EVFPD Fire Alarm Acceptance Report
1836 Wildfire Road BLD G "E"Complete
Score Flagged items Actions
Document No.000020
Property information:
1836 WILD FIRE ROAD , BUILD ING E
Alarm Company :
Trident Security Systems
#303-651-7371
Email service@tridentco.net
Inspection Title 1836 Wildfire Road BLDG "E"
Client / Site KEVIN SUPERINT ENDENT WILDFIRE
ACCEPTANCE TEST FOR ALARM SYSTEM/SPRINKLER S YS TEM/CO S YS TEM
Conducted on 04/18/2022 10:28 am MDT
Prepare d by S andy Garber
Location 1790 Wildfire Rd
Estes Park CO 80517
United S tates
(40.38708869323715, -
105.49095004970964)
Private & Confidential 1/7
Audit 94.74%
Control Panel
Ve rify AC circuit is dedicated and labeled so that the owner can find it. Turn
off and sound the audiovisuals. This is a good time to do a walk- thru to check
each audiovisual and te st the battery on full load for 5 minutes; 15 minutes
for voice evac.
Yes
Photo 1 Photo 2 Photo 3
100%
Good
AL ARM SYST EM RES ULTS CAPT URED DURING TES T
Photo 4 Photo 5 Photo 6 Photo 7 Photo 8 Photo 9
If syste m is monitored over phone lines, ve rify the re are two. Unplug one and
verify system trouble. Performance based transmission means will be
considered.
Yes
S moke alarm
With AC power restored, unplug 1 batte ry lead.Yes
Compare calculated size of batteries in submittal to actual batteries installed.Yes
Tag syste m when the inspe ction is certified. Add manuals and AL fire alarm
permit number in panel.Yes
Provided Record of Comple tion and place one copy in the panel.Yes
Field Devices
Blow canned smoke on at least one detector.Yes
Pull at least one pull station. Verify any spe cial tool is on hand to reset. (48")Yes
Photo 10
Private & Confidential 2/7
Using a magnet or test switch, trip a duct smoke detector and watch fan shut
down.N/A
Re move smoke detector he ad from base to verify trouble annunciation.Yes
Photo 11 Photo 12
Ask installer to remove a wire from one randomly se lected audiovisual.Yes
Create a ground fault on system. Separately, verify operation of audiovisuals
(proper height), including sync strobes. When sile nced, both horns and
strobe s should stop.
Communic ations 100%
Ensure central station has accurate phone for contacting dispatch agency
(Estes Valle y Fire: xxx-xxx-xxxx Good
Re member, 90 seconds for transmission from location to central station, then
90 seconds for operator to contact dispatch.Yes
Ensure central station has valid address that dispatch agre es with. Who is
responding authority?Yes
Discuss how much information should be se nt to the dispatcher and trucks.Yes
Sprink ler Devices
All sprinkle r devices are tested with both sprinkler and fire alarm contractor
pre se nt.Yes
Photo 13
Turn off each valve, watch for supervisory and restore, flowing water for wet
alarm, partially bleeding air for low supervisory, and full alarm for dry system
flow.
Yes
Sig natures
Fire Protection Contractor
Tride nt NI CET(2) Travis Cottrell
04/18/2022 1:25 pm MD T
Private & Confidential 3/7
Photo 14 Photo 15 Photo 16
Estes Valley Fire District Representative
Sandy Garber
04/18/2022 1:32 pm MD T
Fire Alarm System Approved.Yes
Kevin (superintendent wildf ire)
Results of acceptance testing on Alarm S ystem/Sprinkler S ystem/ CO System in the garage area:
1)performed sprinkler tests on wet and dry systems
2)performed a test on the CO system in the garage
3)performed full test on the alarm system
All systems approved and signed off