HomeMy WebLinkAboutPLANS 570 Darcy Dr Solar PV System 2020-09-08 Tuesday, September 8, 2020 Town of Estes Park 170 MacGregor Ave Estes Park, CO 80517 re: Structural Analysis of project at 570 Darcy Dr, Estes Park, CO 80517 Dear Sir or Madam, We have evaluated the solar racking and connections to the roof for the photovoltaic array to be installed using the engineering design factors below. ultimate wind speed V = 175 mph wind exposure category = C ground snow load = 66 psf The PV system shall be flush mounted with no overhang. Attachments to the roof are to be spaced no more than 4’ O.C. Using the assumed engineering loads, we have determined that the design strength of all connections in the solar racking system will be sufficient for this application. The structural supporting members for the roof are 2x4” trusses 24” O.C. The roof framing has been determined to be adequate for the required loads. We do not assume responsibility for any construction flaws that currently exist or caused by other work trades. Sincerely, Anthony P. Boniface, PE 1 2 3 4 5 6 9 8 7 12 11 10 18 19 20 23 22 211617 25 24 13 15 14 MSP 6'-4" 1 7 ' - 1 " 1 4 ' - 0 " 14'-6" 76'-3 " 9 0 ' - 8 " 9 4 ' - 8 " 76'-1" HOUSE PHOTO VICINITY MAP SCALE: NTS SCALE: NTS SITE PLAN & VICINITY MAP REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-1 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 1 SITE PLAN WITH VICINITY MAP SCALE: 1/16" = 1'-0"PV-1 PHOTOVOLTAIC ROOF MOUNT SYSTEM PROJECT SITE 2 PV-1 3 PV-1 25 x 400 SUNPOWER SPR-A400-G-AC (400W) MODULES ROOF MOUNTED SOLAR PHOTOVOLTAIC SYSTEMS PROJECT DESCRIPTION:ARRAY LOCATION GOVERNING CODES: 2018 INTERNATIONAL BUILDING CODE 2018 INTERNATIONAL RESIDENTIAL CODE 2018 INTERNATIONAL FUEL GAS CODE 2018 INTERNATIONAL MECHANICAL CODE 2018 INTERNATIONAL PLUMBING CODE 2018 INTERNATIONAL EXISTING BUILDING CODE 2018 INTERNATIONAL ENERGY CONSERVATION CODE 2017 NATIONAL ELECTRIC CODE SHEET INDEX PV-1 SITE PLAN WITH VICINITY MAP PV-2 ROOF PLAN & MODULES PV-3 STRING LAYOUT PV-3.1 RACKING DETAIL PV-4 ATTACHMENT DETAIL PV-5 ELECTRICAL LINE DIAGRAM PV-6 WIRING CALCULATIONS PV-7 PLACARDS PV-8 SAFETY PLAN PV-9-12 EQUIPMENT SPECIFICATIONS AHJ: TOWN OF ESTES PARK UTILITY:TOWN OF ESTES PARK ATTIC: YES DESIGN SPECIFICATIONS EXPOSURE CATEGORY = C WIND SPEED = 175 MPH GROUND SNOW LOAD = 66 PSF (E) MAIN SERVICE PANEL (IN BASEMENT) SYSTEM SIZE: 10.00 kW DC STC ARRAY AREA #1: 501.50 SQ FT ROOF ACCESS POINT ROOF #1 (25) SUNPOWER SPR-A400-G-AC (400W) MODULES FENCE DARC Y D R PROP E R T Y L I N E P R O P E R T Y L I N E PRO P E R T Y L I N E P R O P E R T Y L I N E DRIVEWAY GARAGE 1 2 3 4 5 6 9 8 7 12 11 10 18 19 20 23 22 211617 25 24 13 15 14 UM MSP ACD S L C JB A C D UD 2 ' - 3 " 1 6 ' - 3 " 7 " 10'-11" 28'-6" 6" 1 ' - 6 " REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-2 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 1 PV-2 SCALE: 1/8" = 1'-0" ROOF PLAN & MODULES SUNPOWER SPR-A400-G-AC (400W) MODULES NOTE TO INSTALLER: FIELD ADJUSTMENTS CAN BE MADE TO THE LAYOUT OF THE ARRAY ROOF PLAN AND MODULES ROOF LAYOUT NOTE SOLAR PANEL LAYOUT IS CONCEPTUAL, BUT AS PROVIDED, CONFORMS WITH THE REQUIREMENTS SET IN SHEET PV-2 CONTRACTOR MAY ADJUST PANEL LOCATION. 72 . 2 " 40" LEGEND - JUNCTION BOXJB MSP - MAIN SERVICE PANEL - TRUSSES - CONDUIT UM - UTILITY METER - VENT, (ROOF OBSTRUCTIONS) MODULE TYPE, DIMENSIONS & WEIGHT NUMBER OF MODULES = 25 MODULES MODULE TYPE = SUNPOWER SPR-A400-G-AC (400W) MODULES MODULE WEIGHT = 46.5LBS/21.1KG. MODULE DIMENSIONS = 72.2"x 40" = 20.06 SF UNIT WEIGHT OF ARRAY = 2.32PSF (N) PV ROOF ATTACHMENT @ 48" O.C. MAX. (N) PV RAIL TYP. (N) RAIL SPLICE (TYP.)SLC -AC PV LOAD CENTER ROOF DESCRIPTION ROOF TYPE COMPOSITION SHINGLES ROOF ROOF TILT AZIMUTH TRUSSES SIZE TRUSSES SPACING #1 20°172°2"X4" & 2"X6"24" O.C. ARRAY AREA & ROOF AREA CALC'S ROOF # OF MODULES ARRAY AREA (Sq. Ft.) ROOF AREA (Sq. Ft.) ROOF AREA COVERED BY ARRAY (%) #1 25 501.50 760.95 65.90 (N) PV JUNCTION BOX (E) MAIN SERVICE PANEL (IN BASEMENT) (E) UTILITY METER (N) FUSED AC DISCONNECT UD -UTILITY DISCONNECT ROOF #1 (25) SUNPOWER SPR-A400-G-AC (400W) MODULES (N) AC PV LOAD CENTER BACK OF RES I D E N C E ROOF # 1 TILT - 20 ° AZIM. - 172 ° FRONT OF RE S I D E N C E CHIMNEY DARCY DR (N) NON-FUSED AC DISCONNECT (N) UTILITY DISCONNECT (E) POLE ACD -FUSED AC DISCONNECT ACD -NON-FUSED AC DISCONNECT 1 STRING LAYOUT PV-3 SCALE: 1/8" = 1'-0" REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-3 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 STRING LAYOUT DISCLAIMER: MATERIALS REQUIRED LIST FOR CONCEPTUAL USE ONLY THE INTENT IS TO AID CONTRACTOR FOR ORDERING REQUIRED MATERIALS FOR THE PROJECT. CONTRACTOR RESPONSIBLE TO VERIFY PRIOR TO SOLAR EQUIPMENT ORDERING BILL OF MATERIALS EQUIPMENT QTY DESCRIPTION SOLAR PV MODULE 25 SUNPOWER SPR-A400-G-AC (400W) MODULES AC DISCONNECT 1 60A FUSED,(2) 50A FUSES,240V NEMA 3R, UL LISTED AC DISCONNECT 1 60A NON-FUSED, 240V NEMA 3R, UL LISTED UTILITY DISCONNECT 60A NON-FUSED, 240V NEMA 3R, UL LISTED ATTACHMENT 82 ECOFASTEN GF1 L-COMP RAILS 26 INVISIMOUNT RAIL-129.125" SECTION RAIL SPLICE 18 SPLICE KIT MID CLAMPS 38 MID CLAMPS / UFO END CLAMPS 24 END CLAMPS / STOPPER SLEEVE GROUNDING LUG 6 INVISIMOUNT GROUNDING LUG CIRCUIT #1-9 MODULES CIRCUIT #2-8 MODULES CIRCUIT #3-8 MODULES BACK OF RESI D E N C E FRONT OF RES I D E N C E DARCY DR 2' - 3 " 16 ' - 3 " 7" 2'-10"10'-9"10'-9"8'-11" 1 RACKING DIAGRAM PV-3.1 SCALE: 1/4" = 1'-0" REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-3.1 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 RACKING DETAILS (N) RAIL SPLICE (TYP.) REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-4 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 ATTACHMENT DETAILS SUNPOWER INVISIMOUNT RACKING SYSTEM PV MODULE GROUNDING END/MID CLAMP GF1-ECOFASTEN L-FOOT SEE (2/PV-4) FOR ENLARGED VIEW ECOFASTEN FLASHING COMPOSITION SHINGLES ROOF 5/16" X 4" GRK 2-1/2" THREAD EMBEDMENT SEALED WITH GEOCELL (OR EQUIV.) 5/16" X 3-1/2" SS LAG BOLT MINIMUM 2-1/2" THREAD EMBEDMENT SEALED WITH GEOCELL (OR EQUIV.) ATTACHMENT DETAIL (ENLARGED VIEW) SCALE: NTS ATTACHMENT DETAIL SCALE: NTS ATTACHMENT DETAIL1 PV-4 SCALE: NTS ATTACHMENT DETAIL (ENLARGED VIEW) SCALE: NTS 2 PV-4 COMP ROOF DETAIL 2"X4" & 2 " X 6 " TRUS S E S @ 24" OC. 2"X4" & 2 " X 6 " TRUS S E S @ 24" OC. PV MODULES SUNPOWER INVISIMOUNT RAIL TYP. REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-5 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 ELECTRICAL LINE DIAGRAM (25) SUNPOWER SPR-A400-G-AC (400W) MODULES (1) CIRCUIT OF 9 MODULES (2) CIRCUITS OF 8 MODULES (CONNECTED IN PARALLEL PER STRING) ELECTRICAL LINE DIAGRAM1 PV-5 SCALE: NTS SYSTEM SIZE: 10.00 kW DC STC NOTE: PV WIRE CAN NOT BE IN SAME CONDUIT AT ANY OTHER LOAD (690.31) WIRE/CONDUITE SCHEDULE TAG #Description Conduit type/size Current carraying conductor type/size Neutral Conductor type/size Grounding conductor type/size ~1 -way length(ft)Notes 1 PV ARRAY TO JUNCTION BOX N/A 6 X #12 DG X 1X #12 Bare Cu 40 2 JUNCTION BOX TO AC PV LOAD CENTER 3/4" EMT 6 X #12 THWN-2 X 1X #12 THWN-2 40 3 AC PV LOAD CENTER TO NON FUSED AC DISCONNECT 3/4" EMT 2 X #8 THWN-2 1 X #8 THWN-2 1X #10 THWN-2 10 4 NON FUSED AC DISCONNECT TO FUSED AC DISCONNECT 3/4" EMT 2 X #8 THWN-2 1 X #8 THWN-2 1X #10 THWN-2 10 5 FUSED AC DISCONNECT TO MAIN SERVICE PANEL 3/4" EMT 2 X #6 THWN-2 1 X #6 THWN-2 x 10 G N L2L1 M BI-DIRECTIONAL UTILITY METER 1-PHASE, 3-W, 120V/240V TO UTILITY GRID N 200A LINE SIDE TAP G AC DISCONNECT: 60A FUSED, 50A FUSES, 240V NEMA 3R, UL LISTED 5 AC DISCONNECT: 60A NON-FUSED, 240V NEMA 3R, UL LISTED G (E) MAIN SERVICE PANEL, 200A RATED, 240V (IN BASEMENT) (E) GROUNDING ROD UTILITY DISCONNECT: 200A NON-FUSED, 240V NEMA 3R, UL LISTED 3 (N) JUNCTION BOX G L1 L2 (N) AC PV LOAD CENTER L2L2 L1L1 L2L2 L1L1 20A 20A G N N G 15A PVS6 8- MICRO-INVERTERS IN BRANCH CIRCUIT #3 L2L2 L1L1 20A 8- MICRO-INVERTERS IN BRANCH CIRCUIT #2 9- MICRO-INVERTERS IN BRANCH CIRCUIT #1 21 4 REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-6 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 WIRING CALCULATIONS ELECTRICAL NOTES 1.) ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. 2.) ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. 3.) WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. 4.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACESSORIES TO FULFILL APPLICABLE CODES AND STANDARDS. 5.) WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. 6.) ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. 7.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. 8.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. AMBIENT TEMPERATURE SPECS AMBIENT TEMP RECORD LOW -23° 34° CONDUIT HEIGHT 0.5" - 3.5" ROOF TOP ADDER 56° PERCENT OF VALUES 0.80 0.70 0.50 NUMBER OF CURRENT CARRYING CONDUCTORS IN EMT 4-6 7-9 10-20 AC CONDUCTOR AMPACITY CALCULATIONS: FROM ROOF TOP JUNCTION BOX TO AC PV LOAD CENTER AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT PER NEC 310.15(B)(3)(c): + 0° EXPECTED WIRE TEMP (°C): 34° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.96 # OF CURRENT CARRYING CONDUCTORS: 6 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 0.80 CIRCUIT CONDUCTOR SIZE: 12 AWG CIRCUIT CONDUCTOR AMPACITY: 30 A AC CONDUCTOR AMPACITY CALCULATIONS: AC PV LOAD CENTER TO NON FUSED AC DISCONNECT AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT EXPECTED WIRE TEMP (°C): 34° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.96 # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 1.00 CIRCUIT CONDUCTOR SIZE: 8 AWG CIRCUIT CONDUCTOR AMPACITY: 55 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 X MAX AC OUTPUT CURRENT X # OF INVERTERS 1.25 X1.45X 25 = 45.31 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96 X 1.00 X 55 = 52.8A SOLAR MODULE SPECIFICATIONS MANUFACTURER MODEL # PMAX PEAK OUTPUT POWER MAX CONTINOUS OUTPUT CURRENT MAX UNIT PER BRANCH CIRCUIT NOM. FREQUENCY 400W 366VA 1.45 11 60HZ SPR-A400-G-AC SUNPOWER MODULE DIMENSION 72.2"L x 40"W x 1.57"D (In Inch) ROOF TOP TEMP 48° TEMP-CORRECTION (AMBIENT TEMP).96 TEMP-CORRECTION (ROOF TOP TEMP).82 CONDUCTOR TEMPERATURE RATE 90° MODULE TEMPERATURE COEFFICIENT OF Voc -0.29% REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 X MAX AC OUTPUT CURRENT X # OF INVERTERS 1.25 X1.45X 9 = 16.31 A 1.25 X1.45X 8 = 14.50 A 1.25 X1.45X 8 = 14.50 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96X 0.80 X 30 = 23.04 A AC CONDUCTOR AMPACITY CALCULATIONS: FUSED AC DISCONNECT TO MSP AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT EXPECTED WIRE TEMP (°C): 34° TEMP CORRECTION PER TABLE 310.15(B)(2)(a): 0.96 # OF CURRENT CARRYING CONDUCTORS: 3 CONDUIT FILL CORRECTION PER NEC 310.15(B)(3)(a): 1.00 CIRCUIT CONDUCTOR SIZE:6 AWG CIRCUIT CONDUCTOR AMPACITY: 75 A REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): 1.25 X MAX AC OUTPUT CURRENT X # OF INVERTERS 1.25 X1.45X 25 = 45.31 A DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(16) TEMP CORR. PER NEC TABLE 310.15(B)(2)(a) X CONDUIT FILL CORR. PER NEC 310.15(B)(3)(a) X CIRCUIT CONDUCTOR AMPACITY = 0.96 X 1.00 X 75 = 72 A REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-7 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 PLACARD WARNING: PHOTOVOLTAIC POWER SOURCE 1. 5 0 " 2. 0 0 " 2. 0 0 " 0. 7 5 " 1. 5 0 " 5.00" BATTERY BACKUP EMERGENCY DISCONNECT 1.75" WARNING Inverter Output Connection Do Not Relocate This Overcurrent Device 4.00" WARNING: DUAL POWER SOURCE 5.00" PV SYSTEM EQUIPPED WITH RAPID SHUTDOWN 5.25" REFLECTIVE PLAQUES 4.00" REFLECTIVE STICKERS STICKERS 3.00" PV AC COMBINER PANEL PV SOURCE CIRCUITS ONLY! PV RAPID SHUTDOWN SWITCH CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT:METER AND MAIN SERVICE PANEL AC DISCONNECT AC PV LOAD CENTER CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT: CAUTION: POWER TO THIS BUILDING IS ALSO SUPPLIED FROM THE FOLLOWING SOURCES WITH DISCONNECTS LOCATED AS SHOWN AT: 2. 0 0 " 2. 0 0 " 1. 5 0 ” 2. 0 0 " 2. 0 0 " PLAQUES 4.00" PV SYSTEM AC DISCONNECT 4.00" PV SYSTEM DC DISCONNECT Isc: Imp: Vmp: Voc max: 4.00" PHOTOVOLTAIC SYSTEM CONNECTED PV PRODUCTION METER 4.50" WARNING Dual Power Sources Second Source is PV System PV AC Output: 36.25A 3.00" (E) MAIN SERVICE PANEL (IN BASEMENT) (E) UTILITY METER (N) AC PV LOAD CENTER (N) FUSED AC DISCONNECT (N) NON FUSED AC DISCONNECT (N) UTILITY AC DISCONNECT DA R C Y D R 1 2 3 4 5 6 9 8 7 12 11 10 18 19 20 23 22 211617 25 24 13 15 14 UM MSP ACD SL C JB AC D UD REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-8 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 SAFETY PLAN GARAGE DRIVEWAY 3/4" EMT CONDUIT RUN (N) PV JUNCTION BOX (E) MAIN SERVICE PANEL (IN BASEMENT) (E) UTILITY METER (N) FUSED AC DISCONNECT (N) AC PV LOAD CENTER BACK O F R E S I D E N C E FRON T O F R E S I D E N C E DARC Y D R (N) NON-FUSED AC DISCONNECT (N) UTILITY DISCONNECT REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-9 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 EQUIPMENT SPECIFICATIONS REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-10 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 EQUIPMENT SPECIFICATIONS REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-11 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 EQUIPMENT SPECIFICATIONS REV SHEET NAME SHEET SIZE SHEET NUMBER Signature with Seal ANSI B 11" X 17" DATEDESCRIPTION REVISIONS PROJECT NAME PV-12 MI C H A E L B R Y S O N 57 0 D A R C Y D R , E S T E S PA R K , C O 8 0 5 1 7 US A 9/8/2020INITIAL DESIGN 00 1501 LEE HILL DR BOULDER, CO 80304 Permits@solarips.com PH# (303) 443-0115 EQUIPMENT SPECIFICATIONS