HomeMy WebLinkAboutPLANS New SFD 133 Stanley Circle Dr 2022-08-23PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SITE PLAN REVIEWED FOR
BUILDING COMPLIANCE - BY
SAFEBUILT - PBLAND
NO PORTION OF ANY BUILDING OR
STRUCTURE SHALL ENCROACH INTO
OR OVER AN EASEMENT, SETBACK
LINES OR PROPERTY LINES
All work shall be performed by Licensed
Contractors OR work shall be performed
by the homeowner residing in the dwelling.
Issuance of a permit or approval of these construction
documents shall not be construed to be a permit for, or an
approval of, any violation of any of the provisions of the
adopted codes or of other ordinances of this jurisdiction.
A permit presuming to give authority to violate or cancel the
provisions of these codes shall be invalid. R105.4
PLANS AND CONSTRUCTION SHALL MEET
THE 2015 IRC AND ALL APPLICABLE
MUNICIPAL CODES & ORDINANCES
All Irrigation Sprinkler Taps Shall be Protected
by an Approved Back Flow Devide
Plans are NOT approved for tankless water
heater - Tankless water heater install requires a
one-line drawing of gas line showing all
appliances and loads, lengths and sizes of pipe.
ALL PERMIT DOCUMENTS: ARCHITECTURAL PLANS,
ENGINEERED PLANS, SOILS REPORTS, TRUSS
DRAWINGS, ENERGY CODE REPORTS/RESCHECKS,
ETC... MUST BE KEPT TOGETHER & ONSITE FOR
INSPECTORS REVIEW.
FOLLOW ALL MANUFACTURER'S INSTRUCTIONS:
Manufacturer's installation instructions, as required by
code, shall be available on the job site at the time of
inspection. R106.1.2
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
This structure must comply
with the requirements of the
2020 National Electrical
Code
CBO GARY RUSU APPROVED COLORADO LICENSED
ARCHITECT JOHN FREEMAN TO TAKE ALL STRUCTURAL &
CIVIL DESIGN AND CONSTRUCTION RESPONSIBLITY
OPEN HOLE REQUIRED
AP
P
R
O
V
E
D
b
y
S
A
F
E
b
u
i
l
t
;
20
1
5
I
n
t
e
r
n
a
t
i
o
n
a
l
C
o
d
e
s
Su
b
j
e
c
t
t
o
i
n
s
p
e
c
t
i
o
n
a
n
d
c
o
m
p
l
i
a
n
c
e
t
o
a
l
l
Re
l
e
v
a
n
t
,
a
d
o
p
t
e
d
B
u
i
l
d
i
n
g
&
M
u
n
i
c
i
p
a
l
Co
d
e
s
08
/
2
3
/
2
0
2
2
SD
SD
SD/CO
within 15' of
bedrooms
SD/CO
garage shall be separated by min. 1/2" gyp'bd
- on garage side - for walls adjacent to living
space
FP Manu instructions to be on site,
Clearances are req'd
Vent termination per manufacture
Cement based substrate or equal
on shower/tub walls - Typ
Dryer Vent to be Run to the
outside, Min 3' away from
any intake. If run greater
than 35', with code assigned
distances for elbows, a label
is required within 6' of dryer
vent
Glazing installed in hazardous
locations as defined in Section
R308.4 shall be Tempered Glass
Freeze Protect pipes per P2603.5
Fall Protection is required where
applicable (R312) - Windows that
are operable at 6' above grade
with sill height lower than 24"
Provide 50 cfm fan in bathroom
- vented to exterior - when no
natural ventilation is provided
by window
Fire Block shall be provided in
enclosed wood framed walls per
locations designated in R302.11
Access doors from Conditioned
spaces to unconditioned spaces (E.G.
Attics and Crawlspaces) shall be
weatherstripped and insulated.
Air gap required at or within
dishwasher - per P2717.1
Appliance and all Equipment
Vent Terminations shall be per
manufacturers specifications
Per R311.6 - Hallways shall
be not less than 3 feet.
Provide Anti-Scald valves on shower
or tub/shower combination valves
All lawn irrigation systems shall be
protected with backflow by vacuum
breaker or reduced pressure principle
assembly Per section P2902.5.3
Showers shall be finished 72 inches
above the floor with a
non-absorbent material. Shower
door minimum clear opening width
is 24 inches and open outward
Any New Gas piping shall be tested
for not less than 15 min. @ 1 1/2
times the proposed maximum
working pressure but not less than
10 psig. - before it is put into
service. See section 2417.4.1 and
local amendments
Min 1 3/8" thick.
Solid or 20 Min.
Fire Door with
Self-Closing
device
Follow Manufacturer's installation instructions:
Manufacturer's installation instructions, as required
by code, shall be available on the job site at the
time of inspection. R106.1.2
Toilets & Lavatories shall be
provided with a min. of 21 inches in
front each fixture
- each side of Toilets shall have 15
inches from the center line of the
toilet and any sidewall or other
obstructions.
Hose Bibs shall be protected by an
atmospheric-type or pressure-type
vacuum breaker, a pressure
vacuum-breaker assembly or a
permanently attached hose connection
vacuum breaker - P2902.4.3
Provide attic access of min. of
22"x30" to enclosed attic space
of combustible roof construction
with a vertical height of 30"
Provide Air Barrier & insulation on
exterior wall at shower/tub, etc...
See Air Barrier table N1102.4.1.1
M1507.2 - Exhaust Air from
bathrooms & toilet rooms shall not
be recirculated within the
residence or other dwelling units
and be exhausted directly outside
If kitchen hood greater than 400
cfm, must have approx equal
make up air on automatically
controlled damper - Per M1503.4
Glazing in walls containing or
facing hot tubs, spas, bathtubs,
showers, indoor or outdoor pools
where the bottom exposed edge of
glazing is less than 60" vertically
above any standing or walking
surface - shall be safety glazing
(R308.4.5)
Do not remove Manufacturers
stickers on windows until after
all final inspections
WATER HAMMER ARRESTORS
ARE TO BE USED ON ALL
APPLIANCES WITH QUIICK
CLOSING VALVES.
Fueled fired appliances shall not be
located in sleeping rooms, bathrooms,
storage closets or spaces that opens
into such rooms or spaces unless
meets section G2406.2
Garage receptacle outlets shall be
provided with 20 amp circuit.
Only the outdoor receptacle outlets are
permitted to be added to this circuit.
If kitchen hood greater than 400 cfm,
must have approx equal make up air
on automatically controlled damper -
Per M1503.6
Hardwired appliances are required to
have a disconnect within sight or a
lockable means at circuit breaker
Closet lights to conform to E4003.12
Bathrooms - Min one - 20 amp circuit
- bathroom countertops or similar
work surfaces shall be GFCI
protected - Typical for each bathroom
(2020 NEC 210.8)
Kitchen to be served by 2 separate 20
Amp GFCI circuits.
IC Rated Sealed Recess Cans in Attic
Receptacles cannot be installed within a zone of 3'
horizontally & 8' from the bathtub rim or shower stall
threshold (410.10D - 2020 NEC)
Outdoor receptacles shall be a min 12" from
final grade, roof surfaces or similar locations.
Laundry room, Dishwasher,
Unfinished basement, garage, &
outdoor receptacles shall have
GFCI protection.
Per 2020 NEC 210.8 - All basement
receptacles (finished or not) except for
permanently installed fire or burglar alarms
shall be GFCI Protected.
Dwelling units shall have a
Service Disconnect on the
exterior of the structure in a
readily accessible outdoor
location and be marked. (230.85 -
2020 NEC)
Per 210.8 (A)(5) Requires all
receptacles installed in garages
& unfinished storage rooms
shall have GFCI Protection
210.52(C)(1).(C)(2).(C)(3) Has
been changed to Use the square
footage of islands and
Peninsulas for how many outlets
are required.
210.S(A)-Requires GFCI
protection to Include the 240 volt
receptacles for Ranges that are
within 6’ from the Edge of sinks
and for 240 volt receptacles
Located in laundry rooms for the
dryers.
Provide Tamper-resistant receptacles -
Installed Per E4002.14
Outlets installed in kitchens, family rooms,
dining rooms, living rooms, parlors,
libraries, dens, bedrooms, sunrooms,
recreation rooms, closets, hallways,
laundry areas and similar rooms or areas
shall be AFCI protected - per E3902.16
See 410.10 (D) for new requirements for
where and what type of fixtures can be
installed in areas containing
bathtubs/showers
A minimum of 90% of the lamps in
permanently installed lighting
fixtures shall be high efficacy
lamps. per 2018 N1104.1
Laundry areas require a 20 amp
branch circuit to supply the
laundry receptacle outlet. This
circuit shall serve only receptacle
outlets located in laundry area.
Shall be GFCI protected
NOT LESS THAN ONE RECEPTACLE
OUTLET, IN ADDITION TO ANY
PROVIDED SPECIFIC EQUIPMENT,
SHALL BE INSTALLED IN EACH
VEHICLE BAY NOT MORE THAN 5.5
FEE ABOVE THE FLOOR IN
DETACHED GARAGES PROVIDE
WITH ELEC. POWER
The entire building must be provided with
Smoke Detectors one in each sleeping room,
outside each sleeping room and on each
additional story of the dwelling
CO Detectors are Required outside of
bedrooms and within 15' of bedroom doors.
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SD
SD
SD/CO
within 15' of
bedrooms
SD/CO
within 15' of
bedrooms
BASEMENT PLAN REVIEW NOTES:
Attach Energy Certificate/Report on
Return Side of Furnace: R-Values,
U-factors, air leakage, Eff of Furn., AC,
water heater
Furnace Install instruction on site
Backflow prevention required per 2902.3
Access doors from Conditioned spaces
to unconditioned spaces (E.G. Attics and
Crawlspaces) shall be weatherstripped
and insulated.
Seal all basement Floor Penetrations
Home must pass blower door test Min 7 air
changes per hour per code amendment
section R303.4
If future plumbing (rough in) provided,
should allow room for future frame,
insulation, min 30" tub/shower, & min
30" space for water closet
Drywall under stairs Min 1/2" if
enclosed as storage
Mechanical room access shall be large enough to
allow for inspection, service, repair and
replacement without removing permanent
construction or other appliances - per M1305.1
Provide Combustion Air to Mech Rm - that
is obtained from outdoors - when fuel fire
appliances or garage that communicates
with dwelling are present - maintain a 30"
clearance for service
Backwater protection required at all
basement level plumbing drains and to
remain accessible
PROVIDE FLOOR PROTECTION FOR
NEW FLOORS PER 2015 IRC SECTION
R302.13 AND LOCAL AMENDMENTS
TRAP BARRIERS TO HAVE A
MINIMUM TRAP SEAL OF 2"
AND NOT MORE THAN 4"
PRESSURE TEST REQUIRED
FOR DWV AND WATER
GAS PIPING TO BE BURIED A
MINIMUM OF 18" BELOW GROUND
WITH A YELLOW TRACER WIRE
Drywall under stairs Min
1/2" if enclosed as storage
All habitable space requires heat
supply and pressure relief.
Fire Block shall be provided in wood
framed walls per locations designated
in R302.11
Cement based substrate or equal
on shower/tub walls - Typ
Freeze Protect pipes per P2603.5
Provide 50 cfm fan in bathroom
- vented to exterior - when no
natural ventilation is provided
by window
Provide Anti-Scald valves on shower
or tub/shower combination valves
Showers shall be finished 72 inches
above the floor with a
non-absorbent material. Shower
door minimum clear opening width
is 24 inches and open outward -
See handout for clearances
Toilets & Lavatories shall be
provided with a min. of 21 inches in
front each fixture
- each side of Toilets shall have 15
inches from the center line of the
toilet and any sidewall or other
obstructions.
Provide Air Barrier & insulation on
exterior wall at shower/tub, Fireplace,
etc... See Air Barrier & Insulation Table
1102.4.1.1
Float all walls - use treated sill
plates (recommended)
BASEMENT FINISHING NOTES:
Backwater protection required at all
basement level plumbing drains and to
remain accessible
All rooms to be AFCI except bath, utility
and unfinished rooms
All basement receptacles including
unfinished rooms to be GFCI
Backwater valves to remain accessible
Smoke alarms required in each sleeping
room
C/O alarms required w/in 15' of vicinity of
bedrooms exteriors
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
R-19 INSULATION REQUIRED PER THE ENERGY
CODE REPORTS
R-19 INSULATION REQUIRED PER THE ENERGY
CODE REPORTS
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
An ice barrier, such as a self-adhering polymer modified
bitumen sheet, shall be installed on the
entire area of roof slopes from two units vertical in 12
units horizontal (17-percent slope), up to
four units vertical in 12 units horizontal (33-percent slope).
General Elevation/Roof Notes:
- Asphalt shingles shall meet 175 mph wind-speed & be tested in
accordance with ASTM D 7158 & packaging shall bear label of
classification
- All asphalt shingles shall be installed per manufacturers
installation instructions (R905.2.4)
- Roof slopes from 2:12 up to 4:12 require double underlayment
- All Roofing materials shall comply with R905
- Roof Ventilation per R806
- Drip edge required on all rakes and eaves
- Siding Coverings to meet 175 MPH wind-speed
- All stone, stucco and siding to have a barrier underneath at
exterior walls - All exterior coverings shall comply with R703
- Sills less than 24" - w/72+" of fall require fall protection
- All stairs, landings, guards, rails and walking surfaces to comply
with R311 and R312
EAVE BAFFLE TO EXTEND PAST INSULATION.
DUCTS RUN IN ATTIC REQUIRE MIN. R-8
IF DUCTS RUN OUTSIDE OF THERMAL
ENVELOPE AT ANY POINT - DUCT
PRESSURE TEST SHALL BE REQUIRED
FLASHING SHALL BE INSTALLED IN A MANNER
THAT WILL PREVENT MOISTURE ENTERING
WALLS AND ROOFS R903.2
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
An ice barrier, such as a self-adhering polymer modified
bitumen sheet, shall be installed on the
entire area of roof slopes from two units vertical in 12
units horizontal (17-percent slope), up to
four units vertical in 12 units horizontal (33-percent slope).
General Elevation/Roof Notes:
- Asphalt shingles shall meet 175 mph wind-speed & be tested in
accordance with ASTM D 7158 & packaging shall bear label of
classification
- All asphalt shingles shall be installed per manufacturers
installation instructions (R905.2.4)
- Roof slopes from 2:12 up to 4:12 require double underlayment
- All Roofing materials shall comply with R905
- Roof Ventilation per R806
- Drip edge required on all rakes and eaves
- Siding Coverings to meet 175 MPH wind-speed
- All stone, stucco and siding to have a barrier underneath at
exterior walls - All exterior coverings shall comply with R703
- Sills less than 24" - w/72+" of fall require fall protection
- All stairs, landings, guards, rails and walking surfaces to comply
with R311 and R312
EAVE BAFFLE TO EXTEND PAST INSULATION.
DUCTS RUN IN ATTIC REQUIRE MIN. R-8
IF DUCTS RUN OUTSIDE OF THERMAL
ENVELOPE AT ANY POINT - DUCT
PRESSURE TEST SHALL BE REQUIRED
FLASHING SHALL BE INSTALLED IN A MANNER
THAT WILL PREVENT MOISTURE ENTERING
WALLS AND ROOFS R903.2
2015 PRESCRIPTIVE INSULATION VALUES:
SLAB EDGE = R-10 for 2 ft.
BASEMENT = R-19 Cont. & Cavity Fill
FLOOR = R-30
WALLS = R-21
ATTIC/CEILING = R-49
FENESTRATION U-FACTOR VALUE:
WINDOW = 0.32
Prescriptive paths must follow all Mandatory requirements in
Section N1101 through N1104 of Chapter 11 of the 2015 IRC
CONTRACTOR IS RESPONSIBLE TO MAKE SURE ALL ENERGY
REPORTS - INCLUDING MANUAL JDS - TO MATCH PLANS AND
FIELD INSTALLATIONS - AND ARE PROVIDED FOR INSPECTORS
REVIEW AT INSPECTIONS PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
ENGINEERS STAMPED TRUSS PLANS AND SPECS
TO BE ON SITE FOR INSPECTORS REVIEW
R-19 INSULATION REQUIRED PER THE ENERGY CODE REPORTS
R-19 Insulation
R-10
R-19 Insulation
R-49 Insulation
2015 PRESCRIPTIVE INSULATION VALUES:
per ResCheck Report
SLAB EDGE = R-10 for 2 ft.
BASEMENT = R-19 Cont. & Cavity Fill
FLOOR = R-30
WALLS = R-21
ATTIC/CEILING = R-49
FENESTRATION U-FACTOR VALUE:
WINDOW = 0.32
Prescriptive paths must follow all Mandatory requirements in
Section N1101 through N1104 of Chapter 11 of the 2015 IRC
CONTRACTOR IS RESPONSIBLE TO MAKE SURE ALL ENERGY
REPORTS - RESCHECK & MANUAL JDS - TO MATCH PLANS AND
FIELD INSTALLATIONS - AND ARE PROVIDED FOR INSPECTORS
REVIEW AT INSPECTIONS
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
ENGINEERS STAMPED TRUSS PLANS AND SPECS
TO BE ON SITE FOR INSPECTORS REVIEW
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have
on site for inspector
REVIEWED BY SAFEBUILT - PBLAND
REScheck Software Version 4.7.2
Compliance Certificate
Project 133 Stanley Circle Dr_ManJSD_080922
Energy Code:2015 IECC
Location:Estes Park, Colorado
Construction Type:Single-family
Project Type:New Construction
Orientation:Bldg. faces 225 deg. from North
Conditioned Floor Area:2,875 ft2
Glazing Area 18%
Climate Zone:5 (7944 HDD)
Permit Date:
Construction Site:Owner/Agent:
Mike Kingswood
Kingswood Homes
970-214-8844
mike@homesbykingswood.com
Designer/Contractor:
Permit Number:
Compliance: Passes using UA trade-off
6.0% Better Than Code Maximum UA:302 Your UA:284
The % Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Compliance:
NOTE: Slab-on-grade tradeoffs are no longer considered in the UA or performance compliance path in REScheck. Each slab-on-
grade assembly in the specified climate zone must meet the minimum energy code insulation R-value and depth requirements.
Envelope Assemblies
Assembly
Gross Area
or
Perimeter
Cavity
R-Value
Cont.
R-Value
Prop.
U-Factor
Req.
U-Factor
Prop.
UA
Req.
UA
Wall, Front: Wood Frame, 16" o.c.
Orientation: Front 256 21.0 0.0 0.057 0.060 12 13
Door, Entry: Solid
Orientation: Front 20 0.203 0.320 4 6
Windows: Vinyl/Fiberglass Frame:Double Pane with
Low-E
Orientation: Front
26 0.320 0.320 8 8
Wall, Left: Wood Frame, 16" o.c.
Orientation: Left side 377 21.0 0.0 0.057 0.060 20 21
Windows: Vinyl/Fiberglass Frame:Double Pane with
Low-E
Orientation: Left side
26 0.320 0.320 8 8
Wall, Back: Wood Frame, 16" o.c.
Orientation: Back 795 21.0 0.0 0.057 0.060 29 31
Windows: Vinyl/Fiberglass Frame:Double Pane with
Low-E
Orientation: Back
159 0.320 0.320 51 51
Door, Dining SGD: Glass
Orientation: Unspecified 40 0.320 0.320 13 13
Door, Living SGD: Glass
Orientation: Unspecified 40 0.320 0.320 13 13
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 1 of 11
08/09/22Report date:
CONTRACTOR IS RESPONSIBLE TO MAKE SURE ALL
ENERGY REPORTS - RESCHECK & MANUAL JDS - TO
MATCH PLANS AND FIELD INSTALLATIONS - AND
ARE PROVIDED FOR INSPECTORS REVIEW AT
INSPECTIONS
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
ENERGY REPORTS ARE REVIEWED
TO VERIFY EQUIVALENCY WITH
PLANS & OTHER REPORTS - BY
SAFEBUILT - PBLAND
Assembly
Gross Area
or
Perimeter
Cavity
R-Value
Cont.
R-Value
Prop.
U-Factor
Req.
U-Factor
Prop.
UA
Req.
UA
Door, Basement Living SGD: Glass
Orientation: Unspecified 40 0.320 0.320 13 13
Wall, Right: Wood Frame, 16" o.c.
Orientation: Right side 304 21.0 0.0 0.057 0.060 17 18
Windows: Vinyl/Fiberglass Frame:Double Pane with
Low-E
Orientation: Right side
12 0.320 0.320 4 4
Wall, Garage Partition: Wood Frame, 16" o.c.
Orientation: Unspecified 220 21.0 0.0 0.057 0.060 12 12
Door, Garage Entry: Solid
Orientation: Unspecified 17 0.203 0.320 3 5
Basement Wall, Front: Solid Concrete or Masonry
Orientation: Front
Wall height: 8.6'
Depth below grade: 8.0'
Insulation depth: 8.6'
158 19.0 0.0 0.043 0.050 7 8
Basement Wall, Left: Solid Concrete or Masonry
Orientation: Left side
Wall height: 8.6'
Depth below grade: 8.0'
Insulation depth: 8.6'
118 19.0 0.0 0.043 0.050 5 6
Window: Vinyl/Fiberglass Frame:Double Pane with
Low-E
Orientation: Left side
6 0.320 0.320 2 2
Basement Wall, Right: Solid Concrete or Masonry
Orientation: Right side
Wall height: 8.6'
Depth below grade: 8.0'
Insulation depth: 8.6'
158 19.0 0.0 0.043 0.050 7 8
Basement Wall, Unfin Front: Solid Concrete or
Masonry
Orientation: Front
Wall height: 8.6'
Depth below grade: 8.0'
Insulation depth: 8.6'
233 0.0 19.0 0.037 0.050 9 12
Basement Wall, Unfin Left: Solid Concrete or
Masonry
Orientation: Left side
Wall height: 8.6'
Depth below grade: 8.0'
Insulation depth: 8.6'
137 0.0 19.0 0.037 0.050 5 7
Basement Wall, Unfin Right: Solid Concrete or
Masonry
Orientation: Right side
Wall height: 8.6'
Depth below grade: 8.0'
Insulation depth: 8.6'
98 0.0 19.0 0.037 0.050 4 5
Floor over ambient: All-Wood Joist/Truss:Over
Outside Air 12 30.0 0.0 0.033 0.033 0 0
Floor, Slab on grade at walkout: Slab-On-
Grade:Unheated
Insulation depth: 2.0'
54 10.0 0.767 0.033 0 0
Ceiling: Flat Ceiling or Scissor Truss 1,464 49.0 0.0 0.026 0.026 38 38
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 2 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Name - Title Signature Date
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application. The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.7.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Project Notes:
Job Number: 133 Stanley Circle Dr_ManJSD_080922
Town of Estes Park
IECC 2015
Site Elevation 7598
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 3 of11
08/09/22Report date:
Mark Scott, Scott Home Inspection LLC August 9, 2022
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Inspection Checklist
Requirements: 0.0% were addressed directly in the REScheck software
REScheck Software Version 4.7.2
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Energy Code: 2015 IECC
Section
#
& Req.ID
Pre-Inspection/Plan Review Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
103.1,
103.2
[PR1]1
Construction drawings and
documentation demonstrate
energy code compliance for the
building envelope. Thermal
envelope represented on
construction documents.
Complies
Does Not
Not Observable
Not Applicable
103.1,
103.2,
403.7
[PR3]1
Construction drawings and
documentation demonstrate
energy code compliance for
lighting and mechanical systems.
Systems serving multiple
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
Complies
Does Not
Not Observable
Not Applicable
302.1,
403.7
[PR2]2
Heating and cooling equipment is
sized per ACCA Manual S based
on loads calculated per ACCA
Manual J or other methods
approved by the code official.
Heating:
Btu/hr_____
Cooling:
Btu/hr_____
Heating:
Btu/hr_____
Cooling:
Btu/hr_____
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 4 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Section
#
& Req.ID
Foundation Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.1.2
[FO1]1
Slab edge insulation R-value.R-_____
Unheated
Heated
R-_____
Unheated
Heated
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.2
[FO3]1
Slab edge insulation
depth/length.
_____ ft _____ ft Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.1
[FO4]1
Conditioned basement wall
insulation R-value. Where interior
insulation is used, verification
may need to occur during
Insulation Inspection. Not
required in warm-humid locations
in Climate Zone 3.
R-_____
R-_____
R-_____
R-_____
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2
[FO5]1
Conditioned basement wall
insulation installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
402.2.9
[FO6]1
Conditioned basement wall
insulation depth of burial or
distance from top of wall.
_____ ft _____ ft Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2.1
[FO11]2
A protective covering is installed
to protect exposed exterior
insulation and extends a
minimum of 6 in. below grade.
Complies
Does Not
Not Observable
Not Applicable
403.9
[FO12]2
Snow- and ice-melting system
controls installed.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 5 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Section
#
& Req.ID
Framing / Rough-In Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.1.1,
402.3.4
[FR1]1
Door U-factor.U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
402.1.1,
402.3.1,
402.3.3,
402.5
[FR2]1
Glazing U-factor (area-weighted
average).
U-_____U-_____Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.1.3
[FR4]1
U-factors of fenestration products
are determined in accordance
with the NFRC test procedure or
taken from the default table.
Complies
Does Not
Not Observable
Not Applicable
402.4.1.1
[FR23]1
Air barrier and thermal barrier
installed per manufacturer’s
instructions.
Complies
Does Not
Not Observable
Not Applicable
402.4.3
[FR20]1
Fenestration that is not site built
is listed and labeled as meeting
AAMA /WDMA/CSA 101/I.S.2/A440
or has infiltration rates per NFRC
400 that do not exceed code
limits.
Complies
Does Not
Not Observable
Not Applicable
402.4.5
[FR16]2
IC-rated recessed lighting fixtures
sealed at housing/interior finish
and labeled to indicate ≤2.0 cfm
leakage at 75 Pa.
Complies
Does Not
Not Observable
Not Applicable
403.3.1
[FR12]1
Supply and return ducts in attics
insulated >= R-8 where duct is
>= 3 inches in diameter and >=
R-6 where < 3 inches. Supply and
return ducts in other portions of
the building insulated >= R-6 for
diameter >= 3 inches and R-4.2
for < 3 inches in diameter.
Complies
Does Not
Not Observable
Not Applicable
403.3.5
[FR15]3
Building cavities are not used as
ducts or plenums.
Complies
Does Not
Not Observable
Not Applicable
403.4
[FR17]2
HVAC piping conveying fluids
above 105 ºF or chilled fluids
below 55 ºF are insulated to ≥R-
3.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
403.4.1
[FR24]1
Protection of insulation on HVAC
piping.
Complies
Does Not
Not Observable
Not Applicable
403.5.3
[FR18]2
Hot water pipes are insulated to
≥R-3.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
403.6
[FR19]2
Automatic or gravity dampers are
installed on all outdoor air
intakes and exhausts.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 6 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 7 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Section
#
& Req.ID
Insulation Inspection Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
303.1
[IN13]2
All installed insulation is labeled
or the installed R-values
provided.
Complies
Does Not
Not Observable
Not Applicable
402.1.1,
402.2.6
[IN1]1
Floor insulation R-value.R-_____
Wood
Steel
R-_____
Wood
Steel
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2,
402.2.7
[IN2]1
Floor insulation installed per
manufacturer’s instructions and
in substantial contact with the
underside of the subfloor, or floor
framing cavity insulation is in
contact with the top side of
sheathing, or continuous
insulation is installed on the
underside of floor framing and
extends from the bottom to the
top of all perimeter floor framing
members.
Complies
Does Not
Not Observable
Not Applicable
402.1.1,
402.2.5,
402.2.6
[IN3]1
Wall insulation R-value. If this is a
mass wall with at least ½ of the
wall insulation on the wall
exterior, the exterior insulation
requirement applies (FR10).
R-_____
Wood
Mass
Steel
R-_____
Wood
Mass
Steel
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.2
[IN4]1
Wall insulation is installed per
manufacturer’s instructions.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 8 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Section
#
& Req.ID
Final Inspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
402.1.1,
402.2.1,
402.2.2,
402.2.6
[FI1]1
Ceiling insulation R-value.R-_____
Wood
Steel
R-_____
Wood
Steel
Complies
Does Not
Not Observable
Not Applicable
See the Envelope Assemblies
table for values.
303.1.1.1,
303.2
[FI2]1
Ceiling insulation installed per
manufacturer’s instructions.
Blown insulation marked every
300 ft².
Complies
Does Not
Not Observable
Not Applicable
402.2.3
[FI22]2
Vented attics with air permeable
insulation include baffle adjacent
to soffit and eave vents that
extends over insulation.
Complies
Does Not
Not Observable
Not Applicable
402.2.4
[FI3]1
Attic access hatch and door
insulation ≥R-value of the
adjacent assembly.
R-_____R-_____Complies
Does Not
Not Observable
Not Applicable
402.4.1.2
[FI17]1
Blower door test @ 50 Pa. <=5
ach in Climate Zones 1-2, and
<=3 ach in Climate Zones 3-8.
ACH 50 =_____ACH 50 =_____Complies
Does Not
Not Observable
Not Applicable
403.3.4
[FI4]1
Duct tightness test result of <=4
cfm/100 ft2 across the system or
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough-in
tests, verification may need to
occur during Framing Inspection.
_____ cfm/100
ft2
_____ cfm/100
ft2
Complies
Does Not
Not Observable
Not Applicable
403.3.3
[FI27]1
Ducts are pressure tested to
determine air leakage with
either: Rough-in test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the system including
the manufacturer’s air handler
enclosure if installed at time of
test. Postconstruction test: Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer’s air
handler enclosure.
_____ cfm/100
ft2
_____ cfm/100
ft2
Complies
Does Not
Not Observable
Not Applicable
403.3.2.1
[FI24]1
Air handler leakage designated
by manufacturer at <=2% of
design air flow.
Complies
Does Not
Not Observable
Not Applicable
403.1.1
[FI9]2
Programmable thermostats
installed for control of primary
heating and cooling systems and
initially set by manufacturer to
code specifications.
Complies
Does Not
Not Observable
Not Applicable
403.1.2
[FI10]2
Heat pump thermostat installed
on heat pumps.
Complies
Does Not
Not Observable
Not Applicable
403.5.1
[FI11]2
Circulating service hot water
systems have automatic or
accessible manual controls.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 9 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Section
#
& Req.ID
Final Inspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
403.6.1
[FI25]2
All mechanical ventilation system
fans not part of tested and listed
HVAC equipment meet efficacy
and air flow limits.
Complies
Does Not
Not Observable
Not Applicable
403.2
[FI26]2
Hot water boilers supplying heat
through one- or two-pipe heating
systems have outdoor setback
control to lower boiler water
temperature based on outdoor
temperature.
Complies
Does Not
Not Observable
Not Applicable
403.5.1.1
[FI28]2
Heated water circulation systems
have a circulation pump. The
system return pipe is a dedicated
return pipe or a cold water supply
pipe. Gravity and thermos-
syphon circulation systems are
not present. Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
Complies
Does Not
Not Observable
Not Applicable
403.5.1.2
[FI29]2
Electric heat trace systems
comply with IEEE 515.1 or UL
515. Controls automatically
adjust the energy input to the
heat tracing to maintain the
desired water temperature in the
piping.
Complies
Does Not
Not Observable
Not Applicable
403.5.2
[FI30]2
Water distribution systems that
have recirculation pumps that
pump water from a heated water
supply pipe back to the heated
water source through a cold
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
water piping to 104ºF.
Complies
Does Not
Not Observable
Not Applicable
403.5.4
[FI31]2
Drain water heat recovery units
tested in accordance with CSA
B55.1. Potable water-side
pressure loss of drain water heat
recovery units < 3 psi for
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units < 2 psi for
individual units connected to
three or more showers.
Complies
Does Not
Not Observable
Not Applicable
404.1
[FI6]1
75% of lamps in permanent
fixtures or 75% of permanent
fixtures have high efficacy lamps.
Does not apply to low-voltage
lighting.
Complies
Does Not
Not Observable
Not Applicable
404.1.1
[FI23]3
Fuel gas lighting systems have
no continuous pilot light.
Complies
Does Not
Not Observable
Not Applicable
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 10 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Section
#
& Req.ID
Final Inspection Provisions Plans Verified
Value
Field Verified
Value Complies?Comments/Assumptions
401.3
[FI7]2
Compliance certificate posted.Complies
Does Not
Not Observable
Not Applicable
303.3
[FI18]3
Manufacturer manuals for
mechanical and water heating
systems have been provided.
Complies
Does Not
Not Observable
Not Applicable
Additional Comments/Assumptions:
1 High Impact (Tier 1)2 Medium Impact (Tier 2)3 Low Impact (Tier 3)
Project Title: 133 Stanley Circle Dr_ManJSD_080922
Data filename: C:\Users\Mark Scott\Desktop\SHI Files\001 Manual JD Projects\2022\133 Stanley
Cir_ManJSD_080922\133 Stanley Circle Dr_REScheck_080922.rck
Page 11 of 11
08/09/22Report date:
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
2015 IECC Energy
Efficiency Certificate
Insulation Rating R-Value
21.00Above-Grade Wall
19.00Below-Grade Wall
10.00Floor
49.00Ceiling / Roof
_______Ductwork (unconditioned spaces):
Glass & Door Rating SHGCU-Factor
0.32Window
0.32Door
Heating & Cooling Equipment Efficiency
_______Heating System:_________________________
_______Cooling System:_________________________
_______Water Heater:___________________________
Name:Date:
Comments
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Project Summary Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844Email: mike@homesbykingswood.com
Town of Estes Park
IECC 2015
Site Elevation 7598
Notes:
Design Information
Fort Collins SAWRS, CO, USWeather:
Winter Design Conditions Summer Design Conditions
Outside db °F4 Outside db °F89Inside db °F72 Inside db °F75
Design TD °F68 Design TD °F14Daily range M
Relative humidity %50Moisture difference gr/lb-24
Heating Summary Sensible Cooling Equipment Load Sizing
Structure Btuh26133 Structure Btuh17626
Ducts Btuh0 Ducts Btuh0Central vent (SER=62% 60 cfm)Btuh1286 Central vent (SER=62% 60 cfm)265 Btuh
Energy recovery Energy recoveryHumidificationBtuh0Blower Btuh0
Piping Btuh0Equipment load Btuh27419 Use manufacturer's data y
Rate/swing multiplier 1.00InfiltrationEquipment sensible load Btuh17891
Method Latent Cooling Equipment Load SizingBlower door
Shielding / stories 3 (partial) / 150 Pa / 3.0 / 949 cfmPressure /ACH /AVF Structure Btuh571
Ducts Btuh0Central vent (LER=50% 60 cfm)-374 Btuh
CoolingHeating Energy recovery28752875Area (ft²)Equipment latent load Btuh198
1898218982Volume (ft³)Air changes/hour 0.110.23 Equipment Total Load (Sen+Lat)Btuh18088
Equiv. AVF (cfm)3471 Req. total capacity at 0.85 SHR ton1.8
Heating Equipment Summary Cooling Equipment Summary
Make Carrier Make CarrierTradeCarrier Comfort 95 Single-Stag...Trade CARRIER
Model 59SC5B060E17--14 Cond 24AAA530A00300AHRI ref 0 Coil CNPVP3621ALA+59SC5B060E17--14
AHRI ref 203074827Efficiency96.5 AFUE Efficiency 12.5 EER, 15 SEER
Heating input Btuh60000 Sensible cooling Btuh23630Heating output Btuh40600 Latent cooling Btuh4170
Temperature rise °F55 Total cooling Btuh27800Actual air flow cfm885 Actual air flow cfm927
Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.053Static pressure in H2O1.00 Static pressure in H2O1.00
Space thermostat Load sensible heat ratio 0.99
PERMIT #22-EP-00438
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
ENERGY REPORTS ARE REVIEWED
TO VERIFY EQUIVALENCY WITH
PLANS & OTHER REPORTS - BY
SAFEBUILT - PBLAND
CONTRACTOR IS RESPONSIBLE TO MAKE SURE ALL
ENERGY REPORTS - RESCHECK & MANUAL JDS - TO
MATCH PLANS AND FIELD INSTALLATIONS - AND ARE
PROVIDED FOR INSPECTORS REVIEW AT INSPECTIONS
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Load Short Form Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
Design Information
InfiltrationClgHtg
Blower doorMethod894Outside db (°F)
3 (partial) / 1Shielding / stories7572Inside db (°F)
50 Pa / 3.0 / 949 cfmPressure /ACH /AVF1468Design TD (°F)
M-Daily range
5030Inside humidity (%)
-2439Moisture difference (gr/lb)
HEATING EQUIPMENT COOLING EQUIPMENT
Make Carrier Make Carrier
Trade Carrier Comfort 95 Single-Stag...Trade CARRIER
Model 59SC5B060E17--14 Cond 24AAA530A00300
AHRI ref 0 Coil CNPVP3621ALA+59SC5B060E17--14
AHRI ref 203074827
Efficiency 96.5 AFUE Efficiency 12.5 EER, 15 SEER
Heating input Btuh60000 Sensible cooling Btuh23630
Heating output Btuh40600 Latent cooling Btuh4170
Temperature rise °F55 Total cooling Btuh27800
Actual air flow cfm885 Actual air flow cfm927
Air flow factor cfm/Btuh0.034 Air flow factor cfm/Btuh0.053
Static pressure in H2O1.00 Static pressure in H2O1.00
Space thermostat Load sensible heat ratio 0.99
ROOM NAME Area Htg load Clg load Htg AVF Clg AVF
(ft²)(Btuh)(Btuh)(cfm)(cfm)
Unfin Basement 335 1599 197 54 10
Storage/Mech 113 708 10 24 1
Hall/Stairs 93 365 4 12 0
W/D 24 0 0 0 0
B Kitchen 191 274 1498 9 79
B Bath 57 321 272 11 14
B Bedroom 201 2095 781 71 41
Office 150 2076 1060 70 56
B Living 267 3231 2400 109 126
Dining 156 2466 1611 84 85
Kitchen 157 1414 1601 48 84
Mud/Laun 55 969 823 33 43
Foyer 81 704 215 24 11
Bedroom 152 2093 1012 71 53
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Bold/italic values have been manually overridden
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 2
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
Bath 48 80 53 3 3
M Bath 81 1014 386 34 20
M WIC 39 0 0 0 0
M Bed 177 2463 1350 83 71
Living 499 4260 4353 144 229
Entire House 2875 26133 17626 885 927
Other equip loads 1286 265
Equip. @ 1.00 RSM 17891
Latent cooling 198
TOTALS 2875 27419 18088 885 927
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Bold/italic values have been manually overridden
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Building Analysis Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
Design Conditions
Location:CoolingHeatingIndoor:
7572Indoor temp era ture (°F)Fort Collins SAWRS, CO, US
1468Design TD (°F)ft7597Elevation:
5030Relative humidity (%)°N41Latitude:
Outdoor:-24.339.3Moisture difference (gr/lb)CoolingHeating
Infiltration:894Dry bul b (°F)
Blower doorMethod)M(20-Da ily ra nge (°F)
3 (partial) / 1Shielding / stories61-We t bu lb (°F)
50 Pa / 3.0 / 949 cfmPressure /ACH /AVF7.515.0Wind speed (mph)
Heating
Walls
Glazing
Other
Ceilings
Floors
Infiltration
Ventilation
% of loadBtuhBtuh/ft²Component
33.792323.7Walls
27.8762021.8Glazing
1.952113.8Doors
7.420391.4Ceilings
9.826881.91.9Floors
14.740332.2Infiltration
00Ducts
00Piping
00Humidification
4.71286Ventilation0Adjustments
100.027419Total
Cooling
Walls
Glazing
Other Ceilings
Infiltration
Internal Gains
% of loadBtuhBtuh/ft²Component
7.813960.6Walls
40.9731120.9Glazing
1.11965.2Doors
8.214691.0Ceilings
0.040.0Floors
2.24000.2Infiltration
00Ducts
1.5265Ventilation
38.36850Internal gains
00Blower
0Adjustments
100.017891Total
Latent Cooling Load = 198 Btuh
Overall U-va lue = 0.0 56 Btuh/ft²-°F
Data entries checked.
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Bold/italic values have been manually overridden
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Component Constructions Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
Design Conditions
Location:CoolingHeatingIndoor:
7572Indoor temp era ture (°F)Fort Collins SAWRS, CO, US
1468Design TD (°F)ft7597Elevation:
5030Relative humidity (%)°N41Latitude:
Outdoor:-24.339.3Moisture difference (gr/lb)CoolingHeating
Infiltration:894Dry bul b (°F)
Blower doorMethod)M(20-Da ily ra nge (°F)
3 (partial) / 1Shielding / stories61-We t bu lb (°F)
50 Pa / 3.0 / 949 cfmPressure /ACH /AVF7.515.0Wind speed (mph)
Construction descriptions GainLossClg HTMHtg HTMInsul RU-valueAreaOr
BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft²
Walls
12F-0sw: Frm wall, wd ext, 1/2" wood shth, r-21 cav ins, 1/2" gypsum
board int fnsh, 2"x6" wood frm, 16" o.c. stud
4790.9322774.4221.00.065515ne
2720.9312944.4221.00.065293se
1950.939294.4221.00.065210sw
3260.9315524.4221.00.065351nw
12730.9360534.4221.00.0651369all
15B19-0wc-8: Bg wall, heavy dry or light damp soil, 2"x4" wood int frm,
concrete wall, r-19 cav ins, 8" thk, 1/2" gypsum board int fnsh
00.0482.8519.00.0403ne
70.044542.8519.00.040159se
70.044532.8519.00.040159sw
30.033102.7619.00.040113nw
180.0412252.8319.00.040433all
DftBelowGradeWall: Bg wall, heavy dry or light damp soil, concrete
wall, r-19 ins, 8" thk
30.032222.2519.00.03299se
70.035272.2519.00.032234sw
40.033102.2519.00.032137nw
150.0310592.2519.00.032470all
Partitions
12F-0sw: Frm wall, 5/8" gyp.bd ext, 1/2" wood shth, r-21 cav ins, 1/2"
gypsum board int fnsh, 2"x6" wood frm, 16" o.c. stud
910.458954.4221.00.065202
Windows
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een;
2.75 ft head ht
25121.026121.800.32012ne
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een;
6.67 ft head ht
50321.052221.800.32024ne
83821.087021.800.32040ne
31426.226121.800.32012se
54521.056621.800.32026nw
12621.013121.800.3206nw
232621.5235021.800.320108all
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een;
9.67 ft head ht
37721.039221.800.32018ne
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Bold/italic values have been manually overridden
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 2
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een; 1.5
ft overhang (4 ft window ht, 0.5 ft sep.); 6.67 ft head ht
50321.052221.800.32024ne
40420.243521.800.32020sw
90620.695721.800.32044all
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een; 10
ft overhang (4 ft window ht, 2 ft sep.); 6.67 ft head ht
24421.025421.800.32012ne
25121.026121.800.32012ne
50321.052221.800.32024ne
99921.0103721.800.32048all
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een;
8.75 ft head ht
72321.075121.800.32035ne
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een; 1.5
ft overhang (6.67 ft window ht, 0.5 ft sep.); 6.67 ft head ht
83821.087021.800.32040ne
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een; 10
ft overhang (6.67 ft window ht, 2 ft sep.); 6.67 ft head ht
83821.087021.800.32040ne
DftWind: 2 glazing, clr low-e, u 0.320, SHGC 0.40; NFRC rated
(SHGC=0.40 ); 50% blin ds 4 5°, medium; 50% out door insec t scr een; 7 f t
overhang (3 ft window ht, 1 ft sep.); 6.67 ft head ht
528.7313121.800.3206sw
Doors
DftDoor: Door, wd sc type 1045.1827613.800.20320sw
925.1824513.800.20318n
1965.1852113.800.20338all
Ceilings
DftCeil: Attic ceiling, asphalt shingles roof mat, r-49 ceil ins, 1/2" gypsum
board int fnsh
14691.0020391.3949.00.0201464
Floors
20P-30w: Flr floor, frm flr, 12" thkns, hrd wd flr fnsh, r-30 cav ins, amb
ovr
40.31292.3830.00.03512
21A-32t: Bg floor, heavy dry or light damp soil, 8' depth 00.020335 004551.36
21A-32w: Bg floor, heavy dry or light damp soil, 8' depth, hrd wd flr
fnsh
013711.3600.0201008 0
DftBGFlor: Bg floor, heavy dry or light damp soil, on grade depth, r-10
edge ins, hrd wd flr fnsh
0083324.110.00.35535
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Bold/italic values have been manually overridden
2022-Aug-09 13:41:31
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:AED Assessment Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
Design Conditions
Location:CoolingHeatingIndoor:
7572Indoor temp era ture (°F)Fort Collins SAWRS, CO, US
1468Design TD (°F)ft7597Elevation:
5030Relative humidity (%)°N41Latitude:
Outdoor:-24.339.3Moisture difference (gr/lb)CoolingHeating
Infiltration:894Dry bul b (°F)
)M(20-Da ily ra nge (°F)
61-We t bu lb (°F)
7.515.0Wind speed (mph)
Test for Adequate Exposure Diversity
Hourly Glazing Load
Hourly Average AE D limit
Gl
a
z
i
n
g
l
o
a
d
(
B
t
u
h
)
Hour of Day
0
1,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
8 9 10 11 12 13 14 15 16 17 18 19 20
Maximum hourly glazing load exceeds average by 10.7%.
House has adequate exposure diversity (AED), based on AED limit of 30%.
AED excursion: 0 Btuh
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
2022-Aug-09 13:41:33
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Manual S Compliance Report Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
Cooling Equipment
Design Conditions
°F75.4Entering coil DB:Btuh17891Sensible gain:°F89.0Outdoor design DB:
°F61.3Entering coil WB:Btuh198Latent gain:°F61.0Outdoor design WB:
Btuh18088Total gain:°F75.0Indoor design DB:
cfm927Estimated airflow:%50Indoor RH:
Manufacturer's Performance Data at Actual Design Conditions
Split ACEquipment type:
24AAA530A00300+CNPVP3621ALA+59SC5B060E17--14Model:CarrierManufacturer:
cfm927Actual airflow:
% of load102Btuh18311Sensible capacity:
% of load733Btuh1450Latent capacity:
%93SHR:% of load109Btuh19761Total capacity:
Heating Equipment
Design Conditions
°F70.2Entering coil DB:Btuh27419Heat loss:°F4.0Outdoor design DB:
°F72.0Indoor design DB:
Manufacturer's Performance Data at Actual Design Conditions
Gas furnaceEquipment type:
59SC5B060E17--14Model:CarrierManufacturer:
cfm885Actual airflow:
°F55Temp. rise:% of load148Btuh40600Output capacity:
Meets all requirements of ACCA Manual S.
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Job #: 133 Stanley Circle Dr_ManJSD_080...
Performed by Mark Scott for:
Mike Kingswood
133 Stanley Circle Dr
Estes Park, CO 80517
Phone: 970-214-8844
mike@homesbykingswood.com
Scale: 1 : 85
Page 1
Ri ght -Sui te ® U ni versa l 20 22
22.0.04 RSU20525
2022-Aug-09 13:42:21
...nley Circle Dr_ManJSD_080922.rup
N
Main Floor
Dining
Kitchen
Mud/LaunFoyer
Bedroom
Bath
M Bath
M WIC
M Bed
Living
Garage
71 cfm
24 cfm 43 cfm
83 cfm
84 cfm
85 cfm
114 cfm 114 cfm
3 cfm
34 cfm
Ret Riser
12 x 8
394 cfm
206 cfm
Ret Riser
8 x 6
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Job #: 133 Stanley Circle Dr_ManJSD_080...
Performed by Mark Scott for:
Mike Kingswood
133 Stanley Circle Dr
Estes Park, CO 80517
Phone: 970-214-8844
mike@homesbykingswood.com
Scale: 1 : 85
Page 2
Ri ght-Sui te ® Uni versa l 20 22
22.0.04 RSU20525
2022-Aug-09 13:42:21
...nley Circle Dr_ManJSD_080922.rup
N
Basement
Unfin Basement
Storage/Mech
Hall/StairsW/D
B Kitchen
B Bath
B Bedroom
Office
B Living
Ret Riser
12 x 8
63 cfm 63 cfm
12 cfm
14 cfm
79 cfm
107 cfm
271 cfm
4 x 6
16 x 1210 x 6
12 x 8
Ret Riser
8 x 6
8 x 6
70 cfm
24 cfm
5 "
14 x 12
4 "
5 "5 "
4 "
5 "6 "
5 "
6 "5 "
71 cfm
4 "
6 "
5 "
5 "
4 "
54 cfm
5 "
4 "5 "
10 x 12
4 "10 x 128 x 12
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
2022-Aug-09 13:41:33
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Duct System Summary Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
CoolingHeating
External static pressure in H2O1.00in H2O1.00
Pressure losses in H2O0.30in H2O0.30
Available static pressure in H2O0.70in H2O0.70
Supply / return available pressure 0.350 / 0.349 in H2O in H2O0.350 / 0.349
Lowest friction rate in/100ft0.118in/100ft0.118
Actual air flow cfm927cfm885
Total effective length (TEL)ft592
Supply Branch Detail Table
Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv
Name (Btuh)(cfm)(cfm)FR (in)(in)Matl Ln (ft)Ln (ft)Trunk
st1A185.022.5ShMt0x05.00.1697991498cB Kitchen
st1B190.040.8ShMt0x04.00.1521411272cB Bath
st1B200.054.0ShMt0x05.00.13841712095hB Bedroom
st1A170.042.3ShMt0x05.00.16563551200cB Living
st1A195.034.8ShMt0x05.00.15263551200cB Living-A
st1B210.039.3ShMt0x04.00.1403353cBath
st1B195.055.3ShMt0x05.00.14053712093hBedroom
st1160.022.8ShMt0x05.00.19185841611cDining
st1B210.041.3ShMt0x04.00.1391124704hFoyer
st1A200.013.0ShMt0x04.00.164012365hHall/Stairs
st1180.04.8ShMt0x05.00.18984481601cKitchen
st1A180.042.8ShMt0x06.00.157114722177cLiving
st1A190.036.5ShMt0x06.00.154114722177cLiving-A
st1B180.044.8ShMt0x04.00.15620341014hM Bath
st1B205.054.5ShMt0x06.00.13571832463hM Bed
st1B250.046.3ShMt0x05.00.1184333823cMud/Laun
st1170.019.8ShMt0x05.00.18456702076hOffice
st1175.04.8ShMt0x04.00.195124708hStorage/Mech
st1B210.047.0ShMt0x05.00.13610541599hUnfin Basement
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
2022-Aug-09 13:41:33
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 2
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
Supply Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
st1B Peak AVF 384 268 0.118 576 9.3 8x12 ShtMetl st1A
st1A Peak AVF 659 702 0.118 842 11.7 10x12 ShtMetl st1
st1 Peak AVF 885 927 0.118 795 12.9 14x12 ShtMetl
Return Branch Detail Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size (in)(cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in)Matl Trunk
rb3 0x 1900 206 295.8 0.118 617 7.4 x6 8 ShMt rt1A
rb1 0x 2550 271 221.8 0.157 650 7.7 x6 10 ShMt rt1A
rb4 0x 1070 56 95.3 0.367 640 4.6 x6 4 ShMt rt1
rb2 0x 3340 394 133.8 0.261 591 8.0 x8 12 ShMt rt1
Return Trunk Detail Table
Trunk Htg Clg Design Veloc Diam H x W Duct
Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk
rt1A Peak AVF 445 476 0.118 572 10.1 10x12 ShtMetl rt1
rt1 Peak AVF 885 927 0.118 695 12.9 16x12 ShtMetl
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
2022-Aug-09 13:41:33
Rig ht-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1
..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_M...Job:Static Pressure and Friction Rate Aug 09, 2022Date:Entire House Mark ScottBy:
Project Information
Mike Kingswood, Kingswood HomesFor:
133 Stanley Circle Dr, Estes Park, CO 80517
Phone: 970-214-8844
Email: mike@homesbykingswood.com
Available Static Pressure
CoolingHeating
(in H2O)(in H2O)
1.001.00External static pressure
Pressure losses
0.110.11Coil
00Heat exchanger
0.030.03Supply diffusers
0.030.03Return grilles
0.100.10Filter
00Humidifier
0.030.03Balancing damper
00Other device
0.700.70Available static pressure
Total Effective Length
ReturnSupply
(ft)(ft)
1619Measured length of run-out
4027Measured length of trunk
240250Equivalent length of fittings
296296Total length
592Total effective length
Friction Rate
CoolingHeating
(in/100ft)(in/100ft)
OK0.118OK0.118Supply Ducts
OK0.118OK0.118Return Ducts
Fitting Equivalent Length Details
4AJ=25, 8AA=20, 8AA=20, 2J5=80, 12O1=10, 12O1=10, 1H2=85: TotalEL=250Supply
6C6=115, 6H=15, 8E=10, 6CB=25, 12F1=20, 6AB=25, 5K=10, 8E=10, 6CA=10: TotalEL=240Return
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 1..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name Entire House Unfin Basement
2 Exposed wall 337.0 ft 54.8 ft
3 Room height 8.5 ft 8.6 heat/coolft
4 Room dimensions ft334.9x1.0
5 Room area 2875.3 f t²334.9 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 795 515 2277 479 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 12 0 261 251 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 24 0 522 503 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 18 0 392 377 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 24 0 522 503 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 12 0 254 244 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 12 0 261 251 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 24 0 522 503 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 35 0 751 723 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 40 0 870 838 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 40 0 870 838 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 40 0 870 838 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 3 3 8 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 305 293 1294 272 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 12 0 261 314 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 159 159 454 7 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 99 99 222 3 99 99 222 3
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 256 210 929 195 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 6 12 131 52 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 20 14 435 404 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 20 20 276 104 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 159 159 453 7 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 234 234 527 7 234 234 527 7
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 377 351 1552 326 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 26 0 566 545 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 119 113 310 3 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 6 0 131 126 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 137 137 310 4 137 137 310 4
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 220 202 895 91 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 18 18 245 92 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 1464 1464 2039 1469 0 0 0 0
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 12 12 29 4 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 335 335 455 0 335 335 455 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 1008 1008 1371 0 0 0 0 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 88 34 833 0 0 0 0 0
6 c) AED excursion 0 -2
Envelope loss/gain 22100 10376 1515 13
12 a)Infiltration 4033 400 72 7
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 5 1150 0 0
Appliances/other 5700 0
Subtotal (lines 6 to 13)26133 17626 1586 20
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 13 177
14 Subtotal 26133 17626 1599 197
15 Duct loads 0%0%0 0 -0%0%0 0
Total room load 26133 17626 1599 197
Air required (cfm)Air required (cfm)885 927 54 10
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 2..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name Storage/Mech Hall/Stairs
2 Exposed wall 21.5 ft 9.3 ft
3 Room height 8.6 heat/coolft 8.6 heat/coolft
4 Room dimensions ft12.3x9.3 ft93.3x1.0
5 Room area 113.3 f t²93.3 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 105 105 300 5 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 79 79 226 4 79 79 226 4
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 0 0 0 0 0 0 0 0
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 113 113 154 0 93 93 127 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion -1 0
Envelope loss/gain 680 7 353 3
12 a)Infiltration 28 3 12 1
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)708 10 365 4
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 708 10 365 4
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 708 10 365 4
Air required (cfm)Air required (cfm)24 1 12 0
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 3..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name W/D B Kitchen
2 Exposed wall 0 ft 0 ft
3 Room height 8.6 heat/coolft 8.6 heat/coolft
4 Room dimensions ft6.0x4.0 ft191.1x1.0
5 Room area 24.0 f t²191.1 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 0 0 0 0 0 0 0 0
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 24 24 33 0 191 191 260 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion -44 -126
Envelope loss/gain 33 -44 260 -126
12 a)Infiltration 0 0 0 0
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 1 230
Appliances/other 500 1200
Subtotal (lines 6 to 13)33 456 260 1304
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution -33 -456 14 194
14 Subtotal 0 0 274 1498
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 0 0 274 1498
Air required (cfm)Air required (cfm)0 0 9 79
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 4..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name B Bath B Bedroom
2 Exposed wall 5.3 ft 29.3 ft
3 Room height 8.6 heat/coolft 8.6 heat/coolft
4 Room dimensions ft57.0x1.0 ft200.8x1.0
5 Room area 57.0 f t²200.8 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 0 0 0 0 125 101 447 94
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 24 0 522 503
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 1 1 4 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 0 0 0 0 51 51 225 47
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 45 39 100 0 74 74 210 3
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 6 0 131 126 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 0 0 0 0 0 0 0 0
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 57 57 78 0 174 174 236 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 27 2 44 0
6 c) AED excursion 60 93
Envelope loss/gain 308 186 1688 741
12 a)Infiltration 7 1 407 40
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)315 186 2095 781
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 6 85 0 0
14 Subtotal 321 272 2095 781
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 321 272 2095 781
Air required (cfm)Air required (cfm)11 14 71 41
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 5..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name Office B Living
2 Exposed wall 24.5 ft 23.0 ft
3 Room height 8.6 heat/coolft 8.6 heat/coolft
4 Room dimensions ft12.3x12.3 ft14.3x18.8
5 Room area 150.1 f t²267.2 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 104 80 352 74 161 97 430 90
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 12 0 254 244
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 12 0 261 251
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 24 0 522 503 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 40 0 870 838
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 1 1 4 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 51 51 226 48 17 17 76 16
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 54 54 154 2 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 0 0 0 0 19 19 85 18
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 0 0 0 0 0 0 0 0
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 126 126 171 0 230 230 313 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 24 12 290 0 37 21 499 0
6 c) AED excursion -103 -232
Envelope loss/gain 1720 524 2788 1226
12 a)Infiltration 356 35 443 44
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 1 230
Appliances/other 500 900
Subtotal (lines 6 to 13)2076 1060 3231 2400
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2076 1060 3231 2400
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 2076 1060 3231 2400
Air required (cfm)Air required (cfm)70 56 109 126
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 6..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name Dining Kitchen
2 Exposed wall 25.0 ft 26.8 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft12.8x12.3 ft157.0x1.0
5 Room area 156.2 f t²157.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 99 59 261 55 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 40 0 870 838 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 103 91 402 85 95 95 420 88
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 12 0 261 314 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 0 0 0 0 4 4 18 4
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 121 121 536 54
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 156 156 218 157 157 157 219 158
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion -113 -155
Envelope loss/gain 2012 1336 1192 149
12 a)Infiltration 454 45 222 22
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 1 230 1 230
Appliances/other 0 1200
Subtotal (lines 6 to 13)2466 1611 1414 1601
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 2466 1611 1414 1601
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 2466 1611 1414 1601
Air required (cfm)Air required (cfm)84 85 48 84
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 7..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name Mud/Laun Foyer
2 Exposed wall 14.5 ft 7.5 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft9.5x5.8 ft80.5x1.0
5 Room area 54.6 f t²80.5 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 46 40 179 38 61 41 179 38
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 6 6 131 52 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 20 20 276 104
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 71 53 234 24 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 18 18 245 92 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 55 55 76 55 81 81 112 81
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion 52 -21
Envelope loss/gain 865 313 568 201
12 a)Infiltration 104 10 136 13
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 500 0
Subtotal (lines 6 to 13)969 823 704 215
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 0 0
14 Subtotal 969 823 704 215
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 969 823 704 215
Air required (cfm)Air required (cfm)33 43 24 11
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 8..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name Bedroom Bath
2 Exposed wall 28.5 ft 0 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft151.5x1.0 ft5.5x8.8
5 Room area 151.5 f t²48.1 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 22 22 98 21 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 113 93 412 87 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 20 7 435 404 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 95 95 420 88 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 152 152 211 152 48 48 67 48
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion 210 -4
Envelope loss/gain 1576 961 67 44
12 a)Infiltration 517 51 0 0
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)2093 1012 67 44
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 0 0 13 9
14 Subtotal 2093 1012 80 53
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 2093 1012 80 53
Air required (cfm)Air required (cfm)71 53 3 3
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 9..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name M Bath M WIC
2 Exposed wall 14.0 ft 0 ft
3 Room height 8.1 heat/coolft 8.1 heat/coolft
4 Room dimensions ft12.0x6.8 ft6.5x6.0
5 Room area 81.0 f t²39.0 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 8 8 36 8 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 8 8 36 8 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 97 91 402 85 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 6 0 131 126 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 81 81 113 81 39 39 54 39
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 12 12 29 4 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion 42 -3
Envelope loss/gain 745 352 54 36
12 a)Infiltration 254 25 0 0
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 0 0
Appliances/other 0 0
Subtotal (lines 6 to 13)999 377 54 36
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 14 9 -54 -36
14 Subtotal 1014 386 0 0
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 1014 386 0 0
Air required (cfm)Air required (cfm)34 20 0 0
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed.
2022-Aug-09 13:41:31Right-Su ite® U niv er sal 20 22 22 .0.04 RSU2 0525 Page 10..._080922\133 Stanley Circle Dr_ManJSD_080922.rup Calc = MJ8 Front Door faces: SW
133 Stanley Circle Dr_ManJ...Job:Right-J® W or ksheet Aug 09, 2022Date:Entire House Mark ScottBy:
1 Room name M Bed Living
2 Exposed wall 26.8 ft 26.5 ft
3 Room height 8.1 heat/coolft 9.3 heat/coolft
4 Room dimensions ft12.0x14.8 ft498.7x1.0
5 Room area 177.0 f t²498.7 f t²
Ty Construction U-value Or HTM Area (f t²)Load Area (f t²)Load
number (Bt uh/f t²-°F)(Bt uh/f t²-°F)(Bt uh/f t²)(Bt uh/f t²)or perimeter (ft)(Btuh)or perimeter (ft)(Btuh)
Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool
6 WW 12F-0sw12F-0sw 0.0650.065 nene 4.424.42 0.930.93 119 95 421 88 179 75 331 70
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 12 0 261 251
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
.GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 18 0 392 377
1 1 GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 24 0 522 503 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 35 0 751 723
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 40 0 870 838
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nene 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nene 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 sese 4.424.42 0.930.93 0 0 0 0 16 16 71 15
GG DftWindDftWind 0.3200.320 sese 21.7621.76 26.1726.17 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 sese 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 sese 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 swsw 4.424.42 0.930.93 0 0 0 0 24 24 106 22
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 8.738.73 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 swsw 21.7621.76 20.1820.18 0 0 0 0 0 0 0 0
DD DftDoorDftDoor 0.2030.203 swsw 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 swsw 2.852.85 0.040.04 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 swsw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
WW 12F-0sw12F-0sw 0.0650.065 nwnw 4.424.42 0.930.93 97 77 340 72 18 18 80 17
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 20 0 435 419 0 0 0 0
WW 15B19-0wc-815B19-0wc-8 0.0690.069 nwnw 2.762.76 0.030.03 0 0 0 0 0 0 0 0
GG DftWindDftWind 0.3200.320 nwnw 21.7621.76 20.9520.95 0 0 0 0 0 0 0 0
WW DftBelowGradeWall 0.049DftBelowGradeWall0.049 nwnw 2.252.25 0.030.03 0 0 0 0 0 0 0 0
PP 12F-0sw12F-0sw 0.0650.065 --4.424.42 0.450.45 0 0 0 0 28 28 125 13
DD DftDoorDftDoor 0.2030.203 nn 13.8013.80 5.185.18 0 0 0 0 0 0 0 0
CC DftCeilDftCeil 0.0200.020 --1.391.39 1.001.00 177 177 246 178 519 519 723 521
FF 20P-30w20P-30w 0.0350.035 --2.382.38 0.310.31 0 0 0 0 0 0 0 0
FF 21A-32t21A-32t 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF 21A-32w21A-32w 0.0200.020 --1.361.36 0.000.00 0 0 0 0 0 0 0 0
FF DftBGFlorDftBGFlor 0.5750.575 --24.1424.14 0.000.00 0 0 0 0 0 0 0 0
6 c) AED excursion 34 314
Envelope loss/gain 1965 1293 3712 3161
12 a)Infiltration 485 48 534 53
b)Room ventilation 0 0 0 0
13 Internal gains:Occupants @ 230230 0 0 1 230
Appliances/other 0 900
Subtotal (lines 6 to 13)2450 1341 4246 4344
Less external loadLess external load 0 0 0 0
Less transferLess transfer 0 0 0 0
RedistributionRedistribution 13 9 14 9
14 Subtotal 2463 1350 4260 4353
15 Duct loads -0%0%0 0 -0%0%0 0
Total room load 2463 1350 4260 4353
Air required (cfm)Air required (cfm)83 71 144 229
PERMIT #22-EP-00438 - Field Copy
REVIEWED BY SAFEBUILT - PBLAND