Loading...
HomeMy WebLinkAboutPLANS Solar 630 Pinewood Ln 2022-08-04July 14, 2022 Skyline Solar 663 West State Street Unit #3 Pleasant Grove, Utah, 84062 Design Criteria: Wind Speed (Vult) - 175.0 mph Ground Snow Load - 70.0 psf Risk Category - 2 Exposure Category - C 580 E Technology Ave, Suite 200, Orem, UT 84097 385.482.1266 rightangleeng.com RE: Structural Roof Evaluation for the Katerine Arterburn Residence: 630 Pinewood Ln, Estes Park, Colorado We have evaluated the roof structure under the proposed solar panel array. The information used to evaluate this structure was gathered during a field visit by Skyline Solar on behalf of Right Angle Engineering. The design criteria used to analyze this structure are listed above and included with this letter. The adopted building codes in this jurisdiction are: The 2015 International Building code and ASCE 7-10. Array Name Connection Type Panel Quantity Min # Connections Reinforcements Array 1 QuickBolt L-Foot 14 28 None Array 2 QuickBolt L-Foot 10 20 None Solar Panel Anchorage The solar panel anchorage shall be installed according to the manufactures most current installation manual. For the loads to be evenly distributed, the roof attachments should be staggered and spread evenly throughout the panel array. Attachment points should be spaced at a maximum of 48 inches on center. Roof anchors that are attached to the substructure should have a 5/16” or 18/8 SS lag screw with 2.5” minimum penetration centered on each truss top chord or rafter. Conclusion Based on our assessment, we have determined that the existing roof framing is in good condition and will safely and adequately support the additional loads imposed by the solar panels without reinforcement. The equipment will not create a negative impact on the building's structural design, including any additional loads imposed (dead,snow, wind/seismic). A roof evaluation was performed with the required loading in accordance with section 324.4 of the Residential Code Regards, 07/14/2022 Robert D. Smythe, P.E. Right Angle Engineering REVIEWED BY SAFEBUILT 08/04/2022 Page 2 letter of approval Scope of work and limitations The evaluation is based on information provided by the client. All information is verified by the engineer from pictures, video, and third party software. Verification of the field observations is the responsibility of the contractor. The contractor shall verify the framing sizes, spacing, spans, and roof pitch noted in this letter and/or sealed plans. The contractor shall notify the engineer if there are any discrepancies, or if there is any damage to the structure (i.e., fire damage, water damage, dry rot, deflections, broken member, broken connection, etc). The scope of work is strictly limited to the fastener attachments and underlying roof framing directly under each solar array. Right Angle Engineering assumes no responsibility for improper installation of solar panels or their components. Waterproofing around the roof penetrations is the responsibility of others. Alterations to this engineering evaluation and/or sealed plans shall not be made without direct written consent of the engineer of record. REVIEWED BY SAFEBUILT 08/04/2022 Page 3 letter of approval Job Details Roof Snow Load - ASCE 7-10 Design Criteria Ground Snow Load (pg) Section 7.2 70.0 psf Design Wind Speed 175.0mph Exposure Factor (Ce) Table 7-2 0.9 Exposure Category C Thermal Factor (Ct) Table 7-3 1.1 Risk Category 2 Importance Factor (Is) Table 1.5-2 1 Mean Roof Height 30 ft Flat Roof Snow Load (pƒ) Equation 7.3-1 48.51 psf Roof Type Gable Roof Slippery Surface Slope Factor (Cs) Figure 7-2 0.83 Building Type Enclosed Non-Slippery Surface Slope Factor (Cs) Figure 7-2 1 Roof Live Load Roof Snow Load Equation 7.4-1 48.51 psf Existing Roof Live Load ASCE 7-10 Table 4-1 20 psf Reduced Snow Load (Slippery Surface) Equation 7.4-1 40.43 psf Roof Live Load with Solar Panels 1607.12.5 0.0 psf 1Roof Dead Load Asphalt Shingles 2.0 psf No Drywall 0.0 psf 5/8" Plywood Sheathing 2.0 psf Solar Panel Array 2.39 psf Roof Framing 1.57 psf Dead Load Without Panels 6.77 psf Insulation 1.2 psf Dead Load With Panels 9.16 psf 1Roof Dead Load is taken from the worst case scenario dead load from all arrays of the job in order to provide a more conservative evaluation. REVIEWED BY SAFEBUILT 08/04/2022 Page 4 letter of approval Array 1 Array Details Beam Stresses Roof Pitch 20.0°Beam Span 200.76"Panel Orientation Portrait Panel Quantity 14 Spacing 24.0"# of Panels on Rafter 2 Panel Area 246.16 ft²Roof Framing Type 2x6 Truss DF#2 Panel Distance From Eave 12.0" Wind Calculations - ASCE 7-10 Panel Area GCp Zone 2 Figure 30.4-(2A-5B)-3.0 Shear Capacity NDS 2015 Table 12k 190.0 lbs GCpi Table 26.11-1 -0.18 Pullout Capacity 266.0 lbs/in Kh Table 27.3-1 0.98 Minimum # of Connections 28 Kht Equation 26.8-1 1 Lag Screw Embedment 2.5" Kd Table 26.6-1 0.85 Total Pullout Capacity 665.0 lbs Velocity Pressure Equation 27.3-1 28.2 psf Zone 2 Pressure Equation 30.8-1 -79.53 psf REVIEWED BY SAFEBUILT 08/04/2022 Page 5 letter of approval Member Design Capacity Member ID FI c(ksi)FI t(ksi)FI bz(ksi)FI by(ksi)FI vy(ksi)FI vz(ksi) 1 5.550 11.026 0.763 0.239 0.891 0.891 2 5.550 11.026 0.763 0.239 0.891 0.891 3 5.550 11.026 0.763 0.239 0.891 0.891 4 5.550 11.026 0.763 0.239 0.891 0.891 5 5.550 11.026 0.763 0.239 0.891 0.891 6 5.550 11.026 0.763 0.239 0.891 0.891 7 5.550 11.026 0.763 0.239 0.891 0.891 8 5.550 11.026 0.763 0.239 0.891 0.891 9 5.550 11.026 0.763 0.239 0.891 0.891 10 5.550 11.026 0.763 0.239 0.891 0.891 11 5.550 11.026 0.763 0.239 0.891 0.891 12 5.550 11.026 0.763 0.239 0.891 0.891 13 5.550 11.026 0.763 0.239 0.891 0.891 Design Ratio Member ID P Mz My Vy Vz C SI D Status 1 0.006 0.124 0.000 0.105 0.000 0.130 0.108 0.016 Pass 2 0.256 0.911 0.000 0.494 0.000 0.979 0.108 0.006 Pass 3 0.565 0.066 0.000 0.005 0.000 0.631 0.519 0.001 Pass 4 0.111 0.000 0.000 0.000 0.000 0.111 0.447 0.000 Pass 5 0.168 0.000 0.000 0.000 0.000 0.168 0.447 0.000 Pass 6 0.056 0.000 0.000 0.000 0.000 0.056 0.316 0.000 Pass 7 0.085 0.000 0.000 0.000 0.000 0.085 0.316 0.000 Pass 8 0.271 0.678 0.000 0.350 0.000 0.743 0.108 0.003 Pass 9 0.009 0.136 0.000 0.146 0.000 0.144 0.108 0.025 Pass 10 0.487 0.051 0.000 0.004 0.000 0.538 0.519 0.000 Pass 11 0.337 0.066 0.000 0.001 0.000 0.403 0.519 0.001 Pass 12 0.230 0.678 0.000 0.315 0.000 0.733 0.108 0.006 Pass 13 0.312 0.911 0.000 0.481 0.000 0.998 0.108 0.005 Pass Node Coordinates ID X Coordinate Y Coordinate 1 0.000 0.000 2 16.730 6.089 3 33.460 0.000 4 -1.500 -0.546 5 34.960 -0.546 6 11.153 0.000 7 22.307 0.000 8 8.365 3.045 9 25.095 3.045 Members ID Node A Node B Section Node A Fixity Node B Fixity Length 1 4 1 1 FFFFRR FFFFFF 1.596 2 2 9 1 FFFFRR FFFFFF 8.902 3 3 7 1 FFFFRR FFFFFF 11.153 4 2 6 1 FFFFRR FFFFRR 8.257 5 2 7 1 FFFFRR FFFFRR 8.257 6 6 8 1 FFFFRR FFFFRR 4.129 7 7 9 1 FFFFRR FFFFRR 4.129 8 1 8 1 FFFFFF FFFFFF 8.902 9 3 5 1 FFFFFF FFFFRR 1.596 10 6 1 1 FFFFFF FFFFRR 11.153 11 7 6 1 FFFFFF FFFFFF 11.153 12 8 2 1 FFFFFF FFFFRR 8.902 13 9 3 1 FFFFFF FFFFFF 8.902 REVIEWED BY SAFEBUILT 08/04/2022 Page 6 letter of approval Supports ID Node ID Restraint Code 1 1 FFFFRR 2 3 RFFRRR Materials ID Name Young's Modulus Density Poisson's Ratio 1 NDS - Table 4A - DOUGLAS FIR-LARCH - No.2 - 2in & wider 1600.000 33.611 0.400 Sections ID Name Depth Width Shear Area Z Shear Area Y Torsion Radius 1 2 x 6 5.500 1.500 6.875 6.875 1.492 ID Centroid Y Centroid Z Area Y-Axis Mol Z-Axis Mol Torsion Constant 1 0.750 2.750 8.250 1.547 20.800 5.124 Point Loads ID Load Group Member Position %Y Magnitude 1 Solar-Snow 8 6.550%-0.334 2 Solar 8 6.550%-0.021 3 Solar-Snow 8 72.772%-0.334 4 Solar 8 72.772%-0.021 Member Distributed Loads ID Load Group Start Position End Position Member Y Magnitude 1 Dead Load 0.000%100.000%1 -0.014 2 Dead Load 0.000%100.000%2 -0.014 3 Snow Load 0.000%68.263%1 -0.097 4 Snow Load 26.754%100.000%12 -0.097 5 Snow Load 0.000%100.000%2 -0.097 6 Roof Live Load 0.000%68.263%1 -0.032 7 Roof Live Load 26.754%100.000%12 -0.032 8 Roof Live Load 0.000%100.000%2 -0.032 9 Dead Load 0.000%100.000%8 -0.014 10 Dead Load 0.000%100.000%9 -0.014 11 Snow Load 0.000%100.000%9 -0.097 12 Roof Live Load 0.000%100.000%9 -0.032 13 Dead Load 0.000%100.000%12 -0.014 14 Dead Load 0.000%100.000%13 -0.014 15 Snow Load 0.000%100.000%13 -0.097 16 Roof Live Load 0.000%100.000%13 -0.032 Load Combinations ID Name Dead Load Factor Snow Load Factor Solar Factor Solar-Snow Factor Roof Live Load Factor 1 1. D 1 0 1 0 0 2 2. D + L 1 0 1 0 0 3 3. D + (S or Lr or R)1 1 1 1 0 4 3. D + (S or Lr or R)1 0 1 0 1 5 3. D + (S or Lr or R)1 0 1 0 0 6 4. D + 0.75L + 0.75(S or Lr or R)1 0.75 1 0.75 0 7 4. D + 0.75L + 0.75(S or Lr or R)1 0 1 0 0.75 8 4. D + 0.75L + 0.75(S or Lr or R)1 0 1 0 0 9 5a. D + 0.6W 1 0 1 0 0 10 5b. D + 0.6E 1 0 1 0 0 11 6a. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0.75 1 0.75 0 12 6a. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0 1 0 0.75 13 6a. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0 1 0 0 REVIEWED BY SAFEBUILT 08/04/2022 Page 7 letter of approval 14 6b. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0.75 1 0.75 0 15 7. 0.6D + 0.6W 0.6 0 0.6 0 0 16 8. 0.6D + 0.7E 0.6 0 0.6 0 0 Internal Member Forces and Moments Member Axial Force (Min/Max) Shear Force Y (Min/Max) Shear Force Z (Min/Max) Torsion (Min/Max) Bending Moment Y (Min/Max) Bending Moment Z (Min/Max) 1 -0.044 / 0.000 -0.120 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.121 / 0.000 2 3.268 / 3.605 -0.562 / 0.363 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.888 / 0.632 3 -4.006 / -4.006 0.006 / 0.006 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.065 4 -0.786 / -0.786 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 5 -1.191 / -1.191 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 6 0.791 / 0.791 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 7 1.201 / 1.201 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 8 3.539 / 3.823 -0.382 / 0.398 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.661 / 0.238 9 -0.060 / 0.000 0.000 / 0.166 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.132 / 0.000 10 -3.456 / -3.456 -0.004 / -0.004 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.050 11 -2.391 / -2.391 -0.003 / -0.003 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.050 / 0.065 12 2.979 / 3.236 -0.359 / 0.349 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.661 / 0.620 13 4.064 / 4.401 -0.377 / 0.547 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.888 / 0.549 Member Displacement Span Check Member Length Max Relative Displacement Span Method 1 1 1.596 0.101 L/712 2 8.902 0.213 L/4055 3 11.153 0.026 L/40815 4 8.257 0.000 L/132095119678 5 8.257 0.000 L/198167405976 6 4.129 0.000 L/65728247909 7 4.129 0.000 L/98592649074 8 8.902 0.154 L/3358 9 1.596 0.161 L/921 10 11.153 0.020 L/37226 11 11.153 0.046 L/19773 12 8.902 0.254 L/4758 13 8.902 0.179 L/4818 Member Stresses Member Axial Stress (Min/Max) Torsion Stress (Min/Max) Shear Stress Y (Min/Max) Shear Stress Z (Min/Max) Top Bending Moment Z (Min/Max) Bottom Bending Moment Z (Min/Max) 1 -0.005 / 0.000 0.000 / 0.000 -0.022 / 0.000 0.000 / 0.000 -0.191 / 0.000 0.000 / 0.191 2 0.396 / 0.437 0.000 / 0.000 -0.102 / 0.066 0.000 / 0.000 -1.409 / 1.002 -1.002 / 1.409 3 -0.486 / -0.486 0.000 / 0.000 0.001 / 0.001 0.000 / 0.000 0.000 / 0.102 -0.102 / 0.000 4 -0.095 / -0.095 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 5 -0.144 / -0.144 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 6 0.096 / 0.096 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 7 0.146 / 0.146 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 8 0.429 / 0.463 0.000 / 0.000 -0.069 / 0.072 0.000 / 0.000 -1.049 / 0.377 -0.377 / 1.049 9 -0.007 / 0.000 0.000 / 0.000 0.000 / 0.030 0.000 / 0.000 -0.210 / 0.000 0.000 / 0.210 10 -0.419 / -0.419 0.000 / 0.000 -0.001 / -0.001 0.000 / 0.000 0.000 / 0.079 -0.079 / 0.000 11 -0.290 / -0.290 0.000 / 0.000 -0.000 / -0.000 0.000 / 0.000 0.079 / 0.102 -0.102 / -0.079 12 0.361 / 0.392 0.000 / 0.000 -0.065 / 0.063 0.000 / 0.000 -1.049 / 0.983 -0.983 / 1.049 13 0.493 / 0.533 0.000 / 0.000 -0.069 / 0.100 0.000 / 0.000 -1.409 / 0.871 -0.871 / 1.409 REVIEWED BY SAFEBUILT 08/04/2022 Page 8 letter of approval Array 2 Array Details Beam Stresses Roof Pitch 20.0°Beam Span 200.76"Panel Orientation Portrait Panel Quantity 10 Spacing 24.0"# of Panels on Rafter 1 Panel Area 175.82 ft²Roof Framing Type 2x6 Truss DF#1 Panel Distance From Eave 12.0" Wind Calculations - ASCE 7-10 Panel Area GCp Zone 2 Figure 30.4-(2A-5B)-3.0 Shear Capacity NDS 2015 Table 12k 190.0 lbs GCpi Table 26.11-1 -0.18 Pullout Capacity 266.0 lbs/in Kh Table 27.3-1 0.98 Minimum # of Connections 20 Kht Equation 26.8-1 1 Lag Screw Embedment 2.5" Kd Table 26.6-1 0.85 Total Pullout Capacity 665.0 lbs Velocity Pressure Equation 27.3-1 28.2 psf Zone 2 Pressure Equation 30.8-1 -79.53 psf REVIEWED BY SAFEBUILT 08/04/2022 Page 9 letter of approval Member Design Capacity Member ID FI c(ksi)FI t(ksi)FI bz(ksi)FI by(ksi)FI vy(ksi)FI vz(ksi) 1 6.515 12.251 0.848 0.266 0.891 0.891 2 6.515 12.251 0.848 0.266 0.891 0.891 3 6.515 12.251 0.848 0.266 0.891 0.891 4 6.515 12.251 0.848 0.266 0.891 0.891 5 6.515 12.251 0.848 0.266 0.891 0.891 6 6.515 12.251 0.848 0.266 0.891 0.891 7 6.515 12.251 0.848 0.266 0.891 0.891 8 6.515 12.251 0.848 0.266 0.891 0.891 9 6.515 12.251 0.848 0.266 0.891 0.891 10 6.515 12.251 0.848 0.266 0.891 0.891 11 6.515 12.251 0.848 0.266 0.891 0.891 12 6.515 12.251 0.848 0.266 0.891 0.891 13 6.515 12.251 0.848 0.266 0.891 0.891 Design Ratio Member ID P Mz My Vy Vz C SI D Status 1 0.005 0.111 0.000 0.105 0.000 0.117 0.108 0.011 Pass 2 0.243 0.815 0.000 0.493 0.000 0.877 0.108 0.006 Pass 3 0.504 0.061 0.000 0.005 0.000 0.564 0.519 0.001 Pass 4 0.121 0.000 0.000 0.000 0.000 0.121 0.447 0.000 Pass 5 0.143 0.000 0.000 0.000 0.000 0.143 0.447 0.000 Pass 6 0.065 0.000 0.000 0.000 0.000 0.065 0.316 0.000 Pass 7 0.077 0.000 0.000 0.000 0.000 0.077 0.316 0.000 Pass 8 0.277 0.620 0.000 0.349 0.000 0.689 0.108 0.001 Pass 9 0.007 0.122 0.000 0.146 0.000 0.129 0.108 0.024 Pass 10 0.474 0.054 0.000 0.005 0.000 0.528 0.519 0.001 Pass 11 0.310 0.061 0.000 0.001 0.000 0.370 0.519 0.001 Pass 12 0.234 0.658 0.000 0.472 0.000 0.709 0.108 0.007 Pass 13 0.294 0.815 0.000 0.480 0.000 0.893 0.108 0.005 Pass Node Coordinates ID X Coordinate Y Coordinate 1 0.000 0.000 2 16.730 6.089 3 33.460 0.000 4 -1.500 -0.546 5 34.960 -0.546 6 11.153 0.000 7 22.307 0.000 8 8.365 3.045 9 25.095 3.045 Members ID Node A Node B Section Node A Fixity Node B Fixity Length 1 4 1 1 FFFFRR FFFFFF 1.596 2 2 9 1 FFFFRR FFFFFF 8.902 3 3 7 1 FFFFRR FFFFFF 11.153 4 2 6 1 FFFFRR FFFFRR 8.257 5 2 7 1 FFFFRR FFFFRR 8.257 6 6 8 1 FFFFRR FFFFRR 4.129 7 7 9 1 FFFFRR FFFFRR 4.129 8 1 8 1 FFFFFF FFFFFF 8.902 9 3 5 1 FFFFFF FFFFRR 1.596 10 6 1 1 FFFFFF FFFFRR 11.153 11 7 6 1 FFFFFF FFFFFF 11.153 12 8 2 1 FFFFFF FFFFRR 8.902 13 9 3 1 FFFFFF FFFFFF 8.902 REVIEWED BY SAFEBUILT 08/04/2022 Page 10 letter of approval Supports ID Node ID Restraint Code 1 1 FFFFRR 2 3 RFFRRR Materials ID Name Young's Modulus Density Poisson's Ratio 1 NDS - Table 4A - DOUGLAS FIR-LARCH - No.1 - 2in & wider 1700.000 33.611 0.400 Sections ID Name Depth Width Shear Area Z Shear Area Y Torsion Radius 1 2 x 6 5.500 1.500 6.875 6.875 1.492 ID Centroid Y Centroid Z Area Y-Axis Mol Z-Axis Mol Torsion Constant 1 0.750 2.750 8.250 1.547 20.800 5.124 Point Loads ID Load Group Member Position %Y Magnitude 1 Solar-Snow 8 6.550%-0.334 2 Solar 8 6.550%-0.021 Member Distributed Loads ID Load Group Start Position End Position Member Y Magnitude 1 Dead Load 0.000%100.000%1 -0.014 2 Dead Load 0.000%100.000%2 -0.014 3 Snow Load 0.000%68.263%1 -0.097 4 Snow Load 60.532%100.000%8 -0.097 5 Snow Load 0.000%100.000%2 -0.097 6 Roof Live Load 0.000%68.263%1 -0.032 7 Roof Live Load 60.532%100.000%8 -0.032 8 Roof Live Load 0.000%100.000%2 -0.032 9 Dead Load 0.000%100.000%8 -0.014 10 Dead Load 0.000%100.000%9 -0.014 11 Snow Load 0.000%100.000%9 -0.097 12 Roof Live Load 0.000%100.000%9 -0.032 13 Snow Load 0.000%100.000%12 -0.097 14 Roof Live Load 0.000%100.000%12 -0.032 15 Dead Load 0.000%100.000%12 -0.014 16 Dead Load 0.000%100.000%13 -0.014 17 Snow Load 0.000%100.000%13 -0.097 18 Roof Live Load 0.000%100.000%13 -0.032 Load Combinations ID Name Dead Load Factor Snow Load Factor Solar Factor Solar-Snow Factor Roof Live Load Factor 1 1. D 1 0 1 0 0 2 2. D + L 1 0 1 0 0 3 3. D + (S or Lr or R)1 1 1 1 0 4 3. D + (S or Lr or R)1 0 1 0 1 5 3. D + (S or Lr or R)1 0 1 0 0 6 4. D + 0.75L + 0.75(S or Lr or R)1 0.75 1 0.75 0 7 4. D + 0.75L + 0.75(S or Lr or R)1 0 1 0 0.75 8 4. D + 0.75L + 0.75(S or Lr or R)1 0 1 0 0 9 5a. D + 0.6W 1 0 1 0 0 10 5b. D + 0.6E 1 0 1 0 0 11 6a. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0.75 1 0.75 0 12 6a. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0 1 0 0.75 13 6a. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0 1 0 0 REVIEWED BY SAFEBUILT 08/04/2022 Page 11 letter of approval 14 6b. D + 0.75L + 0.75(0.6)W + 0.75(S or Lr or R)1 0.75 1 0.75 0 15 7. 0.6D + 0.6W 0.6 0 0.6 0 0 16 8. 0.6D + 0.7E 0.6 0 0.6 0 0 Internal Member Forces and Moments Member Axial Force (Min/Max) Shear Force Y (Min/Max) Shear Force Z (Min/Max) Torsion (Min/Max) Bending Moment Y (Min/Max) Bending Moment Z (Min/Max) 1 -0.044 / 0.000 -0.120 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.121 / 0.000 2 3.470 / 3.806 -0.562 / 0.363 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.884 / 0.633 3 -4.195 / -4.195 0.006 / 0.006 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.066 4 -1.006 / -1.006 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 5 -1.191 / -1.191 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 6 1.012 / 1.012 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 7 1.200 / 1.200 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 8 4.052 / 4.331 -0.397 / 0.370 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.672 / 0.123 9 -0.060 / 0.000 0.000 / 0.166 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.132 / 0.000 10 -3.944 / -3.944 -0.005 / -0.005 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.059 11 -2.580 / -2.580 -0.001 / -0.001 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.059 / 0.066 12 3.328 / 3.665 -0.387 / 0.538 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.672 / 0.713 13 4.265 / 4.602 -0.378 / 0.547 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 -0.884 / 0.551 Member Displacement Span Check Member Length Max Relative Displacement Span Method 1 1 1.596 0.073 L/893 2 8.902 0.201 L/4320 3 11.153 0.025 L/43339 4 8.257 0.000 L/197919943047 5 8.257 0.000 L/113053908499 6 4.129 0.000 L/98591123381 7 4.129 0.000 L/66019415079 8 8.902 0.036 L/4665 9 1.596 0.155 L/991 10 11.153 0.023 L/42932 11 11.153 0.047 L/21904 12 8.902 0.253 L/4441 13 8.902 0.169 L/5135 Member Stresses Member Axial Stress (Min/Max) Torsion Stress (Min/Max) Shear Stress Y (Min/Max) Shear Stress Z (Min/Max) Top Bending Moment Z (Min/Max) Bottom Bending Moment Z (Min/Max) 1 -0.005 / 0.000 0.000 / 0.000 -0.022 / 0.000 0.000 / 0.000 -0.191 / 0.000 0.000 / 0.191 2 0.421 / 0.461 0.000 / 0.000 -0.102 / 0.066 0.000 / 0.000 -1.402 / 1.005 -1.005 / 1.402 3 -0.508 / -0.508 0.000 / 0.000 0.001 / 0.001 0.000 / 0.000 0.000 / 0.104 -0.104 / 0.000 4 -0.122 / -0.122 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 5 -0.144 / -0.144 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 6 0.123 / 0.123 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 7 0.145 / 0.145 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 0.000 / 0.000 8 0.491 / 0.525 0.000 / 0.000 -0.072 / 0.067 0.000 / 0.000 -1.066 / 0.196 -0.196 / 1.066 9 -0.007 / 0.000 0.000 / 0.000 0.000 / 0.030 0.000 / 0.000 -0.210 / 0.000 0.000 / 0.210 10 -0.478 / -0.478 0.000 / 0.000 -0.001 / -0.001 0.000 / 0.000 0.000 / 0.093 -0.093 / 0.000 11 -0.313 / -0.313 0.000 / 0.000 -0.000 / -0.000 0.000 / 0.000 0.093 / 0.104 -0.104 / -0.093 12 0.403 / 0.444 0.000 / 0.000 -0.070 / 0.098 0.000 / 0.000 -1.066 / 1.131 -1.131 / 1.066 13 0.517 / 0.558 0.000 / 0.000 -0.069 / 0.099 0.000 / 0.000 -1.402 / 0.874 -0.874 / 1.402 REVIEWED BY SAFEBUILT 08/04/2022 663 W. STATE STREET, #3 PLEASANT GROVE, UT 84062855-475-9765 GOVERNING CODES: 11. PLUMBING AND MECHANICAL VENTS THROUGH THE ROOF SHALL NOT BE COVERED BY SOLAR MODULES- - NO BUILDING, PLUMBING OR MECHANICAL VENTS TO BE COVERED, CONSTRUCTED OR ROUTED AROUND SOLAR MODULES. 12. ALL FIELD -INSTALLED JUNCTION, PULL AND OUTLET BOXES LOCATED BEHIND MODULES SHALL BE ACCESSIBLE DIRECTLY OR BY DISPLACEMENT OF A MODULE SECURED BY REMOVABLE FASTENERS. ELECTRICAL 1. WIRING MATERIALS SHALL COMPLY WITH MAXIMUM CONTINUOUS CURRENT OUTPUT AT 25°C AND MAXIMUM VOLTAGE AT 600V; WIRE SHALL BE WET RATED AT 90°C. 2. EXPOSED PHOTOVOLTAIC SYSTEM CONDUCTORS ON THE ROOF WILL BE USE 2 OR PV-TYPE WIRE. 3. PHOTOVOLTAIC SYSTEM CONDUCTORS SHALL BE IDENTIFIED AND GROUPED. THE MEANS OF IDENTIFICATION SHALL BE PERMITTED BY SEPARATE COLOR-CODING, MARKING TAPE, TAGGING OR OTHER APPROVED MEANS. 4. ALL EXTERIOR CONDUIT, FITTINGS, AND BOXES SHALL BE RAIN-TIGHT AND APPROVED FOR USE IN WET LOCATIONS. 5. ALL METALLIC RACEWAYS AND EQUIPMENT SHALL BE BONDED AND ELECTRICALLY CONTINUOUS. 6. WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, CONTRACTOR SHALL SIZE THEM ACCORDING TO APPLICABLE CODES. 7. REMOVAL OF A UTILITY-INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL NOT DISCONNECT THE BUILDING CONNECTION BETWEEN THE GROUNDING ELECTRODE CONDUCTOR AND THE PV SOURCE AND/OR OUTPUT CIRCUIT GROUNDED CONDUCTOR. 8. FOR GROUNDED SYSTEMS, THE PHOTOVOLTAIC SOURCE AND OUTPUT CIRCUITS SHALL BE PROVIDED WITH A GROUND-FAULT PROTECTION DEVICE OR SYSTEM THAT DETECTS A GROUND FAULT, INDICATES THAT FAULT HAS OCCURED AND AUTOMATICALLY DISCONNECTS ALL CONDUCTORS OR CAUSES THE INVERTER TO AUTOMATICALLY CEASE SUPPLYING POWER TO OUTPUT CIRCUITS. 9. FOR UNGROUNDED SYSTEMS, THE INVERTER IS EQUIPPED WITH GROUND FAULT PROTECTION AND A GFI FUSE PORT FOR GROUND FAULT INDICATION. 10. PV MODULE FRAMES SHALL BE BONDED TO RACKING RAIL OR BARE COPPER GEC/GEC PER THE MODULE MANUFACTURER'S LISTED INSTRUCTION SHEET. 11. PV MODULE RACKING RAIL SHALL BE BONDED TO BARE COPPER GEC VIA WEEB LUG, ILSCO GBL-4DBT LAY-IN LUG, OR EQUIVALENT LISTED LUG. 12. THE PHOTOVOLTAIC INVERTER WILL BE LISTED AS UL 1741 COMPLIANT. 13. RACKING AND BONDING SYSTEM TO BE UL2703 RATED. 14. ANY REQUIRED GROUNDING ELECTRODE CONDUCTOR WILL BE CONTINUOUS, EXCEPT FOR SPLICES OR JOINTS AS BUS BARS WITHIN LISTED EQUIPMENT. 15. WHEN BACKFED BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, THE BREAKERS SHALL NOT READ "LINE AND LOAD". 16. WHEN APPLYING THE 120% RULE, THE SOLAR BREAKER TO BE POSITIONED AT THE OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. 17. THE WORKING CLEARANCE AROUND THE EXISTING ELECTRICAL EQUIPMENT AS WELL AS THE NEW ELECTRICAL EQUIPMENT WILL BE MAINTAINED. GENERAL 1. UTILITY SHALL BE NOTIFIED BEFORE ACTIVATION OF PHOTOVOLTAIC SYSTEM. 2. 110.2 APPROVAL: ALL ELECTRICAL EQUIPMENT SHALL BE LABELED, LISTED, OR CERTIFIED BY A NATIONALLY RECOGNIZED TESTING LABORATORY ACCREDITED BY THE UNITED STATES OCCUPATIONAL SAFETY HEALTH ADMINISTRATION 3. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS PRIOR TO INITIATING CONSTRUCTION. 4. CONTRACTOR SHALL REVIEW ALL MANUFACTURER INSTALLATION DOCUMENTS PRIOR TO INITIATING CONSTRUCTION. 5. ALL EQUIPMENT AND ASSOCIATED CONNECTIONS, ETC, AND ALL ASSOCIATED WIRING AND INTERCONNECTIONS SHALL BE INSTALLED ONLY BY QUALIFIED PERSONNEL. 6. THE CONTRACTOR OR OWNER MUST PROVIDE ROOF ACCESS (LADDER TO ROOF) FOR ALL THE REQUIRED INSPECTIONS. LADDERS MUST BE OSHA APPROVED, MINIMUM TYPE I WITH A 250LB. RATING, IN GOOD CONDITION AND DESIGNED FOR ITS INTENDED USE. 7. CONTRACTOR SHALL VERIFY THAT THE ROOF STRUCTURE WILL WITHSTAND THE ADDITIONAL LOADS. 8. LAG SCREWS SHALL PENETRATE A MINIMUM 2" INTO SOLID SAWN STRUCTURAL MEMBERS AND SHALL NOT EXCEED MANUFACTURER RECOMMENDATIONS FOR FASTENERS INTO ENGINEERED STRUCTURAL MEMBERS. 9. AN ACCESS POINT SHALL BE PROVIDED THAT DOES NOT PLACE THE GROUND LADDER OVER OPENINGS SUCH AS WINDOWS OR DOORS ARE LOCATED AT STRONG POINTS OF BUILDING CONSTRUCTION AND IN LOCATIONS WHERE THE ACCESS POINT DOES NOT CONFLICT WITH OVERHEAD OBSTRUCTIONS SUCH AS TREE LIMBS, WIRES, OR SIGNS. 10. WHERE DC CONDUCTORS ARE RUN INSIDE BUILDING, THEY SHALL BE CONTAINED IN A METAL RACEWAY; THEY SHALL NOT BE INSTALLED WITHIN 10" OF THE ROOF DECKING OR SHEATHING EXCEPT WHERE COVERED BY THE PV MODULES AND EQUIPMENT. VICINITY MAP AERIAL MAP PV-1REV #1: REV #2: REV #3: DATE: 7/5/2022 DRAWN BY: KM COVER PAGE SYSTEM SIZE: 8.16 kW-DC | 7.60 kW-AC MODULE: ( 24 ) HANWHA Q.PEAK DUO BLK-G6 340W INVERTER: ( 1 ) SOLAREDGE SE7600H-US ARTERBURN, KATHERINE 630 PINEWOOD LN ESTES PARK, CO 80517 ARTERBURN RESIDENCE PHOTOVOLTAIC SYSTEM 630 PINEWOOD LN ESTES PARK, CO 80517 SHEET INDEX: PV-1 - COVER PAGE PV-2 - PROPERTY PLAN PV-3 - SITE PLAN PV-4 - 1-LINE DIAGRAM PV-5 - ELECTRICAL CALCULATIONS PV-6 - ELECTRICAL PHOTOS ALL MATERIALS, EQUIPMENT, INSTALLATION AND WORK SHALL COMPLY WITH THE FOLLOWING APPLICABLE CODES: ·2020 NATIONAL ELECTRIC CODE (NEC) ·2015 INTERNATIONAL FIRE CODE ·2015 INTERNATIONAL BUILDING CODE (IBC) ·2015 INTERNATIONAL EXISTING BUILD CODE (IEBC) ·2015 INTERNATIONAL RESIDENTIAL CODE (IRC) ·2015 INTERNATIONAL MECHANICAL CODE ·2015 INTERNATIONAL FUEL GAS CODE ·2015 INTERNATIONAL PLUMBING CODE ·2015 INTERNATIONAL ENERGY CONSERV. CODE ·OSHA 29 CFR 1910.269 ·UNDERWRITERS LABORATORIES (UL) STANDARDS 22-EP-00358 APPROVAL IS FOR STRUCTURAL REVIEW ONLY. ELECTRICAL INSPECTIONS TO BE PER THE STATE OF COLORADO. INSTALLATION INSTRUCTIONS AND MANUALS MUST BE ON JOB FOR THE INSPECTOR AT THE TIME OF INSPECTION FOR ALL EQUIPMENT. PRINT PLANS IN COLOR AND HAVE FOR INSPECTOR AT TIME OF INSPECTION SAFEbuilt APPROVED Subject to inspection and compliance to all relevant Adopted Building and Municipal codes. Changes in Plans MUST be approved. D.GRAHAM 08/04/2022 N 663 W. STATE STREET, #3 PLEASANT GROVE, UT 84062855-475-9765 SCALE: 1/32" = 1'-0" LEGEND: PROPERTY LINE: PROPERTY PLAN DRIVEWAY: ARTERBURN, KATHERINE 630 PINEWOOD LN ESTES PARK, CO 80517 FENCE: PV-2 630 PINEWOOD LN SINGLE F A M I L Y H O M E DRIVEWAY PROPERTY LINE 210'-3"R21'-4" 134'-2" 224'-5" 176'-10" 56'-6" 78'-5" 47'-5" 29'-2" DATE: 7/5/2022 DRAWN BY: KM REVIEWED BY SAFEBUILT 08/04/2022 N 663 W. STATE STREET, #3 PLEASANT GROVE, UT 84062855-475-9765 SYSTEM LEGEND UM MP AC MAIN SERVICE METER AND SERVICE POINT MAIN SERVICE PANEL UTILITY AC DISCONNECT SCALE: 0.007218 CONDUIT TO BE RUN IN ATTIC IF POSSIBLE, OTHERWISE CONDUIT BLOCKS MIN. 1"/MAX 6" ABOVE ROOF SURFACE, CLOSE TO RIDGE LINES, AND UNDER EAVES; TO BE PAINTED TO MATCH EXTERIOR/EXISTING BACKGROUND COLOR OF ITS LOCATION; TO BE LABELED AT MAX 10' INTERVALS. CONDUIT RUNS ARE APPROXIMATE AND ARE TO BE DETERMINED IN THE FIELD BY THE INSTALLERS CONDUIT RUN ELEVATION DETAIL ATTACHMENT DETAIL FIRE CODE SETBACK (18" MIN / 36" MAX) MODULE INFORMATION MODULE TYPE HANWHA Q.PEAK DUO BLK-G6 340W MAX DESIGN LOAD (WIND & SNOW) 3600 PA UPWARD / 5400 PA DOWNWARD MODULE WEIGHT 43.8 LBS/MODULE MODULE DIMENSIONS (H X L X D)68.5" X 40.5" X 1.25" MODULE AREA 19.23 FT2 I ( 1 ) SOLAREDGE SE7600H-US INVERTER WITH INTEGRATED DC DISCONNECT ( 24 ) HANWHA Q.PEAK DUO BLK-G6 340W WITH SOLAREDGE P370 OPTIMIZERS MOUNTED UNDER EACH MODULE. ROOF SECTION 1: 24 MODULES AZIMUTH: 200° PITCH: 20° ROOF TYPE: ASPHALT SHINGLE ROOF DETAIL 1 ROOF ATTACHMENT POINT SITE PLAN PV-3 JUNCTION BOX AND CONDUIT MODULE MECHANICAL SPECIFICATIONS DESIGN WIND SPEED 175 MPH DESIGN SNOW LOAD 70 PSF ROOF PITCH 20 ° TOTAL ARRAY AREA (SQ. FT)439.20 TOTAL ROOF AREA (SQ. FT) 3149 ARRAY SQ. FT / TOTAL ROOF SQ. FT 13.95% STRUCTURAL ATTACHMENT MODULE ASPHALT SHINGLE TRUSS 24" OC : 2X6" WIND UPLIFT AT ATTACHMENT POINTS IS PROVIDED WITH THE ENGINEERING LETTER. SUPPORT LOCATIONS HAVE BEEN OPTIMIZED TO WITHSTAND UPLIFT PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 8.16 kW AC SYSTEM SIZE: 7.60 kW ARTERBURN, KATHERINE 630 PINEWOOD LN ESTES PARK, CO 80517 STRING DETAIL SOLAREDGE STRINGS STRING # 1: 14 MODULES STRING # 2: 10 MODULES GROUNDING MODULE CLAMP RAIL L-FOOT QUICKBOLT FLASHING MOUNTING SCREWS RAFTER RAIL MOUNTS: 48 ROOF S E C T I O N 1 UM MP ACI DATE: 7/5/2022 DRAWN BY: KM07/06/2022 REVIEWED BY SAFEBUILT 08/04/2022 663 W. STATE STREET, #3 PLEASANT GROVE, UT 84062855-475-9765 PHOTOVOLTAIC SYSTEM: DC SYSTEM SIZE: 8.160 kW AC SYSTEM SIZE: 7.600 kW INVERTER: ( 1 ) SOLAREDGE SE7600H-US MODULE: ( 24 ) HANWHA Q.PEAK DUO BLK-G6 340W NOTES: 1. MODULES ARE BONDED TO RAIL USING UL 2703 RATED BONDING SYSTEM - INTEGRATED BONDING MID-CLAMPS + DIRECT-BURIAL LAY-IN-LUGS; SEE ATTACHED FOR SPECIFICATIONS IF APPLICABLE 2. PV DC SYSTEM IS UNGROUNDED 3. PV ARRAY WILL HAVE A GROUNDING ELECTRODE SYSTEM IN COMPLIANCE WITH NEC 250.58 AND 690.47(A) 4. PV SOURCE, OUTPUT, AND INVERTER INPUT CIRCUIT WIRING METHODS SHALL COMPLY WITH NEC 690.1(G) 5. BACKFED PV BREAKER WILL BE INSTALLED AT OPPOSITE END OF THE BUS BAR FROM THE MAIN BREAKER. A PERMANENT WARNING LABEL TO BE INSTALLED PER SYSTEM SIGNAGE, PAGE 6. BARE COPPER IS TRANSITIONED TO THWN-2 VIA IRREVERSIBLE CRIMP; WHEN PRESENT, THE GEC TO BE CONTINUOUS 7. INVERTER(S) TO BE COMPLIANT WITH UL 1741 SUPPLEMENT A 8. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS 9. CONDUIT AND CONDUCTOR SPECIFICATIONS ARE BASED ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT TO LIMIT UPSIZING AS REQUIRED BY FIELD CONDITIONS. PV MODULE ELECTRICAL SPECIFICATIONS MODULE TYPE HANWHA Q.PEAK DUO BLK ML-G6 340W POWER MAX (PMAX)340W OPEN CIRCUIT VOLTAGE (VOC)40.92V SHORT CIRCUIT CURRENT (ISC)10.58A MAX POWER-POINT VOLTAGE (VMP)34.25V MAX POWER-POINT CURRENT (IMP)10.07A SERIES FUSE RATING 20A INVERTER ELECTRICAL SPECIFICATIONS INVERTER TYPE SOLAREDGE SE7600H-US MAX INPUT DC VOLTAGE 480V MAX INPUT CURRENT 20A NOMINAL DC INPUT VOLTAGE 400V MAXIMUM OUTPUT POWER 7600W NOMINAL AC OUTPUT VOLTAGE 240V MAXIMUM CONT. OUTPUT CURRENT 32A CEC EFFICIENCY 99% POWER OPTIMIZER ELECTRICAL SPECIFICATIONS OPTIMIZER TYPE SOLAREDGE P370 RATED INPUT DC POWER 370W MAXIMUM INPUT VOLTAGE (VOC)60V MAXIMUM SHORT CIRCUIT CURRENT (ISC) 11A MAXIMUM DC INPUT CURRENT 13.75A MAXIMUM OUTPUT CURRENT 15A MAXIMUM OUTPUT VOLTAGE 60V MINIMUM STRING LENGTH 8 MAXIMUM POWER PER STRING 5700W (6000W WITH SE7600- SE11400) OVER-CURRENT PROTECTION DEVICE (OCPD) CALCULATIONS INVERTER TYPE SOLAREDGE 7600H-US # OF INVERTERS 1 MAX CONTINUOUS OUTPUT CURRENT 32A (# OF INVERTERS) X (MAX CONT. OUTPUT CURRENT) X 125% <= OCPD RATING ( 1 x 32A x 1.25)= 40.00A <= 40 A, OK 1-LINE DIAGRAM & CALCULATIONS PV-4 ARTERBURN, KATHERINE 630 PINEWOOD LN ESTES PARK, CO 80517 INSTALLER NOTES: 0 CONDUCTOR AND CONDUIT SCHEDULE TAG WIRE TYPE WIRE SIZE # OF CONDUCTORS CONDUIT TYPE MIN. CONDUIT SIZE 1 PV WIRE #10 2 - L1 L2 FREE AIR N/A 1 BARE COPPER #6 1 - BARE FREE AIR N/A 2 THWN-2 #10 2 - L1 L2 EMT 3/4" 2 THWN-2 EGC #10 1 - GND EMT 3/4" 3 THWN-2 #6 3 - L1 L2 N EMT 3/4" 3 THWN-2 EGC #8 1 - GND EMT 3/4" STRING 1: 14 MODULES - HANWHA Q.PEAK DUO BLK-G6 340W ====== ====== 9 STRING 2: 10 MODULES - HANWHA Q.PEAK DUO BLK-G6 340W 13 NEMA3R RATED JUNCTION BOX: SHALL COMPLY W/ NEC 110.3 & 314.6 SOLAREDGE P370 OPTIMIZER UTILITY INTERACTIVE INVERTER SOLAREDGE ENERGY HUB SE7600H-US S2 SOLAREDGE RAPID SHUTDOWN KIT & INTEGRATED DC DISCONNECT UL1741 CERTIFIED 1 1 (N) AC DISCONNECT 240V/60A NEMA 3R FUSIBLE W/ 40 A FUSES, VISIBLE-LOCKABLE LABELED (E) LOADS 200 A MAIN DISCONNECT UTILITY SERVICE 120/240V SINGLE PHASE (E) 200 A RATED MAIN SERVICE PANEL FACILITY GROUND (E) GROUND ROD + (E) WATER PIPE BOND L1 G N-G SUPPLY SIDE TAP - ILSCO GTA-250-0-W/C PARALLEL TAP CONNECTOR VISIBLE LOCKABLE LABELED DISCONNECT IS WITHIN 10' OF THE UTILITY METER DATE: 7/5/2022 DRAWN BY: KM REVIEWED BY SAFEBUILT 08/04/2022 663 W. STATE STREET, #3PLEASANT GROVE, UT 84062855-475-9765 ! WARNING ! DUAL POWER SOURCES. SECOND SOURCE IS PV SYSTEM LABEL 7 PHOTOVOLTAICAC DISCONNECT OPERATING CURRENT: 40 A AC OPERATING VOLTAGE: 240 V AC LABEL 5 AT POINT OF INTERCONNECTION, MARKED AT DISCONNECTING MEANS [NEC 690.54] ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON BOTH LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. LABEL 3 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.13 AND 690.15] PHOTOVOLTAICDC DISCONNECT UTILITYAC DISCONNECT LABEL 10 AT EACH DC DISCONNECTING MEANS [NEC 690.13(B)] LABEL 12 AT EXPOSED RACEWAYS, CABLE TRAYS, AND OTHER WIRING METHODS; SPACED AT MAXIMUM 10 FT SECTION OR WHERE SEPARATED BY ENCLOSURES, WALLS, PARTITIONS, CEILINGS, OR FLOORS. [NEC 690.31(G)] LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 13 AT EACH AC DISCONNECTING MEANS [NEC 690.13(B)] ! CAUTION ! PHOTOVOLTAIC SYSTEM CIRCUIT IS BACKFED ! WARNING ! POWER SOURCE OUTPUT CONNECTION - DO NOT RELOCATE THIS OVERCURRENT DEVISE LABEL 14 AT POINT OF INTERCONNECTION OVERCURRENT DEVICE [NEC 705.12(B)(2)(3)(B)] LABEL 9 AT UTILITY METER [NEC 690.56(B)] LABEL 4 AT EACH DC DISCONNECTING MEANS [NEC 690.53] LABEL 11 AT RAPID SHUTDOWN SWITCH [NEC 690.56(C)]. LETTERS AT LEAST 3/8 INCH; WHITE ON RED BACKGROUND; REFLECTIVE [IFC 605.11.1.1] LABEL 8 AT POINT OF INTERCONNECTION; LABEL, SUCH AS LABEL 7 OR LABEL 8 MUST IDENTIFY PHOTOVOLTAIC SYSTEM [NEC 705.12(B)(4)] TURN RAPID SHUTDOWN SWICH TO THE "OFF" POSITION TO SHUTDOWN PV SYSTEM AND REDUCE SHOCK HAZARD IN ARRAY LABEL 1 AT RAPID SHUTDOWN SYSTEM [NEC 690.56(C)(1)(A)]. ! WARNING ! ELECTRIC SHOCK HAZARD TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION. DC VOLTAGE IS ALWAYS PRESENT WHEN SOLAR MODULES ARE EXPLOSED TO SUNLIGHT LABEL 2 AT EACH DISCONNECTING MEANS FOR PHOTOVOLTAIC EQUIPMENT [NEC 690.15] MAXIMUM VOLTAGE: 480 V DC MAXIMUM CIRCUIT CURRENT: 20 A DC MAX RATED OUTPUT CURRENT OF THE CHARGE CONTROLLER OR DC-TO-DC CONVERTER (IF INSTALLED):15 A DC LABEL 6 AT RAPID SHUTDOWN DISCONNECT SWITCH [NEC 690.56(C)(3)]. #03-359 LOCAL CODES MAIN SERVICE PANEL FOR ILLUSTRATION ONLY (NOT ACTUAL MSP) MAIN SERVICE METER PV SUB PANEL (IF USED) AC DISCONNECT UTILITY AC DISCONNECT (IF USED) STRING INVERTER (IF USED)JUNCTION BOX (IF USED) #XX-XXX-XXX PRODUCTION METER (IF USED) 4 5 7 89 10 13 2 2 2 2 2 1 6 6 6 FOR MICRO INVERTERS ONLY (NO KNIFE SWITCH DISCONNECT) 611 11 1414 3 3 3 3 DC DISCONNECT (IF USED) BI-DIRECTIONAL METER WARNING: PHOTOVOLTAIC POWER SOURCE PHOTOVOLTAIC SYSTEM EQUIPPED WITH RAPID SHUTDOWN RAPID SHUTDOWN SWITCH FOR SOLAR PV SYSTEM SOLAR PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN SOLAR ELECTRIC PV PANELS WARNING THIS SERVICE METER IS ALSO SERVED BY A PHOTOVOLTAIC SYSTEM ELECTRICAL LABELS LABELING NOTES 1.1 LABELING REQUIREMENTS BASED ON THE 2020 NATIONAL ELECTRICAL CODE, INTERNATIONAL FIRE CODE 605.11, OSHA STANDARD 1910.145, ANSI Z535 1.2 MATERIAL BASED ON THE REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION. 1.3 LABELS TO BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT INVOLVED. 1.4 LABELS TO BE A MINIMUM LETTER HEIGHT OF 3/8” AND PERMANENTLY AFFIXED. 1.5 ALERTING WORDS TO BE COLOR CODED. “DANGER” WILL HAVE RED BACKGROUND; “WARNING” WILL HAVE ORANGE BACKGROUND; “CAUTION” WILL HAVE YELLOW BACKGROUND. [ANSI Z535] PERMANENT PLAQUE OR DIRECTORY PROVIDING THE LOCATION OF THE SERVICE DISCONNECTING MEANS AND THE PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS IF NOT IN THE SAME LOCATION [NEC 690.56(B)] WHERE THE PV SYSTEMS ARE REMOTELY LOCATED FROM EACH OTHER, A DIRECTORY IN ACCORDANCE WITH 705.10 SHALL BE PROVIDED AT EACH PV SYSTEM DISCONNECTING MEANS. PV SYSTEM EQUIPMENT AND DISCONNECTING MEANS SHALL NOT BE INSTALLED IN BATHROOMS [NEC 690.4(D),(E)] ALL SIGNAGE MUST BE PERMANENTLY ATTACHED AND BE WEATHER RESISTANT/SUNLIGHT RESISTANT AND CANNOT BE HAND-WRITTEN PER NEC 110.21(B) PV-5 ARTERBURN, KATHERINE 630 PINEWOOD LN ESTES PARK, CO 80517 REVIEWED BY SAFEBUILT 08/04/2022 663 W. STATE STREET, #3 PLEASANT GROVE, UT 84062855-475-9765 ELECTRICAL PHOTOS PV-6 ARTERBURN, KATHERINE 630 PINEWOOD LN ESTES PARK, CO 80517 DATE: 7/5/2022 DRAWN BY: KM REVIEWED BY SAFEBUILT 08/04/2022 N CAUTION POWER TO THIS BUILDING IS SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN !! SERVICE 1 OF 1 630 PINEWOOD LN , ESTES PARK, CO 80517 UTILITY METER MAIN SERVICE PANEL AC DISCONNECT INVERTER SOLAR PHOTOVOLTAIC ARRAY REVIEWED BY SAFEBUILT 08/04/2022 REVIEWED BY SAFEBUILT 08/04/2022 REVIEWED BY SAFEBUILT 08/04/2022 Single Phase Energy Hub Inverter with Prism Technology For North America SE3000H-US / SE3800H-US / SE6000H-US / SE7600H-US / SE10000H-US / SE11400H-US(1) 12-25 YEAR WARRANTY Optimized battery storage with HD-Wave technology Record-breaking 99% weighted efficiency with 200% DC oversizing Small, lightweight, and easy to install Modular design, future ready with optional upgrades to: DC-coupled storage for full or partial home backup Built-in consumption monitoring Direct connection to the SolarEdge smart EVcharger Multi-inverter, scalable storage solution With enhanced battery power up to 10kW Integrated arc fault protection and rapid shutdown for NEC 2014,NEC 2017 and NEC 2020,per article 690.11 and 690.12 Embedded revenue grade production data, ANSI C12.20 Class 0.5 solaredge.com HO M E BA C K U P REVIEWED BY SAFEBUILT 08/04/2022 Single Phase Energy Hub Inverter with Prism Technology For North America SE3000H-US / SE3800H-US / SE6000H-US / SE7600H-US / SE10000H-US / SE11400H-US(1) SE3000H-US SE3800H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US UNITS OUTPUT - AC ON GRID Rated AC Power 3000 3800 @ 240V 3300 @ 208V 6000 @ 240V 5000 @ 208V 7600 10000 11400 @ 240V 10000 @ 208V W Maximum AC Power Output 3000 3800 @ 240V 3300 @ 208V 6000 @ 240V 5000 @ 208V 7600 10000 11400 @ 240V 10000 @ 208V W AC Frequency Range (min - nom - max) 59.3 - 60 - 60.5(2)Hz Maximum Continuous Output Current @ 240V 12.5 16 25 32 42 47.5 A Maximum Continuous Output Current @ 208V - 16 24 - - 48.5 A GFDI Threshold 1 A Total Harmonic Distortion (THD) <3 % Power Factor 1, adjustable -0.85 to 0.85 Utility Monitoring, Islanding Protection, Country Configurable Thresholds Yes Charge Battery from AC (if allowed) Yes Typical Nighttime Power Consumption <2.5 W OUTPUT - AC BACKUP(3) Rated AC Power in Backup Operation(4) 3000 3800 6000 7600 10000 10300 W 7600* 10300* AC L-L Output Voltage Range in Backup 211 - 264 Vac AC L-N Output Voltage Range in Backup 105 - 132 Vac AC Frequency Range in Backup (min - nom - max) 55 - 60 - 65 Hz Maximum Continuous Output Current in Backup Operation 12.5 16 25 32 42 43 A 32* 43* GFDI 1 A THD <5 % OUTPUT - SMART EV CHARGER AC Rated AC Power 9600 W AC Output Voltage Range 211 - 264 Vac On-Grid AC Frequency Range (min - nom - max) 59.3 - 60 - 60.5 Hz Maximum Continuous Output Current @240V (grid, PV and battery) 40 Aac INPUT - DC (PV AND BATTERY) Transformer-less, Ungrounded Yes Max Input Voltage 480 Vdc Nom DC Input Voltage 380 Vdc Reverse-Polarity Protection Yes Ground-Fault Isolation Detection 600kΩ Sensitivity INPUT - DC (PV) Maximum DC Power @ 240V 6000 7600 12000 15200 22000 22800 W 15200* 22800* Maximum DC Power @ 208V - 6600 10000 - - 20000 W Maximum Input Current(5) @ 240V 8.5 10.5 16.5 20 27 31 Adc 20* 31* Maximum Input Current(5) @ 208V - 9 13.5 - - 27 Adc Max. Input Short Circuit Current 45 Adc Maximum Inverter Efficiency 99 99.2 % CEC Weighted Efficiency 99 99 @ 240V 98.5 @ 208V % 2-pole Disconnection Yes *Supported with PN SExxxxH-USMMxxxxxx or SExxxxH-USMNxxxxxx (1) These specifications apply to inverters with part numbers SExxxxH-USSMxxxxx or SExxxxH-USSNxxxxxx and connection unit model number DCD-1PH-US-PxH-F-x (2) For other regional settings please contact SolarEdge support (3) Not designed for standalone applications and requires AC for commissioning. Backup functionality is only supported for 240V grid(4) Rated AC power in Backup Operation are valid for installations with multiple inverters. For a single backup inverter operation, rated AC power in Backup is 90% of the value stated (5) A higher current source may be used; the inverter will limit its input current to the values stated REVIEWED BY SAFEBUILT 08/04/2022 Single Phase Energy Hub Inverter with Prism Technology For North America SE3000H-US / SE3800H-US / SE6000H-US / SE7600H-US / SE10000H-US / SE11400H-US(1) SE3000H-US SE3800H-US SE6000H-US SE7600H-US SE10000H-US SE11400H-US UNITS INPUT - DC (BATTERY) Supported Battery Types SolarEdge Energy Bank, LG RESU Prime(6) Number of Batteries per Inverter Up to 3 SolarEdge Energy Bank, up to 2 LG RESU Prime Continuous Power(7) 6000 7600 10000 W Peak Power(7) 6000 7600 10000 W Max Input Current 16 20 26.5 Adc 2-pole Disconnection Yes SMART ENERGY CAPABILITIES Consumption Metering Built - in(8) Backup & Battery Storage With Backup Interface (purchased separately) for service up to 200A; Up to 3 inverters EV Charging Direct connection to Smart EV charger ADDITIONAL FEATURES Supported Communication Interfaces RS485, Ethernet, Cellular(9), Wi-Fi (optional),SolarEdge Energy Net (optional) Revenue Grade Metering, ANSI C12.20 Built - in(8) Integrated AC, DC and Communication Connection Unit Yes Inverter Commissioning With the SetApp mobile application using built-in Wi-Fi Access Point for local connection DC Voltage Rapid Shutdown (PV and Battery) Yes, according to NEC 2014, NEC 2017 and NEC 2020 690.12 STANDARD COMPLIANCE Safety UL1741, UL1741 SA, UL1741 PCS, UL1699B, UL1998, UL9540, CSA 22.2 Grid Connection Standards IEEE1547, Rule 21, Rule 14H Emissions FCC part 15 class B INSTALLATION SPECIFICATIONS AC Output and EV AC Output Conduit Size / AWG Range 1'' maximum / 14-4 AWG DC Input (PV and Battery) Conduit Size / AWG Range 1'' maximum / 14-6 AWG Dimensions with Connection Unit (H x W x D) 17.7 x 14.6 x 6.8 / 450 x 370 x 174 17.7 x 14.6 x 6.8 / 450 x 370 x 174 17.7 x 14.6 x 6.8 / 450 x 370 x 174 in / mm 17.7 x 14.6 x 6.8 / 450 x 370 x 174* Weight with Connection Unit 26 / 11.8 26 / 11.8 30.2 / 13.7 lb / kg 30.2 / 13.7* Noise < 25 < 25 < 25 < 50 dBA < 50* Cooling Natural Convection Operating Temperature Range -40 to +140 / -40 to +60(10) ˚F / ˚C Protection Rating NEMA 4 (6)The part numbers SExxxxH-USxMxxxxx only support the SolarEdge Energy Bank. The part numbers SExxxxH-USxNxxxxx support both SolarEdge Energy Bank and LG RESU Prime batteries Requires supporting inverter firmware(7)Discharge power is limited up to the inverter rated AC power for on-grid and backup applications (8)For consumption metering current transformers should be ordered separately: SECT-SPL-225A-T-20 or SEACT0750-400NA-20 units per box. Revenue grade metering is only for production metering (9)Information concerning the Data Plan's terms & conditions is available in the following link: https://www.solaredge.com/sites/default/files/se-communication-plan-terms-and-conditions-eng.pdf (10)Full power up to at least 50°C / 122°F; for power de-rating information refer to: https://www.solaredge.com/sites/default/files/se-temperature-derating-note-na.pdf © SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners.Date:06/2021 DS-000031-1.5-NAM.Subject to change without notice. REVIEWED BY SAFEBUILT 08/04/2022 Power Optimizer For North America P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505 25 YEAR WARRANTY PV power optimization at the module-level Specifically designed to work with SolarEdge inverters Up to 25% more energy Superior efficiency (99.5%) Mitigates all types of module mismatch losses, from manufacturing tolerance to partial shading Flexible system design for maximum space utilization Fast installation with a single bolt Next generation maintenance with module- level monitoring Meets NEC requirements for arc fault protection (AFCI) and Photovoltaic Rapid Shutdown System (PVRSS) Module-level voltage shutdown for installer and firefighter safety solaredge.com P O W E R OP T I M I Z E R REVIEWED BY SAFEBUILT 08/04/2022 Power Optimizer For North America P320 / P340 / P370 / P400 / P401 / P405 / P485 / P505 Optimizer model (typical module compatibility) P320 (for 60-cell modules) P340 (for high- power 60-cellmodules) P370 (for higher- power 60 and 72- cell modules) P400 (for 72 & 96-cellmodules) P401 (for high power 60 and 72 cell modules) P405 (for high- voltage modules) P485 (for high- voltage modules) P505 (for higher current modules) INPUT Rated Input DC Power(1) 320 350 370 400 485 505 W Absolute Maximum Input Voltage (Voc at lowest temperature) 48 60 80 60 125(2) 83(2) Vdc MPPT Operating Range 8 - 48 8 - 60 8 - 80 8-60 12.5 - 105 12.5 - 83 Vdc Maximum Short Circuit Current (Isc) 11 11.02 11 10.1 11.75 11 14 Adc Maximum DC Input Current 13.75 12.5 14.65 12.5 17.5 Adc Maximum Efficiency 99.5 % Weighted Efficiency 98.8 98.6 % Overvoltage Category II OUTPUT DURING OPERATION (POWER OPTIMIZER CONNECTED TO OPERATING SOLAREDGE INVERTER) Maximum Output Current 15 Adc Maximum Output Voltage 60 85 Vdc OUTPUT DURING STANDBY (POWER OPTIMIZER DISCONNECTED FROM SOLAREDGE INVERTER OR SOLAREDGE INVERTER OFF) Safety Output Voltage per Power Optimizer 1 ± 0.1 Vdc STANDARD COMPLIANCE EMC FCC Part15 Class B, IEC61000-6-2, IEC61000-6-3 Safety IEC62109-1 (class II safety), UL1741 Material UL94 V-0, UV Resistant RoHS Yes INSTALLATION SPECIFICATIONS Maximum Allowed System Voltage 1000 Vdc Compatible inverters All SolarEdge Single Phase and Three Phase inverters Dimensions (W x L x H) 129 x 153 x 27.5 / 5.1 x 6 x 1.1 129 x 153 x 33.5 / 5.1 x 6 x 1.3 129 x 153 x 29.5 / 5.1 x 6 x 1.16 129 x 159 x 49.5 / 5.1 x 6.3 x 1.9 129 x 162 x 59 / 5.1 x 6.4 x 2.3 mm / in Weight (including cables) 630 / 1.4 750 / 1.7 655 / 1.5 845 / 1.9 1064 / 2.3 gr / lb Input Connector MC4(3) Single or dual MC4(3)(4) MC4(3) Input Wire Length 0.16 / 0.52 0.16 or 0.9 /0.52 or 2.95(5) 0.16 / 0.52 m / ft Output Wire Type / Connector Double Insulated / MC4 Output Wire Length 0.9 / 2.95 1.2 / 3.9 m / ft Operating Temperature Range(6) -40 to +85 / -40 to +185 ˚C / ˚F Protection Rating IP68 / NEMA6P Relative Humidity 0 - 100 % (1)Rated power of the module at STC will not exceed the optimizer “Rated Input DC Power ”. Modules with up to +5% power tolerance are allowed (2)NEC 2017 requires max input voltage be not more than 80V (3)For other connector types please contact SolarEdge (4)For dual version for parallel connection of two modules use P485-4NMDMRM. In the case of an odd number of PV modules in one string, installing one P485 dual version power optimizer connected to one PV module. When connecting a single module seal the unused input connectors with the supplied pair of seals(5)Longer inputs wire length are available for use. For 0.9m input wire length order P401-xxxLxxx(6)For ambient temperature above +85°C / +185°F power de-rating is applied. Refer to Power Optimizers Temperature De-Rating Technical Note for more details PV System Design Using a SolarEdge Inverter(7)(8) Single Phase HD-Wave Single phase Three Phase for 208V grid Three Phase for 277/480V grid Minimum String Length (Power Optimizers) P320, P340, P370, P400, P401 8 10 18 P405, P485, P505 6 8 14 Maximum String Length (Power Optimizers) 25 25 50(9) Maximum Power per String 5700 (6000 with SE7600-US - SE11400- US) 5250 6000(10) 12750(11) W Parallel Strings of Different Lengths or Orientations Yes (7) For detailed string sizing information refer to: http://www.solaredge.com/sites/default/files/string_sizing_na.pdf (8) It is not allowed to mix P405/P485/P505 with P320/P340/P370/P400/P401 in one string (9) A string with more than 30 optimizers does not meet NEC rapid shutdown requirements; safety voltage will be above the 30V requirement (10) For 208V grid: it is allowed to install up to 6,500W per string when the maximum power difference between each string is 1,000W (11) For 277/480V grid: it is allowed to install up to 15,000W per string when the maximum power difference between each string is 2,000W © SolarEdge Technologies Ltd. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein are trademarks of their respective owners. Date: 08/2021 DS-000044-1.2-NA. Subject to change without notice. 405 REVIEWED BY SAFEBUILT 08/04/2022 INSTALLATION MANUAL FLUSH MOUNT INSTALLATION MANUAL REVIEWED BY SAFEBUILT 08/04/2022 CONTeNTS FLUSH MOUNT INSTALLATION MANUAL - 1© 2019 IRONRIDGE, INC. VERSION 2.3 DISCLAIMER 1RATINGS 2MARKINGS 2CHECKLIST 31. ATTACH BASES 42. PLACE RAILS 43. SECURE LUGS 54. SECURE MODULES 5CAMO 6BONDING JUMPER 6EXPANSION JOINTS 7ELECTRICAL DIAGRAM 8FLASHFOOT2 9ALL TILE HOOK 9KNOCKOUT TILE 9FLAT ROOF ATTACHMENT 10END CAPS 10WIRE CLIPS 10FLUSH STANDOFFS 10MICROINVERTER KITS 11SYSTEMS USING ENPHASE MICROINVERTERS OR SUNPOWER AC MODULES 11SYSTEMS USING MICROSTORAGE PRODUCTS 12FRAMELESS MODULE KITS 12MODULE COMPATIBILITY 13MODULE COMPATIBILITY 14MODULE COMPATIBILITY 15MODULE COMPATIBILITY 16 DISCLAIMeR This manual describes proper installation procedures and provides necessary standards required for product reliability. Warranty details are available on website. All installers must thoroughly read this manual and have a clear understanding of the installation procedures prior to installation. Failure to follow these guidelines may result in property damage, bodily injury or even death. IT IS THe INSTALLeR’S ReSPONSIBILITY TO: • Ensure safe installation of all electrical aspects of the array. All electrical installation and procedures should be conducted by a licensed and bonded electrician or solar contractor. Routine maintenance of a module or panel shall not involve breaking or disturbing the bonding path of the system. All work must comply with national, state and local installation procedures, product and safety standards. • Comply with all applicable local or national building and fire codes, including any that may supersede this manual. • Ensure all products are appropriate for the installation, environment, and array under the site’s loading conditions. • Use only IronRidge parts or parts recommended by IronRidge; substituting parts may void any applicable warranty. • Review the Design Assistant and Certification Letters to confirm design specifications. • Ensure provided information is accurate. Issues resulting from inaccurate information are the installer’s responsibility. • Ensure bare copper grounding wire does not contact aluminum and zinc-plated steel components, to prevent risk of galvanic corrosion. • If loose components or loose fasteners are found during periodic inspection, re-tighten immediately. If corrosion is found, replace affected components immediately. • Provide an appropriate method of direct-to-earth grounding according to the latest edition of the National Electrical Code, including NEC 250: Grounding and Bonding, and NEC 690: Solar Photovoltaic Systems. • Disconnect AC power before servicing or removing modules, AC modules, microinverters and power optimizers. • Review module manufacturer’s documentation for compatibility and compliance with warranty terms and conditions. REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 2© 2019 IRONRIDGE, INC. VERSION 2.3 RATINGS Product markings are located on the Grounding Lug bolt head. MARKINGS UL 2703 LISTeD • Conforms to STD UL 2703 (2015) Standard for Safety First Edition: Mounting Systems, Mounting Devices, Clamping/Retention Devices, and Ground Lugs for Use with Flat-Plate Photovoltaic Modules and Panels. • Certified to CSA STD LTR AE-001-2012 Photovoltaic Module Racking Systems. • Max Overcurrent Protective Device (OCPD) Rating: 25A • Max Module Size: 24ft² • Max Frameless Module Size for Canadian LTR-AE: 19.5 ft² • Module Orientation: Portrait or Landscape • CAMO Specific Allowable Design Load Rating: 50 PSF downward, 50 PSF upward, 15 PSF lateral • LTR AE Canadian Load Rating: 2400 PA • System Level Allowable Design Load Rating: meets minimum requirements of the standard (10 PSF downward, 5 PSF upward, 5 PSF lateral). Actual system structural capacity is defined by PE stamped certification letters. CLASS A SYSTeM FIRe RATING PeR UL 2703 • Any Roof Slope with Module Types 1, 2, and 3• Any module-to-roof gap is permitted, with no perimeter guarding required. This rating is applicable with any third-party attachment.• Class A rated PV systems can be installed on Class A, B, and C roofs without affecting the roof fire rating. WATeR SeAL RATINGS: UL 441 & TAS 100(A)-95 (FLASHFOOT2, ALL TILe HOOK, KNOCKOUT TILe) • Tested and evaluated without sealant. • Any roofing manufacturer approved sealant is allowed. Ratings applicable for roof slopes between 2:12 and 12:12 STRUCTURAL CeRTIFICATION • Designed and Certified for Compliance with the International Building Code & ASCE/SEI-7 FLORIDA PRODUCT APPROVAL #FL29843 • Conforms to TAS202, TAS100(A) • Approved for installation both inside and outside High Velocity Hurricane Zones (HVHZ) • Allowable design pressure up to +100/-100 PSF • Additional details on Approval can be found Here. #5003807 REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 3© 2019 IRONRIDGE, INC. VERSION 2.3 CHeCKLIST PRe-INSTALLATION ☐Verify module compatibility. See Page 10 for info. TOOLS ReQUIReD ☐Cordless Drill (non-impact) ☐Impact Driver (for lag bolts) ☐Torque Wrench (0-250 in-lbs) ☐5/16” Socket ☐7/16” Socket ☐1/2" Socket ☐String Line TORQUe VALUeS ☐FlashFoot2 Lag Bolts (7/16" Socket): Fully Seat ☐Bonded Splice Screws (5/16" Socket): 20 in-lbs ☐Grounding Lug Nuts (7/16" Socket): 80 in-lbs ☐Grounding Lug Terminal Screws (7/16" Socket): 20 in-lbs ☐Universal Fastening Object (7/16" Socket): 80 in-lbs ☐Expansion Joint Nuts (7/16" Socket): 80 in-lbs ☐Flush Standoffs (1/2" Socket): 132 in-lbs ☐Microinverter Kit Nuts (7/16" Socket): 80 in-lbs ☐Frameless Module Kit Nuts (7/16" Socket): 80 in-lbs ☐3/8" Bonding Hardware Nuts (7/16" Socket): 250 in-lbs ☐ All Tile Hook Lags (7/16" Socket): Fully Seat ☐All Tile Hook Carriage Bolts (7/16" Socket): 132 in-lbs ☐Knockout Tile Lags (1/2" Socket): Fully Seat ☐Knockout Tile Nuts (1/2" Socket): 132 in-lbs ☐Flat Roof Attachment Nuts (9/16” Socket): 250 in-lbs Þ If using FlashVue or previous version of: FlashFoot, Integrated Grounding Mid Clamps, Grounding Lug, End Clamps, and Expansion Joints please refer to Alternate Components Addendum (Version 1.3). IRONRIDGe COMPONeNTS Bonded SpliceXR Rail L-Foot FlashFoot2 UFO and Stopper Sleeve CAMO Grounding Lug8" Bonding Jumper Expansion Joint Wire ClipEnd Cap Flush Standoff 3/8" Bonding HardwareMicroinverter Kit Frameless Module Kit A A B B C C D D E E F F 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 Frameless End/Mid Clamp All Tile Hook FlashingA A B B C C D D E E F F 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 Knockout TileA A B B C C D D E E F F 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 Membrane Flashing All Tile Hook Flat Roof Attachment REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 4© 2019 IRONRIDGE, INC. VERSION 2.3 1. ATTACH BASeS A. CONNeCT SPLICeS Use Bonded Splices, when needed, to join multiple sections of rail. Insert Bonded Splice 6" into first rail and secure with two self-drilling screws, spacing them approximately 1” apart and tightening to 20 in-lbs. Slide second rail over Bonded Splice and secure with two more self-drilling screws. Þ Rows exceeding 100 feet of rail must use expansion Joints. Þ For XR10 and XR100 rails, insert screws along the provided lines. Þ Refer to Structural Certification letters for rail splice location requirements. Þ Screws can be inserted on front or back of rails. B. PRePARe HARDWARe Slide square-headed bolts into side-facing rail slot. Space out bolts to match attachment spacing. Þ Tape ends of rail, to keep bolts from sliding out while moving. Þ If using T-bolts, carry hardware onto roof and proceed. C. ATTACH RAILS Drop rail with hardware into roof attachment. Level rail at desired height, then torque to 250 in-lbs. Þ Rail can face either upslope or downslope on roof. 2. PLACe RAILS C Torque to 250 in-lbs B Preload and Space Square Bolts A Torque to 20 in-lbs 6" Inside Rail 1" Þ Tested or evaluated third-party roof attachments:• Anchor Products - U-Anchor • S-5! Standing Seam Metal Roof Clamps - Certification of metal roof clamps includes bonding to both painted and galvalume metal roofs. Tighten S-5! and S-5! Mini set screws to 130- 150 in-lbs (≥ 24 gauge) or 160-180 in-lbs (22 gauge) roofs. Tighten S-5! M10 bolt to 240 in-lbs or S-5! Mini M8 bolt to 160 in-lbs. Use the following fastening guidelines for other S-5! roof clamps: ProteaBracket™ - firmly seat roof screws and tighten hinge bolt to 225 in-lbs; RibBracket™ - firmly seat roof screws and tighten M8 bolt (M8-1.25 x 22mm sold separately) to 160 in-lbs; and SolarFoot™ - firmly seat roof screws and tighten M8 flange nut to 160 in-lbs. • ecoFasten Green Fasten GF-1 Anchors • Rooftech RT-Mini - Attach to L-foot using 5/16-18 x 1.25" stainless steel bolt and nut torqued to 132 in-lbs. • QuickMount PV Roof Mounts QMLM/QMLM - ST and Tile Hooks - Tile Hook attaches to XR Rail using 3/8" Bonding Hardware Kit torqued to 250 in-lbs. • Quickscrews Solar Roof Hooks, ejot Aluminum Roof Hooks, Unirac Creotecc Tile Hooks, or Solarhooks - Attach to XR Rails with L-Foot or 3/8” Bonding Hardware Kit torqued to 250 in-lbs. • Pegasus Comp Mount - Attach to XR Rail using 3/8" Bonding Hardware kit torqued to 250 in-lbs. For composition roofs, refer to FlashFoot2 install instructions on page 8. For tile roofs, refer to All Tile Hook and Knockout Tile install instructions on page 8 and 9. For flat roofs, refer to Flat Roof Attachment install instructions on page 9. When using approved third party attachments, refer to manufacturer's install instructions. REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 5© 2019 IRONRIDGE, INC. VERSION 2.3 3. SeCURe LUGS Insert T-bolt in top rail slot and torque hex nut to 80 in- lbs. Install a minimum 10 AWG solid copper or stranded grounding wire. Torque terminal screw to 20 in-lbs. Þ Ground Lugs are only needed on one rail per continuous row of modules, regardless of row length (unless frameless modules are being used, see Page 9). Þ If using enphase microinverters or Sunpower AC modules, Grounding Lugs may not be needed. See Page 9 for more info. Þ Grounding Lugs can be installed anywhere along the rail and in either orientation shown. If installing lug underneath modules in areas with ground snow loads greater than 40 psf, place lug within 4 inches module frame edge. 4. SeCURe MODULeS A. SeCURe FIRST eND Place first module in position on rails, a minimum of 1” from rail ends. Snap Stopper Sleeves onto UFO. Fasten module to rail using the UFO, ensuring that the UFO is hooked over the top of the module. Torque to 80 in-lbs. Þ ensure rails are square before placing modules. Þ Hold Stopper Sleeves on end while torquing to prevent rotation. Þ If using CAMO instead of UFO + Stopper Sleeve, refer to Page 6 for CAMO installation procedure. B. SeCURe NeXT MODULeS Place UFO into each rail, placing them flush against first module. Slide second module against UFO. Torque to 80 in-lbs. Repeat for each following module. Þ When reinstalling UFO, move modules a minimum of 1/16" so UFOs are in contact with a new section of module frame. Þ When UFOs are loosened and re-tightened, ensure UFO T-bolt bottoms out in rail channel before re-torquing UFO to achieve full engagement between T-bolt and rail. Þ If using Wire Clips, refer to Page 9. C. SeCURe LAST eND Place last module in position on rails, a minimum of 1” from rail ends. Snap Stopper Sleeves onto UFO. Secure UFO Clamps on rails, ensuring they are hooked over top of module. Torque to 80 in-lbs. Þ Hold Stopper Sleeves on end while torquing to prevent rotation. Þ Repeat all steps for each following row of modules, leaving a minimum 3/8" gap between rows. Þ If using CAMO instead of UFO + Stopper Sleeve, refer to Page 6 for CAMO installation procedure. A B Hex Nut (84 in-lbs) Terminal Screw (20 in-lbs) C Hex Nut (80 in-lbs) 1" From Rail End UFO (80 in-lbs) Stopper Sleeve UFO (80 in-lbs) UFO (80 in-lbs) Use with one solid or stranded copper wire, conductor size 10-4AWG. REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 6© 2019 IRONRIDGE, INC. VERSION 2.3 B. PLACe MODULe Place module on rails (module cells not shown for clarity). When installing CAMO the module can overhang the rail no more than 1/4". D. SeCURe TO FRAMe Rotate handle with an upwards motion until CAMO snaps into rail channel. Ensure CAMO bonding pins are fully seated on top of module frame. CAMO A. SLIDe INTO RAIL Slide CAMO into rail channel far enough to clear the module frame. CAMO requires 6" of clearance from end of rail. C. PULL TOWARDS eND Pull CAMO towards rail ends, at 45 degree angle, so the bonding bolt contacts the module flange edge. B C D A 6" C l e a r a n c e 8" BONDING JUMPER 8" Bonding Jumper is an electrical bonding jumper that can be used on the Flush Mount System for row to row bonding; making the module frames the medium for the equipment ground path. Þ Bonding jumper is pushed onto the bottom flange of the module. Þ New jumpers should be used if re-installation of jumper is required. Þ Supports bottom flange thicknesses from 1.2mm to 3.1mm. FRAMe COMPATIBILITY CAMO has been tested or evaluated with all modules listed in the Module Compatibility section having frames within the referenced dimensions. Be sure the specific module being used meets the dimension requirements. Þ For installations with Hanwha Q CeLLS modules with 32 mm frame heights, the maximum ground snow is 45 PSF (33 PSF module pressure). Þ CAMO is not compatible with Canadian Solar modules. REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 7© 2019 IRONRIDGE, INC. VERSION 2.3 eXPANSION JOINTS GROUNDING STRAP eXPANSION JOINT Grounding Strap Expansion Joints are required every 100' of continuous rail to allow for thermal expansion and contraction of the system. Insert Bonded Splice 6" into first rail and secure with two self-drilling screws, spacing them approximately 1” apart and tightening to 20 in-lbs. Assemble and secure Grounding Strap 3/8" from rail end. Slide second rail over Bonded Splice leaving 1" gap between rails. Attach other end of Grounding Strap with hardware and torque hex nuts to 80 in-lbs. Þ Remaining Bonded Splice screws are not used with expansion. Þ Only one Grounding Strap is required per break in row of modules. Þ Do not install modules over expansion joints. A A B B C C D D E E F F 8 8 7 7 6 6 5 5 4 4 3 3 2 2 1 1 Torque to 80 in-lbs 1" Gap 3/8" from Rail End Fully Seat Tek Screws Insert Splice 6" Into Rail No Modules Over Gap One Bonding Strap Per Break In Array REVIEWED BY SAFEBUILT 08/04/2022 eND CAPS (OPTIONAL) FLUSH MOUNT INSTALLATION MANUAL - 8© 2019 IRONRIDGE, INC. VERSION 2.3 eLeCTRICAL DIAGRAM UFO Grounding Lug Minimum 10 AWG Copper Wire Fault Current Ground Path Bonded Splice (Rail Connection) ** *Grounding Lugs and wire are not required in systems using certain Enphase microinverters or certain Sunpower modules. Equipment grounding is achieved with the Engage cable for Enphase or the AC module cable system for Sunpower via their integrated EGC. ** The use of the 8" Bonding Jumper eliminates the need for row to row bonding. A minimum of one grounding lug per continuous array is required for earth ground. CAMO orUFO or CAMO 8" Bonding Jumper (Alternative row to row bond)** REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 9© 2019 IRONRIDGE, INC. VERSION 2.3 FLASHFOOT2 Locate roof rafters and mark locations on roof. Drill 1/4” pilot holes and backfill with approved sealant. Slide flashing between 1st and 2nd course of shingles, ensuring flashing doesn't overhang the downhill shingle. Line up with pilot hole and insert supplied lag bolt with washer through flashing. Fully seat lag bolt. Place Cap onto flashing in desired orientation for E/W or N/S rails and rotate 180 degrees until it locks into place. Þ Rail can be installed on either side of FlashFoot2 Cap. Þ Standalone FlashFoot2 manual available on website. Remove tile and mark rafter. Position base over rafter, adjust arm if necessary and torque hardware to 132 in-lbs (11 ft-lbs). Use base as guide to drill 1/4" pilot holes, back fill with roofing manufacturer’s approved sealant, then insert lag bolts and tighten until fully seated. Replace tiles and notch as necessary to ensure proper fit. Attach rails to either side of slot using bonding hardware and torque to 250 in-lbs (21-ft-lbs). Þ Position arm near the center of valley for curved tiles. Þ Position arm away from seam of joining flat tiles. Þ ensure top of hook does not extend above rail. Þ IronRidge offers an optional aluminum deck flashing. Refer to All Tile Hook Flashing Installation Manual. Other approved flashing methods include user supplied adhesive backed flexible flashing. Þ Standalone All Tile Hook manual available on website. ALL TILe HOOK KNOCKOUT TILe Remove tile and mark rafter. Use base as guide to drill 1/4” pilot hole and fill with roofing manufacturer’s approved sealant. Insert lag bolt with bonded washer through base and drive until fully seated. Insert Tile Replacement Flashing, lower onto base and apply pressure over the threaded post until it dimples the flashing. Place L-Foot over dimple and tap with hammer to punch threaded post through the flashing. Ensure punched pieces of flashing are cleared away. Form flashing as needed to sit flush with surrounding tiles, position L-Foot in desired orientation and torque hardware to 132 in-lbs (11 ft-lbs). Attach rail to either side of L-Foot with bonding hardware and torque to 250 in-lbs (21 ft-lbs). Þ Base can be installed in any orientation relative to rafter. Þ ensure L-Foot does not extend above rail. Þ If deck level flashing is required, approved flashing methods include user supplied adhesive backed flexible flashing. Þ Standalone Knockout Tile manual available on website. Rafter Torque to 132 in-lbs Torque to 250 in-lbs Rafter Orient Base to desired position Tighten until fully seated Dimple Tap With Hammer Torque to 132 in-lbs Torque to 250 in-lbs Tighten Until Fully Seated REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 10© 2019 IRONRIDGE, INC. VERSION 2.3 FLAT ROOF ATTACHMeNT End Caps add a completed look and keep debris and pests from collecting inside rail. Firmly press End Cap onto rail end. Þ end Caps come in sets of left and right. Check that the proper amount of each has been provided. WIRe CLIPS Wire Clips offer a simple wire management solution. Firmly press Wire Clip into top rail slot. Run electrical wire through open clip. Snap closed once all wires have been placed. Press Clip into Slot Run W i r e Snap Clip Closed Attach Standoffs to roof locations with lag bolts (not included). Place flashing over Standoff. Attach L-Foot on Standoff washer with hardware. Torque to 132 in-lbs (11 ft-lbs). Torque to 132 in-lbs (11 ft-lbs) FLUSH STANDOFFS Flashing Provided by Others eND CAPS Flat Roof Attachment can be used with an L-foot for flush mounting modules on low sloped roofs. Mark locations for Flat Roof Attachment. Screws should be installed symmetrically to each other. If using a membrane flashing, remove the silicone washer's protective liner prior to attaching the membrane. Attach L-foot with washers and 3/8” hardware torqued to 250 in-lbs (21 ft-lbs). Seal attachment and/or membrane per roofing manufacturer’s requirements. Þ Type, size, and quantity of roof screws to be specified by Structural engineer. Fastener size not to exceed #15. Þ Membrane flashing available for TPO, PVC, and KEE roofs. Ensure membrane flashing is compatible with existing roofing material. Þ If membrane flashing is not used, only washer on top of L-Foot is required. Þ Standalone Flat Roof Attachment manual available on website. 250 in-lbs Flat Roof Attachment Hardware L-Foot Flat Roof Attachment Membrane Flashing REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 11© 2019 IRONRIDGE, INC. VERSION 2.3 MICROINVeRTeR KITS SYSTeMS USING eNPHASe MICROINVeRTeRS OR SUNPOWeR AC MODULeS IronRidge systems using approved Enphase products or SunPower modules eliminate the need for lay-in lugs and field installed equipment grounding conductors (EGC). This solution meets the requirements of UL 2703 for bonding and grounding and is included in this listing. COMPATIBLe PRODUCTS SunpowerModules with model identifier Ab-xxx-YY and InvisiMount (G5) 46mm frame; where “A” is either E, or X; “b” can be 17, 18, 19, 20, 21, or 22; and “YY” can be C-AC, D-AC, BLK-C-AC, or BLK-D-AC. EnphaseMicroinverters M250-72, M250-60, M215-60, C250-72, and Engage cables ETXX-240, ETXX-208, ETXX-277.  Þ A minimum of two inverters mounted to the same rail and connected to the same Engage cable are required. Þ The microinverters or Sunpower AC modules must be used with a maximum 20 A branch rated overcurrent protection device (OCPD). Þ If an AC module is removed from a circuit for maintenance, you must first disconnect AC power and then install a temporary EGC to bridge the gap by inserting an AC extension cable (or via other NEC-compliant means), in order to maintain effective ground continuity to subsequent modules. One Microinverter Kit Required (80 in-lbs) Use IronRidge's Microinverter Kit to bond compatible microinverters and power optimizers to the racking system. Insert Microinverter Kit T-bolt into top rail slot. Place compatible microinverter or power optimizer into position and tighten hex nut to 80 in-lbs. Þ If installing in areas with ground snow loads greater than 40 psf, install MLPE devices directly next to module frame edge On AP systems equipment, remove Grounding Washer COMPATIBLe PRODUCTS EnphaseM250-72, 250-60, M215-60, C250-72, S230, S280, IQ 6, IQ 6+, IQ IQ7, IQ 7A, IQ 7+, IQ 7X, Q Aggregator DarfonMIG240, MIG300, G320, G640 Solar EdgeP300, P320, P340, P370, P400, P405, P485, P505, P600, P700, P730, P800p, P800s, P850, P860 SMA RoofCommKit-P2-US, TS4-R Module Retrofit Kits (TS4-R-S, TS4-R-O, TS4-R-F) Tigo Tigo Access Point (TAP), TS4-R-X (where X can be O, S, F, or M), TS4-R-X-DUO (where X can be O, S, or M), TS4-A-F, TS4- A-2F, TS4-A-O, TS4-A-O-DUO AP Systems QS1, YC600 Þ Remove Grounding Washer on AP Systems QS1 and YC600 inverters before installing to XR rails. Þ Remove the Stainless Steel Clip on Tigo-”A” MLPE Devices before attaching to XR rails. Þ Use the number of IronRidge Microinverter kits allowed by the MLPE mounting flange. Some will require 1 kit and others 2 kits. Two Microinverter Kits Required (80 in-lbs) REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 12© 2019 IRONRIDGE, INC. VERSION 2.3 Use IronRidge's Microinverter Kit to bond compatible microstroage devices to the racking system. Insert Microinverter Kit T-bolt into top rail slot. Place compatible microstorage into position and tighten hex nut to 80 in-lbs. Microinverter Kit (80 in-lbs) SYSTeMS USING MICROSTORAGe PRODUCTS Insert Frameless Kit T-bolt in top rail slot. Place star washer over T-bolt, allowing it to rest on top of rail. Secure module clamps with a hex nut and torque to 80 in-lbs. Place Star Washer Module Clamp (80 in-lbs)Grounding Lugs Required on Every Rail FRAMeLeSS MODULe KITS COMPATIBLe PRODUCTS PHAZR PHAZR Devices PHAZR-X, where X is 6-12. SolpadSolpad Inverter model SI-1kSolpad Battery Storage model SB-2K Solpad Junction Box model SJB-4k Þ Running a separate equipment grounding conductor to the PHAZR or Solpad devices is not required. Þ If installing in areas with ground snow loads greater than 40 psf and underneath a module, install PHAZR and Solpad devices as close as possible to module frame edge. Þ Solpad may only be installed on XR-100 and XR-1000 Þ Solpad may only be installed with modules having a frame thickness of 35mm or greater. Þ Use the number of IronRidge Microinverter kits allowed by the microstorage mounting flange. Some will require 1 kit and others 2 kits. COMPATIBLe PRODUCTS Sunforson Sunforson silver or black SFS-UTMC-200(B) mid and SFS-UTEC- 200(B) end clamps. SunpremeSunpreme silver or black mid and end clamps with part numbers 7500105X where "X" is 1, 5, 6 or 7. IronridgeIronRidge silver or black mid and end clamps with part numbers FMLS-XC-001-Y where "X" is E or M and "Y" is B or blank. Þ Follow module manufacturer's installation instructions to installthe module clamps. Þ Frameless modules require using a Grounding Lug on every rail. Þ For Sunpreme Modules Only: If required to use slide prevention hardware, see Module Slide Prevention Addendum (Version 1.10). Two sets of two Microinverter Kits (80 in-lbs) Solpad PHAZR REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 13© 2019 IRONRIDGE, INC. VERSION 2.3 MODULe COMPATIBILITY The Flush Mount System may be used to ground and/or mount a PV module complying with UL 2703 only when the specific module has been evaluated for grounding and/or mounting in compliance with the included instructions. Unless otherwise noted, “xxx” refers to the module power rating and both black and silver frames are included in the certification. MAKe MODELS Amerisolar Amerisolar modules with 35, 40 and 50 mm frames AS-bYxxxZ Where "b" can be 5 or 6; "Y" can be M, P, M27, P27, M30, or P30; "xxx" is the module power rating; and "Z" can be blank, W or WB Aptos Aptos modules with 35 and 40 mm frames DNA-yy-zz23-xxx Where "yy" can be 120 or 144; "zz" can be MF or BF; and ""xxx" is the module power rating Astronergy Solar Astronergy modules with 30, 35, 40 and 45 mm frames aaSMbbyyC/zz-xxx Where “aa” can be CH or A; "bb" can be 60, 66, or 72; “yy” can be blank, 10 or 12; "C" can M, P, M(BL), M-HC, M(BL)-HC, P-HC, M(DG), or M(DGT); “zz” can be blank, HV, F-B, or F-BH ; and “xxx” is the module power rating Astronergy frameless modules CHSM6610P(DG)-xxx Where “xxx” is the module power rating ASUN ASUN modules with 35 and 40 mm frames ASUN-xxx-YYZZ-aa Where "xxx" is the module power rating;" YY" can be 60 or 72; "ZZ" can be M,or MH5; and "aa" can be blank or BB Auxin Auxin modules with 40 mm frames AXN6y6zAxxx Where "y" can be M or P; "z" can be 08, 09, 10, 11, or 12; "A" can be F or T; and "xxx" is the module power rating Axitec Axitec Modules with 35 and 40 mm frames AC-xxxY/aaZZb Where "xxx" is the module power rating; "Y" can be M, P or MH; "aa" can be blank, 125- or 156-; "ZZ" can be 54, 60, 72, 120, or 144; "b" can be S or SB Boviet Boviet modules with 35 and 40mm frames BVM66aaYY-xxxBB Where "aa" can be 9, 10 or 12; "YY" is M or P; "xxx" is the module power rating; and "BB" can be blank or L BYD BYD modules with 35 mm frames BYDxxxAY-ZZ Where "xxx" is the module power rating; "A" can be M6, P6, MH or PH; "Y" can be C or K; and "ZZ" can be 30 or 36 Canadian Solar Canadian Solar modules with 30, 35 and 40 mm frames CSbY-xxxZ Where "b" can be 1, 3 or 6; "Y" can be H, K, P, U, V, W, or X; "xxx" refers to the module power rating; and "Z" can be M, P, MS, PX , M-SD, P-AG, P-SD, MB-AG, PB-AG, MS-AG, or MS-SD Canadian Solar frameless modules CSbY-xxx-Z Where "b" can be 3 or 6; "Y" is K, P, U, or X; "xxx" is the module power rating, and "Z" can be M-FG, MS-FG, P-FG, MB-FG, or PB-FG CertainTeed CertainTeed modules with 35 and 40 frames CTxxxYZZ-AA Where "xxx" is the module power rating; "Y" can be M, P or HC; "ZZ" can be 00,01, 10, or 11; and "AA" can be 01, 02, 03 or 04 CSUN Csun modules with 35 and 40 mm frames YYxxx-zzAbb Where "YY" is CSUN or SST; xxx is the module power rating; "zz" is blank, 60, or 72; and "A" is blank, P or M; "bb" is blank, BB, BW, or ROOF Ecosolargy Ecosolargy modules with 35, 40 and 50 mm frames ECOxxxYzzA-bbD Where "xxx" is the module power rating; "Y" can be A, H, S, or T; "zz" can be 125 or 156; "A" can be M or P; "bb" can be 60 or 72; and "D" can be blank or B REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 14© 2019 IRONRIDGE, INC. VERSION 2.3 MODULe COMPATIBILITY ET Solar ET Solar modules with 35, 40 and 50 mm frames ET-Y6ZZxxxAA Where “Y” can be P, L, or M; “ZZ” can be 60 or 72; “xxx” refers to the module power rating; and “AA” can be WB, WW, BB, WBG, WWG, WBAC, WBCO, WWCO, WWBCO or BBAC Flex Flex modules with 35, 40 and 50 mm frames and model identifier FXS-xxxYY-ZZ; where "xxx" is the module power rating; "YY" can be BB or BC; and "ZZ" can be MAA1B, MAA1W, MAB1W, SAA1B, SAA1W, SAC1B, SAC1W, SAD1W, SBA1B, SBA1W, SBC1B, or SBC1W GCL GCL modules with 35 mm and 40 mm frames GCL-ab/YY xxx Where "a" can be M or P; "b" can be 3 or 6; "YY" can be 60, 72, 72H, or 72DH; and xxx is the module power rating GigaWatt Solar Gigawatt modules with 40 mm frames GWxxxYY Where “xxx” refers to the module power rating; and “YY” can be either PB or MB Hansol Hansol modules with 35 and 40 frames HSxxxYY-zz Where "xxx" is the module power rating; "YY" can be PB, PD, PE, TB, TD, UB, UD, or UE; and "zz" can be AH2, AN1, AN3, AN4, HV1, or JH2 Hanwha Solar Hanwha Solar modules with 40, 45, and 50 mm frames HSLaaP6-YY-1-xxxZ Where "aa" can be either 60 or 72; "YY" can be PA or PB; "xxx" refers to the module power rating; and "Z" can be blank or B Hanwha Q CELLS Hanwha Q CELLS Modules with 32, 35, 40, and 42mm frames and model identifier aaYY-ZZ-xxx where "aa" can be Q. or B.; "YY" can be PLUS, PRO, PEAK, LINE PRO, LINE PLUS, PLUS DUO or PEAK DUO; and "ZZ" can be G3, G3.1, G4, G4.1, L-G2, L-G2.3, L-G3, L-G3.1, L-G3y, L-G4, L-G4.2, L-G4y, LG4.2/TAA, BFR-G3, BLK-G3, BFR-G3.1, BLK-G3.1, BFR-G4, BFR-G4.1, BFR G4.3, BLK-G4.1, G4/SC, G4.1/SC, G4.1/TAA, G4.1/MAX, BFR G4.1/TAA, BFR G4.1/MAX, BLK G4.1/TAA, BLK G4.1/ SC, EC-G4.4, G5, BLK-G5, L-G5, L-G5.1, L-G5.2, L-G5.2/H, L-G5.3, G6, G6+, BLK-G6, L-G6, L-G6.1, L-G6.2, L-G6.3, G7, BLK-G6+, BLK-G7, G7.2, G8, BLK-G8, G8+, BLK-G8+ L-G7, L-G7.1, L-G7.2, L-G7.3, L-G8, L-G8.1, L-G8.2, or L-G8.3; and "xxx" is the module power rating Heliene Heliene modules with 40 mm frames YYZZxxxA Where "YY" can be 36, 60, 72, or 96; "ZZ" can be M, P, or MBLK; "xxx" is the module power rating; and "A" can be blank, HomePV, or Bifacial HT-SAAE HT-SAAE modules with 40 mm frames HT72-156Z-xxx Where "Z" can be M, P, M-C, P-C, M(S), M(VS), M(V), P(V), M(V)-C, P(V)-C; and "xxx" is the module power rating Hyundai Hyundai modules with 33, 35, 40 and 50 mm frames HiY-SxxxZZ Where "Y" can be A, D, M or S; "xxx" refers to the module power rating; and "ZZ" can be HG, HI, KI, MI, MF, MG, RI, RG, RG(BF), RG(BK), SG, TI, or TG Itek Itek Modules with 40 and 50 mm frames IT-xxx-YY Where "xxx" is the module power rating; and "YY" can be blank, HE, or SE, or SE72 JA Solar JA Solar modules with 30, 35, 40 and 45 mm frames JAyyzz-bbww-xxx/aa Where “yy” can be M, P, M6 or P6; “zz” can be blank, (K), (L), (R), (V), (BK), (FA), (TG), (FA)(R), (L)(BK), (L)(TG), (R)(BK), (R)(TG), (V)(BK), (BK)(TG), or (L)(BK)(TG); “bb” can be 48, 60, or 72; "ww" can be D09, S01, S02, S03, S06, S09, or S10; “xxx” is the module power rating; and “aa” can be BP, MP, SI, SC, PR, 3BB, 4BB, 4BB/RE, 5BB Jinko Jinko modules with 35 and 40 mm frames JKMYxxxZZ-aa Where "Y" can either be blank or S; "xxx" is the module power rating; "ZZ" can be M, P, or PP; and "aa" can be blank, 60, 60B, 60H, 60L, 60BL, 60HL, 60HBL, 60-J4, 60B-J4, 60B-EP, 60(Plus), 60-V, 60-MX, 72, 72-V, 72H-V, 72L-V, 72HL-V, 72-MX, 72H-BDVP, or 72HL-TV Jinko frameless modules JKMxxxPP-DV Where "xxx" is the module power rating Kyocera Kyocera Modules with 46mm frames KYxxxZZ-AA Where "Y" can be D or U; "xxx" is the module power rating; "ZZ" can be blank, GX, or SX; and "AA" can be LPU, LFU, UPU, LPS, LPB, LFB, LFBS, LFB2, LPB2, 3AC, 3BC, 3FC, 4AC, 4BC, 4FC, 4UC, 5AC, 5BC, 5FC, 5UC, 6BC, 6FC, 8BC, 6MCA, or 6MPA LG LG modules with 35, 40, and 46 mm frames LGxxxYaZ-bb Where "xxx" is the module power rating; "Y" can be A, E, N, Q, S; "a" can be 1 or 2; "Z" can be C, K, T, or W; and "bb" can be A3, A5, B3, G3, G4, J5, K4, or V5 Longi Longi modules with 30, 35 and 40 mm frames LRa-YYZZ-xxxM Where "a" can be 4 or 6; "YY" can be blank, 60 or 72; "ZZ" can be blank, BK, BP, HV, PB, PE, PH, HBD, HPB, or HPH; "xxx" is the module power rating REVIEWED BY SAFEBUILT 08/04/2022 FLUSH MOUNT INSTALLATION MANUAL - 15© 2019 IRONRIDGE, INC. VERSION 2.3 MODULe COMPATIBILITY Mission Solar Mission Solar modules with 33 and 40 mm frames MSEbbxxxZZaa Where “bb” can be blank or 60A; “xxx” is the module power rating; “ZZ” can be blank, MM, SE, SO, SQ , SR, or TS; and “aa” can be blank, 1J, 4J, 4S, 5K, 5T, 60, 6J, 6S, 6W, 8K, 8T, or 9S Mitsubishi Mitsubishi modules with 46 mm frames PV-MYYxxxZZ Where "YY" can be LE or JE; xxx is the module power rating; and "ZZ" can be either HD, HD2, or FB Motech IM and XS series modules with 40, 45 and 50 mm frames Neo Solar Power Neo Solar Power modules with 35 mm frames D6YxxxZZaa Where "Y" can be M or P; xxx is the module power rating; "ZZ" can be B3A, B4A, E3A, E4A, H3A, H4A; and "aa" can be blank, (TF), ME or ME (TF) Panasonic Panasonic modules with 35 and 40 mm frames VBHNxxxYYzzA Where "xxx" refers to the module power rating; "YY" can be either KA, RA, SA or ZA; "zz" can be either 01, 02, 03, 04, 06, 06B, 11, 11B, 15, 15B, 16, 16B, 17, or 18; and "A" can be blank, E, G, or N Peimar Peimar modules with 40 mm frames SbxxxYzz Where "b" can be G or P; “xxx” is the module power rating; “Y” can be M or P; and “zz” can be blank, (BF), or (FB) Phono Solar Phono Solar modules with 35, 40, and 45 mm frames PSxxxY-ZZ/A Where xxx refers to the module power rating; "Y" can be M, M1, MH, or M1H or P; "ZZ" can be 20 or 24; and "A" can be F, T, U, or TH Prism Solar Prism Solar frameless modules BiYY-xxxBSTC Where "YY" can be 48, 60, 60S, 72 or 72S; and "xxx" is the module power rating REC Solar REC modules with 30, 38 and 45 mm frames RECxxxYYZZ Where “xxx” is the module power rating; “YY” can be AA, M, NP, PE, PE72, TP, TP2, TP2M, TP2SM, or TP2S; and “ZZ” can be blank, Black, BLK, BLK2, SLV, or 72 Renesola ReneSola modules with 35, 40 and 50 mm frames AAxxxY-ZZ Where "AA" can be SPM(SLP) or JC; "xxx" refers to the module power rating; "Y" can be blank, F, M or S; and "ZZ" can be blank, Ab, Ab-b, Abh, Abh-b, Abv, Abv-b, Bb, Bb-b, Bbh, Bbh-b, Bbv, Bbv-b, Db, Db-b, or 24/Bb Renogy Renogy Modules with 40 and 50 mm frames RNG-xxxY Where "xxx" is the module power rating; and "Y" can be D or P Risen Risen Modules with 35 and 40 mm frames RSMyy-6-xxxZZ Where "yy" can be 60, 72, 120 or 144; "xxx" is the module power rating; and "ZZ" can be M or P Frameless modules RSMyy-6-xxxZZ Where "yy" can be 60, 72, 120 or 144; "xxx" is the module power rating; and "ZZ" can be MDG or PDG S-Energy S-Energy modules with 40 frames SNxxxY-ZZ Where "xxx" is the module power rating; "Y" can be M or P; and "ZZ" can be 10, or 15 Seraphim Energy Group Seraphim modules with 35 and 40 mm frames SEG-aYY-xxxZZ Where "a" can be blank, 6 or B; "YY" can be blank, MA, MB, PA, or PB; "xxx" is the module power rating; and "ZZ" can be blank, BB, BG, BW, HV, WB, WW, BMB, BMB-HV Seraphim USA Seraphim modules with 40 and 50 mm frames SRP-xxx-6YY Where "xxx" is the module power rating; and "YY" can be MA, MB, PA, PB, QA-XX-XX, and QB-XX-XX Sharp Sharp modules with 35 and 40 mm frames NUYYxxx Where “YY” can be SA or SC; and "xxx" is the module power rating Silfab Silfab Modules with 38 mm frames SYY-Z-xxxAb Where "YY" can be IL, SA, LA, SG or LG; "Z" can be blank, M, P, or X; "A" can be blank, B, H, M, or N; and "b" can be A, L, G, or T Solaria Solaria modules with 40 mm frames PowerXT xxxY-ZZ Where "xxx" is the module power rating; "Y" can be R or C; and "ZZ" can be AC, BD, BX, BY, PD, PX, PZ, WX or WZ Solarcity (Tesla)Solarcity modules with 40 mm frames SCxxxYY Where "xxx" is the module power rating; and "YY" can be blank, B1 or B2 SolarTech SolarTech modules with 42 mm frames STU-xxxYY Where "xxx" is the module power rating; and "YY" can be PERC or HJT REVIEWED BY SAFEBUILT 08/04/2022 MODULe COMPATIBILITY FLUSH MOUNT INSTALLATION MANUAL - 16© 2019 IRONRIDGE, INC. VERSION 2.3 SolarWorld AG / Industries GmbH SolarWorld Sunmodule Plus, Protect, Bisun, XL, Bisun XL, may be followed by mono, poly, duo, black, bk, or clear; modules with 31, 33 or 46 mm frames SW-xxx Where "xxx" is the module power rating SolarWorld Americas Inc.SolarWorld Sunmodule Plus, Protect, Bisun, XL, Bisun XL, may be followed by mono, poly, duo, black, bk, or clear; modules with 33 mm frames SWA-xxx Where "xxx" is the module power rating Stion Stion Thin film modules with 35 mm frames STO-xxx or STO-xxxA Thin film frameless modules STL-xxx or STL-xxxA Where "xxx" is the module power rating SunEdison SunEdison Modules with 35, 40 and 50 mm frames SE-YxxxZABCDE Where "Y" can be B, F, H, P, R, or Z; "xxx" refers to the module power rating; "Z" can be 0 or 4; "A" can be B,C,D,E,H,I,J,K,L,M, or N ; "B" can be B or W; "C" can be A or C; "D" can be 3, 7, 8, or 9; and "E" can be 0, 1 or 2 Suniva Suniva modules with 35, 38, 40, 46 and 50 mm frames OPTxxx-AA-B-YYY-Z MVXxxx-AA-B-YYY-Z Where "xxx" is the module power rating; "AA" is either 60 or 72; "B" is either 4 or 5; "YYY" is either 100,101,700,1B0, or 1B1; and "Z" is blank or B Sunpower Sunpower standard (G3 or G4) or InvisiMount (G5) 40 and 46 mm frames SPR-Zb-xxx-YY Where "Z" is either A, E, P or X; “b” can be blank, 17, 18, 19, 20, 21, or 22; “xxx” is the module power rating and “YY” can be blank, BLK, COM, C-AC, D-AC, E-AC, G-AC, BLK-C-AC, or BLK-D-AC Sunpreme Sunpreme frameless modules GXB-xxxYY Where "xxx" is the module power rating; and "YY" can be blank or SL Sunspark Sunspark modules with 40 mm frames SYY-xxxZ Where “YY” can be MX or ST; “xxx” is the module power rating; and “Z” can be M, P or W Suntech Vd, Vem, Wdb, Wde, and Wd series modules with 35, 40 and 50 mm frames Talesun Talesun modules with 35 and 40 frames TP6yZZaaxxx-b Where "yy" can be blank, F or H; "ZZ" can be 60 or 72; "aa" can be M or P; and "b" can be blank, B, T, or (H) Trina Trina Modules with 30, 35, 40 and 46mm frames TSM-xxxYYZZ Where "xxx" is the module power rating; "YY" can be DD05, DD06, DD14, DE14, DE15, DEG15, PA05, PC05, PD05, PD06, PA14, PC14, PD14, PE14, or PE15 ; and "ZZ" can be blank, .05, .08, .10, .18, .08D, .18D, 0.82, .002, .00S, 05S, 08S, A, A.05, A.08, A.10, A.18, A(II), A.05(II), A.08(II), A.082(II), A.10(II), A.18(II), H, H(II), H.05(II), H.08(II), HC.20(II), HC.20(II), or M Frameless modules TSM-xxxYY Where "YY" can be either DEG5(II), DEG5.07(II), DEG5.40(II), DEG5.47(II), DEG14(II), DEG14C(II), DEG14C.07(II), DEG14.40(II), PEG5, PEG5.07, PEG5.40, PEG5.47, PEG14, or PEG14.40 URE URE modules with 35 mm frames DyZxxxHaa Where "y" can be 6 or 7; "Z" can be K or M; "xxx" is the module power rating; and "aa" can be H3A, H4A, or H8A Vikram Vikram solar modules with 40 mm frames VSyy.ZZ.AAA.bb Where "yy" can be M, P, MBB, MH, MS, MHBB, or PBB; "ZZ" can be 60 or 72; "AAA" is the module power rating; and "bb" can be 03.04 or 05 VSUN VSUN modules with 35 and 40 mm frames, VSUNxxx-YYz-aa, Where "YY" can be 60, 72, 120, or 144; "z" can be M, P, MH, PH, or BMH; and "aa" can be blank, BB, or DG Winaico Winaico modules with 35 and 40 mm frames Wsy-xxxZa Where "y" can be either P or T; "xxx" is the module power rating; "Z" can be either M, P, or MX; and "a" can be blank or 6 Yingli Panda, YGE, YGE-U, and YLM series modules with 35, 40, and 50 mm frames REVIEWED BY SAFEBUILT 08/04/2022 LOW PROFILE QB1 WITH 3” MICROFLASHING® FOR ASPHALT, EPDM, & TPO ROOFS PATENT # 8448407 17667SS 17664, 17666 AHJ CONDENSED PERMIT PACKAGE 2020 Version 5 A DIVISION OF QUICKSCREWS INTERNATIONAL CORP REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.3 Part #Box Quantity 17664 5.25” Bolts (10) 17666 3” Microflashing® (10); 5.25” Bolts (10) 17667SS 3” Microflashing® (25); 5.25” Bolts (25); L-Foot (25); 5/16” Serrated Hex Flange Nuts (25) SPEC SHEET REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.4 REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.5 REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.7 BUILDING CODE LETTER REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.8 ENGINEERING REPORT REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.9 REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.10 REVIEWED BY SAFEBUILT 08/04/2022 5830 Las Positas Road, Livermore CA 94551 | 3948 Airway Drive, Rock Hill SC 29732 Phone: (844) 671-6045 | Fax: (800) 689-7975 | www.quickbolt.com QuickBOLT is a division of Quickscrews International Corp.11 REVIEWED BY SAFEBUILT 08/04/2022 CERTIFICATE OF COMPLIANCE Certificate Number E493748 Report Reference E493748-2017-08-17 Date 2021-August-05 Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/ Issued to:QuickBOLT a Division of Quickscrews International Corp 5830 Las Positas Rd Livermore CA, 94551 US MOUNTING SYSTEMS, MOUNTING DEVICES, CLAMPING DEVICES AND GROUND LUGS FOR USE WITH PHOTOVOLTAIC MODULES AND PANELS - COMPONENT This is to certify that representative samples of See Addendum Page for Product Designation(s). Have been investigated by UL in accordance with the component requirements in the Standard(s) indicated on this Certificate. UL Recognized components are incomplete in certain constructional features or restricted in performance capabilities and are intended for installation in complete equipment submitted for investigation to UL LLC. Standard(s) for Safety:See Addendum Page Additional Information:See the UL Online Certifications Directory at https://iq.ulprospector.com for additional information This Certificate of Compliance does not provide authorization to apply the UL Recognized Component Mark. Only the UL Follow-Up Services Procedure provides authorization to apply the UL Mark. Only those products bearing the UL Recognized Component Mark should be considered as being UL Certified and covered under UL’s Follow-Up Services. Look for the UL Recognized Component Mark on the product. REVIEWED BY SAFEBUILT 08/04/2022 CERTIFICATE OF COMPLIANCE Certificate Number E493748 Report Reference E493748-2017-08-17 Date 2021-August-05 Bruce Mahrenholz, Director North American Certification Program UL LLC Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/ This is to certify that representative samples of the product as specified on this certificate were tested according to the current UL requirements USR – Component, Roof Mounting Hook Units, Models 15891 15893 15987 16000 16317 16318 16988 16990 16991 16993 17508 17509 17510 17511 17512 17513 17514 17515 17516 17517 17518 17519 17520 17521 17522 17523 17524 17525 17526 17527 17536 17537 17538 17539 17540 17541 17542 17543 17544 17545 17546 17547 17548 17549 17550 17551 17552 17553 17554 17555 17556 17558 17559 17560 17568 17569 17570 17571 17572 17573 17574 17575 17576 17577 17578 17579 17580 17585 17586 17587 17588 17589 17592 17596 17597 1759817599 17600 17601 17606 17607 17608 17609 17610 17611 17612 17613 17614 17615 17616 17617 17618 17620 17621 17622 17623 17624 17625 17626 17627 17628 17629 17630 17631 17632 17633 17636 17637 17638 17639 17642 17643 17646 17647 17648 17649 17650 17651 17659 17664 17667 17669 17670 17671 17672 17673 17678 17679 17680 17681 17686 17687 17688 17689 17700 17701 17702 17703 17704 17705 17706 17707 17708 17709 17710 17711 17712 17717 17718 17759 15891-10 15891BLK-10 15987A 15987B 17667SS 17672SS 17680SS 17688SS 17713SS 17720 17721SS 17723 17724SS 17726 17727SS 17729 17730SS 15894SS 15891SS 15987BSS 17660 17661 17662 17663 UL 2703, Mounting systems, mounting devices, lamping/retention devices, and ground lugs for use with flat-plate photovoltaic modules and panels REVIEWED BY SAFEBUILT 08/04/2022