Loading...
HomeMy WebLinkAboutLETTER Fire Approval Commercial Remodel 101 E Elkhorn Ave 2020-08-28 Plan Review Commentary Letter August 28, 2020 RE: Town of Estes Park Building Permit #20-EP-00350; Site & Building Review Property Owner: B Wade Investments, LLC 6624 Powell Street, Loveland, CO 805388714 Attn: Mr. Ben Holcomb Phone (970) 222-6571 General Contractor: Treeline Construction & Consulting, Inc. 638 Pine Tree Drive, Estes Park, CO 80517 Attn: Mr. Kevin Marquart Phone (970) 227-0403 Applicable Building: Historic Downtown Core As per the permit application: 101 East Elkhorn Avenue As per Larimer County records: 113 E Elkhorn Avenue Submittal date 8/21/2020 Thank you for the opportunity to review the above noted project for conformance with the adopted 2018 International Fire Code (IFC), District-specific amendments, and applicable reference standards. The Estes Valley Fire Protection District (EVFPD) is dedicated to ensuring the safety of residents, guests, and the volunteers who respond to assist you. Based upon the information submitted, the drawings/documents shall be considered APPROVED provided the following requirements are satisfied in full: 1. IFC 106.2 Schedule of permit fees- Fees apply for this project in accordance with the District fee schedule in the amount of $500.00. This includes the minimum plan review fees for commercial alterations to existing buildings. Payment will be collected on behalf of the Estes Valley Fire Protection District through the Town of Estes Park’s permitting system. 2. IFC 505.1 Premises identification- Approved addressing shall be provided for all buildings, units, and monument signs. Plan Review Commentary: Please coordinate with this office directly for specific addressing/signage requirements. It appears that this building is incorrectly addressed; the legal address noted on Larimer County property records is 113 East Elkhorn Avenue. Correct addressing shall be assigned and posted. Addressing shall be a minimum of 4 inches in height, shall be white text of a plain font on a blue background, shall have a reflective quality, and shall be posted in locations approved by this office so as to be readily distinguishable for first responders on both the building and any monument signs. 3. IFC Section 906, Portable fire extinguishers- Portable fire extinguishers shall be installed in accordance with IFC 906 and NFPA 10, 2018 edition. Plan Review Commentary: In the event that they are not already provided in the existing portion(s) of the building(s), portable fire extinguishers shall be required. Please coordinate with this office directly to determine approved locations and placement. Portable fire extinguishers/cabinets shall be mounted at 48 inches to the top of the extinguisher to comply with ADA recommendations. Portable fire extinguishers shall be a dry chemical-type, and a minimum size of 2-A:10-B:C for all spaces. Portable fire extinguishers shall be inspected and tagged by a qualified fire extinguisher contractor prior to being placed in service. Portable fire extinguishers shall be a commercial grade, such as manufactured by Amerex, Sentry, or equivalent. Consumer grade extinguishers manufactured by Kidde or First Alert are not approved by this office. 4. IFC, Chapter 33, Fire Safety During Construction and Demolition- It shall be the responsibility of the general contractor to ensure all provision of IFC Chapter 33 are met in full for the duration of construction. Please include this in your general job safety practices, training, and routine meetings. Please do not hesitate to contact this office directly if you have questions, or we can assist with ensuring a safe and successful project. Thank You, Kevin Sullivan, Fire Marshal Estes Valley Fire Protection District Cell phone (970) 238-0678 Office phone (970) 577-3689 Email ksullivan@estesvalleyfire.org