HomeMy WebLinkAboutPLANS Solar 601 Summit Dr 2021-03-12Friday, March 12, 2021 Town of Estes Park re: Structural Analysis 601 Summit Dr. Estes Park CO 80517 Dear Sir or Madam, We have evaluated the solar racking and connections to the roof for the photovoltaic array to be installed using the engineering design factors below. ultimate wind speed V = 175 mph wind exposure category = B ground snow load = 66 psf The PV system shall be flush mounted with no overhang. Attachments to the roof are to be spaced no more than 4’ O.C. Using the assumed engineering loads, we have determined that the design strength of all connections in the solar racking system will be sufficient for this application. The structural supporting members for the roof are 2x6” rafters 24” O.C. The roof framing has been evaluated using the IEBC section 806.2. Since the solar array will weigh less than 3psf, it will not add more than 5% of existing gravity loads and therefore is permitted under this section of code. We do not assume responsibility for any construction flaws that currently exist or caused by other work trades. Sincerely, Anthony P. Boniface, PE 1 2 3 4 5 6 7 8 9 10 11 12 MS P 14 13 HOUSE PHOTO VICINITY MAP SCALE: NTS SCALE: NTS COVER SHEET REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-1 BY SURAJ 1 SITE PLAN WITH VICINITY MAP SCALE: 1/32" = 1'-0" PHOTOVOLTAIC ROOF MOUNT SYSTEM ARRAY LOCATION 2 3 COVER SHEET 14 x 360 SUNPOWER SPR-X22-360-E-AC ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEMS PROJECT DESCRIPTION:GOVERNING CODES: 2015 INTERNATIONAL BUILDING CODE 2015 INTERNATIONAL RESIDENTIAL CODE 2015 INTERNATIONAL FUEL GAS CODE 2015 INTERNATIONAL MECHANICAL CODE 2015 INTERNATIONAL PLUMBING CODE 2015 INTERNATIONAL EXISTING BUILDING CODE 2015 INTERNATIONAL ENERGY CONSERVATION CODE 2017 NATIONAL ELECTRIC CODE SHEET INDEX PV-1 COVER SHEET PV-2 SITE PLAN PV-3 PV LAYOUT PV-3.1 STRING MAP PV-4 ATTACHMENT DETAIL PV-5 ELECTRICAL LINE DIAGRAM PV-6 WIRING CALCULATIONS PV-7 PLACARDS PV-8 SAFETY PLAN PV-9-12 EQUIPMENT SPECIFICATIONS AHJ: ESTES PARK UTILITY: TOWN OF ESTES PARK DESIGN SPECIFICATIONS EXPOSURE CATEGORY = B WIND SPEED = 175 MPH GROUND SNOW LOAD = 66 PSF SYSTEM SIZE: 5.04 kW DC STC ROOF ACCESS POINT PROJECT SITE COVER SHEET COVER SHEET ROOF #1 (14)SUNPOWER SPR-X22-360-E-AC ARRAY AREA #1: 245.56 SQ FT MAIN HOUSE 54'-2" 61'-4" P R O P E R T Y L I N E PROPE R T Y L I N E 1 2 3 4 5 6 7 8 9 10 11 12 JB UMCB MS P ACD 14 13 1 SITE PLAN SCALE: 1/16" = 1'-0" SITE PLAN REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-2 BY SURAJ SUNPOWER SPR-X22-360-E-AC NOTE TO INSTALLER: FIELD ADJUSTMENTS CAN BE MADE TO THE LAYOUT OF THE ARRAY ROOF PLAN AND MODULES ROOF LAYOUT NOTE SOLAR PANEL LAYOUT IS CONCEPTUAL, BUT AS PROVIDED, CONFORMS WITH THE REQUIREMENTS SET IN SHEET PV-2 CONTRACTOR MAY ADJUST PANEL LOCATION. 61 . 3 " 41.2" LEGEND - JUNCTION BOX JB MSP - MAIN SERVICE PANEL - CONDUIT UM -UTILITY METER - VENT, (ROOF OBSTRUCTIONS) MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES = 14 MODULES MODULE TYPE = SUNPOWER SPR-X22-360-E-AC MODULE WEIGHT = 42.9LBS/19.5KG. MODULE DIMENSIONS = 61.3"x 41.2" = 17.54 SF UNIT WEIGHT OF ARRAY = 2.45PSF CB -COMBINER PANEL ROOF DESCRIPTION ROOF TYPE ASHPHALT SHINGLE ROOF ROOF TILT AZIMUTH RAFTER SIZE RAFTER SPACING #1 12°152° 2"X6"24 O.C. ARRAY AREA & ROOF AREA CALC'S ROOF # OF MODULES ARRAY AREA (Sq. Ft.) ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1 14 245.56 750.06 32.74 (E) UTILITY METER (E)MAIN SERVICE PANEL (N) COMBINER PANEL (N) PV JUNCTION BOX (N) 3/4" EMT CONDUIT RUN ROOF # 1 TILT - 12 ° AZIM. - 152 ° (N) AC DISCONNECT ACD -AC DISCONNECT 6 0 1 S U M M I T D R . F R O N T O F R E S I D E N C E B A C K O F H O U S E ROOF #1 (14)SUNPOWER SPR-X22-360-E-AC 1 2 3 4 5 6 7 8 9 10 11 12 3'-0" 40'-11" 10'-9" 3 ' - 0 " 6 ' - 0 " 7 ' - 0 " 14 13 1 PV LAYOUT PV-3.0 SCALE: 3/32" = 1'-0" REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-3 BY SURAJ PV LAYOUT (N) RAIL SPLICE (TYP.) LEGEND - PV RAIL - VENT, (ROOF OBSTRUCTIONS) (N) (30) PV ROOF ATTACHMENT @ 48" O.C. MAX. (N) PV RAIL (TYP.) (E) RAFTER(TYP.) - ROOF ATTACHMENT - RAIL SPLICE SUNPOWER SPR-X22-360-E-AC 61 . 3 " 41.2" - TRUSSES DISCLAIMER: MATERIALS REQUIRED LIST FOR CONCEPTUAL USE ONLY THE INTENT IS TO AID CONTRACTOR FOR ORDERING REQUIRED MATERIALS FOR THE PROJECT. CONTRACTOR RESPONSIBLE TO VERIFY PRIOR TO SOLAR EQUIPMENT ORDERING BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULE 14 SUNPOWER SPR-X22-360-E-AC ATTACHMENT 28 ECOFASTEN GF1 L-COMP RAILS 11 INVISIMOUNT RAIL-129.125" SECTION RAIL SPLICE 6 SPLICE KIT MID CLAMPS 24 MID CLAMPS / UFO END CLAMPS 8 END CLAMPS / STOPPER SLEEVE GROUNDING LUG 1 INVISIMOUNT GROUNDING LUG 18" FIRE S E T B A C K 36 " F I R E S E T B A C K 6 0 1 S U M M I T D R . F R O N T O F R E S I D E N C E B A C K O F H O U S E JB 1 STRING LAYOUT PV-3.0 SCALE: 3/32" = 1'-0" REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-3.1 BY SURAJ STRING MAP CIRCUIT #1-(7) MODULES CIRCUIT #2-(7) MODULES 6 0 1 S U M M I T D R . F R O N T O F R E S I D E N C E B A C K O F H O U S E 12 PANELS MAX PER STRING REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-4 BY SURAJ ATTACHMENT DETAILS SUNPOWER INVISIMOUNT RACKING SYSTEM PV MODULE GROUNDING END/MID CLAMP GF1-ECOFASTEN L-FOOT SEE (2/PV-4) FOR ENLARGED VIEW ECOFASTEN FLASHING ASHPHALT SHINGLE ROOF 5/16" X 4" GRK 2-1/2" THREAD EMBEDMENT SEALED WITH GEOCELL (OR EQUIV.) 5/16" X 3-1/2" SS LAG BOLT MINIMUM 2-1/2" THREAD EMBEDMENT SEALED WITH GEOCELL (OR EQUIV.) ATTACHMENT DETAIL (ENLARGED VIEW) SCALE: NTS ATTACHMENT DETAIL SCALE: NTS ATTACHMENT DETAIL1 PV-4 SCALE: NTS ATTACHMENT DETAIL (ENLARGED VIEW) SCALE: NTS 2 PV-4 ASHPHALT ROOF DETAIL 2"X6" RAFT E R @ 24 OC . PV MODULES SUNPOWER INVISIMOUNT RAIL TYP. 2"X6" RAFT E R @ 24 OC. REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-5 BY SURAJ ELECTRICAL LINE DIAGRAM ELECTRICAL LINE DIAGRAM1 PV-5 SCALE: NTS PV BACKFEED BREAKER SIZE 30A MAIN BREAKER SIZE: 200A, MAIN BUS RATING: 200A TOTAL AMPS ON BUS 200A + 30A = 230A ≤ 240A (120% OF 200A) PER 705.12(B) (14)SUNPOWER SPR-X22-360-E-AC (02) CIRCUITS OF 7 MODULES (CONNECTED IN PARALLEL PER STRING) SYSTEM SIZE: 5.04 kW DC STC G N L2L1 M BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V TO UTILITY GRID N 200A (E) MAIN SERVICE PANEL,200A RATED, 240V(INSIDE) (E) GROUNDING ROD WIRE/CONDUITE SCHEDULE TAG #Description Conduit type/size Current carraying conductor type/size Neutral Conductor type/size Grounding conductor type/size ~1 -way length(ft)Notes 1 PV ARRAY TO JUNCTION BOX N/A 2 X #12 DG X 1X #10 Bare Cu 20 0.00 2 JUNCTION BOX TO AC PV LOAD CENTER 3/4" EMT 4 X #12 THWN-2 X 1X #12 THWN-2 60 0.00 3 AC PV LOAD CENTER TO MSP 3/4" EMT 2 X #10 THWN-2 1 X #10 THWN-2 1X #10 THWN-2 10 0.00 (N) JUNCTION BOX G L1 L2 (N) AC PV LOAD CENTER G N N G 15A PVS6 7- MICRO-INVERTERS IN BRANCH CIRCUIT #1 L2L2 L1L1 20A 1 2 30A 3 ON ROOF ON WALL(OUTSIDE) INSIDE AC DISCONNECT: 30A NON-FUSED, 240V NEMA 3R, UL LISTED G 3 7- MICRO-INVERTERS IN BRANCH CIRCUIT #1 L2L2 L1L1 20A *CONSUMPTION MONITORING MAY NOT BE POSSIBLE REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-6 BY SURAJ WIRING CALCULATIONS ELECTRICAL NOTES 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. 2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. 3.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. 4.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. 5.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. 6.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. 7.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. 8.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. 9.) MINIMUM CONDUCTOR SIZES SHOWN AND MAY BE UP-SIZED IN FIELD SO LONG AS 40% CONDUIT FILL IS NOT EXCEEDED. 10.) CONTRACTOR TO INSTALL SPECIFIED CONDUIT OR EQUIVALENT NEC COMPLIANT RACEWAY. PERCENT OF VALUES 0.80 0.70 0.50 NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT 4-6 7-9 10-20 AC CONDUCTOR AMPACITY CALCULATIONS: FROM ROOF TOP JUNCTION BOX TO AC PV LOAD CENTER AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT PER NEC 310.15(B)(3)(c): + 0° EXPECTED WIRE TEMP (°C): 34° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.96 # OF CURRENT CARRYING CONDUCTORS: 2 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 0.8 CIRCUIT CONDUCTOR SIZE: 12 AWG CIRCUIT CONDUCTOR AMPACITY: 30 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 X MAX AC OUTPUT CURRENT X # OF INVERTERS 1.25 X1.31X 7 = 11.46 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96X 0.8 X 30 = 23.04 A AC CONDUCTOR AMPACITY CALCULATIONS: AC PV LOAD CENTER TO MAIN SERVICE PANEL AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT EXPECTED WIRE TEMP (°C): 34° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.96 # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 1.00 CIRCUIT CONDUCTOR SIZE:10 AWG CIRCUIT CONDUCTOR AMPACITY: 40 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 X MAX AC OUTPUT CURRENT X # OF INVERTERS 1.25 X1.31X 14 = 22.93 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96 X 1.00 X 40 = 38.4A AMBIENT TEMPERATURE SPECS AMBIENT TEMP RECORD LOW -23 34° CONDUIT HEIGHT 0.5" - 3.5" ROOF TOP ADDER 56° ROOF TOP TEMP 51° TEMP-CORRECTION (AMBIENT TEMP).96 TEMP-CORRECTION (ROOF TOP TEMP).71 CONDUCTOR TEMPERATURE RATE 90° MODULE TEMPERATURE COEFFICIENT OF Voc -0.29%/°C SOLAR MODULE SPECIFICATIONS MANUFACTURER MODEL # PMAX PEAK OUTPUT POWER MAX CONTINOUS OUTPUT CURRENT MAX UNIT PER BRANCH CIRCUIT NOM. FREQUENCY 360W 320VA 1.31 12 60HZ SPR-X22-360-E-AC SUNPOWER MODULE DIMENSION 61.3"L x 40.2"W x 1.57"D (In Inch) REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-7 BY SURAJ PLACARD CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT:METER AND MAIN SERVICE PANEL AC PV LOAD CENTER CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT: CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT: CONDUIT / RACEWAYS / COMBINER BOXES / JUNCTION BOXES 1 LABEL LOCATION: PV AC COMBINER PANEL NEC 2020 2 LABEL LOCATION: COMBINER BOX / CIRCUITS / CONDUIT / COMBINER BOX / ENCLOSURES / EMT ENCLOSURES NEC 706.15(C)(4) AND NEC 690.13(B) 3 LABEL LOCATION: EMT / CONDUIT RACEWAYS NEC 690.31(D)(2) INVERTERS / DISCONNECTS 4 LABEL LOCATION: AC DISCONNECT / BREAKER / POINTS OF CONNECTION NEC 690.13(B) MAIN SERVICE PANEL / BREAKER / POINTS OF INTERCONNECTION / METER 7 LABEL LOCATION: MAIN SERVICE DISCONNECT NEC 705.12(C) AND 690.59 8 LABEL LOCATION: MAIN SERVICE DISCONNECT / PV BREAKER NEC 705.12(C) AND 690.59 9 LABEL LOCATION: UTILITY METER NEC 690.13(B) 11 LABEL LOCATION: DC DISCONNECT NEC 690.56(C) IFC1204.5 WARNING: PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM CONNECTED WARNING Inverter Output Connection Do Not Relocate This Overcurrent Device WARNING Dual Power Sources Second Source is PV System PV AC Output: 18.34A PV AC COMBINER PANEL PV SOURCE CIRCUITS ONLY! PV SYSTEM AC DISCONNECT WARNING ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION ! SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN TURN RAPID SHUTDOWN SWITCH TO THE "OFF" POSITION TO SHUT DOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN THE ARRAY. SOLAR ELECTRIC PV PANELS 1 2 3 6 7 8 9 4 11 EQUIPMENT LABELS MAIN SERVICE PANEL PV BACKFEED PANEL UTILITY METER PV AC DISCONNECT PV COMBINER PANEL JUNCTION BOX RACEWAY OR CONDUIT WITHIN 3' OF SERVICE DISCONNECTING MEANS EMERGENCY POWER OFF SWITCH 60 1 S U M M I T D R . (N)AC PV LOAD CENTER (E) UTILITY METER (E)MSP (N)AC DISCONNECT 1 2 3 4 5 6 7 8 9 10 11 12 JB UMCB MS P ACD 14 13 REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-8 BY SURAJ SAFETY PLAN (E) UTILITY METER (E)MAIN SERVICE PANEL (N) AC PV LOAD CENTER 3/4" EMT CONDUIT RUN (N) PV JUNCTION BOX GARAGE MAIN HOUSE DRIVEW A Y (N) AC DISCONNECT 6 0 1 S U M M I T D R . F R O N T O F R E S I D E N C E PANORAMA CIR B A C K O F H O U S E REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-9 BY SURAJ EQUIPMENT SPECIFICATIONS REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-10 BY SURAJ EQUIPMENT SPECIFICATIONS REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-11 BY SURAJ EQUIPMENT SPECIFICATIONS REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME RA Y M O N D S M O L I N S K I DE B O R A H S M O L I N S K I 60 1 S U M M I T D R ES T E S P A R K , C O 8 0 5 1 7 12/03/2021INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PV-12 BY SURAJ EQUIPMENT SPECIFICATIONS