATCHED CONNECTOR USEAGE. BUSBAR CALCULATIONS - PV BREAKER - 120% RULE MAIN BUS RATING 200 MAIN DISCONNECT RATING 150 PV BREAKER RATING 50 (MAIN BUS RATING x 1.2) - MAIN DISCONNECT RATING >= OCPD RATING (200A x 1.2) - 150A >= 50A, OK PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE SILFAB: SIL-400-HC (400W) POWER MAX (PMAX)400W OPEN CIRCUIT VOLTAGE (VOC)43.02V SHORT CIRCUIT CURRENT (ISC)11.58A MAX POWER-POINT VOLTAGE (VMP)36.05V MAX POWER-POINT CURRENT (IMP)11.10A SERIES FUSE RATING 20A INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE ENPHASE IQ8A-72-2-US[240V] MICROINVERTER MAX INPUT DC VOLTAGE 60V MAX DC SHORT CIRCUIT CURRENT 15A MAXIMUM OUTPUT POWER 349W MAXIMUM CONT. OUTPUT CURRENT 1.45A CEC EFFICIENCY 97% MAX UNITS PER 20A CIRCUIT 13 SYSTEM OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE ENPHASE IQ8A-72-2-US[240V] MICROINVERTER # OF INVERTERS 24 MAX CONTINUOUS OUTPUT CURRENT 1.45 (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING (24 x 1.45A x 1.25)= 43.50A <= 50A, OK CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 6 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 6 - L1 L2 EMT 3/4" 2 THWN-2 EGC #8 1 - GND EMT 3/4" 3 THWN-2 #6 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #8 1 - GND EMT 3/4" 4 THWN-2(AL)#2/0 3 - L1 L2 N EMT 1.5" 4 THWN-2 EGC #6 1 - GND EMT 1.5" 2P - 20A 2P - 20A 2P -15A ENVOY-IQ MONITOR (N) 240V/60A PV ENPHASE PV LOAD CENTER, AC COMBINER(X-IQ-AM1-240-4) WITH INTEGRATED MONITORING, NEMA 3R RATED CIRCUIT 3: 6 MODULES - SILFAB: SIL-400-HC (400W) === 7 NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 CIRCUIT 2: 8 MODULES - SILFAB: SIL-400-HC (400W) === 5 THE ENPHASE IQ8A-72-2-US[240V]MICROINVERTER HAVE INTEGRATED GROUND AND DOUBLE INSULATION, SO NO GEC OR EGC IS REQUIRED. THE DC CIRCUIT IS ISOLATED AND INSULATED FROM GROUND AND MEETS THE REQUIREMENTS OF NEC 690.35 ENPHASE IQ8A-72-2-US[240V]MICROINVERTER CIRCUIT 1: 10 MODULES - SILFAB: SIL-400-HC (400W) === 9 2P - 20A (N) AC DISCONNECT 240V/60A NEMA 3R NON-FUSIBLE, VISIBLE-LOCKABLE LABELED (E)150A MAIN DISCONNECT UTILITY SERVICE ESTES PARK UTILITY 120/240V SINGLE PHASE (E)150A RATED MAIN SERVICE PANEL FACILITY GROUND (E) GROUND ROD (N) PV OCPD 2P - 50A (N)150A MAIN DISCONNECT (N)200A RATED SUB PANEL L2 L1 N G N-G N G (E)INTERIOR DISTRIBUTION PANE (E) LOADS N G (E) LOADS ELECTRICAL INSPECTIONS AND PLAN REVIEWS (IF REQUIRED) PER THE STATE OF COLORADO. THIS ELECTRICAL INSTALLATION MUST CONFORM TO THE 2020 NEC 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 PV MODULE FRAME IRONRIDGE RAIL DETAIL, MID CLAMP FRONT IRONRIDGE UNIVERSAL FASTENING OBJECTPV MODULE FRAME DETAIL, MID CLAMP PLAN IRONRIDGE UNIVERSAL FASTENING OBJECT PV MODULE FRAME IRONRIDGE RAIL DETAIL, END CLAMP CAMO FRONT IRONRIDGE STOPPER SLEEVE IRONRIDGE UNIVERSAL FASTENING OBJECTPV MODULE FRAME IRONRIDGE RAIL DETAIL, END CLAMP CAMO PLAN IRONRIDGE STOPPER SLEEVE IRONRIDGE UNIVERSAL FASTENING OBJECT DATE: 6/1/2023 DRAWN BY: AP PV-5 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 MOUNTING DETAILS AND BOM ATTACHMENT TYPE: IRONRIDGE QUICKMOUNT HALO ULTRAGRIP WITH IRONRIDGE XR100 RAILS ROOF TYPE: COMPOSITE SHINGLE, ROOF TILT: 26° MODULE WEIGHT: 47 LBS MODULE DIMENSIONS: 5.78' X 3.4' MODULE WEIGHT/ SQ. FOOT: 2.20 LBS TOTAL NO. OF MODULES: 24 TOTAL MODULE WEIGHT: 1,128 LBS ATTACHMENT DETAILS (N.T.S.) 1 AHJ: ESTES PARK BILL OF MATERIAL EQUIPMENT MAKE QUANTITY MODULE SILFAB: SIL-400-HC (400W)24 INVERTER ENPHASE IQ8A-72-2-US[240V]MICROINVERTER 24 END CLAMPS MODULE END CLAMP STANDARD 20 MID CLAMPS MODULE MIDDLE CLAMP SET STANDARD(INTEGRATED GROUNDING)58 MOUNTING POINTS IRONRIDGE QUICKMOUNT HALO ULTRAGRIP 53 MOUNTING RAILS IRONRIDGE XR 100 RAIL 13 AC DISCONNECT PV SYSTEM UTILITY AC DISCONNECT 60A RATED 1 SUBPANEL 200A RATED SUBPANEL 1 REVIEWED BY SAFEBUILT 06/12/2023 PROVIDE ALL RACKING INSTALLATION INSTRUCTIONS AND DOCUMENTATION TO THE INSPECTOR AT THE TIME OF INSPECTION 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP PV-6 LABELS ARE NOT DRAWN TO SCALE BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 ELECTRICAL LABELS & ELEVATION LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION [NEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B) AHJ: ESTES PARK !WARNING ! DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM LABEL 7 PHOTOVOLTAIC AC DISCONNECT OPERATING CURRENT: 34.8A AC OPERATING VOLTAGE: 240 V AC LABEL 5 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS [NEC 690.54] !WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. LABEL 3 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.13 AND 690.15] PHOTOVOLTAIC DC DISCONNECT UTILITY AC DISCONNECT LABEL 10 AT EACH DC DISCONNECTING MEANS [NEC 690.13(B)] LABEL 12 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 13 AT EACH AC DISCONNECTING MEANS [NEC 690.13(B)] !CAUTION ! PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED !WARNING ! POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVISE LABEL 14 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE [NEC 705.12(B)(2)(3)(B)] LABEL 9 AT UTILITY METER [NEC 690.56(B)] LABEL 4 AT EACH DC DISCONNECTING MEANS [NEC 690.53] LABEL 11 AT RAPID SHUTDOWN SWITCH [NEC 690.56(C)]. LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 8 AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY PHOTOVOLTAIC SYSTEM [NEC 705.12(B)(4)] TURN RAPID SHUTDOWN SWICH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 1 AT RAPID SHUTDOWN SYSTEM [NEC 690.56(C)(1)(A)]. ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPLOSED TO SUNLIGHT LABEL 2 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.15] MAXIMUM VOLTAGE: V DC MAXIMUM CIRCUIT CURRENT: A DC MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED): A DC LABEL 6 AT RAPID SHUTDOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. #03-359 LOCAL CODES BI-DIRECTIONAL METER WARNING: PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS WARNING THIS SERVICE METER IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM THIS SERVICE PANEL IS ENERGIZED FROM MORE THAN ONE SOURCE. ONLY AUTHORIZED PERSON WHO ARE FAMILIAR WITH THIS SYSTEM SHOULD ATTEMPT TO DO SERVICE WORK ON IT WARNING: DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM PHOTOVOLTAIC SYSTEM CONNECTED SOLAR PRODUCTION METER AC DISCONNECT LABEL 15 PER XCEL ON MAIN SERVICE PANEL PER NEC 705.12 (2)(c) TO BE PLACED ON UTILITY METER TO BE PLACED ON PRODUCTION METER TO BE PLACED ON AC DISCONNECT REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 FOR INSTALLER USE ONLY DATE: 6/1/2023 DRAWN BY: AP CIRCUITS MAP PV-7 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK ENPHASE CIRCUITS CIRCUIT # 1: 10 MODULES CIRCUIT DETAIL CIRCUIT # 2: 8 MODULES CIRCUIT-1 CIRCUIT-2 CIRCUIT # 3: 6 MODULES CIRCUIT-3 REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP MODULE DATASHEET PV-8.1 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP INVERTER DATASHEET PV-8.2 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP COMBINER DATASHEET PV-8.3 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP RACKING DATASHEET PV-8.4 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK REVIEWED BY SAFEBUILT 06/12/2023 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 DATE: 6/1/2023 DRAWN BY: AP ROOF ATTACHMENT DATASHEET PV-8.5 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK REVIEWED BY SAFEBUILT 06/12/2023 ENGINEERS' LETTER BASED ON (2) 5/16" SCREWS WITH 2.5" OF EMBEDMENT IN TO RAFTER. 1030 BOSTON AVE,LONGMONT COLORADO 80501 TEL. NO.(303) 484-1410 PROGREEN SOLAR, LLC LIC. NO. EC.0101788 N DATE: 6/1/2023 DRAWN BY: AP PLACARD PV-9 BARWINSKI, DANIEL 704 MOREAU LANE., ESTES PARK, CO 80517 AHJ: ESTES PARK CAUTION POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN !! SERVICE 1 OF 1 INVERTER SOLAR PHOTOVOLTAIC ARRAY 704 MOREAU LANE., ESTES PARK, CO 80517 MAIN SERVICE PANEL UTILITY AC DISCONNECT UTILITY METER SUBPANEL REVIEWED BY SAFEBUILT 06/12/2023