HomeMy WebLinkAboutPLANS PV System 133 Stanley Circle 2023-04-13
4/11/23
Lux Engineering
14 E 1500 N
American Fork, Utah
luke@luxengineers.com
Tuesday, April 11, 2023
Pro Bid Energy
3975 E 56th Ave Unit B1
Commerce City, CO
As requested, I have assessed the roof for the residence at 133 Stanley Circle Drive, Estes Park, CO for the
installation of solar panels. Based on information provided from a site visit by Pro Bid Energy, the existing
roof framing in the locations of the solar arrays is pre-manufactured trusses at 24” on center that appear
to be in good working order. The existing roofing material is asphalt shingles. The additional load from the
22 solar panels will be affecting a roof area of 1300 square feet. In the analysis of the pre-manufactured
trusses with the additional solar weight on the roof, the following loads apply:
Dead Load 19,500 lbs at 15 psf
Snow Load 91,000 lbs at 70 psf
Solar Panels 1,155 lbs at 3 psf
Wind Load (Vult) 175 mph (see attached calculations)
Per 2018 International Existing Building Code (IEBC) Section 806.2, “Any existing gravity load-carrying
structural element for which an alteration causes an increase in design dead, live, or snow load, including
snow drift effects, of more than 5 percent shall be replaced or altered as needed to carry the gravity loads
required by the International Building Code.” The extra load of the solar panels on the roof is 1.05%, which
is under the required 5%. Therefore, the existing structure is adequate and may remain unaltered.
Alteration or replacement is not required according to the 2018 IEBC.
It is my recommendation that the existing trusses will sufficiently and safely support the extra weight of
the solar arrays. The 5/16” lag screws should be staggered to evenly distribute the loads over the affected
roof framing area and must penetrate the truss top chords with a minimum embedment depth of 2”.
Warm regards,
Luke Rowley, PE
REVIEWED
BY SAFEBUILT
04/13/2023
Wind & Gravity Calculations
# of Panels: 22
Area per Panel: 17.5 sq.ft.
Total Area of Panels: 385 sq.ft.
Total Area of Roof: 1300 sq.ft.
Roof Dead Load: 15 psf
Roof Snow Load: 70 psf (non-reducible)
Solar Panel Load: 3 psf
Total Dead Load: 19,500 lbs
Total Snow Load: 91,000 lbs
Total Solar Panel Load: 1,155 lbs
Weight Increase: 1.05 %
OK
V: 175 Mph (3-sec. gust)
Kz: 0.85 ASCE 7 Table 27.3-1
Kzt: 1 ASCE 7 Sec. 26.8.2
Kd: 0.85 ASCE 7 Table 26.6-1
Pressure: 56.6 psf
Roof Pitch: 22 degrees
Minimum Total Attachments: 53
Trib. Area Per Attachment: 7.3 sq.ft.
Horizontal Projection Area: 6.8 sq.ft.
Vertical Projection Area: 2.7 sq.ft.
Shear Load on Screw: 197 lbs
Shear Capacity of Screw: 150 lbs (5/16" Lag, NDS Table 12J)
OK
Pullout Load on Screw: 385 lbs
Pullout Capacity of Screw: 442 lbs (5/16" Lag, NDS Table 12.2A)
OK
REVIEWED
BY SAFEBUILT
04/13/2023
GENERAL NOTES
1.1.1 PROJECT NOTES:
1.1.2 THIS PHOTOVOLTAIC (PV) SYSTEM SHALL COMPLY WITH THE NATIONAL ELECTRIC
CODE (NEC) ARTICLE 690, ALL MANUFACTURERS’S LISTING AND INSTALLATION
INSTRUCTIONS, AND THE RELEVANT CODES AS SPECIFIED BY THE AUTHORITY
HAVING JURISDICTION’S (AHJ) APPLICABLE CODES.
1.1.3 THE UTILITY INTERCONNECTION APPLICATION MUST BE APPROVED AND PV SYSTEM
INSPECTED PRIOR TO PARALLEL OPERATION
1.1.4 GROUND FAULT DETECTION AND INTERRUPTION (GFDI) DEVICE IS INTEGRATED
WITH THE MICROINVERTER IN ACCORDANCE WITH NEC 690.41(B)
1.1.5 ALL PV SYSTEM COMPONENTS; MODULES, UTILITY-INTERACTIVE INVERTERS, AND
SOURCE CIRCUIT COMBINER BOXES ARE IDENTIFIED AND LISTED FOR USE IN
PHOTOVOLTAIC SYSTEMS AS REQUIRED BY NEC 690.4:
PV MODULES: UL1703, IEC61730, AND IEC61215, AND NFPA 70 CLASS C FIRE
INVERTERS: UL 1741 CERTIFIED, IEEE 1547, 929, 519
COMBINER BOX(ES): UL 1703 OR UL 1741 ACCESSORY
1.1.6 MAX DC VOLTAGE CALCULATED USING MANUFACTURER PROVIDED TEMP
COEFFICIENT FOR VOC. IF UNAVAILABLE, MAX DC VOLTAGE CALCULATED
ACCORDING TO NEC 690.7.
1.1.7 ALL INVERTERS, PHOTOVOLTAIC MODULES, PHOTOVOLTAIC PANELS, AND SOURCE
CIRCUIT COMBINERS INTENDED FOR USE IN A PHOTOVOLTAIC POWER SYSTEM WILL
BE IDENTIFIED AND LISTED FOR THE APPLICATION PER 690.4 (D). SHALL BE
INSTALLED ACCORDING TO ANY INSTRUCTIONS FROM LISTING OR LABELING [NEC
110.3].
1.1.8 ALL SIGNAGE TO BE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE. IF
EXPOSED TO SUNLIGHT, IT SHALL BE UV RESISTANT. ALL PLAQUES AND SIGNAGE
WILL BE INSTALLED AS REQUIRED BY THE NEC AND AHJ.
1.2.1 SCOPE OF WORK:
1.2.2 PRIME CONTRACTOR IS RESPONSIBLE FOR THE DESIGN AND SPECIFICATIONS OF
THE GRID-TIED PHOTOVOLTAIC SYSTEM RETROFIT. PRIME CONTRACTOR WILL BE
RESPONSIBLE FOR COLLECTING EXISTING ONSITE REQUIREMENTS TO DESIGN,
SPECIFY, AND INSTALL THE EXTERIOR ROOF-MOUNTED PORTION OF THE
PHOTOVOLTAIC SYSTEMS DETAILED IN THIS DOCUMENT.
1.3.1 WORK INCLUDES:
1.3.2 PV ROOF ATTACHMENTS - UNIRAC FLASHLOC COMP
1.3.3 PV RACKING SYSTEM INSTALLATION - UNIRAC STANDARD
1.3.4 PV MODULE AND INVERTER INSTALLATION - HANWHA Q-CELLS Q.PEAK DUO BLK
ML-G10+400 / ENPHASE IQ7PLUS-72-2-US
1.3.5 PV EQUIPMENT GROUNDING
1.3.6 PV SYSTEM WIRING TO A ROOF-MOUNTED JUNCTION BOX
1.3.7 PV LOAD CENTERS (IF INCLUDED)
1.3.8 PV METERING/MONITORING (IF INCLUDED)
1.3.9 PV DISCONNECTS
1.3.10 PV GROUNDING ELECTRODE & BONDING TO (E) GEC
1.3.11 PV FINAL COMMISSIONING
1.3.12 (E) ELECTRICAL EQUIPMENT RETROFIT FOR PV
1.3.13 SIGNAGE PLACED IN ACCORDANCE WITH LOCAL BUILDING CODE
*NEC2020M
SCOPE OF WORK
SYSTEM SIZE: STC: 23 X 400W = 9.200KW
PTC: 23 X 378.4W = 8.703KW
(23) HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+400
(23) ENPHASE IQ7PLUS-72-2-US
ATTACHMENT TYPE: UNIRAC FLASHLOC COMP
MSP UPGRADE: NO
OWNER
NAME:KINGSWOOD
PROJECT MANAGER
NAME:DANNY GLENNON
PHONE: 303-304-6588
CONTRACTOR
NAME:VENTARA DBA PRO BID ENERGY
PHONE:
AUTHORITIES HAVING JURISDICTION
BUILDING: TOWN OF ESTES PARK
ZONING: TOWN OF ESTES PARK
UTILITY: TOWN OF ESTES PARK
DESIGN SPECIFICATIONS
OCCUPANCY: II
CONSTRUCTION: RESIDENTIAL
GROUND SNOW LOAD: 70 PSF
WIND EXPOSURE: B
WIND SPEED: 175 MPH
APPLICABLE CODES & STANDARDS
BUILDING: IBC 2018, IRC 2018
ELECTRICAL: NEC 2020
FIRE : IFC 2018
PROJECT INFORMATION
ARRAY 1:
WATTS: 9.200 KW
TILT: 25 DEGREES
AZIMUTH: 240 DEGREES
PV WATTS KWH'S/YR: _______KWH/S.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
KINGSWOOD RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
ASSESSOR'S #: 12530236004
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
T-001.00
COVER PAGE
(SHEET 1)
01 AERIAL PHOTO
NOT TO SCALE
N
EW
S
02 PLAT MAP
NOT TO SCALE
SHEET LIST TABLE
SHEET NUMBER SHEET TITLE
T-001 COVER PAGE
G-001 NOTES
A-101 SITE PLAN
A-102 ELECTRICAL PLAN
A-103 SOLAR ATTACHMENT PLAN
E-601 LINE DIAGRAM
E-602 DESIGN TABLES
E-603 PLACARDS
S-501 ASSEMBLY DETAILS
R-001 RESOURCE DOCUMENT
R-002 RESOURCE DOCUMENT
R-003 RESOURCE DOCUMENT
R-004 RESOURCE DOCUMENT
R-005 RESOURCE DOCUMENT
R-006 RESOURCE DOCUMENT
R-007 RESOURSE DOCUMENT
WE
S
T
O
N
L
N
S
T
A
N
L
E
Y
C
I
R
D
R
04/11/2023
SAFEbuilt
APPROVED
Subject to inspection and
compliance to all relevant
Adopted Building and Municipal
codes.
Changes in Plans MUST be
approved.
D.GRAHAM
04/13/2023
I-CODES 2015
PRINT PLANS IN COLOR AND HAVE FOR
INSPECTOR AT TIME OF INSPECTION
INSTALLATION
INSTRUCTIONS AND
MANUALS MUST BE
ON JOB FOR THE
INSPECTOR AT THE
TIME OF
INSPECTION FOR
ALL EQUIPMENT.
2.1.1 SITE NOTES:
2.1.2 A LADDER WILL BE IN PLACE FOR INSPECTION IN COMPLIANCE WITH OSHA REGULATIONS.
2.1.3 THE PV MODULES ARE CONSIDERED NON-COMBUSTIBLE AND THIS SYSTEM IS A UTILITY
INTERACTIVE SYSTEM WITH NO STORAGE BATTERIES.
2.1.4 THE SOLAR PV INSTALLATION WILL NOT OBSTRUCT ANY PLUMBING, MECHANICAL, OR BUILDING
ROOF VENTS.
2.1.5 PROPER ACCESS AND WORKING CLEARANCE AROUND EXISTING AND PROPOSED ELECTRICAL
EQUIPMENT WILL BE PROVIDED AS PER SECTION NEC 110.26.
2.1.6 ROOF COVERINGS SHALL BE DESIGNED, INSTALLED, AND MAINTAINED IN ACCORDANCE WITH
THIS CODE AND THE APPROVED MANUFACTURER'S INSTRUCTIONS SUCH THAT THE ROOF
COVERING SERVES TO PROTECT THE BUILDING OR STRUCTURE.
2.2.1 EQUIPMENT LOCATIONS:
2.2.2 ALL EQUIPMENT SHALL MEET MINIMUM SETBACKS AS REQUIRED BY NEC 110.26.
2.2.3 WIRING SYSTEMS INSTALLED IN DIRECT SUNLIGHT MUST BE RATED FOR EXPECTED OPERATING
TEMPERATURE AS SPECIFIED BY NEC 690.31 (A),(C) AND NEC TABLE 310.15 (B)(1).
2.2.4 JUNCTION AND PULL BOXES PERMITTED INSTALLED UNDER PV MODULES ACCORDING TO NEC
690.34.
2.2.5 ADDITIONAL AC DISCONNECT(S) SHALL BE PROVIDED WHERE THE INVERTER IS NOT WITHIN
SIGHT OF THE AC SERVICING DISCONNECT.
2.2.6 ALL EQUIPMENT SHALL BE INSTALLED ACCESSIBLE TO QUALIFIED PERSONNEL ACCORDING TO
NEC APPLICABLE CODES.
2.2.7 ALL COMPONENTS ARE LISTED FOR THEIR PURPOSE AND RATED FOR OUTDOOR USAGE WHEN
APPROPRIATE.
2.3.1 STRUCTURAL NOTES:
2.3.2 RACKING SYSTEM & PV ARRAY WILL BE INSTALLED ACCORDING TO CODE-COMPLIANT
INSTALLATION MANUAL. TOP CLAMPS REQUIRE A DESIGNATED SPACE BETWEEN MODULES,
AND RAILS MUST ALSO EXTEND A MINIMUM DISTANCE BEYOND EITHER EDGE OF THE
ARRAY/SUBARRAY, ACCORDING TO RAIL MANUFACTURER’S INSTRUCTIONS.
2.3.3 JUNCTION BOX WILL BE INSTALLED PER MANUFACTURERS' SPECIFICATIONS. IF
ROOF-PENETRATING TYPE, IT SHALL BE FLASHED & SEALED PER LOCAL REQUIREMENTS.
2.3.4 ROOFTOP PENETRATIONS FOR PV RACEWAY WILL BE COMPLETED AND SEALED W/ APPROVED
CHEMICAL SEALANT PER CODE BY A LICENSED CONTRACTOR.
2.3.5 ALL PV RELATED ROOF ATTACHMENTS TO BE SPACED NO GREATER THAN THE SPAN DISTANCE
SPECIFIED BY THE RACKING MANUFACTURER.
2.3.6 WHEN POSSIBLE, ALL PV RELATED RACKING ATTACHMENTS WILL BE STAGGERED AMONGST
THE ROOF FRAMING MEMBERS.
2.4.1 WIRING & CONDUIT NOTES:
2.4.2 ALL CONDUIT AND WIRE WILL BE LISTED AND APPROVED FOR THEIR PURPOSE. CONDUIT AND
WIRE SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT
TO LIMIT UP-SIZING.
2.4.3 CONDUCTORS SIZED ACCORDING TO NEC 690.8, NEC 690.7.
2.4.4 VOLTAGE DROP LIMITED TO 1.5%.
2.4.5 DC WIRING LIMITED TO MODULE FOOTPRINT. MICROINVERTER WIRING SYSTEMS SHALL BE
LOCATED AND SECURED UNDER THE ARRAY W/ SUITABLE WIRING CLIPS.
2.4.6 AC CONDUCTORS COLORED OR MARKED AS FOLLOWS:
PHASE A OR L1- BLACK
PHASE B OR L2- RED, OR OTHER CONVENTION IF THREE PHASE
PHASE C OR L3- BLUE, YELLOW, ORANGE**, OR OTHER CONVENTION
NEUTRAL- WHITE OR GRAY
IN 4-WIRE DELTA CONNECTED SYSTEMS THE PHASE WITH HIGHER VOLTAGE TO BE MARKED
ORANGE [NEC 110.15].
2.5.1 GROUNDING NOTES:
2.5.2 GROUNDING SYSTEM COMPONENTS SHALL BE LISTED FOR THEIR PURPOSE, AND GROUNDING
DEVICES EXPOSED TO THE ELEMENTS SHALL BE RATED FOR SUCH USE.
2.5.3 PV EQUIPMENT SHALL BE GROUNDED ACCORDING TO NEC 690.43 AND MINIMUM NEC TABLE
250.122.
2.5.4 METAL PARTS OF MODULE FRAMES, MODULE RACKING, AND ENCLOSURES CONSIDERED
GROUNDED IN ACCORD WITH 250.134 AND 250.136(A).
2.5.5 EQUIPMENT GROUNDING CONDUCTORS SHALL BE SIZED ACCORDING TO NEC 690.45 AND
MICROINVERTER MANUFACTURERS' INSTRUCTIONS.
2.5.6 EACH MODULE WILL BE GROUNDED USING WEEB GROUNDING CLIPS AS SHOWN IN
MANUFACTURER DOCUMENTATION AND APPROVED BY THE AHJ. IF WEEBS ARE NOT USED,
MODULE GROUNDING LUGS MUST BE INSTALLED AT THE SPECIFIED GROUNDING LUG HOLES
PER THE MANUFACTURERS' INSTALLATION REQUIREMENTS.
2.5.7 THE GROUNDING CONNECTION TO A MODULE SHALL BE ARRANGED SUCH THAT THE REMOVAL
OF A MODULE DOES NOT INTERRUPT A GROUNDING CONDUCTOR TO ANOTHER MODULE.
2.5.8 GROUNDING AND BONDING CONDUCTORS, IF INSULATED, SHALL BE COLORED GREEN OR
MARKED GREEN IF #4 AWG OR LARGER [NEC 250.119]
2.5.9 THE GROUNDING ELECTRODE SYSTEM COMPLIES WITH NEC 690.47 AND NEC 250.50 THROUGH
250.106. IF EXISTING SYSTEM IS INACCESSIBLE, OR INADEQUATE, A GROUNDING ELECTRODE
SYSTEM PROVIDED ACCORDING TO NEC 250, NEC 690.47 AND AHJ.
2.5.10 GROUND-FAULT DETECTION SHALL COMPLY WITH NEC 690.41(B)(1) THROUGH (3) TO REDUCE
FIRE HAZARDS
2.6.1 DISCONNECTION AND OVER-CURRENT PROTECTION NOTES:
2.6.2 DISCONNECTING SWITCHES SHALL BE WIRED SUCH THAT WHEN THE SWITCH IS OPENED THE
CONDUCTORS REMAINING ENERGIZED ARE CONNECTED TO THE TERMINALS MARKED “LINE
SIDE” (TYPICALLY THE UPPER TERMINALS).
2.6.3 DISCONNECTS TO BE ACCESSIBLE TO QUALIFIED UTILITY PERSONNEL, BE LOCKABLE, AND BE A
VISIBLE-BREAK SWITCH
2.6.4 PV SYSTEM CIRCUITS INSTALLED ON OR IN BUILDINGS SHALL INCLUDE A RAPID SHUTDOWN
FUNCTION TO REDUCE SHOCK HAZARD FOR EMERGENCY RESPONDERS IN ACCORDANCE WITH
690.12(A) THROUGH (D).
2.6.5 ALL OCPD RATINGS AND TYPES SPECIFIED ACCORDING TO NEC 690.8, 690.9, AND 240.
2.6.6 MICROINVERTER BRANCHES CONNECTED TO A SINGLE BREAKER OR GROUPED FUSES IN
ACCORDANCE WITH NEC 110.3(B).
2.6.7 IF REQUIRED BY AHJ, SYSTEM WILL INCLUDE ARC-FAULT CIRCUIT PROTECTION ACCORDING TO
NEC 690.11 AND UL1699B.
2.7.1 INTERCONNECTION NOTES:
2.7.2 LOAD-SIDE INTERCONNECTION SHALL BE IN ACCORDANCE WITH NEC 705.12
2.7.3 THE SUM OF 125 PERCENT OF THE POWER SOURCE(S) OUTPUT CIRCUIT CURRENT AND THE
RATING OF THE OVERCURRENT DEVICE PROTECTING THE BUSBAR SHALL NOT EXCEED 120
PERCENT OF THE AMPACITY OF THE BUSBAR, PV DEDICATED BACKFEED BREAKERS MUST BE
LOCATED OPPOSITE END OF THE BUS FROM THE UTILITY SOURCE OCPD [NEC 705.12(B)(3)(2)].
2.7.4 AT MULTIPLE ELECTRIC POWER SOURCES OUTPUT COMBINER PANEL, TOTAL RATING OF ALL
OVERCURRENT DEVICES SHALL NOT EXCEED AMPACITY OF BUSBAR. HOWEVER, THE
COMBINED OVERCURRENT DEVICE MAY BE EXCLUDED ACCORDING TO NEC 705.12 (B)(3)(3).
2.7.5 FEEDER TAP INTERCONNECTION (LOAD SIDE) ACCORDING TO NEC 705.12 (B)(1) AND (2)
2.7.6 SUPPLY SIDE TAP INTERCONNECTION ACCORDING TO NEC 705.11 WITH SERVICE ENTRANCE
CONDUCTORS IN ACCORDANCE WITH NEC 230.42
2.7.7 BACKFEEDING BREAKER FOR ELECTRIC POWER SOURCES OUTPUT IS EXEMPT FROM
ADDITIONAL FASTENING [NEC 705.12 (E)].
*NEC2020M
*NEC2020M
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
G-001.00
NOTES
(SHEET 2)
REVIEWED
BY SAFEBUILT
04/13/2023
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
PROPERTY LINE
N
EW
S
01/16" = 1'-0"
SITE PLAN01 8' 16'
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
A-101.00
(SHEET 3)
AREA OF WORK
ENTRANCE
SITE PLAN
S
T
A
N
L
E
Y
C
I
R
D
R
34'-0"
(23) ENPHASE IQ7PLUS-72-2-US
VISIBLE-OPEN TYPE,
LOCKABLE AND READILY
ACCESSIBLE AC
DISCONNECT
UTILITY METER
AC COMBINER BOX
MAIN ELECTRICAL PANEL
WE
S
T
O
N
L
N
38'-1"
28'-5"
80'-0"
04/11/2023
REVIEWED
BY SAFEBUILT
04/13/2023
MODULE:
HANWHA Q-CELLS
Q.PEAK DUO BLK ML-G10+400
400WATTS
41.4"
74.0"
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
FIRE CLEARANCE
MODULE STRINGING
MODULE STRINGING
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
NE
W
S
A-102.00
(SHEET 4)
01/8"=1'-0"
ELECTRICAL PLAN014' 8'
ELECTRICAL PLAN
A
EXTERIOR PV EQUIPMENT
(N) (1) JUNCTION BOX
(N) (1) VISIBLE-OPEN TYPE,
LOCKABLE AND READILY
ACCESSIBLE AC DISCONNECT
(N) (1) AC COMBINER BOX
(E) (1) UTILITY METER
(E) (1) MAIN ELECTRICAL PANEL
ARRAY 1 - 9.200 kW
[x23] (N) MODULES
TILT: 25 DEGREES
ROOF PITCH: 6:12
AZIMUTH: 240 DEGREES
B
B B B B B A A A A A
AAAABBB
A A A
18" FIRE ACCESS PATH
18" FIRE ACCESS PATH
B
B
B
3' FIRE ACCESS PATH
REVIEWED
BY SAFEBUILT
04/13/2023
GENERAL NOTES
1. FIELD VERIFY ALL MEASUREMENTS
2. ITEMS BELOW MAY NOT BE ON THIS PAGE
ROOF TRUSSES
MODULE:
HANWHA Q-CELLS
Q.PEAK DUO BLK ML-G10+400
400WATTS
41.4"
74.0"
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
NE
W
S
01/8" = 1'-0"
SOLAR ATTACHMENT PLAN014' 8'A-103.00
(SHEET 5)
SOLAR ATTACHMENT PLAN
ROOF MATERIAL IS ASPHALT SHINGLE
FLUSH MOUNT MODULES ATTACHED TO
ROOF SURFACE (SEE SHEET S-501 FOR
MOUNTING DETAILS)
44'-1"
04/11/2023
REVIEWED
BY SAFEBUILT
04/13/2023
A MODULE STRINGING
SYSTEM EQUIPPED WITH RAPID
SHUTDOWN DISCONNECT PER NEC 690.12.
SYSTEM COMPLIANT WITH NEC 690.43
G
3SW1A
125A AС COMBINER BOX
ENPHASE IQ COMBINER 4
(X-IQ-AM1-240-4)
120/240V, 1Ø, 3W
MAX. CONTINUOUS CURRENT: 65A
MAX. OCPD: 90A
JUNCTION BOX
IN BRANCH
12 RED
BLACK
GL1NL2
ENPHASE ENVOY
COMMUNICATIONS
GATEWAY
G
CB1
20A
CB3
15A
AC DISCONNECT 60A
EATON DG222URB
2POLE, 60A, 240V AC
MAX BREAKER SIZE:
(200 A x 1.2) - 200 A = 40 A
EQUIPMENT LEFT
LINE IS (N) NEW
EQUIPMENT RIGHT
LINE IS (E) EXISTING
UNLESS OTHERWISE NOTED.
TO UTILITY
GRID (UG)
L1
L2
N
(E)
MAIN
200A
(E) MAIN ELECTRICAL PANEL
240/120 V 1Ø, 3W
MAIN BUSS: 200A
L1
L2
35A/2P
CB4
1
(23) ENPHASE
IQ7PLUS-72-2-US
(23) HANWHA Q-CELLS
Q.PEAK DUO BLK ML-G10+400
2
(E) GROUNDING
ELECTRODE
GROUND
ROD
N G
(E)
UTILITY
METER
TO (E)
LOADS
B
IN BRANCH
11 RED
BLACK
CB2
20A
B MODULE STRINGING
AC DISCONNECT
VISIBLE-OPEN TYPE,
LOCKABLE AND READILY
ACCESSIBLE
PROJECT DESCRIPTION TO INCLUDE:
SYSTEM DC RATING: 9.200KW
INSTALL TYPE: ROOF
BATTERY: NO
AHJ: TOWN OF ESTES PARK
UTILITY: TOWN OF ESTES PARK
PROJECT SPECIFICATIONS TO INCUDE:
SYSTEM AC RATING: 6.670KW
MAX AC CURRENT: 27.83A
MAX AC POWER: 6.670 KVA
NOMINAL OPERATING AC VOLTAGE: 240V
ID TYPICAL CONDUCTOR CONDUIT CURRENT-CARRYING
CONDUCTORS IN CONDUIT OCPD EGC TEMP. CORR.
FACTOR
CONDUIT FILL
FACTOR
CONT.
CURRENT
MAX. CURRENT
(125%)BASE AMP.DERATED
AMP.TERM. TEMP. RATING AMP. @ TERMINAL
11 10 AWG THWN-2, COPPER IN CONDUIT 4 20A 10 AWG THWN-2, COPPER 0.91 (35.3 °C)0.8 14.52A 18.15A 40A 29.12A 75°C 35A
21 8 AWG THWN-2, COPPER IN CONDUIT 2 N/A 8 AWG THWN-2, COPPER 0.91 (35.3 °C)1 27.83A 34.79A 55A 50.05A 75°C 50A
3 1 8 AWG THWN-2, COPPER IN CONDUIT 2 35A 8 AWG THWN-2, COPPER 0.91 (35.3 °C)1 27.83A 34.79A 55A 50.05A 75°C 50A
E-601.00
(SHEET 6)
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
LINE DIAGRAM
ELECTRICAL INSPECTIONS AND PLAN REVIEWS (IF REQUIRED)
PER THE STATE OF COLORADO.
THIS ELECTRICAL INSTALLATION MUST CONFORM TO THE
2020 NEC
BILL OF MATERIALS
CATEGORY MAKE MODEL NUMBER REF QTY UNIT QTY/UNIT DESCRIPTION
MODULE HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+PM1-23 23 PIECES 1 HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+ 400W 0
INVERTER ENPHASE IQ7PLUS-72-2-US I1-23 23 PIECES 1 ENPHASE IQ7PLUS-72-2-US 290W INVERTER
DISCONNECT EATON DG222URB SW1 1 PIECE 1
EATON DG222URB, NON FUSED, 2-POLE, 60A, 240VAC OR EQUIVALENT
MISC ELECTRICAL EQUIPMENT GEN-CABLE-CLIP HDWR26-141 115 PIECES 1 GENERIC CABLE CLIP
AC COMBINER PANEL ENPHASE-IQ4-PANEL EP1 1 PIECE 1
ENPHASE IQ COMBINER 4 (X-IQ-AM1-240-4)
WIRING ENPHASE Q-12-20-200 EN1-23 23 PIECES 1
ENPHASE ENGAGE (TM) TRUNK CABLE
WIRING ENPHASE Q-TERM-10 EN24 1 BUNDLE 10 ENPHASE ENGAGE (TM) BRANCH TERMINATOR
WIRING ENPHASE Q-SEAL-10 EN25 1 BUNDLE 10
ENPHASE ENGAGE (TM) WATERTIGHT SEALING CAP
WIRING GEN-10-AWG-THWN-2-CU-RD WR1 90 FEET 1
10 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-10-AWG-THWN-2-CU-BLK WR1 90 FEET 1 10 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-10-AWG-THWN-2-CU-GR WR1 45 FEET 1
10 AWG THWN-2, COPPER, GREEN (GROUND)
WIRING GEN-8-AWG-THWN-2-CU-RD WR2-3 20 FEET 1
8 AWG THWN-2, COPPER, RED (LINE 1)
WIRING GEN-8-AWG-THWN-2-CU-BLK WR2-3 20 FEET 1
8 AWG THWN-2, COPPER, BLACK (LINE 2)
WIRING GEN-8-AWG-THWN-2-CU-WH WR2-3 20 FEET 1
8 AWG THWN-2, COPPER, WHITE (NEUTRAL)
WIRING GEN-8-AWG-THWN-2-CU-GR WR2-3 20 FEET 1 8 AWG THWN-2, COPPER, GREEN (GROUND)
WIREWAY ENPHASE ET-SPLK-05 EN5 1 BUNDLE 5
ENPHASE ENGAGE (TM) ENGAGE COUPLER
OCPD GENERIC MANUFACTURER GEN-CB-20A-240VAC CB1-2 2 PIECES 1
CIRCUIT BREAKER, 20A, 240VAC
OCPD GENERIC MANUFACTURER GEN-CB-15A-240VAC CB3 1 PIECE 1 CIRCUIT BREAKER, 15A, 240VAC
OCPD GENERIC MANUFACTURER GEN-CB-35A-240VAC CB4 1 PIECE 1
CIRCUIT BREAKER, 35A, 240VAC
TRANSITION BOX GENERIC MANUFACTURER GEN-AWB-TB-4-4X JB1 1 PIECE 1
TRANSITION/PASS-THROUGH BOX, WITH 4 TERMINAL BLOCKS
DISCONNECTS
INVERTERS
OCPDS
MODULES
ASHRAE EXTREME LOW -27°C (-16.6°F), SOURCE: FORT COLLINS (AWOS) (40.45°; -105°)
ASHRAE 2% HIGH 35.3°C (95.5°F), SOURCE: FORT COLLINS (AWOS) (40.45°; -105°)
REF.QTY.RATED CURRENT MAX VOLTAGE
CB1-2 2 20A 240VAC
CB3 1 10A 240VAC
CB4 1 35A 240VAC
REF.QTY.MAKE AND MODEL RATED CURRENT MAX RATED VOLTAGE
SW1 1 EATON DG222URB OR EQUIV.60A 240VAC
REF.QTY.MAKE AND MODEL PMAX PTC ISC IMP VOC VMP TEMP. COEFF. OF VOC FUSE RATING
PM1-23 23 HANWHA Q CELLS Q.PEAK DUO BLK ML-G10+400W 378.4W 11.14A 10.77A 45.3V 37.13V
-0.122V/°C (-0.27%/°C)20A
REF.QTY.MAKE AND MODEL AC
VOLTAGE GROUND OCPD
RATING
RATED
POWER
MAX OUTPUT
CURRENT
MAX INPUT
CURRENT
MAX INPUT
VOLTAGE
CEC WEIGHTED
EFFICIENCY
I1-23 23 ENPHASE IQ7PLUS-72-2-US 240V FLOATING 20A 290W 1.21A 15A 60V 97.0%
SYSTEM SUMMARY
BRANCH #1 BRANCH #2
INVERTERS PER BRANCH 12 11
MAX AC CURRENT 14.52A 13.31A
MAX AC OUTPUT POWER 3,480W 3,190W
ARRAY STC POWER 9,200W
ARRAY PTC POWER 8,703W
MAX AC CURRENT 27.83A
MAX AC POWER 6,670W
DERATED (CEC) AC POWER 6,670W
E-602.00
(SHEET 7)
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
DESIGN TABLES
REVIEWED
BY SAFEBUILT
04/13/2023
MAIN DISTRIBUTION
UTILITY DISCONNECT
FRONT BACK
!CAUTION!
POWER TO THIS BUILDING IS ALSO SUPPLIED
FROM ROOF MOUNTED SOLAR ARRAYS WITH
SAFETY DISCONNECTS AS SHOWN:
E-603.00
(SHEET 8)
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
N
E
W
S
PLACARDS
LABELING NOTES
1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE,
INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535
1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING
JURISDICTION.
1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED.
1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED
BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE
YELLOW BACKGROUND. [ANSI Z535]
ELECTRICAL SHOCK HAZARD
TERMINALS ON THE LINE AND
LOAD SIDES MAY BE ENERGIZED
IN THE OPEN POSITION
WARNING
LABEL 1
AT EACH DISCONNECTING MEANS FOR
PHOTOVOLTAIC EQUIPMENT (2" X 4").
[NEC 690.13].
POWER SOURCE
OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
WARNING
LABEL 2
AT POINT OF INTERCONNECTION
OVERCURRENT DEVICE (2" X 4").
[NEC 705.12(B)(2)(3)(B)].
LABEL 3
AT POINT OF INTERCONNECTION, MARKED
AT DISCONNECTING MEANS (4" X 3").
[NEC 690.54]
LABEL 4
AT EACH AC DISCONNECTING MEANS
(4" X 1").
[NEC 690.13(B)].
INTERACTIVE PHOTOVOLTAIC SYSTEM CONNECTED
PHOTOVOLTAIC SYSTEM DISCONNECT LOCATED
SE SIDE OF THE HOUSE
DIRECTORY
PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE
DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IF NOT IN THE SAME LOCATION (5 3/4" X 1 1/8").
[NEC 690.56(B)]
WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A
DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV
SYSTEM DISCONNECTING MEANS.
PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN
BATHROOMS
[NEC 690.4(D),(E)]
PHOTOVOLTAIC POWER SOURCE
LABEL 9
AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING
METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE
SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS,
OR FLOORS (5 3/4" X 1 1/8").
[NEC 690.31(G)]
LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND;
REFLECTIVE
[IFC 605.11.1.1]
SOLAR PV SYSTEM
EQUIPPED WITH
RAPID SHUTDOWN
TURN RAPID SHUTDOWN SWITCH TO
THE "OFF" POSITION TO SHUT DOWN
PV SYSTEM AND REDUCE SHOCK
HAZARD IN ARRAY
SOLAR ELECTRIC
PV PANELS
LABEL 6
AT RAPID SHUTDOWN SYSTEM
(3 3/4" X 5 1/4"). [NEC 690.56(C)(1)(A)].
WARNING
DUAL POWER SUPPLY
SOURCES: UTILITY GRID
AND PV SOLAR
ELECTRIC SYSTEM
LABEL 7
AT POINT OF INTERCONNECTION
(2 3/4" X 1 5/8").
[NEC 705.12(B)(3)]
WARNING
SOLAR ELECTRIC
CIRCUIT BREAKER
IS BACKFED
LABEL 8
AT POINT OF INTERCONNECTION
(2" X 1").
[NEC 705.12(B)(3)]
CAUTION
MULTIPLE SOURCES OF POWER
LABEL 10
AT UTILITY METER (5 3/4" X 1 1/8")
[NEC 690.56(B)]
RAPID SHUTDOWN
SWITCH FOR
SOLAR PV SYSTEM
LABEL 5
AT RAPID SHUTDOWN DISCONNECT SWITCH (5 1/4" X 2").
[NEC 690.56(C)(3)].
AC DISCONNECT
PHOTOVOLTAIC SYSTEM
POWER SOURCE
RATED AC
OUTPUT CURRENT
NOMINAL OPERATING
AC VOLTAGE
AMPS
VOLTS
PHOTOVOLTAIC SYSTEM
DISCONNECT
27.83
240
PV ARRAY
ELECTRICAL INSPECTIONS AND PLAN REVIEWS (IF REQUIRED)
PER THE STATE OF COLORADO.
SHEET KEYNOTES
1. ROOF MATERIAL: ASPHALT SHINGLE
2. ROOF STRUCTURE: TRUSS
3. ATTACHMENT TYPE: UNIRAC FLASHLOC COMP
4. MODULE MANUFACTURER: HANWHA Q-CELLS
5. MODULE MODEL: Q.PEAK DUO BLK ML-G10+ 400
6. MODULE LENGTH: 74"
7. MODULE WIDTH: 41.1"
8. MODULE WEIGHT: 48.5 LBS
9. SEE SHEET A-103 FOR DIMENSION(S)
10. MIN. FIRE OFFSET: 18" FROM RIDGE, 36" FROM EDGE
11. TRUSS SPACING: 24 IN. O.C.
12. TRUSS SIZE: 2Х4 IN.
13. LAG BOLT DIAMETER: 5/16"
14. LAG BOLT EMBEDMENT: 3-1/2"
15. TOTAL # OF ATTACHMENTS: 51
16. TOTAL AREA: 485.78 SQ. FT.
17. TOTAL WEIGHT: 1288.93 LBS.
18. WEIGHT PER ATTACHMENT: 25.27 LBS.
19. DISTRIBUTED LOAD: 2.65 PSF
20. MAX. HORIZONTAL STANDOFF: 48 IN.
21. MAX. VERTICAL STANDOFF: IN ACCORDANCE WITH MODULE
MANUFACTURER'S INSTRUCTIONS
22. STANDOFF STAGGERING: YES
23. RAIL MANUFACTURER (OR EQUIV.): UNIRAC
24. RAIL MODEL (OR EQUIVALENT): STANDARD
25. RAIL WEIGHT: 0.728 PLF.
26. MAX. TRUSS SPAN: N/A.
27. MODULE CLEARANCE: 3 IN. MIN., 6 IN. MAX.
S-501
D5
20
11
121413151822
RO
O
F
S
L
O
P
E
910
10
6 21
7
S-501
D4
3
1
54
252423
8
27
1 2
1. FIELD VERIFY ALL MEASUREMENTS
GENERAL NOTES
SS LAG BOLT
W/ SS EPDM BONDED WASHER
SS SERRATED T-BOLT
SS SERRATED FLANGE NUT
FLASHLOC BASE
MILL OR DARK
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
S-501.00
ASSEMBLY DETAILS
(SHEET 9)
D4 DETAIL (TRANSVERSE)
NOT TO SCALE D5 DETAIL (LONGITUDINAL)
NOT TO SCALE
D1 RACKING DETAIL (TRANSVERSE)
NOT TO SCALE
D3 RACKING DETAIL (TOP)
NOT TO SCALE
D2 RACKING DETAIL (LONGITUDINAL)
NOT TO SCALE
04/11/2023
REVIEWED
BY SAFEBUILT
04/13/2023
PROVIDE ALL RACKING
INSTALLATION INSTRUCTIONS
AND DOCUMENTATION TO THE
INSPECTOR AT THE TIME OF
INSPECTION
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
R-001.00
(SHEET 10)
RESOURCE DOCUMENT
REVIEWED
BY SAFEBUILT
04/13/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
R-002.00
(SHEET 11)
RESOURCE DOCUMENT
REVIEWED
BY SAFEBUILT
04/13/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
R-003.00
(SHEET 12)
RESOURCE DOCUMENT
REVIEWED
BY SAFEBUILT
04/13/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
R-004.00
(SHEET 13)
RESOURCE DOCUMENT
REVIEWED
BY SAFEBUILT
04/13/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
R-005.00
(SHEET 14)
RESOURCE DOCUMENT
REVIEWED
BY SAFEBUILT
04/13/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
(SHEET 15)
RESOURCE DOCUMENT
R-006.00
REVIEWED
BY SAFEBUILT
04/13/2023
B F
A D E
2
3
UNAUTHORIZED USE OF THIS
DRAWING SET WITHOUT WRITTEN
PERMISSION FROM CONTRACTOR IS IN
VIOLATION OF U.S. COPYRIGHT LAWS
AND WILL BE SUBJECT TO CIVIL
DAMAGES AND PROSECUTIONS.
NEW PV SYSTEM:
9.200 kWp DC / 6.670 kWp AC
ENGINEER OF RECORD
02.17.2023
DESIGN BY:O.S.
M.M.
KINGSWOOD
RESIDENCE
133 STANLEY CIRCLE DRIVE,
ESTES PARK, CO 80517
APN: 2530236004
PAPER SIZE: 11" x 17" (ANSI B)
A C D E G H
B C F G H
1
4
5
6
CONTRACTOR
VENTARA DBA PRO BID ENERGY
PHONE:
LIC. NO.:
DATE:
CHECKED BY:
REVISIONS
HIC. NO.:
ELE. NO.:
ADDRESS:3975 E. 56TH AVE UNIT B1,
COMMERCE CITY, CO 80022
EC.0101800
(SHEET 16)
RESOURCE DOCUMENT
R-007.00
REVIEWED
BY SAFEBUILT
04/13/2023