HomeMy WebLinkAboutDOCUMENT Engineering Solar 570 Darcy Dr 2020-09-08 Tuesday, September 8, 2020 Town of Estes Park 170 MacGregor Ave Estes Park, CO 80517 re: Structural Analysis of project at 570 Darcy Dr, Estes Park, CO 80517 Dear Sir or Madam, We have evaluated the solar racking and connections to the roof for the photovoltaic array to be installed using the engineering design factors below. ultimate wind speed V = 175 mph wind exposure category = C ground snow load = 66 psf The PV system shall be flush mounted with no overhang. Attachments to the roof are to be spaced no more than 4’ O.C. Using the assumed engineering loads, we have determined that the design strength of all connections in the solar racking system will be sufficient for this application. The structural supporting members for the roof are 2x4” trusses 24” O.C. The roof framing has been determined to be adequate for the required loads. We do not assume responsibility for any construction flaws that currently exist or caused by other work trades. Sincerely, Anthony P. Boniface, PE Reviewed and approved by SAFEbuilt 10/14/20