HomeMy WebLinkAboutPLANS Residential Remodel 641 Meeker Dr 2022-09-14Bathroom - 15 or 20 Amp Dedicated Circuit
to be GFCI protected - min. one outlet
within 36" of outside edge of lav basin per
lavatory located on an adjacent wall.
Receptacles cannot be installed within a zone
of 3' horizontally & 8' from the bathtub rim or
shower stall threshold (410.10D - 2020 NEC)
All habitable space requires heat
supply and pressure relief.
Fire Block per section R302.11 -
See Handout
Basement Finish Insulation:
Continuous Insulation = R15
OR
Cavity framing Insulation = R19
on exterior walls
All work shall be performed by
Licensed Contractors OR by the
homeowner residing in the dwelling.
Toilets, Lavatories & Showers - see
attached handout
DO NOT COVER WORK UNTIL IT HAS BEEN APPROVED BY INSPECTION -
IF YOU HAVE FAILED A ROUGH INSPECTION YOU MUST HAVE AN
APPROVED REINSPECTION BEFORE YOU COVER THE WORK UP.
Replacement of existing receptacles outlets
shall comply with NEC 406.4 D 1-6
Backwater protection required at all
basement level plumbing drains and
to remain accessible
Float all walls - use treated sill
plates (recommended)
SEE HANDOUTS FOR
ADDITIONAL CODE NOTES
AND GUIDANCE
The entire building must be provided with
Smoke Detectors/CO Alarms - see handout
PLANS AND CONSTRUCTION
SHALL MEET THE 2015 IRC AND
ALL APPLICABLE MUNICIPAL
CODES & ORDINANCES
KEEP ALL PERMIT DOCUMENTS
TOGETHER & ON-SITE FOR
INSPECTORS REVIEW
This structure must comply
with the requirements of the
2020 National Electrical
Code
PERMIT #22-EP-00451
Field Copy
Print out legibly & in color and have on
site for inspector
REVIEWED BY SAFEBUILT - PBLAND
APPROVED by SAFEbuilt;
2015 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
09/14/2022
PER SECTION R307 & TABLE 307.1BATHROOM CLEARANCES:
Toilets - must be provided with a minimum of 21 inches in front of the toilet and
lavatory. Toilets must also have 15 inches from the center line of the toilet and any
sidewall or other obstructions.
Showers – shall have a minimum inside dimension of 900 square inches, capable of
encompassing a 30 inch circle and be finished 72 inches above the floor with non-
absorbent materials. Shower door minimum clear opening width is 22 inches (see section
P2708.1 exception 2) Shower door clearance shall have 24” in front of door opening.
- Exterior walls adjacent to showers and tubs shall provide air barrier & insulated. See Table N1102.4.1.1
- Cement based substrate or equal on shower/tub walls
- Freeze Protect pipes per P2603.5
- Provide 50 cfm fan in bathroom - vented to exterior - when no natural ventilation is provided by window
- Provide Anti-Scald Valve on shower
- Bathroom - 15 or 20 Amp Dedicated Circuit to be GFCI
protected - min. one outlet within 36" of outside edge of
lav basin per lavatory located on an adjacent wall.
- Receptacles cannot be installed within a zone of
3' horizontally & 8' from the bathtub rim or shower
stall threshold (410.10D - 2020 NEC)
PLAN REVIEW NOTES -- RELATED TO BATHROOM
ELECTRICAL NOTES:
Document Published by SAFEbuilt, Inc. 5.10.2019 2 of 2
Ceiling Heights:
If the finished ceiling will be less than 7’, please consult your
Building Department.
Smoke Alarms:
Smoke alarms are required in all basements. If the finished
basement contains a sleeping room, a smoke alarm must be
installed on the ceiling or wall in the sleeping room and in the
hallway or area within 15’ of the sleeping room. Smoke alarms
added to satisfy the above requirements must be hard-wired with
a battery backup and interconnected with existing smoke alarms.
Smoke alarms are required to be hardwired and interconnected
in new AND existing bedrooms, halls and on each level.
CO Detectors: C/O detectors shall be installed outside of each
separate sleeping area within 15’ of the bedrooms. Detectors
may be battery operated, plug in type or combination smoke/co
detectors hard wired into the houses electrical system.
Insulation: Check with your local building department for
minimum exterior wall insulation requirements.
Fuel Burning Appliances:
Furnaces and water heaters cannot be located in a bed-room or
bathroom unless appliances are installed in a dedicated
enclosure in which all combustion air is taken directly from
outdoors and a weather stripped solid door equipped with an
approved self closing device is installed. If the furnace and water
heater are being enclosed, adequate combustion air must be
provided for these appliances to operate properly. A
minimum of 30” clear working space must be provided
in front of furnaces and water heaters. Maintenance or
PAGE 2
removal of each appliance must be possible without removing the
other or disturbing walls, piping, valves, wiring and junction boxes.
Fire Blocking:
Fire Blocking must be installed in concealed spaces of wood-furred
walls at the ceiling level, at 10’ intervals along the length of the wall
and at all interconnections of concealed vertical and horizontal
spaces such as intersection of stud walls and soffits or dropped
ceilings. A detail of typical fire blocking is included in this handout.
Fire blocks may be constructed of 2” lumber, 3/4” plywood or
particle board, 1/2” gypsum board or fiberglass insulation 16”
minimum in height, securely fastened.
Space under Stairs:
If the area under the stairs is enclosed useable space accessed by
a door or access panel, protect the walls and ceiling with 1/2”
gypsum board.
Bathrooms:
Toilets must be provided with a minimum of 21” in front of the toilet
and 15” from the center of the toilet to any sidewall or other
obstruction. Showers shall have a minimum inside dimension of
900 square inches. A ventilation fan is required in toilet rooms and
bathrooms with unopenable windows. The fan must be vented to
the exterior of the building and not to terminate within 3’ of an
opening into the building.
Sample Floor
RESIDENTIAL BASEMENT FINISH
Floor Joist Install
before
Fireblock here
Or here Minimum R-15
Insulation
Fireblock here
Or here
Or here
Existing concrete foundation
Fireblock concealed spaces of furred walls and soffits at
10 foot intervals along the length of the wall. Nail to
wall stud and hold tight to concrete foundation wall
from floor to ceiling.
Fill remaining gaps at top
New 2x4 perimeter
2x4 or
16”
insula-
tion
securely
Typical soffit
Finish
materi-
Basement Finish Requirements
Emergency Escapes:
All basements and sleeping
rooms must have an emergency
escape window or exterior door.
Emergency escape windows
with a sill height below grade
must be provided with an emer-
gency escape window as well as
ladder. For details on Emergen-
cy escape windows, see Section
R310 of the International Resi-
dential Code.
Sample Construction Details
Emergency Escapes:
All basements and sleeping
rooms must have an emergency
escape window or exterior door.
Emergency escape windows with
a sill height below grade must be
provided with a window well and
a ladder if the window well is
deeper than 44”. For details on
Emergency escape windows, see
Section R310 of the International
Residential Code.
BASEMENT FINISH HANDOUTNOTE: ANY NEW WINDOW
CUTS INTO FOUNDATION
REQUIRES ENGINEERING
Electrical outlets:
Receptacles shall be installed so that no point measured horizontally along the
floor line of any wall space is more than 6' from a receptacle outlet (E3901.2.1)
AND REMODEL