HomeMy WebLinkAboutPLANS Remodel 303 Green Pine Ct 2023-02-23RECOMMENDED TO FLOAT FLOORS IN
BASEMENT
WOOD IN CONTACT WITH CONCRETE IS TO
TREATED OR OTHER APPROVED MATERIAL
MINIMUM CEILING HEIGHT IN BASEMENT 7'
MAINTAIN 30" OF WORKING CLEARANCE
ON SERVICE SIDE OF GAS FUELED
APPLIANCES
COMBUSTION AIR REQUIRED TO GAS
FUELED APPLIANCES
ALL CIRCUITS TO BE ARC FAULT
ALL OUTLETS TO BE TAMPER RESISTANT
MAXIMUM OUTLET SPACING 12'
2015 IECC
-75% OF LAMPS SHALL BE HIGH EFFICIENCY
-ALL DUCT WORK LOCATED OUTSIDE THE THERMAL
ENVELOPE SHALL BE TESTED FOR LEAKAGE
General Notes:
-All rooms to be AFCI except bath, utility and unfinished rooms
-Bath, utility and unfinished rooms to be GFCI
-Backwater valves to remain accessible
-Back flow protect all below grade fixtures
-1/2” dry wall req’d for enclosed usable space under stairs
-Smoke alarms req’d in each sleeping room
-Smoke/CO alarms req’d w/in 15’vicinity of bedroom exteriors
-Min 1 emergency escape and rescue opening req’d per bedroom
APPROVED by SAFEbuilt;
2015 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
02/23/2023
This structure must comply
with the requirements of the
2020 National Electrical Code