Loading...
HomeMy WebLinkAboutPLANS Post Restaurant 333 E Wonderview Ave 2021-03-30OPENING -NEW DOOR AND HARDWARE RENOVATION -OPENING -EXISTING DOOR TO REMAIN RENOVATION -EXISTING WALL TO REMAIN RENOVATION -EXISTING WALL (DASHED) TO BE DEMOLISHED WALL AND OPENING LEGEND RENOVATION -OPENING -EXISTING DOOR (DASHED) TO BE DEMOLISHED STUD WALL FRAMING 1. ABBREVIATIONS REFERENCED FROM THE CONSTRUCTION SPECIFICATIONS INSTITUTE’S UNIFORM DRAWING SYSTEM TERMS AND ABBREVIATIONS MODULE. 2. DIMENSIONS TO FACE OF OBJECTS ARE MARKED BY DIAGONAL TICK MARKS, DIMENSIONS TO GRIDS ARE MARKED BY SOLID DOTS. 3. AT ALL CORRIDORS, LOBBIES, STAIRS AND COMMONS, ALL EXPOSED PARTITION ENDS , OUTSIDE CORNERS, AND TRIMMED OPENINGS SHALL HAVE CORNER GUARDS (GYPSUM BOARD WALLS ONLY). 4. ALL CORRIDOR GYPSUM BOARD FACED WALLS SHALL BE 5/8”FIBER REINFORCED IMPACT RESISTANT GYPSUM BOARD TO 8’–0”AFF. 5. PROVIDE AN INTERNAL CORNER EXPANSION JOINT AT ALL LOCATIONS IN MASONRY VENEERS. 6. FEATURES THAT APPEAR TO BE CENTERED ON BUILDING COLUMNS OR OTHER STRUCTURE ARE, AND HENCE ARE NOT SPECIFICALLY DIMENSIONED ON ARCHITECTURAL PLANS. 7. FACES OF WALLS THAT APPEAR TO BE ALIGNED ARE IN FACT ALIGNED, UNO 8. SHEET SPECIFIC IDENTIFICATION OF ITEMS (E.G. 08 1113.01) DIRECTLY REFERENCE CORRESPONDING ARCHITECTURAL SECTIONS IN THE PROJECT MANUAL. THE DECIMAL POINT AND SUFFIX NUMBERS ARE NOT IDENTIFIED IN SPECIFICATIONS. COMMUNICATIONS T0.1 COMMUNICATIONS TITLE SHEET T0.2 COMMUNICATIONS PROJECT NOTES T0.3 COMMUNICATIONS SCHEDULES T0.4 COMMUNICATIONS SCHEDULES T0.5 COMMUNICATIONS SPECIFICATIONS T0.6 COMMUNICATIONS SPECIFICATIONS T0.7 COMMUNICATIONS SPECIFICATIONS T0.8 COMMUNICATIONS SPECIFICATIONS T1.1 COMMUNICATIONS SITE PLAN T2.1 COMMUNICATIONS BASEMENT FLOOR PLAN T2.2 COMMUNICATIONS FIRST FLOOR PLAN T6.1 COMMUNICATIONS DETAILS T6.2 COMMUNICATIONS DETAILS T6.3 COMMUNICATIONS DETAILS FOOD SERVICE FS-1.0 EQUIPMENT FLOOR PLAN FS-1.1 EQUIPMENT FLOOR PLAN FS-2.0 EQUIPMENT SCHEDULE FS-3.0 PLUMBING PLAN FS-3.1 PLUMBING PLAN FS-4.0 ELECTRICAL PLAN FS-4.1 ELECTRICAL PLAN FS-5.0 BUILDING WORKS PLAN FS-5.1 BUILDING WORKS PLAN FS-6.0 EXHAUST HOOD PLAN FS-6.1 EXHAUST HOOD PLAN FS-6.2 EXHAUST HOOD PLAN FS-6.3 EXHAUST HOOD PLAN FS-6.4 EXHAUST HOOD PLAN GENERAL G-000 COVER SHEET G-001 CODE ANALYSIS & SYSTEM ASSEMBLIES ARCHITECTURE A-090 BASEMENT LEVEL- OVERALL FLOOR PLAN A-100 LEVEL 1 - OVERALL FLOOR PLAN A-110 BASEMENT LEVEL - REFLECTED CEILING PLAN A-120 LEVEL 1 - REFLECTED CEILING PLAN A-451 LARGE SCALE PLANS - BAR A-452 LARGE SCALE ELEVATIONS - BAR A-453 LARGE SCALE PLANS & ELEVATIONS - MERCHANDISE DISPLAY A-454 LARGE SCALE PLANS & ELEVATIONS - DINING A-501 DETAILS - BAR A-502 DETAILS - MERCHANDISE DISPLAY AND DINING A-601 DOOR AND FINISH SCHEDULE A-700 BASEMENT LEVEL - FINISH & FURNITURE PLAN A-701 LEVEL 1 - FINISH & FURNITURE PLAN A-800 SPECIFICATIONS A-801 SPECIFICATIONS A-802 SPECIFICATIONS A-900 PERPECTIVES PLUMBING P-001 PLUMBING GENERAL INFORMATION P-002 PLUMBING SPECIFICATIONS P-100 UNDERGROUND PLUMBING PLAN P-200 BASEMENT PLUMBING PLAN P-201 LEVEL 1 PLUMBING PLAN P-202 ROOF PLUMBING PLAN P-501 PLUMBING ISOMETRICS MECHANICAL M-001 MECHANICAL GENERAL INFORMATION M-002 MECHANICAL SCHEDULES M-003 MECHANICAL SPECIFICATIONS M-004 MECHANICAL COMCHECK M-200 BASEMENT MECHANICAL PLAN M-201 LEVEL 1 MECHANICAL PLAN M-202 ROOF MECHANICAL PLAN M-401 ENLARGED MECHANICAL SECTIONS M-501 MECHANICAL FLOW DIAGRAMS M-601 MECHANICAL DETAILS ELECTRICAL E-001 ELECTRICAL GENERAL INFORMATION E-002 ELECTRICAL SCHEDULES E-003 ELECTRICAL SPECIFICATIONS E-004 ELECTRICAL COMCHECK E-200 BASEMENT LIGHTING PLAN E-201 LEVEL 1 LIGHTING PLAN E-300 BASEMENT POWER PLAN E-301 LEVEL 1 POWER PLAN E-302 ROOF POWER PLAN E-501 ELECTRICAL ONE-LINE DIAGRAM E-502 PANEL SCHEDULES FIRE FA-001 FIRE ALARM GENERAL INFORMATION FA-002 FIRE ALARM SPECIFICATIONS FA-200 BASEMENT FIRE ALARM PLAN FA-201 LEVEL 1 FIRE ALARM PLAN FP-001 FIRE PROTECTION GENERAL INFORMATION FP-002 FIRE PROTECTION SPECIFICATIONS FP-200 BASEMENT FIRE PROTECTION PLAN FP-201 LEVEL 1 FIRE PROTECTION PLAN STL STEEL STOR STORAGE STRUC STRUCTURE or STRUCTURAL SYS SYSTEM T T TILE T&G TONGUE AND GROOVE TB TILE BASE TEL TELEPHONE TEMP TEMPORARY THK THICKNESS TO TOP OF TOW TOP OF WALL TP TOILET PARTITION TS TACK SURFACE TV TELEVISION TYP TYPICAL U UL UNDERWRITER'S LABORATORY UNO UNLESS NOTED OTHERWISE UOS UNLESS OTHERWISE SPECIFIED UP UPHOLSTERY UTIL UTILITY V VCT VINYL COMPOSITION TILE VERT VERTICAL VEST VESTIBULE VF VINYL FLOORING VIF VERIFY IN FIELD VOC VOLATILE ORGANIC COMPOUND VOL VOLUME W W WEST or WIDE FLANGE or WIDTH W/ WITH W/O WITHOUT WB WOOD BASE WC WALL COVERING WD WOOD WDW WINDOW WOM WALK OFF MAT WP WALL PROTECTION WSCT WAINSCOT WT WEIGHT or WINDOW TREATMENT WV WOOD VENEER X X EXTRUDED POLYSTYRENE PED PEDESTRIAN PERF PERFORATED PERIM PERIMETER PF PREFINISHED PL PLATE or PROPERTY LINE or PLASTIC LAMINATE PLAM PLASTIC LAMINATE PLYWD PLYWOOD PR PAIR or PROPOSAL REQUEST PREFAB PREFABRICATED PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT PAINT(ED) PV PHOTOVOLTAIC PVT PAVER TILE PWR POWER Q QA QUALITY ASSURANCE QTY QUANTITY R R RADIUS RB RESILIENT BASE RCP REFLECTED CEILING PLAN RD ROOF DRAIN or ROAD RE REFER TO or REFERENCE REBAR STEEL REINFORCING BARS REF REFRIGERATOR or REFRIGERATED REINF REINFORCED REQD REQUIRED REV REVISE, REVISED or REVISION RF RUBBER FLOORING RFI REQUEST FOR INFORMATION RFP REQUEST FOR PROPOSAL RH RIGHT HAND RHR RIGHT HAND REVERSE RM ROOM RO ROUGH OPENING ROW RIGHT-OF-WAY RSF RESILIENT SPORTS FLOORING RTU ROOFTOP UNIT S S SOUTH SAN SANITARY SC SEALED CONCRETE SCF STATIC CONTROL FLOORING SCHED SCHEDULE SDT STATIC DISSIPATIVE TILE SF SQUARE FOOT (FEET) or SPORTS FLOORING SIM SIMILAR SMACNA SHEET METAL and AIR CONDITIONING CONTRACTOR'S NATIONAL ASSOCIATION SPEC SPECIFICATION(S) SQ SQUARE SS SOLID SURFACING SST STAINLESS STEEL SSTB STAINLESS STEEL BASE ST STONE (REAL / ENGINEERED) STC SOUND TRANSMISSION CLASS STD STANDARD L L ANGLE LAB LABORATORY LAV LAVATORY LF LINEAR FEET / LINOLEUM FLOORING LH LEFT HAND LHR LEFT HAND REVERSE LIB LIBRARY LT LIGHT LVT LUXURY VINYL TILE M M MASONRY MATL MATERIAL MAX MAXIMUM MCM METAL COMPOSITE MATERIAL PANEL MECH MECHANICAL MEMB MEMBRANE MEP MECHANICAL, ELECTRICAL and PLUMBING MEZZ MEZZANINE MFR MANUFACTURER MH MANHOLE MIN MINIMUM MISC MISCELLANEOUS MO MASONRY OPENING MP METAL PANEL MTD MOUNTED MTL METAL N N NORTH NA NOT APPLICABLE NC NOISE CRITERIA NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION NFPA NATIONAL FIRE PROTECTION ASSOCIATION NIC NOT IN CONTRACT NO NUMBER NOM NOMINAL NR NON-RATED NRC NOISE REDUCTION COEFFICIENT NTS NOT TO SCALE O O2 OXYGEN OC ON-CENTER OD OVERFLOW DRAIN OFCI OWNER FURNISHED CONTRACTOR INSTALLED OFF OFFICE OFOI OWNER FURNISHED OWNER INSTALLED OH OVERHEAD DOOR OPH OPPOSITE HAND OPNG OPENING OPP OPPOSITE OSHA OCCUPATIONAL SAFETY and HEALTH ADMINISTRATION P PA PUBLIC ADDRESS PC POLISHED CONCRETE FE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINET FFE FURNITURE, FIXTURES AND EQUIPMENT FFL FINISHED FLOOR LINE FHC FIRE HOSE CABINET FHS FIRE HOSE STATION FL FLOOR LINE FLR FLOOR FO FACE OF FOF FACE OF FINISH FOS FACE OF STUD FR FIRE RATING, FIRE RESISTIVE, FIRE RESISTANT or FRAME FRP FIBERGLASS-REINFORCED PANEL FRT FIRE RETARDENT TREATED FS FLOOR SINK FT FEET or FOOT FURR FURRING G GA GAUGE or GYPSUM ASSOCIATION GALV GLAVANIZED GB GRAB BAR GC GENERAL CONTRACTOR GCMU GLAZED CONCRETE MASONRY UNIT(S) GL GLASS or GLAZING GLU-LAM GLUED-LAMINATED WOOD GMP GUARANTEED MAXIMUM PRICE GYM GYMNASIUM GYP GYPSUM H HB HOSE BIBB HC HANDICAP HDW HARDWARE HM HOLLOW METAL HORIZ HORIZONTAL HR HOUR HSS HOLLOW STRUCTURAL SECTION(S) HT HEIGHT HVAC HEATING, VENTILATION and AIR CONDITIONING HW HOT WATER I IBC INTERNATIONAL BUILDING CODE ID IDENTIFICATION IGU INSULATING GLASS UNIT IN INCH INFO INFORMATION INSUL INSULATED or INSULATION INT INTERIOR INV INVERT J JAN JANITOR JT JOINT K KD KNOCKED DOWN KITCH KITCHEN KPL KICK PLATE DEPT DEPARTMENT DF DRINKING FOUNTAIN DH DOUBLE-HUNG DIA DIAMETER DIAG DIAGONAL DIFF DIFFERENCE DIM DIMENSION or DIMENSIONAL DISP DISPENSER DIST DISTANCE DIV DIVIDE or DIVISION DN DOWN DOC DOCUMENT DPS DOOR POSITION SWITCH DR DRIVE DS DOWNSPOUT DT DRAIN TILE DTL DETAIL DW DISHWASHER DWG DRAWING DWR DRAWER E (E) EXISTING E EAST EA EACH EC EPOXY COUNTERTOP ED EDUCATION(AL) EF EXHAUST FAN or EPOXY FLOORING EIFS EXTERIOR INSULATION and FINISHING SYSTEM EJ EXPANSION JOINT EL ELEVATION ELEC ELECTRIC(AL) ELEV ELEVATOR EMER EMERGENCY ENCL ENCLOSURE ENGR ENGINEER EO EDGE OF EOS EDGE OF SLAB EPA ENVIRONMENTAL PROTECTION AGENCY EPDM ETHYLENE PROPYLENE DIENE MONOMER (roofing) EPS EXPANDED POLYSTYRENE (insulation board) EQ EQUAL EQUIP EQUIPMENT ESMT EASEMENT ETC ET CETERA (and so forth) EWC ELECTRIC WATER COOLER EXH EXHAUST EXP EXPAND, EXPANDED or EXPANSION EXPS EXPOSED STRUCTURE EXT EXTERIOR F FA FIRE ALARM FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL FAF FLUID APPLIED FLOORING FAR FLOOR AREA RATIO FD FLOOR DRAIN FDC FIRE DEPARTMENT CONNECTION FDN FOUNDATION C C CHANNEL CA ARCHITECTURAL CONCRETE CAB CABINET CATV COMMUNITY ANTENNA (cable) TELEVISION CB CORNER BEAD CBB CEMENTITIOUS BACKER BOARD CCD CONTRACT CHANGE DIRECTIVE CCTV CLOSED CIRCUIT TELEVISION CCW COUNTER-CLOCKWISE CD CONSTRUCTION DOCUMENTS or CONTRACT DOCUMENTS CEM CEMENT or CEMENTITIOUS CER CERAMIC CERT CERTIFY or CERTIFICATE CFCI CONTRACTOR FURNISHED CONTRACTOR INSTALLED CG CORNER GUARD CIP CAST-IN-PLACE (CONCRETE) CJ CONTROL JOINT - CONCRETE (CMU) CL CENTERLINE CLG CEILING CLO CLOSET CLR CLEAR CMU CONCRETE MASONRY UNIT CNTR COUNTERTOP CO CLEANOUT COAX COAXIAL CABLE COB CHANGE ORDER BULLETIN COL COLUMN COMM COMMUNICATION CONC CONCRETE CONF CONFERENCE CONN CONNECT(ION) CONST CONST CONSTRUCTION CONT CONTINUE, CONTINUOUS COORD COORDINATE CORR CORRIDOR CPPS CONCRETE PEDESTAL PAVER SYSTEM CPT CARPET CR CARD READER CRSI CONCRETE REINFORCING STEEL INSTITUTE CS STRUCTURAL CONCRETE CSI CONSTRUCTION SPECIFICATIONS INSTITUTE CSK COUNTERSINK or COUNTERSUNK CSMT CASEMENT CSS CLINICAL SERVICE SINK CSWK CASEWORK CT COUNT CTR CENTER CTRL CONTROL CU CUBIC CW CLOCKWISE D D DEPTH dB DECIBEL DBL DOUBLE DEG DEGREE(S) DEMO DEMOLISH or DEMOLITION A AA#(#) ADD ALTERNATE #(#) ACI AMERICAN CONCRETE INSTITUTE ACR ACRYLIC ACT ACOUSTICAL CEILING TILE AD AREA DRAIN ADA AMERICANS WITH DISABILITIES ACT ADD ADD or ADDENDUM ADJ ADJACENT, ADJUSTABLE or ADJOINING AESS ARCHITECTURAL EXPOSED STRUCTURAL STEEL AFF ABOVE FINISHED FLOOR AFS ACCESS FLOOR SYSTEM AGC ASSOCIATED GENERAL CONTRACTORS AHJ AUTHORITY HAVING JURISDICTION AHU AIR HANDLING UNIT AIA AMERICAN INSTITUTE of ARCHITECTS AISC AMERICAN INSTITUTE of STEEL CONSTRUCTION AL ALIGN ALT ALTERNATE ALUM ALUMINUM ANN ANNUNCIATOR ANOD ANODIZED ANSI AMERICAN NATIONAL STANDARDS INSTITUTE AP ACOUSTICAL PANEL APA AMERICAN PLYWOOD ASSOCIATION APPROX APPROXIMATE(LY) APT APARTMENT ARCH ARCHITECT or ARCHITECTURAL ASCE AMERICAN SOCIETY of CIVIL ENGINEERS ASHRAE AMERICAN SOCIETY of HEATING, REFRIGERATION and AIR CONDITIONING ENGINEERS ASI ARCHITECT'S SUPPLEMENTAL INSTRUCTIONS ASID AMERICAN SOCIETY of INTERIOR DESIGNERS ASME AMERICAN SOCIETY of MECHANICAL ENGINEERS ASSY ASSEMBLY ASTM AMERICAN SOCIETY for TESTING and MATERIALS ATM AUTOMATIC TELLER MACHINE ATTN ATTENTION AUTO AUTOMATIC AUX AUXILIARY AV AUDIO / VISUAL AWI ARCHITECTURAL WOODWORKING INSTITUTE AWPA AMERICAN WOOD PRESERVERS ASSOCATION B BD BOARD BIA BRICK INSTITUTE of AMERICA BITUM BITUMINOUS BKT BRACKET BLDG BUILDING BLKG BLOCKING BLVD BOULEVARD BO BOTTOM OF BOD BASIS OF DESIGN BPG BACK PAINTED GLASS BR BEDROOM BSMT BASEMENT BUR BUILT-UP ROOFING Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE FOR OF 3/ 1 1 / 2 0 2 1 4 : 1 9 : 5 1 P M G-000 COVER SHEET St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker Stanley Hotel Post Restaurant TI 333 E Wonderview Ave Estes Park, CO 80517 Owner CONTRUCTION DOCUMENTS 1/15/2021 PROJECT DIRECTORY Architect: MOA ARCHITECTURE 414 14th Street, Suite 300 Denver, CO 80202 303.308.1190 Brian M. Konczak bkonczak@moaarch.com Architect's Consultants: Owner: Structural Engineer:Mechanical / Electrical Engineer: S.A Miro Inc.BCER Grand Heritage Tenant: Big Red F Restaurant Group 4582 S. Ulster Street Pkwy, Suite 750 Denver, CO 80237 303.741.3737 John Karlberg jkarlberg@samiro.com 5420 Ward Rd. Suite 200 Arvada, CO 80002 303.422.7400 Paul Miskowicz pmiskowicz@bcer.com 6380 S. Fiddlers Green Circle, Suite 400 Greenwood Village, CO 80111 970.577.4080 John Cullen jcullen@grandheritage.com 5440 Conestoga Ct. Boulder, CO 80301 303.818.4784 Dave Query dave@bigredf.com REFERENCE SYMBOLS Elevation Numbers Sheet Number ELEVATION INDICATOR: Section Number Sheet Number PARTIAL SECTION: Section Number Sheet Number DETAIL INDICATOR: Section Number Sheet NumberBUILDING SECTION: Section Number Sheet Number SECTION DETAIL: DOOR OPENING:21 0 A SYSTEM NOTE: KEYNOTE INDICATOR: CENTERLINE: REVISION: ELEVATION MARK: DRAWING BLOCK: WINDOW / LOUVER TYPE: Sheet Number Elevation Number Single View Multiple View DRAWING BLOCK TITLE DRAWING SCALE2 CROSS REFERENCE 1 1 2 WALL PANEL TYPE: NORTH INDICATOR: P* LEVEL DESCRIPTOR ELEVATION HEIGHT ACCESSORY / EQUIPMENT INDICATOR: Section Number Sheet Number #L# _# # # 2 F=FLOOR, P=PARTITION W=WALL, C=CEILING, R=ROOF GRAPHIC SCALE: MATCHLINE:MATCHLINE RE: ITEM NO. / SHEET NO.TRUEMATERIAL/FINISH INDICATOR: Exterior Interior ALIGN: --- W D H CASEWORK TAG (AWI): --- A-# VICINITY MAPGENERAL PROJECT NOTES SHEET INDEXTERMS AND ABBREVIATIONS REVISION DATE ASI T03 03.05.21 ASI T03 F. E . C . F.E. 41 SF FREEZER 006 OLF:300 OCC:1 102 SF COOLER 005 OLF:300 OCC:1 49 SF BEER COOLER 003 OLF:300 OCC:1 657 SF TI STORAGE 010 OLF:200 OCC:4 43 SF OFFICE 001 OLF:200 OCC:1 2' - 11 7/8" TRAVEL DISTANCE = 120' (D I S T A N C E B E T W E E N E X I T S )3 9 '-1 1 " CLR 5' - 1 1/2" F.E.C. PLATFORM B02B LOUNGE B02 B.O.H. B02A MEN'S RESTROOM B04 WOMEN'S RESTROOM B05 MECH ROOM B06 BOH HALL B01B ELECTRICAL B07 MECH CONDENSER ROOM B07ALOBBY B01 PA T H A OCC. 48 OCC. 98 OCC. 10 OCC. 1 SHOP/BAR B03 OCC. 1 OCC. 1 OCC. 1 OCC. 1 539 SF PRIVATE DINING 113 OLF:15 OCC:36 104 SF COOLER 112 OLF:300 OCC:1 198 SF DISH 111 OLF:200 OCC:1 706 SF KITCHEN BOH 109 OLF:200 OCC:4 148 SF STORAGE 105 OLF:300 OCC:1 424 SF BAR BOH 108 OLF:200 OCC:3 59 SF ENTRY 101 OLF:15 OCC:4 23 SF LIQ. STORAGE 106 OLF:300 OCC:1 1166 SF PATIO 117 OLF:15 OCC:78 268 SF DINING 115 OLF:15 OCC:18 77 SF RETAIL 102 OLF:60 OCC:2 477 SF PRIVATE PATIO 114 OLF:15 OCC:32 268 SF BAR 107 OLF:5 OCC:54 5' - 9 1/4" 3' - 6" 4' - 1 1 7 / 8 " 5' - 0" 5' - 9 3/8" 5' - 1 0 7 / 8 " 5' - 1 0 7 / 8 " 96 SF BOOTHS 116 OLF:15 OCC:16 124 SF BOOTHS 118 OCC:20 384 SF DINING 102 OLF:15 OCC:26 89 SF CIRCULATION 116 OLF:0 OCC:0 (8 ) B E N C H S E A T I N G 5' - 0 " (8 ) B E N C H S E A T I N G 4' - 0 " 40 LFT 32 LFT OLF: 1 PER 24" OLF: 1 PER 24"3 4 '-0 " (O N E -T H I R D O F E X I T D I S T A N C E , S P R I N K L E R E D ) 1 0 2 '-0 " (D I S T A N C E B E T W E E N E X I T S ) 5 1 '-8 " TRAVEL DISTANCE = 120'< Maximum = 250' PATH CONTINUES FROM LEVEL BELOW O.H. COILING GRILLE F.E.C F.E.C OCC: 65 FROM BASEMENT 559 SF FLEX 120 OLF:15 OCC:38 ASI T01 ASI T01 ASI T01 ASI T01 ASI T01 13 ' - 4 " 54 SF BENCH SEATING 121 OCC:18 13' - 7 1/2" OLF: 1 PER 18" ASI T02 ASI T02 CODE REVIEW 2015 ICC JURISDICTION CODES Town of Estes Park, Larimer County, CO 5,130 GSF1ST FLOOR 5,130 GSFBASEMENT FLOOR 10,260 GSFTOTAL GROSS FLOOR AREA 1NO OF STORIES CODE CITATION OCCUPANCY CLASSIFICATION A-2 SECTIONS 303.2 & 303.3 OCCUPANCY SEPARATION NOT REQUIRED (NON-SEPARATED OCCUPANCIES)SECTION 508.3 CONSTRUCTION V-B SECTION 602, TABLE 601, TABLES 504.3, 504.4, 506.2 ALLOWABLE AREA MIXED-OCCUPANCY, ONE STORY BUILDING TABLE 506.2.2 ALLOWABLE HEIGHT INCREASES TOTAL 40' / 1 STORIES 20' / 1 STORY (FULLY SPRINKLERED) 60' / 2 STORIES TABLE 503 SECTION 504.2 REQUIRED PER GENDER SECTION 2902.2 PLUMBING FIXTURES SEPARATE FACILITIES IBC TABLE 2902.1/ IPC SECTION 403FIXTURE COUNTS OCC. LOAD REQUIRED GENDER SPLIT (50/50) TOILETS URINALS LAVS DF OTHER 500 OCC.260 WOMEN 4 -2 SEE BELOW 1 260 MEN DRINKING FOUNTAINS SERVICE SINKS 4 50% MAX 2 OCC. LOAD (B) PROVIDED GENDER SPLIT (50/50) TOILETS URINALS LAVS DF OTHER WOMEN 4 - 2 SEE BELOW 1 MEN DRINKING FOUNTAINS SERVICE SINKS 2 2* 2 S1 FIRE SPRINKLER CLASSIFICATION TABLES 504.4 AND 506.2 FIRE PROTECTION CHAPTER 9 FIRE SPRINKLERING STANDPIPES THROUGHOUT NOT REQUIRED (HIGHEST FLOOR ≤ 30’) SECTION 903 SECTIONS 905.3.1 THROUGH 905.3.8 CLASS ABC EXTINGUISHERS PROVIDED THROUGHOUT PROVIDED THROUGHOUTFIRE ALARM FIRE EXINGUISHERS TABLE 906.3(1) & 906.3(2) SECTION 907 TABLE 1004.1.2 2 REQUIRED 0.2 x 229 OCC. 2 REQUIRED 0.2 X 166 OCC 0.3 X 166 OCC 1/3 DIAGONAL DISTANCE OF AREA SERVED (FULLY SPRINKLERED) 250 FT MAX. (FULLY SPRINKLERED) TABLE 1006.3.1 & TABLE 1006.3.2 SECTION 1005.3.2, EXCEPTION 1 TABLE 1006.3.1 & TABLE 1006.3.2 SECTION 1005.3.2, EXCEPTION 1 SECTION 1005.3.1, EXCEPTION 1 TABLE 1017.2 NUMBER OF EXITS FROM STORIES: GROUND FLOOR NUMBER OF EXITS CLEAR EGRESS WIDTH BASEMENT NUMBER OF EXITS CLEAR EGRESS WIDTH STAIR WIDTH SEPARATION OF EXITS EXIT ACCESS TRAVEL DIST TABLE 1006.2.1 & TABLE 1006.3.2COMMON PATH OF EGRESS TRAVEL = 45.8" MINIMUM = 33.2" MINIMUM = 49.8" MINIMUM SETION 202 EXITS NUMBER OF EXITS FROM SPACES: ALL SPACES REQUIRE ONLY ONE EXIT WITH THE EXCEPTION OF THE FOLLOWING:TABLE 1006.2.1 SECTION 1006.2.1 SECTION 1006.2.1 LOUNGE B02: 2 EXITS DINING: 2 EXITS 75 FT MAX. (FULLY SPRINKLERED) 2015 International Building Code 2015 International Mechanical Code 2015 International Plumbing Code 2020 National Electrical Code 2015 International Energy Conservation Code 2015 International Fire Code 2015 International Existing Building Code 2009 ICC/ANSI A117.1 Accessibility Standard Americans with Disabilities Act (ADA) ALLOWABLE AREA A-2 (MOST RESTRICTIVE) TYPE V-B, S-1 = 24,000SQFT Restaurant Seating: 232 Restaurant BOH: 8 Storage: 4 244 persons Outdoor Seating: 110 110 persons Auditorium, Stage, and Basement B.O.H., Mechanical, a per Core and Shell documents: 166 Occupants TOTAL OCCUPANTS:520 OCCUPANTS OCCUPANT LOAD *Urinal Substitution allowed per International Pluumbing Code, Section 419.2 5,756 s.f. - Main Level 894 s.f. - Basement 6,650 s.f. - TOTAL TENANT AREA TENANT FLOOR AREA SECTION 410.4 DRINKING FOUNTAIN WHERE RESTAURANTS PROVIDE DRINKING WATER IN A CONTAINER FREE OF CHARGE, DRINKING FOUNTAINS SHALL NOT BE REQUIRED IN THOSE RESTAURANTS. 2015 IPC ASI T01 ASI T01 ASI T01 ASI T02 ASI T02 MEANS OF EGRESS -COMMON PATH EXIT DISCHARGE MEANS OF EGRESS -TRAVEL DISTANCEPATH A PATH B LIFE SAFETY LEGEND FIRE BARRIERS CLASSIFICATION FIRE- RESISTANCE- RATING (HRS) OPENING PROTECTION APPLICATION 1 SM O K E RE S I S T A N T NO FIRE DAMPERS FIRE DOORS FIRE SHUTTERS FIRE GLAZING FIRESTOPPING FIRE AREA SEPARATION PROTECTION OF MEANS OF EGRESS HAZARDOUS AREA ENCLOSURE SHAFT ENCLOSURE SYMBOL CONCEPTUAL DIAGRAM BENCH SEATING BOH STORAGE DINING BAR SEATING RETAIL NOT IN SCOPE 0' - 0 5/8" RE: TAG VARIES 0' - 0 5/8" GYPSUM BOARD, RE: SPECS FOR TYPE09 2116.09 ACOUSTIC SEALANT09 2116.42 METAL STUD FRAMING (NLB)09 2116.01 ACOUSTIC INSULATION09 2116.41 HEAD PLAN BASE 09 2116.42 ACOUSTIC SEALANT GYPSUM BOARD, RE: SPECS FOR TYPE09 2116.09 09 2116.01 METAL STUD FRAMING (NLB) 09 2116.01 METAL STUD FRAMING (NLB) INTERIOR PARTITIONS SCALE: 1 1/2" = 1'-0" FIRE RATING ASSEMBLY: STC RATING: P3 INTERIOR - METAL STUD PARTITION (NR) NON-RATED 45-49 NRCC 816-NV 2-3-81P6 NOTE: APPLIES ONLY WHERE NOTED NOTE: APPLIES ONLY WHERE NOTED NOTE: APPLIES ONLY WHERE NOTED RE: TAG VARIES 0' - 0 5/8" ACOUSTIC SEALANT09 2116.42 ACOUSTIC SEALANT09 2116.42 METAL STUD FRAMING (NLB)09 2116.01 ACOUSTIC INSULATION09 2116.41 HEAD PLAN BASE 09 2116.01 METAL STUD FRAMING (NLB) METAL STUD FRAMING (NLB)09 2116.01 09 2116.01 METAL STUD FRAMING (NLB) SCALE: 1 1/2" = 1'-0" FIRE RATING ASSEMBLY: FR1.5 INTERIOR - METAL STUD FURRED WALL (NR) NON-RATED FR3 FR6 CEILING TYPES 09 5100 ACOUSTICAL CEILINGS SCALE: 1 1/2" = 1'-0"C1 24"X48" ACOUSTICAL CEILING SYSTEM (NR) SCALE: 1 1/2" = 1'-0"G1 GYPSUM BOARD CEILING SYSTEM FIRE RATING ASSEMBLY 1 HR ARMSTRONG -KITCHEN ZONE, 2'X4' VINYL-COVERED GYPSUM PANELS ASI T01 WALL TAG SYSTEM ASSEMBLIES IDENTIFIERS: WALLS / PARTITIONS *FIRE RATING STUD FRAMING - NON-STRUCT. PARTITION [P] FURRING [FR] WALL CORE SIZE [NOMINAL] 1 = 7/8", 1", 1-1/2", 1-7/8" 3 = 3-1/2", 3-5/8" 2 = 2", 2-1/2", 2-7/8" P31 6 = 6" INTERIOR WALL TYPE CATEGORY . WALL TAG LEGEND 6A CXX.Xx XX.Xx BCXX.Xx BDXX.Xx DT LXX.Xx MASONRY/GYPSUM TO 6" ABOVE CLG TYPICAL CONDITION: UNIQUE CONDITION: SEE DETAIL FOR TOP OF WALL INFO MASONRY/GYPSUM TO BOTTOM OF ROOF OR FLOOR DECK MASONRY/GYPSUM TO BOTTOM OF CEILING OR TRUSS <<<<PICK ONE OF THE CONDITIONS BELOW, THEN DELETE FROM LEGEND AND PURGE OUT OF THE PROJECT>>>> ASI T01 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 2 5 / 2 0 2 1 8 : 3 3 : 5 9 A M G-001 CODE ANALYSIS & SYSTEM ASSEMBLIES St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker 1/8" = 1'-0"G-001 1 BASEMENT LEVEL - CODE PLAN 1/8" = 1'-0"G-001 2 LEVEL 1 - CODE PLAN REVISION DATE ASI T01 02.09.21 ASI T02 02.24.21 MM CM WFVS OS OS J J J J J J J J J J J J J J L-1 MSB-1 UR-1 UR-2 WC-1 WC-1 WC-1WC-1 WC-2 WC-2 DET-1 TMV-1 TMV-1 MAU-1MAU-1 DCP-1 SA-4 L-1 TMV-1 TMV-1 MAU-1 T 1 2 3 4 LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 ELEV. B10 COOLER 005 FREEZER 006 AREA WELL AREA WELL MECH. CHASE ABOVE OFFICE 001 AB B C DE WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 FS FS 00 6 004 001 EX EX EX EX EX EX EX EX EX EX 7' - 7 1/2" 6' - 8 1 / 2 " 15 ' - 2 " 7' - 5 " 2' - 6 " 6' - 1 1 1 / 2 " 5' - 0 1/2"2' - 5" 87'-0" T.O. FINISH FLOOR (ABC) JANITOR B01A B.O.H. B02A PLATFORM B02B LOBBY B01 08 A 01B EXTENT OF WORK 005 003 1' - 9" 2' - 0 " MAINTAIN 1- HOUR RATING AT EXISTING WALL B T.O. SLAB 87' - 0" TI STORAGE 010 6AC FR 1 . 5 6AC FR 3 6AC P3 6A CP3 6A CP3 BD P3 . 1 AIR GAP 2" MIN ALIGN NEW FRAMING TO ALLOW FOR BLOCK OUT CONSTRUCTION 5' - 4 1/4" 8' - 1 " 5' - 1 0 5 / 8 " 7' - 1 1/2" BD P3 AL 102 102 102 103 105 105 105 NOT IN SCOPE ASI T01 ASI T01 ASI T01 ASI T01 ASI T01 6A CFR1.5 LOUNGE B02 1. EXTERIOR BUILDING DIMENSIONS ARE TO GRID CENTERLINE, EXTERIOR FACE OF SHEATHING/OUTSIDE FACE OF FOUNDATION. 2. INTERIOR BUILDING DIMENSIONS ARE TO GRID CENTERLINE AND FACE OF STUD FRAMING AT NEW CONSTRUCTION AND FACE OF WALL AT EXISTING CONSTRUCTION. 3. PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT, CASEWORK AND ACCESSORIES. NO EXCEPTIONS. 4. ALL INTERIOR FRAMED WALL ASSEMBLIES TO BE TYPE [ X ], UNO. 5. ALL INTERIOR MASONRY WALL ASSEMBLIES TO BE TYPE [ X ], UNO. 6. ISOLATE PERIMETER OF NON-BEARING WALL BOARD PARTITIONS ON SLAB ON GRADE AT INTERSECTIONS WITH EXTERIOR WALL AND/OR BEARING WALLS – PROVIDE ¼”SPACE VERTICAL SLIP JOINT TRIM EDGES WITH L-TYPE EDGE TRIM AND SEAL WITH ACOUSTIC SEALANT. 7. LOCATE TYPICAL HINGE SIDE DOOR JAMB 4”FROM FINISH WALL TO EDGE OF DOOR OPENING. MAINTAIN A MINIMUM FINISHED CLEARANCE OF 18”TO THE STRIKE SIDE JAMB ON THE PULL SIDE OF ALL PUBLIC ACCESSIBLE DOORS. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION STOREFRONTS, CURTAINWALLS, WINDOWS, AND LOUVERS (PREFIXED WITH 'L') DOOR OPENING / BORROWED LIGHT SYSTEM ASSEMBLY TYPE: FLOORS, WALLS, CEILINGS, AND ROOFS FLOOR PLAN: TAG IDENTIFIERS 20 0 A 1 1 1 EQUIPMENT / ACCESSORY / MATERIAL INDENTIFIER (ALSO ON INTERIOR ELEVATIONS) 1/4" = 1'-0" BASEMENT LEVEL - OVERALL FLOOR PLAN1 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 1 1 P M A-090 BASEMENT LEVEL- OVERALL FLOOR PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker SHEET KEYNOTES NUMBERING IS GROUPED BY TYPE/PHASE OF WORKSHEET OF NON-ARCHITECTURAL ITEMS OR INFORMATIONAL/INSTRCUTIONAL NOTATION SOME NUMBERS MAY BE SKIPPED ON ANY GIVEN DRAWING SHEET 102 PREFABRICATED COOLER WALL BY MANUFACTURER. G.C. TO COORDINATE CLOSURE PANELS, ADJACENT WALLS AND SEALANT AT FLOOR PERIMETER. 103 1/2" CEMENT BOARD TO 4'-0" BEHIND DISHWASHER AND MOP SINK W/ 1/2" PLYWOOD FOR REMAINING HEIGHT OF WALLS. 104 CEMENT BOARD FROM FLOOR TO CEILING BEHIND HOODS. EXTEND MIN 18" PAST HOODS ON EACH SIDE. PROVIDE CONTINUOUS SHEET METAL BLOCKING. MAINTAIN 18" MIN. CLEARANCE FROM HOOD AND ANY COMBUSTIBLE MATERIALS PER IMC 507.2.6. 105 SUBSTITUTE GYP. BD W/ 12" OF CEMENT BOARD AND 1/2" PLYWOOD FOR REMAINING HEIGHT OF WALLS. 106 INTERIOR PARTITON FROM FLOOR TO BOTTOM OF ROOF ASSEMBLY ASI T01 ASI T01 ASI T01 ASI T01 REVISION DATE ASI T01 02.09.21 FA C P GM A P P JJ 1 2 3 4 AB B C DE 4 B PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 101 LIQ. STORAGE 106 PRIVATE PATIO 114 PATIO 117 DINING 115 3 SIDED FIREPLACE WAIT BENCH P.O.S. 2 RETAIL 102 P. O . S 1 AIR GAP 2" M I N . 10' - 0"9' - 6"6' - 11 1/2"8' - 7 1/2" 8' - 3 1/2" 7' - 2 1/2" 1' - 1" 13' - 5" 104'-0" T.O. LOW WALL 100'-6" T.O. BOOTH PLATFORM A 101'-0" T.O. BOOTH PLATFORM B 104'-0" T.O. LOW WALL 104'-0" T.O. LOW WALL 104'-6" T.O. LOW WALL 8' - 2" 9' - 7 1/2"19' - 9" 4' - 0 " 10 ' - 8 1 / 2 " 11 ' - 1 1 / 2 " AL I G N 24' - 5 1/2"2' - 6"4' - 6"1' - 9"24' - 5" 12 ' - 3 " 100'-0" T.O. FINISH FLOOR 10 ' - 3 1 / 2 " 41 ' - 1 1 / 2 " 7' - 0 " 34' - 7 1/2" 8' - 0"96' - 1 1/2" FR3 FR3 (ABC) (K) 112 4' - 1 " 13 ' - 4 " 8' - 8 1 / 2 " 7' - 8 " 5' - 0 " RAILING 11 3 A 103'-6" T.O. LOW WALL EXISTING STAIR DOWN AREA WELL AND CONCRETE WALL AS PART OF CORE AND SHELL BY OTHERS EXISTING STAIR DOWN AL I G N 1' - 9" CEMENT BOARD SHEATHING PER PARTITION NOTE 2 AT MOP SINK PLANTERS BY OWNER PLANTERS BY OWNER A-451 2 A-451 3 A-453 2 A-454 1 A-454 2 A-454 3 MECHANICAL SHAFT6AC P3 6AC P3 6AC P3 6A CP3 BD P3 BDP3 BDP6 BD P6 P3 103 102 103 104 105 106 106 106 6AC P3 MAIN ENTRY 100 FLEX 120 ASI T01 ASI T01 4' - 3 1 / 2 " 4' - 0 1 / 2 " ASI T01 106 106 ADA FLIP UP COUNTER 2' - 2 " ASI T01 A-601 7 104 BD P3 ASI T01 ASI T01 ASI T01 ASI T01 ASI T01 2' - 7 " 3' - 8 1 / 2 " 4' - 4 1 / 2 " 1' - 0 1/4" 3' - 5 1 5 / 1 6 " BD FR 3 BDFR3 BDP3 0' - 6 1/8"0' - 6 1/8" W1 110 10 ' - 8 " 1' - 4" 13' - 8 1/2"29' - 0 3/4"8' - 5 1/2" ASI T03 111 1. EXTERIOR BUILDING DIMENSIONS ARE TO GRID CENTERLINE, EXTERIOR FACE OF SHEATHING/OUTSIDE FACE OF FOUNDATION. 2. INTERIOR BUILDING DIMENSIONS ARE TO GRID CENTERLINE AND FACE OF STUD FRAMING AT NEW CONSTRUCTION AND FACE OF WALL AT EXISTING CONSTRUCTION. 3. PROVIDE BLOCKING FOR ALL WALL MOUNTED EQUIPMENT, CASEWORK AND ACCESSORIES. NO EXCEPTIONS. 4. ALL INTERIOR FRAMED WALL ASSEMBLIES TO BE TYPE [ X ], UNO. 5. ALL INTERIOR MASONRY WALL ASSEMBLIES TO BE TYPE [ X ], UNO. 6. ISOLATE PERIMETER OF NON-BEARING WALL BOARD PARTITIONS ON SLAB ON GRADE AT INTERSECTIONS WITH EXTERIOR WALL AND/OR BEARING WALLS – PROVIDE ¼”SPACE VERTICAL SLIP JOINT TRIM EDGES WITH L-TYPE EDGE TRIM AND SEAL WITH ACOUSTIC SEALANT. 7. LOCATE TYPICAL HINGE SIDE DOOR JAMB 4”FROM FINISH WALL TO EDGE OF DOOR OPENING. MAINTAIN A MINIMUM FINISHED CLEARANCE OF 18”TO THE STRIKE SIDE JAMB ON THE PULL SIDE OF ALL PUBLIC ACCESSIBLE DOORS. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION STOREFRONTS, CURTAINWALLS, WINDOWS, AND LOUVERS (PREFIXED WITH 'L') DOOR OPENING / BORROWED LIGHT SYSTEM ASSEMBLY TYPE: FLOORS, WALLS, CEILINGS, AND ROOFS FLOOR PLAN: TAG IDENTIFIERS 20 0 A 1 1 1 EQUIPMENT / ACCESSORY / MATERIAL INDENTIFIER (ALSO ON INTERIOR ELEVATIONS) NORTH PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 4 / 2 0 2 1 8 : 3 8 : 5 6 A M A-100 LEVEL 1 -OVERALL FLOOR PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker 1/4" = 1'-0" LEVEL 1 - OVERALL FLOOR PLAN1 SHEET KEYNOTES NUMBERING IS GROUPED BY TYPE/PHASE OF WORKSHEET OF NON-ARCHITECTURAL ITEMS OR INFORMATIONAL/INSTRCUTIONAL NOTATION SOME NUMBERS MAY BE SKIPPED ON ANY GIVEN DRAWING SHEET 102 PREFABRICATED COOLER WALL BY MANUFACTURER. G.C. TO COORDINATE CLOSURE PANELS, ADJACENT WALLS AND SEALANT AT FLOOR PERIMETER. 103 1/2" CEMENT BOARD TO 4'-0" BEHIND DISHWASHER AND MOP SINK W/ 1/2" PLYWOOD FOR REMAINING HEIGHT OF WALLS. 104 1/2" MIN CEMENTITIOUS BOARD FROM FLOOR TO CEILING BEHIND HOODS. EXTEND MIN 18" PAST HOODS IN ALL DIRECTIONS. PROVIDE CONTINUOUS SHEET METAL BLOCKING. MAINTAIN 18" MIN. CLEARANCE FROM HOOD AND ANY COMBUSTIBLE MATERIALS PER IMC 507.2.6 SEE FINISH PLANS FOR EXTENT OF STAINLESS STEEL FINISH MATERIAL WHICH IS TO BE INSTALLED BETWEEN THE HOOD AND THE GYPSUM BOARD OR CEMENTITOUS WALLBOARD OVER AN AREA EXTENDING NOT LESS THEN 18 INCHES IN ALL DIRECTIONS OF HOOD. 105 SUBSTITUTE GYP. BD W/ 12" OF CEMENT BOARD AND 1/2" PLYWOOD FOR REMAINING HEIGHT OF WALLS. 106 INTERIOR PARTITON FROM FLOOR TO BOTTOM OF ROOF ASSEMBLY 111 WALL MOUNTED LADDER WITH LADDER GUARD ASI T01 ASI T01 ASI T01 ASI T01 ASI T01 ASI T01 ASI T02 ASI T03 ASI T04 ASI T04 REVISION DATE ASI T01 02.09.21 ASI T02 02.24.21 ASI T03 03.05.21 ASI T04 03.17.21 CO OS OS OS OS OS OS OS OS J J J J J J 1 1 2 2 3 3 4 4 A A B B C C D D E E A1 A1 A1 A1 A1A1A1A1 A1 A1 A1 MFR MFR MFR LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 ELEV. B10 COOLER 005 FREEZER 006 OFFICE 001 WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A PLATFORM B02B LOBBY B01 111'-8" B.O. EXIST. 2x2 ACT CEILING EX EX EX EX EX EXEXEXEXEX EX EX EX EX EX EXEXEXEXEX EX EX EX TYP. U1 4 B 9'-0" C1 6'-8" G1 8'-0" C1 9'-0" C1 A1A1 6'-8" C3 LOUNGE B02 ASI T01 RECESSED LINEAR LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE LUMINAIRE LIGHT FIXTURE CEILING SYMBOLS LEGEND EMERGENCY LINEAR LUMINAIRE LIGHT FIXTURE REFER TO ENGINEERING MECHANICAL, ELECTRICAL, & FIRE PROTECTION DRAWINGS FOR ADDITIONAL INFORMATION RECESSED DOWNLIGHT LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE STRIP OR INDUSTRIAL LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE LINEAR LUMINAIRE LIGHT FIXTURE MECHANICAL -SUPPLY DIFFUSER SURFACE DIRECTIONAL LIGHT LUMINAIRE MECHANICAL -RETURN GRILLE RECESSED WALL WASHER LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE STRIP OR INDUSTRIAL EMERGENCY LUMINAIRE LIGHT FIXTURE RECESSED DOWNLIGHT EMERGENCY LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE EMERGENCY LUMINAIRE LIGHT FIXTURE PARTIAL EMERGENCY LINEAR LUMINAIRE LIGHT FIXTURE MECHANICAL -EXHAUST AIR 1. THIS PLAN SHOWS LOCATIONS OF ITEMS IN ARCHITECTURALLY SIGNIFICANT SPACES ONLY. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL PLANS FOR ALL ITEMS NOT SHOWN. 2. CENTER SUSPENDED ACOUSTICAL CEILING GRID BOTH DIRECTIONS IN ROOMS, UNLESS SHOWN OTHERWISE. 3. CENTER ALL CEILING MOUNTED ITEMS LOCATED IN ACOUSTICAL PANELS, GYPSUM BOARD SOFFITS, AND BETWEEN OTHER CEILING MOUNTED FIXTURES, UNO. SPEAKERS, SMOKE DETECTORS AND HEAT DETECTORS MAY BE CENTERED AT ¼ POINT ON ACOUSTICAL PANELS. 4. ALL CEILING ELEVATION REFERENCES ARE RELATIVE TO FINISHED FLOOR SLAB BELOW. 5. COORDINATE LIGHTING LAYOUTS IN UTILITY/STORAGE/ELECTRICAL/IDF/MDF ROOMS WITH OVERHEAD PIPING, DUCTS, AND OTHER CEILING SUSPENDED EQUIPMENT. 6. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR DEVICES AND REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT PLACEMENT OF DEVICES WITHIN CEILING GRIDS. 7. REFER TO ELECTRICAL DRAWINGS FOR LIGHT FIXTURE SCHEDULE. 8. CEILING TO REMAIN OPEN TO UNFINISHED STRUCTURE ABOVE, UNLESS NOTED OTHERWISE. PAINT ALL EXPOSED DUCTS, PIPING AND CONDUITS BLACK UNLESS PROHIBITED BY CODE. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION ASI T01 1/4" = 1'-0" BASEMENT LEVEL - REFLECTED CEILING PLAN1 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 2 0 P M A-110 BASEMENT LEVEL - REFLECTED CEILING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker REVISION DATE ASI T01 02.09.21 M VFD M VFD M TOMTOM 1 1 2 2 3 3 4 PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 101 LIQ. STORAGE 106 PRIVATE PATIO 114 PATIO 117 DINING 115 RETAIL 102 AB B C DE MFR OPEN TO EXISITING B.O. STRUCTURE AT 11'-6" S1 S1 S1 S1 S1 P2 P2 S1 S1 P1 P1 P1 P1 P1 P1 P1 P1 P1 P5 P1 P1 P1 P1 P1 P1 P4 P1 P1P3 P3 T1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 C1 C1 C1 C1 C1C1C1C1 109'-0" B.O. ASPEN LOG CLOUD T1 T1 C1 C1 C1 C1 C1 C1 107'-0" B.O. HEADER P2 P2 EX EX EX EX COILING OVERHEAD DOOR SHROUD T1 T1 BULKHEAD SIGNAGE UNDER SEPARATE PERMIT SIGNAGE UNDER SEPARATE PERMIT P6 P6 P6 P6 P6 P6 P6 P6 P6 111'-0" B.O. TRACK P5 P5 P5 P5 106'-0" B.O. PENDANTS 111'-0" B.O. TRACK 106'-6" B.O. PENDANTS 111'-0" B.O. TRACK 109'-0" B.O. LOG LIGHTS 106'-6" B.O. PENDANTS S1 111'-0" B.O. TRACK 106'-0" B.O. LIGHTS S2 S2 S4s S2 4 B 8'-6" C1 8'-6" C1 5' - 0" ASI T01 TECTUM ACOUSTIC PANELS ATTACHED TO UNDERSIDE OF ROOF, BETWEEN TRUSSES; PANELS TO BE PAINTED BLACK RECESSED LINEAR LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE LUMINAIRE LIGHT FIXTURE CEILING SYMBOLS LEGEND EMERGENCY LINEAR LUMINAIRE LIGHT FIXTURE REFER TO ENGINEERING MECHANICAL, ELECTRICAL, & FIRE PROTECTION DRAWINGS FOR ADDITIONAL INFORMATION RECESSED DOWNLIGHT LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE STRIP OR INDUSTRIAL LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE LINEAR LUMINAIRE LIGHT FIXTURE MECHANICAL -SUPPLY DIFFUSER SURFACE DIRECTIONAL LIGHT LUMINAIRE MECHANICAL -RETURN GRILLE RECESSED WALL WASHER LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE STRIP OR INDUSTRIAL EMERGENCY LUMINAIRE LIGHT FIXTURE RECESSED DOWNLIGHT EMERGENCY LUMINAIRE LIGHT FIXTURE PENDANT OR SURFACE EMERGENCY LUMINAIRE LIGHT FIXTURE PARTIAL EMERGENCY LINEAR LUMINAIRE LIGHT FIXTURE MECHANICAL -EXHAUST AIR 1. THIS PLAN SHOWS LOCATIONS OF ITEMS IN ARCHITECTURALLY SIGNIFICANT SPACES ONLY. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL PLANS FOR ALL ITEMS NOT SHOWN. 2. CENTER SUSPENDED ACOUSTICAL CEILING GRID BOTH DIRECTIONS IN ROOMS, UNLESS SHOWN OTHERWISE. 3. CENTER ALL CEILING MOUNTED ITEMS LOCATED IN ACOUSTICAL PANELS, GYPSUM BOARD SOFFITS, AND BETWEEN OTHER CEILING MOUNTED FIXTURES, UNO. SPEAKERS, SMOKE DETECTORS AND HEAT DETECTORS MAY BE CENTERED AT ¼ POINT ON ACOUSTICAL PANELS. 4. ALL CEILING ELEVATION REFERENCES ARE RELATIVE TO FINISHED FLOOR SLAB BELOW. 5. COORDINATE LIGHTING LAYOUTS IN UTILITY/STORAGE/ELECTRICAL/IDF/MDF ROOMS WITH OVERHEAD PIPING, DUCTS, AND OTHER CEILING SUSPENDED EQUIPMENT. 6. REFER TO PLUMBING, MECHANICAL AND ELECTRICAL DRAWINGS FOR DEVICES AND REFER TO ARCHITECTURAL DRAWINGS FOR THE EXACT PLACEMENT OF DEVICES WITHIN CEILING GRIDS. 7. REFER TO ELECTRICAL DRAWINGS FOR LIGHT FIXTURE SCHEDULE. 8. CEILING TO REMAIN OPEN TO UNFINISHED STRUCTURE ABOVE, UNLESS NOTED OTHERWISE. PAINT ALL EXPOSED DUCTS, PIPING AND CONDUITS BLACK UNLESS PROHIBITED BY CODE. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION ASI T01 1/4" = 1'-0" LEVEL 1 - REFLECTED CEILING PLAN1 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 2 3 P M A-120 LEVEL 1 -REFLECTED CEILING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker ASI T01 REVISION DATE ASI T01 02.09.21 FI RST FLOOR J M M SS-1 MT-1 WD-1 MT -3 WD-1 MT-1 SS-1 MT-1 WD-1 MT-1 MT-1 2 BCD 6 A-501 A-452 1 2 A-452 5 3 64 1 A-501 2 A-501 3 A-501 24' - 1 1/4"2' - 0" 2' - 0" 19' - 2 5/8"8' - 3" 26' - 1 3/8" 4 A-501 A-452 7 R 1 ' - 0 "R 1 ' - 0 " 0' - 11" 0' - 11" 3' - 2" 2' - 6" 2' - 6" EXTENT OF BAR EQUIPMENT 2' - 10" ELECTRICAL PANELS RE: ELECTRICAL ADD UNDER COUTNER PURSE HOOKS AT 36" +/- A-4528 BEER TAP RE: FOOD SERVICE BEER TAP RE: FOOD SERVICE 7 A-501 8 A-501 5 A-501 ADA FLIP UP COUNTER ASI T01 ASI T01 2 BCD 6 A-501 A-452 1 2 A-452 5 3 64 1 A-501 2 A-501 3 A-501 19' - 2"7' - 9" 25' - 2 5/8" 7' - 0" 4' - 0" 2' - 6 11/16" 4 A-501 A-452 7 P6 P6 LIQ. STORAGE 106 BAR BOH 108 8' - 2" 4' - 11 1/4" 2' - 4" 1' - 4" 2' - 10 1/8" 0' - 10" TYP. 4' - 0" EXTENT OF COUNTER ABOVE A-4528 9' - 0"4' - 0"2' - 0" FILLER 2 1/2" 2' - 0" 2' - 0" 4' - 0" 5' - 0" 3 1/2" 1' - 5 1/2"5' - 0"2' - 0"2' - 0"2' - 0" BACK BAR CABINET, REFRIGERATED RE: FOOD SERVICE EXTENT OF COUNTER ABOVE BACK BAR CABINET, REFRIGERATED RE: FOOD SERVICE BA C K B A R C A B I N E T , RE F R I G E R A T E D RE : F O O D S E R V I C E 4' - 11 1/2" FLOOR SINK RE: PLUMBING FLOOR SINK RE: PLUMBING LI F T -UP A D A C O U N T E R 7 A-501 8 A-501 19' - 10" 3' - 7 1/2" 3' - 2" ASI T01 ASI T01 ADA FLIP UP COUNTER 2' - 7" 5 A-501 5' - 0" 1' - 9 1/2" ASI T01 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 2 7 P M A-451 LARGE SCALE PLANS - BAR St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker AXON - BAR1 1/2" = 1'-0" ENLARGED BAR PLAN - ABOVE COUNTER2 1/2" = 1'-0" ENLARGED BAR PLAN - BELOW COUNTER3 REVISION DATE ASI T01 02.09.21 6 A-501 MT-1 SS-1 FOOT RAIL LIGHTING FIXTURE RE: ELECTRICAL LIGHTING FIXTURE RE: ELECTRICAL 7 A-501 ADA FLIP UP COUNTERMT-1 MT-1 P6 P6 P6 P6 P6 P6 ASI T01 3' - 5 " 5' - 1 " MT -3 WD-1 MT-1 SS-1 LIGHTING FIXTURE RE: ELECTRICAL DUCT RE: MECHANICALLIGHTING FIXTURE RE: ELECTRICAL FOOT RAIL 8 A-501 P6P6P6P6 ASI T01 1 A-501 2 A-501 OPEN TO BEYOND 8' - 3" 8' - 7 " 0' - 4"1' - 10"0' - 4"3' - 3"0' - 4"1' - 10"0' - 4" 0' - 5 " 1' - 1 0 " 0' - 2 " 1' - 8 " 0' - 2 " 1' - 8 " 0' - 2 " 2' - 6 " VENT RE: MECHANCIAL VENT RE: MECHANCIAL BEER TAPS RE: FOOD SERVICE WD-1 SS-1 BACK BAR CABINET, REFRIGERATED RE: FOOD SERVICE BACK BAR CABINET, REFRIGERATED RE: FOOD SERVICE MT-1MT-1MT-1 WT-1 ASI T01 3 A-501 0' - 5 " 3' - 8 " 0' - 2 " 1' - 8 " 0' - 2 " 2' - 6 " 0' - 4"7' - 8"4' - 0" 0' - 4"3' - 4"0' - 4"4' - 0"0' - 4"3' - 4"0' - 4" 12' - 0" 8' - 7 " DUCT RE: MECHANCAL BEER TAPS RE: FOOD SERVICE TV OWERNER PROVIDED WD-1 SS-1 BACK BAR CABINET, REFRIGERATED RE: FOOD SERVICE MT-1MT-1 6 A-501 FRP-1 0' - 6 " LIGHTING FIXTURE RE: ELECTRICAL DRINK RAIL RE: FOOD SERVICE 7 A-501 WD-1 SS-1MT-1 P6P6P6P6P6P6 ASI T01 ASI T01 FRP-2 ASI T02 FRP-1 LIGHTING FIXTURE RE: ELECTRICALDUCT RE: MECHANICAL DRINK RAIL RE: FOOD SERVICE 8 A-501 P6P6P6P6 P6 4 A-501 5' - 0 " 3' - 6 " MT -3 WD-1 EXTENT OF BAR EQUIPMENT 1' - 10"4' - 11 1/2" 5" 1' - 7 " 2" 1' - 7 " 2" 1' - 7 " 2" 1' - 7 " 2" 1' - 2 " 3' - 6 " 4"1' - 7"4"1' - 7"4"1' - 7"4" 6' - 1" 3' - 6 " 2' - 0"2' - 0"2' - 0" MT-1 WD-1 SS-1 8' - 7 " 5 A-501 WT-1 BEYOND PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 2 5 / 2 0 2 1 8 : 3 3 : 5 1 A M A-452 LARGE SCALE ELEVATIONS -BAR St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker 1/2" = 1'-0" EXTERIOR BAR - NORTH ELEVATIONS11/2" = 1'-0" EXTERIOR BAR- WEST ELEVATION2 1/2" = 1'-0" INTERIOR BAR - NORTH ELEVATION31/2" = 1'-0" INTERIOR ELEVATION - WEST ELEVATION4 1/2" = 1'-0" INTERIOR BAR - SOUTH ELEVATION5 1/2" = 1'-0" INTERIOR BAR - EAST ELEVATION6 1/2" = 1'-0" LIQUOR STORAGE - ELEVATION71/2" = 1'-0" WAIT STATION ELEVATION8 ASI T01 REVISION DATE ASI T01 02.09.21 ASI T02 02.24.21 FIRST FLOOR 0' -0" FA C P GM A P P FI RST FLOOR 0' -0" MT-1 ? 3 A A-453 6 7 5 A-453 8 A-453 4 2 A-502 4 A-50210 A-502 BDFR3 BD FR 3 BDP3 0' - 6 1/8"0' - 6 1/8" MT-1 WF-1 4 A-502 10 A-502 FIREPLACE -HEAT&GLO - FDN-4-PIER MT-1 AL 6' - 1 " 2' - 6 " 3' - 6 " 5' - 9" 1' - 4"4' - 5"4 A-502 10 A-502 FIREPLACE -HEAT&GLO - FDN-4-PIER MT-1 110 SHELVING TO BE PROVIEDED BY OWNER 2 A-502 1' - 5 " 2' - 6 " 1' - 6 " 1' - 7 1 / 2 " 2' - 6 " CENTER ON WALL 2' - 6" 1' - 1 " 1' - 0 1 / 4 " 0' - 4 3 / 4 " 10' - 3 1/2" 2' - 0 1/16"2' - 0 13/16"2' - 0 13/16"2' - 0 13/16"2' - 1 9/16" PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 1 1 / 2 0 2 1 4 : 1 9 : 4 8 P M A-453 LARGE SCALE PLANS & ELEVATIONS - MERCHANDISE DISPLAY St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker AXON - MECHANDISE DISPLAY1 1/2" = 1'-0" ENLARGED - MECHANDISE PLAN2 AXON - MECHANDISE DISPLAY 231/2" = 1'-0" FIREPLACE - NORTH ELEVATION41/2" = 1'-0" FIRE PLACE - SOUTH ELEVATION5 1/2" = 1'-0" MECHANDISE DISPLAY- NORTH ELEVATION61/2" = 1'-0" MERCHANDISE DISPLAY - EAST ELEVATION7 1/2" = 1'-0" INTERIOR ENTRY- ELEVATION8 ASI T01 ASI T01 ASI T03 REVISION DATE ASI T01 02.09.21 ASI T03 03.05.21 A-454 4 A-454 5 6 3 A-502 5 A-502 5 A-502 6' - 0" 1' - 11" 0' - 6" WD-1 UP-1 FF-1 1 BC A-454 8 A-454 7 8 A-502 7 A-502 1' - 9 15/32"23' - 11 13/32"0' - 4 7/8" 5' - 0" A-454 9 9 A-502 7 A-502 3 A-502 1' - 7" 1' - 5" 1' - 6" 4' - 6" 0' - 1" 0' - 2"5' - 8"0' - 2" SS-1 ? WD-1 WD-1 WD-1 5 A-502 WF-1WF-1 ASI T01 ASI T01 WF-1 ASI T01 4' - 0" 0' - 10" BOOTHS PROVIDED BY OWNER WF-1 WF-1 8 A-502 3' - 11" SS-1 WD-1 0' - 4 7/8"4' - 7" SS-1 9 A-502 7 A-502 4' - 0" 4' - 0" WD-1 SS-1 BOOTHS PROVIDED BY OWNER WD-1 ASI T01 CUSTOM STRIPE PATTERN PT-1 PT-2 PT-3 PT-4 PT-5 WD-1 ASI T01 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 4 8 P M A-454 LARGE SCALE PLANS & ELEVATIONS -DINING St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker 1/2" = 1'-0" ENLARGED - BANQUETTE AND BENCH PLAN1 1/2" = 1'-0" ENLARGED - BOOTH & POS STATION 1 PLAN2 1/2" = 1'-0" ENLARGED - BOOTH & POS STATION 2 PLAN3 1/2" = 1'-0"A-454 4 WAIT BENCH - ELEVATION 1/2" = 1'-0"A-454 5 BANQUETTE BENCH - EAST ELEVATION 1/2" = 1'-0"A-454 6 BANQUETTE - SOUTH ELEVATION 1/2" = 1'-0" BOOTH 1 - ELEVATION71/2" = 1'-0" POS STATION 1 - ELEVATION8 1/2" = 1'-0" BOOTH & POS STATION 2 ELEVATION9 ASI T01 ASI T01 REVISION DATE ASI T01 02.09.21 0' - 1 1/2" 2' - 0"7 1/2" 11"1' - 1 1/2" 2" FOOT RAIL SS-1 FRP-1 DRINK RAIL RE: FOOD SERVICE P6 4"X4"X4" BENT STEEL PLATE FOR COUNTER SUPPORT 3' - 4 1/2" MT-1 DOWEL TO EXISTING SLAB 6" STEEL CHANNEL PER STURCT 0' - 6" FF-1 VCT-1 2 8'-6" C1 P6 SS-1 FRP-1 3' - 2" 4' - 0" 0' - 1 1/2" 3' - 4 1/2" ADJUSTABLE SHELF BLACK MELAMINE INTERIOR TYP. CABINET GROMMET, TYP ADJUSTABLE SHELF 2 P6 8'-6" C1 2 BEER TAP RE: FOOD SERVICE STEEL 1 1/5" ANGLE LED LIGHT LED LIGHT WD-1 WD-1 WD-1 SS-1 MT-1 3/4" WOOD DOOR WITH MT-1 VENEER CONCEALED HINGES CONCEALED HINGES BLKG TO SUPPORT INTEGRAL BASE 4" BLACK MELAMINE INTERIOR TYP. 5" 1' - 10" 2" 1' - 8" 2" 1' - 8" 2" 2' - 6" 3' - 6" 8' - 7" FAUX CABINET FLOOR SINK RE: PLUMBING 8'-6" C1 3' - 6" 2' - 6" 0' - 2" 1' - 8" 0' - 2" 3' - 8" 0' - 5" BEER TAP RE: FOOD SERVICE 8' - 7" TV PROVIDED BY OWNER STEEL 1 1/5" ANGLE LED LIGHT LED LIGHT SS-1 WD-1 WD-1 WD-1 MT-1 3/4" WOOD DOOR WITH MT-1 VENEER CONCEALED HINGES CONCEALED HINGES BLKG TO SUPPORT INTEGRAL BASE 4" BLACK MELAMINE INTERIOR TYP. FAUX CABINET FLOOR SINK RE: PLUMBING 1' - 2" 1' - 3" 1' - 3" 1' - 3" 1' - 7" 5' - 0" 3' - 6" DUCT RE: MECHANICAL 2X2X 1/8" STEEL TUBE TYP. 1X1X1/8 STEEL TUBE TYP. 1/2" STEEL ANGLE 1/4" STEEL PLATE SHELF INFILL 3/4" STEEL ANGLE EXPANDED METAL INFILL PANEL 3/4" STEEL ANGLE EXPANDED METAL INFILL PANEL BAR TOP ASSEMBLY STAINED VENEER PLYWOOD INFILL PANEL LED LIGHT STRIP AT EACH SHELF EXPANDED METAL INFILL PANEL STAINED VENEER PLYWOOD INFILL PANEL STEEL PLATE CLOSURE TRACK SYSTEM FR3 0' - 10"0' - 0 3/4" 0' - 3 5/8" 0' - 6" PROVIDE HARDWARE TO HINGE DOWN FLUSH AGAINST FINISH FACE. 1 1/2 PR HAFFEL " HEBGO HEAVY DUTY FOLDING BRACKETS. LOCATIONS OF BRACKETS NEED TO MEET ADA CLEARANCE FOR WHEELCHAIR. DOWEL TO EXISTING SLAB 6" STEEL CHANNEL PER STURCT 1' - 9 1/2" AL I G N 1' - 11 1/2" 1" MT-1 MT-1 MT-1 10 1/2" MAX ADA HEIGHT 2' - 10" 6 1/2" 1 1/2" PT-6 ENTIRE CAVITY SERVICE RAIL: KEGWORKS CLASSIC SERVICE BAR RAIL-MATTE BLACK 2" OD DD STEEL 1 1/5" ANGLE LED LIGHT SS-1 ADJUSTABLE SHELF BLACK MELAMINE INTERIOR TYP. CABINET GROMMET, TYP ADJUSTABLE SHELF WD-1 WD-1 3' - 6" 1' - 4" 1' - 9" 1' - 9" 1' - 9" 1' - 7" 5" 8' - 7" 11 1/2" 2' - 1" P3 Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 5 2 P M A-501 DETAILS -BAR St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker 1 1/2" = 1'-0"A-501 6 SECTION - BAR TYP 1 1/2" = 1'-0"A-501 1 SECTION - BAR PASS THROUGH 1 1/2" = 1'-0"A-501 2 SECTION - BACK BAR 1 1 1/2" = 1'-0"A-501 3 SECTION - BACK BAR 2 1 1/2" = 1'-0"A-501 4 SECTION - LIQUOR DISPLAY 1 1/2" = 1'-0"A-501 7 SECTION - ADA FLIP-UP COUNTER 1 1/2" = 1'-0"A-501 8 SECTION - SERVICE RAIL 1 1/2" = 1'-0"A-501 5 SECTION - WAIT STATION ASI T01 REVISION DATE ASI T01 02.09.21 0' - 0 3 / 4 " 0' - 1 1 7 / 8 " 0' - 0 3 / 4 " 0' - 1 1 7 / 8 " 0' - 0 3 / 4 " WD-1 1' - 0 5 / 8 " ASI T03 0' - 3" 6' - 1 " 2' - 6 " 1' - 0 " 0' - 0 3 / 4 " 2' - 0 1 / 2 " 0' - 0 3 / 4 " 0' - 4 " 4' - 2 " 2' - 6 " 1' - 7 3/4" FR3FR3 FR3 FIREPLACE -HEAT&GLO - FDN-4-PIER ADJUSTABLE SHELF BLACK MELAMINE INTERIOR TYP. CABINET GROMMET, TYP 0' - 3 " 0' - 1 " 1' - 9"0' - 2" P3 WD-1 WD-1 WD-1 SOLID WOOD CAP 1' - 6 " 9 7.0 0 ° 0' - 1 1 / 2 " 1' - 1 1 1 / 4 " 0' - 0 3 / 4 " 1' - 8" 1' - 10 1/2" 1' - 6"0' - 4 1/2" WD-1 UP-1 FOOT RAIL BRACKET 2" FOOT RAIL WD-1 RE : F L O O R P L A N VA R I E S RE: FLOOR PLAN VARIES VCT-1 WD-1 4' - 0 " WD-1 WD-1 FOR BANK OF BOOTHS ON INTERIOR WALLS ONLY ASI T01 CABINET DRAWER SS-1 WD-1 WD-1 ADJUSTABLE SHELF BLACK MELAMINE INTERIOR TYP. GROMMET, TYP 0' - 3" 0' - 1 " 0' - 7 " 2' - 6 " 0' - 4 " SS-1 P3 1' - 4" WD-1 CABINET DRAWER 0' - 1 " 0' - 5 " 2' - 2 " 0' - 4 " SS-1 WD-1 ADJUSTABLE SHELF BLACK MELAMINE INTERIOR TYP. GROMMET, TYP 2' - 0"0' - 1" WD-1 SS-1 WD-1 CABINET DRAWER 0' - 3" 2' - 2 " 0' - 5 " 0' - 1 " ADJUSTABLE SHELF BLACK MELAMINE INTERIOR TYP. GROMMET, TYP SS-1 ASI T01 EX T I S T I N G MATCH EXTERIOR FRAMES ALIGN EXISTING EXTERIOR FRAME EXISTING CLAD WINDOW 4" 5"1 1/2" 1 1/2"V. I . F . 6 1 / 2 " 4" EX T I S T I N G MATCH EXTERIOR FRAMES ALIGN EXISTING EXTERIOR FRAME EXISTING MULTI PANLE WINDOW1 1/2" V. I . F . 5 1 / 2 " 4" 4" 5" 1 1/2" Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 1 1 / 2 0 2 1 4 : 1 9 : 4 9 P M A-502 DETAILS -MERCHANDISE DISPLAY AND DINING St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker 1 1/2" = 1'-0" SECTION - EAST MERCH DISPLAY2 1 1/2" = 1'-0" SECTION - FIREPLACE4 1 1/2" = 1'-0" SECTION - WAIT BENCH3 1 1/2" = 1'-0" SECTION - BANQUETTE TYP.51 1/2" = 1'-0" SECTION - BOOTH PLATFORM TYP.7 1 1/2" = 1'-0" SECTION - POS STATION 18 1 1/2" = 1'-0" SECTION - POS STATION 29 1 1/2" = 1'-0" SECTION - HOST STAND10 ASI T01 ASI T01 3" = 1'-0" DETAIL - WINDOW HEAD TRIM6 3" = 1'-0" DETAIL - MULTI DOOR HEAD TRIM11 ASI T01 ASI T01 ASI T01 ASI T01 ASI T03 REVISION DATE ASI T01 02.09.21 ASI T03 03.05.21 TYPE B (E) SINGLE FLUSH PANEL DOOR FINISH FLOOR RE : S C H E D . RE: SCHED. TYPE A COOLER ENTRY DOOR BY MFR. RE: SCHED. RE : S C H E D . RE : S C H E D . RE: SCHED. TYPE C OVERHEAD SECTIONAL DOOR TYPE D CUSTOM SLIDING DOOR WITH SIDELITES 12' - 8" 11 6 " 6" 6" 3' - 2 " EQ . SD L 4 1 / 2 " EQ . FR A M E 0' - 4 5 / 8 " EQ.EQ.6' - 4" FIXED FIXED 7/8 GLAZING CARDINAL LOW-E 272 WITH i89 ASI T01 34 1 / 4 " 82 " O V E R A L L F R A M E H E I G H T 76" OVERALL FRAME WIDTH FINISH FLOOR 1W1 FIXED BI-FOLD PARTITION RE: PLAN FOR DIRECTION 108" 11 6 " EQ EQ EQ TYPE E *NOTE: PROVIDE SAFETY GLAZING IN WINDOW ADJACENT TO OPERABLE PARTITION DOOR AND WINDOW NOTES: 1.All hardware referenced is to be Schlage or approved equal unless noted otherwise. 2.Unless noted otherwise, all doors with head height 8'-0" and below to have 1-1/2 pair hinges -w/ matching 626 finish. 3.G.C. to furnish lock sets, levers, strike plates, bumpers and all other items to provide a complete and functioning hardware package all of matching 626 finish. Refer to Owner representative for keying requirements. 4.Package is subject to additional electronic / security devices -G.C. to coordinate. 5.Provide stops as required. 6.Provide weather-stripping at all exterior doors. 7.All storefront doors to have clear anodized finish to match existing unless noted otherwise. 8.Provide safety glazing as required by code. 9.Refer to Interior Elevations and Millwork drawings for wood and stain types on doors unless noted otherwise. 10.Provide offset hardware to accommodate panic devices, and at re-used doors where panic hardware is indicated. 11.Provide "door to remain unlocked during business hour sign @ all exist without panic. 12.All new entrance doors >50% glass area have to meet Max U-0.73 and SHGC Max 0.38 per Table C402.3 requirements for vertical fenestration. 13.Walk-in Cooler and Freezers: Automatic Door closer shall be provided that fully close walk-in doors that have been closed to within 1 inch of full closure. Dorrways shall be provided with trip doors, curtain, spring-hinged doors or other method of minimizing infiltration when doors are open. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION 08 1113.01 HOLLOW METAL DOOR / FRAME (HM) JA M B D E PT H VA R I E S VARIES RE: PLAN ROOM SIDE CORRIDOR SIDE GLAZING STOP WHERE OCCURS, INSTALL ON SECURE SIDE OF FRAME 09 2116.41 ACOUSTIC INSULATION ALL AROUND FRAME 11 EXISTING EXTERIOR WINDOW FIXED GLASS PANEL WRAP JAMB WITH WOOD; PAINT TO MATCH ADJACENT FIXED GLASS PANEL SLIDING GLASS DOOR SLIDING DOOR HARDWARE GYPSUM BOARD, RE: SPECS FOR TYPE09 2116.09 BLOCKING AS REQUIRED BOX HEADER 3 1/2" FIRST FLOOR PLAN 100' -0" B.O. TRUSS 112' -1" EXISTING STAIR DOWN EXISTING HALF WALL P6 BUILD ON TOP OF EXISTING HALF WALL ELEVATOR DOOR BEYOND EXISTING ROOF HATCH WALL-MOUNTED LADDER UP TO ROOF HATCH. INSTALL WALL SUPPORT BRACKETS. RUNGS TO BE EQUALLY SPACED, NOT MORE THAN 14" APART. INSTALL LADDER GUARD. STEEL ANGLE WALL BRACKETS WITH FASTENERS, EQUALLY SPACED A-601 6 0' - 7" GLAZING STOP WHERE OCCURS, INSTALL ON SECURE SIDE OF FRAME JAMB DEPTH VARIES 08 1113.01 HOLLOW METAL DOOR / FRAME (HM) VARIES RE: PLAN ACOUSTIC INSULATION09 2116.41 AROUND FRAME STEEL ANGLE WALL BRACKET WITH FASTENERS ATTACH ANGLE TO LADDER SIDE RAIL ROOF ACCESS LADDER BE T W E E N R U N G S 14 " M A X CENTERLINE OF RUNGS 7" MIN SE E S C H E D U L E F O R H E I G H T PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 4 / 2 0 2 1 8 : 3 8 : 5 7 A M A-601 DOOR AND FINISH SCHEDULE St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker DOOR SCHEDULE MARK DOOR SIZE (WxH) THICKNESS DOOR TYPE MATERIAL FINISH GLASS FRAME HARDWARE GROUP REMARKS 001 3'-0" x 7'-0" 1-3/4" B HM. PAINT - HM. A 01B EXISTING TO REMAIN - - - PAINT - - B 003 3'-0" x 7'-0" MFR. A MFR. MFR. - MFR. MFR. 004 3'-0" x 7'-0" 1-3/4" B HM. PAINT - HM. B 005 3'-0" x 7'-0" MFR. A MFR. MFR. - MFR. MFR. 006 3'-0" x 7'-0" MFR. A MFR. MFR. - MFR. MFR. 08A EXISTING TO REMAIN - - - - - - C 100 EXISTING TO REMAIN - - - PAINT EX - D 110 9'-0" X 9'-8" MFR E CLR.INTERIOR NANA WALL 112 3'-0" x 7'-0" MFR. A MFR. MFR. - MFR. MFR. 113A 12'-8" x 9'-8" 2" D STL PAINT CLR. - F 113B EXISTING TO REMAIN MFR. - MFR. MFR. EX MFR. MFR. 118 EXISTING TO REMAIN - - - PAINT EX - D DOOR HARDWARE SCHEDULE GROUP CLOSER HANDLE FUNCTION ACCESSORIES COMMENTS A SURFACE MOUNTED D SERIES ATHENS 626 OFFICE PEEPHOLE B SURFACE MOUNTED D SERIES ATHENS 626 STORAGE - C SURFACE MOUNTED - - PEEPHOLE VERIFY OR PROVIDE ENTRANCE FUNCTION D SURFACE MOUNTED - - -VERIFY OR PROVIDE PANIC DEVICE E SURFACE MOUNTED - - PEEPHOLE, HALF HEIGHT KICK PLATE AT INSIDE VERIFY OR PROVIDE PANIC DEVICE F - PULL AT EACH SIDE - -STANLEY DOUBLE TRACK BARN DOOR HARDWARE 1 1/2" = 1'-0" TYPICAL HOLLOW METAL FRAME AT GYPSUM BOARD PARTITION1 FINISH SCHEDULE TAG MANUFACTURER PRODUCT SIZE COLOR/FINISH Comments REVISION BASE WB-1 RUBBER BASE FLEXCO OR EQUAL 6"H BLACK FLOORING FF-1 ARMSTONG VCT TILE 12X12 MIXED- PEAT, PMEGRANATE RED, BASIL GREEN ASI-T01 FF-2 PROTECT - ALL PVC FLOORING DARK GRAY FF-3 DALTILE QUARRY TILE 6X6X3/8 BLACK PUREE EPOXY GROUT ; MAPEI, CHARCOAL, ANTHRACITE, CARBON 47 METAL MT-1 METAL FABRICATOR METAL - BLACKENED STEEL BLACKENED STEEL FINISH TO MATCH ARCHITECTURAL SAMPLE. SAMPLE TO BE PROVIDED TO ARCHITECT. MT-2 SCHULTER METAL - WALL BASE BRUSHED BLACK ANODIZED ALUMINUM AGSB LINEAR BASE AND OUT- CORNER BASE MT-3 METAL FABRICATOR METAL - WIRE MESH TBD MILLWORK PL-1 MILLWORKER MELAMINE LAMINATE BLACK SS-1 MILLWORKER PAPERSTONE GUNMENTAL UP-1 SINA PEARSON EVERYWHER EPU 495 9 | EXPRESSO ASI-T01 WD-1 MILLWORKER STAINED BIRCH VENEERED PLYWOOD STAIN-TBD WD-2 MILLWORKER SOLID WOOD TBD WALL FINISH FRP-1 MARLITE FRP P-100 GC BLACK/ SMOOTH FRP-2 MARLITE FRP P-807 GC WHITE/ SMOOTH FRP-3 MARLITE FRP P-100 GC WHITE/ PEBBLED PT-1 SHERWIN-WILLIAMS ALABASTER SW 7008 PT-2 SHERWIN-WILLIAMS SAWGRASS BASKET 209 -C3 ASI-T01 PT-3 SHERWIN- WILLIAMS BOLERO SW 7600 ASI-T01 PT-4 SHERWIN-WILLIAMS BURGANDY SW 6300 ASI-T01 PT-5 SHERWIN-WILLIAMS CHRYSANTHEMUM SW 6347 ASI-T01 PT-6 SHERWIN-WILLIAMS IRON ORE SW 7069 ASI-T01 WF-1 CENTENNIAL SALVAGED WOOD SIDING SUNDANCE WHITE ASI-T01 WT-1 DALTILE NATURAL HUES, 6121P 6X12 SWEET PEA QH2 ASI-T01 1 1/2" = 1'-0" PLAN - BARN DOOR JAMB71 1/2" = 1'-0" SECTION - BARN DOOR HEAD8 ASI T01 ASI T01 ASI T01 1/2" = 1'-0" ROOF ACCESS LADDER4 ASI T03 1 1/2" = 1'-0" DETAIL - INTERIOR HM FRAME HEAD5 3" = 1'-0" SECTION DETAIL - ROOF ACCESS LADDER WALL BRACKET6 1/8" = 1'-0" DETAIL - NANA WALL HEAD AND SILL DETAIL2 ASI T03 ASI T03 ASI T03 ASI T04 ASI T04 ASI T04 REVISION DATE ASI T01 02.09.21 ASI T03 03.05.21 ASI T04 03.17.21 CO MM CM WFVSTT 1 1 2 2 3 3 4 4 LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 ELEV. B10 COOLER 005 FREEZER 006 AREA WELL AREA WELL PT-1 RB-1 FF-2 001 OFFICE A A B B C C E E WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A PLATFORM B02B LOBBY B01 EX EX EX EX EX EX EX EX RB EX EX RB NOTE: FOOD SERVICE EQUIPMENT IS SHOWN FOR COORDINATION PURPOSES ONLY. RE: FOOD SERVICE DRAWINGS FOR DETAILED INFORMATION ON EQUIPMENT AND LAYOUT. FS FS MOP SINK PAINT AND BLOCK FILLER OVER CONCRETE BLACK LAMINATE COUNTER TOP W/ ADJUSTABLE BLACK LAMINATE SHELVES ABOVE ALUMINUM TRANSITION STRIP ALUMINUM TRANSITION STRIP BLACK LAMINATE COUNTER TOP KICK BRACE BELOW ASI T01 ASI T01 LOUNGE B02 FRP-3 RB-1 FF-2 010 TI STORAGE FRP-3 FRP-3 FRP-3 1. ALL DIMENSIONS ON FINISH PLANS ARE TO FINISHED FACE OF MATERIAL, UNO. 2. ALL WALLS AND FINISHED CEILING SURFACES TO BE PAINTED PTI-1, UNO. 3. PAINT ALL EXPOSED DECK, PIPES, DUCTWORK, AIR DIFFUSERS, AND GRILLS, AND ACCESS DOORS TO MATCH FOLOR OF ADJACENT CEILING OR WALL SURFACE, UNO. 4. PAINT ALL COUNTERTOP SUPPORT KNEE BRACES TO MATCH ADJACENT WALL SURFACE UNLESS FACTORY FINISHED. 5. PAINT ALL EXPOSED DECK, PIPES, DUCTWORK, AIR DIFFUSERS, AND GRILLS TO MATCH COLOR OF ADJACENT WALL OR CEILING SURFACE, UNO. 6. PAINT ALL INTERIOR HOLLOW METAL DOOR AND WINDOW FRAMES IN GYP WALL BOARD TO MATCH ADJACENT WALL COLOR, UNO. 7. REFER TO ELEVATIONS AND REFLECTED CEILING PLAN FOR ADDITIONAL INFORMATION RELATED TO FINISHES AND EXTENTS. 8. ALL FLOORING MATERIALS AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNO. 9. CONTRACTOR TO SUBMIT INSTALLATION PATTERN DRAWINGS FOR ARCHITECT'S APPROVAL FOR ALL APPLICABLE FINISHES (INCLUDING BUT NOT LIMITED TO: CARPET, TILE, RESILIENT FLOORING, GLASS FILM). 10. FLOOR FINISHES TO EXTEND UNDER CASEWORK AND KNEE SPACE, U.N.O. 11. FLOORING SUBCONTRACTORS TO FIELD VERIFY ALL DIMENSIONS. SMALL FLOORING SLIVERS ALONG PERIMETER WILL NOT BE ACCEPTED. COORDINATE WITH ARCHITECT AS REQUIRED. 12. INTERIOR WALL & CEILING FINISHES TO HAVE A FLAME SPREAD INDEX NOT GREATER THAN CLASS B AT ROOMS AND ENCLOSURES AND CLASS B AT CORRIDORS PER IBC (2015) TABLE 803.13 13. INTERIOR FLOOR FINISHES AND FLOOR COVERING MATERIALS SHALL NOT BE LESS THAN CLASS II PER IBC (2015) SECTION 804.2. 14. COOLER WALLS TO HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE- DEVELOPMENT INDEX OF NOT MORE THAN 450 PER IBC (2015) SECTION 2603.4.1.2 15. PROVIDE APPROPRIATE SCHLUTER TRANSITIONS BETWEEN FLOORING MATERIALS, TYPICAL. 16. REFER TO INTERIOR ELEVATIONS FOR ADDITIONAL FINISHES OVERHEAD. 17. IN ALL KITCHEN AREAS W/ FRP. PROVIDE STAINLESS STEEL WALL CAPS AT ALL WING WALLS LESS THAN 6" WIDE AND CORNER GUARDS AT ALL EXTERIOR CORNERS FROM TOP OF COVE TO B.O. CEILING GRID. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION FINISH LEGEND ROOM NAME ROOM NUMBER WF BF FF WALL FINISH MATERIAL BASE FINISH MATERIAL FLOOR FINISH MATERIAL FINISH MATERIAL TAG FINISH NOTE, WHERE OCCURS FINISH NOTE, WHERE OCCURS FINISH MATERIAL/PATTERN DIRECTION X-#X-#FINISH MATERIAL TRANSITION XXX XXX X-# 1/4" = 1'-0" BASEMENT LEVEL - FURNITURE/FINISH PLAN1 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 5 5 P M A-700 BASEMENT LEVEL - FINISH & FURNITURE PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker ASI T01 REVISION DATE ASI T01 02.09.21 FA C P GM A P P MM MM WD-2 /PT RB-1 FF-1 113 PRIVATE DINING COOLER 112 DISH 111 FRP-2 RB-1 FF-2 109 KITCHEN BOH FRP-2 RB-1 FF-2 105 STORAGE FRP-1 RB-1 FF-2 108 BAR BOH RE: ELEVATIONS RB-1 FF-1 101 ENTRY LIQ. STORAGE 106 PRIVATE PATIO 114 PATIO 117 RETAIL WALL P.O.S. SLIDING DOOR RE: ELEVATIONS RB-1 FF-1 102 RETAIL P. O . S DISH DROP VC T RB RB VC T ALUMINUM THRESHOLD ALUMINUM THRESHOLD ALUMINUM THRESHOLD ALUMINUM THRESHOLD ALUMINUM THRESHOLD ALUMINUM THRESHOLD ALUMINUM TRANSITION A C C E S S . S E A T I N G A C C E S S . S E A T I N G AC C E S S . SE A T I N G ACCESS. SEATING ACCESS. SEATING ACCESS. SEATING AC C E S S . SE A T I N G AC C E S S . SE A T I N G AC C E S S . SE A T I N G AC C E S S . SE A T I N G AC C E S S . SE A T I N G A C C E S S . S E A T I N G A C C E S S . S E A T I N G A C C E S S . S E A T I N G STEEL TRANSITION STAINLESS STEEL BEHIND DISH MACHINE THICK DASHED LINE SHOWS EXTEND STAINLESS OF HOOD AND EXTEND A MINIMUN OF 18" IN ALL DIRECTIONS FROM THE HOOD. PER IMC 507.2.6 ALUMINUM THRESHOLD FRP UNDER COUNTERTOP RE: ELEVATIONS RB-1 FF-1 107 BAR RE: ELEVATIONS RB-1 FF-1 115 DINING FRP-2 FRP-2 FRP-2 WT-1 WD-2/ PT-1 RB-1 FF-1 120 FLEX EX RB-1 FF-1 100 MAIN ENTRY WD - 2 WD-2 WD-2 PT-1 WD - 2 WD-2 WD - 2 CU S T O M S T R I P E P A T T E R N PT - 1 PT - 2 PT - 3 PT - 4 PT - 5 DASHED LINE SHOW EXTENT OF STAINLESS STEEL WALL PANELS. DASHED LINE SHOW EXTENT OF STAINLESS STEEL WALL PANELS. ASI T04 SEATING SUMMARY TABLES SEATS 0 9 4 0 36 24 TYPE 2 - Tops 4 - Tops 6 - Tops 13Total 60 TOTAL INDOOR SEATING 139 TOTAL 26360 - 7 0 1 1 0 19 14 0 6 8 0 LOUNGE Stools 2 - Tops 4 - Tops 6 - Tops 8 - Tops 10 - Tops 9Total 47 DINING 0 8 0 0 32 0 2 - Tops 4 - Tops 6 - Tops 8Total 32 PRIVATE DINING TOTAL OUTDOOR SEATING 124 0 28 2 0 0 112 12 0 2 - Tops 4 - Tops 6 - Tops 8 - Tops 30Total 124 OUTDOOR SEATING SEATING LEGEND T-1 T-2 T-3 T-4 T-5 T-6 T-7 T-8 T-9 T-10 30" X 72" FREESTANDING BAR HEIGHT DINING TABLE 24" X 72" FREESTANDING BAR HEIGHT DINING TABLE 26" X 28" FREESTANDING BAR HEIGHT DINING TABLE 36" ROUND FREESTANDING BAR HEIGHT DINING TABLE 30" X 60" FREESTANDING BOOTH TABLE 36" X 36" FREESTANDING DINING TABLE 30" X 48" FREESTANDING DINING TABLE 30" X 48" FREESTANDING EXTERIOR DINING TABLE 30" X 72" FREESTANDING EXTERIOR DINING TABLE 30" X 48" FREESTANDING BOOTH TABLE TABLE DESCRIPTION QUANTITY SEAT 1 1 6 1 4 5 8 28 2 4 NOTES: 1. REFER TO A3.0 FOR TABLE, CHAIR AND BASE SPECIFICATIONS. 2. VERIFY QUANTITY LISTED WITH TABLES SHOWN IN PLAN BEFORE ORDERING. 3. FURNITURE VENDOR TO PROVIDE TWO PURSE HOOKS PER INTERIOR TABLE TO BE INSTALLED BY GC. 1. ALL DIMENSIONS ON FINISH PLANS ARE TO FINISHED FACE OF MATERIAL, UNO. 2. ALL WALLS AND FINISHED CEILING SURFACES TO BE PAINTED PTI-1, UNO. 3. PAINT ALL EXPOSED DECK, PIPES, DUCTWORK, AIR DIFFUSERS, AND GRILLS, AND ACCESS DOORS TO MATCH FOLOR OF ADJACENT CEILING OR WALL SURFACE, UNO. 4. PAINT ALL COUNTERTOP SUPPORT KNEE BRACES TO MATCH ADJACENT WALL SURFACE UNLESS FACTORY FINISHED. 5. PAINT ALL EXPOSED DECK, PIPES, DUCTWORK, AIR DIFFUSERS, AND GRILLS TO MATCH COLOR OF ADJACENT WALL OR CEILING SURFACE, UNO. 6. PAINT ALL INTERIOR HOLLOW METAL DOOR AND WINDOW FRAMES IN GYP WALL BOARD TO MATCH ADJACENT WALL COLOR, UNO. 7. REFER TO ELEVATIONS AND REFLECTED CEILING PLAN FOR ADDITIONAL INFORMATION RELATED TO FINISHES AND EXTENTS. 8. ALL FLOORING MATERIALS AND TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION UNO. 9. CONTRACTOR TO SUBMIT INSTALLATION PATTERN DRAWINGS FOR ARCHITECT'S APPROVAL FOR ALL APPLICABLE FINISHES (INCLUDING BUT NOT LIMITED TO: CARPET, TILE, RESILIENT FLOORING, GLASS FILM). 10. FLOOR FINISHES TO EXTEND UNDER CASEWORK AND KNEE SPACE, U.N.O. 11. FLOORING SUBCONTRACTORS TO FIELD VERIFY ALL DIMENSIONS. SMALL FLOORING SLIVERS ALONG PERIMETER WILL NOT BE ACCEPTED. COORDINATE WITH ARCHITECT AS REQUIRED. 12. INTERIOR WALL & CEILING FINISHES TO HAVE A FLAME SPREAD INDEX NOT GREATER THAN CLASS B AT ROOMS AND ENCLOSURES AND CLASS B AT CORRIDORS PER IBC (2015) TABLE 803.13 13. INTERIOR FLOOR FINISHES AND FLOOR COVERING MATERIALS SHALL NOT BE LESS THAN CLASS II PER IBC (2015) SECTION 804.2. 14. COOLER WALLS TO HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE- DEVELOPMENT INDEX OF NOT MORE THAN 450 PER IBC (2015) SECTION 2603.4.1.2 15. PROVIDE APPROPRIATE SCHLUTER TRANSITIONS BETWEEN FLOORING MATERIALS, TYPICAL. 16. REFER TO INTERIOR ELEVATIONS FOR ADDITIONAL FINISHES OVERHEAD. 17. IN ALL KITCHEN AREAS W/ FRP. PROVIDE STAINLESS STEEL WALL CAPS AT ALL WING WALLS LESS THAN 6" WIDE AND CORNER GUARDS AT ALL EXTERIOR CORNERS FROM TOP OF COVE TO B.O. CEILING GRID. GENERAL NOTES SHEET SPECIFIC GENERAL INFORMATION AND/OR INSTRUCTION FINISH LEGEND ROOM NAME ROOM NUMBER WF BF FF WALL FINISH MATERIAL BASE FINISH MATERIAL FLOOR FINISH MATERIAL FINISH MATERIAL TAG FINISH NOTE, WHERE OCCURS FINISH NOTE, WHERE OCCURS FINISH MATERIAL/PATTERN DIRECTION X-#X-#FINISH MATERIAL TRANSITION XXX XXX X-# 1/4" = 1'-0" LEVEL 1 - FURNITURE/FINISH PLAN1 PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 4 / 2 0 2 1 8 : 3 9 : 0 0 A M A-701 LEVEL 1 -FINISH & FURNITURE PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker ASI T01 REVISION DATE ASI T01 02.09.21 ASI T04 03.17.21 Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 1 : 5 9 P M A-800 SPECIFICATIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker REVISION DATE Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 2 : 0 0 P M A-801 SPECIFICATIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker REVISION DATE Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 2 : 0 2 P M A-802 SPECIFICATIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker REVISION DATE Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 2 / 2 0 2 1 5 : 2 3 : 4 0 P M A-900 PERPECTIVES St a n l e y H o t e l P o s t R e s t a u r a n t T I Author 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS Checker ENTRY VIEW1 BAR MILLWORK2 FIREPLACE PERPECTIVE3 REVISION DATE B F P B F P B F P 3/4"CW 1/2"CW 1/2"CW ROUTE TO BEVERAGE MACHINES. REFER TO FOOD SERVICE DRAWINGS FOR SIZES AND ADDITIONAL INFORMATION. REFER TO PLANS FOR PIPING CONTINUATION. (3) BFP-1 M (E)GAS METER SET BY EXCEL ENERGY, SET PRESSURE TO 10" W.C. (2783 MBH) (3465.8 CFH) FS EQUIP. #136 300 MBH 373.5 CFH FS EQUIP. #127 198 MBH 246.6 CFH FS EQUIP. #130 40 MBH 49.8 CFH FS EQUIP. #129 60 MBH 74.7 CFH FS EQUIP. #128 132 MBH 164.4 CFH FS EQUIP. #125 90 MBH 112.1 CFH FS EQUIP. #124 100 MBH 124.5 CFH 1-1/2"G1-1/4"G3/4"G3/4"G1-1/4"G1"G1"G 2-1/2"G 2-1/2"G (E) 4"G (E) 5"G FIREPLACE 60 MBH 74.7 CFH FIREPLACE 60 MBH 74.7 CFH 1-1/4"G 3/4"G 3/4"G TO EQUIPMENT: DWH-1 500 MBH 622.7 CFH DOAS-1 445 MBH 554.2 CFH B-1 85 MBH 105.9 CFH MAU-1 363 MBH 452.1 CFH TO EQUIPMENT: RTU-1 150 MBH 186.8 CFH SINK REFER TO PLANS FOR WASTE AND VENT SIZING. WASTE VENT SINK 1/2"CW 1/2"HW REFER TO PLANS FOR CONTINUATION (TYP.). SINK REFER TO PLANS FOR WASTE AND VENT SIZING. SINK 1/2"CW 1/2"HW WASTE VENT FIRST FLOOR FIRST FLOOR FLOOR SINK REFER TO PLANS FOR CONTINUATION (TYP.). EXISTING 4" GW IW OD GREASE WASTE INDIRECT WASTE SD OD SD HOT WATER CIRCULATING SANITARY VENT (V) ABOVE GRADE OR FLOOR SANITARY WASTE HOT WATER (HW) COLD WATER (CW) NATURAL GAS LP EQUIPMENT DRAIN PUMPED CONDENSATEPC D PUMP DISCHARGE COMPRESSED AIR LIQUIFIED PETROLEUM GAS PD CA G BD SANITARY (BUILDING DRAIN) BELOW GRADE OR FLOOR NON-POTABLE WATERNP(HWC) TEMPERED WATERTW S/O W SHW SOFT HOT WATER SCW SOFT COLD WATER SOLAR COLLECTOR SUPPLYSCS SOLAR COLLECTOR RETURNSCR FLOOR DRAIN ROOF DRAIN OVERFLOW ROOF DRAIN DOWNSPOUT NOZZLE CLEANOUT, WALL (WCO) CLEANOUT PLUG (LCO) TEMPERATURE GAUGE METER (GAS OR WATER)M TEE DOWN ELBOW DOWN TEE UP BRANCH-BOTTOM CONNECTION GATE VALVE IN VERTICAL BRANCH-TOP CONNECTION RISE OR DROP ELBOW UP UNION P-TRAP PIPE CAP OR PLUG SHOWER HEAD PIPE ALIGNMENT GUIDE PIPE ANCHOR STRAINER FLEXIBLE CONNECTION STRAINER W/BLOWOFF VALVE EXPANSION JOINT BACKFLOW PREVENTER WATER HAMMER ARRESTER W/ BALL VALVE BFP VALVE IN YARD BOX VACUUM BREAKER AQUASTAT T PRESSURE SWITCH PRESSURE INDICATOR WELL FLOW SWITCH GAUGE COCK PI PS FS PRESSURE REDUCING VALVE PRESSURE/TEMPERATURE TAP GAS PRESSURE REGULATOR AUTOMATIC AIR VENT PRESSURE GAUGE GLOBE VALVE CHECK VALVE GAS COCK BUTTERFLY VALVE CIRCUIT SETTER ASSEMBLY RE: PLUMBING DETAIL BALL VALVE PLUG VALVE GATE VALVE SOLENOID VALVE CALIBRATED BALANCE VALVE MANUAL AIR VENT DIA, D DIAMETER EL. C LC CI AP AFF CENTER LINE ELEVATION ABOVE FINISHED FLOOR ACCESS PANEL COMMON CAST IRON INVERT ELEVATIONI.E. NC NO NIC VITRIFIED CLAY PIPE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN TYPICALTYP VCP VENT THROUGH ROOFVTR THERMOSTATIC MIXING VALVE (E) (R) (N) RELOCATED NEW EXISTING (F)FUTURE DIRECTION OF VIEW M-? 1 DRAWN ON THIS SHEET A PICTURE DESIGNATION NEW LIGHT LINE WEIGHT FOR EQUIPMENT, PIPING, SYMBOLS, TEXT, ETC. INDICATES EXISTING CONDITIONS WITH NEW WORK SHOWN AS DARK POINT OF CONNECTION NEW TO EXISTING DIRECTION OF CUT SECTION DESIGNATION 4" DASHED INDICATES EXISTING TO BE REMOVED STORM/RAINWATER DRAIN ABOVE FLOOR OR GRADE STORM/RAINWATER DRAIN BELOW FLOOR OR GRADE OVERFLOW DRAIN ABOVE FLOOR OR GRADE OVERFLOW DRAIN BELOW FLOOR OR GRADE PIPING TO SAND/OIL INTERCEPTOR BELOW FLOOR OR GRADE HOSE END BALL VALVE WITH VACUUM BREAKER TEMPERATURE/PRESSURE RELIEF VALVE STEAM TRAP (INDICATE TYPE) CLEANOUT, FLOOR (FCO) OR GRADE (GCO) FLOOR SINK; (1/2" GRATE SHOWN) WALL HYDRANT WITH VACUUM BREAKER HOSE BIBB WITH VACUUM BREAKER ABBREVIATIONS AND DESCRIPTIONS ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT PLUMBING LEGEND VALVES AND FITTINGS WORK NOTE SYMBOLW1 REVISION SYMBOL W# PLUMBING RISER REFERENCE RISER NUMBER RISER DESIGNATION D = DOMESTIC WATER G = NATURAL GAS W = WASTE/VENT 1 CIRCUIT SETTER BALL VALVEBALL VALVE CHECK VALVE CIRCUIT SETTER BALANCE VALVE BELL & GOSSETT ITT CIRCUIT SETTER CB LEAD FREE SERIES, OR EQUAL. NOTE: 1. ALL COMPONENTS TO BE NSF 372 (LEAD FREE) COMPLIANT. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 2 6 P M P-001 PLUMBING GENERAL INFORMATION St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM DRAWING LIST - PLUMBING P-001 PLUMBING GENERAL INFORMATION P-002 PLUMBING SPECIFICATIONS P-100 UNDERGROUND PLUMBING PLAN P-200 BASEMENT PLUMBING PLAN P-201 LEVEL 1 PLUMBING PLAN P-202 ROOF PLUMBING PLAN P-501 PLUMBING ISOMETRICS DENVER OFFICE COLORADO SPRINGS OFFICE 10807 NEW ALLEGIANCE DRIVE, SUITE 400 COLORADO SPRINGS, CO 80921 719.533.1112 5420 WARD ROAD, SUITE 200 ARVADA, CO 80002 303.422.7400 TAMPA OFFICE 12450 ROOSEVELT BLVD N., SUITE 305 ST. PETERSBURG, FL 33716 727.685.0458 MELBOURNE OFFICE 6555 N. WICKHAM ROAD, SUITE 104 MELBOURNE, FL 32940 321.241.4142 PROJECT DESIGNER PROJECT MANAGER JUSTIN PATTERSON JPATTERSON@BCER.COM 303.405.2856 PAUL MISKOWICZ PMISKOWICZ@BCER.COM 303.405.2902 CONTACT LIST 18. EQUIPMENT E.E.R. AND/OR C.O.P. SHALL COMPLY WITH ASHRAE 90.1. 17. PROVIDE REDLINE MARKUPS OF ANY FIELD CHANGES OR MODIFICATIONS ON THE CONSTRUCTION DOCUMENTS. REDLINE DRAWINGS SHALL BE REQUIRED WHETHER COORDINATION DRAWINGS ARE REQUIRED OR NOT. 16. IT IS THE PLUMBING CONTRACTORS RESPONSIBILITY TO PROVIDE BACKFLOW PREVENTION AS REQUIRED BY CODE TO ALL PLUMBING, MECHANICAL EQUIPMENT AND IRRIGATION, INCLUDING BUT NOT LIMITED TO COFFEE MAKERS, JUICE MACHINES, TEA BREWERS, ICE MAKERS, LABORATORY HOODS, ETC. 15. PROVIDE BALANCE OF DOMESTIC WATER CIRC LINES TO GPM INDICATED ON DRAWING. 14. ALL THREADED HOSE CONNECTIONS TO DOMESTIC WATER SYSTEM SHALL HAVE AN APPROVED VACUUM BREAKER. IE: HOSE BIBBS, WALL HYDRANTS, SYSTEM DRAINS, EQUIPMENT DRAINS, ETC. 13. PROVIDE WATER HAMMER ARRESTERS AT ALL QUICK CLOSING VALVES WITH ISOLATION VALVE AND WITH ACCESS OR ACCESS PANEL. 12. NATURAL GAS INPUTS ARE AT SEA LEVEL. 11. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN THE PLUMBING SCHEDULES AND AS REQUIRED IN EACH SECTION OF SPECIFICATION TO THE ENGINEER FOR REVIEW PRIOR TO THE ORDER, PURCHASE OR INSTALLATION OF THESE SAME ITEMS. 10. THIS PROJECT IS UNDER THE 2015 ICC CODE SUITE AND SHALL INCLUDE COMMISSIONING OF THE PLUMBING SYSTEMS AS REQUIRED BY SECTION C408 OF THE 2015 IECC. THE PLUMBING CONTRACTOR SHALL INCLUDE EXPENSES IN THEIR BID ASSOCIATED WITH THE COMMISSIONING PROCESS. THESE INCLUDE BUT ARE NOT LIMITED TO ATTENDING COMMISSIONING MEETINGS, COMPLETING PREFUNCTIONAL CHECKLISTS, DEMONSTRATING SYSTEM PERFORMANCE, AND ADDRESSING COMMISSIONING AUTHORITY REVIEW COMMENTS. 9. ALL PLUMBING SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE CODES LISTED ON THIS SHEET AND THE ARCHITECTURAL CODE PLAN. 8. CONTRACTOR SHALL FIELD VERIFY ALL PLUMBING ITEMS PRIOR TO COMMENCING NEW WORK. NO ADDITIONAL COST WILL BE ALLOWED FOR CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. 7. CONTRACTOR SHALL CLOSELY COORDINATE NEW PLUMBING WITH ALL NEW AND EXISTING MECHANICAL, PLUMBING, ELECTRICAL, FIRE PROTECTION, ARCHITECTURAL AND STRUCTURAL MEMBERS. REFER TO DIVISION 22 FOR CEILING SPACE ALLOCATION PRIORITIES. 6. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATION AND INSTALLING SLEEVES, INSERTS AND SUPPORTS AS REQUIRED FOR THIS SCOPE OF WORK AND/OR CORE DRILL REQUIREMENTS. COORDINATE WITH GENERAL CONTRACTOR AND STRUCTURAL ENGINEER AS REQUIRED. 5. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY DIRECTED OTHERWISE. 4. CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL DOWNTIME WITH OWNER'S PERSONNEL. CONTRACTOR SHALL PROVIDE A DETAILED M.O.P. AS REQUIRED. DO NOT BEGIN WORK WITHOUT WRITTEN APPROVAL. 3. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN INTENT, ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE AS SHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS ARE REQUIRED FOR FIELD COORDINATION OF ALL TRADES, THIS CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL COSTS. 2. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAVE BEEN SELECTED AS THE BASIS DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATED BY THE CONTRACTOR FOR SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS AND PERFORMANCE. 1. DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY. W HATEVER IS CALLED FOR IN EITHER IS BINDING AS THOUGH CALLED FOR IN BOTH. PLUMBING GENERAL NOTES THIS PROJECT CONSISTS OF RENOVATIONG THE EXISTING STANLEY CARRIAGE HOUSE INTO A RESTAURANT. PROJECT NARRATIVE FLOW RATE (GPM): NEED FLOW TEST RESIDUAL PRESSURE: NEED FLOW TEST STATIC PRESSURE: 150 PSI DATE: NEED FLOW TEST LOCATION: NEED FLOW TEST [MODEL FLOW TEST]: NEED FLOW TEST [ACTUAL FLOW TEST]: NEED FLOW TEST INFORMATION PROVIDED BY: ESTES PARK WATER DISTRICT CITY WATER FLOW TEST INFORMATION PRELIMINARY DESIGN INFORMATION AND LOCAL AMENDMENTS 2020 NATIONAL ELECTRICAL CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL BUILDING CODE ADOPTED/ENFORCED CODES REQUIRED PLUMBING FIXTURE SCHEDULE PLAN CODE DESCRIPTION LOCATION FIXTURE FLUSH VALVE / FAUCET GPF/GPM FIXTURE MOUNTING HEIGHT A.F.F. REMARKS MFGR. MODEL MOUNTING STYLE FIXTURE INSTALLED MFGR. MODEL FIXTURE INSTALLED STYLE MFGR. MODEL MFGR. MODEL WH-1 WALL HYDRANT EXTERIOR LOCATIONS - - WALL WOODFORD B22 LOOSE KEY RE: ARCH DWGS WH-2 WALL HYDRANT EXTERIOR LOCATIONS - - WALL WOODFORD B67 LOOSE KEY RE: ARCH DWGS FD-1 FLOOR DRAIN FINISHED AREAS JAY R. SMITH 2005Y-A05SS FLOOR (1) FS-1 FLOOR SINK KITCHEN JAY R. SMITH 3001Y-12 FLOOR (1)(2)(3) (2) PROVIDE WITH S.S. 1/2 GRATE. (1) PROVIDE WITH TRAP SEAL DEVICE ASSE 1072 APPROVED.(3) PROVIDE WITH BOTTOM DOME STRANER. THERMOSTATIC MIXING VALVE SCHEDULE PLAN CODE MFGR. MODEL INSTALLED SERVICE MINIMUM FLOW (GPM) FLOW (GPM) @ 10 PSI P.D. INLET TEMP. °F OUTLET TEMP. °F ASSE STANDARD REMARKS MFGR. MODEL TMV-1 LEONARD 170A-LF POINT OF USE 0.25 1.25 140 110 1070 (1)(2) TMV-2 LEONARD 270-LF-STSTL REC POINT OF USE 0.25 5.5 140 90 1070 (1)(2) (2) ALL MIXING VALVES TO HAVE CHECK VALVES ON BOTH HOT AND COLD SUPPLIES. SOME UNITS HAVE INTEGRAL CHECK VALVES. VERIFY EACH LOCATION HAS CHECK VALVES. (1) LOCATE IN ACCESSIBLE LOCATION OR PROVIDE ACCESS DOOR. BACKFLOW PREVENTER ASSEMBLY SCHEDULE PLAN CODE TYPE SYSTEM MFGR. MODEL INSTALLED QUANTITY LINE SIZE (INCHES) PRESSURE DROP (PSIG) MIN. FUNNEL DRAIN SIZE REMARKS MFGR. MODEL BFP-1 DUAL CHECK BEVERAGE WATTS SD-3 3 3/8" 10 - (1)(2)(3) (2) PROVIDE TESTING AND CERTIFICATION IN ACCORDANCE WITH COLORADO REQUIREMENTS. (1) ASSE 1022 APPROVED.(3) REFER ALSO TO DETAIL. NOT TO SCALE 2 BALANCE VALVE ASSEMBLY DETAIL NOT TO SCALE 1 BACKFLOW PREVENTER DETAIL NOT TO SCALE 3 T.I. NATURAL GAS SCHEMATIC 4.00 4910 0.99 4860.90 3.00 2410 0.99 2385.90 2.50 1360 0.99 1346.40 2.00 854 0.99 845.46 1.50 443 0.99 438.57 1.25 296 0.99 293.04 1.00 144 0.99 142.56 0.75 77 0.99 76.23 0.5 175 P.D. (5) L.F. (6) Pipe Size (inch) Pipe capacity CFH Based... Specific Gravity Factor (7) Actual CFH Low Pressure Pipe Sizing Chart Total Equivalent Length:172.5 Lineal Feet (5) Equivalent Length Factor:x 1.5 Measured Distance of Pipe: (4) 115 Total CFH:3,465.8 CFH Gas Heating Value:803 BTU/CF (3) Total BTUH:2,783,000 Totals 2,783,000 1 MAU-1 363 7"-14" 363,000 452.1 1 RTU-1 150 4"-13" 150,000 186.8 1 B-1 85 6"-8" 85,000 105.9 1 DOAS-1 445 6"-8" 445,000 554.2 1 DWH-1 500 6"-8" 500,000 622.7 1 FIRE PIT 200 6"-8" 200,000 249.1 1 FIREPLACE 60 6"-8" 60,000 74.7 1 FIREPLACE 60 6"-8" 60,000 74.7 3 FS EQUIP NUM #136 100 6"-8" 300,000 124.5 1 FS EQUIP NUM #130 40 6"-8" 40,000 49.8 1 FS EQUIP NUM #129 60 6"-8" 60,000 74.7 1 FS EQUIP NUM #128 132 6"-8" 132,000 164.4 1 FS EQUIP NUM #127 198 6"-8" 198,000 246.6 1 FS EQUIP NUM #125 90 6"-8" 90,000 112.1 1 FS EQUIP NUM #124 100 6"-8" 100,000 124.5 Quantity Equipment MBH/Unit @ S.L. (1) Required W.C. (2) Total BTUH CFH (Each Unit) Gas Heating Value (3)803 BTU/CF Specific Gravity (3)0.61 (Note: Shaded areas require engineer's input) Natural Gas Sizing For Building Mains - Low Pressure NOT TO SCALE 4 SINK ISOMETRIC - DIRECT CONNECTION NOT TO SCALE 5 SINK ISOMETRIC - INDIRECT CONNECTION REVISION DATE ASI-T01 02.12.2021 ASI-T04 03.17.2021 1 03/22/21 220000 - BASIC PLUMBING REQUIREMENTS GENERAL A.SEE ARCHITECTURAL SPECIFICATION FOR GENERAL CONDITIONS. B. PROVIDE ALL ITEMS FOR COMPLETE AND SUCCESSFUL OPERATION OF ALL PLUMBING SYSTEMS. C.DRAWINGS ARE DIAGRAMMATIC ONLY. FOLLOW DRAWINGS AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHER TRADES WILL PERMIT. D. VISIT SITE AND INCLUDE ALLOWANCE IN BID FOR ALL COSTS RELATED TO THE MECHANICAL INSTALLATION. E. DEMONSTRATE THE OPERATION OF ALL SYSTEMS FOR THE OWNER AT A TIME AS DIRECTED BY THE OWNER. F. LAY OUT ALL WORK IN ADVANCE. DO NOT DEFACE WORK OF OTHER TRADES. INSTALL ALL SLEEVES AND BLOCKOUTS; WATERPROOF AS REQUIRED. FIRESTOP ALL FLOOR AND RATED WALL PENETRATIONS. G.FIELD CHECK ALL EXISTING CONDITIONS AND INCLUDE AN ALLOWANCE IN BID FOR REMOVAL AND/OR RELOCATION OF EXISTING PIPING, DUCTWORK, EQUIPMENT, ETC., AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING MECHANICAL SYSTEMS TO ALL OTHER WORK. EXISTING PIPING AND MATERIAL WHICH SHALL BE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR, EXCEPT EQUIPMENT SO NOTED, WHICH SHALL BECOME THE PROPERTY OF THE OWNER. H. RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTAIN A MARK-UP SET OF DRAWINGS WHICH INDICATE VARIATIONS IN THE ACTUAL INSTALLATION FROM THE ORIGINAL DESIGN. TURN OVER DRAWINGS TO OWNER/ARCHITECT UPON PROJECT COMPLETION. A.ALL PLUMBING MATERIALS SHALL BE NEW, IN FIRST CLASS CONDITION, AND U.L. LISTED WHERE APPLICABLE. B. COMPLY WITH ALL APPLICABLE LOCAL AND STATE ORDINANCES. COMPLY WITH 2015 INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL PLUMBING CODE, AND NATIONAL FIRE PROTECTION ASSOCIATION IN EFFECT FOR THIS C.PROCURE AND PAY FOR ALL PERMITS, DEVELOPMENT FEES, LICENSES, AND LIABILITY INSURANCE, ETC. FURNISH CERTIFICATE OF FINAL INSPECTION AND APPROVAL FROM LOCAL INSPECTOR. D. MATERIAL SHALL BE AS SPECIFIED, AND/OR NOTED ON THE CONTRACT DRAWING. E. ALL MATERIALS AND EQUIPMENT LOCATED IN AIR PLENUMS SHALL BE RATED FOR PLENUM APPLICATION. F. ALL PLUMBING WORK SHALL BE PERFORMED BY A STATE OF COLORADO LICENSED CONTRACTOR UNDER THE SUPERVISION OF A LICENSED PLUMBER. A.REPLACE ANY WORK OR MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FOR NORMAL WEAR, WITHIN ONE (1) YEAR AFTER CERTIFICATE OF COMPLETION IS SECURED. 220500 - BASIC MATERIALS AND METHODS GENERAL WORK INCLUDED A.REMOVALS AND/OR RELOCATION OF EXISTING PLUMBING PIPES, INSULATION, FIXTURES, AND OTHER ASSOCIATED EQUIPMENT AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING PLUMBING SYSTEMS TO ALL OTHER WORK. B. EXCAVATION AND BACKFILLING WORK SHALL INCLUDE REMOVAL AND DISPOSAL OF ALL DEBRIS; EXCAVATION AND TRENCHING AS REQUIRED; THE HANDLING, STORAGE, TRANSPORTATION AND DISPOSAL OF ALL EXCAVATED MATERAL; ALL NECESSARY SHEETING, SHORING AND PROTECTION WORK; BACKFILLING; PIPE EMBEDMENT AND OTHER APPURTENANT WORK. EXCAVATION WORK SHALL BE PERFORMED IN A SAFE AND PROPER MANNER WITH APPROPRIATE PRECAUTIONS AGAINST ALL HAZARDS. EXCAVATIONS SHALL PROVIDE ADEQUATE WORKING SPACE AND CLEARANCES FOR THE WORK TO BE PERFORMED THEREIN. C.IF HAZARDOUS MATERIAL (I.E. ASBESTOS, LEAD-BASED PAINT, ETC.), IN ANY FORM, IS DISCOVERED BY THIS CONTRACTOR IN THE PROCESS OF THEIR WORK, THEY SHALL REPORT SUCH OCCURRENCE TO THE ARCHITECT IMMEDIATELY FOR RESOLUTION. WORK INCLUDED IN THIS SECTION A.COMPLETE INSTALLATIONS OF NEW PLUMBING FIXTURES AND TRIM, ASSOCIATED WASTE, VENT, AND HOT AND COLD WATER PIPING, INCLUDING ALL NEW CONNECTIONS TO EXISTING WASTE AND VENT STACKS AND EXISTING COLD/HOT/HOT RECIRCULATION WATER PIPING, INSULATION, HANGERS AND SUPPORTS, TO MAKE ALL SYSTEMS COMPLETE AND OPERATIONAL. B. BRANCH LINES AND FIXTURE CONNECTION SIZES SHALL BE AS SHOWN AND AS RECOMMENDED BY THE FIXTURE MANUFACTURER. PROVIDE HOSE BIBB WITH CAP AT ALL WATER SYSTEM LOW POINTS FOR EASY DRAINING. C.PROVIDE ALL REQUIRED INDIRECT DRAINS WITH AN AIR GAP TWICE THE DIAMETER OF THE INDIRECT PIPE. D. PROVIDE PIPE SLEEVES BY COMMERCIAL MANUFACTURER OF SUCH SLEEVES. E. PROVIDE EXPANSION AND CONTRACTION METHODS AND SYSTEMS SUBMITTALS ON ALL PIPING, SANITARY WASTE AND VENT, STORM DRAINAGE, DOMESTIC HOT AND COLD AND RECIRCULATION PIPING. EXPANSION AND CONTRACTION METHODS SHALL BE BASED ON PIPING MANUFACTURERS SELECTED AND SUCH MANUFACTURERS REQUIREMENTS. F. PROVIDE UL LISTED FIRESTOPPING SYSTEMS COMPOSED OF COMPONENTS THAT ARE COMPATIBLE WITH EACH OTHER, THE SUBSTRATES FORMING OPENINGS, AND THE ITEMS, IF ANY, PENETRATING THE FIRESTOPPING UNDER CONDITIONS OF SERVICE AND APPLICATION, AS DEMONSTRATED BY THE FIRESTOPPING MANUFACTURER BASED ON TESTING AND FIELD EXPERIENCE. G.PROVIDE COMPONENTS FOR EACH FIRESTOPPING SYSTEM THAT ARE NEEDED TO INSTALL FILL MATERIAL. USE ONLY COMPONENTS SPECIFIED BY THE FIRESTOPPING MANUFACTURER AND APPROVED BY THE QUALIFIED TESTING AGENCY FOR THE DESIGNATED FIRE-RESISTANCE-RATED SYSTEMS. H. PENETRATIONS IN FIRE RESISTIVE RATED WALLS: PROVIDE FIRESTOPPING WITH RATINGS DETERMINED IN ACCORDANCE WITH UL 1479 OR ASTM E 814, AND NOT LESS THAN THE FIRE-RESISTANCE RATING OF THE WALL CONSTRUCTION BEING PENETRATED. I. PENETRATIONS IN HORIZONTAL ASSEMBLIES: PROVIDE FIRESTOPPING WITH RATINGS DETERMINED IN ACCORDANCE WITH UL 1479 OR ASTM E 814, AND NOT LESS THAN THE FIRE-RESISTANCE RATING OF THE FLOOR CONSTRUCTION BEING PENETRATED. J. PENETRATIONS IS SMOKE BARRIERS: PROVIDE FIRESTOPPING WITH RATINGS DETERMINED IN ACCORDANCE WITH UL 1479 OR ASTM E 814. K. FIREAND SMOKE BARRIER PENETRATION SEAL MANUFACTURERS: ELECTRIC PRODUCTS DIVISION/3M, DOW CORNING, FLAME STOP INC., METACAULK, HILTI. 220523 GENERAL DUTY VALVES FOR PLUMBING PIPING A.VALVES SHALL BE NSF/ANSI 372 COMPLIANT FOR POTABLE WATER SERVICE. VALVES FOR DOMESTIC WATER SHALL BE 3RD PARTY CERTIFIED. B.BALL VALVES (LESS THAN OR EQUAL TO 2-1/2 INCH): MSS-SP-110, 600 CWP, TWO-PIECE ASTM B-584 LEAD-FREE CAST BRONZE BODY, FULL PORT, CHROME PLATE BALL, PTFE SEATS, ANTI-BLOWOUT EXTENDED STEM, SEPARATE PACKNUT WITH ADJUSTABLE STEM PACKING, VINYL COVERED STEEL LEVER HANDLE AND THREADED OR SOLDERED ENDS. VALVE SHALL BE NSF/ANSI 372 COMPLIANT. NIBCO MODEL T/S-585-80-LF-EL. C. CHECK VALVES: SWING CHECK VALVES 2-1/2 INCH AND SMALLER, MSS-SP-80, OR MSS-SP-139 PRESSURE RATING 200 CWP, ASTM B-584 LEAD-FREE BRONZE BODY AND BONNET, HORIZONTAL SWING DESIGN, Y PATTERN WITH TFE SEAT DISC, THREADED OR SOLDERED END CONNECTIONS, NSF/ANSI 372 COMPLIANT, NIBCO MODEL T/S-413-Y-LF OR EQUAL. D.DRAIN VALVES SHALL COMPLY WITH NSF/ANSI 372 FOR LEAD-FREE. VALVE SHALL BE EQUIPPED WITH A THREADED HOSE END WITH CAP AND CHAIN. NIBCO MODEL T/S-585-66-LF-HC-EL. E.STRAINERS: LEAD-FREE BRONZE BODY (ASTM B-584) WITH 20 MESH STAINLESS STEEL SCREEN, NSF/ANSI 372 COMPLIANT. WILKENS MODEL YBXL OR EQUAL. F. BALANCING/FLOW VALVES: 200 PSI, LEAD-FREE BRASS BODY, STAINLESS STEEL BALL, TFE SEATS. BLOWOUT PROOF STEM WITH EPDM “O” RING, VALVED READOUT PORTS, WITH HANDLE AND MEMORY STOP. “BELL & GOSSETT ITT CIRCUIT SETTER CB LEAD-FREE SERIES”, OR EQUAL. 220553 IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT A.PROVIDE MECHANICAL IDENTIFICATION FOR ALL NEW PIPING AND EQUIPMENT. IDENTIFICATION SHALL BE BY SETON OR BRADY AND CONSIST OF THE FOLLOWING: 1. BRASS VALVE TAGS WITH STAMPED LETTERS SHALL BE PROVIDED FOR ALL VALVES. SECURE TO THE VALVE WITH CHROME PLATED BALL CHAINS. PROVIDE FRAMED VALVE TAG SCHEDULE WITH GLASS FACE TO OWNER. 2. IDENTIFY ALL NEW PIPING AND EQUIPMENT WITH PAINTED STENCILS, PLASTIC PIPE MARKERS OR PLASTIC TAPE MARKERS. MARKERS SHALL INDICATE TYPE OF SERVICE AND DIRECTION OF FLOW. 3. ALL IDENTIFICATION SHALL CONFORM WITH ANSI A13.1. 220700 - PLUMBING INSULATION A.MANUFACTURERS: OWENS-CORNING; JOHNS-MANVILLE, CORP.; MANSON INSULATION CO.; ARMSTRONG; OR EQUAL. B. PLUMBING PIPING TO BE INSULATED AS FOLLOWS: 1. DOMESTIC COLD WATER. 2. DOMESTIC HOT WATER. 3. DOMESTIC HOT CIRCULATING WATER. C.INSULATION SHALL BE SNAP-ON TYPE, FIBERGLASS PIPE INSULATION, WITH WHITE SELF-SEALING FLAME RETARDANT VAPOR BARRIER JACKET. ALL VALVES AND FITTINGS SHALL BE INSULATED. 1. COLD WATER PIPING: ½-INCH THICKNESS UP TO AND INCLUDING 1-1/4 INCH PIPE SIZE, 1 INCH THICKNESS FOR 1-1/2 INCH PIPE SIZE AND LARGER. 2. HOT WATER AND HOT WATER RECIRCULATION PIPING, CONDENSATE PIPING: 1-INCH THICKNESS UP TO AND INCLUDING 1-1/4 INCH PIPE SIZE, 1-1/2 INCH THICKNESS FOR 1-1/2 INCH PIPE SIZE AND LARGER. D. INSULATION SHALL MEET ALL CODE REQUIREMENTS AND FIRE AND SMOKE HAZARD RATINGS AS TESTED BY PROCEDURE ASTM E-84, NATIONAL FIRE PROTECTION ASSOCIATION 255 AND U.L. 723, NOT EXCEEDING FLAME SPREAD 25 AND SMOKE DEVELOPED 50 RATINGS. E. PROVIDE 360 CALCIUM SILICATE INSERTS AT ALL INSULATED HANGER LOCATIONS. PROVIDE 180 DEGREE GALVANIZED STEEL SADDLES. 221116 DOMESTIC WATER PIPING A.DOMESTIC COLD AND HOT WATER WITHIN THE BUILDING ABOVE GRADE, COPPER WATER TUBE, ASTM B88 AND CONFORM TO THE LEAD-FREE STANDARDS, TYPE “L”, HARD DRAWN, CAST BRONZE OR WROUGHT COPPER FITTINGS, SOLDER JOINT TYPE, USING ONLY LEAD-FREE SOLDER, ASTM b32, MINIMUM TENSILE STRENGTH OF 5,900 PSI, CERTIFIED TO MEET NSF 372. B. PROVIDE NON-CONDUCTING DIELECTRIC FITTINGS OR DIELECTRIC WATERWAY COUPLINGS WHEN JOINING PIPE OF DISSIMILAR METALS. C.ADJUSTING , CLEANING AND BALANCING 1. CLEAN AND DISINFECT WATER DISTRIBUTION PIPING AS FOLLOWS: a. PURGE ALL NEW WATER DISTRIBUTION PIPING SYSTEMS. CLEAN AND REPLACE STRAINERS. VERIFY ALL FAUCET AERATORS ARE OPERATIONAL AS DESIGNED. b. USE THE PURGING AND DISINFECTING PROCEDURE PRESCRIBED BY THE AHJ, OR IN THE CASE A METHOD IS NOT PRESCRIBED BY THE AHJ, THE PROCEDURE SHALL BE AS REQUIRED BY AWWA C651 OR AWWA C652 OR DESCRIBED IN THE PREVAILING CODE. 2. ADJUST AND BALANCE DOMESTIC HOT WATER CIRCULATION TO GPM INDICATED ON DRAWINGS. 221119 DOMESTIC WATER PIPING SPECIALTIES A.IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE BACKFLOW PREVENTION AS REQUIRED BY CODE TO PREVENT CROSS-CONNECTION BETWEEN THE POTABLE WATER SYSTEM AND ANY SOURCE OF POLLUTION OR CONTAMINATION. THIS APPLIES TO ALL PLUMBING, MECHANICAL EQUIPMENT AND IRRIGATION. B. CONTRACTOR SHALL PROVIDE WATER-HAMMER ARRESTORS IN ACCESSIBLE LOCATION OR PROVIDE ACCESS PANEL WHERE QUICK-CLOSING VALVES ARE UTILIZED. LEAD-FREE WATER-HAMMER ARRESTOR SHALL CONFORM TO ASSE 1010 AND NSF ANSI 372. 221123 NATURAL GAS SYSTEMS A. NATURAL GAS PIPING EXPOSED LOCATIONS ABOVE GRADE, 2-INCH AND SMALLER, ASTM A 53 GRADE B, TYPE E SCHEDULE 40 BLACK STEEL, MALLEABLE IRON THREADED FITTINGS AND MALLEABLE THREADED UNIONS. 2-1/2 INCH AND LARGER PIPE, ASTM A 53 GRADE B TYPE S, SCHEDULE 40 SEAMLESS BLACK STEEL PIPE, FORGED STEEL SOCKET WELDED OR WROUGHT STEEL BUTT-WELDED FITTINGS. CONCEALED LOCATIONS SHALL HAVE WELDED JOINTS AND FITTINGS. C. BALL VALVES (NATURAL GAS): UP TO 2-INCH, BRASS BODY, ASME B16.33 (125 PSI) OR B I6.44 (5 PSI). 2-INCH TO 4-INCH, ASME B16.44 (5 PSI). APOLLO MODEL 94A OR EQUAL. VALVES SHALL BE LABELED WITH THE LISTING ORGANIZATION. D. LUBRICATED PLUG VALVES (NATURAL GAS): UP TO 6-INCH, IRON BODY PLUG VALVE. LISTED AND LABELED WITH CGA AND OR UL. MANUFACTURERS: HOMESTEAD, NORDSTROM OR EQUAL. 221316 SANITARY WASTE & VENT PIPING A. ABOVE GROUND: NO-HUB CAST IRON SERVICE WEIGHT, CISPI 301, WITH JOINTS MADE OF NEOPRENE GASKETS AND CISPI 310 STAINLESS STEEL CLAMP AND SHIELD ASSEMBLIES WITH NSF LISTING. B. BELOW GROUND: SERVICE WEIGHT CAST IRON, CLASS B, ASTM A74, HUB AND SPIGOT, CISPI HSN COMPRESSION TYPE WITH ASTM C564 NEPRENE GASKETS. 2. ACCEPTABLE CAST IRON MANUFACTURERS: a. TYLER b. AB & I c. CHARLOTTE C. BELOW GROUND: IRON PIPE SIZE (IPS) POLYVINYL CHLORIDE (PVC) SOLID WALL SCHEDULE 40 DWV, SOLID WALL CONFORMING TO ASTM D-1784 AND ASTM D-2665. FITTINGS: ASTM D-2665, PVC, SOLVENT CEMENT WITH LONG SWEEP BENDS. JOINING MATERIAL: SOLVENT CEMENT CONFORMING OF ASTM-2564 SUITABLE FOR TYPE AND SIZE OF PIPE INSTALLED AS RECOMMENDED BY THE PIPE MANUFACTURER. BELOW GROUND PIPING SHALL BE INSTALLED IN ACCORDANCE TO ASTM D 2321 AND ASTM F 1668.] 1. ACCEPTABLE PVC MANUFACTURERS: a. CHARLOTTE b. SPEARS c. HARVEL d. CRESLINE 221319 SANITARY WASTE PIPING SPECIALTIES A.CLEANOUTS 1. PROVIDE CLEANOUTS WHERE SHOWN ON THE DRAWINGS AND AT ALL BENDS GREATER THAN 45 DEGREES. CLEANOUTS SHALL BE SPACED AT NOT OVER 50-FEET APART IN ANY LINEAL RUN OF PIPING. CLEANOUTS SHALL BE ACCESSIBLE: IF NOT, THEY SHALL BE EXTENDED TO THE FLOOR ABOVE AND PROVIDED WITH CHROME WALL PLATE OR WHERE INSTALLED IN THE FLOOR A NICKEL BRONZE FLOOR COVER SHALL BE USED. 2. CLEANOUTS TO BE FULL SIZE OF THE PIPE LINE WHICH THEY ARE INSTALLED UP TO AND INCLUDING 4-INCH SIZE. e. ACCEPTABLE MANUFACTURERS: i. JOSAM ii. ZURN iii. JAY R. SMITH iv. WADE 223300 PLUMBING FIXTURES A. PLUMBING FIXTURES AND ASSOCIATED TRIM, SUPPORTS AND EQUIPMENT SHALL BE BASED UPON PRODUCTS MANUFACTURED BY THE FOLLOWING MANUFACTURERS. SEE PLUMBING EQUIPMENT SCHEDULE FOR DETAILED DESCRIPTION OF EACH FIXTURE: 1. TRAPS, LEAD-FREE STOPS AND SUPPLIES, DRAINS, AIR GAPS. P-TRAPS TO BE PROVIDED WITH CLEANOUT PLUG AND TO BE MINIMUM 17 GAUGE. ESCUTCHEONS ON WASTE ARMS TO FIT SNUG TO WALL. STOPS AND SUPPLY TUBES SHALL CONFORM NSF/ANSI 372 a. BRASSCRAFT b. OR EQUAL 2. ADA SINK/LAVATORY PIPE INSULATION a. TRUEBRO b. PLUMBEREX PRO-EXTREME SERIES c. DEARBORN-SAFETY SERIES d. MCGUIRE - PROWRAP ADA SEAMLESS INSULATOR B. BELOW GRADE OUTSIDE BUILDINGS: CSST - AS MANUFACTURED BY OMEGAFLEX, TRACPIPE, PSII UNDERGROUND PIPING SHALL CONSIST OF 300 TYPE STAINLESS STEEL CSST WITH AN INTEGRAL POLYETHYLENE SLEEVE. THE SLEEVE SHALL HAVE INTERNAL VENT CHANNELS RUNNING LENGTHWISE TO DIRECT ANY LEAKAGE ALONG THE PIPE TO THE END FITTING. TERMINATE WITH END FITTINGS ABOVE GRADE. END FITTINGS SHALL HAVE A ¼-INCH VENT PORT. FITTINGS ARE NOT ALLOWED BELOW GRADE. PIPING SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURERS REQUIREMENTS. CSST PIPING SHALL BE LISTED IN ACCORDANCE WITH ANSI LC 1/CSA 6.26. B. TRAP SEAL UNITS 1. TRAP SEAL UNIT FITS 2 TO 4-INCE FLOOR DRAINS. INSTALLATION SHALL NOT REQUIRE SPECIAL TOOLS OR SILICON SEALANT. LISTED TO THE REQUIREMENTS OF ASSE 1072, MANUFACTURED BY SURE SEAL COMPANY - RECTORSEAL, OR EQUAL. 1. ACCEPTABLE MANUFACTURES: a. PPP INC. b. SIOUX CHIEF c. WATTS C. TEMPERED WATER SHALL BE PROVIDED TO ALL PUBLIC HAND WASHING FACILITIES. CONTRACTOR SHALL PROVIDE AN APPROVED WATER -TEMPERATURE LIMITING DEVICE CONFORMING TO ASSE 1070 AND NSF 61 ANNEX G AND/OR NSF 372, INSTALLED IN AN ACCESSIBLE LOCATION. 1. ACCEPTABLE MANUFACTURERS: a. POWERS b. LEONARD c. SYMMONS SPECIFICATIONS © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 2 6 P M P-002 PLUMBING SPECIFICATIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM REVISION DATE ASI-T04 03.17.2021 03/22/21 4 3 2 1 AC DE (E)2"PD UP (E)SP-1 (E)4"BD (E)4"W UP TO WCO (E)2"V UP (E)3"W UP TO MSB (E)2"W UP TO (E)FD(E)2"W UP TO (E)FD (E)2"V UP (E)3"SD UP TO (E)AD (E)3"SD UP TO (E)AD (E)3"SD 3"SD (E)3"SD UP TO (E)AD IE=83.47' (E)2"W UP TO (E)UR (E)2"W UP TO (E)UR (E)3"W UP TO (E)FD (E)3"W UP TO (E)FS (E)2"V UP (E)4"W UP TO (E)FS (E)4"BD (E)2"V UP(E)4"W UP TO (E)FS (E ) 4 " B D (E)ESP (E)2"PD UP B IE=85.96' IE=85.10' P1 IE=85.50' (E)3"W UP TO (E)FS IE=84.23' IE=86.50' (E)2"V UP (E)3"SD (E)3"SD UP TO FCO (E)3"SD UP TO FCO (E ) 3 " S D (E)4"BD (E)4"BD (E)4"BD (E)4"W UP (E)3"W UP (E)3"W UP (E)3"W UP (E ) 4 " B D (E)3"BD (E)2"V UP (E)4"BD 3" B D 3"W UP 3"V UP 3"W UP 3"W UP TO FS-1 3" B D (E ) 4 " B D (E)2"CW UP 4"W UP (E)4"BD (E)2"W UP (E)3"W UP (E)4"W UP (E)4"W UP TO WCO (E)2"W UP (E ) 2 " B D (E)4"BD © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 2 8 P M P-100 UNDERGROUND PLUMBING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM N 0 8'8' 4' 1/4" = 1'-0" 1 UNDERGROUND PLUMBING PLAN 2. BUILDING AND STORM DRAIN TO BE SLOPED AT 1/8"/FT. 1. GREASE WASTE TO BE SLOPED AT 1/4"/FT. GENERAL NOTES WORK NOTES P1 REFER TO EXISTING CIVIL DRAWINGS FOR CONTINUATION. EXISTING PIPING TO REMAIN. REVISION DATE ASI-T01 02.12.2021 ASI-T04 03.17.2021 1 03/22/21 (E)MSB M BFP (E)DET (E)DCP-1 BFP TMV-14 3 2 1 AC DE (E)2"FD (E)2"FD (E)SP-1 (E)3"FD (E)3" (E)3/4" (E)2" (E)2 1/2" P3 (E)2"V DN (E)1/2" (E)2" (E)3"AD (E)3"AD (E)3"AD MAU-1 (E)DOAS-1 IE=92.00' (E)4"FS G G 4" (E)3"FS (E)2"V DN IE=95.00' P1 (E)2"PD DN (E ) 2 " P D (E)2" IE=98.00' P1 (E)4"SD (E)1 1/2"CW G G (E)2"V DN (E)1 1/4" (E)4"W DN (E)2"PD DN (E ) 2 " P D P1 (E)DWH-1 B (E)3" (E)B-1 (E)HB (E)3/4"CW DN (E)2"V DN (E)3"FS (E)2" (E)2" G (E)4" (E)4" (E)1 1/4" (E)4"G UP P1 P1 (E)3"SD UP (E)LCO P1 (E)4"FS (E)3"FCO (E)3"FS (E)4"FCO (E)2"V DN (E)3"FD IE=92.00' P21 (E)3"FCO (E)2" (E)2"V UP(E)2"V UP (E)2"(E)BFP-1 (E)BFP-2 (E)BFP-3 (E)2"V(E)2"V G UP (E)LAV (E)TMV (E)LAV (E)TMV (E)UR (E)UR (E)WC (E)WC (E)WC (E)WC (E)WC (E)WC (E)1/2" P4 P4P4 2"W UP TO FS-1 2"W UP TO FS-12"W UP TO FS-1 2"W UP TO FS-1 2"W UP TO FS-1 2"W UP TO FS-1 P4 1/2"CW UP 1/2"HW-140° UP 2"W UP TO FS-1 2"W UP 2"V UP 2"W UP TO FS-1 4"LCO (E)LCO 4" W 3/4" 1" 1" 4"LCO P12 4"LCO 1/2" 1/2" 1/ 2 " 1/ 2 " 1/ 2 " 3" V P6 1" 1" 1/ 2 " P16 3/ 4 " C W 3/4"CW UP 2"W UP TO FD-1 2"W UP TO FD-1 2"W UP TO FD-1 2"W UP TO FD-1 2"W UP TO FD-1 1"HW-140° 1"CW 1" 1/ 2 " 1" 2"G 2"G 1 "C W P18 1/2"CW UP 1/2"CW UP P4 2"W UP 3"V 3"V UP 3"V 3"FS-13"FS-1 1/2"CW DN 1/2" 3/4" 1/ 2 " 1/ 2 " 1/ 2 " 1/ 2 " 1/ 2 " (E)4"G LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 ELEV. B10 COOLER 005 FREEZER 006 OFFICE 001 WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A LOUNGE B02 PLATFORM B02B LOBBY B01 TI STORAGE 010 3/4"G UP 3/4"G UP BAR B03 P20 2"W UP 3"W 4"LCO 4"W 4"W 4"W 2"W UP TO 2"FD-1 2"W UP TO FS-1 4" W 4" W 2"V UP 4"W DN 2"W UP 3"LCO 3"W 3"W 3"V UP 4"WCO 2"W UP TO FS-1 2"W UP 4"LCO 4"GW (E ) 4 " G W 4"GW 4"W 4"GW UP TO FS-1 2"W UP 2"V UP 4"W4"W 2"GW UP TO FS-1 2"W UP TO FD-1 3"GW UP TO FS-1 2"W UP TO FS-1 2"W UP TO FD-1 4"LCO 4"GW (E)4"GW DN 1/ 2 " 1/2"HW-140° DN (E)1/2"HWC (E)1 1/4"HW (E)2"CW (E ) 1 / 2 " (E)3/4" (E)3/4" (E)3/4" (E)3/4"(E)1" (E)1/2" (E)2"V (E)2"V (E)WC (E)LAV (E)WB 3(E)WB © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 3 2 P M P-200 BASEMENT PLUMBING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM 1. CONTRACTOR TO REVIEW FOOD SERVICE DRAWINGS AND MAKE FINAL CONNECTIONS BASED ON EQUIPMENT SPECIFICATIONS. GENERAL NOTES N 0 8'8' 4' 1/4" = 1'-0" 1 BASEMENT PLUMBING PLAN WORK NOTES P1 REFER TO EXISTING CIVIL DRAWINGS FOR CONTINUATION. EXISTING PIPING TO REMAIN. P3 (E)3"V, 2"CW, 2"HW, 1/2"HWC UP. P4 1/2"CW/HW UP TO FIXTURE, REFER TO FOOD SERVICE DRAWINGS FOR CONNECTION INFORMATION. P6 SET TO 0.5 GPM. P12 UNDERGROUND NATURAL GAS PIPING TO BE CSST. REFER TO LEVEL 1 PLUMBING PLAN FOR LOCATION. P16 EXISTING FLOOR SINK TO RECEIVE CONDENSATE DRAINAGE, REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. P18 (E)1"CW TO SERVE MAU-1. P20 3/4"CW/HW, 1/2"HWC STUBOUT FOR FUTURE, PROVIDE WITH VALVE AND CAP. P21 REFER TO EXISTING CIVIL DRAWINGS FOR CONTINUATION (E)4"GW PIPING TO EXISTING 2000 GALLON GREASE INTERCEPTOR. EXISTING PIPING TO REMAIN. REVISION DATE ASI-T01 02.12.2021 ASI-T04 03.17.2021 1 1 1 1 03/22/21 C H D D D C V V G G G GG V CC 14 x 4 8 D D G 24x60 3" M TMV-1 TMV-1 TMV-1 TMV-1 BFP TMV-1 TMV-2 TMV-1 BF P TMV-1 4 3 2 1 AC DE G G DN P2 (E)3"V DN B (E)4"V UP GAS METER SET BY XCEL ENERGY, SET REGULATOR AT 10"W.C. (2783 MBH) (3465.8 CFH) (E)5" (E)4"G UP/DN G (E)4" (E)4" (E)3"W UP TO RD (E)3"OD UP TO OFD (E)3"OD DN (E)3"SD DN (E)3"DSN (E)4" (E)2"V DN (E)2" (E)4"V UP TO VTR 2 1/2"G P7 P6 P10 P19 3/4"G 3/4"G 3/4"G 3/4"G 2"FS-12"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 3"FS-13"FS-1 2"FS-12"FS-1 4"FS-14"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 3"V 1 1/2"CW 1 1/2"HW-140° 1/2"HWC 1 1 / 4 " G 1"HW-140° 1 1/2"CW 3/4" 3/4" 3/4" 1 1/2" 1/2" 3/4" 1/2"HWC 2" V 3/4" 1/2" 2-1/2"G HEADER P14 3" V 2"V 2" V 1 1 / 2 " 1/ 2 " 1/2" 1/2" 1/2" 1/2" 1/2"1/2" 1/2"HW-140° DN 1/2"CW DN 1 1 / 2 " H W -14 0 ° 1 1 / 2 " C W 1/2"CW 1/2"HW-140° 1/2"CW 1/2"HW-140° 1/2"HW-140° 1/2"CW 3/4" 3/4" 2"V P15 1/ 2 " 1/ 2 " 1/ 2 " 1/ 2 " 1/2" 1/2" 1/2"CW 1/2"HW-140° 1/ 2 " C W 1/ 2 " H W -14 0 ° WH-1 P17 WH-2 3/4"CW DN 2"FD-12"FD-1 2"FD-12"FD-1 2"FD-12"FD-1 2"FD-12"FD-1 P16 2"FD-12"FD-1 2"FD-12"FD-1 2"FD-12"FD-1 1/ 2 " 1/ 2 " 3/4" 3/4"1/2"HW-140° DN 1/2"CW DN 3/4"CW BFP-1 1/2"CW DN 3"V DN PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 101 LIQ. STORAGE 106 PRIVATE PATIO 114 PATIO 117 DINING 115 RETAIL 102 BAR 107 MAIN ENTRY 100 ? ? BOOTHS 116 BOOTHS 118 DINING 102 CIRCULATION 116 P19 P9 1/ 2 " C W RESTAURANT SEATING B02C 1 1/4"G UP TO RTU-1 1 1/4" 3"V 2"FS-12"FS-1 2"FS-12"FS-1 2"FS-12"FS-1 2"W DN 2"W DN 2"W DN 3"V 3" V © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 3 7 P M P-201 LEVEL 1 PLUMBING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM N 0 8'8' 4' 1/4" = 1'-0" 1 LEVEL 1 PLUMBING PLAN WORK NOTES P2 (E)2"CW, 2"HW, 1/2"HWC DOWN TO BASEMENT. COORDINATE WITH DUCTWORK AND OTHER PIPING. P6 SET TO 0.5 GPM. P7 ROUTE 3/4"CW DN TO (3) BFP-1 SERVING BEVERAGE MACHINES. REFER TO BACKFLOW PREVENTER DETAIL FOR ADDITIONAL INFORMATION. P9 ROUTE 1-1/4"G ABOVE GRADE FOR FUTURE FIREPLACE. PROVIDE WITH VALVE AND CAP. P10 ROUTE 3/4"G TO FIREPLACE. MAKE FINAL CONNECTION PER MANUFACTURER SPECIFICATIONS. P14 PROVIDE ANSUL SOLENOID VALVE, COORDINATE VENT HOOD REQUIREMENTS WITH KITCHEN CONSULTANT AND MANUFACTURER. P15 3/4"CW/HW DN, ROUTE 1/2"HW/CW TO EACH FIXTURE AND 1/2"CW BELOW FLOOR AND UP TO ADJACENT ISLAND. 1/2"CW TO ISLAND SHALL SERVE FS EQUIP. #162, PROVIDE WITH BFP-1. P16 EXISTING FLOOR SINK TO RECEIVE CONDENSATE DRAINAGE, REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION. P17 ROUTE 1/2"CW/HW TO TMV-2. ROUTE 1/2"HW FROM TMV-2 AND 1/2"CW TO HOT/COLD WH-1. P19 ROUTE 3/4"DOWN AND TRANSITION TO CSST PIPE BELOW GRADE. CSST PIPE TO STUB UP TO PRIVATE PATIO FOR FUTURE FIREPLACE, PROVIDE WITH VALVE AND CAP. 1. CONTRACTOR TO REVIEW FOOD SERVICE DRAWINGS AND MAKE FINAL CONNECTIONS BASED ON EQUIPMENT SPECIFICATIONS. GENERAL NOTES REVISION DATE ASI-T01 02.12.2021 ASI-T04 03.17.2021 1 1 1 1 1 1 03/22/21 4 3 2 1 AC DE B (E)3"OFD (E)3"RD 4"VTR RTU-1 1 1/4"G DN ROOF HATCH ACCESS © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 3 9 P M P-202 ROOF PLUMBING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM N 0 8'8' 4' 1/4" = 1'-0" 1 ROOF PLUMBING PLAN REVISION DATE ASI-T01 02.12.2021 ASI-T04 03.17.2021 1 03/22/21 (E)4"GW TO 2000 GALLON GREASE INTERCEPTOR AS PART OF CORE AND SHELL PHASE. INTERCEPTOR PROVIDED ON CIVIL DRAWINGS. 4"FS-1 6 FU 3"FS-1 5 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU2"FS-1 3 FU 2"FS-1 3 FU 2"FS-1 3 FU HANDSINK 1 FU HANDSINK 1 FU HANDSINK 1 FU HANDSINK 1 FUHANDSINK 1 FU HANDSINK 1 FU 2"FD-1 2"FD-1 2"FD-1 2"FD-1 2"FD-1 2"FD-1 2"FD-1 MSB 5 FU 4"LCO 4"LCO 4"LCO 4"LCO 4"LCO 4"LCO 3"LCO4"LCO (E)4"LCO LEVEL 1 (TYP.) BASEMENT (TYP.) (E)4"BD (E)4"BD (E)4"GW (E)4"GW 4"GW 4"GW 4"W 4"W 4"W 4"W 4"W 4"W 4"W4"W 4"W 4"W 3"W 4"W 2"V 3"V 3"V 3"V 3"V 2"V 3"V 2"V 2"V 2"V © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 4 0 : 3 9 P M P-501 PLUMBING ISOMETRICS St a n l e y H o t e l P o s t R e s t a u r a n t T I JP 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM REVISION DATE ASI-T01 02.12.2021 ASI-T04 03.17.2021 NOT TO SCALE 1 GREASE WASTE / SANITARY WASTE AND VENT ISOMETRIC - KITCHEN 1 Intercepor size shall be determined by multipying the peak drain flow into the interceptor in gallins per minute by a retention time of 30 minutes. EXISTING GREASE INTERCEPTOR SIZE = 2000 GALLONS Required Interceptor Size (Gallons)990 Retention Time (Minutes)30 Peak Flow (GPM)33 0 1-Comp 20 20 14 12 Dishwasher 10 3-Comp 12 12 12 11 1-Compartment Prep Sink 12 Sink Calc Length Width Depth GPM 3-Compartment Sink 11 Fixture Drain Period (Minutes) 2 Fixture GPM Sink Volume Calc IPC Gravity Grease Interceptor Calculation 03/22/21 EXISTING 4" ABBREVIATIONS AND DESCRIPTIONS ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT MECHANICAL LEGEND SHEET METAL FITTINGS AND EQUIPMENT PIPING DESIGNATIONS, FITTINGS AND EQUIPMENT CONTROLS DEVICES BEVELED TAP OFF OF TOP H T VCP TYP (E) (R) (N) DIA, D C EL. CI CL AFF AP FIRE DEPARTMENT CONNECTION MANUAL VOLUME DAMPER MOTORIZED DAMPER MVD MD MIXED AIR INVERT ELEVATION MA I.E. FDC EA OUTSIDE AIR SUPPLY AIR RETURN AIR NIC RA SA NORMALLY OPEN NOT IN CONTRACT NORMALLY CLOSED OA NC NO SUPPLY ROUND DUCT UP (1.5D ELBOW) AIR FLOW - SUPPLY AIR FLOW DIRECTION RELOCATED VITRIFIED CLAY PIPE NEW EXISTING TYPICAL UNIT MOUNTED THERMOSTAT HUMIDISTAT M BD T VANED ELBOW LINEAR SLOT DIFFUSER VANED ELBOW RADIUS ELBOW; 1 DIAMETER DOUBLE VANED ELBOW CONDENSER WATER SUPPLY CHILLED WATER RETURN CHILLED WATER SUPPLY HEATING WATER RETURN HEATING WATER SUPPLY LOW PRESSURE STEAM CONDENSER WATER RETURNCR LPR LPS HWR CWR CS CWS HWS WALL MOUNTED THERMOSTAT N - INDICATES NIGHT S - INDICATES SENSOR FLEXIBLE DUCT CONNECTION MOTORIZED DAMPER MOTOR MANUAL VOLUME DAMPER FLEXIBLE DUCT DOOR UNDERCUT ACCESS PANEL BACK DRAFT DAMPER REFRIGERANT HOT GAS REFRIGERANT SUCTION REFRIGERANT LIQUID RHG RS RL MEDIUM PRESSURE STEAM HIGH PRESSURE STEAM HPR HPS MPR MPS SUPPLY AIR DIFFUSER RADIUS ELBOW F UC TCOAD TCEAD VENT THROUGH ROOFVTR S FS RETURN DUCT UP SUPPLY DUCT UP EXHAUST DUCT UP F AIR FLOW DIRECTION ARROW FLOW SWITCH FLOW TRANSMITTER FS FT H HUMIDITY SENSOR PDT PI PDS PRESSURE DIFFERENTIAL TRANSMITTER POSITION INDICATOR PRESSURE DIFFERENTIAL SWITCH PSL PRESSURE SWITCH LOW PSH PRESSURE SWITCH HIGH TSH TSL TEMPERATURE SWITCH LOW TEMPERATURE SWITCH HIGH T TEMPERATURE SENSOR MANUAL SWITCH P PRESSURE SENSOR S SP STATIC PRESSURE SENSOR SENSOR CO CARBON MONOXIDE N AQUASTATT PRESSURE SWITCH PRESSURE INDICATORPI PS HEAT RECOVERY RETURN HEAT RECOVERY SUPPLY HRR HRS INDICATOR LIGHT CONDENSATE DRAINCD (F)FUTURE SUPPLY ROUND DUCT DOWN (1.5D ELBOW) RETURN DUCT DOWN (MITERED ELBOW) EXHAUST DUCT DOWN (MITERED ELBOW) SUPPLY DUCT DOWN (MITERED ELBOW) BOD BOP UNO UNLESS NOTED OTHERWISE CONDENSER WATER (COMMON) PRE-COOLING WATER RETURN PRE-COOLING WATER SUPPLY PWR CDW PWS NON-POTABLE WATERNP POTABLE (COLD) WATERCW GASG UNIT HEATER DUCT END CAP BASEBOARD HEATER SOUND ATTENUATOR ABOVE FINISHED FLOOR ACCESS PANEL BOTTOM OF DUCT BOTTOM OF PIPE COMMON CAST IRON CENTER LINE ELEVATION DIAMETER EXHAUST AIR ARROW PARALLEL TO LINE INDICATES PITCH ARROW IN LINE INDICATES DIRECTION OF FLOW LOW PRESSURE STEAM (CONDENSATE) RETURN MEDIUM PRESSURE STEAM (CONDENSATE) RETURN HIGH PRESSURE STEAM (CONDENSATE) RETURN ROUND 90° CONICAL TAKE OFF FROM RECTANGLE TRUNK RECTANGULAR 90° TAKEOFF FROM RECTANGULAR TRUNK RECTANGULAR 90° TAKEOFF ON END OF MAIN W/MIN. 12" AIR CUSHION DOWNSTREAM ROUND 90° CONICAL TAKEOFF FROM RECTANGULAR TRUNK W/ MANUAL VOLUME DAMPER ROUND 90° SPIN-IN TAKEOFF FROM RECTANGULAR TRUNK W/MANUAL VOLUME DAMPER DUCT TRANSITION CONCENTRIC DUCT TRANSITION ECCENTRIC SIDE TAKEOFF AT REGISTER OR GRILLE BOTTOM TAKEOFF AT DIFFUSER. PROVIDE TYPICAL PROJECT BALANCING SIDE TAKEOFF AT DIFFUSER RECTANGULAR 90° TAKEOFF WITH BEVELED TAP ROUND DUCT DROP/ RISE IN PLAN RECTANGLE DUCT DROP/RISE IN PLAN DIRECTION OF VIEW M-? 1 DRAWN ON THIS SHEET BOX ##__ A PICTURE DESIGNATION NEW LIGHT LINE WEIGHT FOR EQUIPMENT, PIPING, SYMBOLS, TEXT, ETC. INDICATES EXISTING CONDITIONS WITH NEW WORK SHOWN AS DARK HEATING COIL CONTROL/COIL ACCESS INDICATES SUPPLY AND RETURN PIPING TO UNIT EQUIPMENT TERMINAL OR VAV BOX CFM GPM TB-103 650 1.2 POINT OF CONNECTION NEW TO EXISTING STEAM TRAP TEMPERATURE GAUGE METERM TEE DOWN ELBOW DOWN TEE UP BRANCH-BOTTOM CONNECTION BRANCH-TOP CONNECTION RISE OR DROP ELBOW UP UNION PIPE CAP OR PLUG PIPE ALIGNMENT GUIDE PIPE ANCHOR STRAINER FLEXIBLE CONNECTION STRAINER W/BLOWOFF VALVE EXPANSION JOINT PIPE CONNECTION HOSE END BALL VALVE W/ CAP VENTURI VACUUM BREAKER WELL 2-WAY CONTROL VALVE 3-WAY CONTROL VALVE PRESSURE REDUCING VALVE PRESSURE/TEMPERATURE TAP AUTOMATIC AIR VENT PRESSURE GAUGE W/ COCK CIRCUIT SETTER GLOBE VALVE CHECK VALVE TEMPERATURE/PRESSURE RELIEF VALVE BUTTERFLY VALVE BALANCING VALVE BALL VALVE PLUG VALVE SOLENOID VALVE CALIBRATED BALANCE VALVE GAUGE W/ PIGTAIL MANUAL AIR VENT NEEDLE VALVE PRESSURE INDEPENDENT VALVE GAS COCK GAS PRESSURE REGULATOR BASE MOUNTED PUMP IN-LINE PUMP 2-WAY VALVE DUCT SMOKE DETECTORS OPPOSED BLADE DAMPER PARALLEL BLADE DAMPER VFD MS MOTOR STARTER VARIABLE FREQUENCY DRIVE DM DAMPER ACTUATOR H HUMIDIFIER CS CURRENT SENSOR HORNH FLOW SWITCHFS DIRECTION OF CUT SECTION DESIGNATION TCRAD RETURN OR EXHAUST REGISTER/GRILLE UNSHADED AREAS INDICATE DIRECTION OF AIR FLOW (IF NO SHADING, 4-WAY OR ADJUSTABLE) ROUND DUCT TAKE OFF FROM TOP OF DUCT BURIED, UNDERFLOOR OR UNDER DUCT AIR FLOW - RETURN OR EXHAUST 4" TEMPERATURE CONTROL EXHAUST AIR DAMPER TEMPERATURE CONTROL OUTSIDE AIR DAMPER TEMPERATURE CONTROL RETURN AIR DAMPER EQUIPMENT TYPE FLOOR #__ IF MULTIPLE TRANSITION TO SIZE ON PLANS CONTROL ENCLOSURE DASHED INDICATES EXISTING TO BE REMOVED FIRE/SMOKE DAMPER (# REFERS TO SCHEDULE) FIRE DAMPER SMOKE DAMPER CEILING AIR DEVICE WITH FIRE DAMPER DASHED INDICATES EXISTING TO BE REMOVED R D R D SOFT COLD WATERSCW CO2 CARBON DIOXIDE WORK NOTE SYMBOLM1 REVISION SYMBOL2 RETURN ROUND DUCT UP (1.5D ELBOW) RETURN ROUND DUCT DOWN (1.5D ELBOW) © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 3 : 4 9 P M M-001 MECHANICAL GENERAL INFORMATION St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBMDENVER OFFICE COLORADO SPRINGS OFFICE 10807 NEW ALLEGIANCE DRIVE, SUITE 400 COLORADO SPRINGS, CO 80921 719.533.1112 5420 WARD ROAD, SUITE 200 ARVADA, CO 80002 303.422.7400 TAMPA OFFICE 12450 ROOSEVELT BLVD N., SUITE 305 ST. PETERSBURG, FL 33716 727.685.0458 MELBOURNE OFFICE 6555 N. WICKHAM ROAD, SUITE 104 MELBOURNE, FL 32940 321.241.4142 PROJECT ENGINEER PROJECT MANAGER KARI NELSON KNELSON@BCER.COM 303.405.2890 PAUL MISKOWICZ PMISKOWICZ@BCER.COM 303.405.2902 CONTACT LIST DRAWING LIST - MECHANICAL M-001 MECHANICAL GENERAL INFORMATION M-002 MECHANICAL SCHEDULES M-003 MECHANICAL SPECIFICATIONS M-004 MECHANICAL COMCHECK M-200 BASEMENT MECHANICAL PLAN M-201 LEVEL 1 MECHANICAL PLAN M-202 ROOF MECHANICAL PLAN M-401 ENLARGED MECHANICAL SECTIONS M-501 MECHANICAL FLOW DIAGRAMS M-601 MECHANICAL DETAILS THE LEVEL 1 FLEX SPACE WILL BE SERVED BY A NEW DX COOLING, GAS HEATING, CONSTANT VOLUME ROOFTOP UNIT. DISTRIBUTION DUCTWORK WILL BE EXPOSED WITHIN THE SPACE. THE TENANT FINISH WILL CONSIST OF PROVIDING A GREASE EXHAUST FAN SERVING THE TYPE I GREASE EXHAUST HOOD (PROVIDED UNDER THE FOOD SERVICE PACKAGE). MAKEUP AIR WILL BE THROUGH A GAS HEATING, EVAP COOLING MAKEUP AIR UNIT IN THE BASEMENT MECHANICAL ROOM. DUCTWORK WILL CONNECT TO THE EXISTING VRF FAN COILS TO SERVE NEW GRILLES AND DIFFUSERS IN THE TENANT FINISH SPACE. THIS PROJECT IS A TENANT FINISH FOR AN EXISTING BUILDING. THE BASE BUILDING CORE AND SHELL MECHANICAL SYSTEM CONSISTS OF A VARIABLE REFRIGERANT FLOW (VRF) SYSTEM FOR HEATING AND COOLING. THE VRF SYSTEM UTILIZES INDOOR DUCTED FAN COIL UNITS AND A DEDICATED OUTDOOR AIR UNIT TO PROVIDE VENTILATION TO EACH FAN COIL UNIT. THE KICHTEN WILL HAVE A NEW GREASE FAN SERVING GREASE HOOD AND A NEW INDOOR MAKEUP AIR UNIT. PROJECT NARRATIVE E.NATURAL GAS INPUTS ARE AT SEA LEVEL. D.HORSEPOWERS ARE CORRECTED FOR ALTITUDE. C.HEATING AND COOLING CAPACITIES ARE AT ALTITUDE OF PROJECT. B.STATIC PRESSURES AND AIR PRESSURE DROPS ARE AT SEA LEVEL. A.CFM IS AT ALTITUDE OF PROJECT. 24. CONVENTIONS USED IN THE PRESENTATION OF THE CONTRACT DOCUMENTS: 23. PRIOR TO BALANCING MECHANICAL CONTRACTOR SHALL PROVIDE A CLEAN SET OF FILTERS FOR AIR HANDLING UNITS. THIS CONTRACTOR SHALL PROVIDE A MEANS TO SIMULATE 50% LOADED FILTERS. SYSTEM SHALL BE BALANCED IN THIS MODE. 22. EXISTING EQUIPMENT AS NOTED ON THE DRAWINGS SHALL BE RETURNED TO THE OWNER AT THEIR DESIGNATED LOCATION. 21. EQUIPMENT E.E.R. AND/OR C.O.P. VALUES SHALL COMPLY WITH THE CURRENT EDITION OF ASHRAE 90.1. 20. PROVIDE REDLINE MARK-UPS FOR ANY FIELD CHANGES OR MODIFICATIONS ON THE CONSTRUCTION DOCUMENTS. REDLINE DRAWINGS SHALL BE PROVIDED WHETHER COORDINATION DRAWINGS ARE REQUIRED OR NOT. 19. MOUNT THERMOSTAT AT 48" ON CENTER ABOVE FINISHED FLOOR UNLESS OTHERWISE NOTED. ADA REQUIREMENT. 18. ALL OPENINGS FROM EXHAUST DUCTS, EXHAUST FANS, GRAVITY ROOF VENTS, INTAKE LOUVERS AND GOOSENECKS SHALL BE A MINIMUM OF 12" ABOVE THE TOP OF THE FINISHED ROOFING SURFACE. 17. ALL DUCT DIMENSIONS ARE OUTSIDE DIMENSIONS. WHERE DUCT LINER IS USED, THE THICKNESS OF THE LINER TO MAINTAIN THE CLEAR INSIDE DIMENSION HAS BEEN INCLUDED. REFER TO DUCT INSULATION / LINER SCHEDULE AND/OR DIVISION 23 OF THE SPECIFICATIONS. 16. CONTRACTOR SHALL CONSTRUCT AND INSTALL DUCTWORK ACCORDING TO SMACNA STANDARDS AS A MINIMUM REQUIREMENT. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. 15. PROVIDE MANUAL AIR VENTS ON CLOSED SYSTEM WATER PIPING AT ALL CHANGES IN ELEVATION DOWNWARD IN DIRECTION OF WATER FLOW. 14. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN THE MECHANICAL SCHEDULES AND AS REQUIRED IN EACH SECTION OF SPECIFICATION TO THE ENGINEER/OWNER FOR REVIEW PRIOR TO THE ORDER, PURCHASE OR INSTALLATION OF THESE SAME ITEMS. 13. THIS PROJECT IS UNDER THE 2015 ICC CODE SUITE AND SHALL INCLUDE COMMISSIONING OF THE MECHANICAL SYSTEMS AS REQUIRED BY SECTION C408 OF THE 2015 IECC. THE MECHANICAL CONTRACTOR SHALL INCLUDE EXPENSES IN THEIR BID ASSOCIATED WITH THE COMMISSIONING PROCESS. THESE INCLUDE BUT ARE NOT LIMITED TO ATTENDING COMMISSIONING MEETINGS, COMPLETING PREFUNCTIONAL CHECKLISTS, DEMONSTRATING SYSTEM PERFORMANCE, AND ADDRESSING COMMISSIONING AUTHORITY REVIEW COMMENTS. 12. ALL MECHANICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE CODES LISTED ON THIS SHEET AND THE ARCHITECTURAL CODE PLAN. 11. CONTRACTOR SHALL FIELD VERIFY ALL MECHANICAL ITEMS PRIOR TO COMMENCING NEW WORK. NO ADDITIONAL COST WILL BE ALLOWED FOR CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. 10. CONTRACTOR SHALL CLOSELY COORDINATE NEW MECHANICAL WITH ALL NEW AND EXISTING MECHANICAL, PLUMBING, ELECTRICAL, FIRE PROTECTION, ARCHITECTURAL AND STRUCTURAL MEMBERS. REFER TO DIVISION 23 SPECIFICATIONS FOR CEILING SPACE ALLOCATION PRIORITIES. 9. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND INSTALLING SLEEVES, INSERTS AND SUPPORTS AS REQUIRED FOR THIS SCOPE OF WORK AND/OR CORE DRILL REQUIREMENTS. COORDINATE WITH GENERAL CONTRACTOR AND STRUCTURAL ENGINEER. 8. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY DIRECTED OTHERW ISE. 7. CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL DOWNTIME WITH OWNER'S PERSONNEL. CONTRACTOR SHALL PROVIDE A DETAILED M.O.P. AS REQUIRED. DO NOT BEGIN WORK WITHOUT WRITTEN APPROVAL. 6. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN INTENT, ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE AS SHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS ARE REQUIRED FOR FIELD COORDINATION OF ALL TRADES, THIS CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL COSTS. 5. COORDINATE ALL DIFFUSER AND GRILLE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN, FIRE PROTECTION, AND ELECTRICAL DRAWINGS. 4. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAVE BEEN SELECTED AS THE BASIS OF DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATED BY THE CONTRACTOR AS TO SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS AND PERFORMANCE. ANY ADDITIONAL COSTS EITHER DIRECTLY OR INDIRECTLY CAUSED BY EQUALS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. 3. DUCT AND PIPE SIZE DIMENSIONS ARE IN INCHES UNLESS NOTED OTHERWISE. 2. THIS PROJECT HAS BEEN COMPLETED IN REVIT. THIS CONTRACTOR SHALL REVIEW THE MODEL CREATED BY THE ARCHITECT / ENGINEER THAT ILLUSTRATES THE DESIGN INTENT OF THE PROJECT. THIS MODEL IS NOT INTENDED TO BE USED AS A SHOP DRAWING, BUT IS A TOOL TO ENABLE THE CONTRACTOR TO BE ABLE TO CREATE FABRICATION DRAWINGS AND COORDINATE THE INSTALLATION OF THE WORK DESCRIBED IN THESE DOCUMENTS. 1. DRAWINGS AND SPECIFICATIONS ARE COMPLEMENTARY. W HATEVER IS CALLED FOR IN EITHER IS BINDING AS THOUGH CALLED FOR IN BOTH. MECHANICAL GENERAL NOTES 1. REFER TO SPECIFICATIONS FOR THICKNESS OF DUCT LINER AND EXTERIOR INSULATION FOR EACH SYSTEM. OUTSIDE AIR INTAKE DUCT AND PLENUMS EXTERNALLY INSULATED . . . . TRANSFER AIR INTERNALLY LINED DUCT SIZES LISTED ARE ACTUAL SHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. . . EXHAUST AIR NO INSULATION OR LINER . . . . RETURN AIR INTERNALLY LINED DUCT SIZES LISTED ARE ACTUAL SHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. . . SUPPLY AIR EXPOSED NO INSULATION OR LINER . . . . SUPPLY AIR CONCEALED INTERNALLY LINED DUCT SIZES LISTED ARE ACTUAL SHEET METAL SIZE AND INCLUDE THICKNESS OF LINER. . . SYSTEM INSULATION OR LINER PHYSICAL DUCT DIMENSIONS LISTED ON DRAWINGS REMARKS DUCT LINER / INSULATION SCHEDULE AND LOCAL AMENDMENTS 2020 NATIONAL ELECTRICAL CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL BUILDING CODE ADOPTED/ENFORCED CODES REQUIRED REVISION DATE ASI-T04 3/17/21 03/22/21 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 3 : 5 1 P M M-002 MECHANICAL SCHEDULES St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM MAKE-UP AIR UNIT SCHEDULE PLAN CODE MFR. MODEL INSTALLED FAN DATA HEATER DATA COOLER DATA ELEC. DATA FILTER APPROX. OPPER. WEIGHT (LBS.) REMARKS MFR. MODEL CFM @ ALT. E.S.P. IN. W.C. @ S.L. H.P TYPE EAT (°F) LAT (°F) MBH INPUT @ S.L. MBH OUTPUT @ ALT. MIN. GAS PRESSURE (IN. W.C.) MAX. GAS PRESSURE (IN. W.C.) TURN DOWN FILL MEDIA EFF. (%) (8) MCA MOCP VOLT/PH. MAU-1 CAPTIVEAIRE A2-D.500-20D 4650 1.0 5 DIRECT -20 70.4 362.5 333.5 7 14 10:1 CELDEK 80 9.5 15 460/3 MERV 8 1,400 (1)(2)(3)(4)(5)(6)(7)(8)(9)(10)(11)(12)(13)(14) (7) PROVIDE SCCR RATING OF 5K.(14) PROVIDE INTERLOCK RELAY AND MOTORIZED BACKDRAFT DAMPER. (6) PROVIDE STAINLESS STEEL HEAT EXCHANGER.(13) MOTOR HORSEPOWER ADJUSTMENTS TO INCLUDE REVISIONS NEEDED FOR UNIT DELTA P ADJUSTMENTS, COST OF INCREASE TO BE BORNE BY MANUFACTURER. (5) UNIT SHALL BE INTERLOCKED TO RUN ANYTIME KEF-1 RUNS. PROVIDE WALL THERMOSTAT FOR VENTILATION COOLING DURING SUMMERTIME OPERATION SET TO 70°F. (12) UNIT PRESSURE DROPS NEED TO BE ADJUSTED BY MANUFACTURER DURING SHOP DRAWING PHASE. (4) PROVIDE DISCHARGE AIR CONTROL TO MAINTAIN 70°F DISCHARGE AIR.(11) FILTER PRESSURE DROP FOR FAN SIZE "BASED ON MEDIUM DIRTY RANGE; NOT CLEAN". (3) PROVIDE UNIT WITH PACKAGED CONTROLS SYSTEM. INTERLOCK WITH GREASE HOOD CONTROL PANEL AND GREASE FAN. TIE CONTROLS INTO BASE BUILDING, BUILDING AUTOMATION SYSTEM. REFER TO BASE BUILDING FOR CONTROL SEQUENCES, POINTS AND OTHER REQUIREMENTS. (10) PROVIDE UNIT WITH FACTORY VFD AND VAV PACKAGE AND MANUAL CONTROL OPTION. (2) PROVIDE AUTOMATIC FILL AND DRAIN KIT.(9) EVAPORATIVE MEDIA EFFICIENCY IS BASED ON 400 FPM. (1) PROVIDE ELECTRONIC GAS VALVE MODULATION.(8) PROVIDE AN AIR FLOW PROVING SWITCH WITH THE MAKE-UP AIR UNIT TO PREVENT ANY ONE OF THE GAS VALVES FROM OPENING PRIOR TO PROOF OF FLOW. FAN SCHEDULE PLAN CODE MFR. MODEL INSTALLED SYSTEM FAN TYPE CFM @ ALT. S.P. IN. W.C. @ S.L. WHEEL TYPE / DIAMETER FAN RPM (APPROX.) DRIVE TYPE H.P. DAMPER MOUNTING TYPE ELEC. VOLT/PH. APPROX. WEIGHT (LBS.) REMARKS MFR. MODEL TYPE SIZE KEF-1 COOK 330VX11B GREASE HOOD CENTR. 5,800 1.2 BI / 33 1010 BELT 3 - - ROOF 460/3 550 (1)(2)(3)(4)(5)(6)(7)(8) (8) MOTOR HORSEPOWER ADJUSTMENTS TO INCLUDE REVISIONS NEEDED FOR UNIT DELTA P ADJUSTMENTS, COST OF INCREASE TO BE BORNE BY MANUFACTURER. (7) UNIT PRESSURE DROPS NEED TO BE ADJUSTED BY MANUFACTURER DURING SHOP DRAWING PHASE. (6) PROVIDE GREASE TERMINATOR. (5) PROVIDE UL LISTING FOR COMMERCIAL KITCHEN GREASE EXHAUST. (4) PROVIDE 18" ROOF CURB AND 16" FACTORY VENTED CURB. PROVIDE GREASE GUARD. (3) PROVIDE WITH VFD. (2) PROVIDE BELT AND MOTOR GUARD. (1) INTERLOCK FAN OPERATION WITH KITCHEN GREASE TYPE I HOOD AND MAKEUP AIR UNIT. TIE CONTROLS INTO BASE BUILDING, BUILDING AUTOMATION SYSTEM. REFER TO BASE BUILDING FOR CONTROL SEQUENCES, POINTS AND OTHER REQUIREMENTS. 1. CAPTIVEAIRE GREASE HOODS PROVIDED AS PART OF FOOD SERVICE PACKAGE. HOODS TO BE PROVIDED WITH PACKAGED CONTROLS AND DEMAND CONTROL VENTILATION TO MODULATE GREASE FAN. CONTROL PANEL TO INTERLOCK GREASE HOOD, GREASE FAN, AND MAU TOGETHER. TIE CONTROLS INTO BASE BUILDING, BUILDING AUTOMATIO SYSTEM. MISC. EQUPIMENT 2. THIS COLUMN IS THE DEFAULT OCCUPANCY DENSITY OBTAINED FROM TABLE 403.3.1.1 IN THE IMC. 1. THIS COLUMN REPRESENTS THE ACTUAL SPACE POPULATION THAT IS JUSTIFIED BY THE DOCUMENTED FLOOR PLAN CONFIGURATION. THIS IS USED WHEN THE DEFAULT OCCUPANCY DENSITY IS NOT APPROPRIATE FOR THE DESIGNED SPACE. NOTES: TOTAL:5,244 609 323 67 2,364 2,972 3,715 0 0 0 0.8 0 118 LOUNGE FOOD AND BEVERAGE SERVICE BARS, COCKTAIL LOUNGES 195 0.18 35 25 7.5 188 223 0.8 278 115, 117 DINING AREA #1 AND #2 FOOD AND BEVERAGE SERVICE RESTAURANT DINING ROOMS 880 0.18 158 95 7.5 713 871 0.8 1,089 113 PRIVATE DINING FOOD AND BEVERAGE SERVICE RESTAURANT DINING ROOMS 525 0.18 95 32 7.5 240 335 0.8 418 103 RETAIL / DINING FOOD AND BEVERAGE SERVICE RESTAURANT DINING ROOMS 190 0.18 34 6 7.5 45 79 0.8 99 100 ENTRY PUBLIC ASSEMBLY SPACES LOBBIES 580 0.06 35 5 5.0 25 60 0.8 75 B001 OFFICE OFFICE BUILDINGS OFFICE SPACE 45 0.06 3 1 5.0 5 8 0.8 10 B08 PREP FOOD AND BEVERAGE SERVICE CAFETERIA/FAST FOOD DINING 660 0.18 119 8 7.5 60 179 0.8 224 B01 LOBBY PUBLIC ASSEMBLY SPACES LOBBIES 445 0.06 27 67 5.0 334 360 0.8 451 B03 SHOP/BAR OFFICE BUILDINGS OFFICE SPACE 91 0.06 5 1 5.0 5 10 0.8 13 B02 LOUNGE PUBLIC ASSEMBLY SPACES AUDITORIUM SEATING AREA 1,633 0.06 98 150 5.0 750 848 0.8 1,060 Az Ra Az*Ra Pz Pz Rp Pz*Rp Vbz Ez Voz SF CFM/SF CFM PEOPLE PEOPLE CFM/PERS CFM CFM FRACTION CFM ROOM # ROOM NAME CATEGORY SUB-CATEGORY ZONE AREA AREA OUTDOOR RATE FROM PLANS (1) OCCUPANT DENSITY (2)PEOPLE OUTDOOR RATE BREATHING ZONE OUTDOOR AIRFLOW ZONE DISTRIBUTION EFFECTIVENESS ZONE OUTDOOR AIRFLOW ZONE (TERMINAL) INFORMATION AREA BASED OUTDOOR AIRFLOW PEOPLE BASED OUTDOOR AIRFLOW ZONE OUTDOOR AIRFLOW ZONE LEVEL VALUES SYSTEM OUTDOOR AIRFLOW Vou 3,240 CFM SUM OF ZONE POPULATION SUM Pz 390 PEOPLE BASEMENT SPACES (SHADED) SHOWN FOR REFERENCE ONLY. PART OF CORE AND SHELL SCOPE. DOAS-1 CAPACITY = 3,500 CFM. SYSTEM OCCUPANT POPULATION Ps 327 PEOPLE LEED IEQc2 COMPLIANCE (30% INCREASED VENTILATION)NO SYSTEM LEVEL VALUES IMC 2015, 100% OUTDOOR AIR SYSTEM VENTILATION CALCULATION (DOAS-1) GRILLES, REGISTERS, AND DIFFUSERS SCHEDULE PLAN CODE MFR. TYPE MODEL INSTALLED FRAME MATERIAL FINISH DAMPER TYPE LEGEND REMARKS MFR. MODEL SD-1 TITUS PLAQUE OMNI-AA LAY-IN ALUMINUM ARCH SPECIFY - SEE PLANS FOR NECK SIZE 24"x24" OR 12"x12" FACE. SEE PLANS SG-2 TITUS DUCT MOUNTED SUPPLY S300FL DUCT MOUNTED ALUMINUM ARCH SPECIFY ASD SEE PLANS FOR FACE SIZE MOUNT FLUSH WITH DUCT, PROVIDE AIR SCOOP DEVICE, 3/4" BLADE SPACING WITH DOUBLE DEFLECTION. LS-1 TITUS LINEAR SLOT ML-39 SURFACE ALUMINUM ARCH SPECIFY -SEE PLANS FOR NUMBER OF SLOTS AND NECK SIZE 1" SLOT, PROVIDE WITH PATTERN CONTROLLER AND 4' SUPPLY PLENUM (MODEL MPI: HP FOR DIFFUSERS THAT SIT FLUSH WITH THE BOTTOM OF THE TRUSSES OR IN SIDEWALL, LP FOR DIFFUSERS THAT SIT FLUSH WITH TOP OF TRUSS) RG-1 TITUS EGGCRATE 50F LAY-IN ALUMINUM ARCH SPECIFY - - 24"x24" FACE. RG-2 TITUS RETURN GRILLE 350FL SURFACE ALUMINUM ARCH SPECIFY - SEE PLANS FOR FACE SIZE SEE PLANS FOR FACE SIZE. 3/4" SPACING, 35 DEGREE DEFLECTION. TOTALS 7,665 10,150 1,600 8,550 BUILDING IS 11% POSITIVE (885 CFM) FLEX SPACE SUPPLY ((E)EF-1) - 2,000 1,600 400 GENERAL EXHAUST ((E)EF-1) 1,865 - - - VENTILATION ((E)DOAS-1) - 3,500 0 3,500 SUPPLIES EXISTING FAN COIL UNITS (FCU-1 TO FCU-9) KITCHEN HOOD SUPPLY (MAU-1) - DIRECT MAKE-UP 4,650 0 4,650 KITCHEN HOOD EXHAUST (KEF-1) 5,800 - - - ITEM EXHAUST CFM SUPPLY CFM RETURN AIR CFM OUTDOOR AIR INTAKE CFM REMARKS AIR BALANCE SCHEDULE ROOFTOP AIR HANDLING UNIT SCHEDULE (GAS FIRED / DX) PLAN CODE MFR. MODEL INSTALLED LOCATION AREA SERVED SUPPLY FAN DATA RETURN / RELIEF FAN DATA HEATING DATA MFR. MODEL CFM @ ALT. MIN O.A. WHEEL TYPE / DIA. (IN.) RPM (APPROX.) HP CFM @ ALT. E.S.P. IN. W.C. @ S.L. WHEEL TYPE / DIA. (IN.) RPM (APPROX.) BHP HP EAT (°F) LAT (°F) MBH TYPE INPUT @ S.L. MBH OUTPUT @ ALT. MBH MIN GAS PRESSURE (IN. W.C.) MAX GAS PRESSURE (IN. W.C.) NO. OF STAGES TURN DOWN RTU-1 CARRIER 48FCFA06B3MF ROOF L1 FLEX SPACE 2000 400 16.6 VA 2601 2.0 - - - - - - 70 121.1 150 NG 150 81.6 4" 13"2 - ROOFTOP AIR HANDLING UNIT SCHEDULE (GAS FIRED / DX) CONTINUED PLAN CODE COOLING DATA FILTER DATA APPROX. UNIT DIMENSIONS ELEC. DATA OPER. WEIGHT (LBS.) REMARKS ENTERING AIR LEAVING AIR MBH (SENSIBLE) NOMINAL TONNAGE REFRIG. TYPE REFRIG. CHARGE (LBS.) SEER COMP. QTY. TYPE % EFF. LENGTH (IN.) WIDTH (IN.) HEIGHT (IN.) MCA MOCP VOLT/PH. °F DB °F WB °F DB °F WB RTU-1 80 62 50.4 50.4 47.26 5 R-410A 8 LBS 9 OZ 14.0 1 TA MERV 8 74.4" 46.6" 33.4" 28 40 208/3 850 (1)(2)(3)(4)(5)(6)(7)(8)(9)(10)(11) (6) PROVIDE UNIT MOUNTED DISCONNECT SWITCH AND SINGLE POINT POWER CONNECTION. CONTROL POWER TO BE PART OF RTU POWER. (11) PROVIDE BACNET COMPATIBLE CONTROLS CAPABLE OF TYING INTO BASE BUILDING CONTROLS AND REFER TO SEQUENCE OF OPERATION FOR FURTHER REQUIREMENTS. (5) MOTOR HORSEPOWER ADJUSTMENTS TO INCLUDE REVISIONS NEEDED FOR UNIT DELTA P ADJUSTMENTS, COST OF INCREASE TO BE BORNE BY MANUFACTURER. (10) PROVIDE ULTRA LOW LEAK ECONOMIZER WITH BAROMETRIC RELIEF (4) UNIT PRESSURE DROPS NEED TO BE ADJUSTED BY MANUFACTURER DURING SHOP DRAWING PHASE.(9) PROVIDE HINGED ACCESS PANELS, AND COIL HAIL GUARD. MOUNT ON EXISTING 18" ROOF CURB. (3) FILTER PRESSURE DROP FOR FAN SIZE "BASED ON MEDIUM DIRTY RANGE; NOT CLEAN"(8) UNIT SCCR RATING OF 5K. (2) FILTER AIR PRESSURE DROP IS INLUDED WITH THE ROOFTOP UNIT, NOT IN THE EXTERNAL PRESSURE DROP.(7) PROVIDE RETURN AIR SMOKE DETECTOR. COORDINATE COMPATIBILITY WITH FIRE ALARM SYSTEM. (1) CONTRACTOR / SUPPLIER SHALL VERIFY THE INTERNAL UNIT PRESSURE DROPS AND ADJUST THE BHP/MOTOR H.P. REQUIREMENTS. (6) INLUDE WATER SENSOR (SAFE-T-SWITCH OR SIMILAR) TO SHUT UNIT DOWN UPON PRIMARY DRAIN BLOCKAGE. 3. Evz IS CALCULATED USING ASHRAE 62.1 APPENDIX A METHODOLOGY AS PERMITTED BY THE IMC SECTION 403.3.1.1.2.3.2 2. THIS COLUMN IS THE DEFAULT IMC OCCUPANCY DENSITY OBTAINED FROM TABLE 403.3.1.1 IN THE 2015 IMC 1. THIS COLUMN REPRESENTS THE ACTUAL SPACE POPULATION THAT IS JUSTIFIED BY THE DOCUMENTED FLOOR PLAN CONFIGURATION. THIS IS USED WHEN THE IMC DEFAULT OCCUPANCY DENSITY IS NOT APPROPRIATE FOR THE DESIGNED SPACE NOTES: TOTAL:2,000 815 49 45 0 225 274 342 9 FLEX SPACE HOTELS, MOTELS, RESORTS, AND...MULTIPURPOSE ASSEMBLY 2000 815 0.06 49 45 5.0 225 274 0.8 342 (Az) (Ra) (Az*Ra) (Pz) (Pz) (Rp) (Pz*Rp) Vbz Ez Voz CFM SF CFM/SF CFM PEOPLE PEOPLE CFM/PERS CFM CFM FRACTION CFM ROOM # ROOM NAME CATEGORY SUB-CATEGORY MAX PRIMARY AIR ZONE AREA AREA OUTDOOR RATE FROM PLANS (1)FROM IMC (2) PEOPLE OUTDOOR RATE BREATHING ZONE OUTDOOR AIRFLOW ZONE DISTRIBUTION EFFECTIVENESS ZONE OUTDOOR AIRFLOW ZONE (TERMINAL) INFORMATION AREA BASED OUTDOOR AIRFLOW PEOPLE BASED OUTDOOR AIRFLOW ZONE OUTDOOR AIRFLOW ZONE LEVEL VALUES CORRECTED SYSTEM OUTDOOR AIRFLOW Vot 342 CFM UNCORRECTED SYSTEM OUTDOOR AIRFLOW Vou 274 CFM SYSTEM PRIMARY AIRFLOW (∑VPz) Vps 2,000 CFM PROVIDE 400 CFM OF OUTSIDE AIR FOR RTU-1. SUM OF ZONE POPULATION SUM Pz 45 PEOPLE NOTE: SYSTEM OCCUPANT POPULATION Ps 45 PEOPLE SYSTEM LEVEL VALUES 2015 IMC SINGLE ZONE SYSTEM VENTILATION CALCULATION (RTU-1) REVISION DATE ASI-T01 2/12/21 ASI-T04 3/17/21 1 1 1 1 1 03/22/21 MECHANICAL SPECIFICATIONS 230000 - BASIC MECHANICAL REQUIREMENTS GENERAL REQUIREMENTS A.SEE ARCHITECTURAL SPECIFICATION AND DRAWINGS FOR GENERAL CONDITIONS. B. PROVIDE ALL ITEMS FOR COMPLETE AND SUCCESSFUL OPERATION OF ALL MECHANICAL SYSTEMS. C.DRAWINGS ARE DIAGRAMMATIC ONLY. FOLLOW DRAWINGS AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHER TRADES WILL PERMIT. D. VISIT SITE AND INCLUDE ALLOWANCE IN BID FOR ALL COSTS RELATED TO THE MECHANICAL INSTALLATION. E. DEMONSTRATE THE OPERATION OF ALL SYSTEMS FOR THE OWNER AT A TIME AS DIRECTED BY THE OWNER. F. LAY OUT ALL WORK IN ADVANCE. DO NOT DEFACE WORK OF OTHER TRADES. INSTALL ALL SLEEVES AND BLOCKOUTS; WATERPROOF AS REQUIRED. FIRESTOP ALL FLOOR AND RATED WALL PENETRATIONS. G.FIELD CHECK ALL EXISTING CONDITIONS AND INCLUDE AN ALLOWANCE IN BID FOR REMOVAL AND/OR RELOCATION OF EXISTING PIPING, DUCTWORK, EQUIPMENT, ETC., AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING MECHANICAL SYSTEMS TO ALL OTHER WORK. EXISTING PIPING AND MATERIAL WHICH SHALL BE REMOVED SHALL BECOME THE PROPERTY OF THE CONTRACTOR, EXCEPT EQUIPMENT SO NOTED, WHICH SHALL BECOME THE PROPERTY OF THE OWNER. H. RECORD DRAWINGS: MAINTAIN A MARK-UP SET OF DRAWINGS WHICH INDICATE VARIATIONS IN THE ACTUAL INSTALLATION FROM THE ORIGINAL DESIGN. TURN OVER DRAWINGS TO OWNER/ARCHITECT UPON PROJECT COMPLETION. I. VERIFY THE ACTUAL ELECTRICAL SERVICE/VOLTAGE WITH THE ELECTRICAL DRAWINGS AND CONTRACTOR PRIOR TO ORDERING ANY MECHANICAL EQUIPMENT REQUIRING ELECTRICAL CONNECTIONS. STANDARDS A.ALL MECHANICAL MATERIALS SHALL BE NEW, IN FIRST CLASS CONDITION, AND U.L. LISTED WHERE APPLICABLE. B. COMPLY WITH ALL APPLICABLE AND STATE HEALTH AND HOSPITAL REGULATIONS. COMPLY WITH 2015 INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL PLUMBING CODE, AND NATIONAL FIRE PROTECTION ASSOCIATION IN EFFECT FOR THIS JURISDICTION. C.PROCURE AND PAY FOR ALL PERMITS, DEVELOPMENT FEES, LICENSES, AND LIABILITY INSURANCE, ETC. FURNISH CERTIFICATE OF FINAL INSPECTION AND APPROVAL FROM LOCAL INSPECTOR. D. MATERIAL SHALL BE AS SPECIFIED, AND/OR NOTED ON THE CONTRACT DRAWING. E. ALL MATERIALS AND EQUIPMENT LOCATED IN AIR PLENUMS SHALL BE RATED FOR PLENUM APPLICATION. GUARANTEE A.REPLACE ANY WORK OR MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FOR NORMAL WEAR, WITHIN ONE (1) YEAR AFTER CERTIFICATE OF COMPLETION IS SECURED. COORDINATION A.PRIOR TO FABRICATION OR INSTALLATION OF ANY MECHANICAL DUCTWORK, PIPING, AND PLUMBING, AND FIRE PROTECTION WORK, PARTICIPATE IN COORDINATION PLANNING MEETINGS WITH ALL OTHER BUILDING UTILITIES SYSTEMS TRADES, SO AS TO COMPLETELY ESTABLISH ROUTINGS, ELEVATIONS, SPACE REQUIREMENTS, AND COORDINATION OF LAYOUT AND SUSPENSION REQUIREMENTS IN RELATIONSHIP TO THE BUILDING STRUCTURE AND THE WORK OF ALL OTHER TRADES. OPERATION AND MAINTENANCE MANUALS A.PROVIDE O&M MANUALS FOR ARCHITECT/ENGINEER APPROVAL TWO (2) WEEKS / TEN WORKING (10) DAYS BEFORE FINAL PUNCHLIST IS SCHEDULED. B. INCLUDE DESCRIPTION OF MECHANICAL EQUIPMENT, MANUFACTURER'S PRINTED OPERATING PROCEDURES, MAINTENANCE PROCEDURES, SERVICING INSTRUCTIONS AND SCHEDULES, MANUFACTURER'S SERVICE MANUALS, VALVE TAG LIST, NAME, ADDRESS AND TELEPHONE NUMBER FOR 24-HOUR SERVICE, STARTING, STOPPING, LUBRICATION, EQUIPMENT IDENTIFICATION NUMBERS, AND ADJUSTMENT CLEARLY INDICATED, PARTS LIST, MECHANICAL WARRANTIES, TEST AND BALANCE REPORT. C.FINAL OBSERVATION WILL NOT BE CONDUCTED UNTIL ALL ITEMS HAVE BEEN SUBMITTED. 230500 - BASIC MATERIALS AND METHODS GENERAL WORK INCLUDED A.THE WORK INCLUDED UNDER THIS HEADING CONSISTS OF FURNISHING MATERIALS, SUPPLIES, EQUIPMENT, TOOLS, TRANSPORTATION AND FACILITIES, AND PERFORMING ALL LABOR AND SERVICES FOR, AS REQUIRED IN CONNECTION WITH, OR PROPERLY INCIDENTAL TO, THE HVAC, PLUMBING AND FIRE PROTECTION WORK, AS DESCRIBED IN THESE SECTIONS OF THE SPECIFICATIONS, SHOWN ON THE DRAWINGS, OR REASONABLY IMPLIED THEREFROM. B. PROVIDE MECHANICAL IDENTIFICATION FOR ALL NEW PIPING. IDENTIFICATION SHALL BE BY SETON OR BRADY AND CONSIST OF THE FOLLOWING: 1. IDENTIFY ALL NEW PIPING AND EQUIPMENT WITH PLASTIC PIPE MARKERS OR PLASTIC TAPE MARKERS. PROVIDE MARKERS SHALL INDICATE TYPE INCLUDING SUPPLY OR RETURN AND DIRECTION OF FLOW. 2. PROVIDE ENGRAVED MELAMINE PLASTIC LAMINATE, COMPLYING WITH FS L-P-387, ENGRAVED WITH ENGRAVER'S STANDARD LETTER STYLE OF THE SIZES AND WORDING INDICATED, BLACK WITH WHITE CORE (LETTER COLOR) EXCEPT AS OTHERWISE INDICATED, PUNCHED FOR MECHANICAL FASTENING EXCEPT WHERE ADHESIVE MOUNTING IS NECESSARY BECAUSE OF SUBSTRATE. LETTERING SHALL BE MIN. 1/4 INCH HIGH. 3. ALL IDENTIFICATION SHALL CONFORM WITH ANSI A13.1. 230593 - TESTING, ADJUSTING, AND BALANCING REQUIREMENTS A.SUBMIT TEST REPORTS FOR TESTING, ADJUSTING AND BALANCING. B. AGENCY SHALL BE COMPANY SPECIALIZING IN THE ADJUSTING AND BALANCING OF SYSTEMS SPECIFIED IN THIS SECTION WITH MINIMUM THREE (3) YEARS DOCUMENTED EXPERIENCE AND NEBB CERTIFIED. PERFORM WORK UNDER SUPERVISION OF REGISTERED PROFESSIONAL ENGINEER. C.TOTAL SYSTEM BALANCE SHALL BE PERFORMED IN ACCORDANCE WITH NEBB PROCEDURAL STANDARDS FOR TESTING, BALANCING AND ADJUSTING OF ENVIRONMENTAL SYSTEMS. D. BEFORE COMMENCING WORK, VERIFY THAT SYSTEMS ARE COMPLETE AND OPERABLE. ENSURE THE FOLLOWING: 1. EQUIPMENT IS OPERABLE AND IN A SAFE AND NORMAL CONDITION. 2. TEMPERATURE CONTROL SYSTEMS ARE INSTALLED COMPLETE AND OPERABLE. 3. PROPER THERMAL OVERLOAD PROTECTION IS IN PLACE FOR ELECTRICAL EQUIPMENT. 4. PRE-FILTERS AND FINAL FILTERS ARE CLEAN AND IN PLACE. IF REQUIRED, INSTALL TEMPORARY MEDIA IN ADDITION TO FINAL FILTERS. 5. DUCT SYSTEMS ARE CLEAN OF DEBRIS. 6. CORRECT FAN ROTATION. 7. FIRE SMOKE AND VOLUME DAMPERS ARE IN PLACE AND OPEN. 8. ACCESS DOORS ARE CLOSED AND DUCT END CAPS ARE IN PLACE. 9. AIR OUTLETS ARE INSTALLED AND CONNECTED. 10. DUCT SYSTEM LEAKAGE HAS BEEN MINIMIZED. E. PROMPTLY REPORT ABNORMAL CONDITIONS IN MECHANICAL SYSTEMS OR CONDITIONS WHICH PREVENT SYSTEM BALANCE. F. BEGINNING OF WORK MEANS ACCEPTANCE OF EXISTING CONDITIONS. G.ADJUSTING AND BALANCING: 1. ADJUST AIR HANDLING SYSTEMS TO PLUS OR MINUS 5 PERCENT FOR SUPPLY SYSTEMS AND PLUS OR MINUS 10 PERCENT FOR RETURN AND EXHAUST SYSTEMS FROM FIGURES INDICATED. 2. RECORDED DATA SHALL REPRESENT ACTUALLY MEASURED, OR OBSERVED, INITIAL CONDITION, AND FINAL CONDITION AFTER BALANCING. 3. PERMANENTLY MARK SETTINGS OF VALVES, DAMPERS, AND OTHER ADJUSTMENT DEVICES ALLOWING SETTINGS TO BE RESTORED. SET AND LOCK MEMORY STOPS. 4. LEAVE SYSTEMS IN PROPER WORKING ORDER, REPLACING BELT GUARDS, CLOSING ACCESSORY DOORS, CLOSING DOORS TO ELECTRICAL SWITCH BOXES, AND RESTORING THERMOSTATS TO SPECIFIED SETTINGS. 5. ADJUST AIR HANDLING AND DISTRIBUTION SYSTEMS TO PROVIDE REQUIRED DESIGN SUPPLY, RETURN, AND EXHAUST AIR QUANTITIES. 6. MAKE AIR QUANTITY MEASUREMENTS IN DUCTS BY PITOT TUBE TRAVERSE OF ENTIRE CROSS SECTIONAL AREA OF DUCT. 7. MEASURE AIR QUANTITIES AT AIR INLETS AND OUTLETS. 8. ADJUST DISTRIBUTION SYSTEM TO OBTAIN UNIFORM SPACE TEMPERATURES FREE FROM OBJECTIONABLE DRAFTS AND NOISE. 9. USE VOLUME CONTROL DEVICES TO REGULATE AIR QUANTITIES ONLY TO EXTENT THAT ADJUSTMENTS DO NOT CREATE OBJECTIONABLE AIR MOTION OR SOUND LEVELS. EFFECT VOLUME CONTROL BY DUCT INTERNAL DEVICES SUCH AS DAMPERS AND SPLITTERS. 10. PROVIDE SYSTEM SCHEMATIC WITH REQUIRED AND ACTUAL AIR QUANTITIES RECORDED AT EACH OUTLET OR INLET. 11. WHERE MODULATING DAMPERS ARE PROVIDED, TAKE MEASUREMENTS AND BALANCE AT EXTREME CONDITIONS. BALANCE VARIABLE VOLUME SYSTEMS AT MAXIMUM AIR FLOW RATE, FULL COOLING, AND AT MINIMUM AIR FLOW RATE, FULL HEATING. 12. PROVIDE BALANCE OF DOMESTIC WATER CIRCULATION LINES TO GPM INDICATED ON DRAWING. 13. REFERENCE SEQUENCE OF OPERATION. COORDINATE W ITH AND ASSIST T.C. CONTRACTORS TO SET MINIMUM OUTSIDE AIR VOLUME. 230700 - MECHANICAL INSULATION A.MANUFACTURERS: CERTAINTEED; OWENS-CORNING; JOHNS-MANVILLE, CORP.; MANSON INSULATION CO.; ARMSTRONG; OR EQUAL. B. INSULATION SHALL BE SNAP-ON TYPE, FIBERGLASS PIPE INSULATION, 1-1/2 INCH THICK, WITH WHITE SELF-SEALING FLAME RETARDANT VAPOR BARRIER JACKET. ALL VALVES AND FITTINGS SHALL BE INSULATED. INSULATION AT VALVES SHALLL BE EASILY REMOVED. C.INSULATION SHALL MEET ALL CODE REQUIREMENTS AND FIRE AND SMOKE HAZARD RATINGS AS TESTED BY PROCEDURE ASTM E-84, NATIONAL FIRE PROTECTION ASSOCIATION 225 AND U.L. 723, NOT EXCEEDING FLAME SPREAD 25 AND SMOKE DEVELOPED 50 RATINGS. D. PROVIDE 180 DEGREE CALCIUM SILICATE INSERTS AT ALL INSULATED HANGER LOCATIONS. PROVIDE 180 DEGREE GALVANIZED STEEL SADDLES. 230900 - CONTROLS AND INSTRUMENTATION A.ACCEPTABLE MANUFACTURERS 1. COLORADO CONTROLS - RELIABLE CONTROLS 2. APPROVED ALTERNATIVE WORK INCLUDED A.PROVIDE ALL LABOR, EQUIPMENT, AND MATERIAL NECESSARY FOR COMPLETE AND FULLY OPERATIONAL TEMPERATURE CONTROL SYSTEM AND PROVIDE INTERFACE WITH BAS THROUGH CREATION OF SCREEN AND SOFTWARE INTERFACE. B. INSTALL ALL FIELD DEVICES, AND PROVIDE WIRING, FOR CONTROLS DEVICES SUPPLIED WITH EQUIPMENT. C.THE AUTOMATIC TEMPERATURE CONTROL SYSTEM SHALL BE ELECTRIC. UNLESS OTHERWISE SPECIFIED, ALL CONTROLS SHALL BE FULLY PROPORTIONING. D. THE CONTROL SYSTEM SHALL INCLUDE ALL CONTROL DEVICES, VALVES, DAMPERS, OPERATORS, THERMOSTATS AND CONTROL WIRING AND CONDUIT AS SPECIFIED AND REQUIRED TO FULFILL THE INTENT OF THE SPECIFICATIONS AND THE SEQUENCE OF OPERATION. COORDINATE ALL WORK WITH THE EQUIPMENT SUPPLIERS AND THE DIVISION 16 INSTALLER. E. PROVIDE ALL COMPLETION SERVICES SPECIFIED HEREINAFTER, INCLUDING FINAL SYSTEM PERFORMANCE VERIFICATION, TO ENSURE THE SYSTEM FUNCTIONS AS SPECIFIED IN THE SEQUENCE OF OPERATION. DAMPER ACTUATORS A.ALL DAMPER ACTUATORS SHALL BE FURNISHED UNDER THIS SECTION AND INSTALLED PER THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. B. DAMPER ACTUATORS SHALL BE FOR NORMALLY-OPEN OR NORMALLY-CLOSED OPERATION AS SHOWN ON THE DRAWINGS. CONTROL WIRING A.ELECTRICAL WIRING: PROVIDE IN ACCORDANCE WITH DIVISION 16 AS REQUIRED FOR THE TEMPERATURE CONTROL SYSTEM, INCLUDING ELECTRICAL INTERLOCK WIRING. COMPLY WITH THE NATIONAL ELECTRICAL CODE, LOCAL CODES, AND DIVISION 16 OF THESE SPECIFICATIONS. B. INTERNAL CONTROL WIRING FOR EQUIPMENT SHALL BE PROVIDED BY THE MANUFACTURERS OF THAT EQUIPMENT. 233113 - AIR DISTRIBUTION A.GENERAL: PROVIDE ALL SHEET METAL DUCT SYSTEMS, CONNECTIONS, DAMPERS DUCT TURNS, HOUSINGS, HINGED SHEET METAL DOORS AND NECESSARY REMOVABLE ACCESS DOORS FOR THE COMPLETE SUPPLY AND EXHAUST SYSTEMS. PROVIDE ACCESS DOORS IN DUCTWORK FOR OBSERVATION AND MAINTENANCE OF ALL DAMPERS, COILS, FIRE DAMPERS, ETC. B. ACCESS DOOR HARDWARE: VENTLOK SERIES 100 LATCHES, HINGES, AND GASKETING TO BE USED ON DOORS LESS THAN 4 SQ. FT. IN AREA; SERIES 200 ON LARGER DOORS. C.METAL AND GAUGE: UNLESS SPECIFIED OTHERWISE, GALVANIZED IRON SHALL BE USED THROUGHOUT, FABRICATED, AND INSTALLED SO THAT NO VIBRATING OR NOISE RESULTS. IT SHALL BE MADE FROM THE BEST GRADE OF MILD STEEL SHEET OF THE U.S. STANDARD GAUGE AS RECOMMENDED IN THE LATEST EDITION OF ASHRAE GUIDE AND SMACNA WITH JOINTS AS TABULATED IN THE GUIDE AND/OR SMACNA. I.DAMPERS: SINGLE BLADE TYPE VOLUME DAMPERS SHALL BE INSTALLED WHERE CALLED FOR ON DRAWINGS AND WHERE REQUIRED FOR PROPER BALANCING. INSTALL AS FAR UPSTREAM OF DIFFUSER AS POSSIBLE. HANDLE SHALL BE VISIBLE THROUGH INSULATION. J. DUCT SIZES AS INDICATED ON THE DRAWINGS ARE OUTSIDE DIMENSIONS. K. SEAL ALL TRANSVERSE JOINTS USING A DUCT SEALER SUCH AS “HARDCAST”, OR EQUAL. L. DUCT LINER (SQUARE AND RECTANGULAR DUCTS) SHALL BE 1-INCH THICK VINYL COATED FIBERGLASS, 'K' VALUE OF .29 AT 75 DEGREES F, 1.5 LB. PER CU. FT. DENSITY, SECURED TO THE METAL WITH A SOLID COAT OF ADHESIVE, VINYL COATED SIDE TO THE AIR STREAM. ROUND DUCT LINER SHALL BE 1-INCH THICK FIBERGLASS RIGID ROUND DUCT, U.L. APPROVED, CLASS I AIR DUCT. M. SEAL ALL TRANSVERSE JOINTS USING A DUCT SEALER SUCH AS “HARDCAST”, OR EQUAL. ROUND FLEXIBLE DUCTWORK (ACOUSTICAL INSULATED) A.MANUFACTURERS: 1. FLEXMASTERTYPE 6 M OR EQUAL B. INSULATED LOW PRESSURE FLEXIBLE DUCT SHALL BE A FACTORY FABRICATED ASSEMBLY CONSISTING OF A CORROSION RESISTANT GALVANIZED STEEL HELIX; MECHANICALLY LOCKED TO A NYLON FABRIC INNER DUCT; FIBERGLASS INSULATION NOMINAL 1” THICK WITH 1.LB PER CF DENSITY (R=0.6) BETWEEN FABRIC AND FIRE RETARDANT VAPOR BARRIER OUTER LAYER. RATED VELOCITY OF 4000 FPM. VAPOR BARRIER PERMEANCE OF 0.1 PERM, ASTM. C.DUCT SHALL BE U.L. 181 CLASS 1 RATED, WITH FLAME SPREAD LESS THAN 25, SMOKE DEVELOPED LESS THAN 50. PROVIDE COMPLIANCE WITH NFPA 90A & 90B. D. SOUND ATTENUATION SHALL BE LESS THAN OR EQUAL TO THE FOLLOWING: 1. FOR 8”d, 6ft. LENGTH, OCT BANDS: 63-7dBA, 125-19dBA, 250-19dBA, 500-20 dBA INSERTION LOSS. MEASURED PER ADC, TEST CODE FD-72-R1 BY ETL. E. INSULATED LOW PRESSURE FLEXIBLE DUCT SHALL BE EQUAL TO FLEXMASTER TYPE 6 M. REGISTERS, GRILLES AND DIFFUSERS A.PROVIDE SUPPLY, RETURN AND EXHAUST REGISTERS AND DIFFUSERS AS NOTED ON THE EQUIPMENT SCHEDULE FOR TYPE, SIZE, STYLE, MATERIAL AND FINISH. B. MANUFACTURER'S SHALL BE: TITUS, METALAIRE, KRUEGER, PRICE, OR EQUAL. MAKEUP AIR AND DOAS UNITS A.ACCEPTABLE MANUFACTURERS 1. CAPTIVEAIRE 2. OR EQUAL B. GENERAL 1. FABRICATE BLOW-THRU/ SINGLE-ZONE TYPE UNIT SUITABLE FOR INDOOR INSTALLATION TO MEET CAPACITIES AS SCHEDULED. 2. FABRICATE UNIT WITH FAN SECTION PLUS ACCESSORIES, INCLUDING TWO-POSITION INTAKE DAMPER, 2-INCH MERV 8 FILTERS, FAN SECTION, GAS HEATING SECTION, BASE RAIL. PROVIDE EVAPORATIVE COOLING SECTION ON MAKEUP AIR UNITS. 3. BASE PERFORMANCE ON ALTITUDE OF 5,300 FT. 4. UNIT SHALL BE CONSTRUCTED IN MODULES WHICH WILL BE ASSEMBLED WITHIN BUILDING ADDITIONS. 5. MANUFACTURER'S REPRESENTATIVE VERIFY DIMENSIONS OF LOCATION WHERE UNIT IS TO BE INSTALLED PRIOR TO PREPARING SHOP DRAWINGS. 233413 AIR HANDLING FANS CENTRIFUGAL ROOF VENTILATORS: A.MANUFACTURERS 1. GREENHECK 2. LOREN COOK CO. 3. PENN BARRY B. GENERAL DESCRIPTION: BELT-DRIVEN OR DIRECT DRIVE, CENTRIFUGAL FANS CONSISTING OF HOUSING, WHEEL, FAN SHAFT, BEARINGS, DRIVE ASSEMBLY, MOTOR AND DISCONNECT SWITCH, CURB BASE, AND ACCESSORIES. C.HOUSING: HEAVY-GAUGE, REMOVABLE, SPUN-ALUMINUM, DOME TOP AND OUTLET BAFFLE; SQUARE, ONE-PIECE, HINGED, ALUMINUM BASE W ITH VENTURI INLET CONE. 1. UPBLAST UNITS: PROVIDE SPUN-ALUMINUM DISCHARGE BAFFLE TO DIRECT DISCHARGE AIR UPWARD, WITH RAIN AND SNOW DRAINS. D. BEARINGS: GREASE LUBRICATED BALL OR ROLLER ANTI-FRICTION TYPE WITH EXTENDED LUBRICATION LINES TO OUTSIDE FAN HOUSING. E. ACCESSORIES: THE FOLLOWING ACCESSORIES ARE REQUIRED AS INDICATED: 1. DISCONNECT SWITCH. 2. ROOF CURB. 3. BIRD SCREEN 4. BACKDRAFT DAMPER F. DUCT WORKMANSHIP: ALL DUCTWORK SHALL BE CONSTRUCTED AND ERECTED IN A WORKMANLIKE MANNER. DUCTS SHALL BE STRAIGHT AND SMOOTH ON THE INSIDE WITH NEATLY FINISHED JOINTS, AIRTIGHT, AND SHALL BE FREE FROM VIBRATION UNDER ALL CONDITIONS OF OPERATION. THE INTERNAL ENDS OF SLIP JOINTS SHALL BE MADE IN THE DIRECTION OF AIR FLOW. DUCTS SHALL BE SECURELY ATTACHED TO THE BUILDING CONSTRUCTION IN AN APPROVED MANNER. CHANGES IN DIMENSIONS AND SHAPE OF DUCTS SHALL BE GRADUAL. ALL DUCT SIZES FALL WITHIN LIMITING DIMENSIONS INDICATED ON THE DRAWINGS UNLESS OTHERWISE APPROVED. G. DUCT TURNS: ALL 90 DEGREE ELBOWS ON LOW PRESSURE SYSTEMS SHALL HAVE AN INSIDE RADIUS OF NOT LESS THAN ONE-HALF (1/2) THE W IDTH OF THE DUCT. ALL 90 DEGREE ELBOWS ON MEDIUM PRESSURE SYSTEMS SHALL HAVE AN INSIDE RADIUS OF NOT LESS THAN THE WIDTH OF THE DUCT. WHERE SHOWN ON THE DRAWINGS, 90 DEGREE ELBOWS WITH TURNING VANES SHALL BE USED CONSISTING OF SINGLE BLADE DUCT VANES WITH 2-1/2 INCH BLADE SPACING. H. FLEXIBLE CONNECTIONS: FURNISH AND INSTALL SOUND ISOLATING FLEXIBLE CONNECTIONS ON THE INLET AND OUTLET OF EACH FAN AND UNIT TO WHICH DUCT CONNECTIONS ARE MADE. FLEXIBLE CONNECTIONS SHALL BE MADE FROM VENTGLASS, NEOPRENE COATED GLASS FABRIC. AT LEAST 1-INCH SLACK SHALL BE ALLOWED IN THESE CONNECTIONS TO ENSURE THAT NO VIBRATION IS TRANSMITTED FROM FAN TO DUCTWORK: FABRIC SHALL EITHER BE FOLDED IN WITH THE METAL OR ATTACHED WITH METAL COLLAR FRAMES AT EACH END TO PREVENT AIR LEAKAGE. D. EXPOSED DUCTWORK: WHERE DUCTWORK IS EXPOSED TO VIEW IN OCCUPIED SPACES, PROVIDE MILL PHOSPHATIZED FINISH THAT IS FREE FROM VISUAL IMPERFECTIONS, INCLUDING PITTING, SEAM MARKS, ROLLER MARKS, STAINS, DENTS, DISCOLORATIONS, AND OTHER IMPERFECTIONS, INCLUDING THOSE THAT WOULD IMPAIR PAINTING. E. GREASE DUCTS: FABRICATE DUCTWORK SERVING TYPE 1 HOODS USING STEEL HAVING A MINIMUM THICKNESS OF 0.0058” (16 GAUGE) OR STAINLESS STEEL NOT LESS THAN 0.045” (NO. 18 GAGE) IN THICKNESS. 1. JOINTS, SEAMS AND PENETRATION SHALL BE MADE WITH A CONTINUOUS WELD AND BE LIQUID TIGHT. EXCEPTIONS ARE JOINTS USING LISTED SEALANTS, INTERNALLY WELDED JOINTS THAT ARE GROUND SMOOTH AND OBSERVABLE, AND LISTED FACTORY BUILT GREASE DUCTS. 2. JOINTS SHALL BE TESTED TO BE LIQUID TIGHT BY A LIGHT TEST AND/OR OTHER METHODS APPROVED BY THE AUTHORITY HAVING JURISDICTION. THIS TEST SHALL BE DONE PRIOR TO USE OF CONCEALMENT OF DUCTWORK. 3. FASTENERS OF ANY TYPE SHALL NOT PENETRATE GREASE DUCTS. 4. INSTALL DUCTS TO PITCH TOWARDS HOOD OR APPROVED GREASE RESERVOIR. DUCTS SHALL SLOPE ¼” PER FOOT. HORIZONTAL DUCTS EXCEEDING 75' IN LENGTH SHALL SLOPE 1” PER FOOT. 5. GREASE DUCTS THAT ARE EXPOSED SHALL HAVE A CLEARANCE OR NOT LESS THAN 18” FROM COMBUSTIBLE CONSTRUCTION MATERIALS, AND NOT LESS THAN 3” CLEARANCE FROM NON-COMBUSTIBLE CONSTRUCTION AND GYPSUM WALLBOARD. 6. PROVIDE GREASE DUCT CLEANOUTS ON HORIZONTAL SECTIONS OF DUCTS THAT ARE SPACED NO LESS THAN 20' APART. THE OPENING SHALL BE A MINIMUM OF 12” ON EACH SIDE AND BE LOCATED ON THE SIDE OF THE DUCT, NO LESS THAN 1 ½” ABOVE THE BOTTOM OF DUCT AND NO LESS THAN 1” FROM THE TOP. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 3 : 5 2 P M M-003 MECHANICAL SPECIFICATIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM REVISION DATE ASI-T04 3/17/21 03/22/21 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 0 5 P M M-004 MECHANICAL COMCHECK St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM REVISION DATE ASI-T04 3/17/21 03/22/21 MAU-1 DOAS-1 T T 4 3 2 1 AC DE (E)OAL-1 110x48 3500 (E)B-1 (E)GF (E)CP-1 (E)ET-1 (E)ER-1 8x6 100 (E)ER-1 12x12 400 TYP.2 16x12 26x12 12Ø 12Ø 12 x 1 2 36 x 1 0 (E)OAL-3 110x126 27000 EXHAUST INTAKE (E)FCU-1 38 x 1 4 (E)FCU-2 38 x 1 4 (E)FCU-3 38 x 1 4 20 x 1 6 20x16 (E)AC-1 (E)CU-2 (E)CU-3 (E)CU-1 (E)CP-2 6Ø 6Ø EXHAUST 8Ø 28x24 M9 M11 INTAKE 12Ø 12Ø 4Ø4Ø B (E)UH-1 (E)RG-2 (E)RG-1 (E)RG-2 (E)SD-1 8Ø 135 TYP.6 24x1012x10 12x10 24x10 (E)SD-1 8Ø 135 TYP.6 24x12 24x12 8Ø 6Ø 32 x 1 2 12x12 12Ø (E)SG-1 8x4 50 (E)TG-1 20x12 (E)SG-1 10x10 115 8Ø (E)RG-3 10x10 12 Ø 16x16 (E)OAL-2 110x34 10000 (E)SG-1 6x6 50 18x12 (E)LS-1 96, 2 SLOTS(S) 220 8Ø (E)ER-1 6x6 70 6Ø TI STORAGE 010 LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 BAR B03 ELEV. B10 COOLER 005 FREEZER 006 OFFICE 001 TI STORAGE 010 WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A PLATFORM B02B LOBBY B01 M8 M6 M6 M6 M7M7 1"CD 1"CD M7 1"CD 1 1/2"CD M12 36x20 UP 36x10 UP SD-1 24x24 160 TYP.2 (E)SD-1 24x24 165 8Ø 8Ø 8Ø 12Ø RG-1 RG-1 SD-1 12x12 65 6Ø FCU-3 40x20 20x20 36 x 2 0 36 x 2 0 48 x 1 4 1 1 1 1 1 (E)TG-1 10x6 TYP.2 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 1 1 P M M-200 BASEMENT MECHANICAL PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM 2. CLOSELY COORDINATE ALL DUCTWORK ELEVATIONS WITH ALL OTHER DISCIPLINES. 1. ALL EXPOSED INTERIOR DUCTWORK SHALL BE PRIMED FOR PAINTING. COORDINATE WITH ARCHITECT FOR PAINT COLOR. GENERAL NOTES N 0 4'4' 2' 1/4" = 1'-0" 1 BASEMENT MECHANICAL PLAN WORK NOTES M6 EQUIPMENT SHOWN IS PART OF COOLER PACKAGE AND IS TO BE VERIFIED AND PROVIDED BY THE COOLER CONTRACTOR. LOCATION IS SHOWN FOR REFERENCE ONLY. REFRIGERATION PIPING BETWEEN COIL AND CONDENSING UNIT IS BY COOLER CONTRACTOR M7 ROUTE 1" SLOPED CONDENSATE DRAIN FROM EVAPORATOR SERVING REFRIGERATED SPACE TO FLOOR SINK. PROVIDE INDIRECT WASTE CONNECTION. M8 REFRIGERATION DESIGN IS BY COOLER MANUFACTURER. REFER TO FOOD SERVICE PACKAGE FOR FURTHER INFORMATION. M9 ACCESS FOR MAU TO BE PROVIDED ON THIS SIDE OF UNIT. M11 MAU LOCATED ON MECH ROOM FLOOR WITH HOUSEKEEPING PAD. CONNECT DUCTWORK TO OUTDOOR AIR LOUVER PROVIDED AS PART OF CORE AND SHELL PACKAGE. DOAS (REFER TO CORE AND SHELL PACKAGE) SUSPENDED ABOVE MAU. M12 PROVIDE 1-1/2" CONDENSATE DRAIN FROM MAU EVAPORATIVE SECTION TO FLOOR SINK IN MECHANICAL ROOM. REFER TO DETAIL. REVISION DATE ASI-T01 2/12/21 ASI-T04 3/17/21 1 03/22/21 C H D D D C C 14 x 4 8 D D G T T T T T T 4 3 2 1 AC DE FCU-4 FCU-5 FCU-6 FCU-7 FCU-8 FCU-9 46 x 1 4 B 46x14 54 x 1 4 54 x 1 4 54 x 1 4 54 x 1 4 54x14 54x12 12 Ø 12 Ø 12 Ø 12 Ø 28x16 28x12 16x16 UP TO EF-1 8Ø UP/DN 4Ø UP/DN 4Ø UP/DN 24x24 UP TO KEF-1 12Ø 12Ø 6Ø UP/DN 6Ø UP/DN PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 101 MAIN ENTRY 100 PRIVATE PATIO 114 PATIO 117 DINING 115 DINING 102 RETAIL 102 7 M-401 8 M-401 1 M-401 2 M-401 M8 1"CD M7 M6 M3 M5 M4 M10 D D D M4 LS-1 48", 3 SLOTS(S) 160 TYP.5 LS-1 48", 3 SLOTS(S) 165 TYP.3 M13 M13 M13 M13 M13 LS-1 48", 4 SLOTS(S) 165 TYP.4 LS-1 48", 4 SLOTS(S) 165 TYP.2 LS-1 48", 4 SLOTS(S) 165 TYP.18 M14 M14 M13 M14M14 M14 M14M14 M14 M14 M14M14M14M14 RG-1 RG-1 RG-1 SD-1 325 10Ø TYP.8 M17 M17 M17 M17 M17 M17 M17 M17 M17 M17 M17 3 M-401 M1 M1M1 M2 5 M-401 8Ø 10 Ø 48x8 RG-2 36x12 RG-2 36x12 M22 M22 M21 10Ø 10Ø 10 Ø 10 Ø 10Ø 10Ø 10 Ø 10 Ø 10 Ø 10 Ø 10 Ø 14Ø 14Ø 48x8 48x8 16Ø 10 Ø 10 Ø 10 Ø 10 Ø 10 Ø 10 Ø 10 Ø 10 Ø FCU-4 M25 M25 4 M-401 48x8 10Ø 10Ø 10Ø 12Ø 12Ø 12Ø FCU-5, FCU-8 FCU-6 M14 M14 10Ø 10Ø 10Ø 10Ø 10 Ø 10Ø 12Ø 12Ø 20 Ø 20 Ø 46x20 56x16 FCU-7 FCU-9 36x12 36x12 RG-1 RG-2 48x24 TYP.3 RG-2 48x24 RG-2 48x24 M3 28x16 SG-2 18x6 235 TYP.6 12Ø 12Ø 12Ø 1 RTU-1 SG-2 18x6 195 TYP.3 RG-2 38x12 TYP.2 M27 1 12Ø UP 12Ø UP 12Ø UP 12x36 UP 12x36 UP © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 1 7 P M M-201 LEVEL 1 MECHANICAL PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM 2. CLOSELY COORDINATE ALL DUCTWORK ELEVATIONS WITH ALL OTHER DISCIPLINES. 1. ALL EXPOSED INTERIOR DUCTWORK SHALL BE PRIMED FOR PAINTING. COORDINATE WITH ARCHITECT FOR PAINT COLOR. GENERAL NOTES N 0 4'4' 2' 1/4" = 1'-0" 1 LEVEL 1 MECHANICAL PLAN WORK NOTES M17 MOUNT LINEAR SLOT DIFFUSER IN SIDEWALL. PROVIDE HIGH PROFILE INSULATED PLENUM BOX. M21 MECHANICAL CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION OF THE DUCT SMOKE DETECTOR SUPPLIED BY THE FIRE ALARM CONTRACTOR. FINAL LOCATION AND INSTALLATION SHALL BE IN ACCORDANCE WITH THE INSTALLATION INSTRUCTIONS FOR THE DUCT SMOKE DETECTOR AND ACTUAL DUCT INSTALLATION. THE REQUIRED NEW DUCT SMOKE DETECTOR IS SHOWN ON SHEET FA-201. M22 MOUNT RETURN GRILLES IN SIDEWALL. REFER TO SECTIONS AND CONFIRM FINAL LOCATION WITH ARCHITECT. M25 MOUNT GRILLE FLUSH TO DUCT AT 35 DEGREES FROM HORIZONTAL, TYP. M27 PROVIDE RETURN GRILLES AT ROOF LEVEL BETWEEN JOISTS. WORK NOTES M2 12" ROUND TYPE I EA DUCT DOWN TO HOOD (1,450 CFM, TYPICAL OF 4). MVD AT HOOD COLLAR PROVIDED BY HOOD MANUFACTURER. REFER TO FOOD SERVICE DRAWINGS FOR FURTHER INFORMATION ON HOOD. M3 28"X12" MA DUCT DOWN TO HOOD (771 CFM, TYPICAL OF 6). MVD AT HOOD COLLAR PROVIDED BY HOOD MANUFACTURER. REFER TO FOOD SERVICE DRAWINGS FOR FURTHER INFORMATION ON HOOD. M4 INTERLOCK TYPE I KITCHEN HOOD OPERATION TO MAU-1 AND KEF-1. REFER TO BASE BUILDING PACKAGE FOR CONTROLS INFORMATION. TYPE I HOOD, HOOD CONTROL PANEL AND ANSUL SYSTEM BY FOOD SERVICE CONSULTANT. REFER TO FOOD SERVICE DRAWINGS FOR FURTHER INFORMATION. M5 ROUTE 24"X24" TYPE I EA DUCT UP TO KEF-1. M6 EQUIPMENT SHOWN IS PART OF COOLER PACKAGE AND IS TO BE VERIFIED AND PROVIDED BY THE COOLER CONTRACTOR. LOCATION IS SHOWN FOR REFERENCE ONLY. REFRIGERATION PIPING BETWEEN COIL AND CONDENSING UNIT IS BY COOLER CONTRACTOR M7 ROUTE 1" SLOPED CONDENSATE DRAIN FROM EVAPORATOR SERVING REFRIGERATED SPACE TO FLOOR SINK. PROVIDE INDIRECT WASTE CONNECTION. M8 REFRIGERATION DESIGN IS BY COOLER MANUFACTURER. REFER TO FOOD SERVICE PACKAGE FOR FURTHER INFORMATION. M13 MOUNT DIFFUSER FLUSH WITH BOTTOM OF STRUCTURE. PROVIDE HIGH PROFILE INSULATED PLENUM BOX. M14 MOUNT DIFFUSER SUCH THAT IT SITS DIRECTLY ABOVE THE BOTTOM OF THE TRUSS. LOCATE AS CLOSE TO WALL AS POSSIBLE THROUGH THE USE OF A LOW PROFILE INSULATED PLENUM BOX AND USE PATTERN CONTROLLER TO DIRECT AIR TOWARDS WINDOW. REVISION DATE ASI-T01 2/12/21 ASI-T04 3/17/21 1 1 03/22/21 EF-2 KEF-1 RTU-1 4 3 2 1 AC DE EF-1 CU-1 B 6Ø 6Ø 4Ø 4Ø 8Ø 2 M-401 M15 M18 M19 10Ø 8Ø M20M10M20 M26 14x28 22 x 1 8 12Ø DN 12Ø DN 36x12 DN 1 ROOF HATCH M28M28 12Ø DN 12x36 DN 10 ' © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 1 9 P M M-202 ROOF MECHANICAL PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM 2. CLOSELY COORDINATE ALL DUCTWORK ELEVATIONS WITH ALL OTHER DISCIPLINES. 1. ALL EXPOSED INTERIOR DUCTWORK SHALL BE PRIMED FOR PAINTING. COORDINATE WITH ARCHITECT FOR PAINT COLOR. GENERAL NOTES N 0 4'4' 2' 1/4" = 1'-0" 1 ROOF MECHANICAL PLAN WORK NOTES M10 PROVIDE 10" ROUND OA DUCT AND 8", TYPE B, FLUE FOR FIRE PLACE. ROUTE FLUE AND COMBUSTION AIR DUCT AS SHOWN AND TERMINATE THROUGH ROOF. FOLLOW ALL MANUFACTURERS RECOMMENDATIONS AND MAINTAIN A MINIMUM OF 1" CLEARANCE TO COMBUSTIBLES AROUND THE FLUE. REFER TO WORK NOTE 20 FOR FURTHER INFORMATION. M15 REFER TO DETAIL FOR GREASE EXHAUST DUCT AND FAN INFORMATION. M18 APPROXIMATE LOCATION FOR COOLER PACKAGE EQUIPMENT AND IS TO BE VERIFIED AND PROVIDED BY THE COOLER CONTRACTOR. LOCATION IS SHOWN FOR REFERENCE ONLY. REFRIGERATION PIPING BETWEEN COIL AND CONDENSING UNIT IS BY COOLER CONTRACTOR. M19 PROVIDE GREASE GUARD FOR FAN. M20 TERMINATE 8", TYPE B, FLUE FOR FIREPLACE WITH MANUFACTURER RECOMMENDED POWER VENT, MODEL PVK-45. 120V/1, 1.2 AMPS, 1/9 HP. FLUE TO BE SEALED USING HIGH TEMPERATURE RTV SILICONE AND/OR FOIL TAPE PER MANUFACTURER'S RECOMMENDATIONS. M26 PROVIDE RTU-1 AND MOUNT TO EXISTING ROOF CURB. M28 DUCTWORK MINIMUM 12" ABOVE FINISHED ROOF. DUCT SHALL HAVE 1" LINER AND 2" DUCT WRAP. REVISION DATE ASI-T01 2/12/21 ASI-T04 3/17/21 1 03/22/21 FIRST FLOOR 100' -0" ROOF LEVEL 112' -1" CD D D 14x46 M1 M2 M1 M4M4 KITCHEN BOH 109 12Ø 12Ø 12Ø 12Ø B.O.H. 104 FIRST FLOOR 100' -0" ROOF LEVEL 112' -1" C B 5' 5' KEF-1 46x14 24x24 M5 M15 M19 STORAGE 105 MAIN ENTRY 100 B.O.H. 104 FIRST FLOOR 100' -0" ROOF LEVEL 112' -1" 1 MOUNT DIFFUSER DIRECTLY ABOVE THE BOTTOM OF THE TRUSS USE LOW PROFILE PLENUM BOX TO POSITION LINEAR SLOT DIFFUSER AS CLOSE AS POSSIBLE TO EXTERIOR WALL. LS-1 48", 4 SLOTS(S) 165 M14 RESTAURANT SEATING 101 FIRST FLOOR 100' -0" ROOF LEVEL 112' -1" CD KITCHEN BOH 109 16x28 12Ø 12Ø 12Ø 12x28 28x12 28x12 28x12 28x12 28x12 RG-1 0 20Ø 12Ø12Ø 12Ø M3 M4M4 20Ø16x28 FIRST FLOOR 100' -0" ROOF LEVEL 112' -1" ACDEB8 M-401 10Ø 10Ø 10 Ø 10 Ø 10 Ø 10 Ø 10 Ø 14Ø 14Ø FCU-4 48x8 48x8 FCU-6 48x8 12Ø FCU-7 10Ø10Ø 10Ø10Ø10Ø LS-1 48", 4 SLOTS(S) 165 TYP.4 LS-1 48", 4 SLOTS(S) 165 TYP.2 10Ø FCU-512Ø12Ø RG-2 48x24 RG-2 48x24 RG-2 48x24 RG-2 36x12 RG-1 LS-1 48", 3 SLOTS(S) 160 10Ø LS-1 48", 4 SLOTS(S) 165 TYP.3 LS-1 48", 4 SLOTS(S) 165 16Ø 10Ø 10Ø10Ø10Ø10Ø10Ø DISH 111 BAR BOH 108 BAR 107 DINING 102 RESTAURANT SEATING 102 RESTAURANT SEATING 101 M22 M22 12x36 M17 M17 M17 M14 M13 FCU-9FCU-8 10Ø 10Ø 10Ø 10 Ø 8Ø 10Ø SD-1 325 TYP.8 FIRST FLOOR 100' -0" ROOF LEVEL 112' -1" B 8 M-401 36 x 2 0 56 x 1 6 36 x 1 0 20Ø16x28 12Ø 12Ø 12Ø 12 Ø RG-1 FCU-9 46x20 20Ø TRANSITION DUCT TO 56"X14" ABOVE LEVEL 1 SLAB OPENING. 21 7 M-401 1 M-401 5 M-401 4 M-401 LS-1 48", 4 SLOTS(S) 165 TYP.1 1 0 Ø 10Ø 16Ø 10Ø 10Ø 10Ø 10Ø10Ø 10Ø 12Ø 12Ø 20Ø 10 x 3 6 16 x 5 6 20Ø BAR 107 M14 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 2 9 P M M-401 ENLARGED MECHANICAL SECTIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM 0'2'1'2'4'8' 1/4" = 1'-0"M-201 KITCHEN HOOD AND GREASE DUCT SECTIONKITCHEN HOOD AND GREASE DUCT SECTION1 0'2'1'2'4'8' 1/4" = 1'-0"M-201 GREASE EXHAUST FAN SECTIONGREASE EXHAUST FAN SECTION2 0'2'1'2'4'8' 1/4" = 1'-0"M-201 LINEAR SLOT SECTIONLINEAR SLOT SECTION3 WORK NOTES M1 46"X16" TYPE I EA DUCT. SLOPE TYPE I DUCTWORK TOWARDS HOOD AT 1/4" PER FOOT. REFER TO SECTION FOR FURTHER INFORMATION. PROVIDE CONTINUOUS FIRE RATED ENCLOSURE AROUND THE DUCT ( 2 LAYERS OF UL LISTED FIRE DUCT WRAP). REFER TO DETAIL. M2 12" ROUND TYPE I EA DUCT DOWN TO HOOD (1,450 CFM, TYPICAL OF 4). MVD AT HOOD COLLAR PROVIDED BY HOOD MANUFACTURER. REFER TO FOOD SERVICE DRAWINGS FOR FURTHER INFORMATION ON HOOD. M3 28"X12" MA DUCT DOWN TO HOOD (771 CFM, TYPICAL OF 6). MVD AT HOOD COLLAR PROVIDED BY HOOD MANUFACTURER. REFER TO FOOD SERVICE DRAWINGS FOR FURTHER INFORMATION ON HOOD. M4 INTERLOCK TYPE I KITCHEN HOOD OPERATION TO MAU-1 AND KEF-1. REFER TO BASE BUILDING PACKAGE FOR CONTROLS INFORMATION. TYPE I HOOD, HOOD CONTROL PANEL AND ANSUL SYSTEM BY FOOD SERVICE CONSULTANT. REFER TO FOOD SERVICE DRAWINGS FOR FURTHER INFORMATION. M5 ROUTE 24"X24" TYPE I EA DUCT UP TO KEF-1. M13 MOUNT DIFFUSER FLUSH WITH BOTTOM OF STRUCTURE. PROVIDE HIGH PROFILE INSULATED PLENUM BOX. M14 MOUNT DIFFUSER SUCH THAT IT SITS DIRECTLY ABOVE THE BOTTOM OF THE TRUSS. LOCATE AS CLOSE TO WALL AS POSSIBLE THROUGH THE USE OF A LOW PROFILE INSULATED PLENUM BOX AND USE PATTERN CONTROLLER TO DIRECT AIR TOWARDS WINDOW. M15 REFER TO DETAIL FOR GREASE EXHAUST DUCT AND FAN INFORMATION. M17 MOUNT LINEAR SLOT DIFFUSER IN SIDEWALL. PROVIDE HIGH PROFILE INSULATED PLENUM BOX. M19 PROVIDE GREASE GUARD FOR FAN. M22 MOUNT RETURN GRILLES IN SIDEWALL. REFER TO SECTIONS AND CONFIRM FINAL LOCATION WITH ARCHITECT. 0'2'1'2'4'8' 1/4" = 1'-0"M-201 KITCHEN HOOD AND GREASE DUCT SECTIONKITCHEN HOOD AND GREASE DUCT SECTION4 0'2'1'2'4'8' 1/4" = 1'-0"M-201 OVERALL BUILDING SECTION 1OVERALL BUILDING SECTION 17 0'2'1'2'4'8' 1/4" = 1'-0"M-201 MAKEUP AND DOAS DUCTWORK AT SHAFTMAKEUP AND DOAS DUCTWORK AT SHAFT5 NOT TO SCALE MAKEUP AND DOAS DUCTWORK AT SHAFT 3D VIEW6 0'2'1'2'4'8' 1/4" = 1'-0"M-201 OVERALL BUILDING SECTION 2OVERALL BUILDING SECTION 28 REVISION DATE ASI-T04 3/17/21 03/22/21 PRE-FILTER RETURN AIR GAS HEATING SECTION SUPPLY FAN T DM 15 THE RTU SHALL BE FURNISHED WITH FACTORY PROVIDED DDC CONTROLS. THE RTU MANUFACTURER SHALL PROVIDE AN OPEN PROTOCOL BACNET INTERFACE FOR COMMUNICATION WITH THE BUILDING BAS. THE CONTROLS CONTRACTOR SHALL COORDINATE WITH THE RTU MANUFACTURER TO PROVIDE THE FOLLOWING SPECIFIED SEQUENCE. THE RTU SHALL OPERATE AS A SINGLE ZONE VAV UNIT. THE RTU SHALL HAVE GAS HEATING, DX COOLING, AND AN AIRSIDE ECONOMIZER. THE RTU SHALL OPERATE ON AN OCCUPIED/UNOCCUPIED TIME OF DAY SCHEDULE DEFINED BY THE OWNER. THE OCCUPIED/UNOCCUPIED SCHEDULE SHALL BE DETERMINED THROUGH A USER-ADJUSTABLE, GRAPHICAL SEVEN DAY SCHEDULE. ALL TEMPERATURE AND PRESSURE SETPOINTS SHALL BE ADJUSTABLE. DAMPER NORMAL POSITION: OUTSIDE AIR DAMPER - NORMALLY CLOSED. RETURN AIR DAMPER - NORMALLY OPEN. EXHAUST AIR DAMPER - NORMALLY CLOSED (BACKDRAFT DAMPER). OCCUPIED MODE: THE UNIT ENABLES THE SUPPLY FAN TO RUN CONTINUOUSLY WITH THE OUTSIDE AIR DAMPER OPEN TO ITS MINIMUM VENTILATION CFM SETPOINT. THE SUPPLY FAN SPEED SHALL BE AT 50% SCHEDULED AIRFLOW. THE UNIT MONITORS THE STATUS OF THE SUPPLY FAN. IF THE SUPPLY FAN FAILS TO PROVIDE RUN STATUS WHILE COMMANDED "ON", THE UNIT RETURNS THE DAMPERS TO THEIR NORMAL POSITIONS, AND AN ALARM IS GENERATED AT ALL BAS CENTRAL WORKSTATIONS. MINIMUM OUTSIDE AIR VOLUME THE UNIT MODULATES THE OUTSIDE/RETURN AIR DAMPERS TO MAINTAIN THE MINIMUM VENTILATION CFM. THE OUTSIDE AIR CFM SHALL BE MEASURED BY AN INTEGRAL AIRFLOW MONITOR PROVIDED BY THE RTU MANUFACTURER. DISCHARGE AIR TEMPERATURE CONTROL: WHEN THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE, THE ECONOMIZER SHALL BE ENABLED. THE UNIT MODULATES THE GAS HEATING, THE MIXED AIR DAMPERS, AND CYCLES THE DX COOLING STAGES IN SEQUENCE TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SET POINT OF 55°F (ADJ.). THE DISCHARGE AIR TEMPERATURE SET POINT SHALL BE RESET FROM 55°F TO 90° F TO MAINTAIN THE SPACE TEMPERATURE SETPOINTS OF 70°F (ADJ) HEATING AND 75°F (ADJ) COOLING. IF THE SPACE TEMPERATURE SETPOINTS ARE NOT MET, THE UNIT MODULATES THE SUPPLY FAN SPEED FROM 50% TO 100% TO MAINTAIN THE SPACE HEATING AND COOLING SETPOINTS. WHEN THE OUTSIDE AIR TEMPERATURE IS GREATER THAN THE RETURN AIR TEMPERATURE, THE OUTSIDE AIR DAMPERS SHALL RETURN TO THE SCHEDULED MINIMUM OSA CFM. DEMAND CONTROL VENTILATION A RETURN AIR CARBON DIOXIDE SENSOR RESETS THE OUTSIDE AIR DAMPER'S MINIMUM POSITION TO MAINTAIN THE CO2 SET POINT (ADJ.). UNOCCUPIED MODE: THE SUPPLY FANS IS OFF, THE OUTSIDE AIR AND EXHAUST DAMPERS ARE CLOSED, THE RETURN AIR DAMPER IS OPEN, THE GAS HEATING IS OFF, AND THE DX COOLING IS OFF. THE BAS SHALL MONITOR THE SPACE TEMPERATURE. IF THE SPACE TEMPERATURE FALLS BELOW THE UNOCCUPIED HEATING SET POINT OF 65°F (ADJ.), THE DDC ENABLES THE SUPPLY FAN. THE OUTSIDE AIR AND EXHAUST DAMPERS REMAIN CLOSED. THE DDC MODULATES THE GAS HEATING TO MAINTAIN THE DISCHARGE AIR TEMPERATURE SET POINT OF 90°F (ADJ.). WHEN THE SPACE TEMPERATURE REACHES THE UNOCCUPIED HEATING SET POINT, THE SUPPLY FAN SHALL DISABLE AND THE GAS HEATING VALVE SHALL BE DE-ENERGIZE. OPTIMAL START: AN OPTIMAL START PROGRAM IS UTILIZED TO ENABLE THE UNIT AT THE LATEST POSSIBLE TIME TO ENSURE THE SPACE IS WITHIN THE OCCUPIED HEATING AND COOLING SET POINTS AT THE TIME OF OCCUPANCY. THE SUPPLY AND EXHAUST FANS ENERGIZE AS DESCRIBED IN THE OCCUPIED MODE. UNIT SAFETIES: UPON SENSING A DISCHARGE AIR TEMPERATURE LESS THAN 45°F (ADJ), AN ALARM IS GENERATED AT ALL BAS WORKSTATIONS. UPON ACTIVATION OF THE HARDWIRED CONDENSATE OVERFLOW SWITCH, THE SUPPLY FAN STOPS, THE OUTSIDE AIR DAMPER CLOSES, AND AN ALARM IS GENERATED AT ALL BAS WORKSTATIONS. UPON ACTIVATION OF THE DUCT SMOKE DETECTOR (BY DIV. 28), THE SUPPLY FAN STOPS, THE OUTSIDE AIR DAMPER CLOSES, AND AN ALARM IS GENERATED AT ALL BAS WORKSTATIONS. UNIT DIAGNOSTICS: THE UNIT CONTROLLER SHALL BE CAPABLE OF MANUALLY INITIATING EACH OPERATING MODE SO THAT OPERATION OF THE COMPRESSORS, ECONOMIZERS, FAN, AND HEATING SYSTEM CAN BE INDEPENDENTLY TESTED AND VERIFIED. THE UNIT CONTROLLER SHALL PROVIDE THE FOLLOWING SYSTEM STATUS/FAULTS TO THE BAS: 1. FREE COOLING AVAILABLE 2. ECONOMIZER ENABLED 3. COMPRESSOR ENABLED 4. HEATING ENABLED 5. MIXED AIR LOW LIMIT CYCLE ACTIVE 6. CURRENT VALUE OF EACH SENSOR 7. AIR TEMPERATURE SENSOR FAILURE/FAULT 8. NOT IN ECONOMIZER WHEN UNIT SHOULD BE 9. IN ECONOMIZER WHEN UNIT SHOULD NOT BE 10. FAILURE OF DAMPERS TO MODULATE 11. EXCESS OUTSIDE AIR SEQUENCE OF OPERATION RTU-1 DX COOLING COIL DP T8 N.O. CS VFD FACTORY CONTROL PANEL T 7S 22 CO2 1 3 4 5 217 18 10 11 21 12 9 20 24 6 F A C P 23 OUTSIDE AIR RELIEF AIR DM N.C. 14 T 16 BAROMETRIC DAMPER FT 13 MIXED AIRRETURN AIR CONDENSING SECTION © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 3 0 P M M-501 MECHANICAL FLOW DIAGRAMS St a n l e y H o t e l P o s t R e s t a u r a n t T I KRD 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM NOT TO SCALE 3 RTU-1 CONTROL DIAGRAM RTU-1 POINTS LIST PO I N T I D E N T I F I E R N U M B E R SYSTEM POINT DESCRIPTION PO I N T T Y P E ( B I , A I , B O , A O ) SH O W O N S Y S T E M G R A F H I C IN C L U D E D A T A I N T R E N D L O G IN C L U D E D A T A I N T R E N D G R A P H AL A R M C O N D I T I O N S NOTES 1 SUPPLY FAN START/STOP BO X X X 2 SUPPLY FAN STATUS-CURRENT SENSOR BI X X 3 SUPPLY FAN VFD SPEED AO X X X 4 SUPPLY FAN VFD ALARM BI X X 5 SUPPLY FAN VFD POSITION FEEDBACK AI X X X X 6 SUPPLY AIR TEMPERATURE AI X X X X 7 SA TEMPERATURE RESET AO X X X 8 SPACE TEMPERATURE AI X X X X 9 SPACE TEMPERATURE RESET AO X X X 10 GAS HEATING ENABLE BO X X X 11 GAS HEATING MODULATION AO X X X 12 DX COOLING MODULATION AO X X X 13 OUTSIDE AIR CFM AI X X X X 14 MIXED AIR DAMPER CONTROL AO X X X 15 MIXED AIR TEMPERATURE AI X X X 16 RETURN AIR TEMPERATURE AI X X X 17 RETURN AIR CO2 AI X X X 18 DRY FILTER ALARM BI X X 20 ECONOMIZER CONTROL AI X X X X 21 CONDENSATE OVERFLOW SWITCH BI X X 22 RETURN AIR SMOKE DETECTOR STATUS BI X X 23 FIRE ALARM STATUS BI X X 24 RTU BACNET CARD/INTERFACE REVISION DATE ASI-T04 3/17/21 03/22/21 BFP PIPING IN AIR STREAM TO BE CONSTRUCTED OF MATERIAL WHICH COMPLIES WITH RATINGS: SMOKE DEVELOPED <50 AND FLAME SPREAD <25 BALANCING BALL VALVE 1 1/2" OVERFLOW CIRCULATING PUMP POSITIVE SLOPED DRAIN PAN 1 1/2" MANUAL DRAIN WITH BALL VALVE, SET TO MAINTAIN T.D.S. (TOTAL DISSOLVED SOLIDS) RECOMMENDED BY MANUFACTURER DIRECT EVAPORATIVE COOLING SECTION DISTRIBUTION HEADER MEDIA AIR FLOW DIRECTION FLOAT OPERATED MAKE-UP VALVE SOLENOID MAKE-UP VALVE ELECTRIC LEVEL CONTROLLER (DELETE IF FLOAT VALVE IS USED) SUMP 1 1/2" DRAIN SOLENOID DRAIN VALVE 3/4" REMOVABLE CAP FOR TRAP CHARGING 1 1/2" DRAIN TO FLOOR SINK, OPEN- SITE AT FLOOR SINK 4" TRAP, REFER TO DETAIL 3/4" QUICK FILL SEE PLANS FOR CONTINUATION 3/4" CW REDUCED PRESSURE BACK FLOW PREVENTER W/ DRAIN FUNNEL PILOT LIGHT SWITCH BY DIVISION 26. HARD WIRED INTERLOCK TO EXHAUST FAN BY DIVISION 26. COORDINATE EXACT LOCATION WITH OWNER & WITH SEQUENCE OF OPERATION DRAWINGS. GREASE WRAP NOT LESS THAN 1 HR FIRE RESISTANCE FOR BUILDING LESS THAN 4 STORIES IN HEIGHT. GREASE WRAP SHALL BE CONTINUOUS TO OUTLET TEMRINAL. CLEARANCES TO NON- COMBUSTIBLE ENCLOSURE: NFPA 96=6", UBC=3" HORIZONTAL DUCTS SHALL BE SLOPED AT 1/4" PER 12" TOWARD HOOD OR GREASE RESERVOIR (UNLESS > 75'; THEN USE 1" PER 12") PROVIDE APPROVED GREASE WRAP IN ACCORDANCE WITH ASTM E 2336. 0" IN. MINIMUM TO NONCOMBUSTIBLES 3 IN. MININIMUM TO LIMITED COMBUSTIBLES 18 IN. MININIMUM TO COMBUSTIBLES ADD F/S DAMPER IF HOOD IS NOT COMPLIANT W/ NFPA 96 UL LISTED LIGHT FIXTURE BOTTOM OF SHAFT ENCLOSURE SEALED AROUND DUCT AT THIS POINT EXHAUST HOOD (RE: FS PACKAGE) COOKING SURFACE ACCESS PANEL AT EACH CHANGE OF DIRECTION, WITH GREASE-TIGHT GASKET, CARBON OR STAINLESS STEEL FASTENERS THAT DO NOT PENETRATE DUCT, AND LABELED "ACCESS PANEL - DO NOT OBSTRUCT" ACCESSIBLE OPENING IN GREASE WRAP FOR ACCESS PANEL NO ACCESS PANELS IN BOTTOM SIDE OF DUCT 1 1/2" MIN. NO DAMPERS IN EXHAUST DUCTS GREASE DUCT, MIN. 16 GA. WELDED STEEL MINIMUM 18 GA. STEEL HOOD (RE: FOOD SERVICE PACKAGE) HOOD SHALL HAVE FIRE SUPPRESSION SYSTEM EQUIPPED WITH INTERLOCKED GAS SHUT-OFF VALVE (OR SHUNT TRIP COIL OF CIRCUIT BREAKER) AND LABELED, MANUAL (MECHANICALLY OPERATED) (RE: FOOD SERVICE PACKAGE) GREASE FILTERS MOUNTED AT ANGLE NOT LESS THAN 45° FROM HORIZONTAL (RE: FOOD SERVICE PACKAGE) GREASE DRIP TRAY (RE: FOOD SERVICE PACKAGE) 24" MIN. 40" ROOF 18" HINGED, UPBLAST EXHAUST FAN 10'-0" FROM ADJACENT BUILDING OR PROPERTY LINE, OR AIR INTAKE WEATHER PROTECTED CHASE VENT OPENING (OR VENTILATED CURB BASE) RAINPROOF GREASE RESERVOIR F 18 IN. MINIMUM CLEARANCE TO COMBUSTIBLES. 18 IN. CLEARANCE TO CEMENT BOARD UNLESS PROVIDED WITH SMOOTH, CLEANABLE, NONABSORBENT AND NONCOMBUSTIBLE MATERIAL BETWEEN THE HOOD AND CEMENT BOARD EXTENDING NOT LESS THAN 18 IN. IN ALL DIRECTIONS FROM THE HOOD. 1 1 2 WORK NOTES: 1. CONTRACTOR TO VERIFY SPECIFIC MANUFACTURER'S INSTALLATION REQUIREMENTS. FIREMASTER DUCT WRAP PACKING MATERIAL FLOOR OR WALL FIREMASTER DUCT WRAP PACKING MATERIAL FIREMASTER DUCT WRAP DUCT FB-2000+ CAULK DUCT BANDING 2 1 " T Y P .1 0 1 /2 " 1 0 1 /2 " 1 1 /2 " 1 1 /2 " 1 1 /2 " 1 1 /2 " 1 1/2"x1 1/2"x1/8" ANGLE MIN. 3/8" DIAMETER HANGER ROD TWO LAYERS FIREMASTER DUCT WRAP 3" PERIMETER OVERLAP 3" LONGITUDINAL OVERLAP BANDING AND FILLIMENT TAPE L W VOLUME DAMPER W/ LOCKING QUADRANT WHERE SPECIFIED ON DRAWING AIR FLOW REMOTE CEILING OPERATOR WHERE DAMPER IS INACCESSIBLE. REFER TO DAMPER REGULATOR DETAIL. NOTE: DAMPER SHALL NOT BE INSTALLED CLOSER THAN TWO DUCT WIDTHS TO ELBOW OR INTERSECTIONS NOTE: L=0.25 W(6" MIN.) NOTE: LESS THAN 2" WATER COLUMN 45° MVD CROSS-SECTION AREA (A) FACE AREA OF TAKEOFF SHALL BE: 1.3 (A) NOTE: PROVIDE ONLY WHERE TAKEOFF DUCT IS SAME DIMENSION TO HEIGHT OF RECTANGULAR DUCT. OBD WHERE SPECIFIED REFER TO G.R.D. SCHEDULE FOR REQUIREMENTS. AIR DEVICE REFER TO G.R.D. SCHEDULE AND PLANS FOR TYPE. 1" DUCT LINER BRANCH DUCT CEILING SPIN-IN W/ MVD WHERE SPECIFIED. FLEXIBLE DUCT (MAX. 6'-0") SUPPORT AT 3'-0" O.C. ELBOW W/ 3/4" DIAMETER INNER RADIUS MINIMUM CONNECT FLEX TO AIR DEVICE PER SPECS. STAINLESS STEEL CLAMPING BAND DRAIN CONNECTION DRAIN PAN NIPPLE CLEANOUT PLUG TEE UNION 1. PITCH DRAIN FOR PROPER RUN-OFF. 2. MANUALLY PRIME FILL TRAP BEFORE STARTUP TO FORM INITIAL DRY SEAL. 3. SUPPORT DRAIN LINES TO PREVENT SAG AND CONDENSATE OVERFLOW. GENERAL NOTES: PITCH AT 1/8" PER FT. HEIGHT: MINIMUM 1" PLUS CASING STATIC PRESSURE HEIGHT: FROM BOTTOM OF DRAIN PAN TO TOP OF TRAP SEAL DISCHARGE MUST BE BELOW LEVEL OF DRAIN PAN TRAP SEAL (HALF OF THE "HEIGHT" REQUIRED) ROOF CURB AND FLASHING SHALL BE INSTALLED PER THE NATIONAL ROOFING CONTRACTORS ASSOCIATION RECOMMENDATIONS AND DETAILS. NOTE: WATERSEAL GASKETING MATERIAL BY MFR. (TYP.) METAL ROOF CURB COUNTER FLASHING FLASHING ROOFING 5ML PLASTIC LINER FLEXIBLE DUCT CONNECTION ROOFTOP AIR HANDLING UNIT 4" HIGH DENSITY INSULATION (3 LB/CU. FT.) SEAL DUCT PENETRATION W/ HIGH DENSITY INSULATION FLEXIBLE MASTIC ON ALL SIDES OF DUCT INSTALL ROOF CURB LEVEL AND PLUMB ROOF CONSTRUCTION TRAP COOLING COIL, DAYLIGHT ON ROOF. PROVIDE SPLASH BLOCK. OR WIRE TO INTERRUPT THERMOSTAT SIGNAL PER MANUFACTURERS INSTRUCTIONS WATER LEVEL SENSOR TO SHUT SYSTEM DOWN IF WATER LEVEL RISES ABOVE DRAIN OPENING (SAFE-T OR SIMILAR) MECHANICALLY FASTEN BARRIER TO DUCT A RETURN AIR OPENING ON TOP OF DUCT LINED RETURN AIR DUCT. 16 GAUGE SHEET METAL WITH 1" THICK, 3# DENSITY DUCT LINER. 45° A © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 2 / 2 0 2 1 4 : 2 4 : 3 2 P M M-601 MECHANICAL DETAILS St a n l e y H o t e l P o s t R e s t a u r a n t T I KAN 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS PBM NOT TO SCALE 6 EVAPORATIVE COOLER PIPING DETAIL NOT TO SCALE 1 KITCHEN HOOD EXHAUST DETAIL NOT TO SCALE 2 KITCHEN GREASE DUCT FIRE WRAP AND PENETRATION DETAIL NOT TO SCALE 5 BRANCH DUCT TAKE-OFF DETAIL NOT TO SCALE 7 SQUARE DUCT TAKEOFF/TRANSITION DETAIL NOT TO SCALE 4 AIR DEVICE DETAIL NOT TO SCALE 8 DRAW-THRU UNIT COIL CONDENSATE TRAP PIPING DETAIL NOT TO SCALE 3 ROOF MOUNTED AHU SUPPORT AND ISOLATION DETAIL NOT TO SCALE 9 RETURN AIR DUCT DETAIL REVISION DATE ASI-T01 2/12/21 ASI-T02 2/24/21 ASI-T04 3/17/21 03/22/21 FACP FAA FARP FSCP FFCP ASFP MM CM RM M V RTS A H J P R FABP P S FF VS WF PS AA FS CO CO B 2 ABBREVIATIONS AND DESCRIPTIONS ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT ELECTRICAL LEGEND LIGHTING POWER ONE-LINE DIAGRAMS SYSTEMS GROUNDING/LIGHTNING I TO A A T1 4 K KEYLESS FIXTURE 600/100 100/5 TTB 30/3 30A 30/3 POLE MOUNTED FIXTURE FLUORESCENT STRIP CEILING FIXTURE WALL MOUNTED FIXTURE EXIT SIGN W/ARROW BATTERY PACK LANDSCAPE FIXTURE SINGLE-POLE SWITCH b P PHOTOCELL C POWER/TELEPHONE POLE IG DUPLEX RECEPTACLE SPECIAL PURPOSE OUTLET SINGLE RECEPTACLE L RACEWAY TURNED DOWN RACEWAY TURNED UP TC B S R T BUZZER HORN BELL PUSH BUTTON SOLENOID (LOW VOLTAGE) RELAY (LOW VOLTAGE) TIME CLOCK THERMOSTAT (LINE VOLTAGE) PB T2 CB J M JUNCTION BOX METER MOTOR BLANKED OUTLET PULL BOX B M D ELECTRIC DAMPER THERMAL OVERLOAD SWITCH LP EXOTHERMIC CONNECTION VS AS V A AMMETER SELECTOR SWITCH AMMETER VOLTMETER FUSE AND SWITCH < 600V FUSE < 600V CIRCUIT BREAKER < 600V CAPACITOR SWITCH AIR BREAK FUSE > 600V CABLE TERMINATION ST G ENGINE-GENERATOR UNIT C R G DIFFERENTIAL RELAY LOCKOUT RELAY PRESSURE SWITCH OVER VOLTAGE RELAY AC CIRCUIT BREAKER TIME OVER CURRENT RELAY 87 86 63 52 59 50 51 MANUAL SELECTOR SWITCH UNDER VOLTAGE RELAY27 43 OVERHEAD GUY OVERHEAD LINE 25 DOWN GUY AND ANCHOR 6 A 4 S INTERCOM MASTER UNIT VOLUME CONTROL TELEVISION OUTLET INTERCOM OUTLET M MICROPHONE OUTLET SPEAKER CALL-IN SWITCH SPEAKER SPEAKER HORN AMPLIFIER TELEPHONE/DATA OUTLET A M S S V WORK NOTE SYMBOL ROOM NUMBER REVISION SYMBOL E-5 1 220 (2#12 & 1#12G)3/4"C. (4#12 & 1#12G)3/4"C. (6#12 & 1#12G)3/4"C. (8#12 & 1#12G)3/4"C. M L1 2 9 2 J J WALL WASH BATTERY PAD MOUNTED TRANSFORMER 6M12 LC T GFP J (R)(RELOCATED) J J P C POWER JUNCTION BOX COMMUNICATION JUNCTION BOX 4WG100 AHU-1 FLUORESCENT FIXTURES MONITOR MODULE CONTROL MODULE RELEASE MODULE STROBE HORN/SPEAKER (RE: SPEC) HORN/SPEAKER/STROBE (RE: SPEC) MINI HORN MAGNETIC DOOR HOLD REMOTE LIGHT/TEST SWITCH FIRE OR EMERGENCY PHONE MANUAL PULL STATION HEAT DETECTOR - THERMAL R/C = RATE COMPENSATION HEAT DETECTOR - LINE TYPE (CABLE) SMOKE DETECTOR VALVE SUPERVISORY SWITCH PRESSURE SWITCH LOW AIR PRESSURE ALARM FIRE/SMOKE DAMPER CARBON MONOXIDE DETECTOR AUDIBLE ALARM ABORT SWITCH JLT GROUNDING CONDUCTORG GROUND BUS ON WALLGROUND ROD GROUND PATIENT GROUNDING POINTG XXcd XXcd CARD READERCR (RR) ISOLATED GROUND RECEPTACLE DOUBLE DUPLEX RECEPTACLE DUPLEX RECEPTACLE SPLIT WIRED NUMBER DESIGNATES DETAIL PRIMARY FUSE CUTOUT OIL TYPE CURRENT TRANSFORMER W/RATIO POTENTIAL TRANSFORMER W/RATIO VOLTMETER SELECTOR SWITCH AUTOMATIC TRANSFER SWITCH MANUAL TRANSFER SWITCH END OF LINE RESISTOR (EOL) RED AND GREEN PILOT LIGHTS PUSH-BUTTON-NORMALLY OPEN CONTACT NORMALLY OPEN (N.O.) CONTACT NORMALLY CLOSED (N.C.) AMP TRIPAT MANUAL TRANSFER SWITCHMTS HORSE POWERHP RELOCATED(R) BKR BREAKER DP (D) CKT C DISTRIBUTION PANEL DEDICATED CIRCUIT CONDUIT ATS AIC AF AFG AHU AFF +4'-6" A AMPERE INTERRUPTING CAPACITY AMP FRAME AUTO. TRANSFER SWITCH ABOVE FINISHED FLOOR ABOVE FINISHED GRADE AIR HANDLING UNIT MOUNTING HEIGHT AFF AMPS G GFCI FDR FA FCU GROUND FAN COIL UNIT FEEDER FIRE ALARM EPO EX F EWC EM EMT EOL EF (E) EMERGENCY POWER OFF EXPLOSION-PROOF ELECTRIC WATER COOLER FUSE OR FIRE END OF LINE RESISTOR ELEC. METALLIC TUBING EMERGENCY EXHAUST FAN EXISTING MDS MH MG MDP MTD MCC MAIN DIST. SWITCHBOARD MOTOR GENERATOR UNIT MANHOLE MAIN DISTRIBUTION PANEL MOTOR CONTROL CENTER MOUNTED KW L KVAR KV KVA IG GRC H KILOWATT KILOVAR ISOLATED GROUND KILO VOLT-AMPERE KILOVOLT GALVANIZED RIGID CONDUIT PT POTENTIAL TRANSFORMER RTU RM RT PVC ROOF TOP UNIT POLYVINYL CHLORIDE ROOM RAINTIGHT PF ø OR PH PDU NO NC NIC N POWER FACTOR POWER DISTRIBUTION UNIT PHASE NORMALLY CLOSED NORMALLY OPEN NOT IN CONTRACT NEUTRAL UPS V UG VOLTS UNDERGROUND TTC TTB SW TS SRG ST SCA TELEPHONE TERMINAL CABINET TELEPHONE TERMINAL BOARD SIGNAL REFERENCE GRID TEST SWITCH SWITCH SHUNT TRIP WP WHM VFD VDC VAC WEATHERPROOF WATTHOUR METER VARIABLE FREQUENCY DRIVE VOLTS DIRECT CURRENT AC ALTERNATING CURRENT B BATTERY CP CONTROL PANEL EC ELECTRICAL CONTRACTOR FS FI FIRE SUPPRESSION FILM ILLUMINATOR MONITOR LOW VOLTAGE M LV MECHANICAL CONTRACTORMC PREACTION SYSTEMPA ac ABOVE COUNTER REMOVE & RELOCATE(RR) CURRENT TRANSFORMERCT UC UNDERCABINET UF UNDERFLOOR ARC FAULT CIRCUIT INTERRUPTERAFCI UNO UNLESS NOTED OTHERWISE LOW VOLTAGE SWITCH b S SEAL OFF CAP FEEDER BUS DUCT 6(C)18 UG W EXTENSION WHIP MCC MOTOR CONTROL CENTER CP CONTROL PANEL OH OHG PRESENCE STATION MASTER STATION DUTY STATION STAFF STATION PATIENT STATION - 2 BED PATIENT STATION - 1 BED M 1 2 S D P EMERGENCY STATION DOME LIGHT WITH BUZZER E E S 2 B Z ZONE DOME LIGHT C M C C MASTER CLOCK CLOCK AND SPEAKER UNIT CLOCK OUTLET & CLOCK C C C 24 HOUR CLOCK 24 ET R ELAPSED TIME CLOCK GROUND FAULT CIRCUIT INTERRUPTER PREFIX DENOTING 277/480 PANEL PREFIX DENOTING 120/208V PANEL SHORT CIRCUIT CURRENT AVAILABLE VOLTS ALTERNATING CURRENT UNINTERRUPTIBLE POWER SUPPLY NUMBER REFERS TO FEEDER SCHEDULE REFERS TO EQUIPMENT SCHEDULE SHEET ON WHICH DETAIL IS LOCATED DASHED SYMBOLS DENOTE REMOVAL WORK LIGHT LINE WEIGHT SYMBOLS DENOTE EXISTING (REMOVE & RELOCATE) LIGHTING CONTACTOR W/ NO OF POLES LETTER REFERS TO FIXTURE SCHEDULE ALL FIXTURES IN ROOM ARE THIS TYPE UNLESS NOTED OTHERWISE LOWER CASE LETTER INDICATES SWITCHING SWITCHES GANGED IN SAME BOX REFER TO LIGHTING CONTROL SCHEDULE 2 = DOUBLE-POLE SWITCH 3 = THREE-WAY SWITCH 4 = FOUR-WAY SWITCH P = SWITCH AND PILOT LIGHT K = KEY OPERATED SWITCH D = DIMMER SWITCH RECESSED FLUORESCENT FIXTURES LIGHT TRACK WITH FIXTURE HEADS FIXTURE(S) ON EMERGENCY CIRCUIT GROUND FAULT CIRCUIT INTERRUPTER RECEPTACLE COMBINATION SWITCH AND DUPLEX RECEPTACLE CEILING SPECIAL PURPOSE OUTLET CEILING DUPLEX RECEPTACLE FLOOR MOUNTED DUPLEX RECEPTACLE MULTI-OUTLET ASSEMBLY (NO. INDICATES RECEPTACLES AND SPACING IN INCHES O.C.) FLOOR MOUNTED JUNCTION BOX TRANSFORMER (SEE TRANSFORMER SCHEDULE) TOGGLE DISCONNECT SWITCH 30 AMP CIRCUIT BREAKER DISCONNECT W/SIZE NON-FUSED DISCONNECT SWITCH W/SIZE FUSED DISCONNECT SWITCH W/SIZE MOTOR STARTER OR CONTACTOR COMBINATION MOTOR STARTER/DISCONNECT SWITCH BASEBOARD HEATING STRIP (ELECTRICAL) BRANCH CIRCUIT PANELBOARD MAIN DISTRIBUTION PANEL OR SWITCHBOARD CABLE TRAY WITH DEPTH/LOAD/WIDTH CONCEALED RACEWAY HOME RUN INDICATES NUMBER OF CIRCUITS, WIRES AND CONDUIT SIZE UNLESS OTHERWISE NOTED: WEATHER HEAD SERVICE ENTRANCE SINGLE PHASE TRANSFORMER: NUMERAL INDICATES RATING IN KVA PRIMARY FUSE CUTOUT AIR TYPE SWITCH AIR BREAK, GANG OPERATED UNDERGROUND DUCTS: NUMERAL INDICATES QUANTITY OF DUCTS LETTER INDICATES SYSTEM MANHOLE: NUMERAL INDICATES THE ASSIGNED NUMBER AND THE LETTER INDICATES THE TYPE PUSH-BUTTON- NORMALLY CLOSED OPERATING COIL (LADDER DIAGRAM) OPERATING COIL (SCHEMATIC DIAGRAM) INSTANTANEOUS OVER CURRENT RELAY LOAD BREAK ELBOW SEPARABLE CONNECTION PANEL BOARD DESIGNATION INSIDE TRANSFORMER (SEE TRANFORMER SCHEDULE) CIRCUIT BREAKER WITH GROUND FAULT PROTECTION BREAKER WITH DRAWOUT FEATURE < 600V BREAKER WITH DRAWOUT FEATURE > 600V FUSED DISCONNECT SWITCH > 600V CIRCUIT BREAKER WITH: ST = SHUNT TRIP K = KEY INTERLOCKED E = ELECTRIC OPERATED TELEPHONE TERMINAL CABINET "TTC" TELEPHONE TERMINAL BACKBOARD TELEPHONE OUTLET FLOOR MOUNTED TELEPHONE OUTLET W = WALL MOUNTED P = PAY PHONE F = FIREMAN PHONE CCTV AIR SAMPLING CONTROL DETECTION PANEL FIRE ALARM ANNUNCIATOR FIRE ALARM BOOSTER PANEL FIRE ALARM RELEASE PANEL FIREFIGHTER SMOKE CONTROL PANEL FIRE FIGHTER CONTROL PANEL V = BELL VS = BELL/STROBE C = CHIME CS = CHIME/STROBE FIRE OR EMERGENCY PHONE - HANDSET FIRE OR EMERGENCY PHONE - ACCESSIBLE FIRE OR EMERGENCY PHONE - JACK R = RATE OF RISE ONLY F = FIXED TEMPERATURE R/F = R OF R & FIXED TEMPERATURE FLAME DETECTOR F = FLAME UV = ULTRAVIOLET IR = INFRARED VR = VISIBLE RADIATION DUCT SMOKE DETECTOR S = SUPPLY AIR R = RETURN AIR C = COMBINATION SMOKE/HEAT DETECTOR P = PHOTOELECTRIC I = IONIZATION BT = BEAM TRANSMITTER BR = BEAM RECIEVER ASD = AIR SAMPLING EMERGENCY STATION S = SHOWER T = TOILET DOME LIGHT MASTER CLOCK AND PROGRAM CONTROL RESET SWITCH FOR ELAPSED TIME CLOCK LIGHTNING PROTECTION BARE CONDUCTOR SURGE ARRESTER PLUS GROUND LIGHTNING PROTECTION AIR TERMINAL GROUND ROD WITH INSPECTION WELL FIRE ALARM CONTROL PANEL NUMBER INDICATES LAMPS WR WEATHER RESISTANT SPD SURGE PROTECTIVE DEVICE S = SURFACE UG = UNDERGROUND W = WIREWAY UF UF = UNDERFLOOR NL NIGHT LIGHT TR TAMPER RESISTANT WATER FLOW SWITCH T J 18 " ( 1 ' - 6 " ) 42 " ( 3 ' - 6 " ) 48 " ( 4 ' - 0 " ) - 7 9 " ( 6 ' - 7 " ) MA X 7 9 " ( 6 ' - 7 " ) P E R N E C 4 0 4 . 8 ( A ) TOP OF OPERABLE DEVICE/HANDLE TOP OF OPERABLE DEVICE/HANDLE FINISHED FLOOR NOTES: 1. DEVICES ABOVE DOORS SHALL BE CENTERED BETWEEN TOP OF DOOR TRIM AND CEILING LINE. 2. MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE. 3. MOUNTING HEIGHTS SHALL BE COORDINATED WITH OTHER DEVICES, ARCHITECT, AND BE COMPLIANT WITH ADA AND CODE REQUIREMENTS. CENTER OF DEVICE CENTER OF DEVICE VFD LC © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 0 8 A M E-001 ELECTRICAL GENERAL INFORMATION St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTVDENVER OFFICE COLORADO SPRINGS OFFICE 10807 NEW ALLEGIANCE DRIVE, SUITE 400 COLORADO SPRINGS, CO 80921 719.533.1112 5420 WARD ROAD, SUITE 200 ARVADA, CO 80002 303.422.7400 TAMPA OFFICE 12450 ROOSEVELT BLVD N., SUITE 305 ST. PETERSBURG, FL 33716 727.685.0458 MELBOURNE OFFICE 6555 N. WICKHAM ROAD, SUITE 104 MELBOURNE, FL 32940 321.241.4142 PROJECT ENGINEER/DESIGNER PROJECT MANAGER BRENT SPANGLER BSPANGLER@BCER.COM 720.879.4466 PAUL MISKOWICZ PMISKOWICZ@BCER.COM 303.405.2902 CONTACT LIST DRAWING LIST - ELECTRICAL E-001 ELECTRICAL GENERAL INFORMATION E-002 ELECTRICAL SCHEDULES E-003 ELECTRICAL SPECIFICATIONS E-004 ELECTRICAL COMCHECK E-200 BASEMENT LIGHTING PLAN E-201 LEVEL 1 LIGHTING PLAN E-300 BASEMENT POWER PLAN E-301 LEVEL 1 POWER PLAN E-302 ROOF POWER PLAN E-501 ELECTRICAL ONE-LINE DIAGRAM E-502 PANEL SCHEDULES REMODEL TO CORE AND SHELL TO PROVIDE POWER AND LIGHTING FOR KITCHEN, BAR, AND DINING. PROJECT NARRATIVE 25. PROVIDE INDIVIDUAL NEUTRALS AS REQUIRED BY NEC ON ALL NEW AND AFFECTED EXISTING CIRCUITS. 24. PROVIDE UNIT PRICE FOR ADDITIONAL EXIT SIGN(S) AND INSTALLATION AS REQUIRED BY INSPECTOR (AHJ). 23. PROTECT FIXTURES THROUGHOUT CONSTRUCTION. 22. RECEPTACLES SHALL NOT BE MOUNTED BACK-TO-BACK IN ANY WALLS. 21. ALL EXTERIOR RECEPTACLES TO HAVE LOCKABLE, IN-USE COVERS. 20. X-RAY THE FLOOR PRIOR TO CORE DRILL UNLESS NOTED OTHERWISE. 19. IDENTIFY JUNCTION BOXES WITH PANEL AND CIRCUIT NUMBER. 18. ALL RECEPTACLES WITHIN 6 FEET OF A SINK ARE TO BE GFCI TYPE AND GFCI RECEPTACLES SHALL BE IN A READILY ACCESSIBLE LOCATION PER NEC. WHERE RECEPTACLE IS INACCESSIBLE, PROVIDE A REMOTE GFCI RESET BUTTON IN A READILY ACCESSIBLE LOCATION. 17. NOT USED. 16. SUPPORT ALL CONDUITS, CABLES, BOXES AND LUMINAIRES FROM STRUCTURE PER NEC 300.11. LAY-IN FIXTURES SHALL BE SUPPORTED WITH TWO #12AWG WIRES FROM OPPOSITE ENDS UNLESS OTHERWISE NOTED. 15. EXISTING ELECTRICAL OUTLET, DEVICE, EQUIPMENT ITEM, LUMINAIRE, ETC., (SHOWN AS DASHED) SHALL BE REMOVED TO THE NEAREST REMAINING OUTLET OR BRANCH CIRCUIT OVER-CURRENT DEVICE. MAKE MODIFICATIONS TO EXISTING REMAINING SYSTEM AS REQUIRED TO MAINTAIN CONTINUITY. 14. CONTRACTOR TO VISIT THE JOB SITE TO SURVEY EXISTING CONDITIONS PRIOR TO BID. 13. CONTRACTOR TO UPDATE PANELBOARD DIRECTORIES WHERE CIRCUITS HAVE BEEN DELETED OR ADDED. 12. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN THE ELECTRICAL SCHEDULES AND AS REQUIRED IN EACH SECTION OF SPECIFICATION TO THE ENGINEER FOR REVIEW PRIOR TO THE ORDER, PURCHASE OR INSTALLATION OF THESE SAME ITEMS. 11. ALL ELECTRICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE CODES LISTED ON THIS SHEET AND THE ARCHITECTURAL CODE PLAN. 10. CONTRACTOR SHALL FIELD VERIFY ALL ELECTRICAL ITEMS PRIOR TO COMMENCING NEW WORK. NO ADDITIONAL COST WILL BE ALLOWED FOR CONTRACTOR'S FAILURE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. 9. CONTRACTOR SHALL CLOSELY COORDINATE NEW ELECTRICAL WITH ALL NEW MECHANICAL, PLUMBING, ELECTRICAL, FIRE PROTECTION, ARCHITECTURAL AND STRUCTURAL MEMBERS. 8. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATION AND INSTALLATION OF SLEEVES, INSERTS AND SUPPORTS AS REQUIRED FOR THIS SCOPE OF WORK AND/OR CORE DRILL REQUIREMENTS. COORDINATE WITH G.C. AND STRUCTURAL ENGINEER AS REQUIRED. 7. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY DIRECTED OTHERW ISE. 6. CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY SYSTEMS/SERVICES WITHOUT FIRST COORDINATING ALL DOWNTIME WITH OWNER'S PERSONNEL. CONTRACTOR SHALL PROVIDE A DETAILED M.O.P. AS REQUIRED. DO NOT BEGIN WORK WITHOUT WRITTEN APPROVAL. 5. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN INTENT, ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE AS SHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS ARE REQUIRED FOR FIELD COORDINATION OF ALL TRADES, THIS CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL COSTS. 4. COORDINATE ALL LUMINAIRE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN, FIRE PROTECTION, AND ELECTRICAL DRAWINGS. 3. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAVE BEEN SELECTED AS THE BASIS OF DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATED BY THE CONTRACTOR AS TO SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS AND PERFORMANCE. ANY ADDITIONAL COSTS EITHER DIRECTLY OR INDIRECTLY CAUSED BY EQUALS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. 2. DRAWINGS AND SPECIFICATIONS ARE COMPLIMENTARY. W HATEVER IS CALLED FOR IN EITHER IS BINDING AS THOUGH CALLED FOR IN BOTH. 1. ALL NEW WORK IS SHOWN BY SOLID BOLD LINES; ALL EXISTING WORK IS SHOWN AS LIGHT LINES. DASHED LINES INDICATES REMOVAL. ELECTRICAL GENERAL NOTES 4. A FINAL COMMISSIONING REPORT SHALL BE PROVIDED PRIOR TO BUILDING TURNOVER WHICH INCLUDES DOCUMENTATION OF ALL TESTS, RESULTS, CORRECTIVE MEASURES TAKEN, ETC. COMMISSIONING REPORT SHALL BE IN COMPLIANCE WITH THE REFERENCED CODES ABOVE. 3. THE COMMISSIONING SCOPE SHALL INCLUDE, BUT IS NOT LIMITED TO, ATTENDING COMMISSIONING MEETINGS, COMPLETING PREFUNCTIONAL CHECKLISTS. DEMONSTRATING SYSTEM PERFORMANCE AND ADDRESSING COMMISSIONING AUTHORITY REVIEW COMMENTS. 2. THE ELECTRICAL CONTRACTOR SHALL INCLUDE AN ALLOWANCE IN THEIR BID ASSOCIATED WITH THE COMMISSIONING PROCESS. 1. THIS PROJECT SHALL INCLUDE COMMISSIONING OF THE ELECTRICAL AND LIGHTING SYSTEMS AS REQUIRED BY SECTION C408 OF THE 2015 IECC. ELECTRICAL COMMISSIONING NOTES AND LOCAL AMENDMENTS 2020 NATIONAL ELECTRICAL CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL BUILDING CODE ADOPTED/ENFORCED CODES REQUIRED REVISION DATE ASI-T01 02/12/2021 1 1 1 NOT TO SCALE 1 TYPICAL DEVICE MOUNTING HEIGHTS 1 1 03/23/21 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 1 0 A M E-002 ELECTRICAL SCHEDULES St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV LUMINAIRE SCHEDULE KEY SOURCE POWER DESCRIPTION FINISH MOUNTING MANUFACTURER CATALOG # NOTES TYPE CRI CCT DELIVERED LUMENS VOLT VA DIMMING TYPE DEPTH MOUNT HEIGHT E24 LED 80 3500 4103 277 V 36 0-10V 2'X4' LED EDGE LIT FLAT PANEL WHITE BAKED ENAMEL RECESSED 1.68" COLUMBIA CFP24-4135-HE EE LED 70 3000 1830 277 V 28 0-10V DECORATIVE WALL SCONCE WITH TYPE III DISTRIBUTION ARCTIC WHITE WALL ** ARCHITECTURAL AREA LIGHTING PROS-Y3-2030-WH-WMA59U P1 HALOG EN 120 V 20 ELV 3" ROUND PUCK LIGHT WITH LOW VOLTAGE TRANSFORMER CLEAR SURFACE 6-7/16" FURNISHED BY OTHERS P2 LED 120 V 25 10% 2FT DIAMETER LED PENDANT FIXTURE FURNISHED BY OTHERS P3 LED 120 V 25 10% 2FT DIAMETER LED PENDANT FIXTURE FURNISHED BY OTHERS P4 LED 90+ 3000 1000 277 V 14 0-10V 12" METAL DOME PENDANT WITH WIRE GUARD AND COIL CORD DROP MOUNTING. GALVANIZED PENDANT +9'-0" BASELITE SG12-49-TLB-LED12W-27K-G R12-CDM7-120/277 P5 LED 80+ 2700 2000 277 V 25 0-10V 3" CYLINDER, SURFACE MOUNT, WIDE DISTRIBUTION BLACK SURFACE 6" PRESCOLITE LTC-3RD-S-20L-27K-8-WD-D M1 P6 HALOG EN 120 V 60 ELV 4FT HOUSING 3 LED HEAD ACCENT LIGHTS WHITE FURNISHED BY OTHERS R LED 80 3500 4800 277 V 55 0-10V 4' LENSED LED STRIP PROVIDE IN CORE AND SHELL PROJECT TO BE REMOVED STANDARD SURFACE OR CHAIN 3.06" RX2 LED N/A N/A N/A 277 V 4 NONE RELOCATED FROM PHASE 1, DOUBLE FACE LED EXIT SIGN WHITE UNIVERSAL --- DUAL-LITE SEDGWE S2 LED 70 3000 1830 120 V 75 ELV TOLEDO OUTDOOR WALL SCONCE 11" SHADE, OLD SILVER FINISH ARCTIC WHITE WALL ** TROY LIGHTING TRY111948 S4 LED 120 V 25 10% CORD PENDANT FIXTURE WITH LED GLASS LAMP FURNISHED BY OTHERS T8 LED 80 2700 1070 277 V 30 0-10V 8' LIGHTING TRACK (48V) WITH 3 LED HEADS, E15 SPOT 3" BLACK BRUCK TRACK: SMT-0##-2, HEAD: 350419-SW-13LM-27K-80-SS A40-BK-SMT-DIM10Z T12 LED 80 2700 1070 277 V 50 0-10V 12' LIGHTING TRACK (48V) WITH 5 LED HEADS, E15 SPOT 3" BLACK BRUCK TRACK: SMT-0##-2, HEAD: 350419-SW-13LM-27K-80-SS A40-BK-SMT-DIM10Z T26 LED 80 2700 1070 277 V 80 0-10V 26' LIGHTING TRACK (48V) WITH 8 LED HEADS, E15 SPOT 3" BLACK BRUCK TRACK: SMT-0##-2, HEAD: 350419-SW-13LM-27K-80-SS A40-BK-SMT-DIM10Z X1 LED N/A N/A N/A 277 V 4 NONE SINGLE FACE LED EXIT SIGN WHITE UNIVERSAL --- DUAL-LITE SESGWE C. SUBMITTALS FOR ALL LUMINAIRES MUST INCLUDE PROJECT SPECIFIC SHOP DRAWINGS INDICATING ALL PARTS AND ACCESSORIES REQUIRED FOR A COMPLETE AND OPERATIONAL ASSEMBLY. B. VERIFY EXACT LENGTHS OF LUMINAIRE COMPONENTS WITH ARCHITECTURAL RCP AND ARCHITECTURAL ELEVATIONS PRIOR TO STARTING WORK. A. COORDINATE AND VERIFY ALL LUMINAIRE REQUIREMENTS WITH ARCHITECT PRIOR TO SUBMITTALS INCLUDING, BUT NOT LIMITED TO, MOUNTING METHOD, MOUNTING HEIGHT(S), AND FINISHES AND/OR COLORS. LUMINAIRE SCHEDULE GENERAL NOTES E - KITCHEN EQUIPMENT SCHEDULE EQUIPMENT DESIGNATION EQUIPMENT DESCRIPTION Voltage Phase VA DISC. SIZE Panel Circuit Number CB SIZE FEEDER SIZE REMARKS Level 1A WALK-IN FREEZER, LTG 120 V 1 720 VA S K1A 80 Basement 1B WALK-IN COOLER, LTG 120 V 1 720 VA S K1A 78 Basement 1C WALK-IN BEER COOLER, LTG 120 V 1 720 VA S K1A 74 Basement 2/3/4 REFRIGERATION SYSTEM REMOTE RACK 208 V 3 18072 VA 100/3 K1A 2,4,6 100 (3#1 & 1#8G)1-1/4"C Roof Level 5 BEER COOLER EVAP 120 V 1 192 VA S K1A 72 Basement 6 COOLER EVAP 120 V 1 192 VA S K1A 76 Basement 7 FREEZER EVAP 208 V 1 1123 VA S2P K1A 82,84 Basement 17 PLANETARY MIXER 208 V 1 3328 VA NEMA 6-15 K1A 60,62 20 (2#12 & 1#12G)3/4"C Basement 18 WATER METER 120 V 1 200 VA REC K1A 68 Basement 23 SODA 120 V 1 720 VA REC K1A 66 Basement 30 FOOD PROCESSING MACHINE 120 V 1 840 VA REC K1A 70 Basement 33 IMMERSION HAND MIXER 120 V 1 938 VA REC K1A 64 Basement 97 EXHAUST HOOD 120 V 1 720 VA S K1A 13 Level 1 103 DISHWASHER 208 V 3 19800 VA 100/3 K1A 8,10,12 70 (3#4 & 1#8G)1-1/4"C Level 1 110 WALK-IN COOLER, LTG 120 V 1 720 VA S K1A 11 Level 1 111 WALK-IN COOLER, EVAP 120 V 1 192 VA S K1A 9 Level 1 123 TILTING SKILLET BRAISING PAN 208 V 1 12000 VA CB K1B 27,29 80 (2#4 & 1#8G)1"C Level 1 124A GAS CONVECTION OVEN, BLOWER MOTORS 120 V 1 924 VA REC K1B 17 Level 1 124B GAS CONVECTION OVEN, BLOWER MOTORS 120 V 1 924 VA REC K1B 14 Level 1 126 EQUIP. STAND, REFRIGERATED BASE 120 V 1 1248 VA REC K1B 7 Level 1 136A GAS FRYER, CONTROLLER/FILTER 120 V 1 1200 VA REC K1B 19 Level 1 136B GAS FRYER, HEAT LAMP 120 V 1 938 VA REC K1B 13 Level 1 136C GAS FRYER, CONTROLLER/FILTER 120 V 1 1200 VA REC K1B 20 Level 1 136D GAS FRYER, HEAT LAMP 120 V 1 938 VA REC K1B 25 Level 1 137A ELECTRIC PRESSURE FRYER 208 V 3 10512 VA CB K1B 2,4,6 50 (3#6 & 1#10G)3/4"C Level 1 137B ELECTRIC PRESSURE FRYER 208 V 3 10512 VA CB K1B 1,3,5 50 (3#6 & 1#10G)3/4"C Level 1 137C ELECTRIC PRESSURE FRYER 208 V 3 10512 VA CB K1B 8,10,12 50 (3#6 & 1#10G)3/4"C Level 1 141A HEATED HOLDING CABINET 120 V 1 960 VA REC K1A 27 Level 1 141B HEATED HOLDING CABINET 120 V 1 960 VA REC K1A 19 Level 1 142A UNDERCOUNTER REFRIGERATOR 120 V 1 480 VA REC K1A 25 Level 1 142B UNDERCOUNTER REFRIGERATOR 120 V 1 480 VA REC K1A 21 Level 1 143 UNDERCOUNTER REFRIGERATOR 120 V 1 360 VA REC K1A 17 Level 1 145 SERVICES CUSTOM FABRICATION 120 V 1 500 VA CB K1A 23 Level 1 146 SERVICES CUSTOM FABRICATION 120 V 1 500 VA CB K1A 15 Level 1 147 HEATED HOLDING CABINET 120 V 1 960 VA REC K1A 49 Level 1 148 PIZZA PREP REFRIGERATOR 120 V 1 468 VA REC K1A 55 Level 1 149 REACH-IN U.C. FREEZER 120 V 1 276 VA REC K1A 53 Level 1 150 HOT WELL UNIT 208 V 1 3600 VA CB K1A 45,47 30 (2#10 & 1#10G)3/4"C Level 1 151 SANDWICH/SALAD PREP. REGRIG. 120 V 1 780 VA REC K1A 41 Level 1 152 COLD FOOD WELL UNIT, REFRIGERATED 120 V 1 240 VA REC K1A 35 Level 1 153A WAFFLE MAKER/BAKER 120 V 1 1440 VA REC K1A 37 Level 1 153B WAFFLE MAKER/BAKER 120 V 1 1440 VA REC K1A 39 Level 1 154 CONVEYOR TOASTER 208 V 1 4451 VA NEMA 6-30 K1A 31,33 30 (2#10 & 1#10G)3/4"C Level 1 160 INFRARED FOOD WARMER 120 V 1 3680 VA CB K1A 57 40 (2#8 & 1#10G)3/4"C Level 1 161 UNDERCOUNTER REFRIGERATOR 120 V 1 360 VA REC K1A 77 Level 1 162 ICED TEA BREWER 120 V 1 1680 VA REC K1A 75 Level 1 163 COFFEE BREWER 208 V 1 2980 VA CB K1A 79,81,83 20 (3#12 & 1#12G)3/4"C Level 1 164 SODA & ICE BEVERAGE DISPENSER 120 V 1 180 VA S K1A 73 Level 1 166A POS 120 V 1 180 VA REC K1A 36 Level 1 166B POS 120 V 1 180 VA REC K1A 71 Level 1 166C POS 120 V 1 180 VA REC K1A 44 Level 1 166D POS 120 V 1 180 VA REC K1A 42 Level 1 166E POS 120 V 1 180 VA REC K1A 40 Level 1 167A REFRIGERATED BACK BAR CABINET 120 V 1 330 VA REC K1A 43 Level 1 167B REFRIGERATED BACK BAR CABINET 120 V 1 330 VA REC K1A 51 Level 1 167C REFRIGERATED BACK BAR CABINET 120 V 1 330 VA REC K1A 38 Level 1 171 ICE MAKER 208 V 1 3016 VA CB K1A 14,16,18 30 (3#10 & 1#10G)3/4"C Level 1 178A BLENDER STATION 120 V 1 1440 VA REC K1A 34 Level 1 178B BLENDER STATION 120 V 1 1440 VA REC K1A 32 Level 1 REVISION DATE ASI-T01 02/12/2021 MECHANICAL EQUIPMENT SCHEDULE TAG DESCRIPTION VOLTAGE PHASE HP MCA KW KVA DISC. SIZE PANEL CIRCUIT CB SIZE FEEDER SIZE REMARKS KEF-1 KITCHEN EXHAUST FAN 480 V 3 3 4.0 30/3 HMA 7,9,11 15 (3#12 & 1#12G)3/4"C MAU-1 MAKE-UP AIR UNIT 480 V 3 9.5 7.9 30/3 HMA 2,4,6 15 (3#12 & 1#12G)3/4"C RTU-1 ROOF TOP AIR HANDLING UNIT 208 V 3 28 10.1 60/3 K1A 50,52,54 40 (3#8 & 1#10G)3/4"C (4) (3) (2) AIM SENSOR TO PROVIDE BEST COVERAGE. AIM TO AVOID FALSE READINGS FROM OUTSIDE OF THE SPACE CONTROLLED. (1) PROVIDE ALL REQUIRED RELAYS, ROOM CONTROLLERS, ETC. FOR A COMPLETE AND OPERATIONAL SYSTEM. LIGHTING CONTROLS SCHEDULE PROJECT SPECIFIC NOTES G. NOT ALL LIGHTING CONTROL DESIGNATIONS UTILIZED IN THIS PROJECT. F. COORDINATE ENGRAVING OF MULTI-BUTTON SWITCHES WITH OWNER PRIOR TO ORDERING AND INSTALLATION. E. COORDINATE OCCUPANCY AND PHOTOCELL LOCATIONS FOR OPTIMAL PERFORMANCE BASED ON MANUFACTURER'S RECOMMENDATIONS. D. ALL DEVICES SHALL BE CALIBRATED BY THE VENDORS STARTUP TEAM. ELECTRICAL CONTRACTOR SHALL SCHEDULE THIS PRIOR TO FINAL PUNCH. C. ALL DEVICES SHALL BE OF THE SAME MANUFACTURER, UNLESS NOTED OTHERWISE. B. ALL SENSOR LAYOUTS AND QUANTITIES ARE SCHEMATIC IN NATURE AND ARE SHOWN ONLY TO COMMUNICATE THE DESIGN INTENT OF EACH SPACE. A. PROVIDE PROJECT SPECIFIC SHOP DRAWINGS FOR ALL LIGHTING CONTROLS ASSOCIATED WITH THIS PROJECT. PROVIDE FLOOR PLANS WITH ALL DEVICES LOCATED, CONTROL DIAGRAMS WITH WIRING CONNECTIONS SHOWN, EQUIPMENT LOAD CALCS, AND CUT SHEETS. LIGHTING CONTROLS SCHEDULE GENERAL NOTES 1E EMERGENCY TRANSFER DEVICE 277 V WATTSTOPPER 1R LOW VOLTAGE ROOM CONTROLLER 277 V WATTSTOPPER SC SCENE CONTROLLER X X X X 24V WATTSTOPPER 5C LOW VOLTAGE ADJUSTABLE OCCUPANCY SENSOR X X PIR 90 DEGREE 24 V 30 MIN WATTSTOPPER (1) 4C LOW VOLTAGE OCCUPANCY SENSOR X X PIR 360 DEGREE 24 V 30 MIN WATTSTOPPER (1) 3C LOW VOLTAGE OCCUPANCY SENSOR X X DUAL CORRIDOR 24 V 30 MIN WATTSTOPPER (1) 2C LOW VOLTAGE ADJUSTABLE OCCUPANCY SENSOR X X DUAL 90 DEGREE 24 V 30 MIN WATTSTOPPER (1) (2) 1C LOW VOLTAGE OCCUPANCY SENSOR X X DUAL 360 DEGREE 24 V 30 MIN WATTSTOPPER (1) 1T LOW VOLTAGE SWITCH WITH ON/OFF CONTROL AND INTEGRAL TIMER X X 24 V 5-30 MIN WATTSTOPPER 4P WALL MOUNTED LOW VOLTAGE PHOTOCELL OPEN LOOP 24 V 35 WATTSTOPPER 3P WALL MOUNTED LOW VOLTAGE PHOTOCELL CLOSED LOOP 24 V 35 WATTSTOPPER 2P CEILING MOUNTED LOW VOLTAGE PHOTOCELL OPEN LOOP 24 V 35 WATTSTOPPER 1P CEILING MOUNTED LOW VOLTAGE PHOTOCELL CLOSED LOOP 24 V 35 WATTSTOPPER 5L MULTI BUTTON LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING CONTROL 24 V 5 WATTSTOPPER 4L MULTI BUTTON LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING CONTROL 24 V 4 WATTSTOPPER 3L MULTI BUTTON LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING CONTROL 24 V 3 WATTSTOPPER 2L MULTI BUTTON LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING CONTROL 24 V 2 WATTSTOPPER 1L SINGLE BUTTON LOW VOLTAGE SWITCH WITH ON/OFF AND 0-10V DIMMING CONTROL 24 V 1 WATTSTOPPER 2S LINE VOLTAGE SWITCH WITH INTEGRAL SENSOR X X DUAL 277 V 10 MIN WATTSTOPPER 1S LINE VOLTAGE SWITCH WITH INTEGRAL SENSOR X X DUAL 277 V 10 MIN WATTSTOPPER 2W LOW VOLTAGE ADJUSTABLE OCCUPANCY SENSOR X X PIR 90 DEGREE 24 V 10 MIN WATTSTOPPER (1) (2) 1W LOW VOLTAGE ADJUSTABLE OCCUPANCY SENSOR X X DUAL 90 DEGREE 24 V 10 MIN WATTSTOPPER (1) (2) KEY DEVICE TYPE/DESCRIPTION AUTO ON AUTO OFF MANUAL ON MANUAL OFF TECHNOLOGY COVERAGE PATTERN VOLTAGE NUMBER OF BUTTONS MAINTAINED FOOTCANDLE... TIME DELAY NEUTRAL REQUIRED MANUFACTURER CATALOG # ALTERNATE MANUFACTURER ALTERNATE CATALOG #NOTES LIGHTING CONTROLS SCHEDULE 1 03/23/21 ELECTRICAL SPECIFICATIONS DIVISION 260000 -ELECTRICAL SPECIFICATION 260500 -BASIC ELECTRICAL REQUIREMENTS GENERAL REQUIREMENTS A. SEE GENERAL CONDITIONS AND ALL OTHER REQUIREMENTS RELATING TO ELECTRICAL SYSTEMS FOR THIS PROJECT. B. PROVIDE ALL ITEMS FOR COMPLETE AND SUCCESSFUL OPERATION OF ALL ELECTRICAL SYSTEMS. C. ELECTRICAL DRAWINGS ARE DIAGRAMMATIC ONLY. ELECTRICAL SUBCONTRACTOR IS RESPONSIBLE FOR INSTALLATION OF ALL WORK ACCORDING TO ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AS WELL. D. WORD "PROVIDE" SHALL MEAN "THIS CONTRACTOR SHALL FURNISH, INSTALL AND CONNECT". E. VISIT SITE AND INCLUDE ALLOWANCE IN BID FOR ALL COSTS RELATED TO THE ELECTRICAL INSTALLATION. F. DEMONSTRATE THE OPERATION OF ALL ELECTRICAL SYSTEMS FOR THE OWNER AT A TIME AS DIRECTED BY ARCHITECT. G. LAY OUT ALL WORK IN ADVANCE. DO NOT DEFACE WORK OF OTHER TRADES. INSTALL ALL SLEEVES AND BLOCKOUTS; WATERPROOF AS REQUIRED. H. ALL OUTAGES ON THE ENTIRE OR ON PORTIONS OF EXISTING OR NEW ELECTRICAL SYSTEM SHALL BE MINIMIZED AND SHALL BE COORDINATED WITH THE OWNER AND UTILITY COMPANY. OUTAGE DURATION SHALL BE AS ACCEPTED BY THE OWNER AND SHALL BE SCHEDULED THREE (3) DAYS IN ADVANCE. INCLUDE AN OVERTIME ALLOWANCE IN THE BID FOR PERFORMANCE OF WORK REQUIRING OUTAGES AT SUCH A TIME AS IS APPROVED BY THE OWNER. I. FIELD CHECK ALL EXISTING CONDITIONS AND INCLUDE AN ALLOWANCE IN THE BID FOR THE REMOVAL AND/OR RELOCATION OF EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, ETC., AS INDICATED ON THE PLANS OR AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING ELECTRICAL SYSTEMS TO ALL OTHER WORK. J. FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT AND PROVIDE ALL LABOR REQUIRED TO COMPLETE THE WORK SHOWN ON THE DRAWINGS. ALL OTHER WORK AND MISCELLANEOUS ITEMS NOT SPECIFICALLY MENTIONED BUT REQUIRED FOR TESTING THE SYSTEM SHALL BE PROVIDED. IT IS THE INTENT OF DRAWINGS AND SPECIFICATIONS THAT ALL SYSTEMS BE COMPLETE AND OPERABLE. STANDARDS A. ALL ELECTRICAL MATERIALS SHALL BE NEW (EXCEPT IF INDICATED OR SPECIFIED OTHERWISE), IN FIRST-CLASS CONDITION, UNDERWRITERS' LABORATORIES, INC. (UL) APPROVED AND SHALL COMPLY WITH APPLICABLE NEMA STANDARDS. B. COMPLY WITH ALL APPLICABLE LOCAL AND STATE ORDINANCES AND LATEST EDITION OF: IBC -INTERNATIONAL BUILDING CODE, NEC -NATIONAL ELECTRICAL CODE, NFPA CODES, AND WITH THE REQUIREMENTS OF UTILITY AND TELEPHONE COMPANIES FURNISHING SERVICE. C. PROCURE AND PAY FOR ALL PERMITS, LICENSES AND LIABILITY INSURANCE, ETC. FURNISH CERTIFICATE OF FINAL INSPECTION AND APPROVAL FROM LOCAL INSPECTOR. D. MATERIAL SHALL BE AS SPECIFIED UNLESS PRIOR ACCEPTANCE HAS BEEN OBTAINED FROM ARCHITECT SEVEN (7) DAYS BEFORE BID OPENING. GUARANTEE A. REPLACE ANY WORK OR MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FROM NORMAL WEAR, WITHIN ONE (1) YEAR AFTER COMPLETION. COORDINATION A. PRIOR TO FABRICATION OR INSTALLATION OF ANY ELECTRICAL WORK, PARTICIPATE IN DETAILED COORDINATION PLANNING MEETINGS WITH ALL OTHER CONSTRUCTION TRADES, UNDER THE DIRECTION OF THE GENERAL CONTRACTOR, SO AS TO COMPLETELY ESTABLISH ROUTINGS, ELEVATIONS, SPACE REQUIREMENTS, AND COORDINATION OF ACCESS, LAYOUT, AND SUSPENSION REQUIREMENTS IN RELATIONSHIP TO THE BUILDING STRUCTURE AND THE WORK OF ALL OTHER TRADES. B. THIS CONTRACTOR SHALL COORDINATE DIVISION 26 WORK WITH THE INSTALLER OF DIVISION 21,22, AND 23 AND OTHER WORK TO ENSURE THAT CODE REQUIRED CLEARANCES RELATING TO SPACE REQUIRED FOR ACCESS TO ELECTRICAL EQUIPMENT, ALONG WITH LIMITATIONS RELATING TO INSTALLATION OF MECHANICAL OR OTHER PIPING, DUCTWORK, OR EQUIPMENT ABOVE, OR ADJACENT TO, ELECTRICAL APPARATUS, ARE PROPERLY MAINTAINED. C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATION AND MOUNTING HEIGHTS OF DEVICES. FINAL LOCATION OF ALL DEVICES TO BE DETERMINED BY THE ARCHITECT. D. PRIOR TO COMMENCING CONSTRUCTION, NOTIFY ENGINEER OF ANY DISCREPANCIES BETWEEN ELECTRICAL DRAWINGS AND ANY OTHER PROJECT DRAWINGS (I.E., ARCHITECTURAL, FURNITURE SYSTEM, MECHANICAL, STRUCTURAL, ETC) AS WELL AS DISCREPANCIES BETWEEN DRAWINGS AND EXISTING FIELD CONDITIONS. E. ALL OPENINGS MADE IN FIRE-RATED WALLS, FLOORS OR CEILINGS, SHALL BE PATCHED AND MADE TIGHT IN A MANNER TO CONFORM TO THE FIRE RATING FOR THE SURFACE PENETRATED. 260519 -BUILDING WIRE AND CABLE A. MINIMUM WIRE SIZE FOR BRANCH CIRCUITS NO. 12 AWG. EXCEPT FOR CONTROL CIRCUITS, WHICH MAY BE NO. 14 AWG. SIGNAL CIRCUITS WIRE SIZE SHALL BE AS INDICATED ON THE DRAWINGS. ALL WIRING SHALL BE ROUTED WITHIN RACEWAYS. B. USE NO. 10 AWG CONDUCTOR FOR 20 AMPERE, 120-VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 75 FEET, AND FOR 20 AMPERE, 277-VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 200 FEET. C. CONDUCTOR INSULATION SHALL BE OF TYPE RECOGNIZED BY THE NATIONAL ELECTRIC CODE AS APPROVED FOR ITS PARTICULAR APPLICATION. 1. ALL WIRES REGARDLESS OF SIZE, TYPE THWN AND THHN EXCEPT AS NOTED. 2. ALL WIRING IN METAL ROOF DECKS, IN OR NEAR ROOF INSULATION, OR EXPOSED TO SUN, TYPE THW. D. THE USE OF MC CABLE IS ACCEPTABLE WHERE PROPERLY SUPPORTED AND WHEN INSTALLED IN ACCORDANCE WITH NEC. E. SPLICES FOR NO. 8 AND SMALLER WIRE, WIRE OR WING NUTS. F. ALL WIRE SHALL BE COPPER, INSULATED FOR 600 VOLTS. G. ALL WIRES SHALL BE COLOR CODED. WIRES NO. 6 AWG AND SMALLER SHALL BE FACTORY COLOR-CODED. WIRE NO. 4 AWG AND LARGER MAY BE COLOR-CODED BY FIELD PAINTING OR COLOR TAPING OF 6 INCH LENGTH OF EXPOSED ENDS. H. 120/208V SYSTEM: PHASE A = BLACK, B = RED, C = BLUE, NEUTRAL = WHITE, GROUND = GREEN I. 277/480V SYSTEM: PHASE A = BROWN, B = ORANGE, C = YELLOW, NEUTRAL = GRAY, GROUND = GREEN 260532 -CONDUIT SYSTEMS A. RIGID CONDUIT, INTERMEDIATE METALLIC CONDUIT, AND/OR ELECTRICAL METALLIC TUBING AS PERMITTED BY NEC. B. SCHEDULE 40, RIGID PVC PLASTIC CONDUIT FOR ALL LOCATIONS DIRECTLY IN EARTH, GRAVEL, ETC, OR DIRECTLY BELOW OR IN CONCRETE SLAB-ON-GRADE. C. PROVIDE FLEXIBLE METAL CONDUIT WHERE WIRING MUST BE FISHED OR FOR EQUIPMENT, MOTORS, LIGHTING FIXTURE OR TRANSFORMER CONNECTIONS. D. ALL EMT CONNECTORS AND COUPLINGS SHALL BE STEEL, COMPRESSION GLAND OR SETSCREW TYPE. CONNECTORS AND COUPLINGS MADE OF MALLEABLE IRON OR OTHER MATERIALS ARE NOT ACCEPTABLE. E. INSTALL RACEWAYS CONCEALED. SURFACE-MOUNT CONDUITS IN ELECTRICAL AND MECHANICAL ROOMS OR WHERE APPROVED BY THE ARCHITECT. F. EXPOSED RACEWAY, FITTINGS, JUNCTION BOXES AND COVERS INSTALLED IN FINISHED AREAS SHALL BE PRE-FINISHED BLACK. G. RACEWAY AND OUTLET SUPPORTS: 1. TOGGLE BOLTS IN HOLLOW MASONRY. 2. EXPANSION BOLTS IN CONCRETE OR BRICK. 3. MACHINE SCREWS ON METAL SURFACES. 4. WOOD SCREWS ON WOOD CONSTRUCTION. 260534 -BOXES A. FOUR-INCH (4") SQUARE OR OCTAGONAL, ZINC-COATED SHEET STEEL BOXES. B. PROVIDE THREE-EIGHTHS INCH (3/8") NO BOLT FIXTURE STUDS FOR FIXTURE OUTLETS. C. PROVIDE COVERS SET TO COME FLUSH WITH FINISHED WALLS. D. UTILITY OR SECTIONAL SWITCH BOXES ONLY WHERE PERMITTED. E. VERIFY MOUNTING HEIGHTS OF ALL OUTLETS PRIOR TO INSTALLATION. LOCATE OUTLETS TO CLEAR COUNTERS, BENCHES, BASEBOARDS OR FINTUBE HEATERS, ETC, OR AS REQUIRED TO SERVICE EQUIPMENT. F. SUPPORT: OUTLET, DEVICE, PULL AND JUNCTION BOXES RIGIDLY FROM THE STRUCTURE EITHER DIRECTLY OR BY USING A RIGID SUPPORT, IN ACCORDANCE WITH REQUIREMENTS OF ART. 314-23 OF THE NEC. 262726 -WIRING DEVICES A. DEVICES SHALL BE AS FOLLOWS: 1. SPECIFICATION GRADE RECEPTACLES: P&S 5850 SERIES OR AS ACCEPTED; GROUND FAULT CIRCUIT INTERRUPTERS: P&S 2097 SERIES, OR AS ACCEPTED. MOUNTING HEIGHT +18 INCH A.F.F. TO CENTER OR AS NOTED. 2. WEATHERPROOF OUTLET COVER: P&S WIU SERIES, OR AS ACCEPTED. 3. AC QUIET-OPERATING TYPE SWITCHES: P&S PS20 SERIES, OR AS ACCEPTED. MOUNTING HEIGHT +42 INCH A.F.F. TO CENTER OR AS NOTED. 4. DIMMER SWITCH: "SLIDE TO OFF" TYPE, WITH A VA (W) RATING SUITABLE FOR THE LOAD SERVED: LUTRON NOVA SERIES, OR AS ACCEPTED. MOUNTING HEIGHT +42-INCH A.F.F. TO CENTER OR AS NOTED. B. DEVICE PLATES SHALL BE: NYLON, EXCEPT AS DIRECTED BY ARCHITECT. C. SPECIAL PURPOSE RECEPTACLES OR OTHER DEVICES SHALL BE AS INDICATED ON THE DRAWINGS. D. WIRING DEVICES AND DEVICE PLATES COLOR SHALL BE AS DIRECTED BY THE ARCHITECT AND OWNER. FOR REMODEL WORK, MATCH COLOR OF NEW WITH REMAINING. 260526 -GROUNDING A. ALL SERVICE EQUIPMENT, CONDUIT SYSTEMS, SUPPORTS, CABINETS, LIGHTING STANDARDS, POLES, EQUIPMENT, FIXTURES, ETC, AND THE GROUNDED CIRCUIT CONDUCTOR SHALL BE PROPERLY GROUNDED IN ACCORDANCE WITH THE LATEST ISSUE OF THE NATIONAL ELECTRICAL CODE. PROVIDE BONDING JUMPERS, GROUNDING BUSHINGS, CLAMPS, ETC, FOR COMPLETE GROUNDING. 1. PROVIDE A SEPARATE GROUNDING CONDUCTOR, SECURELY GROUNDED ON EACH SIDE OF ALL RACEWAYS CONTAINING SECTIONS OF PLASTIC, FIBER, CEMENT, OR FLEXIBLE RACEWAYS. SIZE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. 2. PROVIDE A GREEN GROUNDING JUMPER FROM THE GROUND SCREW TO A BOX GROUNDING SCREW OR CLIP FOR ALL GROUNDING TYPE DEVICES. USE INSULATED WIRE. 3. PROVIDE A SEPARATE EQUIPMENT GROUNDING CONDUCTOR IN EVERY FEEDER AND BRANCH CIRCUITS, INCLUDING MC CABLE. IF THE SIZE IS NOT INDICATED ON THE DRAWINGS, SIZE IN ACCORDANCE WITH TABLE 250-122 OF NEC. 260580 -EQUIPMENT WIRING SYSTEM A. WHERE OUTLETS ARE INDICATED FOR MISCELLANEOUS EQUIPMENT REQUIRING ELECTRICAL POWER OR CONTROL, PROVIDE WIRE, CONDUIT, OUTLETS, HEAVY DUTY DISCONNECT SWITCHES, ETC, AND MAKE ALL REQUIRED CONNECTIONS. B. PROVIDE GROUNDING FOR ALL EQUIPMENT IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE. C. VERIFY EXACT CONNECTIONS REQUIRED FOR ALL EQUIPMENT PRIOR TO ROUGH IN. D. FOR INDIVIDUALLY MOUNTED MOTOR CONTROLLERS SUPPLIED UNDER SPECIFICATIONS DIVISIONS OTHER THAN DIVISION 26, CONTROLLERS AND DISCONNECTS SHALL BE SUPPLIED BY THE EQUIPMENT SUPPLIER. ELECTRICAL CONTRACTOR TO SET IN PLACE AND PROVIDE ALL REQUIRED CONNECTIONS. E. ELECTRICAL CONTRACTOR TO PROVIDE ALL MATERIALS AND LABOR REQUIRED FOR THE INSTALLATION AND TESTING OF OWNER SUPPLIED EMERGENCY GENERATOR AND TRANSFER SWITCH. 262411 -ELECTRIC SERVICE A. PROVIDE SERVICE AS INDICATED ON THE DRAWINGS. COORDINATE SERVICE LOCATION WITH UTILITY COMPANY. VERIFY AND COMPLY WITH ALL UTILITY COMPANY REQUIREMENTS. B. PROVIDE METERING FACILITIES, C.T. CABINETS, ETC., AS INDICATED ON THE DRAWINGS AND AS REQUIRED BY THE UTILITY COMPANY REQUIREMENTS. C. FUSIBLE DISCONNECT SWITCH SHALL BE HEAVY DUTY AND U.L. LISTED FOR SERVICE USE. 262413 -DISTRIBUTION EQUIPMENT A. CIRCUIT BREAKER OR SWITCH AND FUSE DISTRIBUTION PANELS AS INDICATED ON THE DRAWINGS. 262200 -DRY TYPE TRANSFORMERS A. NEMA ST 20, FACTORY-ASSEMBLED; COPPER WINDING; VENTILATED AIR COOLED DRY TYPE TRANSFORMERS; WITH RATINGS AS INDICATED ON THE DRAWINGS. B. INSULATION SYSTEM AND AVERAGE WINDING TEMPERATURE RISE FOR RATED KVA AS FOLLOWS: 1. 1-15 KVA: CLASS 185 WITH 115 DEGREES C RISE. 2. 16-500 KVA: CLASS 220 WITH 115 DEGREES C RISE. CASE TEMPERATURE NOT EXCEED 35 DEGREES C RISE ABOVE AMBIENT AT WARMEST POINT AT FULL LOAD. C. TAPS AND SOUND LEVEL PER NEMA ST 20. SOUND LEVEL SHALL NOT EXCEED 42 DB. D. MOUNTING: SUITABLE FOR WALL, FLOOR, OR TRAPEZE MOUNTING AS INDICATED ON THE DRAWINGS. TRANSFORMER CORE AND COIL TO BE ISOLATED FROM ENCLOSURE USING VIBRATION-ABSORBING MOUNTS. TRANSFORMER ENCLOSURE SHALL BE PROVIDED WITH LIFTING EYES OR BRACKETS. 1. USE FLEXIBLE CONDUIT, 2 FEET MINIMUM LENGTH, FOR CONNECTIONS TO TRANSFORMER CASE. MAKE CONDUIT CONNECTIONS TO SIDE PANEL OF ENCLOSURE. 2. MOUNT WALL-MOUNTED TRANSFORMERS USING INTEGRAL FLANGES OR ACCESSORY BRACKETS FURNISHED BY THE MANUFACTURER. 3. PROVIDE ISOLATING PADS SUITABLE FOR ISOLATING THE TRANSFORMER NOISE FROM THE BUILDING STRUCTURE. PROVIDE SEISMIC RESTRAINTS. E. PROVIDE GROUNDING AND BONDING IN ACCORDANCE WITH NEC. F. MEASURE PRIMARY AND SECONDARY VOLTAGES AND MAKE APPROPRIATE TAP ADJUSTMENTS FOR THE SPECIFIED VOLTAGE RANGE. G. WHEN HARMONIC RATED TRANSFORMERS ARE INDICATED ON DRAWINGS OR REQUIRED, THEY SHALL HAVE A RATING NOT LESS THAN K13. 262416 -PANELBOARDS A. DEAD-FRONT, CIRCUIT BREAKER TYPE, KEY LOCK, AND TYPED DIRECTORY CARDS. PANELS SHALL BE "DOOR IN DOOR" CONSTRUCTION. B. THERMAL MAGNETIC CIRCUIT BREAKERS, COMPLETELY INTERCHANGEABLE, BOLTED TO THE BUS. MULTI-POLE BREAKERS SHALL HAVE COMMON, INTERNAL TRIP. C. MINIMUM INTEGRATED SHORT CIRCUIT RATING: 10,000 AMPERES RMS SYMMETRICAL FOR 240 VOLT PANELBOARDS; 14,000 AMPERES RMS SYMMETRICAL FOR 480 VOLT PANELBOARDS, OR AS INDICATED ON THE DRAWINGS. D. EXCEPT SPECIFIED OTHERWISE, PANELBOARDS TYPE SHALL BE AS FOLLOWS: MANUFACTURER 120/208V*277/480V*15/1200A* 1. GENERAL ELECTRIC AQ AE CP 2. CUTLER-HAMMER PRL1 PRL2 PRL4 3. SQUARE-D NQOD NF I-LINE 4. SIEMENS P SERIES P SERIES P SERIES E.PANELBOARDS MAY CONTAIN NOT MORE THAN TWO SUBFEED BREAKERS WITH RATINGS IN EXCESS OF 100A, BUT LESS THAN 225A. F.PANELBOARDS SHALL BE OF TYPE SCHEDULED WHERE MORE THAN TWO SUBFEED BREAKERS RATED IN EXCESS OF 100A ARE REQUIRED, AND FOR ANY PANELBOARD CONTAINING BREAKERS WITH RATINGS OF 225A OR MORE. G.PANEL BUSES SHALL BE COPPER. 265100 -LIGHTING FIXTURES A. PROVIDE ALL NEW LIGHTING FIXTURES COMPLETE WITH LAMPS, DRIVERS, REFLECTORS, PLASTER FRAMES, FLANGES, LOUVERS, STEM HANGERS, ETC., ASSEMBLED AND READY FOR OPERATION AND AS DESCRIBED ON THE DRAWINGS. (VERIFY CEILING TYPES.) B. MOUNT ALL FIXTURES AT POSITION AND HEIGHT TO CLEAR DUCTS, ETC. C. PROVIDE TWO NO. 12 GAUGE HANGERS CONNECTED FROM THE FIXTURE HOUSING TO THE STRUCTURE, IN ADDITION TO THE FIXTURE REQUIRED ATTACHMENT TO THE CEILING SUSPENSION SYSTEM. D. ALL LAMPS SHALL BE ENERGY EFFICIENT TYPE, EQUAL TO GENERAL ELECTRIC, PHILLIPS OR SYLVANIA. 271100 -VOICE AND DATA CONDUIT SYSTEM A. COORDINATE WITH OWNER’S LOW VOLTAGE SYSTEM CONTRACTOR. PROVIDE BOXES, RACEWAYS, ETC. AS REQUIRED. END OF SPECIFICATION © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 1 0 A M E-003 ELECTRICAL SPECIFICATIONS St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV REVISION DATE ASI-T01 02/12/2021 1 03/23/21 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 1 4 A M E-004 ELECTRICAL COMCHECK St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV REVISION DATE ASI-T01 02/12/2021 1 03/23/21 F.E.C. F. E . C . F.E. OS OS OS OS OS OS OS LC 3C OS J J J J J J J J J J J J J J J J J J OS J J J LC 1S LC 1L LC 2S 4 3 2 1 AC DE A4 A4 A4 A4 A4 A4 A4 A4 A4 A4 A4 A4 A4 A4 B A4D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 D4 C4 B8 B8 B3L B3R B3R B3L X1 X1 X1 HBA-1 HBA INV INV-1 WJWJ WJ WJ WJ WJ CDM CDM CD CD WJWJ WJWJ WJWJ WJWJ C4 C4 TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS TS LBA LBA-21 LBA-23 INV-3 INV-4 LBA-25 INV-5 A4 A4 C4 INV-6 TS FREEZER 006 COOLER 005 BEER COOLER 003 E24 E24 E24 E24 E24 E24 E24 E24 E24 E24 E24 E24 L1 L1 L1 L1 L1 L1 L1 L1 L2 L2 L2 L4 L6LIQUOR STORAGE 004 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 ELEV. B10 OFFICE 001 WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A PLATFORM B02B LOBBY B01 TI STORAGE 010 R 1C C2 C1 a a a a a a a HBA-7 X1 X1 1 W2 C4 C4 C4 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 1 7 A M E-200 BASEMENT LIGHTING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV N 0 4'4' 2' 1/4" = 1'-0" 1 BASEMENT LIGHTING PLAN WORK NOTES C1 LIGHTING IN THIS ROOM SHALL BE CONTROLLED VIA LINE VOLTAGE SWITCH WITH INTEGRAL OCCUPANCY SENSOR. SWITCH SHALL PROVIDE ON/OFF AND 0-10V DIMMING CONTROL. C2 LIGHTING IN THIS ROOM SHALL BE CONTROLLED VIA LINE VOLTAGE SWITCH WITH INTEGRAL OCCUPANCY SENSOR. SWITCH SHALL PROVIDE ON/OFF CONTROL. L1 LIGHT FIXTURE PROVIDED IN CORE AND SHELL PROJECT TO BE REMOVED ALONG WITH ALL ASSOCIATED CONTROL DEVICES, WIRE AND CONDUIT TO ALLOW FOR NEW CONSTRUCTION IN THIS PROJECT. MAINTAIN POWER CONTINUITY TO LIGHT FIXTURES ON THE SAME CIRCUIT TO REMAIN. PROTECT FIXTURES AND CONTROL DEVIES FOR RE-USE WHERE POSSIBLE. FIXTURES AND CONTROL DEVICES NOT RE-USED TO BE TURNED OVER TO OWNER. L2 REFER TO COOLER/FREEZER UNIT MANUFACTURER WIRING DIAGRAMS AND CONNECT INTEGRAL LIGHTING AS REQUIRED. REFER TO POW ER PLAN AND KITCHEN EQUIPMENT SCHEDULE FOR CIRCUITING. L4 RELOCATED CEILING MOUNTED OCCUPANCY SENSOR. L6 RELOCATED LIGHT FIXTURE REVISION DATE ASI-T01 02/12/2021 1 1 03/23/21 C H D D D C V V G G G GG V CC D D G 3" J J J J J J J J J J J LC 1C LC 1C LC 1C LC 1C LC 1C LC 1CLC1C LC 1C LC 1C LC 1C LC SC LC1L LC 1L LC LC 3C LC 3C LC 3C LC 1C LC LC1L LC 1L 4 3 2 1 AC DE X1 X1 X1 RX2 B 3 3 DD DD DD DD DDDD C4 C4 F1F2F3 C3W C3W C3WC3WC3W C3W C3W DD DD DD C3W C3W C3W EE EE EE EE EEEE C4 C4 C4 C4 INV-1 INV-5 4 E24 E24 E24 E24 E24 E24 E24 E24 E24 P2 P2 T8 T8 T8 T26 T26 T26 T12 T8 P2 P1 P1 P1P1P1P1P1P1P1P1P1P1P1P1 P1 P1 P1 P1 P3 P3 P2 S2 P5 P5 P5 P5 P5 S4 (TYP.) L2 P6 P6 P6 P6 P6 P6 P6 P6 P6 E24 E24 E24 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 L1 PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 101 LIQ. STORAGE 106 PRIVATE PATIO 114 DINING 115 RETAIL 102 BAR 107 MAIN ENTRY 100 ? ? BOOTHS 116 BOOTHS 118 DINING 102 CIRCULATION 116 X1 X1 X1 X1 X1 S2 EE EE E24 E24 E24 E24 E24 E24 E24 E24 E24 L7L7 L1A-27 P4P4 P4 P4 P4 P4 P4P4P4 P4P4 P4 L1A-29 T12 T26 S2 X1 HBA-9 a a a a b b c c c c c c c c c d d d d HBA-5 a aaaa aaaa HBA-6 (VIA INVB) L8 e e e e e e e e e e e e e e f f f e e e e HBA-8 (VIA INVC) L9 a a b c c c c 3L a,b,c HBA-11 (VIA INVC) L10 L1A-33 1L g g L1A-35 1 C4 C4 C4 C4 C4 C5 k k k k k k k k k © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 2 1 A M E-201 LEVEL 1 LIGHTING PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV N 0 4'4' 2' 1/4" = 1'-0" 1 LEVEL 1 LIGHTING PLAN WORK NOTES C4 LIGHTING IN THIS ROOM TO BE CONTROLLED VIA NETWORKED TIMECLOCK. COORDINATE SCHEDULED SCENE CONTROLS WITH OWNER. PROVIDE LOW VOLTAGE SWITCH FOR MANUAL OVERRIDE CONTROLS, 2-HR TIMEOUT AFTER HOURS. OCCUPANCY SENSOR TO OVERRIDE AFTER HOURS, 10-MINUTE TIMEOUT. C5 LIGHTING IN THIS ROOM TO BE CONTROLLED VIA NETWORKED TIMECLOCK. COORDINATE SCHEDULE WITH OWNER. PROVIDE LOW VOLTAGE SWITCH FOR MANUAL OVERRIDE CONTROLS, 2-HR TIMEOUT AFTER HOURS. OCCUPANCY SENSOR TO OVERRIDE AFTER HOURS, 10-MINUTE TIMEOUT. L1 LIGHT FIXTURE PROVIDED IN CORE AND SHELL PROJECT TO BE REMOVED ALONG WITH ALL ASSOCIATED CONTROL DEVICES, WIRE AND CONDUIT TO ALLOW FOR NEW CONSTRUCTION IN THIS PROJECT. MAINTAIN POWER CONTINUITY TO LIGHT FIXTURES ON THE SAME CIRCUIT TO REMAIN. PROTECT FIXTURES AND CONTROL DEVIES FOR RE-USE WHERE POSSIBLE. FIXTURES AND CONTROL DEVICES NOT RE-USED TO BE TURNED OVER TO OWNER. L2 REFER TO COOLER/FREEZER UNIT MANUFACTURER WIRING DIAGRAMS AND CONNECT INTEGRAL LIGHTING AS REQUIRED. REFER TO POWER PLAN AND KITCHEN EQUIPMENT SCHEDULE FOR CIRCUITING. L7 PROVIDE CONTECH TAPE LIGHT AT TOP OF EACH SHELF, PROVIDE CONTECT TLT24V1RGBW, WITH REEL LENGTH AS REQUIRED. PROVIDE WITH POWER SUPPLIES, REPEATERS, CONNECTORS, ACCESSORIES, ETC. AS REQUIRED FOR A COMPLETE INSTALLATION. PROVIDE WITH ALUMINUM MOUNTING CHANNEL (TLACS6), QUANTITY AS REQUIRED. PROVIDE WITH FROSTED LENS (TLALF6), QUANTITY AS REQUIRED. PROVIDE WITH RGBW CONTROLLER (TLPRGBWRF). ALL TAPE LIGHT SHALL BE CONTROLLED FROM ONE REMOTE. DESIGN ASSUMES APPROXIMATELY 150' OF TAPE LIGHT FOR ALL SHELVING. COORDINATE EXACT MOUNTING WITH ARCHITECT. COORDINATE CONTROL INTENTION WITH OWNER. L8 PROVIDE EMERGENCY LIGHTING INVERTER "INVB" TO SERVE LIGHTING LOADS ON CIRCUIT NOTED. DUALLITE LG-250-S-AO. EMERGENCY LIGHTING TO DIM TO 50% OUTPUT UPON LOSS OF NORMAL POWER. L9 PROVIDE EMERGENCY LIGHTING INVERTER "INVC" TO SERVE LIGHTING LOADS ON CIRCUIT NOTED. DUALLITE LG-125-S-AO. EMERGENCY LIGHTING TO DIM TO 50% OUTPUT UPON LOSS OF NORMAL POWER. L10 PROVIDE EMERGENCY LIGHTING INVERTER "INVD" TO SERVE LIGHTING LOADS ON CIRCUIT NOTED. DUALLITE LG-125-S-AO. EMERGENCY LIGHTING TO DIM TO 50% OUTPUT UPON LOSS OF NORMAL POWER. REVISION DATE ASI-T01 02/12/2021 1 1 03/23/21 VFD M VFD M M TOM TOM TOM J J M M M VFD M VFD M VFD M M TOM TOM M J M J J J J J J J J J TOM TOM 4 3 2 1 AC DE MDP XLDP XLBA HBALBAHMA LDP LBT ac ac DOAS-1DOAS-1 MAU-1 AC-1AC-1 B-1B-1 CP-1CP-1 CP-2CP-2 +36" FCU-2FCU-2 FCU-1FCU-1 FCU-3FCU-3 CU-1CU-1 CU-2CU-2 CU-3CU-3 B INV UH-1UH-1 DWH-1DWH-1 DCP-1DCP-1 SP-1SP-1 ESP-1ESP-1 FREEZER 006 COOLER 005 BEER COOLER 003 5 1B 6 7 1A 1C E1 IT RACK LBT-3 LBT-1 LBT-1 LBA-2 LBA-2 LBA-2 LBA-8 LBA-6 LBT-3 LBA-5 LBA-5 LBA-5 LBA-3 LBA-3 LBA-3 LBA-1 LBA-10 LBA-3 LBA-3 LBA-20 LBA-22 LBA-24 LBA-12 LBA-12 LBA-26 LBA-12 LBA-12 1817 30 33 OFFICE 001 ac ac E3 LBA-32 LBA-34 LBA-36 E4 E4E5 K1A-58 23 1 LBA-38 LBA-40 LBA-42 2 2 2 LBA-39 LBA-37 IBT-1IBT-1 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 2 4 A M E-300 BASEMENT POWER PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV N 0 4'4' 2' 1/4" = 1'-0" 1 BASEMENT POWER PLAN WORK NOTES E1 SYMBOL INDICATES KITCHEN EQUIPMENT. ALL KITCHEN RECEPTACLES ARE TO BE FED FROM GFCI CIRCUIT BREAKERS IN THE PANELBOARD. REFER TO KITCHEN EQUIPMENT SCHEDULE FOR ELECTRICAL REQUIREMENTS FOR EACH ITEM. VERIFY ALL POWER REQUIREMENTS, LOCATIONS, AND MOUNTING HEIGHTS WITH KITCHEN EQUIPMENT SUPPLIER FOR ACTUAL KITCHEN EQUIPMENT TO BE PROVIDED FOR THIS PROJECT PRIOR TO ORDERING ELECTRICAL DEVICES AND PRIOR TO ROUGH IN. E3 PROVIDE PLUGMOLD WITH ALTERNATING USB AND NEMA 5-15 OUTLETS, 9" SPACING, LEGRAND BK20GB509TRUSBA OR APPROVED EQUAL. E4 PROVIDE SO DROP CORD. NEMA L5-20 TWIST-LOCK RECEPTACLE AND PLUG. (2#12, 1#12G) SO CORD WITH KELLEMS GRIP STRAIN RELIEF AT EACH END OF CORD. TERMINATE DROP CORD IN WOODHEAD YELLOW COMPOSITE BOX WITH 20A, 125V DUPLEX WEATHERPROOF RECEPTACLE. RECEPTACLE TO BE INSTALLED AT +60"AFF. E5 PROVIDE CORD REEL AT CEILING RECEPTACLE. HUBBELL CAT. NO. HBLI25143. TERMINATE CORD IN WOODHEAD YELLOW COMPOSITE BOX WITH 20A, 125V DUPLEX WEATHERPROOF RECEPTACLE. REVISION DATE ASI-T01 02/12/2021 ASI-T04 3/17/2021 03/23/21 C H D D D C V V G G G GG V CC D D G 3" JJ M M M MM M J J J J J J J J J J TO J J J JJJJ J J J J J J J J J 4 3 2 1 AC DE K1A LBA-1 FCU-8FCU-8 FCU-9FCU-9 FCU-6FCU-6 FCU-7FCU-7 FCU-5FCU-5 FCU-4FCU-4 L1A B WP/WR WP/WRWP/WR WP/WR WP/WR WP/WR WP/WR L1A-14 L1A-16 110 111 97 123 124A124B 126 136A 136B 136C 136D 137A 137B 137C 141A 142A 142B145 141B 143 146 154 152 153A 153B 151 150 147 149 148 167A 167B 160 166A 167C 103 166A 161 162 163 164 166B 178B 178A WP/WR WP/WR WP/WR WP/WR WP/WR WP/WR 166C 166D E1 (TYP.) AV RACK TV +72" 166E TV +102" TV +112" L1A-18 L1A-23 L1A-25 L1A-15 L1A-14L1A-17 L1A-19 L1A-21 COOLER 112 PRIVATE DINING 113 DISH 111 CIRCULATION 116 KITCHEN BOH 109 DINING 102 ENTRY 101 RETAIL 102 MAIN ENTRY 100 STORAGE 105 BAR BOH 108 PATIO 117 171 E3 (TYP) +30"AFF +30"AFF +30"AFF +30"AFF PROJECTOR +30"AFF +30"AFF K1B K1A-20 K1A-24 K1A-22 K1A-28 K1A-30 K1A-26 L1A-20 L1A-22 L1A-24 L1A-26 L1A-28 L1A-30 K1A-46 (PART) K1A-46 (PART)K1A-48 L1A-32 L1A-34 FIREPLACE 1 1 L1A-31 L1A-41 FACP1 SIGN 1 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 2 8 A M E-301 LEVEL 1 POWER PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV N 0 4'4' 2' 1/4" = 1'-0" 1 LEVEL 1 POWER PLAN WORK NOTES E1 SYMBOL INDICATES KITCHEN EQUIPMENT. ALL KITCHEN RECEPTACLES ARE TO BE FED FROM GFCI CIRCUIT BREAKERS IN THE PANELBOARD. REFER TO KITCHEN EQUIPMENT SCHEDULE FOR ELECTRICAL REQUIREMENTS FOR EACH ITEM. VERIFY ALL POWER REQUIREMENTS, LOCATIONS, AND MOUNTING HEIGHTS WITH KITCHEN EQUIPMENT SUPPLIER FOR ACTUAL KITCHEN EQUIPMENT TO BE PROVIDED FOR THIS PROJECT PRIOR TO ORDERING ELECTRICAL DEVICES AND PRIOR TO ROUGH IN. E3 PROVIDE PLUGMOLD WITH ALTERNATING USB AND NEMA 5-15 OUTLETS, 9" SPACING, LEGRAND BK20GB509TRUSBA OR APPROVED EQUAL. 1. ALL ELECTRICAL ITEMS SHOWN IN LIGHT LINE WEIGHT HAVE BEEN PROVIDED IN THE CORE AND SHELL PROJECT. ALL NEW ELECTRICAL WORK IS SHOWN IN DARK LINE WEIGHT AND AS NOTED. GENERAL NOTES REVISION DATE ASI-T01 02/12/2021 1 1 03/23/21 M VFD M TOM TOM J M M TOM 4 3 2 1 AC DE LBA-1 ACU-1ACU-1 EF-1EF-1 EF-2EF-2 KEF-1 B LBA-19 WP/WR RTU-1 2/3/4 L1A-36 FIREPLACE POWER VENT 1 E6 1 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 2 9 A M E-302 ROOF POWER PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV N 0 4'4' 2' 1/4" = 1'-0" 1 ROOF POWER PLAN WORK NOTES E6 REFER TO KITCHEN EQUIPMENT SCHEDULE. COORDINATE FUSE SIZE WITH EQUIPMENT VENDOR. REVISION DATE ASI-T01 02/12/2021 1 03/23/21 KVA KVA K 1 B G U A R D T V S S GF P M H B A L B A T L D P T L 1 A L B T K 1 A M H M A UG UG T UG G N #2/0 CU TO BUILDING STEEL SP A R E SP A C E SP A C E 200A 3P 350A 3P 400A 3P 100A 3P 1000A 3P MAIN DISTRIBUTION PANEL "MDP" 277/480V, 3Ø, 4W, N&G (1000A, 65,000 A.I.C.) 100A 3P T3 45 T7 225 UG UG UG UG SCC 90A 3P #2/0 CU TO BUILDING MAIN COLD WATER PIPE INCOMING PRIMARY SERVICE INCOMING SECONDARY SERVICE UTILITY PAD MOUNTED TRANSFORMER SECONDARY CONNECTION CABINET WITH BAR TYPE CT'S. 3/4"Øx10' LONG COPPER CLAD GROUND ROD STUB, CAP AND MARK AT LOCATION NEAR FILM CENTER METER MOUNTED ON SECONDARY CONNECTION CABINET. #6 CU BOTH MAIN BONDING JUMPER AND EQUIPMENT BONDING JUMPER SHALL BE 2/0 CU MINIMUM. 100A 3PH XLDPXLBA TV S S 4W G 2 0 0 P R I S E C PR I SE C 4W G 1 0 0 4W G 1 5 0 4W G 4 0 0 4W G 4 0 0 SE 4W G 2 2 5 S 30HP 100/3 90A ELEVATOR 4WG100 TO FILM CENTER 4WG150 (N) (N) 1 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 3 0 A M E-501 ELECTRICAL ONE-LINE DIAGRAM St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV NOT TO SCALE 1 ELECTRICAL ONE-LINE DIAGRAM Heating 3000 VA 100.00% 3000 VA PANEL CAPACITY:700 A Lighting 10500 VA 125.00% 13125 VA SPARE CAPACITY:231 A Kitchen - Non-Dwelling Unit 110575 VA 65.00% 71874 VA DEMAND CURRENT:469 A Equipment 48891 VA 100.00% 48891 VA Receptacle 19300 VA 75.91% 14650 VA DEMAND LOAD:168946 VA Motor 14886 VA 116.93% 17406 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:68836 VA 73614 VA 64702 VA 29 SPACE -- --0 0 -- -- SPACE 30 27 SPACE -- -- 0 0 -- -- SPACE 28 25 SPACE -- -- 0 0 -- -- SPACE 26 23 SPACE -- --0 0 -- -- SPACE 24 21 SPACE -- -- 0 0 -- -- SPACE 22 19 SPACE -- -- 0 0 -- -- SPACE 20 17 SPACE -- --0 0 -- -- SPACE 18 15 SPACE -- -- 0 0 -- -- SPACE 16 13 SPACE -- -- 0 0 -- -- SPACE 14 11 -- -- --5290 3200 -- -- -- 12 9 -- -- -- 5020 4400 -- -- -- 10 7 L1A 3 100 5756 2760 100 3 PANEL (E) GS 8 5 -- -- --9000 47212 -- -- -- 6 3 -- -- -- 9360 54834 -- -- -- 4 1 LBT 3 150 9360 50960 400 3 K1A 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING MCB RATING:700 A LOCATION:ELECTRICAL B07 VOLTAGE:208Y/120V, 3-PH MAINS TYPE:MCB FED FROM:XLDP AIC RATING:10,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:800 A NEUTRAL BUS:100%MOUNTING:SURFACE PANEL: LDP Heating 4200 VA 100.00% 4200 VA PANEL CAPACITY:1000 A Lighting 19956 VA 125.00% 24945 VA SPARE CAPACITY:553 A Kitchen - Non-Dwelling Unit 110575 VA 65.00% 71874 VA DEMAND CURRENT:447 A Equipment 86829 VA 100.00% 86829 VA Receptacle 26280 VA 69.03% 18140 VA DEMAND LOAD:371860 VA Motor 156872 VA 105.74% 165872 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:404712 VA 20 19 18 17 16 15 14 13 12 11 10 9 8 7 BUSSED SPACE 0 -- 6 SPARE - 100A3P 0 5 TVSS 0 4 ELEVATOR 33988 3 XLDP 207152 2 HMA 133240 1 HBA 30332 CKT DESCRIPTION LOAD REMARKS PANEL NOTES:EXISTING MCB RATING:1000 A LOCATION:ELECTRICAL B07 VOLTAGE:480Y/277V, 3-PH MAINS TYPE:MCB FED FROM: AIC RATING:65,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:1000 A NETURAL BUS:100.00%MOUNTING:FLOOR PANEL: MDP E. CONDUIT SIZES BASED ON EMT TYPE AND THW/THHW/THW-2/TW WIRE INSULATION. D. CONDUCTORS ARE COPPER WITH 60° C TERMINATIONS UP TO #1 AWG AND 75° C TERMINATIONS FOR LARGER CONDUCTORS PER N.E.C. 110.14. C. SUPPLY SIDE BONDING JUMPER SIZED PER TABLE 250.102(C)(1) OF 2020 N.E.C. B. EQUIPMENT BONDING JUMPER SIZED PER TABLE 250.102(C)(1) OF 2020 N.E.C. A. GROUNDING ELECTRODE CONDUCTOR SIZED PER TABLE 250.66 OF 2020 N.E.C. NOTES: T9 500 600 750 2[(3#500KCMIL & 1#1/0G)3"C] 1388 1600 5[(4#400KCMIL & 1#250KCMIL-G)4"C] #3/0 T8 300 360 450 2[(3#4/0 & 1#2G)2"C] 833 1000 4[(4#250KCMIL & 1#2/0G)2-1/2"C] #2/0 T7 225 270 350 (3#500KCMIL & 1#3G)3"C 625 700 2[(4#500KCMIL & 1#2/0G)3-1/2"C] #2/0 T6 150 180 225 (3#4/0 & 1#4G)2"C 416 500 2[(4#250KCMIL & 1#1/0G)3-1/2"C] #1/0 T5 112.5 135 175 (3#2/0 & 1#6G)2"C 312 350 (4#500KCMIL & 1#1/0G)3-1/2"C #1/0 T4 75 90 125 (3#1 & 1#6G)1-1/2"C 208 225 (4#4/0 & 1#2G)2-1/2"C #2 T3 45 54 70 (3#4 & 1#8G)1"C 125 150 (4#1/0 & 1#6G)2"C #6 T2 30 36 45 (3#6 & 1#10G)1"C 84 100 (4#1 & 1#6G)2"C #6 T1 15 18 25 (3#10 & 1#10G)3/4"C 42 50 (4#6 & 1#8G)1"C #8 FLA OCP (A) FEEDER (PRI) SEE NOTES: B, D, E FLA OCP (A) FEEDER (SEC) SEE NOTES: B, C, D, E KEY KVA 480 VOLT, 3 PHASE DELTA - PRIMARY 208Y/120 VOLT, 3 PHASE, 4W - SECONDARY GROUND ELECTRODE CONDUCTOR (GEC... DRY TYPE TRANSFORMER SCHEDULE E. NOT ALL FEEDER SIZES INDICATED ARE UTILIZED ON THIS PROJECT. D.CONDUIT SIZES BASED ON EMT OR PVC TYPE AS SHOWN AND THW/THHW/THW-2/TW WIRE INSULATION. C.ALL CONDUCTORS ARE COPPER WITH 60°C TERMINATIONS UP TO #1 AWG AND 75°C TERMINATIONS FOR LARGER CONDUCTORS PER NEC 110.14. B.WIRE SIZES CORRELATING TO OVERCURRENT DEVICE SETTING ARE NOT SIZED FOR VOLTAGE DROP. CONTRACTOR IS RESPONSIBLE FOR INCREASING WIRE AND CONDUIT SIZE TO MAINTAIN NO MORE THAN 3% VOLTAGE DROP FOR FEEDERS BASED ON MAX ALLOWABLE LOAD. A.EQUIPMENT GROUNDING CONDUCTOR SIZED PER TABLE 250.122 OF 2020 NEC. NOTES: - MECH REFER TO MECHANICAL EQUIPMENT SCHEDULE TVSS (3#1 + 1#1G)1-1/2"C - SE 4[(4#250KCMIL)2-1/2"C-PVC] GEC #3/0 3000 3WG3000 8[(3#500KCMIL + 1#400KCMILG)3"C] 4WG3000 8[(4#500KCMIL + 1#400KCMILG)3-1/2"C] 2500 3WG2500 7[(3#500KCMIL + 1#350KCMILG)3"C] 4WG2500 7[(4#500KCMIL + 1#350KCMILG)3-1/2"C] 2000 3WG2000 6[(3#500KCMIL + 1#250KCMILG)3"C] 4WG2000 6[(4#500KCMIL + 1#250KCMILG)3-1/2"C] 1600 3WG1600 5[(3#500KCMIL + 1#4/0G)3"C] 4WG1600 5[(4#500KCMIL + 1#4/0G)3-1/2"C] 1200 3WG1200 4[(3#350KCMIL + 1#3/0G)2-1/2"C] 4WG1200 4[(4#350KCMIL + 1#3/0G)3"C] 1000 3WG1000 4[(3#250KCMIL + 1#2/0G)2-1/2"C] 4WG1000 4[(4#250KCMIL + 1#2/0G)3"C] 800 3WG800 2[(3#500KCMIL + 1#1/0G)3"C] 4WG800 2[(4#500KCMIL + 1#1/0G)3-1/2"C] 600 3WG600 2[(3#350KCMIL + 1#1G)2-1/2"C] 4WG600 2[(4#350KCMIL + 1#1G)3"C] 500 3WG500 2[(3#250KCMIL + 1#2G)2-1/2"C] 4WG500 2[(4#250KCMIL + 1#2G)2-1/2"C] 400 3WG400 (3#500KCMIL + 1#3G)3"C 4WG400 (4#500KCMIL + 1#3G)3-1/2"C 350 3WG350 (3#500KCMIL + 1#3G)3"C 4WG350 (4#500KCMIL + 1#3G)3-1/2"C 300 3WG300 (3#350KCMIL + 1#4G)2-1/2"C 4WG300 (4#350KCMIL + 1#4G)3-1/2"C 250 3WG250 (3#250KCMIL + 1#4G)2-1/2"C 4WG250 (4#250KCMIL + 1#4G)2-1/2"C 225 3WG225 (3#4/0 + 1#4G)2"C 4WG225 (4#4/0 + 1#4G)2-1/2"C 200 3WG200 (3#3/0 + 1#6G)2"C 4WG200 (4#3/0 + 1#6G)2"C 175 3WG175 (3#2/0 + 1#6G)2"C 4WG175 (4#2/0 + 1#6G)2"C 150 3WG150 (3#1/0 + 1#6G)1-1/2"C 4WG150 (4#1/0 + 1#6G)2"C 125 3WG125 (3#1 + 1#6G)1-1/2"C 4WG125 (4#1 + 1#6G)2"C 100 3WG100 (3#1 + 1#8G)1-1/4"C 4WG100 (4#1 + 1#8G)1-1/2"C 70 3WG70 (3#4 + 1#8G)1"C 4WG70 (4#4 + 1#8G)1-1/4"C 60 3WG60 (3#4 + 1#10G)1"C 4WG60 (4#4 + 1#10G)1-1/4"C 50 3WG50 (3#6 + 1#10G)3/4"C 4WG50 (4#6 + 1#10G)1"C 40 3WG40 (3#8 + 1#10G)3/4"C 4WG40 (4#8 + 1#10G)3/4"C 30 3WG30 (3#10 + 1#10G)3/4"C 4WG30 (4#10 + 1#10G)3/4"C 20 3WG20 (3#12 + 1#12G)1/2"C 4WG20 (4#12 + 1#12G)3/4"C FEEDER IDENTIFIER COPPER CONDUCTORS IN EMT FEEDER IDENTIFIER COPPER CONDUCTORS IN EMT OC DEVICE SETTING THREE WIRE + GROUND FOUR WIRE + GROUND FEEDER SCHEDULE X21 K1B 5 208 1X C S 600 S 8925 1 5,141 0.0240 0.9766 5,020 X21 X20 RTU-1 30 208 8 C S 600 S 1557 1 5,141 0.8248 0.5480 2,817 X20 X19 SP 30 480 12 C S 600 S 617 1 1,710 0.3000 0.7693 1,315 X19 X18 KEF 40 480 12 C S 600 S 617 1 2,849 0.6665 0.6000 1,710 X18 X17 DOAS 40 480 12 C S 600 S 617 1 8,545 1.9989 0.3335 2,849 X17 X16 CONDENSING UNITS 35 480 6 C S 600 S 2425 1 15,396 0.8018 0.5550 8,545 X16 X15 ELEVATOR CONTROLLER 46 480 4X C S 600 S 15082 1 18,537 0.2040 0.8306 15,396 X15 X14 ELEVATOR DISC. 25 480 4X C S 600 S 15082 1 20,849 0.1247 0.8891 18,537 X14 X13 HMA 22 480 500 C S 600 S 22185 1 20,849 0.0746 0.9306 19,402 X13 X12 LBT 70 208 1X C S 600 S 8925 1 5,141 0.3357 0.7486 3,849 X12 X11 K1A 60 208 500 C S 600 S 22185 1 5,814 0.1309 0.8842 5,141 X11 X10 L1A 58 208 1 C S 600 S 7292 1 9,454 0.6262 0.6149 5,814 X10 X9 LDP 15 208 500 C S 600 S 22185 2 9,713 0.0273 0.9734 9,454 X9 X8 XLDP 480 208 225 T S 600 S 5 1 18,924 3.4962 0.2224 9,713 X8 X7 XLDP PRIMARY 30 480 500 C S 600 S 22185 1 20,849 0.1017 0.9077 18,924 X7 X6 LBA 10 208 1X C S 600 S 8925 1 3,514 0.0328 0.9683 3,402 X6 X5 XLBA 480 208 45 T S 600 S 3.2 1 15,245 9.0130 0.0999 3,514 X5 X4 XLBA PRIMARY 11 480 4 C N 600 S 3826 1 18,109 0.1879 0.8418 15,245 X4 X3 HBA 28 480 3X C N 600 S 13923 1 20,849 0.1513 0.8686 18,109 X3 X2 MDP 210 480 500 C N 600 S 26706 8 22,514 0.0799 0.9261 20,849 X2 X1 SCC 10 480 500 C N 600 S 26706 8 22,600 0.0038 0.9962 22,514 X1 X0 1000 KVA XCEL XFMR 22,600 X0 VOLTAGE VOLTAGE KVA RATING (C OR A) T=XFRMR (V) RUNS UPSTREAM PRIMARY SECONDARY XFRMR TRANSFORMER (S OR N) CLASS (S OR T) VALUE PARALLEL AVAILABLE DESCRIPTION LENGTH/ VOLTAGE/ WIRE SIZE/ WIRE MATERIAL/ CONDUIT VOLTAGE WIRES C OR Z # OF Isc f M I(sc Fault) PROJECT NAME:Stanley Hotel Carriage House PROJECT NO: 125120001 BY:BMS SHORT CIRCUIT SCHEDULE REVISION DATE ASI-T01 02/12/2021 1 1 1 1 UTILITY XFMR 1 03/23/21 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 3/ 2 3 / 2 0 2 1 1 1 : 2 5 : 3 3 A M E-502 PANEL SCHEDULES St a n l e y H o t e l P o s t R e s t a u r a n t T I BMS 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS JTV [1] LOAD SHOWN IS CONNECTED LOAD. PROVIDE 40A CIRCUIT BREAKER AND CIRCUIT USING (2#8, 1#10G)3/4"C. PANEL CAPACITY:225 A Heating 1200 VA 100.00% 1200 VA SPARE CAPACITY:184 A Lighting 9456 VA 125.00% 11820 VA DEMAND CURRENT:41 A Equipment 3950 VA 100.00% 3950 VA Receptacle 6980 VA 100.00% 6980 VA DEMAND LOAD:33721 VA Motor 8746 VA 111.72% 9771 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:10349 VA 10912 VA 9071 VA 41 SPARE 1 20 0 8556 -- -- -- 42 39 SPARE 1 20 0 9640 -- -- -- 40 37 SPARE 1 20 0 5440 70 3 XLBA 38 35 SPARE 1 20 0 0 20 1 SPARE 36 33 SPARE 1 20 0 0 20 1 SPARE 34 31 SPARE 1 20 0 0 20 1 SPARE 32 29 SPACE -- --0 0 -- -- SPACE 30 27 SPACE -- -- 0 0 -- -- SPACE 28 25 SPACE -- -- 0 0 -- -- SPACE 26 23 SPACE -- --0 0 -- -- SPACE 24 21 SPACE -- -- 0 0 -- -- SPACE 22 19 SPACE -- -- 0 0 -- -- SPACE 20 17 SPACE -- --0 0 -- -- SPACE 18 15 SPACE -- -- 0 0 -- -- SPACE 16 13 SPACE -- -- 0 0 -- -- SPACE 14 11 LTG-KITCHEN EM 1 20 169 0 -- -- SPACE 12 9 LTG-KITCHEN/BAR...1 20 793 0 -- -- SPACE 10 7 BASEMENT LIGHTING 1 20 364 170 20 1 TRACK LTG INVB 8 5 LTG-CIRCULATION 1 20 106 240 20 1 TRACK LTG INVC 6 3 FIRST LVL LIGHTING 1 20 54 425 20 1 LIGHTING 4 1 BASEMENT LIGHTING 1 20 843 3532 40 1 INVERTER [1]2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING MCB RATING:-LOCATION:ELECTRICAL B07 VOLTAGE:480Y/277V, 3-PH MAINS TYPE:MLO FED FROM:MDP AIC RATING:22,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:225 A NEUTRAL BUS:100%MOUNTING:SURFACE PANEL: HBA PANEL CAPACITY:400 A SPARE CAPACITY:229 A DEMAND CURRENT:171 A DEMAND LOAD:142240 VA Motor 133240 VA 106.75% 142240 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:44413 VA 44413 VA 44413 VA 41 SPACE -- --0 0 -- -- SPACE 42 39 SPACE -- -- 0 0 -- -- SPACE 40 37 SPACE -- -- 0 0 -- -- SPACE 38 35 -- -- --583 0 -- -- SPACE 36 33 -- -- -- 583 0 -- -- SPACE 34 31 ESP-1 3 20 583 0 -- -- SPACE 32 29 -- -- --3333 167 -- -- -- 30 27 -- -- -- 3333 167 -- -- -- 28 25 UH-1 3 20 3333 167 20 3 SP-1 26 23 -- -- --12000 12000 -- -- -- 24 21 -- -- -- 12000 12000 -- -- -- 22 19 CU-2 3 50 12000 12000 50 3 CU-3 20 17 -- -- --0 11033 -- -- -- 18 15 -- -- -- 0 11033 -- -- -- 16 13 SPARE 3 20 0 11033 45 3 CU-1 14 11 -- -- --1330 0 -- -- -- 12 9 -- -- --1330 0 -- -- -- 10 7 KEF-1 3 15 1330 0 20 3 SPARE 8 5 -- -- --1333 2633 -- -- --6 3 -- -- -- 1333 2633 -- -- --4 1 DOAS-1 3 15 1333 2633 15 3 MAU-1 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING MCB RATING:-LOCATION:ELECTRICAL B07 VOLTAGE:480Y/277V, 3-PH MAINS TYPE:MLO FED FROM:MDP AIC RATING:22,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:400 A NEUTRAL BUS:100%MOUNTING:SURFACE PANEL: HMA [1] GFCI CIRCUIT BREAKER. [2] PROVIDE LOCKING HASP. CIRCUIT BREAKER TO SERVE AS DISCONNECTING MEANS IAW NEC 422.31 [3] - PROVIDE SHUNT TRIP CIRCUIT BREAKER. PANEL CAPACITY:400 A Lighting 2880 VA 125.00% 3600 VA SPARE CAPACITY:74 A Kitchen - Non-Dwelling Unit 110575 VA 65.00% 71874 VA DEMAND CURRENT:326 A Equipment 20491 VA 100.00% 20491 VA Receptacle 8980 VA 100.00% 8980 VA DEMAND LOAD:117545 VA Motor 10080 VA 125.00% 12600 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:50960 VA 54834 VA 47212 VA 83 -- -- --993 562 -- -- -- 84 81 -- -- -- 993 562 20 2 FREEZER EVAP 82 79 [2] COFFEE BREWER 3 20 993 720 20 1 FREEZER LTG 80 77 [1] UC REFRIG 1 20 360 720 20 1 COOLER LTG 78 75 [1] ICED TEA BREWER 1 20 1680 192 20 1 COOLER EVAP 76 73 SODA,ICE, BEV DISP. 1 20 180 720 20 1 BEER COOLER LTG 74 71 [1] POS 1 20 180 192 20 1 BEER COOLER EVAP 72 69 SPARE 1 20 0 840 20 1 [1] FOOD PROCESSER 70 67 SPARE 1 20 0 200 20 1 [1] WATER METER 68 65 SPARE 1 20 0 720 20 1 [1] SODA 66 63 SPARE 1 20 0 938 20 1 [1] IMMERSION HAND... 64 61 [1] SPARE 1 20 0 1664 -- -- -- 62 59 [1] SPARE 1 20 0 1664 20 2 [1] PLANETARY MIXER 60 57 [2] IR FOOD WARMER 1 40 3680 180 20 1 [1] BASEMENT CORD... 58 55 [1] PIZZA PREP REF 1 20 468 0 -- -- SPACE 56 53 [1] REACH IN UC FRZR 1 20 276 3360 -- -- -- 54 51 [1] REFRIG BACK BAR 1 20 330 3360 -- -- -- 52 49 [1] HEATED HOLDING... 1 20 960 3360 40 3 RTU-1 50 47 -- -- --1800 360 20 1 [1] BAR TVS 48 45 [2] HOT WELL UNIT 2 30 1800 720 20 1 [1] KITCHEN CONV.... 46 43 [1] REFRIG BACK BAR 1 20 330 180 20 1 [1] POS 44 41 [1] SAND/SALAD PRE... 1 20 780 180 20 1 [1] POS 42 39 [1] WAFFLE MAKER 1 20 1440 180 20 1 [1] POS 40 37 [1] WAFFLE MAKER 1 20 1440 330 20 1 [1] REFRIG BACK BAR 38 35 [1] COLD FOOD WELL 1 20 240 180 20 1 [1] POS 36 33 -- -- -- 2226 1440 20 1 [1] BLENDER STATION 34 31 [1] CONVEYOR... 2 30 2226 1440 20 1 [1] BLENDER STATION 32 29 [1] SPARE 1 20 0 1000 20 1 [1] BAR PLUGMOLD 30 27 [1] HEATED HOLDING... 1 20 960 1000 20 1 [1] BAR PLUGMOLD 28 25 [1] UC REFRIGERATOR 1 20 480 1500 20 1 [1] BAR PLUGMOLD 26 23 [2] SERVICES 1 20 500 1000 20 1 [1] BACK BAR... 24 21 [1] UC REFRIGERATOR 1 20 480 1000 20 1 [1] BACK BAR... 22 19 [1] HEATED HOLDING... 1 20 960 1500 20 1 [1] BACK BAR... 20 17 [1] UC REFRIGERATOR 1 20 360 1005 -- -- -- 18 15 [2] SERVICES 1 20 500 1005 -- -- -- 16 13 EXHAUST HOOD 1 20 720 1005 30 3 [2] ICE MAKER 14 11 COOLER LTG 1 20 720 6600 -- -- -- 12 9 COOLER EVAP 1 20 192 6600 -- -- -- 10 7 SHUNT TRIP PANEL... -- -- 0 6600 70 3 DISHWASHER 8 5 -- -- --17436 6024 -- -- -- 6 3 -- -- -- 16512 6024 -- -- -- 4 1 [3] PANEL K1B 3 150 16960 6024 100 3 REFRIG SYS.RACK 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING PANEL. PROVIDE ALL NEW CIRCUIT BREAKERS. MCB RATING:-LOCATION:KITCHEN BOH 109 VOLTAGE:208Y/120V, 3-PH MAINS TYPE:MLO FED FROM:LDP AIC RATING:10,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:400 A NEUTRAL BUS:100%MOUNTING:RECESSED PANEL: K1A [1] - PROVIDE "LOCK ON" DEVICE FOR FIRE ALARM CONTROL PANEL CIRCUIT BREAKER TO PREVENT ACCIDENTAL "OFF". PANEL CAPACITY:100 A SPARE CAPACITY:53 A Lighting 2420 VA 125.00% 3025 VA DEMAND CURRENT:47 A Equipment 500 VA 100.00% 500 VA Receptacle 8340 VA 100.00% 8340 VA DEMAND LOAD:16965 VA Motor 4806 VA 106.12% 5100 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:5756 VA 5020 VA 5290 VA 41 [1] FACP 1 20 500 0 20 1 SPARE 42 39 SPARE 1 20 0 0 20 1 SPARE 40 37 SPACE -- -- 0 0 20 1 SPARE 38 35 LTG-TAPE LIGHT 1 20 720 150 20 1 FIREPLACE PWR VENT 36 33 LTG-BAR 1 20 765 500 20 1 FIRE PLACE 34 31 REC-DINING SOUTH 1 20 720 1080 20 1 REC-NORTH DINING 32 29 LTG DINING SOUTH 1 20 460 720 20 1 REC-PRIVATE DINING 30 27 LTG PRIVATE DINING 1 20 475 720 20 1 REC PRVT DINE 28 25 EXT SOFFIT REC 1 20 180 360 20 1 AV RACK PRVT DINE 26 23 EXT SOFFIT REC 1 20 180 720 20 1 REC DINING SOUTH 24 21 EXT SOFFIT REC 1 20 180 540 20 1 EXT REC SOUTH 22 19 EXT SOFFIT REC 1 20 180 540 20 1 EXT REC WEST 20 17 EXT SOFFIT REC 1 20 180 500 20 1 SIGN PROVISION 18 15 EXT SOFFIT REC 1 20 180 500 20 1 SIGN PROVISION 16 13 EF-2 1 20 1176 360 20 1 MAIN LEVEL RECEP 14 11 -- -- --290 290 -- -- -- 12 9 FCU-8 2 15 290 290 15 2 FCU-9 10 7 -- -- -- 290 290 -- -- -- 8 5 FCU-6 2 15 290 290 15 2 FCU-7 6 3 -- -- -- 290 290 -- -- -- 4 1 FCU-4 2 15 290 290 15 2 FCU-5 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING MCB RATING:-LOCATION:KITCHEN BOH 109 VOLTAGE:208Y/120V, 3-PH MAINS TYPE:MLO FED FROM:LDP AIC RATING:10,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:100 A NEUTRAL BUS:100%MOUNTING:RECESSED PANEL: L1A PANEL CAPACITY:150 A Heating 1200 VA 100.00% 1200 VA SPARE CAPACITY:80 A Lighting 2760 VA 125.00% 3450 VA DEMAND CURRENT:70 A Equipment 3950 VA 100.00% 3950 VA Receptacle 6980 VA 100.00% 6980 VA DEMAND LOAD:25351 VA Motor 8746 VA 111.72% 9771 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:5440 VA 9640 VA 8556 VA 41 EF-1 1 20 1656 180 20 1 BAR POS 42 39 MAU CONTROL PANEL 1 20 1200 1200 20 1 BAR DISHWASHER 40 37 IBT-1 HEATER (DOAS) 1 20 1200 500 20 1 BAR FRIG BAR 38 35 -- -- --450 720 20 1 REC-BASEMENT 36 33 BRANCH SEL BOXES 2 20 450 1220 20 1 REC-OFFICE/PLUGM...34 31 SPARE 1 20 0 360 20 1 IT RACK 32 29 -- -- --2050 200 20 1 DWH-1 30 27 AC-1 2 20 2050 180 20 1 DCP-1 28 25 LTG BSMT RESTROOM 1 20 840 350 20 1 SUMP PUMP CONTROL 26 23 LTG BSMT LOBBY 1 20 760 350 20 1 FLUE FAN CONTROL 24 21 LTG BSMT LOBBY 1 20 1160 350 20 1 SNOWMELT CONTROL 22 19 REC ROOF 1 20 180 180 20 1 REC GLYCOL FEED 20 17 -- -- --185 200 20 1 CP-1 18 15 FCU-3 2 15 185 200 20 1 B-1 16 13 -- -- -- 185 200 20 1 CP-2 14 11 FCU-2 2 15 185 900 20 1 REC MECH 12 9 -- -- -- 185 180 20 1 REC CONDENSORS 10 7 FCU-1 2 15 185 180 20 1 REF SHOP 8 5 REC JAN & RESTRM 1 20 540 180 20 1 REF SHOP 6 3 REC BSMNT 1 20 1080 0 20 1 SPARE 4 1 REC ELEV SHAFT TOP 1 20 540 540 20 1 REC RM B02A 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING MCB RATING:150 A LOCATION:ELECTRICAL B07 VOLTAGE:208Y/120V, 3-PH MAINS TYPE:MCB FED FROM:XLBA AIC RATING:10,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:225 A NEUTRAL BUS:100%MOUNTING:SURFACE PANEL: LBA [1] DO NOT PROVIDE THIS CIRCUIT BREAKER. SHOWN ONLY TO CONNECT ASSUMED LOAD. PANEL CAPACITY:150 A SPARE CAPACITY:73 A DEMAND CURRENT:77 A Equipment 27000 VA 100.00% 27000 VA DEMAND LOAD:27720 VA Receptacle 720 VA 100.00% 720 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:9360 VA 9360 VA 9000 VA 41 SPARE 1 20 0 0 20 1 SPARE 42 39 SPARE 1 20 0 0 20 1 SPARE 40 37 SPARE 1 20 0 0 20 1 SPARE 38 35 SPARE 1 20 0 0 20 1 SPARE 36 33 SPARE 1 20 0 0 20 1 SPARE 34 31 SPARE 1 20 0 0 20 1 SPARE 32 29 SPACE -- --0 0 -- -- SPACE 30 27 SPACE -- -- 0 0 -- -- SPACE 28 25 SPACE -- -- 0 0 -- -- SPACE 26 23 SPACE -- --0 0 -- -- SPACE 24 21 SPACE -- -- 0 0 -- -- SPACE 22 19 SPACE -- -- 0 0 -- -- SPACE 20 17 SPACE -- --0 0 -- -- SPACE 18 15 SPACE -- -- 0 0 -- -- SPACE 16 13 SPACE -- -- 0 0 -- -- SPACE 14 11 SPACE -- --0 0 -- -- SPACE 12 9 SPACE -- -- 0 0 -- -- SPACE 10 7 SPACE -- -- 0 0 -- -- SPACE 8 5 SPACE -- --0 9000 -- -- -- 6 3 REC LOUNGE 1 20 360 9000 -- -- -- 4 1 REC STAGE 1 20 360 9000 100 3 ASSUMED LOAD [1] 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:EXISTING MCB RATING:150 A LOCATION:B.O.H. B02A VOLTAGE:208Y/120V, 3-PH MAINS TYPE:MCB FED FROM:LDP AIC RATING:10,000 GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:150 A NEUTRAL BUS:100%MOUNTING:SURFACE PANEL: LBT [1] GFCI CIRCUIT BREAKER. [2] PROVIDE LOCKING HASP. CIRCUIT BREAKER TO SERVE AS DISCONNECTING MEANS IAW NEC 422.31 PANEL CAPACITY:150 A SPARE CAPACITY:58 A DEMAND CURRENT:92 A DEMAND LOAD:33090 VA Kitchen - Non-Dwelling Unit 50908 VA 65.00% 33090 VA LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR DEMAND LOAD TOTALS TOTAL CONNECTED LOAD:16960 VA 16512 VA 17436 VA 29 -- -- --6000 0 20 1 SPARE 30 27 [2] TILTING SKILLET 2 80 6000 0 20 1 SPARE 28 25 [1] FRYER HEAT LAMP 1 20 938 0 20 1 SPARE 26 23 [1] SPARE 1 20 0 0 -- -- SPACE 24 21 [1] SPARE 1 20 0 0 -- -- SPACE 22 19 [1] FRYER 1 20 1200 1200 20 1 [1] FRYER 20 17 [1] CONVECTION OVEN 1 20 924 0 -- -- SPACE 18 15 SPACE -- -- 0 0 -- -- SPACE 16 13 [1] FRYER HEAT LAMP 1 20 938 924 20 1 [1] CONVECTION OVEN 14 11 SPACE -- --0 3504 -- -- -- 12 9 SPACE -- -- 0 3504 -- -- -- 10 7 [1] REFRIG EQUIP... 1 20 1248 3504 50 3 [2] PRESSURE FRYER 8 5 -- -- --3504 3504 -- -- -- 6 3 -- -- -- 3504 3504 -- -- -- 4 1 [2] PRESSURE FRYER 3 50 3504 3504 50 3 [2] PRESSURE FRYER 2 CKT DESCRIPTION P CB A B C CB P DESCRIPTION CKT PANEL NOTES:NEW MCB RATING:-LOCATION:KITCHEN BOH 109 VOLTAGE:208Y/120V, 3-PH MAINS TYPE:MLO FED FROM:K1A AIC RATING:10K GROUNDING BUS:Yes ENCLOSURE:NEMA 1 AMPACITY:150 A NEUTRAL BUS:100%MOUNTING:RECESSED PANEL: K1B REVISION DATE ASI-T01 02/12/2021 ASI-T04 3/17/2021 1 1 1 2 03/23/21 RTS R P CO A XX SP XX F ABBREVIATIONS AND DESCRIPTIONS ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT FIRE ALARM LEGEND 4" FIRE ALARM FDC PA STANDPIPE DAS FIREMAIN DRY/AUTOMATIC SPRINKLER SP/AS FM SP AUTOMATIC SPRINKLERAS DIRECTION OF VIEW PICTURE DESIGNATION 4" EXIST. NEW DIA, D DIAMETER EL. C LC CI AP AFF CENTER LINE ELEVATION ABOVE FINISHED FLOOR ACCESS PANEL COMMON CAST IRON INVERT ELEVATIONI.E. NC NO NIC VITRIFIED CLAY PIPE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN TYPICAL EXISTING NEW RELOCATED (N) (R) (E) TYP VCP VENT THROUGH ROOFVTR FIRE DEPT. CONNECTION DSP DRY/STANDPIPE CLEAN AGENTCA WATERMISTWM CO D RM HORN FIRE ALARM PULL STATION MINI HORN CARBON MONOXIDE DETECTOR ABORT SWITCH MAGNETIC DOOR HOLDER FIRE SMOKE DAMPER MONITOR MODULE CONTROL MODULE RELEASE MODULE FIRE ALARM ANNUNCIATORDUCT DETECTOR FIRE ALARM CONTROL PANELR/F R/C RATE COMPENSATION F FIXED TEMPERATURE - - - C COMBINATION SMOKE/- I IONIZED- BT BEAM TRANSMITTER- BR BEAM RECIEVER- ASD AIR SAMPLING- HEAT DETECTOR SMOKE DETECTOR PREACTION AUTOMATIC SPRINKLER COMBINATION STANDPIPE/ AUTOMATIC SPRINKLER DELUGE AUTOMATIC SPRINKLER FIRE STANDPIPE DESIGNATIO N FIRE SPRINKLER RISER DESIGNATION LIGHT LINE WEIGHT FOR EQUIPMENT, PIPING, SYMBOLS, TEXT, ETC. INDICATES EXISTING CONDITIONS WITH NEW WORK SHOWN AS DARK DASHED INDICATES EXISTING TO BE REMOVED POINT OF CONNECTION NEW TO EXISTING CARBON MONOXIDE DETECTOR WITH AUDIBLE ALARM xxcd 15cd COMBINATION: RATE OF RISE AND FIXED TERMPERATURE FUTURE(F) P WP xxcd LHD 15cd S S - SUPPLY R - RETURN REMOTE TEST SWITCH ASFP ACCESS CONTROL PANELACP DACT GRAPHIC MAPGMAP ADDRESSABLE OUTPUT MODULEAOM WITH GUARDWG UNLESS NOTED OTHERWISEUNO WEATHER PROOFWP R RATE OF RISE ONLY- P PHOTOELECTRIC- HEAT DETECTOR WATER FLOW SWITCH PRESSURE SWITCH VALVE SUPERVISORY SWITCH LOW AIR PRESSURE ALARM VS WF PS AA HEAT DETECTOR - LINE TYPE (CABLE) STROBE WALL MOUNTED STROBE CEILING MOUNTED HORN/STROBE CEILING MOUNTED HORN/STROBE WALL MOUNTED WP DENOTES WEATHERPROOF SMOKE DETECTOR PHOTOELECTRIC WITH CARBON MONOXIDE DETECTION DIGITAL ALARM COMMUNICATOR TERMINAL AIR SAMPLING CONTROL DETECTION PANEL FAA FACP CM MM CO M FS WORK NOTE SYMBOLFA1 F-? 1 DRAWN ON THIS SHEET DIRECTION OF CUT SECTION DESIGNATION REVISION SYMBOL2 FINISHED FLOOR 80 " ( 6 ' - 8 " ) M I N I M U M 6" ( M I N . ) 96 " ( 8 ' ) M A X I M U M 90 " ( 7 ' - 6 " ) M I N I M U M STROBE LENS MUST BE ENTIRELY BETWEEN 80"- 96" AFF, AND NOT LESS THAN 6" FROM THE CEILING. VISIBLE AND COMBINATION AUDIBLE/VISIBLE DEVICES. AUDIBLE ONLY DEVICES 6" ( M I N . ) IF CEILING HEIGHT ALLOWS, AUDIBLE DEVICE SHALL HAVE ITS TOP NOT LESS THAN 90" AFF, BUT DEVICE SHALL BE AT LEAST 6" BELOW CEILING. TOP OF EQUIPMENT 48 " ( 4 ' - 0 " ) 64 " ( 5 ' - 4 " ) 78 " ( 6 ' - 6 " ) TOP OF PANEL FAA FACP FIRE DEPARTMENT PHONE JACK OPERATIONAL HANDLE OF MANUAL PULL STATION © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 8 : 5 8 A M FA-001 FIRE ALARM GENERAL INFORMATION St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB DENVER OFFICE COLORADO SPRINGS OFFICE 10807 NEW ALLEGIANCE DRIVE, SUITE 400 COLORADO SPRINGS, CO 80921 719.533.1112 5420 WARD ROAD, SUITE 200 ARVADA, CO 80002 303.422.7400 TAMPA OFFICE 12450 ROOSEVELT BLVD N., SUITE 305 ST. PETERSBURG, FL 33716 727.685.0458 MELBOURNE OFFICE 6555 N. WICKHAM ROAD, SUITE 104 MELBOURNE, FL 32940 321.241.4142 PROJECT ENGINEER PROJECT MANAGER CLAIRE MESTLER CMESTLER@BCER.COM 303.405.2866 PAUL MISKOWICZ PMISKOWICZ@BCER.COM 303.405.2902 CONTACT LIST DRAWING LIST - FIRE ALARM FA-001 FIRE ALARM GENERAL INFORMATION FA-002 FIRE ALARM SPECIFICATIONS FA-200 BASEMENT FIRE ALARM PLAN FA-201 LEVEL 1 FIRE ALARM PLAN 17. GRAPHIC MAPS SHALL BE ORIENTED CORRECTLY FOR THEIR INSTALLED LOCATION. 16. PROVIDE LABELS ON THE CEILING GRID, VISIBLE FROM THE FLOOR LEVEL, FOR ALL EQUIPMENT INSTALLED ABOVE THE CEILING, AS APPLICABLE. A "P-TOUCH" OR SIMILAR LABEL IS ACCEPTABLE WITH APPROVAL FROM THE OWNER. 15. THE FIRE ALARM SYSTEM SHALL BE MONITORED BY AN APPROVED, UL LISTED SUPERVISING STATION IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS. 14. ALL EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY DIRECTED OTHERWISE. 13. INSTALL CEILING MOUNTED DEVICES AND APPLIANCES IN THE CENTER OR QUARTER POINT OF CEILING TILES, WHERE APPLICABLE. 12. ADDRESSABLE CONTROL MODULES SHALL BE INSTALLED TO SHUT DOWN FIRE/SMOKE DAMPERS UPON FIRE ALARM SIGNAL. VERIFY LOCATION OF FIRE/SMOKE DAMPERS WITH MECHANICAL CONTRACTOR. 11. DOOR HOLD OPENS SHALL BE CONTROLLED VIA ADDRESSABLE OUTPUT MODULES. PROVIDE AUTOMATIC SMOKE DETECTION IN ACCORDANCE WITH NFPA 72 FOR DOOR HOLDER RELEASE. 10. DUCT SMOKE DETECTOR LOCATIONS ARE SHOWN FOR REFERENCE ONLY. THE CONTRACTOR SHALL FIELD VERIFY ALL DUCT SMOKE DETECTOR LOCATIONS AND PROVIDE THE NECESSARY INTERFACE TO SHUT DOWN THE FAN UNIT AND CLOSE ANY ASSOCIATED DAMPERS. REMOTE TEST SWITCHES AND INDICATORS SHALL BE LOCATED IN AN ACCESSIBLE LOCATION. CONFIRM THE LOCATION WITH THE OWNER PRIOR TO INSTALLATION. 9. FIRE ALARM CONTRACTOR SHALL COORDINATE WITH APPROPRIATE VENDORS FOR SYSTEM INTERFACE PRIOR TO THE COMMENCEMENT OF CONSTRUCTION. COORDINATION SHALL INCLUDE BUT NOT BE LIMITED TO: MECHANICAL HVAC, ELECTRICAL, KITCHEN EQUIPMENT, AUTOMATIC SPRINKLER SYSTEMS AND ELEVATOR EQUIPMENT. 8. CONTRACTOR SHALL PROVIDE SUBMITTALS ON ITEMS LISTED IN EQUIPMENT LIST PROVIDED IN EACH SECTION OF SPECIFICATION TO THE DESIGN ENGINEER FOR REVIEW PRIOR TO THE ORDER, PURCHASE OR INSTALLATION OF THESE SAME ITEMS. 7. CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING AND INSTALLING SLEEVES, INSERTS AND SUPPORTS AS REQUIRED FOR HIS WORK AND/OR CORE DRILL REQUIREMENTS. 6. FURNISH AND INSTALL A FULLY ADDRESSABLE AND ANALOG FIRE DETECTION AND ALARM SYSTEM WITH OCCUPANT NOTIFICATION THROUGHOUT. 5. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN, ARRANGEMENT AND EXTENT OF SYSTEMS. DO NOT SCALE DRAWINGS NOR USE AS SHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS ARE REQUIRED FOR COORDINATION OF ALL WORK, THE CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL COSTS. 4. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAS BEEN SELECTED AS THE BASIS FOR DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATED BY THE CONTRACTOR FOR SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS AND PERFORMANCE. 3. THE MINIMUM REQUIRED NUMBER AND LOCATIONS OF NOTIFICATION APPLIANCES ARE SHOWN. CONTRACTOR SHALL ADD NOTIFICATION AS REQUIRED TO MEET AUDIBILITY REQUIREMENTS OF NFPA 72 AS REQUIRED BASED ON THE PERFORMANCE OF THE SELECTED EQUIPMENT. THE NUMBER AND LOCATION OF NOTIFICATION APPLIANCES SHALL NOT BE REDUCED. 2. THE COMBINED REQUIREMENTS OF THESE DRAWINGS AND SPECIFICATIONS ARE APPLICABLE TO THE DESIGN AND INSTALLATION OF THIS SYSTEM. 1. THE SUCCESSFUL CONTRACTOR WILL BE THE ENGINEER OF RECORD FOR THE DESIGN OF THE FIRE ALARM SYSTEM. IT IS THE CONTRACTOR'S RESPONSIBILITY THAT THE SYSTEM MEETS ALL THE REQUIREMENTS OF NFPA, THE INTERNATIONAL BUILDING AND FIRE CODES AND THE AUTHORITY HAVING JURISDICTION. FIRE ALARM GENERAL NOTES NOT TO SCALE 1 TYPICAL DEVICE MOUNTING HEIGHTS AND LOCAL AMENDMENTS 2013 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2013 NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2020 NATIONAL ELECTRICAL CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL BUILDING CODE ADOPTED/ENFORCED CODES REQUIRED THE STANLEY CARRIAGE HOUSE IS AN EXISTING RESTAURANT IN ESTES PARK, COLORADO. THE BUILDING IS APPROXIMATELY 9,400 SQUARE FEET, MIXED A-1 & A-2 OCCUPANCIES, TYPE V-B CONSTRUCTION AND IS FULLY SPRINKLERED. THIS PHASE CONSISTS OF THE TENANT FINISH OF THE SPACE. CONTRACTOR SHALL MODIFY THE EXISTING FIRE ALARM SYSTEM INSTALLED UNDER THE CORE SHELL PROJECT TO ACCOMODATE THE ARCHITECTURAL MODIFICATIONS ASSOCIATED WITH THE TENANT FINISH. HORN/STROBE OCCUPANT NOTIFICATION SHALL BE PROVIDED THROUGHOUT. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS. PROJECT NARRATIVE REVISION DATE FIRE ALARM SPECIFICATIONS C. REMOTE STATUS AND ALARM INDICATORS: INSTALL NEAR EACH SMOKE DETECTOR AND EACH SPRINKLER WATER-FLOW SWITCH AND VALVE-TAMPER SWITCH THAT IS NOT READILY VISIBLE FROM NORMAL VIEW ING POSITION. D. AUDIBLE ALARM-INDICATING DEVICES: INSTALL NOT LESS THAN 6 INCHES (150 MM) BELOW THE CEILING. INSTALL BELLS AND HORNS ON FLUSH-MOUNTED BACK BOXES WITH THE DEVICE-OPERATING MECHANISM CONCEALED BEHIND A GRILLE. E. VISIBLE ALARM-INDICATING DEVICES: INSTALL ADJACENT TO EACH ALARM BELL OR ALARM HORN AND AT LEAST 6 INCHES (150 MM) BELOW THE CEILING. F. FACP: SURFACE MOUNT WITH TOPS OF CABINETS NOT MORE THAN 72 INCHES (1830 MM) ABOVE THE FINISHED FLOOR. WIRING INSTALLATION A. INSTALL WIRING IN ACCORDANCE WITH THE NEC. B. FIRE ALARM CIRCUITS AND EQUIPMENT CONTROL WIRING ASSOCIATED WITH THE FIRE ALARM SYSTEM SHALL BE INSTALLED IN A DEDICATED METAL RACEWAY SYSTEM. THIS SYSTEM SHALL NOT BE USED FOR ANY OTHER WIRE OR CABLE. C. SIGNALING LINE CIRCUITS: POWER-LIMITED FIRE ALARM CABLES MAY BE INSTALLED IN THE SAME CABLE OR RACEWAY AS SIGNALING LINE CIRCUITS. D. EXPOSED PATHWAYS SHALL BE INSTALLED IN CONDUIT. E. OPEN CABLING SHALL BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER AND SHALL BE RUN PERPENDICULAR OR PARALLEL TO BUILDING STRUCTURAL MEMBERS. DIAGONAL ROUTING OF CABLE SHALL NOT BE CONSIDERED ACCEPTABLE AND SHALL CAUSE TO BE REMOVED AND REINSTALLED. F. OPEN CABLING SHALL BE ROUTED AWAY FROM OTHER BUILDING CABLING AND EQUIPMENT AND SHALL BE ROUTED TO AND FROM THE DEVICE IN A VERTICAL OR HORIZONTAL MANNER. MAINTAIN CABLING AT THE SAME LEVEL WHERE POSSIBLE, CABLING THAT IS NOT DROPPED VERTICALLY TO THE DEVICE OR ROUTED HORIZONTALLY STRAIGHT TO THE DEVICE SHALL NOT BE CONSIDERED ACCEPTABLE. CABLING THAT IS ROUTED THROUGH, OVER, UNDER OR AROUND OTHER EQUIPMENT, WHEN A STRAIGHT HORIZONTAL OR VERTICAL PATH IS AVAILABLE SHALL NOT BE CONSIDERED ACCEPTABLE AND SHALL CAUSE THE CABLE TO BE REMOVED AND BE REINSTALLED. G. OPEN CABLING SHALL BE SUPPORTED AT A MINIMUM OF EVERY 4 TO 6 FEET TO BUILDING STRUCTURAL MEMBERS UTILIZING METAL BRIDLE RINGS. CABLING THAT IS SECURED TO SPRINKLER PIPING, HVAC DUCTWORK, ELECTRICAL CONDUIT OR OTHER NON-STRUCTURAL BUILDING MEMBER SHALL NOT BE ACCEPTABLE AND SHALL CAUSE THE CABLE TO BE RE-INSTALLED AND RE-SUPPORTED IN A PROPER MANNER. GROUNDING A. GROUND THE FACP AND ASSOCIATED CIRCUITS; COMPLY WITH IEEE 1100. INSTALL A GROUND WIRE FROM MAIN SERVICE GROUND TO THE FACP. FIELD QUALITY CONTROL A. MANUFACTURER'S FIELD SERVICE: ENGAGE A FACTORY-AUTHORIZED SERVICE REPRESENTATIVE TO INSPECT, TEST, AND ADJUST FIELD-ASSEMBLED COMPONENTS AND EQUIPMENT INSTALLATION, INCLUDING CONNECTIONS, AND TO ASSIST IN FIELD TESTING. REPORT RESULTS IN WRITING. B. TESTS SHALL BE WITNESSED BY AUTHORITIES HAVING JURISDICTION. C. FIRE ALARM SYSTEM WILL BE CONSIDERED DEFECTIVE IF IT DOES NOT PASS TESTS AND INSPECTIONS. D. COSTS FOR REINSPECTIONS FOR INCOMPLETE NONCOMPLIANT WILL BE CHARGED TO THE CONTRACTOR. SYSTEM. 9. ANNUNCIATE LOCAL AUDIBLE ALARM SIGNAL COMPLIANT WITH ANSI TEMPORAL FOUR. 10. TEST BUTTON SIMULATES AN ALARM CONDITION. NOTIFICATION APPLIANCES A. VISIBLE ALARM DEVICES: XENON STROBE LIGHTS LISTED UNDER UL 1971, WITH CLEAR OR NOMINAL WHITE POLYCARBONATE LENS MOUNTED ON AN ALUMINUM FACEPLATE. THE WORD "FIRE" IS ENGRAVED IN MINIMUM 1-INCH- (25-MM-) HIGH LETTERS ON THE LENS. 1. RATED LIGHT OUTPUT: AS DENOTED ON PLANS AND REQUIRED BY NFPA 72. a. 15/30/75/95/110 CD, SELECTABLE IN THE FIELD. b. 135/150/185 CD, SELECTABLE IN THE FIELD. 2. STROBE LEADS: FACTORY CONNECTED TO SCREW TERMINALS. 3. MOUNTING: WALL MOUNTED UNLESS OTHERWISE INDICATED. 4. FOR UNITS WITH GUARDS TO PREVENT PHYSICAL DAMAGE, LIGHT OUTPUT RATINGS SHALL BE DETERMINED WITH GUARDS IN PLACE. 5. FLASHING SHALL BE IN A TEMPORAL PATTERN, SYNCHRONIZED WITH OTHER UNITS. 6. STROBE LEADS: FACTORY CONNECTED TO SCREW TERMINALS. 7. MOUNTING FACEPLATE: FACTORY FINISHED, WHITE. SPRINKLER SYSTEM REMOTE INDICATORS A. REMOTE STATUS AND ALARM INDICATOR AND TEST STATIONS, WITH LED INDICATING LIGHTS. LIGHT IS CONNECTED TO FLASH WHEN THE ASSOCIATED DEVICE IS IN AN ALARM OR TROUBLE MODE. ELEVATORS A. ELEVATOR SHUT DOWN: HEAT DETECTOR OPERATION IN THE ELEVATOR MACHINE ROOM OR HOISTWAY SHUTS DOWN ELEVATOR POWER BY OPERATING A SHUNT TRIP IN A CIRCUIT BREAKER FEEDING THE ELEVATOR. HEAT DETECTOR ACTIVATION OPERATES BUILDING NOTIFICATION APPLIANCES AND ANNUNCIATOR. 1. HEAT DETECTORS SHALL BE LOCATED WITHIN TWO FEET OF EACH SPRINKLER IN THE SPACE AND SHALL HAVE A LOWER TEMPERATURE AND FASTER RTI AS COMPARED TO THE SPRINKLER. B. ELEVATOR RECALL: SMOKE DETECTORS AT THE FOLLOW ING LOCATIONS SHALL INITIATE AUTOMATIC ELEVATOR RECALL. 1. ELEVATOR RECALL SHALL BE INITIATED ONLY BY ONE OF THE FOLLOWING ALARM INITIATING DEVICES: a. ELEVATOR LOBBY DETECTORS. b. SMOKE DETECTOR IN ELEVATOR MACHINE ROOM. c. SMOKE DETECTORS IN ELEVATOR HOISTWAY. 2. ELEVATOR CONTROLLER SHALL BE PROGRAMMED TO MOVE THE CARS TO THE ALTERNATE RECALL FLOOR IF ELEVATOR LOBBY DETECTORS LOCATED ON THE DESIGNATED RECALL FLOORS ARE ACTIVATED. 3. WATERFLOW ALARM CONNECTED TO SPRINKLER IN AN ELEVATOR SHAFT AND ELEVATOR MACHINE ROOM SHALL SHUT DOWN ELEVATORS ASSOCIATED WITH THE LOCATION WITHOUT TIME DELAY. a. WATERFLOW SWITCH ASSOCIATED WITH THE SPRINKLER IN THE ELEVATOR PIT MAY HAVE A DELAY TO ALLOW ELEVATORS TO MOVE TO THE DESIGNATED FLOOR. WIRE AND CABLE A. WIRE AND CABLE FOR FIRE ALARM SYSTEMS SHALL BE UL LISTED AND LABELED AS COMPLYING WITH NFPA 70, ARTICLE 760. B. SIGNALING LINE CIRCUITS: TWISTED, SHIELDED PAIR, SIZE AS RECOMMENDED BY SYSTEM MANUFACTURER. C. NON-POWER-LIMITED CIRCUITS: SOLID-COPPER CONDUCTORS WITH 600-V RATED, 75 DEG C, COLOR-CODED INSULATION, SIZE AS RECOMMENDED BY THE MANUFACTURER. EXECUTION A. SMOKE DETECTOR SPACING: 1. SPACING OF SMOKE DETECTORS SHALL BE DETERMINED BASED ON REQUIREMENTS IN NFPA 72. B. HVAC: LOCATE DETECTORS NOT CLOSER THAN 3 FEET (1 M) FROM AIR-SUPPLY DIFFUSER OR RETURN-AIR OPENING. SYSTEM SMOKE DETECTORS A. GENERAL DESCRIPTION: 1. UL 268 LISTED, OPERATING AT 24-V DC, NOMINAL. 2. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE DETECTOR STATUS (NORMAL, ALARM, OR TROUBLE) TO THE FACP. 3. SELF-RESTORING: DETECTORS DO NOT REQUIRE RESETTING OR READJUSTMENT AFTER ACTUATION TO RESTORE THEM TO NORMAL OPERATION. 4. INTEGRAL VISUAL-INDICATING LIGHT: LED TYPE. INDICATING DETECTOR HAS OPERATED AND POWER-ON STATUS. B. PHOTOELECTRIC SMOKE DETECTORS: 1. SENSOR: LED OR INFRARED LIGHT SOURCE WITH MATCHING SILICON-CELL RECEIVER. 2. DETECTOR SENSITIVITY: BETWEEN 2.5 AND 3.5 PERCENT/FOOT (0.008 AND 0.011 PERCENT/MM) SMOKE OBSCURATION WHEN TESTED ACCORDING TO UL 268A. DUCT SMOKE DETECTORS: A. GENERAL DESCRIPTION: 1. UL 268A LISTED, OPERATING AT 24-V DC, NOMINAL. 2. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE DETECTOR STATUS (NORMAL, ALARM, OR TROUBLE) TO THE FACP. 3. SELF-RESTORING: DETECTORS SHALL NOT REQUIRE RESETTING OR READJUSTMENT AFTER ACTUATION TO RESTORE THEM TO NORMAL OPERATION. 4. INTEGRAL VISUAL-INDICATING LIGHT: LED TYPE. INDICATING DETECTOR HAS OPERATED AND POWER-ON STATUS. PROVIDE REMOTE STATUS AND ALARM INDICATOR AND TEST STATION WHERE INDICATED. 5. REMOTE CONTROL: UNLESS OTHERWISE INDICATED, DETECTORS SHALL BE ANALOG-ADDRESSABLE TYPE, INDIVIDUALLY MONITORED AT THE FACP FOR CALIBRATION, SENSITIVITY, AND ALARM CONDITION, AND INDIVIDUALLY ADJUSTABLE FOR SENSITIVITY FROM THE FACP. 6. EACH SENSOR SHALL HAVE MULTIPLE LEVELS OF DETECTION SENSITIVITY. 7. SAMPLING TUBES: DESIGN AND DIMENSIONS AS RECOMMENDED BY MANUFACTURER FOR THE SPECIFIC DUCT SIZE, AIR VELOCITY, AND INSTALLATION CONDITIONS WHERE APPLIED. 8. RELAY FAN SHUTDOWN: RATED TO INTERRUPT FAN MOTOR-CONTROL CIRCUIT. HEAT DETECTORS A. GENERAL DESCRIPTION: 1. UL 521 LISTED. 2. COMBINATION TYPE: ACTUATED BY EITHER A FIXED TEMPERATURE OF 135 DEG F (57 DEG C) OR RATE-OF-RISE OF TEMPERATURE THAT EXCEEDS 15 DEG F (8 DEG C) PER MINUTE, UNLESS OTHERWISE INDICATED. 3. HEAT DETECTOR, FIXED-TEMPERATURE TYPE: ACTUATED BY TEMPERATURE THAT EXCEEDS A FIXED TEMPERATURE OF 190 DEG F (88 DEG C). 4. MOUNTING: TWIST-LOCK BASE INTERCHANGEABLE WITH SMOKE DETECTOR BASES. 5. INTEGRAL ADDRESSABLE MODULE: ARRANGED TO COMMUNICATE DETECTOR STATUS (NORMAL, ALARM, OR TROUBLE) TO THE FACP. CARBON MONOXIDE DETECTORS 1.2 CARBON MONOXIDE DETECTORS A. GENERAL: 1. CARBON MONOXIDE DETECTOR LISTED FOR CONNECTION TO FIRE ALARM SYSTEM. 2. MOUNTING: ADAPTER PLATE FOR OUTLET BOX MOUNTING. 3. TESTABLE BY INTRODUCING TEST CARBON MONOXIDE INTO THE SENSING CELL. 4. DETECTOR SHALL PROVIDE ALARM CONTACTS AND TROUBLE CONTACTS. 5. DETECTOR SHALL SEND TROUBLE ALARM WHEN NEARING END-OF-LIFE, POWER SUPPLY PROBLEMS, OR INTERNAL FAULTS. 6. COMPLY WITH UL 2075. 7. LOCATE, MOUNT, AND WIRE ACCORDING TO MANUFACTURER'S WRITTEN INSTRUCTIONS. 8. PROVIDE MEANS FOR ADDRESSABLE CONNECTION TO FIRE ALARM SECTION 28 46 21 - FIRE DETECTION AND ALARM GENERAL REQUIREMENTS A. SEE ARCHITECTURAL SPECIFICATION AND DRAWINGS FOR GENERAL CONDITIONS. B. PROVIDE ALL ITEMS REQUIRED FOR COMPLETE AND SUCCESSFUL OPERATION OF THE FIRE ALARM SYSTEM. C. DEMONSTRATE THE OPERATION OF ALL SYSTEMS FOR THE OWNER AT A TIME AS DIRECTED BY THE OWNER. D. THE SUCCESSFUL CONTRACTOR WILL BE THE ENGINEER OF RECORD FOR THE DESIGN OF THE SYSTEM. THE DESIGN AND ENGINEERING OF THE FIRE ALARM SYSTEM SHALL BE BY THE FIRE ALARM CONTRACTOR SIGNED BY A NICET IV OR PE REGISTERED IN THE STATE OF COLORADO. IT IS THE CONTRACTOR'S RESPONSIBILITY THAT THE SYSTEM MEETS ALL THE REQUIREMENTS OF APPLICABLE NFPA AND THE LOCAL AUTHORITY HAVING JURISDICTION. NO WORK SHALL BE INSTALLED WITHOUT APPROVED DRAWINGS. 1. PRODUCT DATA AND SHOP DRAWING SUBMITTALS SHALL BE SUBMITTED IN CONJUNCTION WITH ONE ANOTHER. SUBMITTALS THAT ARE RECEIVED INDIVIDUALLY WILL BE RETURNED WITHOUT REVIEW UNTIL BOTH ARE RECEIVED. 2. SHOP DRAWINGS SHALL BE SIGNED BY LEVEL IV NICET TECHNICIAN OR SIGNED AND STAMPED BY A PROFESSIONAL ENGINEER REGISTERED IN THE STATE OF COLORADO AT THE TIME OF SUBMITTAL. E. REPLACE ANY WORK OR MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FOR NORMAL WEAR, WITHIN ONE (1) YEAR AFTER CERTIFICATE OF COMPLETION IS SECURED.SYSTEM DESCRIPTION F. INSTALLING PERSONNEL SHALL BE TRAINED AND CERTIFIED BY MANUFACTURER FOR INSTALLATION OF UNITS REQUIRED FOR THIS PROJECT AND SHALL BE CERTIFIED BY NICET AS FIRE ALARM LEVEL II. WORK OF THIS SECTION SHALL BE PERFORMED BY A UL LISTED COMPANY. G. RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTAIN A MARK-UP SET OF DRAWINGS WHICH INDICATE VARIATIONS IN THE ACTUAL INSTALLATION FROM THE ORIGINAL DESIGN. TURN OVER DRAWINGS TO OWNER/ARCHITECT UPON PROJECT COMPLETION. H. ALL MATERIALS SHALL BE NEW AND UL LISTED. FIRE ALARM CONTROL PANEL A. MODULAR, POWER-LIMITED DESIGN WITH ELECTRONIC MODULES, UL 864 LISTED. B. ADDRESSABLE INITIATION DEVICES THAT COMMUNICATE DEVICE IDENTITY AND STATUS. CIRCUITS A. SIGNALING LINE & NOTIFICATION APPLIANCE CIRCUITS: NFPA 72, CLASS B. B. TRANSMISSION TO REMOTE ALARM RECEIVING STATION: AUTOMATICALLY TRANSMIT ALARM, TROUBLE, AND SUPERVISORY SIGNALS TO A REMOTE ALARM STATION THROUGH A DIGITAL ALARM COMMUNICATOR TRANSMITTER AND TELEPHONE LINES. C. PRIMARY POWER: 24-V DC OBTAINED FROM 120-V AC SERVICE AND A POWER-SUPPLY MODULE. INITIATING DEVICES, NOTIFICATION APPLIANCES, SIGNALING LINES, TROUBLE SIGNAL, SUPERVISORY AND DIGITAL ALARM COMMUNICATOR TRANSMITTER SHALL BE POWERED BY THE 24-V DC SOURCE. D. SECONDARY POWER: 24-V DC SUPPLY SYSTEM WITH BATTERIES AND AUTOMATIC BATTERY CHARGER AND AN AUTOMATIC TRANSFER SWITCH. E. INSTALL SURGE PROTECTION ON NORMAL AC POWER FOR THE FACP AND ITS ACCESSORIES. INSTALL SURGE PROTECTORS RECOMMENDED BY FACP MANUFACTURER. INSTALL ON ALL SYSTEM WIRING EXTERNAL TO THE BUILDING HOUSING THE FACP. MANUAL FIRE ALARM BOXES A. GENERAL DESCRIPTION: 1. UL 38 LISTED; FINISHED IN RED WITH MOLDED, RAISED-LETTER OPERATING INSTRUCTIONS IN CONTRASTING COLOR. 2. STATION SHALL SHOW VISIBLE INDICATION OF OPERATION. 3. MOUNTED ON RECESSED OUTLET BOX; IF INDICATED AS SURFACE MOUNTED, PROVIDE MANUFACTURER'S SURFACE BACK BOX. 4. SINGLE ACTION MECHANISM, PULL-LEVER TYPE WITH INTEGRAL ADDRESSABLE MODULE, ARRANGED TO COMMUNICATE MANUAL-STATION STATUS (NORMAL, ALARM, OR TROUBLE) TO THE FACP. 5. STATION RESET - KEY OR WRENCH OPERATED SWITCH. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 8 : 5 9 A M FA-002 FIRE ALARM SPECIFICATIONS St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB REVISION DATE F.E.C. F. E . C . F.E. MM CM WFVS CO 4 3 2 1 AC DE 75cd 15cd 30cd 30cd 30cd 15cd B DOAS-1 75cd 75cd 30cd AREA OF WORK AREA OF WORKFA1 FA1 LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 ELEV. B10 COOLER 005 FREEZER 006 OFFICE 001 WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A THEATER B02 PLATFORM B02B LOBBY B01 TI STORAGE 010 AREA OF WORKFA1 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 9 : 0 3 A M FA-200 BASEMENT FIRE ALARM PLAN St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB 3. ALL EQUIPMENT SHALL BE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM AND SHALL BE UL LISTED OR FM APPROVED. 2. DRAWINGS ARE DIAGRAMMATIC AND MAY NOT NECESSARILY REPRESENT ALL OF THE COMPONENTS FOR A FULLY FUNCTIONAL SYSTEM. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE A FULLY FUNCTIONAL AND CODE COMPLIANT FIRE ALARM SYSTEM. 1. COORDINATE ALL DEVICE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DOCUMENTS. GENERAL NOTES N 0 4'4' 2' 1/4" = 1'-0" 1 BASEMENT FIRE ALARM PLAN WORK NOTES FA1 MODIFY EXISTING FIRE ALARM SYSTEM IN THIS AREA TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. REVISION DATE FA C P GM A P P MM MM P CM FA C P GM A P 4 3 2 1 AC DE FA7 95cd 95cd 30cd 15cd 75cd WP B 75cd AREA OF WORK 30cd FA4 75cd 75cd FA4 FA5 15cd 15cd 15cd 30cd 30cd PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 100 LIQ. STORAGE 106 PRIVATE PATIO 114 PATIO 117 DINING 115 RETAIL 103 BAR 107 CIRCULATION 009 BENCH SEATING 119 BOOTHS 116 BOOTHS 118 DINING 102 CIRCULATION 116 RTU-1 FA6 FA1 FA3 FA3 FA2 30cd 1 1 1 © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 2/ 1 1 / 2 0 2 1 3 : 1 3 : 5 3 P M FA-201 LEVEL 1 FIRE ALARM PLAN St a n l e y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB 3. ALL EQUIPMENT SHALL BE COMPATIBLE WITH THE EXISTING FIRE ALARM SYSTEM AND SHALL BE UL LISTED OR FM APPROVED. 2. DRAWINGS ARE DIAGRAMMATIC AND MAY NOT NECESSARILY REPRESENT ALL OF THE COMPONENTS FOR A FULLY FUNCTIONAL SYSTEM. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE A FULLY FUNCTIONAL AND CODE COMPLIANT FIRE ALARM SYSTEM. 1. COORDINATE ALL DEVICE AND EQUIPMENT LOCATIONS WITH ARCHITECTURAL, MECHANICAL, PLUMBING AND ELECTRICAL DOCUMENTS. GENERAL NOTES N 0 4'4' 2' 1/4" = 1'-0" 1 LEVEL 1 FIRE ALARM PLAN WORK NOTES FA1 MODIFY EXISTING FIRE ALARM SYSTEM IN THIS AREA TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. FA2 RELOCATE EXISTING FIRE ALARM CONTROL PANEL, SMOKE DETECTOR AND GRAPHIC MAP TO THIS LOCATION. UPDATE EXISTING GRAPHIC MAP TO REFLECT ARCHITECTURAL AND FIRE ALARM SYSTEM MODIFICATIONS. LOCATION OF FIRE ALARM CONTROL PANEL SHALL BE APPROVED BY THE AHJ PRIOR TO INSTALLATION. FA3 EXISTING MONITOR MODULES FOR INTERFACE WITH KITCHEN SUPPRESSION SYSTEM. FA4 REMOVE EXISTING HORN/STROBE. REMOVED DEVICES SHALL BE REINSTALLED WHERE APPLICABLE. UNUSED DEVICES SHALL BE RETURNED TO OWNER. FA5 RELOCATE EXISTING MANUAL PULL STATION ADJACENT TO THE DOOR BY NEW FIRE ALARM CONTROL PANEL LOCATION IN CIRCULATION 009. FA6 PROVIDE NEW DUCT SMOKE DETECTION, CONTROL MODULE AND REMOTE TEST SWITCH. COORDINATE LOCATION AND QUANTITY OF DETECTORS WITH MECHANICAL DUCTWORK AND MECHANICAL CONTRACTOR. COORDINATE REMOTE TEST SWITCH LOCATION WITH OWNER PRIOR TO INSTALLATION. FA7 RELOCATE EXISTING FIRE ALARM CONTROL PANEL, SMOKE DETECTOR AND GRAPHIC MAP. REFERENCE WORK NOTE FA2 FOR NEW LOCATION. REVISION DATE ASI-T01 2/12/21 1 1 1 WF PS AA VS A RP XX SP XX F ABBREVIATIONS AND DESCRIPTIONS ALL SYMBOLS IN LEGEND MAY NOT NECESSARILY BE USED ON THIS PROJECT FIRE SPRINKLER LEGEND 4" FIRE PROTECTION VALVES AND FITTINGS FIRE SPRINKLERS FDC PA STANDPIPE DAS FIREMAIN DRY/AUTOMATIC SPRINKLER SP/AS FM SP AUTOMATIC SPRINKLERAS TEE DOWN ELBOW DOWN TEE UP BRANCH-BOTTOM CONNECTION BRANCH-TOP CONNECTION RISE OR DROP ELBOW UP UNION PIPE CAP OR PLUG PIPE GUIDE PIPE ANCHOR STRAINER FLEXIBLE CONNECTION STRAINER W/BLOWOFF VALVE EXPANSION JOINT BACKFLOW PREVENTER VENTURI PRESSURE REDUCING VALVE GLOBE VALVE CHECK VALVE BALL VALVE SOLENOID VALVE MANUAL AIR VENT DIRECTION OF VIEW PICTURE DESIGNATION 4" EXIST. NEW DIA, D DIAMETER EL. C LC CI AP AFF CENTER LINE ELEVATION ABOVE FINISHED FLOOR ACCESS PANEL COMMON CAST IRON INVERT ELEVATIONI.E. NC NO NIC VITRIFIED CLAY PIPE NORMALLY CLOSED NOT IN CONTRACT NORMALLY OPEN TYPICAL EXISTING NEW RELOCATED (N) (R) (E) TYP VCP VENT THROUGH ROOFVTR FIRE DEPARTMENT CONNECTION DSP DRY/STANDPIPE CLEAN AGENTCA WATERMISTWM D PREACTION AUTOMATIC SPRINKLER COMBINATION STANDPIPE/ AUTOMATIC SPRINKLER DELUGE AUTOMATIC SPRINKLER FIRE STANDPIPE DESIGNATION FIRE SPRINKLER RISER DESIGNATION LIGHT LINE WEIGHT FOR EQUIPMENT, PIPING, SYMBOLS, TEXT, ETC. INDICATES EXISTING CONDITIONS WITH NEW WORK SHOWN AS DARK DASHED INDICATES EXISTING TO BE REMOVED POINT OF CONNECTION NEW TO EXISTING TEMPERATURE/PRESSURE RELIEF VALVE PRESSURE GAUGE WITH GAUGE COCK HOSE END BALL VALVE WITH VACUUM BREAKER FIRE HOSE VALVE CABINET (SURFACE MOUNTED) BACKFLOW PREVENTER (REDUCED PRESSURE) FIRE HOSE VALVE CABINET (RECESSED) BUTTERFLY VALVE W/TAMPER SWITCHFREE STANDING FIRE DEPARTMENT CONNECTION MAIN DRAIN ASSEMBLY FIRE DEPARTMENT CONNECTION WATER FLOW SWITCH ANGLE VALVE DRY PIPE VALVE PRESSURE SWITCH PREACTION VALVE POST INDICATOR VALVE FIRE HOSE RACK FUTURE(F) VALVE SUPERVISORY SWITCH FIRE HYDRANT WITH GUARDWG UNLESS NOTED OTHERWISEUNO WEATHER PROOFWP DRY UPRIGHT SPRINKLER UPRIGHT SPRINKLER DRY PENDENT SPRINKLER PENDENT SPRINKLER SPRINKLER WITH GUARD DRY SPRINKLER WITH GUARD HORIZONTAL SIDEWALL SPRINKLER OUTSIDE SPRINKLER DRY OUTSIDE SPRINKLER WATER SPRAY NOZZLE - DELUGE WATER WASH WINDOW SPRINKLER DRY SIDEWALL SPRINKLER C CONCEALED- R RECESSED- FIRE HOSE VALVE LIGHT HAZARD 0.10 GPM/1500 SQ. FT. SPRINKLER DENSITY ORDINARY HAZARD G1 0.15 GPM/1500 SQ. FT. NOTE: "EC" DENOTES EXTENDED COVERAGE SPRINKLER DELUGE VALVE LOW AIR SUPERVISORY SWITCH PRESSURE ALARM GATE VALVE IN VERTICAL WITH TAMPER SWITCH NON-INDICATING VALVE (NON-RISING STEM) T T T T T TT WORK NOTE SYMBOLFP1 REVISION SYMBOL2 F-? 1 DRAWN ON THIS SHEET DIRECTION OF CUT SECTION DESIGNATION © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 9 : 0 6 A M FP-001 FIRE PROTECTION GENERAL INFORMATION St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB THE STANLEY CARRIAGE HOUSE IS AN EXISTING RESTAURANT IN ESTES PARK, COLORADO. THE BUILDING IS APPROXIMATELY 9,400 SQUARE FEET, MIXED A-1 & A-2 OCCUPANCIES, TYPE V-B CONSTRUCTION AND IS FULLY SPRINKLERED. THIS PHASE CONSISTS OF THE TENANT FINISH OF THE SPACE. CONTRACTOR SHALL MODIFY THE EXISTING SPRINKLER SYSTEM INSTALLED UNDER THE CORE SHELL PROJECT TO ACCOMMODATE THE ARCHITECTURAL MODIFICATIONS ASSOCIATED WITH THE TENANT FINISH. THE SPRINKLER SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE CODES AND STANDARDS. PROJECT NARRATIVE DENVER OFFICE COLORADO SPRINGS OFFICE 10807 NEW ALLEGIANCE DRIVE, SUITE 400 COLORADO SPRINGS, CO 80921 719.533.1112 5420 WARD ROAD, SUITE 200 ARVADA, CO 80002 303.422.7400 TAMPA OFFICE 12450 ROOSEVELT BLVD N., SUITE 305 ST. PETERSBURG, FL 33716 727.685.0458 MELBOURNE OFFICE 6555 N. WICKHAM ROAD, SUITE 104 MELBOURNE, FL 32940 321.241.4142 PROJECT ENGINEER PROJECT MANAGER CLAIRE MESTLER CMESTLER@BCER.COM 303.405.2866 PAUL MISKOWICZ PMISKOWICZ@BCER.COM 303.405.2902 CONTACT LIST DRAWING LIST - FIRE PROTECTION FP-001 FIRE PROTECTION GENERAL INFORMATION FP-002 FIRE PROTECTION SPECIFICATIONS FP-200 BASEMENT FIRE PROTECTION PLAN FP-201 LEVEL 1 FIRE PROTECTION PLAN B. MECHANICAL AND STORAGE AREAS, KITCHEN, RETAIL SPACES. 2. ORDINARY HAZARD OCCUPANCIES - GROUP 1 - 0.15 GPM/S.F. OVER A REMOTE AREA OF 1500 SQUARE FEET. A. OFFICES, SEATING AREAS, RESTROOMS. 1. LIGHT HAZARD OCCUPANCIES - 0.10 GPM/S.F. OVER A REMOTE AREA OF 1500 SQUARE FEET. COVERAGE REQUIREMENTS MINIMUM FIRE SPRINKLER 17. ALL SPRINKLER HEADS INSTALLED SHALL BE NEW; EXISTING SPRINKLER HEADS SHALL NOT BE REMOVED AND REINSTALLED IN ANOTHER LOCATION. FOR REMODEL AREAS, NEW SPRINKLER HEADS INSTALLED SHALL MATCH EXISTING SPRINKLERS FOR FINISHES, RESPONSE TYPE, AND TEMPERATURE RATING UNLESS OTHERWISE NOTED. INSTALL ALL NEW SPRINKLER HEADS IN REMODEL AREAS IF MATCHING SPRINKLER HEADS CANNOT BE FOUND. ALL SPRINKLER FINISHES SHALL BE APPROVED BY THE OWNER AND ARCHITECT PRIOR TO INSTALLATION. 16. FIRE SPRINKLER SHOP DRAWINGS SHALL PROVIDE DIMENSIONALLY LOCATED PIPE MAINS AND BRANCH LINES TO FACILITIES STRUCTURE SUCH AS COLUMN LINES, WALLS, RECOGNIZED BENCH MARKS, ETC. 15. FIRE SPRINKLER SHOP DRAWINGS SHALL LOCATE AND DESCRIBE GUIDES, ANCHORS AND HANGERS FOR ALL PIPING. FIRE SPRINKLER SHOP DRAWINGS TO PROVIDE PROTECTION FOR UNDERNEATH DUCTWORK AND OTHER OBSTRUCTIONS AS NEEDED. 14. PROVIDE TAMPER VALVES, WATERFLOW SWITCHES, AND PRESSURE GAUGES FOR EACH FIRE SPRINKLER ZONE. COORDINATE CONNECTION OF SUPERVISORY SWITCHES, WATERFLOW SWITCHES AND ASSOCIATED WIRING WITH FIRE ALARM CONTRACTOR. 13. SPRINKLER CONTRACTOR TO COORDINATE SPRINKLER HEAD FINISHES WITH ARCHITECT AND OWNER PRIOR TO THE PURCHASE AND INSTALLATION OF SPRINKLERS. 12. INSTALL SPRINKLERS IN THE CENTER OR QUARTER POINT OF CEILING TILES, WHERE APPLICABLE. 11. SPRINKLERS SHALL BE SPACED PER NFPA 13 REGARDING OBSTRUCTIONS, BEAM POCKETS, HVAC DUCTWORK, PENETRATIONS AND ANY OTHER CLEARANCE RELATED ITEMS. CONTRACTOR SHALL VERIFY ALL SPACING AND OBSTRUCTIONS PRIOR TO INSTALLATION. 10. THE FIRE SPRINKLER CONTRACTOR/ENGINEER OF RECORD SHALL SECURE THE SITE FLOW TEST INFORMATION AND DOCUMENTATION FROM THE LOCAL WATER DEPARTMENT PRIOR TO THE DESIGN OF THE FIRE SPRINKLER SYSTEM. THE WATER FLOW TEST SHALL BE NO OLDER THAN ONE YEAR FROM THE DATE OF SYSTEM INSTALLATION. 9. FIRE SUPPRESSION SYSTEM TO BE HYDRAULICALLY CALCULATED BASED ON NFPA 13, WITH A SAFETY FACTOR OF 10% UP TO 10 PSI OF THE WATER SUPPLY CURVE. 8. PROVIDE ALL FITTINGS, RISER NIPPLES, ARM-OVERS, HANGERS, ETC. TO MAINTAIN CONFORMANCE WITH APPLICABLE STANDARDS AND TO POSITION THE SPRINKLER HEADS IN THE PROPER LOCATIONS. 7. SEAL ALL PENETRATIONS THROUGH FIRE-RESISTANCE RATED WALLS, CEILINGS AND FLOORS WITH UL LISTED ASSEMBLIES AS REQUIRED TO MAINTAIN THE INTEGRITY OF THE FIRE-RESISTANCE RATING. 6. FIRE SPRINKLER CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL NEW EQUIPMENT AND PIPING WITH ALL OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND SYSTEM INSTALLATION, SO AS NOT TO INTERFERE WITH THE ROUTING OF NEW DUCTWORK, PLUMBING, PIPING, ETC. CONTRACTOR SHALL REVIEW ALL PROJECT DOCUMENTS INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING: ARCHITECTURAL, ELECTRICAL, MECHANICAL, STRUCTURAL, SITE/CIVIL DOCUMENTS FOR THE COORDINATION OF THE SPRINKLER SYSTEM DESIGN AND INSTALLATION 5. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL DESIGN, ARRANGEMENT AND EXTENT OF THE SYSTEMS. DO NOT SCALE DRAWINGS NOR USE AS SHOP DRAWINGS. WHERE ALTERNATE ROUTING, OFFSETS AND TRANSITIONS ARE REQUIRED FOR THE COORDINATION OF ALL WORK, THE CONTRACTOR SHALL MAKE CHANGES WITHOUT ADDITIONAL COSTS. 4. THE EQUIPMENT SPECIFIED ON THE DRAWINGS HAS BEEN SELECTED AS THE BASIS FOR DESIGN. THE USE OF REVIEWED OR SPECIFIED EQUALS SHALL BE COORDINATED BY THE CONTRACTOR FOR SPACE REQUIREMENTS, EQUIPMENT DIMENSIONS AND PERFORMANCE. 3. FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES NECESSARY FOR THE INSTALLATION OF A COMPLETE AND PROPERLY FUNCTIONING FIRE SPRINKLER SYSTEM. 2. THE COMBINED REQUIREMENTS OF THESE DRAWINGS AND SPECIFICATIONS ARE APPLICABLE TO THE DESIGN AND INSTALLATION OF THIS SYSTEM. 1. THE SUCCESSFUL CONTRACTOR WILL BE THE ENGINEER OF RECORD FOR THE DESIGN AND INSTALLATION OF THE FIRE SPRINKLER SYSTEM. IT IS THE CONTRACTOR'S RESPONSIBILITY THAT THE SYSTEM MEET ALL THE REQUIREMENTS OF NFPA, THE INTERNATIONAL BUILDING AND FIRE CODES, AND THE AUTHORITY HAVING JURISDICTION. FIRE SPRINKLER GENERAL NOTES AND LOCAL AMENDMENTS 2013 NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE 2013 NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2020 NATIONAL ELECTRICAL CODE 2015 INTERNATIONAL FIRE CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL BUILDING CODE ADOPTED/ENFORCED CODES REQUIRED REVISION DATE FIRE PROTECTION SPECIFICATIONS FIELD QUALITY CONTROL A. THE FIRE SPRINKLER SYSTEM SHALL NOT BE CONNECTED TO UNDERGROUND PIPING UNTIL THE FIRE SERVICE MAIN IS TESTED AND APPROVED. B. THE FIRE PROTECTION CONTRACTOR SHALL CONDUCT AND BEAR THE COSTS OF ALL NECESSARY TESTS OF THE FIRE PROTECTION WORK, FURNISH ALL LABOR, POWER AND EQUIPMENT. ALL PIPING SHALL BE TESTED WITH WATER AS REQUIRED, THE TESTS WITNESSED BY THE AUTHORITY HAVING JURISDICTION. C. THE FIRE PROTECTION PIPING SHALL BE TESTED UNDER A HYDROSTATIC PRESSURE OF NOT LESS THAN 200 PSIG, FOR A DURATION OF NOT LESS THAN TWO (2) HOURS. D. REPLACE PIPING SYSTEM COMPONENTS WHICH DO NOT PASS THE TEST PROCEDURES SPECIFIED, AND RETEST REPAIRED PORTION OF THE SYSTEM AT FIRE PROTECTION CONTRACTOR'S EXPENSE. E. ALL PIPING TESTS (PNEUMATIC AND HYDROSTATIC) SHALL BE CONDUCTED PRIOR TO THE APPLICATION OF ANY PAINTING MATERIALS. THIS WILL PREVENT HIDDEN LEAKS AND/OR REPAINTING OF REPAIRED/ALTERED PIPING. F. WATER DAMAGE - THE FIRE PROTECTION CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE WORK OF OTHERS, TO BUILDING AND PROPERTY/MATERIALS OF OTHERS CAUSED BY LEAKS IN AUTOMATIC SPRINKLER EQUIPMENT, UNPLUGGED OR DISCONNECTED PIPES OR FITTINGS, AND SHALL PAY FOR NECESSARY REPLACEMENT OR REPAIR OF WORK OR ITEMS SO DAMAGED DURING THE INSTALLATION AND TESTING PERIODS OF THE AUTOMATIC SPRINKLER WORK. SYSTEM TESTS A. HYDROSTATICALLY TEST ALL SYSTEMS, BASED UPON REQUIREMENTS SET FORTH IN NFPA 13. B. TESTS SHALL BE WITNESSED BY AUTHORITIES HAVING JURISDICTION. C. COSTS FOR RE-INSPECTIONS FOR INCOMPLETE NON-COMPLYING SYSTEMS WILL BE CHARGED TO THE CONTRACTOR. B. FLANGES: CLASS 175 FORGED STEEL SLIP-ON FLANGES FOR FERROUS PIPING. C. MECHANICAL GROOVED COUPLINGS: MALLEABLE IRON HOUSING CLAMPS TO ENGAGE AND LOCK, DESIGNED TO PERMIT SOME ANGULAR DEFLECTION, CONTRACTION, AND EXPANSION; “C” SHAPED COMPOSITION SEALING GASKET, STEEL BOLTS, NUTS, AND WASHERS. FIRE DEPARTMENT CONNECTIONS A. FIRE DEPARTMENT CONNECTIONS INCLUDING LOCATION SHALL MEET THE APPROVAL OF THE FIRE DEPARTMENT HAVING JURISDICTION. EXECUTION A. INSTALLATION - PIPE 1. SCREW JOINT STEEL PIPING UP TO AND INCLUDING 2 INCH DIAMETER. 2. MECHANICAL GROOVED JOINTS MAY BE USED INSTEAD OF THREADED OR WELDED JOINTS AT ACCESSIBLE LOCATIONS. 3. DIE CUT SCREW JOINTS WITH FULL CUT STANDARD TAPER PIPE THREADS WITH RED LEAD AND LINSEED OIL OR OTHER NON-TOXIC JOINT COMPOUND APPLIED TO MALE THREADS ONLY. 4. COAT THREADED ENDS WITH PIPE LUBRICANT COMPOUND. 5. DO NOT PENETRATE BUILDING STRUCTURAL MEMBERS UNLESS INDICATED OR APPROVED BY THE PROJECT STRUCTURAL ENGINEER OR THE ARCHITECT. 6. PLACE PIPE RUNS TO MINIMIZE OBSTRUCTION TO THE W ORK OF OTHER TRADES. 7. PLACE PIPING ABOVE SUSPENDED CEILINGS. 8. CENTER HEADS IN ONE (1) DIRECTION IN CEILING TILES. DO NOT CUT SUSPENDED CEILING SUPPORT ANGLES. 9. PROVIDE AUXILIARY DRAINS FOR ALL TRAPPED SECTIONS OF SPRINKLER PIPING. 10. PROVIDE ALL REQUIRED SIGNAGE PER NFPA 13. B. INSTALLATION - VALVES 1. INSTALL VALVES WITH STEMS UPRIGHT OR HORIZONTAL, NOT INVERTED. 2. PROVIDE BALL VALVES FOR SHUTOFF OR ISOLATING SERVICE. SPRINKLER HEAD INSTALLATIONS A. ANY SPRINKLERS WITH ANY PAINT ON THEM, AS A RESULT OF THE PAINTING OF THE SPRINKLER PIPING, SHALL BE REPLACED. THE SPRINKLER SYSTEM SHALL THEN BE HYDROSTATICALLY TESTED AGAIN AT THE CONTRACTOR'S EXPENSE. B. SPRINKLER HEADS SHALL BE POSITIONED SO AS TO COMPLY WITH NFPA 13 FOR ANY OBSTRUCTIONS. C. PROTECT SPRINKLER HEADS AGAINST MECHANICAL INJURY WITH STANDARD GUARDS. D. PROVIDE HEADS IN "POCKETED" AREAS CAUSED BY EXPOSED DUCT, PIPING OR BEAMS. E. INSTALL SPRINKLER PIPING IN A MANNER SUCH THAT MECHANICAL EQUIPMENT, CEILING TILES OR LIGHTS CAN BE ACCESSED AND EASILY REMOVED. F. MINIMUM FIRE SPRINKLER HEAD TEMPERATURE RATING FOR SPRINKLERS IN ELECTRICAL ROOMS SHALL BE 212 DEGREE F. KEEP SPRINKLERS AS FAR FROM TRANSFORMERS AND/OR PANELS AS SPACING ALLOWS. CLEANING A. FLUSH NEW SPRINKLER PIPING SYSTEMS OF FOREIGN MATTER. SUBMIT CONTRACTOR VERIFICATION FORM FOR ABOVE GROUND SPRINKLER PIPING SYSTEMS PER NFPA 13. SECTION 21 05 00 - FIRE PROTECTION GENERAL REQUIREMENTS A. SEE ARCHITECTURAL SPECIFICATION AND DRAWINGS FOR GENERAL CONDITIONS. B. THIS SECTION OUTLINES THE GENERAL, BUT NOT SPECIFIC, SCOPE OF THE PROJECT'S FIRE PROTECTION SYSTEM. C. PROVIDE ALL ITEMS FOR COMPLETE AND SUCCESSFUL OPERATION OF ALL FIRE PROTECTION SYSTEMS. D. THE SUCCESSFUL CONTRACTOR WILL BE THE ENGINEER OF RECORD FOR THE DESIGN OF THE SYSTEM. THE DESIGN AND ENGINEERING OF THE FIRE PROTECTION SYSTEM SHALL BE BY THE FIRE PROTECTION CONTRACTOR. E. IT IS THE CONTRACTOR'S RESPONSIBILITY THAT THE SYSTEM MEET ALL THE REQUIREMENTS OF APPLICABLE NFPA AND THE LOCAL AUTHORITY HAVING JURISDICTION. F. REPLACE ANY WORK OR MATERIAL INSTALLED OR FURNISHED UNDER THIS CONTRACT WHICH DEVELOPS DEFECTS, EXCEPT FOR NORMAL WEAR, WITHIN ONE (1) YEAR AFTER CERTIFICATE OF COMPLETION IS SECURED. G. ALL SYSTEMS SHALL INCLUDE, BUT NOT BE LIMITED TO, THE FOLLOWING: ALL PIPING AND FITTINGS, VALVES, SPRINKLER HEADS, EXTRA SPRINKLER HEAD CABINETS AND ASSOCIATED WRENCHES, ALL REQUIRED DRAINS, VALVES, HANGERS AND SUPPORTS, AND ALL REQUIRED ACCESSORIES, DEVICES, ETC. H. FIRE PROTECTION CONTRACTOR SHALL SIGN AND SEAL INSTALLATION SHOP DRAWINGS, AND HYDRAULIC CALCULATIONS, PRIOR TO ISSUANCE TO THE LOCAL GOVERNING AUTHORITIES FOR APPROVAL AND PERMIT. NO WORK SHALL BE INSTALLED WITHOUT APPROVED DRAWINGS OR HYDRAULIC CALCULATIONS. SEAL TO BE BY ENGINEER REGISTERED IN THE STATE OF COLORADO OR A NICET LEVEL 4 DESIGNER PRACTICING IN THE FIELD OF FIRE SPRINKLER DESIGN. I. FIRE PROTECTION CONTRACTOR SHALL VERIFY WATER FLOW DATA WITH LOCAL WATER AND/OR FIRE DEPARTMENT. A COPY OF THE WATER FLOW TEST DATA SHALL ACCOMPANY THE HYDRAULIC CALCULATIONS. J. RECORD DRAWINGS: THE CONTRACTOR SHALL MAINTAIN A MARK-UP SET OF DRAWINGS WHICH INDICATE VARIATIONS IN THE ACTUAL INSTALLATION FROM THE ORIGINAL DESIGN. TURN OVER DRAWINGS TO OWNER/ARCHITECT UPON PROJECT COMPLETION. EQUIPMENT, FITTINGS AND VALVES A. BEAR U.L./F.M. LABEL OR MARKING. B. PROVIDE MANUFACTURER'S NAME AND PRESSURE RATING MARKED ON VALVE BODY AND INSTALL IN CLEAR VIEW. PIPING AND TUBING (INSIDE BUILDING) A. STEEL PIPE: ASTM A53; OR ANSI/ASTM A135; BLACK; SCHEDULE 40. B. AMERICAN TUBE COMPANY “DYNA THREAD 40” AND “DYNA FLOW”, ALLIED TUBE AND CONDUIT CORPORATION ”SUPER FLO” ARE ACCEPTABLE ALTERNATES TO SCHEDULE 40 PIPING. C. ACCEPTABLE ALTERNATES TO SCHEDULE 40 PIPE SHALL BE INSTALLED PER MANUFACTURERS RECOMMENDATIONS. D. SCHEDULE 10 PIPE SHALL ONLY BE ALLOWED FOR PIPE SIZES 2-1/2” AND LARGER. E. ALLIED ASTM A120 NOT ACCEPTABLE. PIPE FITTINGS A. STEEL FITTINGS: ANSI/ASME B16.9, WROUGHT STEEL. B. CAST IRON FITTINGS: ANSI/ASME B16.1, FLANGES AND FITTINGS. B16.4, SCREWED FITTINGS. UNIONS, FLANGES, AND COUPLINGS A. UNIONS: CLASS 175 MALLEABLE IRON FOR THREADED FERROUS PIPING. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 9 : 0 6 A M FP-002 FIRE PROTECTION SPECIFICATIONS St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB REVISION DATE 4 3 2 1 AC DE 2 1/2" B 6"AS AREA OF WORK FP2 AREA OF WORKFP1 FP1 FP3 FP3 FP3 LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A COOLER 005 FREEZER 006 OFFICE 001 B.O.H. B02A THEATER B02 LOBBY B01 TI STORAGE 010 AREA OF WORKFP1 SPRINKLER DENSITY LEGEND LIGHT HAZARD 0.10 GPM/1500 SQ. FT. ORDINARY HAZARD G1 0.15 GPM/1500 SQ. FT. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 9 : 1 2 A M FP-200 BASEMENT FIRE PROTECTION PLAN St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB 5. COORDINATE DEVICE LOCATIONS WITH ARCHITECT, MECHANICAL, PLUMBING AND ELECTRICAL CONTRACTORS. 4. FINAL APPROVAL OF SPRINKLER FINISHES SHALL BE COORDINATED IWTH THE OWNER AND ARCHITECT PRIOR TO THE PURCHASE OR INSTALLATION OF ANY SPRINKLERS. 3. ALL EQUIPMENT MUST BE FM APPROVED AND UL LISTED. 2. ALL FIRE SUPPRESSION SYSTEMS TO BE HYDRAULICALLY CALCULATED PER NFPA 13 WITH A MAXIMUM 32 FPS VELOCITY IN PIPES. 1. INSTALL FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS AND ANY APPLICABLE AMENDMENTS. GENERAL NOTES N 0 4'4' 2' 1/4" = 1'-0" 1 BASEMENT FIRE PROTECTION PLAN WORK NOTES FP1 MODIFY EXISTING SPRINKLER SYSTEM IN THIS AREA TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. FP2 LOCATION OF EXISTING FIRE SPRINKLER WATER ENTRY. FP3 INSTALL DRY PENDENT SPRINKLERS IN FREEZER/COOLER. REVISION DATE F.E. 4 3 2 1 AC DE B AREA OF WORKFP1 FP3 FP4 PRIVATE DINING 113 COOLER 112 DISH 111 KITCHEN BOH 109 STORAGE 105 BAR BOH 108 ENTRY 100 LIQ. STORAGE 106 PRIVATE PATIO 114 PATIO 117 DINING 115 RETAIL 103 BAR 107 CIRCULATION 009 BENCH SEATING 119 BOOTHS 116 BOOTHS 118 DINING 102 CIRCULATION 116 SPRINKLER DENSITY LEGEND LIGHT HAZARD 0.10 GPM/1500 SQ. FT. ORDINARY HAZARD G1 0.15 GPM/1500 SQ. FT. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO.PLAN NORTH Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 8 : 5 9 : 1 7 A M FP-201 LEVEL 1 FIRE PROTECTION PLAN St a n e l y H o t e l P o s t R e s t a u r a n t T I CMM 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS TLB N 0 4'4' 2' 1/4" = 1'-0" 1 LEVEL 1 FIRE PROTECTION PLAN 5. COORDINATE DEVICE LOCATIONS WITH ARCHITECT, MECHANICAL, PLUMBING AND ELECTRICAL CONTRACTORS. 4. FINAL APPROVAL OF SPRINKLER FINISHES SHALL BE COORDINATED IWTH THE OWNER AND ARCHITECT PRIOR TO THE PURCHASE OR INSTALLATION OF ANY SPRINKLERS. 3. ALL EQUIPMENT MUST BE FM APPROVED AND UL LISTED. 2. ALL FIRE SUPPRESSION SYSTEMS TO BE HYDRAULICALLY CALCULATED PER NFPA 13 WITH A MAXIMUM 32 FPS VELOCITY IN PIPES. 1. INSTALL FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH APPLICABLE CODES AND STANDARDS AND ANY APPLICABLE AMENDMENTS. GENERAL NOTES WORK NOTES FP1 MODIFY EXISTING SPRINKLER SYSTEM IN THIS AREA TO ACCOMMODATE ARCHITECTURAL RENOVATIONS. FP3 INSTALL DRY PENDENT SPRINKLERS IN FREEZER/COOLER. FP4 INSTALL SPRINKLERS ABOVE AND BELOW DROP CEILINGS TO PROTECT COMBUSTIBLE SPACES ABOVE CEILINGS. REFERENCE ARCHITECTURAL PLANS FOR EXTENT OF CEILINGS. REVISION DATE KEYNOTE DRAWING NOTE EQUIPMENT SCHEDULE ID REVISION NUMBER DESCRIPTIONSYMBOL OR (XX###) DETAIL CALLOUT * # REFERENCE INDICATOR; ASTERISK IS INCLUSIVE OF ALL DETAILS ON REFERENCED SHEET REFERENCE SHEET NUMBER ELEVATION CALLOUT A,B,C,D # WALL ELEVATION REFERENCE REFERENCE SHEET NUMBER BREAK LINE DETAIL FURNISH / INSTALL CALLOUT (ON DETAILS WHERE CALLOUTS ARE USED, ASSUME EC FOR X AND Y WHERE NOT INDICATED FOR COMPONENTS) UON IN TECHNOLOGY RESPONSIBILITY MATRIX) X INDICATES ENTITY (ABBREVIATED) BCER RECOMMENDS BE RESPONSIBLE FOR FURNISHING Y INDICATES ENTITY (ABBREVIATED) BCER RECOMMENDS BE RESPONSIBLE FOR INSTALLING X Y CONTINUANCE LINE TELECOM AREA BOUNDARY LINE TELECOM ROOM BOUNDARY LINE XY TYPICAL WALL MOUNTED DEVICE NOTATION. EXAMPLE: CEILING-MOUNTED SPEAKER WALL-MOUNTED SPEAKER TYPICAL STATION CALLOUT X INDICATES NUMBER OF VOICE/DATA PORTS/CABLES, UNLESS FOLLOWED BY AN "F", THEN IT INDICATES NUMBER OF STRANDS Y INDICATES NUMBER OF COAX PORTS/CABLES (ASSUME 0 IF BLANK) F WHEN INCLUDED IN THE STATION CALLOUT, INDICATES TO PROVIDE FIBER OPTIC CABLING TYPICAL POLE OR BOOM MOUNTED DEVICE NOTATION. EXAMPLE: WALL-MOUNTED SECURITY CAMERA POLE-MOUNTED SECURITY CAMERA +H TYPICAL DEVICE OR EQUIPMENT NON-STANDARD HEIGHT (TELECOM OUTLET EXAMPLE SHOWN) H INDICATES DIMENSION OF DEVICE OR EQUIPMENT CENTERLINE (UON) ABOVE FINISHED FLOOR IF TYPICAL ASSEMBLY NOTATION, INCLUDES: - INFRASTRUCTURE: FLOOR BOX, POKE-THRU, WALL BOX, SURFACE RACEWAY, ENCLOSURE, HOUSING, RACK, ETC. -SERVICES: DEVICES AND/OR CABLING AS SHOWN ASSOCIATED WITH INFRASTRUCTURE. (FLOORBOX WITH INTERFACE PLATE AND TELECOM OUTLET EXAMPLE SHOWN). 2 X WALL SYMBOL/DEVICE CONGESTION NOTATION INCLUDES: LEADER INDICATOR: USED TO IDENTIFY INTENDED LOCATION OF SYMBOL(S) THAT WOULD OTHERWISE OVERLAP OR CREATE CONGESTION WITH OTHER SYMBOLOGY. TARGET INDICATOR: USED TO IDENTIFY INTENDED LOCATION OF LEADER ARROWHEAD TERMINATION THAT WOULD OTHERWISE OVERLAP OR CREATE CONGESTION WITH OTHER SYMBOLOGY. CONGESTION INDICATOR: USED TO IDENTIFY ARRANGEMENT OF CONGESTED DEVICES. X INDICATES CONGESTION TYPE: H HORIZONTAL V VERTICAL (ALONG SAME STUD OR STUD CAVITY) B BOTH HORIZONTAL AND VERTICAL -- SINGLE ITEM (NOT ALIGNED) 2 A X FUTURE EQUIPMENT, RACK, OR ENCLOSURE OUTLINE # XX## XX### # OR # * # A B C D # DRAWING ANNOTATIONS S A A S SYMBOL SYMBOL ABBREV.DEFINITIONABBREV. DEFINITION ABBREVIATIONS SYMBOL SYMBOL SYMBOLSYMBOL ET WxH SR U CS OSP CT-DxW FSD FPA A A IF A A A CP EAES S S X S S S T T T LEGEND A A A SECURITY AUDIOVISUAL COMMON WORK / ELECTRICAL COMMUNICATIONS S S P SUBSCRIPT DESCRIPTION DETAILS E WS RS SYMBOL EC C C C EP P P P P P SPECIALTY SYSTEMS EI NOT ALL ITEMS LISTED IN THIS LEGEND ARE USED ON TECHNOLOGY DRAWINGS. SUBSCRIPTS ADJACENT SYMBOLS ELSEWHERE ON DRAWINGS INDICATE ADDITIONAL INFORMATION REGARDING APPLICATION OF DEVICE OR EQUIPMENT. REFER TO ABBREVIATIONS, DRAWING ANNOTATIONS, SCHEDULES, AND SPECIFICATIONS FOR ADDITIONAL SYMBOL SUBSCRIPT INFORMATION. 1. 2. LEGEND NOTES MULTIPLE SUBSCRIPTS ADJACENT A SYMBOL SIGNIFY MULTIPLE DEVICE TYPES OR MULTIPLE INSTALLATION REQUIREMENTS FOR ONE OR MORE DEVICES. MULTIPLE SUBSCRIPTS REPRESENTING DIFFERENT DEVICE TYPES ADJACENT A SYMBOL IS EQUIVALENT TO MULTIPLE DEVICES LOCATED AT THE SAME OR APPROXIMATE PLAN LOCATION, BUT AT DIFFERENT ELEVATIONS. THE FIRST SUBSCRIPTS (STARTING FROM THE LEFT OR TOP) IS ASSOCIATED WITH THE DEVICE AT THE HIGHEST ELEVATION, THE SECOND SUBSCRIPT IS ASSOCIATED WITH THE DEVICE AT THE NEXT HIGHEST ELEVATION, ETC. 3. © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 0 A M T0.1 COMMUNICATIONS TITLE SHEET St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER LL LINE LEVEL LEFT CHANNEL AUDIO LM LINE LEVEL MONO AUDIO LPS LOCK POWER SUPPLY LR LINE LEVEL RIGHT CHANNEL AUDIO MAG MAGNETIC LOCK MECH MECHANICAL MED MEDICAL EQUIPMENT MFR MANUFACTURER MIC MICROPHONE LEVEL AUDIO MIN MINIMUM MM MULTIMODE FIBER OPTIC CABLE (N) NEW NA NOT APPLICABLE NACLGS NON ACCESSIBLE CEILING SPACE NEC NATIONAL ELECTRIC CODE NS NETWORK SWITCH NVR NETWORK VIDEO RECORDER O OWNER OB OVERRIDE BUTTON OC ON CENTER OD OUTSIDE DIAMETER OFCI OWNER FURNISHED, CONTRACTOR INSTALLED OFOI OWNER FURNISHED, OWNER INSTALLED OSP OUTSIDE PLANT PA PUBLIC ADDRESS POE POWER OVER ETHERNET PP PATCH PANEL(S) PR PAIR PS POWER SUPPLY PWR POWER (RL) REMOVE AND RELOCATE (RE) REMOVE REV REVISION REX REQUEST TO EXIT SWITCH RM ROOM RMC RIGID METALLIC CONDUIT RNC RIGID NONMETALLIC CONDUIT RW CABLE RUNWAY RW-A CABLE RUNWAY, ALTERNATE SPACING SC SECURITY CONTRACTOR SCHED SCHEDULE SM SINGLEMODE FIBER OPTIC CABLE SMT SURFACE MOUNT SP SURGE PROTECTOR SPEC SPECIFICATION SPKR LOUDSPEAKER LEVEL AUDIO SR SURFACE RACEWAY STP SHIELDED TWISTED PAIR TB TERMINATION BLOCK(S) TBB TELECOMMUNICATIONS BONDING BACKBONE TBD TO BE DETERMINED TC TELECOMMUNICATIONS CONTRACTOR TEL TELEPHONE TR TELECOMMUNICATIONS ROOM (IDF, FD) TYP TYPICAL U UNIT UGND UNDERGROUND UON UNLESS OTHERWISE NOTED UPS UNINTERRUPTIBLE POWER SUPPLY UTP UNSHIELDED TWISTED PAIR VB VOICE BACKBONE VGA+A HD ANALOG VIDEO TYP 15 PIN D-SUB & 3.5MM TRS VMS VIDEO MANAGEMENT SYSTEM VOIP VOICE OVER INTERNET PROTOCOL WP WEATHER PROOF ACEG ALTERNATING CURRENT ELECTRICAL GROUND ACLGS ACCESSIBLE CEILING SPACE ACT ACOUSTIC CEILING TILE AFF ABOVE FINISHED FLOOR AHJ AUTHORITY HAVING JURISDICTION APC ANGLE POLISHED CONNECTOR ARCH ARCHITECT AVC AUDIOVISUAL CONTRACTOR AWG AMERICAN WIRE GAUGE BAS BUILDING AUTOMATION SYSTEM BB BACKBONE BEP BUILDING ENTRANCE PROTECTOR BLDG BUILDING BO BY OTHERS CAB CABINET CATV CABLE TELEVISION CC CONTACT CLOSURE CCTV CLOSED CIRCUIT TELEVISION CLG CEILING COM COMMON COMM COMMUNICATION CR CARD READER CT COUNT DB DIRECT BURIAL (D) DEMOLISH DIA DIAMETER DP DISPLAY PORT DPS DOOR POSITION SWITCH DR DOOR RELEASE DVR DIGITAL VIDEO RECORDER DWG DRAWING (E) EXISTING TO REMAIN EB EXIT BUTTON EC ELECTRICAL CONTRACTOR ECL ELECTRIC CYLINDER LOCK ECP ELEVATOR CONTROL PANEL EF ENTRANCE FACILITY (DEMARC) EIB EMERGENCY INFORMATION BOARD ELEC ELECTRICAL ELV ELEVATOR EMT ELECTRICAL METALLIC TUBING ENCL ENCLOSURE EQPMT EQUIPMENT ER EQUIPMENT ROOM ES ELECTRIC STRIKE (F) FUTURE FAC FIRE ALARM CONTRACTOR FACP FIRE ALARM CONTROL PANEL FB FIBER BACKBONE, FLOOR BOX FD FLOOR DISTRIBUTOR FLEX FLEXIBLE CONDUIT FPA FLOOR PENETRATION ASSEMBLY FS FURNITURE SUPPLIER FSD FIRE STOP DEVICE G GROUND GC GENERAL CONTRACTOR HB HANDICAP BUTTON HC HORIZONTAL CABLE IF INTERFACE PLATE IG ISOLATED GROUND IMC INTERMEDIATE METAL CONDUIT IP INTERNET PROTOCOL ISP INSIDE PLANT IWC IN-BUILDING WIRELESS CONTRACTOR KS KEYSWITCH LC LOW VOLTAGE/SPECIALITY CONTRACTOR SUBSCRIPT DESCRIPTION DETAILS SECURITY EQUIPMENT LOCATION ACS ACCESS CONTROL SYSTEM T-MH, TS-ACSP IDS INTRUSION DETECTION SYSTEM T-MH, TS-ACSP VSS VIDEO SURVEILLANCE SYSTEM T-MH WORKSTATION LOCATION ACS ACCESS CONTROL SYSTEM VSS VIDEO SURVEILLANCE SYSTEM FIXED CAMERA (NO SUBSCRIPT) T-MH, TS-CD 180 180 DEGREE LENS T-MH, TS-CD 360 360 DEGREE LENS T-MH, TS-CD PAR PARAPET TS-CD FIXED CAMERA (CEILING) (NO SUBSCRIPT) TS-CD 180 180 DEGREE LENS TS-CD 360 360 DEGREE LENS TS-CD PAN - TILT - ZOOM CAMERA (NO SUBSCRIPT) T-MH, TS-CD PAR PARAPET TS-CD PAN - TILT - ZOOM CAMERA (CEILING) (NO SUBSCRIPT) TS-CD ACCESS CONTROL SYSTEM DOOR (X INDICATES DOOR TYPE) C CONTROLLED TS-DD CW CONTROLLED WIRELESS M MONITORED TS-DPS R REMOTELY CONTROLLED TS-DD PERSONNEL VERIFICATION DEVICE (NO SUBSCRIPT) T-MH, TS-SD KP KEYPAD T-MH, TS-SD L LONG RANGE T-MH M MULLION T-MH PERSONNEL VERIFICATION DEVICE (HARDWARE INTEGRATED) (NO SUBSCRIPT) INTRUSION DETECTION DEVICE GB GLASS BREAK T-MH, TS-SD KP KEYPAD T-MH, TS-SD M MOTION T-MH, TS-SD INTRUSION DETECTION DEVICE (CEILING) GB GLASS BREAK TS-SD M MOTION TS-SD SECURITY DEVICE CA INTERCOM - CALL AUDIO T-MH, TS-SD CV INTERCOM - CALL VIDEO T-MH, TS-SD D DURESS BUTTON T-MH L LOCKDOWN BUTTON T-MH S STROBE T-MH SECURITY CEILING DEVICE MC MICROPHONE S STROBE SECURITY FIELD LOCATED DEVICE D DURESS BUTTON DR DOOR RELEASE MA INTERCOM - MASTER AUDIO MV INTERCOM - MASTER VIDEO SUBSCRIPT DESCRIPTION DETAILS AUDIOVISUAL EQUIPMENT LOCATION SHARED RACK SPACE (TYP TR) T-MH, TC SERIES LOUDSPEAKER STANDARD (WALL) T-MH, TA-IFB A TYPE A T-MH B TYPE B T-MH C TYPE C T-MH LOUDSPEAKER (CEILING) STANDARD ACT (REPLACEMENT OR CUT-IN) TA-CSD N NON-ACCESSIBLE CEILING TA-CSD P PENDANT TA-CSD VIDEO DISPLAY STANDARD (WALL) DS DIGITAL SIGNAGE VW VIDEO WALL VIDEO DISPLAY (CEILING) PLENUM ACT CEILING TA-DMD A ACT CEILING TA-DMD DS DIGITAL SIGNAGE E EXPOSED TA-DMD N NON-ACCESSIBLE CEILING TA-DMD PROJECTION SCREEN STANDARD (WALL) TA-WMS PROJECTION SCREEN (CEILING) RECESSED TA-CRS C SUSPENDED TA-CSS CONTROL PANEL STANDARD (BACKBOX) T-MH, TA-IFCP A TYPE A T-MH, TA-IFCP T TABLE TOP / TOUCH PANEL ROOM SCHEDULER (NO SUBSCRIPT) T-MH, TA-IFRS INTERFACE PLATE STANDARD (WALL) T-MH, TA-IFW B TYPE B T-MH C TYPE C T-MH F STANDARD, FLOOR TA-FIF T TABLE TOP / FURNITURE TA-TIF PROJECTOR SHORT THROW (INTERACTIVE) TA-WPD A SHORT THROW (PRESENTATION) B TYPE B PROJECTOR (CEILING) PLENUM ACT CEILING TA-PMD A ACT CEILING TA-PMD E EXPOSED TA-PMD N NON-ACCESSIBLE CEILING TA-PMD PROJECTOR LIFT CEILING MOUNTED TA-PL FIXED CAMERA (CEILING) (NO SUBSCRIPT) A TYPE A PAN - TILT - ZOOM CAMERA (NO SUBSCRIPT) T-MH, TA-IFB A TYPE A T-MH, TA-IFB PAN - TILT - ZOOM CAMERA (CEILING) (NO SUBSCRIPT) A TYPE A LECTERN (NO SUBSCRIPT) AUDIOVISUAL DEVICE ALS ASSISTIVE LISTENING T-MH AP WIRELESS ACCESS POINT TRANSCEIVER T-MH S SCREEN SWITCH T-MH VC VOLUME CONTROL T-MH WM WIRELESS MIC ANTENNA T-MH AUDIOVISUAL CEILING DEVICE ALS ASSISTIVE LISTENING AP WIRELESS ACCESS POINT TRANSCEIVER M MICROPHONE PS PARTITION SENSOR WM WIRELESS MIC ANTENNA AUDIOVISUAL FIELD LOCATED DEVICE DM DUAL-ELEMENT BOUNDARY MICROPHONE M MICROPHONE TM TRI-ELEMENT BOUNDARY MICROPHONE WC WEB CAM STRUCTURAL BLOCKOUT (WIDTH x HEIGHT) CABLE PATHWAY FIRESTOPPING DEVICE TE-WFS FIRE-RATED FLOOR PENETRATION ASSEMBLY TE-FFS GROUND CONDUIT WITH BUSHING CONDUIT WITH CAP CONDUIT UP CONDUIT DOWN CONDUIT / CABLE HOME RUN SURFACE RACEWAY CONDUIT UNDERGROUND / FLOOR / SLAB OSP UNDERGROUND DUCTBANK PULL BOX UTILITY POLE CABLE SUPPORT PATHWAY (NO SUBSCRIPT) TE-CR J J-HOOKS CABLE TRAY (DEPTH x WIDTH) (NO SUBSCRIPT) TE-BJ, TE-CT, TE-CTUB, TE-CR GROUNDING BUSBAR TGB GROUND BUS T-MH, TE-GS TMBG MAIN GROUND BUS T-MH, TE-GS DEVICE BOX EMPTY (NO SUBSCRIPT) T-MH, TE-CR AV AUDIOVISUAL TE-CR, TA-DETAILS FF FURNITURE FEED TE-CR S SECURITY TS-SD SEP SITE EMERGENCY PHONE TE-CR DEVICE BOX EMPTY (CEILING) (NO SUBSCRIPT) TE-CR AV AUDIOVISUAL TE-CR, TA-DETAILS S SECURITY TS-SD FLOOR BOX (NO SUBSCRIPT) TE-FD FB4 4-GANG TE-FD FB6 6-GANG TE-FD FB8 8-GANG TE-FD FB10 10-GANG TE-FD FBF FURNITURE FEED TE-FD POKE THRU PT6 6-INCH TE-FD PT8 8-INCH TE-FD PTF FURNITURE FEED TE-FD ENCLOSURE AUDIOVISUAL CEILING BOX TA-PE S SECURITY CEILING ENCLOSURE TS-SD WALL BOX VIDEO DISPLAY T-MH, TA-DWB EQUIPMENT RACK AUDIOVISUAL (FLOOR) TA-IFER W AUDIOVISUAL (WALL) TA-IFWR HAND HOLE / PULL BOX (NO SUBSCRIPT) TE-PB MAINTENANCE HOLE (NO SUBSCRIPT) TE-MH, TE-MHCE SUBSCRIPT DESCRIPTION DETAILS COMMUNICATIONS EQUIPMENT LOCATION (NO SUBSCRIPT) T-MH TELECOM OUTLET (NO SUBSCRIPT) T-MH, TE-CR AC ABOVE COUNTER T-MH, TE-CR AV AUDIOVISUAL TE-CR, TA-DETAILS DS DIGITAL SIGNAGE TE-CR, TA-DETAILS E EMERGENCY INFORMATION BOARD TE-CR ELEC ELECTRICAL EQUIPMENT TE-CR ELV ELEVATOR EQUIPMENT TE-CR EP EMERGENCY BLUE PHONE TE-CR F FURNITURE MOUNTED FACP FIRE ALARM CONTROL PANEL TE-CR K KIOSK TE-CR LCP LIGHTING CONTROL PANEL TE-CR MECH MECHANICAL/HVAC EQUIPMENT TE-CR POS POINT OF SALE TE-CR S SECURITY CAMERA TS-CD SR SURFACE RACEWAY TW TWO WAY COMMUNICATION BASE STATION T-MH, TE-CR VND VENDING MACHINE TE-CR W WALL TELEPHONE T-MH, TE-CR WAP WIRELESS ACCESS POINT TE-CR TELECOM OUTLET (CEILING) (NO SUBSCRIPT) TE-CR AV AUDIOVISUAL TE-CR, TA-DETAILS DS DIGITAL SIGNAGE TE-CR, TA-DETAILS E EMERGENCY INFORMATION BOARD TE-CR S SECURITY CAMERA TS-CD WAP WIRELESS ACCESS POINT TE-CR COMMUNICATIONS DEVICE (NO SUBSCRIPT) COMMUNICATIONS CEILING DEVICE (NO SUBSCRIPT) COMMUNICATIONS FIELD LOCATED DEVICE (NO SUBSCRIPT) DENVER OFFICE COLORADO SPRINGS OFFICE 10807 NEW ALLEGIANCE DRIVE, SUITE 400 COLORADO SPRINGS, CO 80921 719.533.1112 5420 WARD ROAD, SUITE 200 ARVADA, CO 80002 303.422.7400 TAMPA OFFICE 12450 ROOSEVELT BLVD N., SUITE 305 ST. PETERSBURG, FL 33716 727.685.0458 MELBOURNE OFFICE 6555 N. WICKHAM ROAD, SUITE 104 MELBOURNE, FL 32940 321.241.4142 CONTACT LIST PROJECT MANAGER CONSTRUCTION ADMINISTRATOR Paul Miskowicz pmiskowicz@bcer.com 303.405.2902 Tony Nutsch tnutsch@bcer.com 303.405.2854 DETAIL SHEET DETAIL INDEX T-MH - MOUNTING HEIGHT DETAIL T6.1 TE-CR - TYPICAL DEVICE ROUGH-IN AND CABLE PATHWAY DETAIL T6.1 TE-CS - TYPICAL CABLE SUPPORT STRAP PATHWAY T6.1 TE-GS - TYPICAL GROUNDING AND BONDING SYSTEM DETAIL T6.2 TE-JH - TYPICAL CABLE J-HOOK PATHWAY T6.1 TE-PB - TELECOM PULLBOX DETAIL T6.1 TE-SEDB - SAND ENCASED DUCTBANK DETAILS T6.1 TE-WAP - WIRELESS ACCESS POINT BACK BOX - OPEN CEILING T6.1 TS-CD - CAMERA ROUGH-IN DETAILS T6.2 TS-DD - DOOR DETAILS T6.3 SHEET# TITLE SHEET LIST T0.1 COMMUNICATIONS TITLE SHEET T0.2 COMMUNICATIONS PROJECT NOTES T0.3 COMMUNICATIONS SCHEDULES T0.4 COMMUNICATIONS SCHEDULES T0.5 COMMUNICATIONS SPECIFICATIONS T0.6 COMMUNICATIONS SPECIFICATIONS T0.7 COMMUNICATIONS SPECIFICATIONS T0.8 COMMUNICATIONS SPECIFICATIONS T1.1 COMMUNICATIONS SITE PLAN T2.1 COMMUNICATIONS BASEMENT FLOOR PLAN T2.2 COMMUNICATIONS FIRST FLOOR PLAN T6.1 COMMUNICATIONS DETAILS T6.2 COMMUNICATIONS DETAILS T6.3 COMMUNICATIONS DETAILS SUBSCRIPT DESCRIPTION DETAILS PUBLIC ADDRESS EQUIPMENT LOCATION (NO SUBSCRIPT) T-MH PUBLIC ADDRESS LOUDSPEAKER (NO SUBSCRIPT) T-MH PUBLIC ADDRESS LOUDSPEAKER (CEILING) (NO SUBSCRIPT) N NON-ACCESSIBLE CEILING TL-CSD P PENDANT TL-CSD PUBLIC ADDRESS DEVICE CALL BUTTON (NO SUBSCRIPT) T-MH PUBLIC ADDRESS CEILING DEVICE (NO SUBSCRIPT) PUBLIC ADDRESS FIELD LOCATED DEVICE (NO SUBSCRIPT) CLOCK EQUIPMENT LOCATION (NO SUBSCRIPT) T-MH CLOCK (NO SUBSCRIPT) T-MH CLOCK (CEILING) (NO SUBSCRIPT) CLOCK DEVICE (NO SUBSCRIPT) CLOCK CEILING DEVICE (NO SUBSCRIPT) CLOCK FIELD LOCATED DEVICE (NO SUBSCRIPT) IN-BUILDING WIRELESS EQUIPMENT LOCATION (NO SUBSCRIPT) T-MH REVISION DATE A THESE COMMUNICATIONS NOTES INDICATE GENERAL REQUIREMENTS FOR WORK INDICATED ON THE DRAWINGS. THE NOTES LISTED HERE SHALL BE APPLIED TO AND CONSIDERED PART OF THE WORK REQUIREMENTS FOR EACH INDIVIDUAL DRAWING SHEET, AS APPLICABLE. B EVERY CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE GENERAL NOTES - GENERAL SECTION FOR PROJECT NOTES THAT APPLY TO MORE THAN ONE TRADE AS WELL AS ALL OTHER NOTES PROVIDED FOR OTHER TRADES FOR FULL COORDINATION BETWEEN ALL TRADES. C THIS PROJECT SHALL BE ACTIVELY MANAGED BY THE CONTRACTOR'S PROJECT MANAGER WHICH SHALL NOT ALSO BE THE CONTRACTOR'S FOREMAN OR BE INVOLVED IN TECHNICAL WORK IN THE FIELD. DOWNTIME, DELAYS OR NON-SCHEDULED OUTAGES DUE TO THE CONTRACTOR'S FAILURE TO ACTIVELY MANAGE THE WORK, INCLUDING BUT NOT LIMITED TO EFFECTIVELY PLANNING, SEQUENCING, SCHEDULING, AND EXECUTING THE WORK WILL NOT BE ACCEPTABLE AT ANY TIME. D PRIOR TO PROCUREMENT AND INSTALLATION OF BACKBONE CABLE, PHYSICALLY VERIFY ON SITE THE TOTAL RUN LENGTH FOR EACH CABLE FROM ENDPOINT TO ENDPOINT USING ACTUAL ROUTING, INCLUDING VERTICAL TRANSITIONS, REQUIRED CABLE SLACK, ETC. PRE-CUT/PRE-MANUFACTURED CABLES OF INSUFFICIENT LENGTH ARE THE SOLE RESPONSIBILITY OF THE CONTRACTOR. E PRIOR TO PROCUREMENT AND INSTALLATION OF CABLE, COORDINATE CABLE ROUTING AND DUCT UTILIZATION WITH OWNER. F PRIOR TO INSTALLATION, VERIFY THE TOTAL RUN LENGTH FOR EACH HORIZONTAL CABLE FROM THE TELECOM OUTLET TO THE SERVING TELECOMMUNICATIONS ROOM, USING THE RACEWAYS (CONDUIT, SLEEVES, ETC) AS INSTALLED. FOR RUN LENGTHS WHICH EXCEED 270 FEET, INCLUDING UP/DOWN TRANSITIONS, REQUIRED CABLE SLACK, ETC., OBTAIN THE ENGINEER'S DIRECTION PRIOR TO PROCEEDING. G PROVIDE OSP CAT6 CABLING FOR ALL HORIZONTAL (STATION) CABLING INSTALLATIONS IN PATHWAY CONSIDERED TO BE WET LOCATION PER THE NEC, INCLUDING BUT NOT LIMITED TO UNDERSLAB OR IN SLAB ON GRADE. THE INSTALLATION OF HORIZONTAL (STATION) OSP CABLING SHALL ALSO MEET THE REQUIREMENTS OF NEC 800.48. WHERE CONDUITS FOR HORIZONTAL (STATION) OSP CABLING ENTER THE BUILDING FROM OUTSIDE AT A LEVEL THAT IS WITHIN THE BUILDING THE CONTRACTOR SHALL EITHER PROVIDE IMC CONDUIT THE ENTIRE WAY TO THE TELECOM ROOM AS LONG AS NO PULL BOXES ARE REQUIRED DUE TO LENGTH OF RUN OR NUMBER OF BENDS. IF PULL BOXES ARE REQUIRED THEN THE CONTRACTOR SHALL LOCATE THE FIRST PULL BOX AS CLOSE TO THE ENTRANCE OF THE CONDUIT INTO THE BUILDING AND IN AN ACCESSIBLE LOCATION. THE CONTRACTOR SHALL LOCATE THE BEP IN THAT PULL BOX AND PROVIDE ISP RATED HORIZONTAL (STATION) CABLING FROM THAT POINT TO THE TR. THE CONTRACTOR SHALL CONFIRM ALL SUCH INSTALLATIONS WITH THE ENGINEER AND OWNER PRIOR TO ROUGH IN AND INSTALL. A THESE GENERAL NOTES INDICATE THE GENERAL REQUIREMENTS FOR THE WORK INDICATED ON THE DRAWINGS. THE NOTES LISTED HERE SHALL BE APPLIED TO AND CONSIDERED PART OF THE WORK REQUIREMENTS FOR EACH INDIVIDUAL DRAWING SHEET, AS APPLICABLE. B THE GENERAL NOTES SHALL GOVERN UNLESS OTHERWISE NOTED ON DRAWINGS. C EXAMINE THE CONTRACT DOCUMENTS IN THEIR ENTIRETY, INCLUDING BUT NOT LIMITED TO GENERAL AND SUPPLEMENTAL REQUIREMENTS, DRAWINGS AND SPECIFICATIONS OF OTHER DIVISIONS, AND ADDENDA, FOR EQUIPMENT OR WORK WHICH MAY AFFECT WORK UNDER THIS SECTION, REGARDLESS OF WHETHER SUCH REQUIREMENTS OR WORK ARE SPECIFICALLY INDICATED IN THIS SECTION. D WORK SHALL COMPLY WITH THE GOVERNING REQUIREMENTS LISTED IN THE SPECIFICATIONS. E IF DISCREPANCIES OR CONFLICTS ARE DISCOVERED IN THE CONSTRUCTION DOCUMENTS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER IN WRITING AND WAIT FOR INSTRUCTION PRIOR TO PROCEEDING WITH WORK RELATED TO DISCREPANCIES OR CONFLICTS. F SUBSTITUTIONS OF PRODUCT AND DEVIATIONS FROM METHODS OF CONSTRUCTION SPECIFIED SHALL BE CONSIDERED AT SUBMITTAL REVIEW. SUCH SUBSTITUTIONS USED FOR BID SHALL BE AT THE SOLE RISK OF CONTRACTOR, AND AS SUCH ARE SUBJECT TO REJECTION WITHOUT CONSIDERATION. G RECORD DRAWINGS SHALL BE MAINTAINED ON SITE PER SPECIFICATIONS SHOWING ADDITIONS, CHANGES, DELETIONS THROUGHOUT CONSTRUCTION. H PROVIDE SEISMIC BRACING AS REQUIRED BY THE GOVERNING REQUIREMENTS. I DRAWING ELEMENTS SHOWN IN GRAY ARE EXISTING TO REMAIN. WHERE SUCH ELEMENTS AFFECT THE CONTRACTORS WORK, COORDINATE DEPENDENCIES WITH APPLICABLE OTHERS IN A TIMELY MANNER, BEFORE SUCH DEPENDENCIES ARISE IN THE FIELD. ALL DEVICES AND EQUIPMENT SHOWN ON THE DEMOLITION DRAWINGS IN BLACK ARE SCHEDULED TO BE REMOVED. REVIEW ALL DEMOLITION NOTES, DRAWING NOTES, AND SPECIFICATIONS FOR ADDITIONAL DEMOLITION REQUIREMENTS. EXISTING DEVICES NOT SHOWN ON THE DEMOLITION DRAWINGS SHALL REMAIN UNLESS OTHERWISE NOTED IN THE CONTRACT DOCUMENTS. J THIS PROJECT SHALL BE ACTIVELY MANAGED BY THE CONTRACTOR'S PROJECT MANAGER WHICH SHALL NOT ALSO BE THE CONTRACTOR'S FOREMAN OR BE INVOLVED IN TECHNICAL WORK IN THE FIELD. DOWNTIME, DELAYS OR NON-SCHEDULED OUTAGES DUE TO THE CONTRACTOR'S FAILURE TO ACTIVELY MANAGE THE WORK, INCLUDING BUT NOT LIMITED TO EFFECTIVELY PLANNING, SEQUENCING, SCHEDULING, AND EXECUTING THE WORK WILL NOT BE ACCEPTABLE AT ANY TIME. K WORK REQUIRING UTILITY AND/OR TECHNOLOGY SYSTEM OUTAGES SHALL BE COORDINATED WITH THE OWNER IN ADVANCE AND PRE-APPROVED IN WRITING. L COORDINATION IS REQUIRED PRIOR TO ROUGH-IN. DRAWINGS ARE DIAGRAMMATIC AND SHALL NOT BE SCALED FOR BOX, DEVICE AND/OR EQUIPMENT LOCATIONS. M WHERE COORDINATION DICTATES THAT FINAL LOCATIONS VARY SIGNIFICANTLY FROM THAT SHOWN ON THE DRAWINGS, THE CONTRACTOR SHALL NOTIFY THE ENGINEER AND AWAIT APPROVAL PRIOR TO ELECTRICAL ROUGH-IN. N IDENTIFY AND COORDINATE WITH OTHER TRADES LOCATION AND SIZE OF REQUIRED OPENINGS IN NEW CONCRETE OR MASONRY PRIOR TO THE FORMING AND POURING OF CONCRETE OR CONSTRUCTION OF MASONRY. OPENINGS MAY NOT BE INDICATED ON DRAWINGS. O CONTRACTOR SHALL COORDINATE ALL PENETRATIONS, OPENINGS, FASTENERS, CONNECTIONS, HANGERS, AND SUPPORTS WITH STRUCTURAL DRAWINGS AND ENGINEER PRIOR TO COMMENCEMENT OF WORK. P PENETRATION OF CONCRETE AND STRUCTURAL ELEMENTS SHALL BE AVOIDED WHERE POSSIBLE. OBTAIN WRITTEN APPROVAL FROM STRUCTURAL ENGINEER/ARCHITECT PRIOR TO SUCH NECESSARY PENETRATIONS. Q PROVIDE SLEEVES FOR LOCATIONS WHERE CABLE PASSES THROUGH WALLS, FLOORS, OR FOUNDATIONS. SLEEVES SHALL BE SIZED TO SUPPORT CABLES PER NEC FILL RATIOS AND TIA/EIA 569 CABLE CAPACITY STANDARDS PLUS 25 PERCENT FUTURE EXPANSION. R PROVIDE SMOKE AND ACOUSTICAL PATHWAY DEVICES/SLEEVES FOR LOCATIONS WHERE CABLE WILL PENETRATE THROUGH A NON-FIRE RATED BARRIER THAT IS SMOKE RATED OR WHERE THERE IS AN ACOUSTICAL TRANSMISSION CONCERN SUCH AS IN LOCATIONS WHERE ADJACENT ROOMS HAVE NO CEILINGS. REVIEW ALL PORTIONS OF THE ARCHITECTURAL CONSTRUCTION DOCUMENTS INCLUDING, BUT NOT LIMITED TO THE LIFE SAFETY PLANS FOR WALL AND CEILING TYPE INFORMATION. PROVIDE SMOKE AND ACOUSTICAL PATHWAY DEVICE(S) IN SUFFICIENT QUANTITY SUCH THAT THE COMBINED USEABLE CROSS SECTIONAL AREA OF THE DEVICE(S) MATCHES OR EXCEEDS THE CROSS SECTIONAL AREA OF CABLE TRAY TO BE SERVED. S CABLE SUPPORTS EXTERIOR TO COMMUNICATIONS EQUIPMENT ROOMS WHERE CABLE TRAY OR CONDUIT PATHWAY IS NOT PROVIDED ACCORDING TO THE TECHNOLOGY CONSTRUCTION DOCUMENTS SHALL BE WIDE BASED J-HOOKS OR STRAPS/SLINGS. CABLE SUPPORTS ON INTERIOR OF COMMUNICATIONS EQUIPMENT ROOMS SHALL BE CABLE STRAPS OF SAME COLOR AS CABLE. T PER NEC REQUIREMENTS, COMMUNICATIONS SYSTEMS DEVICES AND EQUIPMENT SHALL NOT BE SECURED TO OR SUPPORTED BY SUSPENDED CEILING SYSTEM (INCLUDING SUPPORTS WIRES), HANGERS FOR CABLE SUPPORTS SHALL BE INDEPENDENT (DEDICATED). PER NEC REQUIREMENTS, WIRE HANGERS SHALL BE SUPPORTED AT BOTH ENDS AND DISTINGUISHABLE FROM SUSPENDED CEILING SYSTEM SUPPORT WIRE. IN EXPOSED STRUCTURAL CEILING SPACES, WIRE SHALL NOT BE USED AS A HANGER FOR SUPPORT. U HANGERS AND SUPPORTS SHALL BE PROVIDED AT INTERVALS PER THE NEC, SHALL BE ATTACHED TO STRUCTURE AND NOT BE ATTACHED TO OTHER BUILDING SYSTEMS AND THEIR ASSOCIATED SUPPORTS. CABLE SUPPORTS SHALL BE MOUNTED AT VARYING INTERVALS NOT TO EXCEED 5 FEET AND ROUTED PARALLEL AND PERPENDICULAR TO BUILDING LINES. CABLE SUPPORTS SHALL NOT SHARE CABLES OF DIFFERENT TECHNOLOGY SYSTEMS OR EXCEED 50 PERCENT OF THE MANUFACTURER'S RECOMMENDED FILL. INCLUDE CABLE SUPPORT ROUTING ON RECORD DRAWINGS. V PROVIDE TELECOM OUTLET(S) AT BUILDING FIRE ALARM CONTROL PANELS (FACP) AND FIRE ALARM ANNUNCIATOR PANELS (FAA). A MINIMUM OF 2 VOICE/DATA PORTS AND CABLES SHALL BE ASSUMED AT EACH FIRE ALARM PANEL. COORDINATE WITH FIRE ALARM DRAWINGS AND FIRE ALARM CONTRACTOR FOR PANEL LOCATIONS AND COMMUNICATIONS CONNECTIVITY REQUIREMENTS. W PROVIDE TELECOM OUTLET(S) AT SECURITY PANEL LOCATIONS. A MINIMUM OF 2 VOICE/DATA PORTS AND CABLES SHALL BE ASSUMED AT EACH PANEL. COORDINATE WITH SECURITY SYSTEM DRAWINGS AND SECURITY CONTRACTOR FOR PANEL LOCATIONS AND COMMUNICATIONS CONNECTIVITY REQUIREMENTS. X PROVIDE TELECOM OUTLET AT EACH MECHANICAL BUILDING AUTOMATION SYSTEM PANEL (TEMPERATURE CONTROL PANEL). A MINIMUM OF 4 VOICE/DATA PORTS AND CABLES SHALL BE ASSUMED AT EACH PANEL. COORDINATE WITH MECHANICAL DRAWINGS, MECHANICAL CONTRACTOR, AND TEMPERATURE CONTROLS CONTRACTOR FOR PANEL QUANTITIES AND LOCATIONS, AND FOR FINAL PORT/CABLE QUANTITY REQUIREMENTS. ROUTE CABLES TO DESIGNATED TELECOMMUNICATIONS ROOM. REPORT FINAL PORT/CABLE QUANTITY REQUIREMENTS FOR EACH TELECOMMUNICATIONS ROOM TO OW NER FOR PURPOSES OF OWNER PROVIDED NETWORK INTERFACES. Y 1 VOICE/DATA OUTLET AND CABLE SHALL BE ASSUMED FOR EACH ELEVATOR CAB. COORDINATE WITH ELEVATOR SHOP DRAWINGS AND CONTRACTOR FOR CONTROL PANEL LOCATIONS AND COMMUNICATIONS CONNECTIVITY REQUIREMENTS. Z WAP OUTLET QUANTITY AND LOCATIONS SHOWN PROVIDE SUITABLE DENSITY AND LAYOUT TO ENSURE THAT FINAL WAP LOCATIONS WILL BE WITHIN PATCH CORD LENGTH OF WAP OUTLET. AA BOXES ON OPPOSITE SIDES OF WALLS SHALL NOT BE BACK TO BACK. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES. AB REFER TO SPECIFICATIONS, SCHEDULES, AND DETAILS FOR ADDITIONAL INFORMATION REGARDING BOX, PATHWAY, STRUCTURAL SUPPORT, MOUNTING, AND OTHER REQUIREMENTS. AC REFER TO THE MOUNTING HEIGHT DETAIL FOR TYPICAL DEVICE HEIGHT REQUIREMENTS. FOR NON-TYPICAL DEVICE LOCATIONS REFER TO ARCHITECTURAL DRAWINGS, DETAILS AND/OR SPECIFICATIONS FOR DEVICE BOX MOUNTING HEIGHTS. MOUNT EQUIPMENT AND DEVICES AT ADA COMPLIANT HEIGHT. AD CABLE DAMAGED BY THE CONTRACTOR SHALL BE REPLACED BY THE CONTRACTOR WITHIN 4 HOURS OF THE DAMAGING EVENT, AT NO ADDITIONAL COST TO THE OWNER. AE CAMERA LOCATIONS SHOWN ARE APPROXIMATE. THE CONTRACTOR IS RESPONSIBLE FOR LOCATING CAMERAS IN THEIR FINAL POSITION SUCH THAT VIEWING ANGLES ARE OPTIMIZED, AND BLIND SPOTS, OBSTRUCTIONS, AND OTHER LIMITATIONS TO CAMERA EFFECTIVENESS ARE MINIMIZED. AF TELECOM OUTLETS LOCATED IN MECHANICAL, ELECTRICAL, PLUMBING AND OTHER SUPPORT SPACES THAT ARE NOT DESIGNATED FOR SPECIFIC EQUIPMENT EITHER BY WORKNOTE OR SUBSCRIPT ARE PROVIDED FOR USE BY ANY MECHANICAL, ELECTRICAL OR SUPPORT SYSTEMS / EQUIPMENT THAT ENDS UP REQUIRING A NETWORK CONNECTION. THE ELECTRICAL AND TELECOM CONTRACTORS SHALL REFER TO THE CONSTRUCTION DRAWINGS FOR ALL DISCIPLINES AND COORDINATE WITH THE CONTRACTORS FROM THE OTHER DISCIPLINES TO DETERMINE WHERE TO LOCATE THE TELECOM OUTLETS AND WHAT THE REQUIREMENTS ARE FOR CONNECTION TO THE SYSTEMS / EQUIPMENT. A THESE COMMON WORK / ELECTRICAL NOTES INDICATE GENERAL REQUIREMENTS FOR WORK INDICATED ON THE DRAWINGS. THE NOTES LISTED HERE SHALL BE APPLIED TO AND CONSIDERED PART OF THE WORK REQUIREMENTS FOR EACH INDIVIDUAL DRAWING SHEET, AS APPLICABLE. B EVERY CONTRACTOR IS RESPONSIBLE FOR REVIEWING THE GENERAL NOTES - GENERAL SECTION FOR PROJECT NOTES THAT APPLY TO MORE THAN ONE TRADE AS WELL AS ALL OTHER NOTES PROVIDED FOR OTHER TRADES FOR FULL COORDINATION BETWEEN ALL TRADES. C THIS PROJECT SHALL BE ACTIVELY MANAGED BY THE CONTRACTOR'S PROJECT MANAGER WHICH SHALL NOT ALSO BE THE CONTRACTOR'S FOREMAN OR BE INVOLVED IN TECHNICAL WORK IN THE FIELD. DOWNTIME, DELAYS OR NON-SCHEDULED OUTAGES DUE TO THE CONTRACTOR'S FAILURE TO ACTIVELY MANAGE THE WORK, INCLUDING BUT NOT LIMITED TO EFFECTIVELY PLANNING, SEQUENCING, SCHEDULING, AND EXECUTING THE WORK WILL NOT BE ACCEPTABLE AT ANY TIME. D CONDUIT BENDS (OTHER THAN BENDS IN OSP CONDUIT DUCTBANKS) SHALL BE SWEEPING, BE NO MORE THAN 90 DEGREES, BE A MINIMUM OF 6 TIMES THE INTERNAL DIAMETER OF 2-INCHES OR SMALLER CONDUITS, BE A MINIMUM OF 10 TIMES THE INTERNAL DIAMETER OF CONDUITS LARGER THAN 2-INCHES, AND CONFORM TO TIA-569 BEND RADIUS REQUIREMENTS. FOR CONDUITS LARGER THAN 1-1/4 INCH, BENDS SHALL BE FACTORY-MANUFACTURED. 90 DEGREE CONDULET (LB) FITTINGS ARE NOT PERMITTED. E THE TOTAL OF CONDUIT BENDS FOR A CONDUIT SEGMENT BETWEEN END POINTS/PULL BOXES SHALL NOT EXCEED 180 DEGREES, EXCEPT ONE ADDITIONAL BEND OF UP TO 90 DEGREES IS ACCEPTABLE IF THE BEND IS LOCATED WITHIN 12 INCHES OF THE CABLE FEED END. F THE USE OF FLEXIBLE CONDUIT IS PERMITTED ONLY WHERE INDICATED ON DRAWINGS OR OTHERWISE REQUESTED BY CONTRACTOR AND ACCEPTED BY ENGINEER IN WRITING. IF FLEXIBLE CONDUIT IS PERMITTED, IT SHALL BE ONE TRADE SIZE LARGER THAN THE REQUIRED NON FLEXIBLE CONDUIT (EX. 1 1/4 EMT TO 1 1/2 FLEXIBLE). G CONDUITS FOR HORIZONTAL OR SYSTEMS CABLE OVER 3 FEET LONG SHALL HAVE MINIMUM 200 POUND TEST RATED PULL TAPE WITH PRINTED FOOTAGE INDICATOR SECURED AT CONDUIT ENDS AND EXTENDING A MINIMUM OF 3 FEET BEYOND CONDUIT ENDS. H CONDUITS FOR BACKBONE CABLE OVER 3 FEET LONG SHALL HAVE 2400 POUND TEST SEQUENTIALLY NUMBERED PULL TAPE SECURED AT CONDUIT ENDS AND EXTENDING A MINIMUM OF 3 FEET BEYOND CONDUIT END OF INTERIOR CONDUITS AND 10 FEET BEYOND CONDUIT END OF EXTERIOR OR UNDERGROUND CONDUITS (DUCTS). I CONDUIT END(S) SHALL BE PROVIDED WITH INSULATED THROAT BUSHINGS FOR METALLIC CONDUIT AND PVC BUSHINGS FOR PVC CONDUIT PRIOR TO CABLE INSTALLATION. J EACH CONDUIT ORIGIN SHALL BE LABELED WITH CONDUIT TERMINATION LOCATION. EACH CONDUIT TERMINATION SHALL BE LABELED WITH CONDUIT ORIGIN LOCATION. EACH CONDUIT ORIGIN AND TERMINATION SHALL BE LABELED WITH CONDUIT LENGTH BETWEEN ORIGIN AND TERMINATION LOCATION. K COORDINATE ROUTING OF CONDUITS STUBBED OR ROUTED FROM INTERIOR TO EXTERIOR OF BUILDING ABOVE OR BELOW GRADE WITH OWNER PRIOR TO ROUGH-IN. CAP AND SEAL CONDUITS WATERTIGHT/WEATHERPROOF. PROVIDE FIRE STOPPING AT ORIGIN OR TERMINATION OF SUCH CONDUIT WHEN ORIGIN OR TERMINATION OCCURS AT A FIRE RATED OR EXTERIOR WALL. L INTERIOR CONDUITS SHALL BE ROUTED IN THE MOST DIRECT ROUTE POSSIBLE, PARALLEL AND PERPENDICULAR TO BUILDING LINES, CLOSE TO STRUCTURE, CONCEALED WHEN POSSIBLE. M CONDUITS STUBBED INTO AN ACCESSIBLE CEILING SPACE SHALL TERMINATE A MINIMUM OF 6-INCHES ABOVE ACCESSIBLE SPACE AND SHALL BE ANGLED AT 90 DEGREES AND SHALL TERMINATE WITH ORIENTATION DIRECTED ALONG PATHWAY OF CABLE ROUTING TO INTERMEDIATE OR FINAL DESTINATION. N JUNCTION BOXES SHALL SERVE AS TRANSITION POINT BETW EEN PATHWAYS/RACEWAYS, SHALL BE MINIMUM 4-11/16 INCHES BY 4-11/16 INCHES SQUARE BY 2-1/8 INCHES DEEP. O UNLESS NOTED OTHERWISE, COMMUNICATIONS BACK BOXES SHALL BE MINIMUM 4-11/16 INCHES SQUARE BY 2-1/8 INCHES DEEP WITH SINGLE-GANG MUD RING AND (1) 1-INCH CONDUIT, TYPICAL. ADDITIONAL REQUIREMENTS APPLY TO SUPPORT HIGHER COMMUNICATIONS CABLE COUNTS, AND FOR AV DEVICE AND SECURITY DEVICE LOCATIONS. REFER TO FLOORPLANS, ENLARGED PLANS, AND DETAIL SHEETS FOR ADDITIONAL REQUIREMENTS. P IN ROOMS WITH NON-ACCESSIBLE CEILINGS AND/ OR OPEN STRUCTURE CEILINGS, EXTEND CONTINUOUS CONDUITS AS NECESSARY TO TRANSIT THE CEILING SPACE. CONDUITS SHALL TERMINATE AT ACCESSIBLE LOCATION TO PROVIDE READY ACCESS FOR CABLE INSTALLATION AND MAINTENANCE ACTIVITIES. NOTIFY ARCHITECT AND GC IF CONFLICTING FIELD CONDITIONS ARE DISCOVERED. Q OUTLET BOXES SHALL BE LOCATED WITHIN 3 FEET OF AN ELECTRICAL POWER RECEPTACLE. R PROVIDE PULL BOXES FOR CONDUIT RUNS AT INTERVALS NOT TO EXCEED 100 FEET BETWEEN END POINTS/PULL BOXES. DO NOT INSTALL CONDUITS INTO OR ADJACENT A PULL BOX IN SUCH A WAY AS TO OBSTRUCT THE INSTALLATION OF FUTURE CONDUITS INTO OR OUT OF THE PULL BOX. S PULL BOXES SHALL BE SIZED PER NOTES OR SCHEDULES ON DRAWINGS OR AS INDICATED IN TABLE IN SPECIFICATIONS, ACCESSIBLE, MOUNTED TO STRUCTURE WHEN POSSIBLE, MOUNTED A MAXIMUM OF 4 FEET ABOVE SUSPENDED CEILINGS, HAVE CONDUITS THAT ENTER AND EXIT OUT OF OPPOSITE ENDS (SHALL NOT BE SUBSTITUTED FOR A 90 DEGREE BEND), AND BE LABELED WITH UNIQUE IDENTIFIER. T TELECOMMUNICATIONS BONDING AND GROUNDING PLANNING AND INSTALLATION SHALL BE INSTALLED IN ACCORDANCE WITH NECA/BICSI 607-2011, STANDARD FOR BONDING AND GROUNDING PLANNING AND INSTALLATION METHODS FOR COMMERCIAL BUILDINGS, ANSI/TIA-607 GROUNDING AND BONDING STANDARD, NEC, AND SPECIFICATIONS. ACCEPTED/ACCEPTABLE: WORK OR MATERIALS CONFORMING W ITH THE INTENT OF THE PROJECT, AND IN GENERAL, CONFORMING TO THE PERTINENT INFORMATION IN THE CONSTRUCTION DOCUMENTS. APPROVED/APPROVAL: THE WRITTEN APPROVAL OF THE ENGINEER. AGREEMENT: THE CONTRACTUAL AGREEMENT BETWEEN THE OWNER AND THE CONTRACTOR. THE CONTRACT: THE CONTRACT DOCUMENTS FORM THE CONTRACT. THE CONTRACT REPRESENTS THE ENTIRE AND INTEGRATED AGREEMENT BETWEEN THE OWNER AND THE CONTRACTOR AND SUPERSEDES ANY PRIOR NEGOTIATIONS, REPRESENTATIONS OR AGREEMENTS, EITHER WRITTEN OR ORAL. THE CONTRACT SHALL NOT BE CONSTRUED TO CREATE A CONTRACTUAL RELATIONSHIP OF ANY KIND (1) BETWEEN THE ENGINEER AND THE CONTRACTOR, (2) BETWEEN THE OWNER AND A SUBCONTRACTOR, OR (3) BETWEEN ANY PERSONS OR ENTITIES OTHER THAN THE OWNER AND CONTRACTOR. CONTRACTOR: THE PARTY RESPONSIBLE FOR PROVIDING THE COMMUNICATION SYSTEM(S) AS INDICATED HEREIN. DRAWINGS: THE GRAPHIC AND PICTORIAL PORTIONS OF THE CONTRACT DOCUMENTS, WHEREVER LOCATED AND WHENEVER ISSUED, SHOWING THE DESIGN, LOCATION AND DIMENSIONS OF THE WORK, GENERALLY INCLUDING (BUT NOT LIMITED TO) PLANS, ELEVATIONS, SECTIONS, DETAILS, SCHEDULES AND/OR DIAGRAMS. ENGINEER: THE PARTY RESPONSIBLE FOR PRODUCING THE COMMUNICATION SYSTEM(S) CONSTRUCTION DOCUMENTS. FINAL COMPLETION: THE DATE WHEN THE ENGINEER CONFIRMS IN WRITING THAT THE CONTRACTOR HAS COMPLETED THE WORK IN ACCORDANCE WITH THE CONSTRUCTION DOCUMENTS, INCLUDING COMPLETION OF ALL PUNCH LIST ITEMS, CLEANUP WORK AND DELIVERY OF ALL REQUIRED GUARANTEES, WARRANTIES, LICENSES, RELEASES AND OTHER REQUIRED DELIVERABLES. GOVERNING REQUIREMENTS: COLLECTIVE TERM FOR REGULATIONS, LAWS, ORDINANCES, CODES, RULES, STANDARDS, REQUIREMENTS, GUIDELINES, AND RECOMMENDATIONS THAT GOVERN THE INSTALLATION AND INSPECTION OF THE WORK DEFINED IN THE CONTRACT DOCUMENTS. HANGER/SUPPORT SYSTEM: ALL EQUIPMENT, MATERIALS, AND INCIDENTALS REQUIRED TO SUPPORT THE RACEWAY/PATHWAY AND CABLING SYSTEMS, INCLUDING BUT NOT LIMITED TO METALLIC HANGERS AND SUPPORTS, CONDUIT, CABLE TRAY, CONDUIT, PULL BOXES, DEVICE BOXES, U-CHANNELS, THREADED RODS, CLAMPS, CONCRETE INSERTS, ANCHOR BOLTS, CABLES, BACKING BOARDS, ETC. INSIDE PLANT (ISP): INFRASTRUCTURE WITHIN A BUILDING. OR EQUAL: MATERIALS APPROVED FOR USE BY THE ENGINEER AND WHICH ARE DIMENSIONALLY SUITABLE AND OPERATIONALLY IDENTICAL TO THE SPECIFIED ITEM. OUTSIDE PLANT (OSP): INFRASTRUCTURE EXTERIOR TO A BUILDING. OWNER: THE OWNER AND THE OWNER’S DESIGNATED REPRESENTATIVE(S). THE PROJECT: THE TOTAL CONSTRUCTION OF WHICH THE WORK PERFORMED UNDER THE CONTRACT DOCUMENTS MAY BE THE WHOLE OR A PART, AND WHICH MAY INCLUDE CONSTRUCTION BY THE OWNER AND/OR SEPARATE CONTRACTORS. A B ACCESSIBLE: EASY ACCESS. ACCESS ATTAINED WITHOUT REQUIRING EXTENSIVE REMOVAL OF OTHER MATERIALS TO GAIN ACCESS. C ACCESSIBLE CEILING: ACOUSTICAL TILE HANGING CEILINGS (“HARD-LID” CEILINGS (CONCEALED SPINE OR SHEETROCK/GYPSUM CEILINGS), EVEN WHEN PROVIDED WITH ACCESS PANELS, ARE NOT CONSIDERED AN ACCESSIBLE CEILING.) D E F COMMUNICATIONS (OR TECHNOLOGY) GROUNDING SYSTEM: INCLUDES (BUT IS NOT LIMITED TO) PROVIDING A PERMANENT GROUNDING AND BONDING INFRASTRUCTURE FOR THE COMMUNICATIONS CABLING SYSTEM. G ELECTRICAL FOR COMMUNICATIONS SYSTEMS ALSO REFERRED TO AS COMMUNICATIONS (OR TECHNOLOGY) PATHWAY SYSTEM: INCLUDES (BUT IS NOT LIMITED TO) DEVICE BOXES, PULL BOXES, CONDUIT, CABLE TRAY, DUCT/DUCTBANK, AND OTHER PATHWAY AND RACEWAY COMPONENTS NECESSARY TO PROVIDE PATHWAY FOR, SUPPORT, AND ROUTE COMMUNICATIONS CABLES. H COMMUNICATIONS (OR TECHNOLOGY) SYSTEMS: INCLUDES (BUT IS NOT LIMITED TO) COMMUNICATION CABLING SYSTEM, ELECTRICAL FOR COMMUNICATIONS SYSTEMS (PATHWAY AND GROUNDING), STRUCTURED CABLING SYSTEM (SCS). I CONCEALED: HIDDEN FROM SIGHT IN INTERSTITIAL BUILDING SPACES, CHASES, FURRED SPACES, SHAFTS, CRAWL SPACES, ETC. J CONSTRUCTION DOCUMENTS: COLLECTIVE TERM FOR THE ENTIRE SET OF BOUND OR UNBOUND MATERIAL DESCRIBING THE CONSTRUCTION AND SERVICES REQUIRED, INCLUDING ALL DRAWINGS, SPECIFICATIONS, ADDENDA ISSUED PRIOR TO EXECUTION OF THE CONTRACT, AND MODIFICATIONS ISSUED AFTER EXECUTION OF THE CONTRACT (SUCH AS CHANGE ORDERS, CONSTRUCTION CHANGE DIRECTIVES, SUPPLEMENTAL INSTRUCTIONS, ETC.). K CONTRACT DOCUMENTS: THE AGREEMENT (INCLUDING OTHER DOCUMENTS LISTED IN THE AGREEMENT), CONDITIONS OF THE CONTRACT (GENERAL, SUPPLEMENTARY AND OTHER CONDITIONS), AND THE CONSTRUCTION DOCUMENTS. L M N O P EXPOSED: NOT CONCEALED (SEE ABOVE) AND NOT INSTALLED UNDERGROUND. Q R FURNISH: TO PURCHASE, SUPPLY, AND DELIVER TO THE PROJECT MATERIALS IN NEW AND OPERABLE CONDITION, READY FOR INSTALLATION. S GOVERNING AUTHORITY: ENTITIES OR THEIR REPRESENTATIVES CHARGED WITH FORMATION AND/OR ENFORCEMENT OF GOVERNING REQUIREMENTS, SUCH AS THE AUTHORITY HAVING JURISDICTION (AHJ). T U V W INSTALL: TO PLACE IN FINAL POSITION IN FULLY OPERABLE, TESTED CONDITION. X Y Z AA AB PROVIDE: TO FURNISH AND INSTALL, COMPLETE, TESTED AND READY FOR INTENDED USE. SUBSTANTIAL COMPLETION: THE DATE WHEN ALL WORK REQUIRED BY THE CONSTRUCTION DOCUMENTS SHALL BE COMPLETE (SUBJECT TO THE FINAL PUNCH LIST TO BE PREPARED BY THE ENGINEER) AND ON W HICH THE APPLICABLE JURISDICTIONAL AUTHORITIES HAVE ISSUED A TEMPORARY CERTIFICATION OF OCCUPANCY. SECTION: AN INDIVIDUAL SECTION OF THE SPECIFICATIONS. SHOWN ON DRAWINGS: NOTED, INDICATED, SCHEDULED, DETAILED, OR ANY OTHER WRITTEN REFERENCE MADE ON THE DRAWINGS. SPECIFICATIONS: THE PORTION OF THE CONTRACT DOCUMENTS CONSISTING OF THE WRITTEN REQUIREMENTS FOR MATERIALS, EQUIPMENT, CONSTRUCTION SYSTEMS, STANDARDS AND WORKMANSHIP FOR THE WORK AND PERFORMANCE OF RELATED SERVICES. SPECIFICATION SECTION(S): ONE OR MORE SECTIONS OF THE SPECIFICATIONS. SECTION(S): AN ABBREVIATED FORM OF SPECIFICATION SECTION(S). THE WORK: THE CONSTRUCTION AND SERVICES REQUIRED BY THE CONTRACT DOCUMENTS, WHETHER COMPLETED OR PARTIALLY COMPLETED, AND ALL OTHER LABOR, MATERIALS, EQUIPMENT AND SERVICES PROVIDED OR TO BE PROVIDED BY THE CONTRACTOR TO FULFILL THE CONTRACTOR’S OBLIGATIONS. THE WORK MAY CONSTITUTE THE WHOLE OR A PART OF THE PROJECT. AC ROUGH-IN: PROVIDE THE COMMUNICATIONS PATHWAY SYSTEM, INCLUDING (BUT NOT LIMITED TO) DEVICE BOXES, PULL BOXES, WALL BOXES, FLOOR BOXES, POKE-THROUGH DEVICES, CONDUIT, ENCLOSURES, CABLE TRAY, DUCTS/DUCTBANKS, MAINTENANCE HOLES, HAND HOLES, AND OTHER PATHWAYS AND ITEMS INDICATED (OR AS REQUIRED) FOR ROUTING, SUPPORTING, AND INSTALLING COMMUNICATIONS CABLES, DEVICES, OR EQUIPMENT WHICH SHALL BE PROVIDED BY OTHERS OR PROVIDED UNDER A SUBSEQUENT SET OF CONTRACT DOCUMENTS. AD AE AF AG AH AI AJ GENERAL NOTES GENERAL COMMON WORK / ELECTRICALGENERAL (CONT.) COMMUNICATIONS TERMS AND DEFINITIONS GENERAL © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 0 A M T0.2 COMMUNICATIONS PROJECT NOTES St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE COMPONENT ENTITY NOTES APPLY TO ALL ENTITIES FURNISH INSTALL COMMON WORK CABLE PATHWAY FIRE STOPPING DEVICE EC EC 1,7 CONDUIT SLEEVES EC EC 1 FIRE RATED FLOOR PENETRATION ASSEMBLY EC EC 1,7 HANGER SUPPORTS FOR CABLE SUPPORTS TC TC 2 HANGER SUPPORTS FOR CONDUITS EC EC 1 MISCELLANEOUS FIRE STOPPING MATERIAL GC GC 1,5,7 PENETRATION GC GC 1,5,7 STRAPS/SLINGS TC TC 2 WIDE BASE CABLE SUPPORTS (J-HOOKS)TC TC 2 ELECTRICAL FOR COMMUNICATIONS SYSTEMS BACKBOXES EC EC 1 CONDUIT, FITTINGS, PULL STRINGS EC EC 1 FLOOR BOXES EC EC 1,3 GROUND RISER CONDUCTORS EC EC INNERDUCTS (SUBDUCTS)EC EC 1 JUNCTION BOXES EC EC 1 PULL BOXES EC EC 1 WALL BOXES (AV)EC EC 1 TELECOMMUNICATIONS (COMMUNICATIONS CABLING SYSTEM) BACKBOARDS GC GC 8 BUILDING ENTRANCE PROTECTION TC TC CABLE RUNWAY AND ACCESSORIES TC TC CONNECTORS BACKBONE CABLE TC TC CONNECTORS HORIZONTAL CABLE TC TC EQUIPMENT FRAMES AND ACCESSORIES TC TC EQUIPMENT RACKS AND ACCESSORIES TC TC FACEPLATES TC TC HORIZONTAL CABLING TC TC IDENTIFICATION TC TC OSP BACKBONE CABLING TC TC PATCH PANELS TC TC SPLICE ENCLOSURES TC TC TELECOM ROOM EQUIPMENT GROUNDING AND BONDING TC TC TERMINATION BLOCKS TC TC WIRELESS ACCESS POINTS O O AUDIOVISUAL SYSTEM(S) EQUIPMENT RACKS (STAND-ALONE IN ROOM)O O HANGER WIRE SUPPORTS FOR LOUDSPEAKERS WITHIN LAYING CEILINGS O O INTERFACE PLATES O O PROJECTION SCREEN O O PROJECTORS O O VIDEO DISPLAYS O O STRUCTURAL SUPPORTS FOR AV EQUIPMENT O O 9 SECURITY SYSTEM(S) ACCESS CONTROL SYSTEM 10 ACCESS CONTROL SOFTWARE O O ACCESS CONTROL SYSTEM CABLING (ANALOG)O O ACCESS CONTROL SYSTEM CABLING (CONNECTORIZATION)O O 11 ACCESS CONTROL SYSTEM CABLING (PROVIDE, BUT NO CONNECTORIZATION) O O 11 CARD READER / VERIFICATION DEVICE O O DOOR HARDWARE O O DOOR POSITION SWITCH O O DOOR RELEASES O O HEAD END EQUIPMENT O O NETWORK SERVER FOR ACCESS CONTROL SYSTEM O O NETWORK SWITCHES AND POE O O POWER SUPPLIES O O REQUEST-TO-EXIT O O SURGE PROTECTION DEVICES FOR CARD READERS O O VIDEO SURVEILLANCE SYSTEM 10 CAMERAS AND MOUNT HARDWARE O O NETWORK BASED HORIZONTAL CABLING FOR CAMERAS TC TC NETWORK BASED PATCH CORDS FOR CAMERAS (AT DEVICE)O O NETWORK SWITCHES AND POE O O NETWORK VIDEO RECORDER AND SERVER O O VIDEO MANAGEMENT SOFTWARE O O GENERAL NOTES A.FURNISH AND INSTALL RESPONSIBILITIES ARE ONLY RECOMMENDATIONS AND PROVIDED AS A COURTESY TO CONTRACTOR. B.SOME COMPONENTS AND ASSOCIATED FURNISH AND INSTALL RESPONSIBILITIES MAY NOT BE INDICATED ON THIS MATRIX. C. THE DETAIL FURNISH / INSTALL CALLOUT ANNOTATION PROVIDES SPECIFIC RECOMMENDATIONS THAT SUPERSEDE GENERAL RECOMMENDATIONS FOUND IN THIS TECHNOLOGY RESPONSIBILITY MATRIX. D.EQUIPMENT SCHEDULES MAY CONTAIN ADDITIONAL FURNISH OR INSTALL RESPONSIBILITY RECOMMENDATIONS. THESE SUPERSEDE RECOMMENDATIONS FOUND IN DETAIL ANNOTATIONS AND THIS TECHNOLOGY RESPONSIBILITY MATRIX. E.CONTRACTOR IS RESPONSIBLE FOR FINAL DETERMINATION OF ALL COMPONENTS AND ASSOCIATED FURNISH AND INSTALL RESPONSIBILITIES REQUIRED FOR PROVISION OF COMPLETE COMMUNICATIONS SYSTEMS READY FOR OWNER'S USE. DETERMINATION OF SUCH SHALL OCCUR PRIOR TO BID. F.DETERMINATION AND EXECUTION OF ALL NECESSARY COMPONENTS AND ASSOCIATED FURNISH AND INSTALL RESPONSIBILITIES SHALL CONFORM TO PROJECT SCHEDULE. G. CABLING FOR COMPONENTS SHALL BE PROVIDED BY ENTITY INSTALLING COMPONENT UNLESS OTHERWISE INDICATED. H.EACH TRADE SHALL COORDINATE ROUGH-IN REQUIREMENTS (INCLUDING SLEEVES) WITH ELECTRICAL CONTRACTOR PRIOR TO ROUGH-IN. MATRIX NOTES 1.EACH RESPECTIVE TRADE SHALL COORDINATE EXTENT OF WORK WITH ELECTRICAL CONTRACTOR PRIOR TO ROUGH IN. 2.EACH TRADE SHALL COORDINATE PROVISION OF THIS COMPONENT WITH TELECOMMUNICATIONS CONTRACTOR. TELECOMMUNICATIONS CONTRACTOR SHALL PROVIDE THIS COMPONENT UNLESS DETERMINED OTHERWISE IN CONJUNCTION WITH TELECOMMUNICATIONS CONTRACTOR. 3. COMPONENT SPECIFICATION MAY BE INDICATED ON E-SERIES DOCUMENTS. 4.FURNISHING CONTRACTOR TO PROVIDE ROUGH IN DIMENSIONS / TEMPLATE AND DESIRED LOCATION FOR TABLE TOP INTERFACE. INSTALLING CONTRACTOR SHALL CUT-OUT SURFACE OF TABLE, IDENTIFYING AND COORDINATING ANY POTENTIAL CONFLICTS WITH DESIRED LOCATION PRIOR TO PERFORMING ANY WORK. 5.EACH TRADE SHALL COORDINATE PROVISION OF THIS COMPONENT WITH GENERAL CONTRACTOR. GENERAL CONTRACTOR SHALL PROVIDE THIS COMPONENT UNLESS DETERMINED OTHERWISE IN CONJUNCTION WITH GENERAL CONTRACTOR. 6.ELECTRICAL CONTRACTOR SHALL PROVIDE PADS DURING ROUGH-IN. AFTER ROUGH IN, REQUIRED PADS SHALL BE PROVIDED BY RESPECTIVE TRADES. 7.ELECTRICAL CONTRACTOR SHALL COORDINATE EXTENT OF WORK WITH GENERAL CONTRACTOR. 8.TELECOMMUNICATIONS CONTRACTOR SHALL COORDINATE EXTENT OF WORK WITH GENERAL CONTRACTOR. 9. AUDIOVISUAL CONTRACTOR SHALL COORDINATE EXTENT OF WORK WITH GENERAL CONTRACTOR. 10.THE FURNISHING CONTRACTOR SHALL PROVIDE ALL SYSTEM REQUIREMENTS FOR A FULLY FUNCTIONAL AND OPERATING SYSTEM READY FOR THE OWNERS USE. REQUIREMENTS SHALL INCLUDE BUT NOT BE LIMITED TO SYSTEM COMPONENTS, CABLING, PROGRAMING, INSTALLATION AND COORDINATION UNLESS NOTED OTHERWISE. 11.NOT USED 12.THE OWNER SHALL INSTALL FAR END PATCH CORDS FOR ALL OWNER FURNISHED DEVICES. THE CONTRACTOR SHALL INSTALL FAR END PATCH CORDS FOR ALL CONTRACTOR FURNISHED DEVICES. TRADE SPECIFIC NETWORK BASED SYSTEMS THAT ARE NOT PART OF OWNERS TELECOMMUNICATIONS NETWORK SHALL BE PROVIDED BY RESPECTIVE CONTRACTOR UNLESS OTHERWISE NOTED. EXAMPLES OF SUCH TRADE SPECIFIC SYSTEMS INCLUDE BALUNS AND CONTROL NETWORKS. COMMUNICATIONS RESPONSIBILITY MATRIX © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 0 A M T0.3 COMMUNICATIONS SCHEDULES St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE 27 11 00 - EQUIPMENT ROOM FITTINGS (ER) DESCRIPTION MANUFACTURER/PART NUMBER SPECIAL REQUIREMENTSCPI-- -- -- WALL-MOUNT SWING GATE RACK 11791-xxx -- -- -- CPI 11791-xxx 27 11 19 - TERMINATION EQUIPMENT (TE) DESCRIPTION MANUFACTURER/PART NUMBER SPECIAL REQUIREMENTS Commscope Systimax Corning Legrand/Sup. Essex nCompass Panduit/Gen. Cable "PanGen" HORIZONTAL COPPER PATCH PANEL-CAT 6 (24 PORT, 1U, IDC TERMINATION, U/UTP) GigaSPEED XL PATCHMAX GS3 (760062356) N/A OR-PHD66U24 DP24688TGY TERMINATION BLOCK -110 STYLE 558635-1 -- -- P110B100R2Y 27 15 00 - HORIZONTAL CABLING (HC) DESCRIPTION MANUFACTURER/PART NUMBER SPECIAL REQUIREMENTS Commscope Systimax -- Berk-Tek/Leviton Technologies Panduit/Gen. Cable "PanGen" HORIZONTAL COPPER CABLE (ENHANCED CAT6, U/UTP) GigaSPEED XL 2071E --LANmark-1000, p/o CX6150 System GenSPEED 6000 27 15 43 - FACEPLATES AND CONNECTORS (FC) DESCRIPTION MANUFACTURER/PART NUMBER Commscope Systimax Corning Legrand/Sup. Essex nCompass Panduit/Gen. Cable "PanGen"SPECIAL REQUIREMENTS PLENUM SURFACE MOUNT BOX (BISCUIT) M202 Plenum SMB-262 -- Provide For Wireless Access (WAP) And Security Camera (SC) locations. PLASTIC FACEPLATE M-Series -- OR-403HDJ14 CFPLxyyY COPPER CONNECTOR (CAT6, U/UTP)GigaSPEED XL MGS400 -- OR-TJ600-xx CJ688TGxx 27 16 19 - PATCH CORDS (PC) DESCRIPTION MANUFACTURER/PART NUMBER SPECIAL REQUIREMENTS Commscope Systimax Corning Legrand/Sup. Essex nCompass Panduit/Gen. Cable "PanGen" COPPER PATCH CORD (CAT6) - BOOTED CPC33xx-xx -- EZRD6xxQxx-06 PVUTPSPCxxBBUY SM FIBER PATCH CORD (DUPLEX LC) FDWLxLxxx 040402Rxxxxxxxx -- NKFP92ERLLSMxxx COORDINATE CONNECTION TYPE WITH OWNER 27 04 06 - HANGERS AND SUPPORTS (JS) MANUFACTURER / PART NUMBER DESCRIPTION ERICO ARLINGTON HUBBELL CPI SPECIAL REQUIREMENTS HANGER/SUPPORT SYSTEM See Special Rqmt See Special Rqmt -- See Special Rqmt B-Line, Erico, Kindorf, Unistrut or approved equal WIDE BASE CABLE SUPPORTS (J-HOOKS) CADDY CableCat -- -- See Erico -- 27 05 26 - GROUNDING AND BONDING (GB) MANUFACTURER / PART NUMBER DESCRIPTION CPI ERICO COOPER B-LINE --SPECIAL REQUIREMENTS TELECOMMUNICATIONS MAIN GROUNDING BUSBAR (TMGB) 20" X 4" X 1/4" (NOMINAL)40153-020 TMGB-A20L27PT SBTMGB20 -- -- ALL ACCESSORIES AND RELATED EQUIPMENT REQUIRED FOR A COMPLETE COMMUNICATIONS GROUNDING AND BONDING SYSTEM. See Special Rqmt See Special Rqmt See Special Rqmt -- Product shall be from the same manufacturer as the provided Grounding Busbars (CPI, Erico or Cooper B-Line). 27 05 33 - CONDUIT AND BOXES (CB) MANUFACTURER / PART NUMBER DESCRIPTION WIREMOLD HUBBELL CHIEF --SPECIAL REQUIREMENTS FLOOR BOX (6-GANG) Evolution EFB6S-xx -- -- -- Provide the On-Grade (-OG) version for Slab-On-Grade installations; the Fire Classified (-FC) version for all Fire-Rated Slabs and the standard version for all other installations. DISPLAY WALL BOX -- -- PAC526FC -- REFER TO THE AV CONDUIT RISER DIAGRAMS AND THE AV ROUGH-IN DETAILS. CONFIRM COLOR WITH ARCHITECT BEFORE ORDERING. 27 05 45 - MAINTENANCE AND HAND HOLES (MH) MANUFACTURER / PART NUMBER DESCRIPTION Oldcastle Precast Other -- -- SPECIAL REQUIREMENTS PULLBOX 3060-30 -- -- -- -- EQUIPMENT SCHEDULE - COMMUNICATIONSEQUIPMENT SCHEDULE - COMMON WORK / ELECTRICAL © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 0 A M T0.4 COMMUNICATIONS SCHEDULES St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 1 A M T0.5 COMMUNICATIONS SPECIFICATIONS St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 2 A M T0.6 COMMUNICATIONS SPECIFICATIONS St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 3 A M T0.7 COMMUNICATIONS SPECIFICATIONS St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 3 A M T0.8 COMMUNICATIONS SPECIFICATIONS St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER REVISION DATE F.E.C. F. E . C . F.E. F.E. COORDINATE SITE PLAN HAND HOLE WITH OTHER TRADES AND INCOMING SERVICES COORDINATE IN BASEMENT TO ROUTE INTO FLOOR BELOW WALL RACK O S P O S P (2) 4-INCH CONDUITS © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 5 A M T1.1 COMMUNICATIONS SITE PLAN St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER WORK NOTES N 0 8'8' 4' 1/8" = 1'-0" 1 COMMUNICATIONS SITE PLAN REVISION DATE F.E.C. F. E . C . F.E. A REFER TO PROJECT NOTES ON THE BEGINNING SHEETS OF T-SERIES FOR ADDITIONAL INFORMATION RELATED TO THIS SHEET. B REFER TO PROJECT SPECIFICATIONS ON BEGINNING SHEETS OF T-SERIES FOR ADDITIONAL INFORMATION RELATED TO THIS SHEET. C ALL CAMERA AND ACCESS CONTROL LOCATIONS SHOWN ARE APPROXIMATE AND SHALL BE COORDINATED WITH ARCHITECT AND OWNER PRIOR TO INSTALL. D FOR ALL CEILING MOUNTED EQUIPMENT, TO INCLUDE BUT NOT BE LIMITED TO WAPS AND CAMERAS, CONTRACTOR SHALL COORDINATE MOUNTING LOCATION WITH OWNER, ARCHITECT AND OTHER TRADES PRIOR TO INSTALL. 1 2 3 4 ABC DE LIQUOR STORAGE 004 BEER COOLER 003 CONDENSER UNITS B07A ELECTRICAL B07 MECH ROOM B06 SHOP/BAR B03 ELEV. B10 COOLER 005 FREEZER 006 OFFICE 001 TI STORAGE 010 WOMEN'S RESTROOM B05 MEN'S RESTROOM B04 JANITOR B01A B.O.H. B02A THEATER B02 PLATFORM B02B LOBBY B01 3 WALL MOUNT SWING GATE IT RACK LOCATION WAP 2 WAP 2 WAP 2 WAP 2 WAP 2 WAP 2 08A T31 3 FIRST FLOOR PLAN 100' -0" BASEMENT FLOOR PLAN 87' -0" TMGB CONDUIT WALL MOUNT RACK GENERAL NOTES © Copyright BCER Engineering ALL DRAWINGS, SPECIFICATIONS, AND OTHER WORK PRODUCT PREPARED BY BCER ENGINEERING FOR THIS PROJECT ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF BCER ENGINEERING. BCER ENGINEERING SHALL RETAIN ALL COMMON LAW, STATUTORY AND OTHER RESERVED RIGHTS, INCLUDING THE COPYRIGHT THERETO. Date Drawn By Checked By: Project Number Sheet Name Copyright: ALL DRAWN AND WRITTEN INFORMATION APPEARING HEREIN SHALL NOT BE DUPLICATED, DISCLOSED OR OTHERWISE USED WITHOUT THE WRITTEN CONSENT OF MOA ARCHITECTURE 1/ 1 5 / 2 0 2 1 1 0 : 1 8 : 2 6 A M T2.1 COMMUNICATIONS BASEMENT FLOOR PLAN St a n e l y H o t e l P o s t R e s t a u r a n t T I BCER 1/15/2021 20175.00 33 3 E W o n d e r v i e w A v e E s t e s P a r k , C O 8 0 5 1 7 CONTRUCTION DOCUMENTS BCER WORK NOTES T31 ACCESS CONTROL AND SECURITY SYSTEMS ARE OWNER FURNISHED AND INSTALLED. ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL PATHWAY AND INFRASTRUCTURE. COORDINATE WITH OWNER AND ARCHITECT FOR DEVICE COORDINATION AND FINAL LOCATIONS. N 0 4'4' 2' 1/4" = 1'-0" 1 COMMUNICATIONS BASEMENT PLAN 0 4'4' 2' 1/4" = 1'-0" 2 WALL MOUNT SWING GATE IT RACK WALL ELEVATTION REVISION DATE