Loading...
HomeMy WebLinkAboutLETTER Fire Alarm New Multi-Family Building 1826 Widfire Rd Building E 2022-04-1894.74%0 0 EVFPD Fire Alarm Acceptance Report 1836 Wildfire Road BLD G "E"Complete Score Flagged items Actions Document No.000020 Property information: 1836 WILD FIRE ROAD , BUILD ING E Alarm Company : Trident Security Systems #303-651-7371 Email service@tridentco.net Inspection Title 1836 Wildfire Road BLDG "E" Client / Site KEVIN SUPERINT ENDENT WILDFIRE ACCEPTANCE TEST FOR ALARM SYSTEM/SPRINKLER S YS TEM/CO S YS TEM Conducted on 04/18/2022 10:28 am MDT Prepare d by S andy Garber Location 1790 Wildfire Rd Estes Park CO 80517 United S tates (40.38708869323715, - 105.49095004970964) Private & Confidential 1/7 Audit 94.74% Control Panel Ve rify AC circuit is dedicated and labeled so that the owner can find it. Turn off and sound the audiovisuals. This is a good time to do a walk- thru to check each audiovisual and te st the battery on full load for 5 minutes; 15 minutes for voice evac. Yes Photo 1 Photo 2 Photo 3 100% Good AL ARM SYST EM RES ULTS CAPT URED DURING TES T Photo 4 Photo 5 Photo 6 Photo 7 Photo 8 Photo 9 If syste m is monitored over phone lines, ve rify the re are two. Unplug one and verify system trouble. Performance based transmission means will be considered. Yes S moke alarm With AC power restored, unplug 1 batte ry lead.Yes Compare calculated size of batteries in submittal to actual batteries installed.Yes Tag syste m when the inspe ction is certified. Add manuals and AL fire alarm permit number in panel.Yes Provided Record of Comple tion and place one copy in the panel.Yes Field Devices Blow canned smoke on at least one detector.Yes Pull at least one pull station. Verify any spe cial tool is on hand to reset. (48")Yes Photo 10 Private & Confidential 2/7 Using a magnet or test switch, trip a duct smoke detector and watch fan shut down.N/A Re move smoke detector he ad from base to verify trouble annunciation.Yes Photo 11 Photo 12 Ask installer to remove a wire from one randomly se lected audiovisual.Yes Create a ground fault on system. Separately, verify operation of audiovisuals (proper height), including sync strobes. When sile nced, both horns and strobe s should stop. Communic ations 100% Ensure central station has accurate phone for contacting dispatch agency (Estes Valle y Fire: xxx-xxx-xxxx Good Re member, 90 seconds for transmission from location to central station, then 90 seconds for operator to contact dispatch.Yes Ensure central station has valid address that dispatch agre es with. Who is responding authority?Yes Discuss how much information should be se nt to the dispatcher and trucks.Yes Sprink ler Devices All sprinkle r devices are tested with both sprinkler and fire alarm contractor pre se nt.Yes Photo 13 Turn off each valve, watch for supervisory and restore, flowing water for wet alarm, partially bleeding air for low supervisory, and full alarm for dry system flow. Yes Sig natures Fire Protection Contractor Tride nt NI CET(2) Travis Cottrell 04/18/2022 1:25 pm MD T Private & Confidential 3/7 Photo 14 Photo 15 Photo 16 Estes Valley Fire District Representative Sandy Garber 04/18/2022 1:32 pm MD T Fire Alarm System Approved.Yes Kevin (superintendent wildf ire) Results of acceptance testing on Alarm S ystem/Sprinkler S ystem/ CO System in the garage area: 1)performed sprinkler tests on wet and dry systems 2)performed a test on the CO system in the garage 3)performed full test on the alarm system All systems approved and signed off Private & Confidential 4/7 Appendix Photo 1 Photo 3 Phot o 2 Phot o 4 Private & Confidential 5/7 Photo 5 Photo 7 Photo 9 Photo 11 Phot o 6 Phot o 8 Phot o 10 Private & Confidential 6/7 Photo 13 Photo 15 Phot o 12 Phot o 14 Phot o 16 Private & Confidential 7/7