HomeMy WebLinkAboutPLANS PV System 133 Stanley Circle 2023-04-13 4/11/23 Lux Engineering 14 E 1500 N American Fork, Utah luke@luxengineers.com Tuesday, April 11, 2023 Pro Bid Energy 3975 E 56th Ave Unit B1 Commerce City, CO As requested, I have assessed the roof for the residence at 133 Stanley Circle Drive, Estes Park, CO for the installation of solar panels. Based on information provided from a site visit by Pro Bid Energy, the existing roof framing in the locations of the solar arrays is pre-manufactured trusses at 24” on center that appear to be in good working order. The existing roofing material is asphalt shingles. The additional load from the 22 solar panels will be affecting a roof area of 1300 square feet. In the analysis of the pre-manufactured trusses with the additional solar weight on the roof, the following loads apply: Dead Load 19,500 lbs at 15 psf Snow Load 91,000 lbs at 70 psf Solar Panels 1,155 lbs at 3 psf Wind Load (Vult) 175 mph (see attached calculations) Per 2018 International Existing Building Code (IEBC) Section 806.2, “Any existing gravity load-carrying structural element for which an alteration causes an increase in design dead, live, or snow load, including snow drift effects, of more than 5 percent shall be replaced or altered as needed to carry the gravity loads required by the International Building Code.” The extra load of the solar panels on the roof is 1.05%, which is under the required 5%. Therefore, the existing structure is adequate and may remain unaltered. Alteration or replacement is not required according to the 2018 IEBC. It is my recommendation that the existing trusses will sufficiently and safely support the extra weight of the solar arrays. The 5/16” lag screws should be staggered to evenly distribute the loads over the affected roof framing area and must penetrate the truss top chords with a minimum embedment depth of 2”. Warm regards, Luke Rowley, PE REVIEWED BY SAFEBUILT 04/13/2023 Wind & Gravity Calculations # of Panels: 22 Area per Panel: 17.5 sq.ft. Total Area of Panels: 385 sq.ft. Total Area of Roof: 1300 sq.ft. Roof Dead Load: 15 psf Roof Snow Load: 70 psf (non-reducible) Solar Panel Load: 3 psf Total Dead Load: 19,500 lbs Total Snow Load: 91,000 lbs Total Solar Panel Load: 1,155 lbs Weight Increase: 1.05 % OK V: 175 Mph (3-sec. gust) Kz: 0.85 ASCE 7 Table 27.3-1 Kzt: 1 ASCE 7 Sec. 26.8.2 Kd: 0.85 ASCE 7 Table 26.6-1 Pressure: 56.6 psf Roof Pitch: 22 degrees Minimum Total Attachments: 53 Trib. Area Per Attachment: 7.3 sq.ft. Horizontal Projection Area: 6.8 sq.ft. Vertical Projection Area: 2.7 sq.ft. Shear Load on Screw: 197 lbs Shear Capacity of Screw: 150 lbs (5/16" Lag, NDS Table 12J) OK Pullout Load on Screw: 385 lbs Pullout Capacity of Screw: 442 lbs (5/16" Lag, NDS Table 12.2A) OK REVIEWED BY SAFEBUILT 04/13/2023 GENERAL NOTES 1.1.1 PROJECT NOTES: 1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY HAVING JURISDICTION’S (AHJ) APPLICABLE CODES. 1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM INSPECTED PRIOR TO PARALLEL OPERATION 1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATED WITH THE MICROINVERTER IN ACCORDANCE WITH NEC 690.41(B) 1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4: PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519 COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY 1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED ACCORDING TO NEC 690.7. 1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC 110.3]. 1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ. 1.2.1 SCOPE OF WORK: 1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN, SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT. 1.3.1 WORK INCLUDES: 1.3.2 PV ROOF ATTACHMENTS - UNIRAC FLASHLOC COMP 1.3.3 PV RACKING SYSTEM INSTALLATION - UNIRAC STANDARD 1.3.4 PV MODULE AND INVERTER INSTALLATION - HANWHA Q-CELLS Q.PEAK DUO BLK ML-G10+400 / ENPHASE IQ7PLUS-72-2-US 1.3.5 PV EQUIPMENT GROUNDING 1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX 1.3.7 PV LOAD CENTERS (IF INCLUDED) 1.3.8 PV METERING/MONITORING (IF INCLUDED) 1.3.9 PV DISCONNECTS 1.3.10 PV GROUNDING ELECTRODE & BONDING TO (E) GEC 1.3.11 PV FINAL COMMISSIONING 1.3.12 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV 1.3.13 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE *NEC2020M SCOPE OF WORK SYSTEM SIZE: STC: 23 X 400W = 9.200KW PTC: 23 X 378.4W = 8.703KW (23) HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+400 (23) ENPHASE IQ7PLUS-72-2-US ATTACHMENT TYPE: UNIRAC FLASHLOC COMP MSP UPGRADE: NO OWNER NAME:KINGSWOOD PROJECT MANAGER NAME:DANNY GLENNON PHONE: 303-304-6588 CONTRACTOR NAME:VENTARA DBA PRO BID ENERGY PHONE: AUTHORITIES HAVING JURISDICTION BUILDING: TOWN OF ESTES PARK ZONING: TOWN OF ESTES PARK UTILITY: TOWN OF ESTES PARK DESIGN SPECIFICATIONS OCCUPANCY: II CONSTRUCTION: RESIDENTIAL GROUND SNOW LOAD: 70 PSF WIND EXPOSURE: B WIND SPEED: 175 MPH APPLICABLE CODES & STANDARDS BUILDING: IBC 2018, IRC 2018 ELECTRICAL: NEC 2020 FIRE : IFC 2018 PROJECT INFORMATION ARRAY 1: WATTS: 9.200 KW TILT: 25 DEGREES AZIMUTH: 240 DEGREES PV WATTS KWH'S/YR: _______KWH/S. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 ASSESSOR'S #: 12530236004 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 T-001.00 COVER PAGE (SHEET 1) 01 AERIAL PHOTO NOT TO SCALE N EW S 02 PLAT MAP NOT TO SCALE SHEET LIST TABLE SHEET NUMBER SHEET TITLE T-001 COVER PAGE G-001 NOTES A-101 SITE PLAN A-102 ELECTRICAL PLAN A-103 SOLAR ATTACHMENT PLAN E-601 LINE DIAGRAM E-602 DESIGN TABLES E-603 PLACARDS S-501 ASSEMBLY DETAILS R-001 RESOURCE DOCUMENT R-002 RESOURCE DOCUMENT R-003 RESOURCE DOCUMENT R-004 RESOURCE DOCUMENT R-005 RESOURCE DOCUMENT R-006 RESOURCE DOCUMENT R-007 RESOURSE DOCUMENT WE S T O N L N S T A N L E Y C I R D R 04/11/2023 SAFEbuilt APPROVED Subject to inspection and compliance to all relevant Adopted Building and Municipal codes. Changes in Plans MUST be approved. D.GRAHAM 04/13/2023 I-CODES 2015 PRINT PLANS IN COLOR AND HAVE FOR INSPECTOR AT TIME OF INSPECTION INSTALLATION INSTRUCTIONS AND MANUALS MUST BE ON JOB FOR THE INSPECTOR AT THE TIME OF INSPECTION FOR ALL EQUIPMENT. 2.1.1 SITE NOTES: 2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS. 2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES. 2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING ROOF VENTS. 2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26. 2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE. 2.2.1 EQUIPMENT LOCATIONS: 2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26. 2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1). 2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC 690.34. 2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN SIGHT OF THE AC SERVICING DISCONNECT. 2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO NEC APPLICABLE CODES. 2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN APPROPRIATE. 2.3.1 STRUCTURAL NOTES: 2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES, AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS. 2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS. 2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR. 2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE SPECIFIED BY THE RACKING MANUFACTURER. 2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST THE ROOF FRAMING MEMBERS. 2.4.1 WIRING & CONDUIT NOTES: 2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING. 2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7. 2.4.4 VOLTAGE DROP LIMITED TO 1.5%. 2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING SYSTEMS SHALL BE LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS. 2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS: PHASE A OR L1- BLACK PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION NEUTRAL- WHITE OR GRAY IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED ORANGE [NEC 110.15]. 2.5.1 GROUNDING NOTES: 2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE. 2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE 250.122. 2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED GROUNDED IN ACCORD WITH 250.134 AND 250.136(A). 2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45 AND MICROINVERTER MANUFACTURERS' INSTRUCTIONS. 2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED, MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS. 2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE. 2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119] 2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH 250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ. 2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) THROUGH (3) TO REDUCE FIRE HAZARDS 2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES: 2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE SIDE” (TYPICALLY THE UPPER TERMINALS). 2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A VISIBLE-BREAK SWITCH 2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH 690.12(A) THROUGH (D). 2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240. 2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN ACCORDANCE WITH NEC 110.3(B). 2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO NEC 690.11 AND UL1699B. 2.7.1 INTERCONNECTION NOTES: 2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH NEC 705.12 2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120 PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)]. 2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3). 2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2) 2.7.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCE CONDUCTORS IN ACCORDANCE WITH NEC 230.42 2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM ADDITIONAL FASTENING [NEC 705.12 (E)]. *NEC2020M *NEC2020M B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 G-001.00 NOTES (SHEET 2) REVIEWED BY SAFEBUILT 04/13/2023 GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE PROPERTY LINE N EW S 01/16" = 1'-0" SITE PLAN01 8' 16' B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 A-101.00 (SHEET 3) AREA OF WORK ENTRANCE SITE PLAN S T A N L E Y C I R D R 34'-0" (23) ENPHASE IQ7PLUS-72-2-US VISIBLE-OPEN TYPE, LOCKABLE AND READILY ACCESSIBLE AC DISCONNECT UTILITY METER AC COMBINER BOX MAIN ELECTRICAL PANEL WE S T O N L N 38'-1" 28'-5" 80'-0" 04/11/2023 REVIEWED BY SAFEBUILT 04/13/2023 MODULE: HANWHA Q-CELLS Q.PEAK DUO BLK ML-G10+400 400WATTS 41.4" 74.0" GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE FIRE CLEARANCE MODULE STRINGING MODULE STRINGING B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 NE W S A-102.00 (SHEET 4) 01/8"=1'-0" ELECTRICAL PLAN014' 8' ELECTRICAL PLAN A EXTERIOR PV EQUIPMENT (N) (1) JUNCTION BOX (N) (1) VISIBLE-OPEN TYPE, LOCKABLE AND READILY ACCESSIBLE AC DISCONNECT (N) (1) AC COMBINER BOX (E) (1) UTILITY METER (E) (1) MAIN ELECTRICAL PANEL ARRAY 1 - 9.200 kW [x23] (N) MODULES TILT: 25 DEGREES ROOF PITCH: 6:12 AZIMUTH: 240 DEGREES B B B B B B A A A A A AAAABBB A A A 18" FIRE ACCESS PATH 18" FIRE ACCESS PATH B B B 3' FIRE ACCESS PATH REVIEWED BY SAFEBUILT 04/13/2023 GENERAL NOTES 1. FIELD VERIFY ALL MEASUREMENTS 2. ITEMS BELOW MAY NOT BE ON THIS PAGE ROOF TRUSSES MODULE: HANWHA Q-CELLS Q.PEAK DUO BLK ML-G10+400 400WATTS 41.4" 74.0" B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 NE W S 01/8" = 1'-0" SOLAR ATTACHMENT PLAN014' 8'A-103.00 (SHEET 5) SOLAR ATTACHMENT PLAN ROOF MATERIAL IS ASPHALT SHINGLE FLUSH MOUNT MODULES ATTACHED TO ROOF SURFACE (SEE SHEET S-501 FOR MOUNTING DETAILS) 44'-1" 04/11/2023 REVIEWED BY SAFEBUILT 04/13/2023 A MODULE STRINGING SYSTEM EQUIPPED WITH RAPID SHUTDOWN DISCONNECT PER NEC 690.12. SYSTEM COMPLIANT WITH NEC 690.43 G 3SW1A 125A AС COMBINER BOX ENPHASE IQ COMBINER 4 (X-IQ-AM1-240-4) 120/240V, 1Ø, 3W MAX. CONTINUOUS CURRENT: 65A MAX. OCPD: 90A JUNCTION BOX IN BRANCH 12 RED BLACK GL1NL2 ENPHASE ENVOY COMMUNICATIONS GATEWAY G CB1 20A CB3 15A AC DISCONNECT 60A EATON DG222URB 2POLE, 60A, 240V AC MAX BREAKER SIZE: (200 A x 1.2) - 200 A = 40 A EQUIPMENT LEFT LINE IS (N) NEW EQUIPMENT RIGHT LINE IS (E) EXISTING UNLESS OTHERWISE NOTED. TO UTILITY GRID (UG) L1 L2 N (E) MAIN 200A (E) MAIN ELECTRICAL PANEL 240/120 V 1Ø, 3W MAIN BUSS: 200A L1 L2 35A/2P CB4 1 (23) ENPHASE IQ7PLUS-72-2-US (23) HANWHA Q-CELLS Q.PEAK DUO BLK ML-G10+400 2 (E) GROUNDING ELECTRODE GROUND ROD N G (E) UTILITY METER TO (E) LOADS B IN BRANCH 11 RED BLACK CB2 20A B MODULE STRINGING AC DISCONNECT VISIBLE-OPEN TYPE, LOCKABLE AND READILY ACCESSIBLE PROJECT DESCRIPTION TO INCLUDE: SYSTEM DC RATING: 9.200KW INSTALL TYPE: ROOF BATTERY: NO AHJ: TOWN OF ESTES PARK UTILITY: TOWN OF ESTES PARK PROJECT SPECIFICATIONS TO INCUDE: SYSTEM AC RATING: 6.670KW MAX AC CURRENT: 27.83A MAX AC POWER: 6.670 KVA NOMINAL OPERATING AC VOLTAGE: 240V ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR. FACTOR CONDUIT FILL FACTOR CONT. CURRENT MAX. CURRENT (125%)BASE AMP.DERATED AMP.TERM. TEMP. RATING AMP. @ TERMINAL 11 10 AWG THWN-2, COPPER IN CONDUIT 4 20A 10 AWG THWN-2, COPPER 0.91 (35.3 °C)0.8 14.52A 18.15A 40A 29.12A 75°C 35A 21 8 AWG THWN-2, COPPER IN CONDUIT 2 N/A 8 AWG THWN-2, COPPER 0.91 (35.3 °C)1 27.83A 34.79A 55A 50.05A 75°C 50A 3 1 8 AWG THWN-2, COPPER IN CONDUIT 2 35A 8 AWG THWN-2, COPPER 0.91 (35.3 °C)1 27.83A 34.79A 55A 50.05A 75°C 50A E-601.00 (SHEET 6) B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 LINE DIAGRAM ELECTRICAL INSPECTIONS AND PLAN REVIEWS (IF REQUIRED) PER THE STATE OF COLORADO. THIS ELECTRICAL INSTALLATION MUST CONFORM TO THE 2020 NEC BILL OF MATERIALS CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION MODULE HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+PM1-23 23 PIECES 1 HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+ 400W 0 INVERTER ENPHASE IQ7PLUS-72-2-US I1-23 23 PIECES 1 ENPHASE IQ7PLUS-72-2-US 290W INVERTER DISCONNECT EATON DG222URB SW1 1 PIECE 1 EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENT MISC ELECTRICAL EQUIPMENT GEN-CABLE-CLIP HDWR26-141 115 PIECES 1 GENERIC CABLE CLIP AC COMBINER PANEL ENPHASE-IQ4-PANEL EP1 1 PIECE 1 ENPHASE IQ COMBINER 4 (X-IQ-AM1-240-4) WIRING ENPHASE Q-12-20-200 EN1-23 23 PIECES 1 ENPHASE ENGAGE (TM) TRUNK CABLE WIRING ENPHASE Q-TERM-10 EN24 1 BUNDLE 10 ENPHASE ENGAGE (TM) BRANCH TERMINATOR WIRING ENPHASE Q-SEAL-10 EN25 1 BUNDLE 10 ENPHASE ENGAGE (TM) WATERTIGHT SEALING CAP WIRING GEN-10-AWG-THWN-2-CU-RD WR1 90 FEET 1 10 AWG THWN-2, COPPER, RED (LINE 1) WIRING GEN-10-AWG-THWN-2-CU-BLK WR1 90 FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2) WIRING GEN-10-AWG-THWN-2-CU-GR WR1 45 FEET 1 10 AWG THWN-2, COPPER, GREEN (GROUND) WIRING GEN-8-AWG-THWN-2-CU-RD WR2-3 20 FEET 1 8 AWG THWN-2, COPPER, RED (LINE 1) WIRING GEN-8-AWG-THWN-2-CU-BLK WR2-3 20 FEET 1 8 AWG THWN-2, COPPER, BLACK (LINE 2) WIRING GEN-8-AWG-THWN-2-CU-WH WR2-3 20 FEET 1 8 AWG THWN-2, COPPER, WHITE (NEUTRAL) WIRING GEN-8-AWG-THWN-2-CU-GR WR2-3 20 FEET 1 8 AWG THWN-2, COPPER, GREEN (GROUND) WIREWAY ENPHASE ET-SPLK-05 EN5 1 BUNDLE 5 ENPHASE ENGAGE (TM) ENGAGE COUPLER OCPD GENERIC MANUFACTURER GEN-CB-20A-240VAC CB1-2 2 PIECES 1 CIRCUIT BREAKER, 20A, 240VAC OCPD GENERIC MANUFACTURER GEN-CB-15A-240VAC CB3 1 PIECE 1 CIRCUIT BREAKER, 15A, 240VAC OCPD GENERIC MANUFACTURER GEN-CB-35A-240VAC CB4 1 PIECE 1 CIRCUIT BREAKER, 35A, 240VAC TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1 1 PIECE 1 TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS DISCONNECTS INVERTERS OCPDS MODULES ASHRAE EXTREME LOW -27°C (-16.6°F), SOURCE: FORT COLLINS (AWOS) (40.45°; -105°) ASHRAE 2% HIGH 35.3°C (95.5°F), SOURCE: FORT COLLINS (AWOS) (40.45°; -105°) REF.QTY.RATED CURRENT MAX VOLTAGE CB1-2 2 20A 240VAC CB3 1 10A 240VAC CB4 1 35A 240VAC REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE SW1 1 EATON DG222URB OR EQUIV.60A 240VAC REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING PM1-23 23 HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+400W 378.4W 11.14A 10.77A 45.3V 37.13V -0.122V/°C (-0.27%/°C)20A REF.QTY.MAKE AND MODEL AC VOLTAGE GROUND OCPD RATING RATED POWER MAX OUTPUT CURRENT MAX INPUT CURRENT MAX INPUT VOLTAGE CEC WEIGHTED EFFICIENCY I1-23 23 ENPHASE IQ7PLUS-72-2-US 240V FLOATING 20A 290W 1.21A 15A 60V 97.0% SYSTEM SUMMARY BRANCH #1 BRANCH #2 INVERTERS PER BRANCH 12 11 MAX AC CURRENT 14.52A 13.31A MAX AC OUTPUT POWER 3,480W 3,190W ARRAY STC POWER 9,200W ARRAY PTC POWER 8,703W MAX AC CURRENT 27.83A MAX AC POWER 6,670W DERATED (CEC) AC POWER 6,670W E-602.00 (SHEET 7) B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 DESIGN TABLES REVIEWED BY SAFEBUILT 04/13/2023 MAIN DISTRIBUTION UTILITY DISCONNECT FRONT BACK !CAUTION! POWER TO THIS BUILDING IS ALSO SUPPLIED FROM ROOF MOUNTED SOLAR ARRAYS WITH SAFETY DISCONNECTS AS SHOWN: E-603.00 (SHEET 8) B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 N E W S PLACARDS LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] ELECTRICAL SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION WARNING LABEL 1 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT (2" X 4"). [NEC 690.13]. POWER SOURCE OUTPUT CONNECTION DO NOT RELOCATE THIS OVERCURRENT DEVICE WARNING LABEL 2 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE (2" X 4"). [NEC 705.12(B)(2)(3)(B)]. LABEL 3 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS (4" X 3"). [NEC 690.54] LABEL 4 AT EACH AC DISCONNECTING MEANS (4" X 1"). [NEC 690.13(B)]. INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED SE SIDE OF THE HOUSE DIRECTORY PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8"). [NEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] PHOTOVOLTAIC POWER SOURCE LABEL 9 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS (5 3/4" X 1 1/8"). [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY SOLAR ELECTRIC PV PANELS LABEL 6 AT RAPID SHUTDOWN SYSTEM (3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)]. WARNING DUAL POWER SUPPLY SOURCES: UTILITY GRID AND PV SOLAR ELECTRIC SYSTEM LABEL 7 AT POINT OF INTERCONNECTION (2 3/4" X 1 5/8"). [NEC 705.12(B)(3)] WARNING SOLAR ELECTRIC CIRCUIT BREAKER IS BACKFED LABEL 8 AT POINT OF INTERCONNECTION (2" X 1"). [NEC 705.12(B)(3)] CAUTION MULTIPLE SOURCES OF POWER LABEL 10 AT UTILITY METER (5 3/4" X 1 1/8") [NEC 690.56(B)] RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM LABEL 5 AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2"). [NEC 690.56(C)(3)]. AC DISCONNECT PHOTOVOLTAIC SYSTEM POWER SOURCE RATED AC OUTPUT CURRENT NOMINAL OPERATING AC VOLTAGE AMPS VOLTS PHOTOVOLTAIC SYSTEM DISCONNECT 27.83 240 PV ARRAY ELECTRICAL INSPECTIONS AND PLAN REVIEWS (IF REQUIRED) PER THE STATE OF COLORADO. SHEET KEYNOTES 1. ROOF MATERIAL: ASPHALT SHINGLE 2. ROOF STRUCTURE: TRUSS 3. ATTACHMENT TYPE: UNIRAC FLASHLOC COMP 4. MODULE MANUFACTURER: HANWHA Q-CELLS 5. MODULE MODEL: Q.PEAK DUO BLK ML-G10+ 400 6. MODULE LENGTH: 74" 7. MODULE WIDTH: 41.1" 8. MODULE WEIGHT: 48.5 LBS 9. SEE SHEET A-103 FOR DIMENSION(S) 10. MIN. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE 11. TRUSS SPACING: 24 IN. O.C. 12. TRUSS SIZE: 2Х4 IN. 13. LAG BOLT DIAMETER: 5/16" 14. LAG BOLT EMBEDMENT: 3-1/2" 15. TOTAL # OF ATTACHMENTS: 51 16. TOTAL AREA: 485.78 SQ. FT. 17. TOTAL WEIGHT: 1288.93 LBS. 18. WEIGHT PER ATTACHMENT: 25.27 LBS. 19. DISTRIBUTED LOAD: 2.65 PSF 20. MAX. HORIZONTAL STANDOFF: 48 IN. 21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULE MANUFACTURER'S INSTRUCTIONS 22. STANDOFF STAGGERING: YES 23. RAIL MANUFACTURER (OR EQUIV.): UNIRAC 24. RAIL MODEL (OR EQUIVALENT): STANDARD 25. RAIL WEIGHT: 0.728 PLF. 26. MAX. TRUSS SPAN: N/A. 27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX. S-501 D5 20 11 121413151822 RO O F S L O P E 910 10 6 21 7 S-501 D4 3 1 54 252423 8 27 1 2 1. FIELD VERIFY ALL MEASUREMENTS GENERAL NOTES SS LAG BOLT W/ SS EPDM BONDED WASHER SS SERRATED T-BOLT SS SERRATED FLANGE NUT FLASHLOC BASE MILL OR DARK B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 S-501.00 ASSEMBLY DETAILS (SHEET 9) D4 DETAIL (TRANSVERSE) NOT TO SCALE D5 DETAIL (LONGITUDINAL) NOT TO SCALE D1 RACKING DETAIL (TRANSVERSE) NOT TO SCALE D3 RACKING DETAIL (TOP) NOT TO SCALE D2 RACKING DETAIL (LONGITUDINAL) NOT TO SCALE 04/11/2023 REVIEWED BY SAFEBUILT 04/13/2023 PROVIDE ALL RACKING INSTALLATION INSTRUCTIONS AND DOCUMENTATION TO THE INSPECTOR AT THE TIME OF INSPECTION B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 R-001.00 (SHEET 10) RESOURCE DOCUMENT REVIEWED BY SAFEBUILT 04/13/2023 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 R-002.00 (SHEET 11) RESOURCE DOCUMENT REVIEWED BY SAFEBUILT 04/13/2023 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 R-003.00 (SHEET 12) RESOURCE DOCUMENT REVIEWED BY SAFEBUILT 04/13/2023 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 R-004.00 (SHEET 13) RESOURCE DOCUMENT REVIEWED BY SAFEBUILT 04/13/2023 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 R-005.00 (SHEET 14) RESOURCE DOCUMENT REVIEWED BY SAFEBUILT 04/13/2023 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 (SHEET 15) RESOURCE DOCUMENT R-006.00 REVIEWED BY SAFEBUILT 04/13/2023 B F A D E 2 3 UNAUTHORIZED USE OF THIS DRAWING SET WITHOUT WRITTEN PERMISSION FROM CONTRACTOR IS IN VIOLATION OF U.S. COPYRIGHT LAWS AND WILL BE SUBJECT TO CIVIL DAMAGES AND PROSECUTIONS. NEW PV SYSTEM: 9.200 kWp DC / 6.670 kWp AC ENGINEER OF RECORD 02.17.2023 DESIGN BY:O.S. M.M. KINGSWOOD RESIDENCE 133 STANLEY CIRCLE DRIVE, ESTES PARK, CO 80517 APN: 2530236004 PAPER SIZE: 11" x 17" (ANSI B) A C D E G H B C F G H 1 4 5 6 CONTRACTOR VENTARA DBA PRO BID ENERGY PHONE: LIC. NO.: DATE: CHECKED BY: REVISIONS HIC. NO.: ELE. NO.: ADDRESS:3975 E. 56TH AVE UNIT B1, COMMERCE CITY, CO 80022 EC.0101800 (SHEET 16) RESOURCE DOCUMENT R-007.00 REVIEWED BY SAFEBUILT 04/13/2023