HomeMy WebLinkAboutPLANS Garage 325 Macgregor Ave 2021-10-083,500
6
325 MacGregor Ave
Wind Speed: = 175mph
Snow Load: = 66 psf
Elevation: = 7575 feet
Roof: 47 psf
Soil Bearing Capacity =3,500 psf
Hemp-Fir
ED GRUEFF
325 MACGREGOR AVE.
ESTES PARK, CO
SEE SHEET 6 - ENGINEERED STAMPED
DRAWING TAKES PRESEDENCE FOR
STRUCTURAL REQUIREMENTS
APPROVED by SAFEbuilt;
2015 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
10/08/2021
PERMIT #21-EP-00481
Field Copy
Print out in color and have
on site for inspector
REVIEWED BY
SAFEBUILT - PBLAND
6
32
5
M
a
c
G
r
e
g
o
r
A
v
e
SEE SHEET 6 - ENGINEERED
STAMPED DRAWING FOR
STRUCTURAL REQUIREMENTS
W1.4xW1.4
All Roofing materials shall comply with R905
All Exterior Coverings shall comply with R703
Drip Edge all rakes and eaves
ICE AND WATER SHEILD IS REQUIRED
ROOF VENTS PER R806 &
MANUFACTURERS SPECIFICATIONS
FLASHING SHALL BE INSTALLED IN A MANNER
THAT WILL PREVENT MOISTURE ENTERING
WALLS AND ROOFS R903.2
As Required provide gutters or a controlled
method of water disposal from roofs - that will
collect and discharge to the ground surface not
less than 5' from foundation or to an approved
drainage system. R801.3
PERMIT #21-EP-00481
Field Copy
Print out in color and have
on site for inspector
REVIEWED BY
SAFEBUILT - PBLAND
19/32 OSB
(2) 11-7/8" LVL (2) 11-7/8" LVL
6
See Garage Door Wall, Sheet 6,
Detail E
32
5
M
a
c
G
r
e
g
o
r
A
v
e
SEE SHEET 6 - ENGINEERED
STAMPED DRAWING FOR
STRUCTURAL REQUIREMENTS
See Engineers & Manufacturers Specs
PERMIT #21-EP-00481
Field Copy
Print out in color and have
on site for inspector
REVIEWED BY
SAFEBUILT - PBLAND
Lep Siding To Match House
7/16 " OSB
SHEATHING
6
Class B Fiberglass
30#
32
5
M
a
c
G
r
e
g
o
r
A
v
e
19/32 OSB
Lap Siding To Match House
7/ 16 OSB SHEATHING
CLASS B FIBER GLASS
30#
19/32 OSB
LAP SIDING
PRE ENG TRUSSES
@ 24" O.C.
SIMPSON H2.5
LAP SIDING TO
MATCH HOUSE
FAUX STONE
30#
@ 30" O.C
See Section B, Sheet 6
SEE SHEET 6
SEE SHEET 6 - ENGINEERED
STAMPED DRAWING FOR
STRUCTURAL REQUIREMENTS
PERMIT #21-EP-00481
Field Copy
Print out in color and have
on site for inspector
REVIEWED BY
SAFEBUILT - PBLAND
6
32
5
M
a
c
G
r
e
g
o
r
A
v
e
LAP SIDING
7/16 OSB SHEATHING
LEP SIDING
7/16 OSB SHEATHING
LAP SIDING
7/16 OSB SHEATHING
LAP SIDING
7/16 OSB SHEATHING
LAP SIDING
7/16 OSB SHEATHING
7/16 OSB SHEATHING
LAP SIDING
LAP SIDING TO
MATCH HOUSE
PRE ENGINEERED TRUSS
7/16 OSB SHEATHING
SIMPSON H2.5 TIE
CLASS B FIBER GLASS
30#
7/16 OSB
(2) 11-7/8" LVL HEADER
(2) 11-7/8" LVL HEADER
Pre-Engineered Truss Drawings
shall be on-site for inspectors review
SEE SHEET 6 - ENGINEERED
STAMPED DRAWING FOR
STRUCTURAL REQUIREMENTS
19/32 OSB ROOF SHEATHING
PERMIT #21-EP-00481
Field Copy
Print out in color and have
on site for inspector
REVIEWED BY
SAFEBUILT - PBLAND
1-ALL WOOD TO BE #2 HEM-FIR UNLESS OTHERWISE
SPECIFIED
3-ALL STRUCTURAL BACKFILL MUST BE COMPACTED TO 95%
STANDARD PROCTOR.
4-ALL CONCRETE DESIGN IS BASED UPON "BUILDING CODE
REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-14).
5-CONCRETE SPECIFICATIONS: Fc = 3,500 psi @ 28 DAYS WITH 6%
AIR (Ø 1.5%)
6-ANCNOR BOLTS: 1/2" X 10" J FOUNDATION ANCHOR OR EQUAL
SPACED AT 30" OC MAXIMUM INTERVALS AND 1'-0" FROM
CORNERS AND STEPS TO ANCHOR, 2"X4" PRESSURE TREATED
SILL PLATE AROUND PERIMETER, AND 2"X2"X3/16" WASHERS.
7- WALL SHEATHING TO BE 7
16" OSB INSTALLED HORIZONTALLY W/
JOINTS OVERLAPING 16" MIN AND NAILED W/8D NAILS 6" O.C.
EDGES AND 12" O.C. FIELD , EXCEPT AS NOTED ON SHEAR WALLS
8- ALL WINDOW/DOOR OPENINGS TO HAVE (1) KING STUD FOR
EVERY TWO FLOOR JOISTS/ROOF RAFTERS WITHIN THE SPAN OF
THE HEADER AND (2) JACKS STUDS
9- SIMPSON H2.5 HURRICANE TIES OR EQUAL TO BE INSTALLED AT
ALL RAFTER ENDS
10-ROOF SHEATHING TO BE 19
32" OSB NAILED W/ 8D NAILS @ 6" O.C.
EDGES AND 8" O.C. FIELD
11- ALL ENGINEERED LUMBER TO BE INSTALLED PER MANUFACTURE
RECOMMENDATIONS.
12- ALL SIMPSON HANGERS TO BE INSTALLED PER MANUFACTURES
RECOMMENDATIONS.
13-CONTROL JOINTS ARE RECOMMENDED @ 10' O.C. IN EACH
DIRECTION AND HAVE A MINIMUM DEPTH OF 1"
NOTES:
1.ALL EXTERIOR SHEATHING TO BE PLACED HORIZONTAL.
2.SHEATHING IS TO FULLY OVERLAP DOOR AND WINDOW
FRAMING WITH NO VERTICAL SEAMS AT WINDOW AND
DOOR CORNERS.
3.ALL HORIZONTAL SEAMS IN SHEATHING TO BE FULLY
BLOCKED.
4.HEADERS MEMBERS TO BE FLUSH WITH INTERIOR AND
EXTERIOR WALLS.
SHEAR WALL NOTES
GROUND SNOW LOAD = 66 PSF (ELEV = 7575 FT)
ULTIMATE WIND LOAD = 175 MPH
ROOF SNOW LOAD = 47 PSF
SOIL BEARING CAPACITY = 3,500 PSF
DECOMPOSED AND FRACTURED GRANITE BEDROCK
ALL CONSTRUCTION TO CONFORM TO TOWN OF ESTES PARK
STANDARDS AND CURRENT INTERNATIONAL RESIDENTIAL
CODE AND ALL OTHER APPLICABLE CODES.
DESIGN LOAD CRITERIA:
SECTION B-B'
NOT TO SCALE
FND DETAIL B
4" CONCRETE SLAB w/ 6x6
W1.4xW1.4 WELDED WIRE FABRIC
OR #4 REBAR @ 1' O.C. E.W.
2'4"
(3) #4 REBAR
CONT.1'
1/2"x10" J BOLTS @
48" O.C. (TYP)
2x PRESSURE TREATED
SILL PLATE (TYP)
SCALE 1
4" = 1'-0"
GARAGE DOOR FRAMING
SIMPSON STHD14
EMBEDDED IN CONCRETE
NAILED DIRECTLY TO
FRAMING
11
2"
DOUBLE TOP PLATE
NAILED @ 3" O.C. EACH
2x6 TREATED PLATE W/
ADDITIONAL DBL SILL PLATE
(2) 11-7/8" LVL HEADER
DBL. 2x6 BLOCKING
4' AND ALL HORIZONTAL SEAMS4 TRIM
SIMPSON MSTC40
STRAP OPPOSITE SIDE
OF SHEATHING
SIMPSON MSTC40
STRAP OPPOSITE SIDE
OF SHEATHING
2x4 FRAMING & 23/32"
OSB SHEATHING W/
16d NAILS @ 2" ON
EDGE 4" IN FIELD IN
PORTAL WALL (TYP)
SECTION E-E'
1'-111
2"9'-2"1'-5"9'-2"3'-2"3'-2"1'-111
2"2'
FASTEN SHEATHING TO
HDR. W/ 16D NAILS IN 2"
ON EDGE 4" IN FIELD
11
2"
(2) 2X12
HEADER
1/2" DIA. ANCHOR BOLTS W/ 2"x2"x 3
16""
WASHERS 7" MIN. EMBEDMENT
E
1 SIMPSON LSTHD 8
2 SIMPSON STHD 14
SHEAR WALL TIE DOWNS
2x4 FRAMING AT
PERIMETER WALLS (TYP)
SIMPSON H2.5
HURRICANE TIES
EACH RAFTER.
4" CONCRETE SLAB
TYVEK HOME WRAP
(OR APPROVED EQUAL)
7
16" OSB SHEATHING
SCALE 1
4" = 1'-0"
TYPICAL SECTION
SECTION A-A'
A
LAP SINGLE SIDING
TO MATCH RESIDENCE
12
4
PRE ENGINEERED
TRUSSES @ 24" O.C.
CLASS B FIBERGLASS
SHINGLES, OVER 30# FELT,
OVER 19/32" SHEATHING
(TYP)
FAUX RIVER STONE
VENEER TO MATCH
RESIDENCE
30'
14'
8'-1 1
8"
1-12"
end distance
#4 rebar
continuous
SIMPSON
Strong-Tie
â
Typical STHD
Corner Installation
SCALE 3/16" = 1'-0"
BRACED WALL PLAN
1
SEE GARAGE DOOR WALL
FRAMING DETAIL - E
2
30'
20'
8'-6"
8'-6"
20'
1'-111
2"1'-5"3'-2"
30'
BWL A BWL B
BWL 1
BWL 2 2 2 2 2 2
1
1 1
1
1
1
1
M
A
C
G
R
E
G
O
R
A
V
E
.
S
0
0
°
3
3
'
1
9
"
W
91
.
6
5
F
T
EXISTING
RESIDENCE
N 89°26'00" W 120.41 FT
25' SET BACK
10' SET BACK
10' SET BACK
10' SET BACK
N 89°01'45" E
PROPOSED
GARAGE
30 FT
24 FT
235 MACGREGOR AVE.
235 MACGREGOR AVE.
ESTES PARK, CO 80517
SHEET TITLE:
6 CLIENT:
SHEET
PROJECT TITLE:
60438_005
JOB NO.SHEET
DATE:
SCALE:
09/20/2021
AS SHOWN
APPROVED BY:MST
REVISION:BY:
CHECKED BY:
DRAWN BY:
DESIGNED BY:
DATE:
MST
MST
MST
ED GRUEFF 2018 CORNERSTONE ENGINEERING & SURVEYING, INC.
COPYRIGHT - ALL RIGHTS RESERVED
1692 BIG THOMPSON AVE.
SUITE 200
ESTES PARK, CO 80517
PH: (970) 586-2458
FAX: (970) 586-2459
325 MACGREGOR AVE.
ESTES PARK, CO 80517
DETACHED GARAGE
SITE PLAN
SCALE 1"=30'
VICINITY MAP
SCALE 1"=700'
ENGINEER IS RESPONSIBLE FOR SOIL
BEARING CAPACITY VIA SOILS REPORT
FOR DESIGN LOAD CRITERIA
Pre-Engineered Truss Drawings
shall be on-site for inspectors review
30" Min.
PERMIT #21-EP-00481
Field Copy
Print out in color and have
on site for inspector
REVIEWED BY
SAFEBUILT - PBLAND
APPROVED by SAFEbuilt;
2015 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
10/08/2021