Deck Design Document
for
3 Square Construction LLC
for
890 Elk Meadow Court
Estes Park, CO 80517
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Plan View
All work shall be performed by Licensed
Contractors OR work shall be performed
by the homeowner residing in the dwelling
PLANS AND CONSTRUCTION SHALL
MEET THE 2015 IRC AND ALL
APPLICABLE MUNICIPAL CODES &
ORDINANCES
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
3D View
Dimension View - Deck 2
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
Wood materials used to be Preservative-treated or
approved Naturally durable wood in accordance with
Section R317 & AWPA U1 - Unless noted otherwise
on this drawing
Plastic composite decking, treads and handrail to comply with
R507.2.2 & ASTM D7032.
Verify composite decking can span the required joist spacing
Caisson to be min. 30" below grade
OPEN HOLE INSPECTION REQUIRED
BEFORE CAISSON CONCRETE IS POURED
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Post View – Deck 1
Post View - Deck 2
Post
View -
Deck 2
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Joist Layout View
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
1 .
2 .
3 .
. 4
5 .
6 .
. 7
8 .
. 9
. 10
. 11
12 .
. 13
Riser - A board attached to the vertical cut surface of a stair stringer.
Stringer - The diagonal board used to support treads and risers on a stairway.
Tread - The horizontal surface of a stair.
Fascia - Vertical boards that face outwards from the edges of the deck, attached to the
rim joists.
Top Rail - The upper horizontal piece that connects rail posts and supports balusters.
Bottom Rail - The lower horizontal piece that connects rail posts and supports
balusters.
Baluster - The vertical pieces of a railing spaced at regular intervals between posts.
Rail Cap - The top horizontal trim on railing.
Rail Post - The vertical post connected to the deck framing that supports the railing.
Decking -The boards used to make the walking surface of the deck.
Post - Footer Concrete filled hole that the post is attached to.
Joist - A horizontal frame piece that supports the decking and spreads the weight over
the beams.
Beam - A horizontal framing piece, which rests on posts and supports joists.
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Railing Details View
NOTE: Customer has selected pre-constructed powder coated aluminum railing.
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Deck Information
Deck 1 Deck 2
Construction Method Beam Flush With Joist Beam Flush With Joist
Footing Type Pier In-Ground Pier In-Ground
Live Load 60 100
Dead Load 10 10
Decking Spacing 1/8 in 1/8 in Joist Spacing
Joist Spacing 12 in 12 in
Beam Spacing 192 in 96 in
Post Spacing 56 1/2 in 58 5/32 in
Decking L5/4x6 RedTone PT Southern
Pine Select L5/4x6 RedTone PT Southern Pine Select
Beams L2x8 RedTone PT Southern
Pine No. 1 Joists L2x8 RedTone PT Southern Pine No. 1
L2x10 RedTone PT Southern
Pine No. 1 L2x6 RedTone PT Southern Pine No. 1
Posts L4x4 Treated SOLumber No. 2 L4x4 Treated SOLumber No. 2
Deck Height 60 in 60 in
Diagonal Bracing Yes Yes
Joist Overhang 0 in 0 in
Beam Overhang 0 in 0 in
Decking Deflection Factor 360 360
Joist Deflection Factor 360 360
Beam Deflection Factor 360 360
Pref Decking Size 5/4x6 Pref Joist Size 5/4x6 Pref Joist Size
Pref Beam Size NONE NONE
Pref Post Size NONE NONE
Diag Brace Height 1 24 in 24 in
Diag Brace Height 2 24 in 24 in
Railing Height 36 in
Baluster Spacing 3 3/4 in
Toe Space 3 3/4 in
Railing Height 36 in
Baluster Spacing 3 3/4 in
Toe Space 3 3/4 in
Railing Height 36 in
Baluster Spacing
Toe Space 3 3/4 in
Railing Height 36 in
Baluster Spacing 3 3/4 in
Toe Space 3 3/4 in
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Material List
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
SEE ENGINEERS PLANS FOR ALL
STRUCTURAL REQUIREMENTS
Cost Estimate
Category Cost Code Title Cost Type Unit Cost Quantity Price
1000 -
Preparation
Preliminaries
1010 - Permits Obtain Permits Labor $150.00 1. $150.00
1000 -
Preparation
Preliminaries
1050 - Architecture Deck Layout &
Drawings
Labor $550.00 1. $550.00
2000 - Excavation
& Foundations
2250 - Foundation Labor Install Foundation
Footings
Labor $325.00 14. $4,550.00
3000 - Rough
Structure
3100 - Framing Labor Install Deck Framing Labor $11.00 602. $3,480.00
3000 - Rough
Structure
3100 - Framing Labor Install Framing for
Exterior Door
Labor $605.00 1. $605.00
5000 - Exterior
Finishes
5250 - Exterior Door Labor Install Exterior Door
and Jamb
Labor $445.00 1. $445.00
5000 - Exterior
Finishes
5999 - Exterior Finish
Specialties
Install Composite
Decking
Labor $26.00 602. $15,652.00
$25,432.00
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
Design Criteria
1. Building code:
1.1 Model building code: 2015 IRC
1.2 Town of Estes Park Amendments
2. Dead loads:
2.1 Roof total 15 psf
2.2 Floor 10 psf
2.3 Walls 10 psf
3. Live loads
3.1 Residential 40 psf
3.2 Roof 20 psf
4. Snow loads
4.1 Ground Snow Load 70 psf
5. Wind Design Data
6.1 Exposure Category C
6.2 Wind Speed V = 175 mph Ultimate
6.3 Occupancy Cat. Iw = 2
General notes:
1. Construction documents are valid for a single use at the project location and shall not be reused, copied, or reproduced without
written approval of the registered design professional in reasonable charge.
2. General notes and typical details are provided as a supplement to the construction documents and apply where specific notes
and details are not available. Specific notes and structural details shall take precedence over general notes and typical details.
Structural requirements shown in the framing plans and in the structural shall take precedence over structural notes indicated in
architectural sections.
3. Printed dimensions shall take precedence over scales shown on construction documents. The registered design professional in
reasonable charge does not warrant the accuracy of scaled dimensions.
4. Approval by the inspector does not imply approval by the registered design professional in reasonable charge. Structural
specifications that are unclear or ambiguous shall be referred to the registered design professional in reasonable charge for
interpretation or clarification.
5. The contractor is responsible for the methods, means and sequence of all structural erection except when specifically noted
otherwise in the construction documents. The contractor shall provide temporary shoring and bracing, providing adequate
vertical and lateral support during erection. Shoring and bracing shall remain in place until all permanent members are placed and
all final connections are completed.
6. The contractor is responsible for standard connections unless notes otherwise. The contractor shall obtain additional assistance
from the registered design professional in reasonable charge for all non-standard connections.
7. The contractor agrees that, in accordance with generally accepted construction practices, the contractor will be required to
assume sole and complete responsibility for job site conditions during the course of construction of the project, including safety of
all persons and property. This requirement shall be made to apply continuously and not be limited to normal working hours. The
contractor further agrees to defend, indemnify and hold owner and engineer harmless from any and all liability, real or alleged, in
connection with the performance of work on this project, exempting liability arising from the sole negligence of engineer.
Disclaimer:
1. In as much as the site review of an existing structure for the purpose of observing the structure conditions requires
that certain assumptions be made regarding existing conditions and because some of these assumptions may not be
verifiable without expending additional sums of money or destroying otherwise adequate or serviceable portions of the
building, the Client agrees that, except for negligence on the part of the Engineer, the Client will hold harmless, indemnify
and defend Engineer from and against any and all claims arising out of the professional services we have provided.
Concrete
1. Concrete materials, quality control and construction shall comply with IRC Chapter 4 and ACI 318.
2. Compressive strength (minimum specified at 28 days)
2.1 Footing 3500 psi
2.2 Wall 3500 psi
2.3 Slab 3500 psi
3. Materials
3.1 Cements (ASTM C 150) Concrete exposed to freezing and thawing or deicing chemicals shall conform to the maximum
water-cementitious material ratio and minimum compressive strength requirements of ACI 318 table 4.3.1.
3.2 Aggregates (ASTM C 33) nominal maximum size of course aggregates shall conform
3.3 Water used in mixing concrete shall be potable and clean. Steel
3.4 Deformed Bars: fy =60 ksi (ASTM A615)
3.5 At the time concrete is placed, reinforcement shall be free from mud, oil, and other nonmetallic coatings that decrease bond
4. Minimum Concrete cover (ACI 318 7.7.1)
4.1 Concrete cast against earth: 3 inches
4.2 Concrete exposed to earth or weather:
4.2.1 No. 6 or larger 2 inches
4.2.2 No. 5 bars, W31 Wire, or smaller: 1.5 inches
5. Form-work shall conform to ACI 318-11 and ACI 347. Forms shall be removed in a manner as not to impair safety and serviceability of the
structure. Concrete exposed by form removal shall have sufficient strength not to be damaged by removal operation.
Wood
1. Wood materials, quality and construction shall conform to IRC chapters 6 and 9.
2. Structural lumber:
2.1 Bearing walls: Hem-Fir (HF) Stud (ASTM D 1990, DOC PS 20)
2.2 Post: Hem-Fir (HF) #2 or better (ASTM D 1990, DOC PS 20)
2.3 Beam and Headers Hem-Fir (HF) #2 or better (ASTM D 1990, DOC PS 20)
2.4 Sill Plates Preservative-treated wood Southern Yellow Pine #2
3. Structural composite lumber and engineered wood (2005 NDS 8.1.1)
3.1 Laminated strand lumber
3.1.2 Microllam LVL Ex = 2.0E
4. Wood Structural panels
4.1 Roof, floor and sheathing: Oriented Strand Board (OSB) (DOC PS 1,2)
4.2 Sheathing shall be manufactured with exterior glue and not less than 4x8 feet, except at boundaries and at changes in framing.
4.3 Wall Sheathing
4.3.1 Oriented Strand Board (OSB) (DOC PS 1,2)
4.3.2 All panel joints in wall shall occur over studs or blocking using 8D nails spaced a minimum of 6 inches at panel edges and 12
inches at intermediate framing. Stagger sheathing joints.
5. Joist hanger, column caps, column bases, framing hardware:
5.1 Acceptable manufacturer Simpson Strong Tie
(800) 925-5099 http://www.strongtie.com
5.2 Substitutions: not permitted.
6. Adhesive:
6.1 Liquid nails heavy duty construction adhesive (ln-903/lnp-903)
6.2 Specification ASTM c-557
6.3 Substitutions: permitted.
DRAFTED BY:
DESIGNED BY:
PREPARED FOR:JOB #:
DRAWING:
SHEET:
SCALE:
PO Box 7285
Dillon, CO 80435
(303) 501-2458
NEW DECK TO BE INSTALLED AT:
890 ELK MEADOW CT.
ESTES PARK, CO 80517
REVISIONS
1
2
3
4 C1
Digitally signed by Matthew Weber,
PE
DN: CN="Matthew Weber, PE",
E=mweber@weberengineering.net
Reason: I am the author of this
document
Location: your signing location here
Date: 2022.06.16 22:42:35-06'00'
Foxit PDF Reader Version: 11.2.2
Matthew
Weber, PE
APPROVED by SAFEbuilt;
2015 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
07/13/2022
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
and chapter 5, section 507
Connectors & fasteners in contact with
preservative-treated wood shall be of hot
dipped, zinc coated galvanized steel,
stainless steel, silicone bronze or copper
DECK FRAMING PLAN
1/4" = 1'-0"
(4) 1 34 x 9 12" LVL
15
'
-
7
"
13
'
-
7
"
2x6 PT @ 12" O.C.7'
-
1
1
"
5'
-
8
"
2x6 PT @ 12" O.C.
2x10 PT @ 12" O.C.
4'-512"4'-512"4'-512"4'-512"4'-512"
5'
5'
5'
(2) 2x8 PT(2) 2x8 PT(2) 2x8 PT(2) 2x8 PT(2) 2x8 PT(2) 2x8 PT
(2) 2x8 PT
(2) 2x8 PT
(2) 2x8 PT (2) 2x8 PT (2) 2x8 PT (2) 2x8 PT (2) 2x8 PT (2) 2x8 PT (2) 2x8 PT (2) 2x8 PT
4'-512"4'-512"4'-512"4'-512"4'-512"2'4'-1112"4'-1112"4'-1112"
INSTALLING BLOCKING AT MID-SPAN
4x4 PT ON 10"
DIAMETER 3' DEEP
CAISSON (TYP)
1
S2
(E) HOUSE
CANT. EACH BEAM TO
SUPPORT WHERE
DECK 1 JOINS DECK 2
CANT. EACH BEAM TO
SUPPORT WHERE
DECK 1 JOINS DECK 2
DECK 1
DECK 2
A HOT TUB MAY
BE INSTALLED
ANYWHERE ON
DECK 1
INSTALL (4) SIMPSON STRONG
TIE DTT2Z W/ 12" ANCHOR BOLT
EVENLY SPACED
(2) 2x8 PT (2) 2x8 PT (2) 2x8 PT
DRAFTED BY:
DESIGNED BY:
PREPARED FOR:JOB #:
DRAWING:
SHEET:
SCALE:
PO Box 7285
Dillon, CO 80435
(303) 501-2458
NEW DECK TO BE INSTALLED AT:
890 ELK MEADOW CT.
ESTES PARK, CO 80517
REVISIONS
1
2
3
4 S1
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
Wood materials used to be Preservative-treated
or approved Naturally durable wood in
accordance with Section R317 & AWPA U1 -
Unless noted otherwise on this drawing
OPEN HOLE INSPECTION REQUIRED
BEFORE CAISSON CONCRETE IS POURED
APPROVED by SAFEbuilt;
2018 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
07/13/2022
10" DIA.
1'
4x4 PT
SIMPSON STRONG-TIE
ABA44Z OR EQUAL
SECTION 1
1" = 1'-0"
SIMPSON STRONG-TIE BCS2-2/4
BEAM PER PLAN
6" MIN
3'
JOISTS
PER PLAN
SIMPSON STRONG
TIE DTT2Z W/ 12"
ANCHOR BOLT (OR
EQUAL) AT EACH
POST INSTALL PER
MANUFACTURERS
RECOMMENDATION
4x4 PT POST @ 48" O.C. W/ HAND
RAIL BETWEEN WHERE REQ'D
12" THROUGH
BOLT
DECKING PER
OWNER
(2) #4 VERT.
REBAR W/ 3"
CLEAR COVER
RIM BOARD
TO MATCH
JOIST SIZE
H2.5 IF INSTALLED
DROPPED, LUS26Z &
LUS210Z IF FLUSH
THIS IS ONLY ONE POSSIBLE
HAND RAIL OPTION.
CONTRACTOR/HOMEOWNER
MAY SELECT A PREFAB HAND
RAIL & REQUEST APPROVAL
FROM ENGINEER
2x4 PT
w/ (2) 16d PER STRINGER
(N) WEDGE ANCHORS
2x12 PT STRINGER
@ 12" o.c.
(N) CONCRETE PAD
STAIR DETAIL - BOTTOM
1/2" = 1'-0"2
(N) 2x4 LEDGER
2x12 PT STRINGER
734"
M
A
X
10" MIN
(1) 5" LEDGERLOK
PER STRINGER
5" LEDGERLOK
STAGGERED @ 18" o.c.
PT DECK JOIST PER PLAN
BEAM PER PLAN
1/2" = 1'-0"
STAIR DETAIL - TOP2
DRAFTED BY:
DESIGNED BY:
PREPARED FOR:JOB #:
DRAWING:
SHEET:
SCALE:
PO Box 7285
Dillon, CO 80435
(303) 501-2458
NEW DECK TO BE INSTALLED AT:
890 ELK MEADOW CT.
ESTES PARK, CO 80517
REVISIONS
1
2
3
4 S2
PERMIT #22-EP-00360
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
Min. Stair Hand/Guard Rail Requirements (R311.7 - R312):
1. Stairways to be not less than 36" in width
2. Risers = 7 3/4" max
3. Treads = 10" min.
4. The length of Run and the height of Riser shall not vary more
than 3/8" in the entire run of the stair.
5. Stairs are required to be illuminated
6. Open risers opening = less than 4"
7. Nosing = 3/4" min.
8. Guardrail required for over 30"
9. Guardrail openings = less than 4"
10. Guardrail to meet 200lb. uniform live load
11. Handrail reqd for 4 or more risers
12. Handrail = 34" min. - 38" max
13. Handrail to be continuous one side min.
14. Hand-grip = 1-1/4" min to 2" max
15. Handrails to return to wall, post or terminal
Plastic composite decking, treads and handrail
to comply with R507.2.2 & ASTM D7032.
Verify composite decking can span the required
joist spacing