HomeMy WebLinkAboutPLANS 660 Community Dr Electrical 2016-10-31OS S/DS
S
FAA
S
V
M
6'-8"
5'-4"
6'-0"
TO CENTER
(SEE NOTE 6)
1'-6"
3'-8"
TO BOTTOM OF DEVICE (SEE NOTE 4)
TOP OF CABINET
CENTER OF CABINET
TYPICAL 9'-0" CEILING
TYPICAL 8'-0" CEILING
8'-0"
7'-4"
TO CENTER
TO BOTTOM
5'-0"
TO CENTER
AC AC AC AC
POWER PANEL, FIRE
ALARM PANEL, OR
MASTER CLOCK
1. WHERE MULTIPLE LINE VOLTAGE DEVICES ARE SHOWN ADJACENT TO EACH OTHER, THEY ARE ALL TO
SHARE THE SAME JUNCTION BOX, UP TO FOUR GANGS.
2. WHERE MORE THAN FOUR DEVICES ARE SHOWN ADJACENT TO EACH OTHER, DEVICES ARE TO STACK
VERTICALLY ABOVE ONE ANOTHER IN TWO ROWS IN AS SMALL OF GANG BOXES AS POSSIBLE. I.E. SIX
DEVICES WILL USE TWO THREE GANG BOXES, FIVE DEVICES WILL USE ONE THREE GANG AND ONE TWO
GANG BOX.
3. SEPARATELY GANGED DEVICES ARE NOT ALLOWED TO BE INSTALLED ADJACENT TO ONE ANOTHER
HORIZONTALLY WITHIN THE SAME STUD BAY.
4. AUDIBLE/VISUAL FIRE ALARM DEVICES SHOWN ARE TO BE MOUNTED AT 90" OR 6" BELOW CEILING,
WHICHEVER IS LOWER. ADA STROBES TO BE MOUNTED AT 80" AFF OR 6" BELOW CEILING, WHICHEVER IS
LOWER.
5. MAXIMUM ELEVATION FOR ALL LOAD CENTER CIRCUIT BREAKERS SHALL NOT EXCEED 48" AFF, WITHIN
DWELLING UNITS.
6. THE E.C. SHALL REFER TO ARCHITECTURAL ELEVATIONS TO COORDINATE ALL COUNTER HEIGHTS. ALL "AC"
DEVICES SHALL HAVE BOTTOM OF BACK-BOX MOUNTED 4" ABOVE THE BACK/SIDE SPLASH.
NOTES:
S
MDC
3
4
K
D
DOOR
TO
WS(x)
C
S
D
OS
OS
OS
WOS
TC
PC
HP
R
J
K
RA
F
FS
D
TS
S
TS
MH
S
M
T
M
T
M
V
S
SYSTEMS
DISTRIBUTION AND RACEWAY
FIRE ALARM
LIGHTING FIXTURES
WIRING DEVICES
ABBREVIATIONS AND SYMBOLS
FACP
FA-RPS
FAA
C
A
a
J
J
SR
x
x
x
x
x
x
x
A AMPERE(S)
AC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTING CAPACITY
ATS AUTOMATIC TRANSFER SWITCH
BFF BELOW FINISHED FLOOR
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
DISC DISCONNECT
DW DISHWASHER
DWG(S) DRAWING(S)
(E) EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
(ER) EXISTING TO BE RELOCATED
EM EMERGENCY
EPO EMERGENCY POWER OFF
EWC ELECTRIC WATER COOLER
(R) EXISTING TO BE REMOVED
F FUSE
FLA FULL LOAD AMPS
FD GARBAGE DISPOSAL
G GROUND
GC GENERAL CONTRACTOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
HP HORSEPOWER
IDF INTERMEDIATE DISTRIBUTION FACILITY
IG ISOLATED GROUND
ISC SHORT CIRCUIT CURRENT
KVA KILOVOLT AMPERE(S)
KW KILOWATT(S)
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPERE(S)
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION CENTER
MDF MAIN DISTRIBUTION FACILITY
MLO MAIN LUGS ONLY
MTS MANUAL TRANSFER SWITCH
MW MICROWAVE
NC NORMALLY CLOSED
NL NIGHT LIGHT - SEE GENERAL NOTES
NO NORMALLY OPEN
OAE OR APPROVED EQUAL
OH OVERHEAD
P POLE
PART PARTIAL CIRCUIT
PH PHASE
PNL PANEL
RCPT RECEPTACLE
REF REFRIGERATOR
(RL) RELOCATED
SPD SURGE PROTECTION DEVICE
UC UNDER COUNTER/CABINET
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT(S)
W WATT(S) OR WIRE
WG WIRE GUARD
WP WEATHERPROOF
XFMR TRANSFORMER
POOL EQUIPMENT SCHEDULE NOTATION
KITCHEN EQUIPMENT SCHEDULE NOTATION
MECHANICAL EQUIPMENT SCHEDULE NOTATION
DETAIL NOTE
DELTA REVISION NOTE
ELECTRICAL WIRE SIZE
MAIN DISTRIBUTION CENTER (MDC)
SURFACE MTD PANELBOARD
RECESSED PANELBOARD
TRANSFORMER
BRANCH CIRCUIT HOMERUN
CONDUIT CONCEALED IN FLOOR OR UNDERGROUND
CONDUIT EXPOSED OR CONCEALED IN WALL OR
CEILING
RACEWAY UP
RACEWAY DOWN
CAPPED CONDUIT
CURRENT TRANSFORMER
CIRCUIT BREAKER SWITCH
FUSED SWITCH
GROUNDING ELECTRODE CONDUCTOR
METER
FIRE ALARM CONTROL PANEL
FIRE ALARM ANNUNCIATOR/GRAPHIC MAP
FIRE ALARM REMOTE POWER SUPPLY
CONTROL MODULE
MONITOR MODULE
MANUAL PULLDOWN STATION
WALL MOUNTED ADA STROBE
ADA HORN OR SPEAKER WITH STROBE
MINI HORN / STROBE
ELECTROMAGNETIC DOOR HOLD OPEN
SPRINKLER FLOW SWITCH
SPRINKLER TAMPER SWITCH
THERMAL DETECTOR
PHOTOELECTRIC SMOKE DETECTOR
DUCT SMOKE DETECTOR, SUPPLY OR RETURN
REMOTE INDICATING LIGHT (TEST SWITCH)
120V. MOTORIZED SMOKE DAMPER
RESCUE ASSISTANCE PHONE
FIRE FIGHTERS PHONE JACK
TTB, MDF OR IDF SYSTEM BACKBOARD
TELECOMMUNICATION OUTLET
FLOOR MOUNTED TELECOMMUNICATION OUTLET
TELEVISION OUTLET
SPEAKER - PAGING AND OR SOUND SYSTEM -
INDICATES SPEAKER ZONE
MICROPHONE OUTLET
VOLUME CONTROL
PUSH BUTTON
CLOSED CIRCUIT TELEVISION CAMERA
CABLE TRAY (LENGTH AS INDICATED ON DRAWINGS)
LUMINAIRE TYPE, REFERENCING LUMINAIRE
SCHEDULE, TYPICAL ALL FIXTURES. SUBSCRIPT,
IF SHOWN, REFERENCES WALL SWITCH.
WALL MOUNTED LUMINAIRE
SURFACE MOUNTED LUMINAIRE
RECESSED LUMINAIRE
DOWNLIGHT LUMINAIRE
SURFACE CEILING LUMINAIRE
PENDANT LUMINAIRE
WALLWASH LUMINAIRE
STRIP LUMINAIRE
SURFACE OR PENDANT TRACK LUMINAIRE
LINEAR PENDANT LUMINAIRE (LENGTH AS
INDICATED ON DRAWINGS/SCHEDULE)
EXIT LUMINAIRE - SHADED INDICATES FACE/
DIRECTIONAL ARROWS AS SHOWN.
BATTERY PACK EMERGENCY LUMINAIRE
EMERGENCY LUMINAIRE - SHADED PROVIDE WITH
INTEGRAL BATTERY BACKUP
PORCELAIN LAMP HOLDER
STEP LIGHT TYPE LUMINAIRE
BOLLARD OR POST TOP LUMINAIRE
EXTERIOR AREA LIGHT
DUPLEX RECEPTACLE
FOUR PLEX RECEPTACLE
SINGLE RECEPTACLE
COMBO RECEPTACLE/SWITCH
SWITCHED DUPLEX RECEPTACLE
SPECIAL PURPOSE RECEPTACLE
FLOOR MOUNTED SPECIAL PURPOSE RECEPTACLE
FLOOR MOUNTED RECEPTACLE DUPLEX/QUAD
SURFACE RACEWAY
CLOCK RECEPTACLE
JUNCTION BOX
WALL MOUNTED J-BOX
FLOOR MOUNTED JUNCTION BOX
MOLDED CASE CIRCUIT BREAKER IN ENCLOSURE
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MAGNETIC CONTROLLER (STARTER)
COMBINATION STARTER/DISCONNECT SWITCH
MOTOR
RELAY
TIME CLOCK
PHOTOCELL
THERMAL OVERLOAD SWITCH
SINGLE POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
KEY OPERATED SWITCH
DIMMER SWITCH
RECESSED DOOR SWITCH
LIGHTING CONTROL SYSTEM LOW VOLTAGE DIGITAL
WALL STATION. (X) INDICATES INDIVIDUAL WALL
STATION ADDRESS. REFER TO LIGHTING CONTROL
ONELINE DRAWING.
SINGLE RELAY OCCUPANCY SENSOR/SWITCH.
DOUBLE RELAY OCCUPANCY SENSOR/SWITCH.
CEILING MOUNTED OCCUPANCY SENSOR.
WALL MOUNTED OCCUPANCY SENSOR.
S
S
S
S
S
S
S
x CONTROL INTENT SCHEDULE NOTATION
x LIGHTING CONTROL DEVICE SCHEDULE NOTATION
TP TAMPER-PROOF
UNDERWATER LIGHT
EXISTING STRUCTURAL STEEL
POOL
SHELL BONDING GRID
NEW STRUCTURAL
STEEL PERIMETER
BONDING GRID
POOL BONDING REQUIREMENTS
1. ALL GROUNDING AND BONDING OF ALL METALLIC PARTS ASSOCIATED WITH THE POOL AND
WHIRLPOOL ARE TO BE IN COMPLIANCE WITH 2014 NEC SECTION 680.
2. THE POOL CONCRETE REINFORCING STEEL REBAR SHALL BE BONDED WITH STEEL TIE WIRES, OR
EQUAL, AND SHALL THEREBY SERVE AS A COMMON BONDING GRID FOR ALL PARTS REQUIRED BY
N.E.C. 2011 680.26 TO BE BONDED TOGETHER. BONDING LUGS TO BE SUPPLIED BY ELECTRICAL
CONTRACTOR.
3. ISOLATED PARTS THAT ARE NOT MORE THAN 4" IN ANY DIMENSION AND DO NOT GENERATE INTO THE
POOL STRUCTURE MORE THAN 1" SHALL NOT REQUIRE BONDING.
4. BONDING CONDUCTORS SHALL BE MINIMUM #8 SOLID COPPER, INSULATED. E.C. SHALL COORDINATE
APPROVED CONNECTOR TYPE AND METHOD WITH LOCAL ELECTRICAL AND/OR POOL INSPECTOR.
5. SPECIFIC MANUFACTURER'S INSTRUCTIONS REGARDING BONDING OR GROUNDING OF POOL
EQUIPMENT, WHETHER INDICATED HEREIN OR NOT, SHALL BE STRICTLY FOLLOWED.
6. THE COMMON BONDING GRID SHALL NOT BE CONNECTED TO ANY ELECTRICAL DISTRIBUTION
EQUIPMENT.
7. ANY PARTS IN ADDITION TO THOSE DESCRIBED HEREIN THAT ARE INDICATED BY POOL CONTRACTOR
OR LOCAL INSPECTION AUTHORITY SHALL BE BONDED TO THE COMMON BONDING GRID WITH NO
ADDITIONAL COSTS INCURRED BY THE OWNER.
8. THE ELECTRICAL CONTRACTOR SHALL COORDINATE BONDING WITH POOL CONTRACTOR AND GENERAL
CONTRACTOR.
9. THE FOLLOWING PARTS SHALL BE BONDED TOGETHER AND CONNECTED TO THE COMMON BONDING
GRID (WHERE APPLICABLE OR PROVIDED):
A. ALL METALLIC PARTS OF THE POOL STRUCTURE, INCLUDING COPYING STONES,
DECK, PERMANENT PLAY STRUCTURES, PERMANENT EXERCISE STRUCTURES.
B. ALL METAL FITTINGS WITHIN OR ATTACHED TO THE POOL STRUCTURE.
C. METAL PARTS ASSOCIATED WITH THE POOL WATER CIRCULATING SYSTEM,
INCLUDING PUMPS, FILTERS, AND HEATERS.
D. METAL PARTS ASSOCIATED WITH POOL COVERS.
E. METAL SHEATHED CABLES AND RACEWAYS, METAL PIPING, AND ALL FIXED METAL
PARTS WITHIN 5 FEET HORIZONTALLY OF INSIDE WALLS OF POOL AND WITHIN 12
FEET ABOVE THE MAXIMUM WATER LEVEL OF THE POOL.
F. METAL PARTS ASSOCIATED WITH OBSERVATION STANDS, TOWERS, PLATFORMS,
AND DIVING STRUCTURES.
G. METAL PARTS ASSOCIATED WITH THE POOL SLIDE TOWER, SLIDE STAIRS, AND
ASSOCIATED SLIDE STRUCTURE.
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
NTS
10
/
3
1
/
2
0
1
6
1
1
:
1
5
:
4
3
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL COVER
SHEET
E000
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
COVERSHEET NOTES
1 THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL NECESSARY FOR A COMPLETE AND FUNCTIONING ELECTRICAL SYSTEM.
2 MATERIALS AND INSTALLATION SHALL COMPLY WITH CODES, LAWS AND ORDINANCES OF FEDERAL, STATE AND LOCAL GOVERNING BODIES
HAVING JURISDICTION.
3 MATERIALS AND EQUIPMENT SHALL BE LISTED AND/OR LABELED BY U.L., ETL, CSA OR ANOTHER RECOGNIZED TESTING LAB.
4 ALL WORK REQUIRED FOR THE INSTALLATION AS SHOWN ON DRAWINGS INCLUDING LABOR, EQUIPMENT AND MATERIALS SHALL BE IN STRICT
COMPLIANCE WITH THE BUILDING STANDARDS, EXCEPT AS NOTED OTHERWISE.
5 THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES, TAXES AND LICENSES NECESSARY FOR THE PROPER
EXECUTION AND COMPLETION OF THE ELECTRICAL WORK.
6 THE CONTRACTOR SHALL PREPARE AND SUBMIT TO GOVERNMENTAL AGENCIES AND UTILITY COMPANIES SHOP DRAWINGS, WHICH ARE REQUIRED
BY THESE AGENCIES, FOR THEIR APPROVAL.
7 THE CONTRACTOR SHALL NOTIFY THE ARCHITECT/ENGINEER/OWNER OF ANY MATERIALS OR APPARATUS BELIEVED TO BE INADEQUATE,
UNSUITABLE, IN VIOLATION OF LAWS, ORDINANCES, RULES OR REGULATIONS OF AUTHORITIES HAVING JURISDICTION.
8 FOR ALL JOBS THAT INCLUDE DEMOLITION WORK BY THE ELECTRICAL CONTRACTOR, DURING AND AFTER DEMOLITION, EC SHALL MAINTAIN
CIRCUIT CONTINUITY TO ALL EXISTING DEVICES THAT ARE TO REMAIN. EC SHALL REMOVE, RELOCATE, AND/OR REWORK ANY CONDUIT AND
WIRING TO FACILITATE THE NEW CONSTRUCTION SCOPE OF WORK. FOR A LUMINAIRES THAT ARE EXISTING TO REMAIN OR EXISTING TO BE
RELOCATED, EC SHALL CLEAN LENSES AND REPLACE ALL EXTINGUISHED LAMPS, UON.
9 THE CONTRACTOR SHALL CAREFULLY EXAMINE THE CONTRACT DOCUMENTS, VISIT THE SITE, AND THOROUGHLY BECOME FAMILIAR WITH THE
BUILDING STANDARDS AND LOCAL CONDITIONS RELATING TO THE WORK. FAILURE TO DO SO WILL NOT RELIEVE THE CONTRACTOR OF THE
OBLIGATIONS OF THE CONTRACT.
10 ALL MATERIALS, AND EQUIPMENT SHALL BE ERECTED, INSTALLED, CONNECTED, CLEANED, ADJUSTED, TESTED, CONDITIONED, AND PLACED IN
SERVICE IN ACCORDANCE WITH THE MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS.
11 ALL CUTTING, DRILLING AND PATCHING OF MASONRY, STEEL OR IRON WORK BELONGING TO THE BUILDING MUST BE DONE BY THIS CONTRACTOR
IN ORDER THAT HIS WORK MAY BE PROPERLY INSTALLED, BUT UNDER NO CONDITIONS MAY STRUCTURAL WORK BE CUT, EXCEPT AT THE
DIRECTION OF THE ARCHITECT-DESIGNER OR THEIR REPRESENTATIVE.
12 E.C. IS TO REFER TO ARCHITECTURAL PLANS AND SPECIFICATIONS FOR ALL FIRE RATED PENETRATION INSTALLATION REQUIREMENTS. E.C. IS TO
NOTIFY ENGINEER AND ARCHITECT PRIOR TO INSTALLING ANY FIXTURES WITHIN A FIRE RATED CEILING OR WALL. FIRE RATING MUST BE
MAINTAINED FOR THIS TYPE OF INSTALLATION WITH DRYWALL TENTING.
13 E.C. SHALL PROVIDE COORDINATION STUDY OF NEW AND/OR NEW GEAR COMBINED WITH EXISTING GEAR DURING THE SUBMITTAL PROCESS.
14 SHOP DRAWINGS SHALL INCLUDE MANUFACTURER'S NAMES, CATALOG NUMBERS, CUTS, DIAGRAMS AND OTHER SUCH DESCRIPTIVE DATA AS MAY
BE REQUIRED TO IDENTIFY AND REVIEW THE EQUIPMENT. SUBMITTALS SHALL BE IN LOGICAL GROUPS, FOR EXAMPLE, ALL LIGHTING FIXTURES,
PARTIAL SUBMITTALS WILL NOT BE REVIEWED.
15 PROVIDE THE FOLLOWING INFORMATION, PER IECC 2015 C408.2.5.2 TO THE PARTY RESPONSIBLE FOR PROJECT COMMISSIONING PLAN
(COMMISSIONING AGENT/ MECHANICAL ENGINEER) AND ELECTRICAL ENGINEER.
A. CUTSHEETS FOR ALL INSTALLED LIGHTING AND LIGHTING CONTROLS.
B. OPERATION AND MAINTENANCE MANUALS FOR EACH PIECE OF INSTALLED LIGHTING, REQUIRED ROUTINE MAINTENANCE ACTIONS, CLEANING
AND RECOMMENDED RELAMPING SHALL BE CLEARLY IDENTIFIED.
C. SCHEDULE FOR INSPECTING AND RECALIBRATING ALL LIGHTING CONTROLS. INSPECTION OF ALL LIGHTING CONTROLS SHALL BE PERFORMED
PRIOR TO ELECTRICAL ENGINEER'S COMMISSIONING SITE VISIT. RECALIBRATION OF LIGHTING CONTROLS SHALL BE PERFORMED FOLLOWING SITE
VISIT AND SHALL BE BASED UPON THE RECOMMENDATIONS OF THE ELECTRICAL ENGINEER.
16 ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW, UNLESS SPECIFICALLY INDICATED AS EXISTING TO BE REUSED.
17 CONTRACTOR SHALL OBTAIN AND VERIFY EXACT UTILITY COMPANY DRAWINGS AND REQUIREMENTS. ELECTRICAL CONTRACTOR IS TO SUBMIT A
COMPLETE CONSTRUCTION DRAWING SET TO THE ELECTRICAL UTILITY COMPANY WITHIN 10 DAYS OF AWARD OF CONTRACT. COORDINATE
TIMELINE OF THE REVIEW, APPROVAL, ALL ASSOCIATED DOWN TIME, CONSTRUCTION SCHEDULING, DELIVERY, AND INSTALLATION OF THE UTILITY
TRANSFORMER. NOTIFY OWNER OF SCHEDULING CONFLICTS.
18 ALL NEW CIRCUIT BREAKERS FOR NEW OR EXISTING PANELBOARDS SHALL MATCH EXISTING BUILDING PANELBOARD MANUFACTURER AND
BREAKER TYPE. THE CONTRACTOR SHALL PROVIDE NEW TYPE WRITTEN PANEL DIRECTORIES FOR ALL NEW PANELS AND EXISTING PANELS
WHICH HAVE CHANGED. PANELBOARD SHALL BE MARKED WHERE THE SOURCE OF POWER SUPPLY ORIGINATES, AND IF SERIES COMBINATION
SYSTEMS ARE UTILIZED AND THEIR LISTED AMPERE RATING.
19 DO NOT SHARE NEUTRAL CONDUCTORS FOR MULTIWIRE BRANCH CIRCUITS. WHERE THE E.C. PROPOSES THE USE OF SHARED NEUTRAL
CONDUCTORS OR SHARED NEUTRAL CONDUCTORS ARE REQUIRED (SUCH AS POWERED FURNITURE SYSTEMS), HANDLE TIES SHALL BE PROVIDED
ON THE CIRCUIT BREAKERS, WITH SHARED NEUTRALS, SUCH THAT IT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS. ALL
HANDLE TIES ARE REQUIRED TO BE INDICATED ON THE PANELBOARD SHOP DRAWINGS.
20 SHOULD ACTUAL FIELD CONDITIONS REQUIRE INDICATED CIRCUIT DESIGNATIONS TO VARY, INDICATE THE CIRCUIT NUMBER USED ON THE
"AS-BUILT" DRAWINGS.
21 ALL SERVICE EQUIPMENT (OTHER THAN IN DWELLING UNITS) SHALL BE LEGIBLY MARKED IN THE FIELD BY THE ELECTRICAL CONTRACTOR WITH
THE MAXIMUM AVAILABLE FAULT CURRENT AS INDICATED WITHIN THESE DOCUMENTS. THE FIELD MARKING(S) SHALL COMPLY WITH ELECTRICAL
SPECIFICATIONS FOR READABILITY AND DURABILITY.
22 ALL NEW CIRCUITS SHALL HAVE A GROUND WIRE INSTALLED.
23 ALL WIRING NOT INSTALLED IN CONDUIT AND INSTALLED IN THE CEILING SPACE SHALL BE PLENUM RATED.
24 ELECTRICAL CONTRACTOR SHALL PROVIDE ALL SPECIAL OUTLET BOXES THAT MAY BE REQUIRED TO ENCLOSE RECEPTACLES.
25 IN EXPOSED AND SUSPENDED CEILING APPLICATIONS, ROUTE CONDUIT AS CLOSE TO STRUCTURAL SLAB OR DECK AS POSSIBLE, AND SUPPORT
CONDUIT AND JUNCTION BOXES DIRECTLY FROM THE STRUCTURAL SLAB, DECK, OR FRAMING PROVIDED FOR THAT PURPOSE. LIGHTING BRANCH
CIRCUIT CONDUITS SHALL NOT BE CLIPPED TO THE CEILING SYSTEM HAS BEEN SPECIFICALLY DESIGNED FOR THAT PURPOSE.
26 ALL EXPOSED CONDUIT SHALL BE CONCEALED TO THE GREATEST EXTENT POSSIBLE, AND SHALL BE INSTALLED PARALLEL AND CLOSE TO
STRUCTURAL MEMBERS. GENERAL CONTRACTOR SHALL PAIN CONDUIT TO MATCH ADJACENT FINISHES.
27 WHERE FLOOR FITTINGS REQUIRE PENETRATION OF THE FLOOR SLAB, THEY SHALL BE STANDARD DEVICE LISTED BY UL FOR THE PURPOSE AND
HAVE A UL FIRE RATING EQUAL TO THE FLOOR RATING. FLOOR SERVICE BOXES SHALL BE MODULAR, ADJUSTABLE FLUSH TYPE, DUAL SERVICE
UNITS SUITABLE FOR WIRING METHOD USED. COMPARTMENT BARRIERS SHALL SEPARATE POWER FROM LOW VOLTAGE CABLING. PROVIDE
RECTANGULAR SERVICE PLATE WITH SATIN FINISH.
28 ALL RECEPTACLES SHALL BE SPECIFICATION GRADE NEMA 5-20R, UNLESS OTHERWISE NOTED.
29 ALL LIGHT SWITCHES SHALL BE SPECIFICATION GRADE, QUIET OPERATION RATED 120/277 VOLT, 20 AMPS, UNLESS OTHERWISE NOTED.
30 ALL FACE PLATE AND DEVICE COLORS SHALL BE APPROVED BY ARCHITECT OR OWNER/LEASEE.
31 PROVIDE LUMINAIRES SHOWN AS SHADED WITH EMERGENCY BATTERY BALLASTS. EMERGENCY LUMINAIRES SHALL SENSE UNSWITCHED POWER
TO THE SPACE AND OPERATED AUTOMATICALLY UPON LOSS OF NORMAL POWER. ALL SHADED LUMINAIRES WITH 2' AND 4' LAMPS OR LONG BIAX
LAMPS SHALL HAVE ONE (1) 90 MINUTE, TWO LAMP, 1400 LUMEN EMERGENCY BALLAST. ALL SHADED LUMINAIRES WITH COMPACT FLUORESCENT
LAMPS SHALL HAVE A FACTORY INSTALLED 90 MINUTE EMERGENCY BALLAST. ALL EMERGENCY LUMINAIRES SHALL HAVE REMOTE TEST
SWITCHES AND VISIBLE INDICATING LIGHTS. CONNECT THE EMERGENCY BATTERY BALLAST TO THE UN-SWITCHED LEG OF THE LIGHTING CIRCUIT
INDICATED.
32 ALL BATTERY BACKUP EMERGENCY LIGHTING AND EXIT LIGHTS SHALL BE WIRED AHEAD OF ANY LOCAL SWITCHING, UON.
33 UNLESS OTHERWISE NOTED, LUMINAIRES DESIGNATED AS NIGHT LIGHT (NL) SHALL BE CONNECTED AHEAD OF LOCAL SWITCHING AND REMAIN ON
24 HOURS A DAY.
34 ALL DIMMED LIGHTING CIRCUITS ARE TO RECEIVE DEDICATED NEUTRALS. DO NOT SHARE NEUTRALS ON DIMMED LIGHTING CIRCUITS.
35 WHERE DUAL LEVEL SWITCHING IS INDICATED, THE SWITCH CLOSEST TO THE DOOR SHALL CONTROL ALL OUTER LAMPS IN THE INDICATED
LUMINAIRE AND THE ADJACENT SWITCH SHALL CONTROL ALL INNER LAMP(S) IN THE INDICATED LUMINAIRES, UON.
36 PROVIDE OWNER WITH A COMPLETE LISTING OF ALL LAMPS UTILIZED ON THE PROJECT INCLUDING MANUFACTURER AND CATALOG INFORMATION.
PROVIDE A SUGGESTED SOURCE, INCLUDING CONTACT NAME AND PHONE NUMBER, FOR REORDERING.
37 THE CONTRACTOR SHALL VERIFY THE CEILING TYPE BEFORE ORDERING LIGHTING.
38 ROUGH-IN FOR MECHANICAL EQUIPMENT SHALL ONLY OCCUR AFTER MECHANICAL EQUIPMENT SUBMITTALS ARE THOROUGHLY REVIEWED FOR
CHANGES. NOTIFY ENGINEER OF ANY DISCREPANCIES.
39 FINAL LAYOUT AND QUANTITY OF ALL FIRE ALARM DEVICES SUBJECT TO APPROVAL OF LOCAL AUTHORITY HAVING JURISDICTION.
40 PROVIDE NEMA 3R AND CORROSION RESISTANT ELECTRICAL EQUIPMENT AND WIRING METHODS WITHIN POOL EQUIPMENT, POOL AND WHIRLPOOL
AREAS. REFER TO DRAWINGS AND SPECIFICATION.
41 THE POWER AND CONTROL REQUIREMENTS FOR ALL EQUIPMENT CONNECTIONS SHALL BE CONFIRMED WITH APPROVED SHOP DRAWINGS PRIOR
TO ELECTRICAL ROUGH-IN. FINAL POWER REQUIREMENTS, DIMENSIONED ROUGH-IN LOCATIONS, LOW VOLTAGE SYSTEM CONNECTIONS, ETC.
SHALL BE CONFIRMED AND MODIFIED AS REQUIRED.
42 ALL DEVICES IN OR ABOVE COUNTERS SHALL HAVE LOCATIONS AND MOUNTING HEIGHTS CONFIRMED WITH ARCHITECTURAL ELEVATIONS &
OWNER PRIOR TO ROUGH-IN. ANY ADJUSTMENTS TO MOUNTING HEIGHTS REQUIRED BY LACK OF COORDINATION WILL BE AT THE CONTRACTOR'S
EXPENSE.
43 ALL EXISTING ELECTRICAL SERVICES NOT SPECIFICALLY INDICATED TO BE REMOVED OR ALTERED SHALL REMAIN AS THEY PRESENTLY EXIST.
44 G.C. SHALL INCLUDE IN HIS COST THE REMOVAL OF ALL EXISTING ELECTRICAL DEVICES, CONDUITS, FIXTURES AND EQUIPMENT. TURN EQUIPMENT
OVER TO OWNER AS INDICATED OR RECYCLE/DISCARD ALL EQUIPMENT AS REQUIRED. E.C. SHALL BE RESPONSIBLE FOR DISCONNECTING
PRIMARY SERVICE AND TEMPORARY POWER.
45 WHERE EXISTING CEILINGS ARE REVISED FROM ACCESSIBLE TO NON-ACCESSIBLE, CONTRACTOR IS TO INCLUDE IN HIS BID THE COSTS
ASSOCIATED WITH RELOCATING ALL ELECTRICAL EQUIPMENT REQUIRING ACCESS ABOVE THE EXISTING CEILING TO A NEW ACCESSIBLE CEILING
LOCATION APPROVED BY ARCHITECT AND ENGINEER. THE USE OF ACCESS PANELS IN THE NEW CEILING TO AVOID RELOCATION OF THIS
EQUIPMENT IS NOT ACCEPTABLE.
46 CONTRACTOR TO CONDUCT FUNCTIONAL TESTING OF LIGHTING CONTROLS EQUIPMENT AS REQUIRED BY IECC 2012/2015, SECTION C408.3. AFTER
THIS TESTING IS OBSERVED AND COMPLETED, THE REGISTERED DESIGN PROFESSIONAL OR COMMISSIONING AUTHORITY SHALL PROVIDE
DOCUMENTATION TO THE AHJ THAT CERTIFIES THAT THE INSTALLATION MEETS THE DOCUMENTED PERFORMANCE CRITERIA OF SECTION C405.
NTS1DEVICE MOUNTING HEIGHT
SHEET LIST
SHEET
NUMBER SHEET NAME
E000 ELECTRICAL COVER SHEET
E010 ELECTRICAL SITE PLAN
E102 ELECTRICAL POWER PLAN - LOWER LEVEL
E103 ELECTRICAL POWER PLAN - UPPER LEVEL - NORTH
E104 ELECTRICAL POWER PLAN - UPPER LEVEL - SOUTH
E105 ELECTRICAL ROOF PLAN
E106 ELECTRICAL ENLARGED POWER PLANS
E112 ELECTRICAL LIGHTING PLAN - LOWER LEVEL
E113 ELECTRICAL LIGHTING PLAN - UPPER LEVEL - NORTH
E114 ELECTRICAL LIGHTING PLAN - UPPER LEVEL - SOUTH
E400 ELECTRICAL ONE-LINE DIAGRAM
E401 ELECTRICAL DIAGRAMS
E402 LIGHTING CONTROL SCHEDULES AND DIAGRAMS
E403 LIGHTING CONTROL DIAGRAMS
E500 ELECTRICAL SCHEDULES
E501 ELECTRICAL SCHEDULES
E502 ELECTRICAL SCHEDULES
E503 ELECTRICAL SCHEDULES
E504 ELECTRICAL SCHEDULES
E505 ELECTRICAL SCHEDULES
NTS4POOL BONDING DETAIL
T
T
T
S
S
S
S
S
S
S
S
S
S
SS
SS
SS
868
11
77
8 HC
17
4
12
13
12
9
4 HC
4
15
16
4 HC
16
4
J
1
2
3
4
5
6
7
'MSD'
EA1
RP2A-4
EA1
RP2A-4
EA1
RP2A-6
EA2
RP2A-4
EB3
RP2A-8
EB3
RP2A-9
EB4
RP2A-8
EP5
RP2A-5
EA1
RP2A-4
EA1
RP2A-6
EA2
RP2A-4
EA1
RP2A-4
EA1
RP2A-4
EA2
RP2A-6
EA2
RP2A-6
EB3
RP2A-9
EB3
RP2A-8
EB3
RP2A-8
EB3
RP2A-8
EB3
RP2A-9
EB3
RP2A-8
EB3
RP2A-8
EB3
RP2A-8
EB3
RP2A-9
EP5
RP2A-7
EP5
RP2A-5
EP5
RP2A-7
EB4
RP2A-8
EB4
RP2A-8
EB4
RP2A-8
EP5
RP2A-7 EB4
RP2A-8
EB4
RP2A-8
EP5
RP2A-5
8
9
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
10
ESTES VALLEY COMMUNITY CENTER
11
LP2B-82
LP2B-82
LP2B-82
LP2B-83
LP2B-83
LP2B-83
LP2B-83
LP2B-83
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
LP2B-82
LP2B-82
LP1B-83
B
ATTACH TO
REBAR
WITH
BONDING
CLAMP
I
ANCHOR BOLT
ANCHOR BOLT DATA
4-#4 BARS
VERTICAL
ELEVATION
H
EA1
KEY
POLE
25'0"
HEIGHT
OVERALL
4"
A
F
G
24"
H
PER MANUFACTURER
B SIZE C
D
6" 8'0"
E F
10'0"
G
TOP VIEW
36"
I
BASE PLATE
1" CHAMFER
BASE COVER
ATTACH TO
BONDING LUG ON
POLE
D
A
C
HAND HOLE
E
H
BELOW TOP 5" OF
FOUNDATION #3
HORIZ. TIES @ 12" O.C.
PVC RIGID
CONDUIT
TYP.
FINISH GRADE
VARIES
3-#3 HORIZ. TIES WITHIN
TOP 5" OF FOUNDATION
EA2 25'0"4"24"PER MANUFACTURER 6" 8'0" 10'0" 36"
PER MANUFACTUREREP5 15'0"4"24"6" 8'0" 10'0" 36"
PER MANUFACTUREREB3/EB4 3'0"4-3/8"
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
As indicated
10
/
3
1
/
2
0
1
6
1
1
:
1
6
:
0
0
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL SITE
PLAN
E010
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
1" = 30'-0"1 ELECTRICAL SITE PLAN
NTS2POLE BASE DETAIL
GENERAL NOTES
A UNLESS OTHERWISE NOTED, ALL CIRCUIT NUMBERS INDICATED ON THIS SHEET
SHALL REFER TO CIRCUIT ORIGINATING IN PANELBOARDS BASED UPON THE
FOLLOWING CONVENTION, (THIS SHEET ONLY):
TBD-# = CIRCUIT TO PANEL 'TBD'
B EC SHALL REFER TO SECURITY DRAWINGS AND IRRIGATION DRAWINGS FOR
ADDITIONAL CONDUIT, WIRING, AND CIRCUITY TO BE PROVIDED IN ADDITION TO
THAT SHOWN ON THE ELECTRICAL DRAWINGS.
EC SHALL PROVIDE EXPANSION JOINT FITTINGS FOR ALL CONDUITS AS
REQUIRED BY STRUCTURAL DRAWINGS.
ALL EXTERIOR LIGHTING CIRCUITS SHALL UTILIZE A MINIMUM WIRE SIZE OF
#8AWG COPPER, UNLESS OTHERWISE NOTED.
C
D
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 EXISTING UTILITY PAD MOUNTED TRANSFORMER TO BE DEMOLISHED. REFER
TO ELECTRICAL DEMOLITION ONE-LINE DIAGRAM FOR MORE INFORMATION.
2 APPROXIMATE ROUTING OF EXISTING UTILITY PRIMARY.
3 APPROXIMATE ROUTING OF EXISTING LOW-VOLTAGE/TELEPHONE SERVICE
TO EXISTING MTTB IN MAIN ELECTRICAL ROOM.
4 LOCATION OF EXISTING MAIN ELECTRICAL ROOM AND EXISTING ELECTRICAL
SERVICE EQUIPMENT.
5 APPROXIMATE LOCATION OF EXISTING UTILITY POLE.
6 APPROXIMATE LOCATION OF EXISTING TELEPHONE SERVICE PEDESTAL.
7 LOCATION OF NEW 480/277V, 3-PHASE, PAD MOUNTED UTILITY
TRANSFORMER. ALL PRIMARY TRENCHING/BACKFILLING AND CONDUIT
BETWEEN THE UTILITY VAULT AND NEW TRANSFORMER LOCATION SHALL BE
PROVIDED/INSTALLED BY UTILITY. PRIMARY LINES SHALL BE 4' DEEP WITH
RED WARNING TAPE INSTALLED AT 2' DEPTH. REFER TO UTILITY
REQUIREMENTS FOR CONDUIT PRIMARY PIPE RACK AND ADDITIONAL
CONDUIT REQUIREMENTS. THE EC SHALL PERFORM ALL
TRENCHING/BACKFILLING FOR THE TRANSFORMER SECONDARY FEEDERS,
AND PROVIDE/INSTALL ALL SECONDARY CONDUIT. EC SHALL COORDINATE
ALL CONDUIT ROUTING IN FIELD AND VERIFY PRIMARY ROUTING TO
TRANSFORMER PRIMARY CONNECTION POINT WITH UTILITY PRIOR TO WORK
COMMENCE. PRPA SHALL MAKE ALL FINAL CONNECTIONS OF PRIMARY AND
SECONDARY FEEDERS REQUIRED AT THE TRANSFORMER LANDINGS. EC
SHALL COORDINATE ALL UTILITY TRANSFORMER PAD INSTALLATION
REQUIREMENTS, CLEARANCES, PAD ORIENTATION, UTILITY METERING
REQUIREMENTS AND INSTALLATION OF METERING EQUIPMENT WITH UTILITY
PRIOR TO WORK COMMENCE.
8 APPROXIMATE ROUTING OF TRANSFORMER SECONDARY FEEDER TO MAIN
SERVICE DISCONNECT. REFER TO ELECTRICAL ONE-LINE DIAGRAM FOR
MORE INFORMATION.
9 APPROXIMATE ROUTING OF NEW LOW-VOLTAGE/TELEPHONE SERVICE FROM
NEW TELEPHONE SERVICE PEDESTAL TO NEW LAN LOCATION. EC SHALL
COORDINATE EXACT ROUTING AND TERMINATION LOCATIONS PRIOR TO
ROUGH-IN.
10 PROVIDE (1) 1" AND (1) 1-1/4" UNDERGROUND CONDUIT FOR 120V, 20-AMP
POWER CONNECTION AND DATA CONNECTION TO INTERNALLY ILLUMINATED
MONUMENT SIGN. POWER BRANCH CIRCUIT TO BE 2#8, 1#10G (UPSIZED FOR
VOLTAGE DROP). COORDINATE EXACT LOCATION WITH ARCHITECT PRIOR TO
ROUGH-IN.
11 CONDUIT LOCATION FOR (1) 1-1/2" ORANGE PVC SPARE CONDUIT FROM
TRANSFORMER STUBBED INTO BUILDING PROVIDED BY UTILITY AND
INSTALLED BY CONTRACTOR.
DN
DN
S
J
J J J
J
CLG
J
CLG
T
SS
J
CUH
3
CUH
4UH
5 CUH
5
TF
2
UH
4
J
J
CLG
J
CLG
J
J
J
J
J
J
J
JJ
J
S
S
S
J
S
J
CLG
J
CLG
J
CLG
EF
16
J
J
J
ELEV
1
S
T
SP
1
J
J
J
A
B
1
L
3 4 6 7
A1
A4
AB
A5
AE
AD
AH
AC
C
D
E
F
K
A2
A3
AG
AF
AA
A.1
B.7
H H
J J
J.3
12
5
GFI
WP
GFI
WP
GFI
WP
GFI
WP
RECV & STOR
115
CLASSROOM
114
MEN
110
WOMEN
111
ELEV
117
GYM
131
P&R DIRECTOR
108
VEST
101
KITCHEN
112
WOMEN
104
EMP ENTRY
103
STORAGE
143
COMMUNITY
141
COMMUNITY KITCHEN
142
STOR
113
STRENGTH
123
MP GROUP EX
124
GYM STORAGE
132 EXIT STAIR
S10
STRENGTH
123
STAFF
107
GAMES
106
LOUNGE
102
JR GOLF
121
HITTING
122
MEN
105
ELEC
109
GFI
WP
GFI
WP
3
3
3 3
'LP1B'
'HL1B'
'HM1B'
'RP1B'
STORAGE
118
GFI
WP
+42"
GFI
+42"
GFI
AC
AC
AC
AC
GFI
AC
GFI
4
5
3
6
7
8
+72"
+72"
9
FAN FAN1010
10
10
11
11
12
13
13
14
13
15
13
4
4
4
4
4
4
16
+72"
+72"
+72"
+72"
+72"
+72"
GFI
GFI
GFI
EWC
GFI
REF
AC
GFI
AC
GFI
+60"
GFI
MW
AC
GFI
17
GFI
EWC
CLG
CLG
CLG
CLG
16
9
E102
2
'T1B'
WP
FS
TS
FS
TS
GD
2021
22
22 22 22
RANGE
30A/2P
AC
GFI
AC
GFI
GFI
EWC
3
3
23
23
LP1B-2
LP1B-2
LP1B-2
LP1B-2
LP1B-4
LP1B-4
LP1B-4
LP1B-4
LP1B-4
LP1B-4
LP1B-5
LP1B-9
LP1B-8
LP1B-10
LP1B-5
LP1B-11
LP1B-5
LP1B-9
LP1B-5
LP1B-5
LP1B-8
LP1B-7
LP1B-7
LP1B-6
LP1B-6
LP1B-6
LP1B-6
LP1B-6
LP1B-5
LP1B-12
LP1B-12
LP1B-14
LP1B-15
LP1B-29LP1B-26
LP1B-12
LP1B-12
LP1B-12
LP1B-13
LP1B-12
LP1B-72
LP1B-71
LP1B-70
LP1B-16LP1B-69
LP1B-16
LP1B-16
LP1B-51
LP1B-12
LP1B-12
LP1B-53LP1B-54
LP1B-55
LP1B-56
LP1B-57 LP1B-58 LP1B-59
LP1B-18 LP1B-19 LP1B-19 LP1B-19
LP1B-18
LP1B-18
LP1B-20
LP1B-20
LP1B-20
LP1B-21
LP1B-21 LP1B-21
LP1B-27
LP1B-24
LP1B-25
LP1B-27
LP1B-27LP1B-27
LP1B-25
LP1B-22
LP1B-22
LP1B-23
LP1B-23
LP1B-25
LP1B-25
LP1B-23
LP1B-31 LP1B-28
LP1B-33
LP1B-39LP1B-34
LP1B-32
LP1B-30LP1B-39
LP1B-39
LP1B-36
LP1B-41
LP1B-39
LP1B-39
LP1B-38
LP1B-38LP1B-25
LP1B-35,37
LP1B-40
LP1B-40
LP1B-40
LP1B-40
LP1B-45
LP1B-45
LP1B-27
LP1B-45
LP1B-42
LP1B-45 LP1B-45
LP1B-42
LP1B-64
LP1B-64
LP1B-64
LP1B-64
LP1B-45
LP1B-39
LP1B-44
LP1B-44
LP1B-50 LP1B-50
LP1B-46
LP1B-46
LP1B-46
LP1B-48
LP1B-49
LP1B-61
LP1B-61
LP1B-61
LP1B-61
LP1B-63
LP1B-61 LP1B-60
LP1B-62
LP1B-60
LP1B-60
LP1B-68
LP1B-60
LP1B-60
LP1B-60
12
LP1B-70
LP1B-69
LP1B-70
LP1B-70LP1B-69
LP1B-70
LP1B-66
LP1B-68
LP1B-65
LP1B-67
LP1B-68
LP1B-68
LP1B-69
LP1B-16
LP1B-73
LP1B-73
LP1B-42 LP1B-42
LP1B-64LP1B-64
LP1B-42
LP1B-42
1010 10 10
GFI
LP1B-12
E106
2
14
LP1B-68
25
26
LP1B-78
LP1B-79
A4
A5
AH
K
2
GFI
18
19
1
GFI
WP
24
LP1B-43
LP1B-75
LP1B-80
LP1B-81
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
As indicated
10
/
3
1
/
2
0
1
6
1
1
:
2
8
:
4
0
A
M
C:
\
U
s
e
r
s
\
k
m
e
n
y
h
a
r
t
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
nt
r
a
l
_
k
m
e
n
y
h
a
r
t
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL POWER
PLAN - LOWER
LEVEL
E102
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NORTH
1/8" = 1'-0"1 LOWER LEVEL POWER PLAN
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 APPROXIMATE LOCATION OF ELEVATOR MANUFACTURER PROVIDED ELEVATOR
POWER CONTROL WITHIN THE PIT. THE ELEVATOR CONTROL PANEL INCLUDES
INTEGRAL 80A/3P CIRCUIT BREAKER DISCONNECT WITH SHUNT TRIP COIL FOR
CONNECTION TO THE FIRE ALARM SYSTEM.
2 PROVIDE KEYED SWITCH FOR ELEVATOR CAB POWER AND LIGHTING CIRCUIT.
3 PROVIDE FIRE ALARM DEVICE WITH MANUFACTURER'S STANDARD WIRE GAURD
PROTECTION.
4 FLOORBOX TO BE HUBBELL RECESSED CONCRETE WITH SMOOTH METALLIC
COVER, SIMILAR TO HUBBELL LCFBCXX (OR APPROVED EQUAL) CARPET
APPLICATIONS TO BE FLANGE COVERPLATE. ALL COVERPLATES SHALL BE FLUSH
WITH FLOOR FINISH TO REDUCE TRIPPING HAZARDS. EC SHALL PROVIDE 1-1/2"C
FOR DATA AND 3/4"C FOR POWER ROUTED UP NEAREST WALL THROUGH
ACCESSIBLE CEILING. EC TO VERIFY SPECIFICATIONS PRIOR TO ORDERING. EC
SHALL COORDINATE LOCATIONS AND REQUIREMENTS WITH OW NER/ARCHITECT
PRIOR TO ROUGH-IN ARCHITECT SHALL CHOOSE COVER PLATE FINISH.
5 PROVIDE 120V, 30mA GROUND FAULT PROTECTED EQUIPMENT CONNECTION FOR
HEAT TRACE. COORDINATE EXACT LOCATION AND HEAT TRACE LENGTH WITH
ARCHITECT/OWNER PRIOR TO INSTALLATION. COORDINATE ALL CONTROLLER
CONNECTION REQUIREMENTS WITH APPROVED EQUIPMENT SHOP DRAWINGS
PRIOR TO INSTALLATION.
6 CEILING MOUNTED JUNCTION BOX FOR 120V POWER CONNECTION TO GOLF
SIMULATOR PROJECTOR SYSTEM.
7 CEILING MOUNTED JUNCTION BOX WITH 1"C BACK TO WALL JUNCTION BOX FOR
GOLF SIMULATOR PROJECTOR SYSTEM AV CABLING.
8 APPROXIMATE LOCATION OF COMMUNICATIONS CONDUIT, FROM UTILITY
CONNECTION CABINET AT PROPERTY LINE, ENTERING BUILDING. EXTEND
CONDUIT FROM UNDER SLAB, THROUGH LOWER FLOOR AREA, UP INTO STUB OUT
8" ABOVE UPPER FLOOR IT ROOM.
9 JUNCTION BOX MOUNTED ABOVE CEILING FOR 120V, 20A POWER CONNECTION TO
CEILING MOUNTED MOTORIZED PROJECTION SCREEN OPERATOR. EC SHALL
COORDINATE EXACT LOCATION/CONTROL/CONNECTION REQUIREMENTS WITH
APPROVED AV DRAWINGS PRIOR TO ROUGH IN.
10 RECEPTACLE IS MOUNTED IN MIRROR WALL. COORDINATE FACEPLATE FINISH
WITH ARCHITECT.
11 FUTURE SCOREBOARD LOCATION. SURFACE MOUNTED JUNCTION BOX MOUNTED
ON GYM SIDE OF TRACK FOR FUTURE MOUNTING OF SCOREBOARD TO TRACK
WALL. PROVIDE JUNCTION BOX WITH BLANK FACEPLATE AND 3/4" CONDUIT.
CONDUIT FOR FUTURE SCOREBOARD SHALL BE SUNK IN TRACK DECK CONCRETE.
12 SCOREBOARD POWER LOCATION ON FRONT OF TRACK. EC SHALL COORDINATE
ELECTRICAL REQUIREMENTS AND EXACT LOCATION/ELEVATION WITH FINAL
ARCHITECTURAL DRAWINGS AND APPROVED SHOP DRAWINGS PRIOR TO
ROUGH-IN. CONDUIT FOR SCOREBOARD SHALL BE SUNK IN TRACK DECK
CONCRETE.
13 WALL MOUNTED RECESSED JUNCTION BOX WITH 1"C TO ROOM JOIST SPACE FOR
SCOREBOARD COMMUNICATIONS CABLING/RACEWAY.
14 WALL MOUNTED RECESSED JUNCTION BOX WITH 1"C TO ABOVE ACCESSIBLE
CEILING FOR SCORERS TABLE COMMUNICATIONS CABLING/RACEWAY.
15 WALL MOUNTED JUNCTION BOXES WITH 3/4"C TO ABOVE ACCESSIBLE CEILING
FOR DIVIDER CURTAIN AND BASKET HEIGHT ADJUSTER CONTROLS LOCATION.
EXACT LOCATION, QUANTITY, AND CONNECTION REQUIREMENTS TBD.
16 120V DUPLEX AND DATA RECEPTACLES MOUNTED FLUSH IN CEILING FOR
PROJECTOR POWER AND LOW VOLTAGE CABLING CONNECTIONS. EC SHALL
COORDINATE EXACT REQUIREMENTS WITH APPROVED AV DRAW INGS PRIOR TO
ROUGH-IN.
17 120V POWER CONNECTION FOR GAS FIREPLACE IGNITION CIRCUIT UNDER
ALTERNATE. EC SHALL COORDINATE EXACT LOCATION AND CONNECTION
REQUIREMENTS WITH APPROVED SHOP DRAWINGS.
18 JUNCTION BOX FOR 120V, 20A POWER CONNECTION TO ELEVATOR CAB. EC SHALL
COORDINATE JUNCTION BOX LOCATION WITH APPROVED SHOP DRAWINGS PRIOR
TO ROUGH-IN.
19 JUNCTION BOX AND 3/4" CONDUIT TO ABOVE ADJACENT ACCESSIBLE CEILING FOR
ELEVATOR LOW VOLTAGE TELEPHONE CABLING RACEWAY. CONTRACTOR SHALL
PROVIDE (1) CAT6 CABLE FROM 110BLOCKS LOCATED WITHIN THE LAN ROOM FOR
CONNECTION TO ELEVATOR CONTROL PANEL. COORDINATE EXACT LOCATION
PRIOR TO ROUGH-IN.
20 JUNCTION BOX FOR 120V POWER CONNECTION TO MOTORIZED AUTOMATED
ACCESS DOOR OPERATOR. EC SHALL MAKE ALL NECESSARY INTERCONNECTIONS
BETWEEN JUNCTION BOX, SECURITY SYSTEM, OPERATOR MOTOR, AND PUSH PAD
LOCATIONS PER MANUFACTURER'S REQUIREMENTS. COORDINATE EXACT
LOCATIONS WITH APPROVED EQUIPMENT SHOP DRAWINGS AND SECURITY
SYSTEM INSTALLER.
21 JUNCTION BOX FOR 120V POWER CONNECTION TO MOTORIZED AUTOMATED
ACCESS DOOR OPERATOR. EC SHALL MAKE ALL NECESSARY INTERCONNECTIONS
BETWEEN JUNCTION BOX, OPERATOR MOTOR, AND PUSH PAD LOCATIONS PER
MANUFACTURER'S REQUIREMENTS. COORDINATE EXACT LOCATIONS WITH
APPROVED EQUIPMENT SHOP DRAWINGS.
22 WALL MOUNTED RECESSED JUNCTION BOX WITH 3/4"C FOR INSTALLATION OF
MOTORIZED ASSIST PUSH PAD DEVICE INSTALLATION. COORDINATE EXACT
LOCATION AND CONNECTION REQUIREMENTS WITH APPROVED SHOP DRAWINGS
PRIOR TO ROUGH-IN.
23 PROVIDE 120V, 10A POWER FOR SECURITY SYSTEM DOOR HOLD. REFER TO
SECURITY DRAWINGS FOR ADDITIONAL INFORMATION.
24 PROVIDE 120V, 20-AMP POWER CONNECTION TO ELEVATOR SUMP PUMP CONROL
PANEL. COORDINATE EXACT LOCATION IN THE FIELD WITH OTHER EQUIPMENT IN
ELEVATOR MACHINE ROOM. COORDINATE EXACT REQUIREMENTS WITH
MECHANICAL CONTRACTOR PRIOR TO INSTALLATION.
25 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING PLANE FOR 120V POWER
CONNECTION TO VAV CONTROLS TRANSFORMER. EC SHALL COORDINATE EXACT
LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
26 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING FOR 120V POWER
CONNECTION TO FIRE SMOKE DAMPER. EC SHALL COORDINATE EXACT LOCATION
AND FIRE ALARM SYSTEM CONNECTION REQUIREMENTS WITH APPROVED
MECHANICAL SHOP DRAWINGS PRIOR TO ROUGH-IN.
GENERAL NOTES
A EC SHALL REFER TO AUDIO VISUAL AND SECURITY SYSTEMS DRAWINGS FOR
ADDITIONAL EC PROVIDED AND INSTALLED CONDUIT, WIRING, AND CIRCUITING.
1/4" = 1'-0"2 ELEVATOR MECHANICAL ROOM & PIT ENLARGED POWER PLAN
S
J J J J
EF
7
EF
8
CF
1
UH
1
CF
2
J
CLG
S
S
S
T
S
J
UH
6
J
J
J
J
DSIU
1
T
T
TF
1
A
B
L
3 4 6 7
A4
A5
8
AE
AD
AH
C
D
E
F
G
K
A3
AG
AF
A.1
B.7
H H
J
J.3
12
12
5
5
DESK STAFF
272
WOMEN
204
MEN
203
WATER & FIRE ENTRY
273
EXEC DIR
281
M/P GROUP EX
262
CARDIO
261
ST.
263
LOBBY
202
FINANCE
287
FACILITY DIR
285
HR
283
ADMIN
271
COPY
278
LAN
276
ELEC
282
IT
274
CONFERENCE
275
MARKET
277
ASST
279
1
1 1
1
AC
GFI
AC
GFI
AC
GFI
AC AC
AC
AC
AC
GFI
MW
GFI
REF
2
3
GFI
EWC
4
4
AED
CLG
CLG
5
+12" +12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"
+12"+12"
+12"
+12"
+12"
6
7
7
+12"
+12"+12"
+12"
+12"+12"
+12"
+12"+12"
+12"
+12"+12"
+12"+12"
+12"+12"
+12"
+12"+12"
COPIER
+12"
+12"
+12"
+12"
+12"
+12"
AC
LP2B-32LP2B-27
LP2B-28 LP2B-33
LP2B-34LP2B-29
LP2B-30 LP2B-35
LP2B-31 LP2B-36
LP2B-15
LP2B-16
LP2B-17
LP2B-18
LP2B-19
LP2B-20
LP2B-21
LP2B-22
LP2B-23
LP2B-24
LP2B-25
LP2B-26
LP2B-59
LP2B-60
LP2B-65
LP2B-66
LP2B-64
LP2B-63
LP2B-62
LP2B-67
LP2B-61
LP2B-58
LP2B-58
LP2B-58
LP2B-57
LP2B-57
LP2B-57
LP2B-57
LP2B-56
LP2B-57
LP2B-57 LP2B-53
LP2B-54
LP2B-52
LP2B-55
LP2B-51
LP2B-51
LP2B-51
LP2B-41
LP2B-41
LP2B-41
LP2B-51
LP2B-41
LP2B-45
LP2B-41
LP2B-44
LP2B-42
LP2B-43
LP2B-41
LP2B-40
LP2B-40
LP2B-40
LP2B-40
LP2B-39
LP2B-39
LP2B-39LP2B-38
LP2B-38
LP2B-38
LP2B-38LP2B-37
LP2B-37
LP2B-37LP2B-37
LP2B-47
LP2B-47 LP2B-47
LP2B-49
LP2B-46
LP2B-48
LP2B-49
LP2B-49
LP2B-49
LT2B-1
LT2B-1
LT2B-1
LP2B-50
LP2B-50
LP2B-50
LP2B-51
LP2B-58
LP2B-69
LP2B-69
LP2B-69
LP2B-70
LP2B-71
LP2B-71
E103
2
LP2B-58 LP2B-58 LP2B-58888
LP2B-68 LP2B-72
LP2B-72
LP2B-73
AC
LP2B-73
AC
LP2B-71
LP2B-71 LP2B-71
LP2B-71 LP2B-71 LP2B-71
E103
3
11
LP2B-85
12
LP2B-86
13
LP2B-87
LT2B-2
LT2B-3
LT2B-7
LT2B-6
LT2B-5
LT2B-4
LT2B-8
LT2B-9
LT2B-10
LT2B-11
LT2B-12
LT2B-13
LT2B-14
LT2B-15
LT2B-16
LT2B-17
LT2B-18
LT2B-19
9
9
9
9
9
9
9
'LT2B'
10
10
10 10
10
LP2B-49
'LP2B'
'HM2B'
'HL2B'
'RP2A'
'T2B'
'TBT'
SUSPENDED
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
As indicated
10
/
3
1
/
2
0
1
6
1
1
:
1
6
:
2
8
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL POWER
PLAN - UPPER
LEVEL - NORTH
E103
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
GENERAL NOTES
A
NORTH
1/8" = 1'-0"1 UPPER LEVEL POWER PLAN - NORTH
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 PROVIDE 120V, 20A POWER CONNECTION TO FORWARD FOLDING MOTORIZED
ADJUSTABLE HEIGHT BASKETBALL GOAL. EC SHALL COORDINATE EXACT
CONNECTION REQUIREMENTS AND LOCATION WITH APPROVED MANUFACTURERS
SUBMITTALS PRIOR TO ROUGH-IN.
2 120V, 20A POWER CONNECTION TO GYMNASIUM DIVIDER CURTAIN SYSTEM
OPERATOR. EC SHALL COORDINATE EXACT CONNECTION REQUIREMENTS AND
LOCATION WITH APPROVED MANUFACTURERS SUBMITTALS PRIOR TO ROUGH-IN.
3 JUNCTION BOX MOUNTED ABOVE CEILING FOR 120V, 20A POWER CONNECTION TO
CEILING MOUNTED MOTORIZED PROJECTION SCREEN OPERATOR. EC SHALL
COORDINATE EXACT LOCATION/CONTROL/CONNECTION REQUIREMENTS WITH
APPROVED AV DRAWINGS PRIOR TO ROUGH IN.
4 PROVIDE 120V, 20A POWER CONNECTION TO FORWARD FOLDING MOTORIZED
BASKETBALL GOAL. EC SHALL COORDINATE EXACT CONNECTION REQUIREMENTS
AND LOCATION WITH APPROVED MANUFACTURERS SUBMITTALS PRIOR TO
ROUGH-IN.
5 120V DUPLEX AND DATA RECEPTACLES MOUNTED FLUSH IN CEILING FOR
PROJECTOR POWER AND LOW VOLTAGE CABLING CONNECTIONS. EC SHALL
COORDINATE EXACT REQUIREMENTS WITH APPROVED AV DRAWINGS PRIOR TO
ROUGH-IN.
6 PROVIDE POWER CONNECTION TO LAP TIMER. EC SHALL COORDINATE EXACT
CONNECTION REQUIREMENTS AND LOCATION WITH APPROVED MANUFACTURERS
SUBMITTALS PRIOR TO ROUGH-IN.
7 PROVIDE POWER CONNECTION FOR MOTORIZED VOLLEYBALL SLEEVES. EC SHALL
COORDINATE EXACT CONNECTION REQUIREMENTS AND LOCATION WITH
APPROVED MANUFACTURERS SUBMITTALS PRIOR TO ROUGH-IN.
8 MOUNT RECEPTACLES HORIZONTALLY UNDER MIRROR.
9 PROVIDE NEMA 5-30R TWISTLOCK RECEPTACLE. SUSPENDED PENDANT MOUNT
ABOVE RACK LOCATION ADJACENT TO OVERHEAD CABLE TRAY. FIELD
COORDINATE EXACT FINAL LOCATION WITH STRUCTURED CABLING INSTALLER.
10 PROVIDE NEMA 5-20R QUAD RECEPTACLE SUSPENDED PENDANT MOUNT ABOVE
RACK LOCATION ADJACENT TO OVERHEAD CABLE TRAY. FIELD COORDINATE
EXACT FINAL LOCATION WITH STRUCTURED CABLING INSTALLER.
11 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING PLANE FOR 120V POWER
CONNECTION TO VAV CONTROLS TRANSFORMER. EC SHALL COORDINATE EXACT
LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
12 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING FOR 120V POWER
CONNECTION TO FIRE SMOKE DAMPER. EC SHALL COORDINATE EXACT LOCATION
AND FIRE ALARM SYSTEM CONNECTION REQUIREMENTS WITH APPROVED
MECHANICAL SHOP DRAWINGS PRIOR TO ROUGH-IN.
13 IRRIGATION CONTROLLER, PROVIDE 120V CONNECTION. EC SHALL FIELD
COORDINATE EXACT LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO
ROUGH-IN.
EC SHALL REFER TO AUDIO VISUAL AND SECURITY SYSTEMS DRAWINGS FOR
ADDITIONAL EC PROVIDED AND INSTALLED CONDUIT, WIRING, AND CIRCUITING.
1/4" = 1'-0"2 ENLARGED LAN ROOM 276
1/4" = 1'-0"3 UPPER LEVEL NORTH ELEC ROOM
J
J
J
J
J
J
J J J J
J
CLG
J
CLG
GWH
1
PP
1
CUH
1
CUH
2
UH
2
CF
3
EF
3
TF
3
UH
3
B
1
B
2
CP
1
CP
2
P
1
P
2
TT
J
J
J
J
J
SS
S
S
S
S
S
S
WN
A
WN
A
WN
A
WN
A
WN
A
WN
A
WN
A
WN
A
WN
A
WN
A
GWH
2
GWH
3
B
3
CP
3
J
J
CLG
JJ
ECH
3
WN
A
WN
A
S
J
CF
4A
CF
5A
J J
J
J
J
J
J
S
S
S
J
J
J
JJ
E1 E2 E3
E4 E5 E6 E7 E8 E9 E10 E11 E12
E13
E14
EA
EB
EC
ED
EE
EF
2
Q
9 10
EG
EH
1
L
P
M
3 4 6 7
A4
A5
8
M.6
AH
N
7.96.4
NJ
5
GFI
+42"
GFI
+42"
GFI
AC
GFI
GFI
GFI
AC
GFI
AC
GFI
AC
GFI
GFI
WP
AC
GFI
GFI
AC
GFI
GFI
WP
GFI
WP
GFI
WP
ACTIVITY POOL
001
POOL MECH
253
POOL STORAGE
255
POOL OFFICE
256
CIRC
259
W. LOCKERS
221
M. LOCKERS
231
JAN
229
ACR3
216
CHG
215ACR2
214
FAM CHANGING
212
ACR1
213
W. TOILETS
223
W. SHOWERS
222 M. TOILETS
233
M. SHOWERS
232
MECHANICAL
A102
FOYER
A101EXIST LAUNDRY
A111
EXIST ELEC
A113
EXIST POOL MECH
A112
EXIST POOL EQUIP
A114
EXIST NATATORIUM
A110
POOL STORAGE
A108
M. TEAM LOCKER
A107
W. TEAM LOCKERS
A106
EXIST POOL DECK
A109
EXIST POOL DECK
A109
PARTY
211
VESTIBULE
201
LOBBY
202
INDOOR PLAY
205
GFI
GFI
GFI
GFIGFI
GFI
GFI
GFI
GFI
GFI
GFIGFI
GFI
GFI
GFI GFI
GFI
GFI
TP
TP
TP
TP
TP
'FAA'
1 1
2 3
4
5
5
5
6
TP
ELEC
254
KID WATCH
288
KIDS T
207
OFFICE
206
EXIST CHEM
A115
ALT WATER SLIDE
002
E106
1
GUARDS
258
GUARD CHG
257+42"
GFI
GFI
WP
'MSD'
'(E) L2'
'(E) H2'
'(E) H1'
'(E) L1'
'(E) TL1'
'TL2'
'(E) BUSSED
GUTTER'
(E)(E)
AC
GFI
AC
GFI
AC
GFI
AC
GFI
AC
GFI
GD
AC
GFI
MW
AC
GFI GFI
REF
AC
GFI TP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
AC
GFI
7
5
GFI
REF
AC
GFI
MW
GFI
EWC
AC
GFI
5
5
AC
GFI
GFI
EWC
4
4
4
TP
TP
+78"
+78"
8
AED
WP
9999
10
11
11
11
AMENITY PUMP #1
AMENITY PUMP #2
CURRENT PUMP #1 AND #2
12SLIDE PUMP
VESTIBULE
A104
STORAGE
A105
POOL MECH
253
13
14
15 16 GFI
LP2B-70
LP2B-70
LP2A-26
LP2A-26
LP2A-25
LP2A-27
LP2A-28
LP2A-31
LP2A-31
LP2A-29 LP2A-30
LP2A-31 LP2A-31
LP2A-32
LP2A-32
LP2A-32
LP2A-32
LP2B-75
LP2A-36
LP2A-36
LP2A-36
LP2A-32
LP2A-33
LP2A-33
LP2A-33
LP2A-33
LP2A-37
LP2A-37 LP2A-37 LP2A-37
LP2A-37
LP2A-36
LP2A-36
LP2A-37
LP2A-48,50
LP2A-41
LP2A-43
LP2A-43
LP2A-44
LP2A-44
LP2A-45 LP2A-45
LP2A-38,40
LP2A-57
LP2A-45
LP2A-58
LP2A-45
LP2A-45
LP2A-54
LP2A-52 LP2A-55
LP2A-56
LP2A-54
LP2A-47,49
LP2A-56
LP2B-76
LP2B-77
LP2B-77LP2B-78LP2B-77
LP2B-77
LP2B-77
LP2A-56
LP2A-56
LP2A-56
LP2A-63
LP2A-51,53
LP2A-64
LP2A-63
LP2A-61
LP2A-62
LP2A-59
LP2A-59 LP2A-59
LP2A-59
LP2A-59
LP2A-63
LP2A-59
LP2A-64
LP2A-65 LP2A-65 LP2A-65
LP2A-65
LP2A-66
LP2A-66
LP2A-66
LP2A-66
LP2A-66
LP2A-65
1
LP2A-60
10
10
10
10
10
WP
WP
WP
WP
WP
WP
TP
LP2A-32 TP
LP2A-33
AC
GFI TP
LP1B-47
LP2B-74
LP2B-74
GFI
LP2B-74
GFI
LP2B-74
LP2B-75
LP2B-75
LP2B-75
LP2B-75
LP2A-67
GFI
LP2A-66
10
LP2A-66
GFI
GFI
LP2B-74
LP2B-80
LP2B-80 LP2B-79
LP2B-79
LP2B-81
LP2B-80
LP2A-46
LP2A-1217
'VECP'
5
LP2A-39
5
5
18
18
18
19
LP2A-68
LP2A-42
LP2A-70
LP2A-70
LP2A-70
LP2A-72
5
LP2A-74
LP2A-78
20RP2A-13
20
RP2A-13
20
RP2A-13
20
RP2A-13
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/8" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
6
:
4
3
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL POWER
PLAN - UPPER
LEVEL - SOUTH
E104
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
GENERAL NOTES
A
NORTH
1/8" = 1'-0"1 UPPER LEVEL POWER PLAN - SOUTH
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 PROVIDE 120V, 30A/1P RECEPTACLE FOR POOL VACUUM. PROVIDE HINGED
WATER-PROOF COVER AND GASKETED FACEPLATE SUITABLE FOR INTENDED USE
IN NATATORIUM ENVIRONMENT. CONNECT WITH 2#10, 1#10G, 3/4"C AND PROVIDE
GFCI CIRCUIT BREAKER AT PANEL. COORDINATE EXACT CONNECTION
REQUIREMENTS WITH APPROVED SHOP DRAWINGS AND VERIFY EXACT LOCATION
WITH POOL CONTRACTOR AND ARCHITECT PRIOR TO ROUGH-IN.
2 JUNCTION BOX FOR 120V POWER CONNECTION TO MOTORIZED AUTOMATED
ACCESS DOOR OPERATOR. EC SHALL MAKE ALL NECESSARY INTERCONNECTIONS
BETWEEN JUNCTION BOX, OPERATOR MOTOR, AND PUSH PAD LOCATIONS PER
MANUFACTURER'S REQUIREMENTS. COORDINATE EXACT LOCATIONS WITH
APPROVED EQUIPMENT SHOP DRAWINGS.
3 JUNCTION BOX FOR 120V POWER CONNECTION TO MOTORIZED AUTOMATED
ACCESS DOOR OPERATOR. EC SHALL MAKE ALL NECESSARY INTERCONNECTIONS
BETWEEN JUNCTION BOX, SECURITY SYSTEM, OPERATOR MOTOR, AND PUSH PAD
LOCATIONS PER MANUFACTURER'S REQUIREMENTS. COORDINATE EXACT
LOCATIONS WITH APPROVED EQUIPMENT SHOP DRAWINGS AND SECURITY
SYSTEM INSTALLER.
4 WALL MOUNTED JUNCTION BOX FOR 208V, 20A POWER CONNECTION TO HAIR
DRYER, COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH
ARCHITECT PRIOR TO ROUGH-IN.
5 WALL MOUNTED JUNCTION BOX FOR 120V, 20A CONNECTION TO ELECTRIC HAND
DRYER. EC SHALL COORDINATE EXACT LOCATION, HEIGHT, AND ELECTRICAL
REQUIREMENTS WITH ARCHITECTURAL ELEVATIONS AND APPROVED SHOP
DRAWINGS PRIOR TO ROUGH IN.
6 ALL RECEPTACLES LOCATED IN THE CHILDWATCH AREA BELOW 5'-0" SHALL BE
TAMPER PROOF. REFER TO DIVISION 26 SPECIFICATIONS FOR MORE
INFORMATION.
7 WALL MOUNTED JUNCTION BOX FOR 120V, 20A POWER CONNECTION TO SUIT
SPINNER. EC SHALL COORDINATE EXACT LOCATION AND CONNECTION
REQUIREMENTS WITH APPROVED SHOP DRAWINGS PRIOR TO ROUGH-IN.
8 LOCATION OF EMERGENCY 'EPO' SWITCHES FOR SHUT DOWN OF POOL PUMP
SYSTEMS AS SET FORTH IN POOL ENGINEERING DRAWINGS.
9 WALL MOUNTED RECESSED JUNCTION BOX WITH 3/4"C FOR INSTALLATION OF
MOTORIZED ASSIST PUSH PAD DEVICE INSTALLATION. COORDINATE EXACT
LOCATION AND CONNECTION REQUIREMENTS WITH APPROVED SHOP DRAWINGS
PRIOR TO ROUGH-IN.
10 EC SHALL UTILIZE EXISTING LOCATION FOR NEW SPEAKER STROBE. UTILIZE
EXISTING CONDUITS TO AVOID SURFACE MOUNTED CONDUITS.
11 EC SHALL PROVIDE START/STOP SWITCH WITH INTEGRAL INDICATOR LIGHT FOR
PUMP INDICATED. DO NOT USE SWITCHES THAT NEED TO BE HELD DOWN TO
START THE VFD SLOW START CYCLE; SWITCHES SHOULD OPERATE BY MAKING
CONTACT BEFORE THE CYCLE STARTS. ALL FACEPLATES SHALL BE PROVIDED
WITH LABEL TO INDICATE THE PUMP CONTROLLED. EC SHALL REFER TO POOL
DRAWINGS FOR SCHEMATIC INTERLOCK DIAGRAM.
12 EC SHALL PROVIDE START/STOP SWITCH WITH INTEGRAL INDICATOR LIGHT FOR
PUMP INDICATED, PER ALTERNATE #4. ALL FACEPLATES SHALL BE PROVIDED
WITH LABEL TO INDICATE THE PUMP CONTROLLED. EC SHALL REFER TO POOL
DRAWING
13 PROVIDE 120V, 10A POWER FOR SECURITY SYSTEM DOOR HOLD. REFER TO
SECURITY DRAWINGS FOR ADDITIONAL INFORMATION.
14 EPO LOCATION FOR ALTERNATE WATER SLIDE PER ALTERNATE #4. IF ALTERNATE
IS ACCEPTED, FIELD COORDIATE EXACT LOCATION. IF ALTERNATE IS NOT
ACCECPTED, PROVIDE EMPTY CONDUIT FROM LOCATION INDICATED BACK TO
STUB OUT ABOVE ENTRY DOOR WITHIN THE POOL MECHANICAL ROOM.
15 FUTURE SPA EPO LOCATION. PROVIDE JUNCTION BOX AND EMPTY 3/4" CONDUIT
FROM LOCATION INDICATED BACK TO STUB OUT ABOVE ENTRY DOOR WITHIN THE
POOL MECHANICAL ROOM.
16 FUTURE SPA TIME SWITCH LOCATION. PROVIDE JUNCTION BOX AND EMPTY 3/4"
CONDUIT FROM LOCATION INDICATED BACK TO STUB OUT ABOVE ENTRY DOOR
WITHIN THE POOL MECHANICAL ROOM.
17 PROVIDE 120V CONNECTION FOR TEMPERATURE CONTROL PANEL. RE:
MECHANICAL FOR ADDITIONAL INFORMATION.
18 JUNCTION BOX LOCATED ABOVE CEILING FOR 120V POWER CONNECTION TO FIRE
ACCORDIAN DOOR SYSTEM. EC SHALL COORDINATE EXACT LOCATION AND FIRE
ALARM SYSTEM CONNECTION REQUIREMENTS WITH APPROVED
MANUFACTURER'S SHOP DRAWING PRIOR TO ROUGH-IN.
19 JUNCTION BOX LOCATED ABOVE ACCESSIBLE CEILING PLANE FOR 120V POWER
CONNECTION TO VAV CONTROLS TRANSFORMER. EC SHALL COORDINATE EXACT
LOCATION WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
20 LOCATION OF FLUSH MOUNTED, CORROSION RESISTANT, JUNCTION BOX LISTED
FOR POOL USE, AND LOCATED INSIDE WALL RECESS WITH ACCESS PANEL FOR
CONNECTION TO UNDERWATER OF POOL WET NICHE CONDUIT/FIXTURE.
JUNCTION BOX SHALL BE LOCATED A MINIMUM OF 18" ABOVE THE ASSOCIATED
DECK LEVEL. INSTALLATION SHALL COMPLY WITH ALL REQUIREMENTS OF NEC
ARTICLE #680.
EC SHALL REFER TO AUDIO VISUAL AND SECURITY SYSTEMS DRAWINGS FOR
ADDITIONAL EC PROVIDED AND INSTALLED CONDUIT, WIRING, AND CIRCUITING.
EF
9
EF
1 EF
2
EF
4
EF
6
RTU
2
EF
10
EF
12
RTU
1
MAU
1
DSCU
1
RTU
3
PDU
1A
EF
5
EF
11
J
CLG
J
CLG
J
CLG
J
CLG
EF
15
EF
14
PDU
2
EF
17
E1 E2 E3 E4 E5 E6 E7 E8 E9 E10 E11 E12 E13 E14
EA
EB
EC
ED
EE
EF
2
A
B
Q
9 10
EG
EH
1
LL
P
MM
3 4 6 7
A1
A4
AB
A5
8
AE
AD
M.6
AH
AC
C
D
E
F
G
K
N
A2
A3
AG
AF
AA
6.4
NJ
A.1
H
J
J.3
12
5
5
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
GFI
WP
1
1
GFI
WP
LP2B-11
2
3
4
5
1
1
LP2B-13
LP2B-12
LP2B-13
LP2B-14
LP2B-13
LP2B-14
LP2B-14
LP2B-14
LP2A-24
LP2A-24
LP2A-22LP2A-24
LP2A-23
LP2A-21
LP2A-23
LP2A-24
LP2A-23LP2A-23
LP2A-24
GFI
WP
LP2A-24
GFI
WP
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/16" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
7
:
0
2
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL ROOF
PLAN
E105
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NORTH
1/16" = 1'-0"1 ROOF POWER PLAN
GENERAL NOTES
A EC SHALL REFER TO AUDIO VISUAL AND SECURITY SYSTEMS DRAWINGS FOR
ADDITIONAL EC PROVIDED AND INSTALLED CONDUIT, WIRING, AND CIRCUITING.
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 EC SHALL ROUTE HEATTRACE CABLE WITHIN GUTTER FOR LENGTHS AS
INDICATED.
2 EC SHALL PROVIDE 120V, 1PH JUNCTION BOX AND HEATTRACE ALONG GUTTER
AND DOWNSPPOUTS. REFER TO PLUMBING DRAWINGS FOR SPECIFICATIONS
AND LOCATIONS. TOTAL 146 LF RUN INCLUDING DOWNSPOUTS. 1,460 WATTS
TOTAL. PROVIDE 2"12, 1#12G, 3/4" C TO JUNCTION BOX.
3 EC SHALL PROVIDE 120V, 1PH JUNCTION BOX AND HEATTRACE ALONG GUTTER
AND DOWNSPPOUTS. REFER TO PLUMBING DRAWINGS FOR SPECIFICATIONS
AND LOCATIONS. TOTAL 20 LF RUN INCLUDING DOWNSPOUTS. 200 WATTS
TOTAL. PROVIDE 2"12, 1#12G, 3/4" C TO JUNCTION BOX.
4 EC SHALL PROVIDE 120V, 1PH JUNCTION BOX AND HEATTRACE ALONG GUTTER
AND DOWNSPPOUTS. REFER TO PLUMBING DRAWINGS FOR SPECIFICATIONS
AND LOCATIONS. TOTAL 40 LF RUN INCLUDING DOWNSPOUTS. 400 WATTS
TOTAL. PROVIDE 2"12, 1#12G, 3/4" C TO JUNCTION BOX.
5 EC SHALL PROVIDE 120V, 1PH JUNCTION BOX AND HEATTRACE ALONG GUTTER
AND DOWNSPPOUTS. REFER TO PLUMBING DRAWINGS FOR SPECIFICATIONS
AND LOCATIONS. TOTAL 35 LF RUN INCLUDING DOWNSPOUTS. 350 WATTS
TOTAL. PROVIDE 2"12, 1#12G, 3/4" C TO JUNCTION BOX.
TT
SE
1,2
CP
1
CP
2LAP
2
LAP
1
SLCP
1
LCP
1
LH
1
SCP
1
SJP
1SH
1
CCS
2
CCS
1
FC
1
AP
1
CC
2
CH
1
CH
2
J J
CC
1
AC
1
SJB
1 FC
2
CCEB
1
CCEB
2
AP
2
J
CCBP
1
CCBP
2
T
EF
13
KH
1
E3
E4 E5
E6
2
Q
EH
1
NJ
'LA2A'
'HA2A'
'HM2A'
'TPA' SUSP
'TAA' PAD
MOUNTED
'FACP'
'MDC'
GFI
POOL MECH
253
ELEC
254
GFI
'MSD'
1
1
GFI
GFI
GFI
'RP2A'
2
'LP2A'
LA2A-14
LA2A-13
LA2A-13
LA2A-13
LA2A-10
LA2A-10
LA2A-13
LA2A-13
LP2A-1LP2A-2
COMMUNITY KITCHEN
142
'T1K'
SUSPENDED
'LK1B'
LK1B-17
AC
GFI
LK1B-17
AC
GFI
LK1B-17
GFI
LK1B-16
AC
GFI
LK1B-15
AC
GFI
LK1B-14
AC
GFI
LK1B-13
GFI
REF
LK1B-12
GFI
REFLK1B-11
AC
GFI
LK1B-8,10
OVEN
30A/2P
LK1B-7,9
RANGE
30A/2P
LK1B-6
AC
GFI
LK1B-5
AC
GFI
LK1B-4
AC
GFI
MW
LK1B-3
AC
GFI
LK1B-2
DW
30A/1P
LK1B-1
AC
GFI
DED
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/4" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
7
:
0
9
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
ENLARGED POWER
PLANS
E106
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
1/4" = 1'-0"1 UPPER LEVEL ENLARGED POWER PLAN - POOL MECH
GENERAL NOTES
A
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 PROVIDE 120V, 20-AMP POWER CONNECTION FOR AUTO-FILL CONTROLLER.
COORDINATE EXACT LOCATION AND REQUIREMENTS WITH POOL CONTRACTOR
PRIOR TO ROUGH-IN. LOW-VOLTAGE WIRING AND CONNECTIONS SHALL BE BY
POOL CONTRACTOR. COORDINATE ALL CONDUIT ROUTING AS REQUIRED.
2 PROVIDE 120V CONNECTION FOR SE-1 AND SE-2 CONTROL PANEL. COORDINATE
EXACT LOCATION AND POWER REQUIREMENTS WITH APPROVED PLUMBING
PLANS. RE: PLUMBING FOR ADDITIONAL INFORMATION.
EC SHALL REFER TO AUDIO VISUAL AND SECURITY SYSTEMS DRAWINGS FOR
ADDITIONAL EC PROVIDED AND INSTALLED CONDUIT, WIRING, AND CIRCUITING.
1/4" = 1'-0"2 LOWER LEVEl COMMUNITY KITCHEN ENLARGED VIEW
DN
DN
VS
S
OSC
3
3
VS
S
OSC
33
VS
S
VS S
D
OSC
OSC
D
D
D
OSC
K
K
OSC
OSC
VS S
3
VS
S
VS
S
WS
2
T
RC
D
D
O
SC
3
3
3
VS
S
D
RC
RC
3 3
OSC
RC
W S3
WS4
W S5
TS1
TS1
TS1
RC
RC
RC
OSC
OSC
OSC
OSC
OS C
O
SC
A
B
9 10
L
3 4 6 7
A1
A4
AB
A5
8
AE
AD
AH
AC
C
D
E
F
G
K
A2
A3
AG
AF
AA
7.96.4
A.1
B.7
H
J
J.3
12
5
MP GROUP EX
124
STRENGTH
123
HITTING
122
JR GOLF
121
STAIR
120
RECV & STOR
115
ELEV
117
MEN
110
WOMEN
111
P&R DIRECTOR
108 ELEC
109
STAFF
107
GAMES
106
GYM
131
WOMEN
104
MEN
105
LOUNGE
102 VEST
101
KITCHEN
112
CLASSROOM
114
STOR
113
COMMUNITY
141
STORAGE
143
EMP ENTRY
103
EXIT STAIR
S10
GYM STORAGE
132
COMMUNITY KITCHEN
142
STORAGE
118
D1EM D1EM
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
R2
L2
R2
R2
R1 R1
R1
R1
F1
F1
D1
D1EM
D1 D1
D1
D1EM
D1
D1
F1 F1 F1 F1 F1
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1EM
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
D1EM
RP1B-6
D1
RP1B-6
bD1 bD1 bD1
bD1
aL1A
cT1 cT1
aL1B
aL1A
aL1BaL1B
aL1A
R22
RP1B-5
R22EM
RP1B-5
R22
RP1B-5
R22EM
RP1B-5
R22
RP1B-5
P3
RP1B-5
P3
RP1B-5
P3EM
RP1B-5
P3
RP1B-5
P3EM
RP1B-5
R22EM
RP1B-5
R22EM
RP1B-5
P3
RP1B-5
P3
RP1B-5
P3EM
RP1B-5
P3
RP1B-5
P3
RP1B-5
R9
R9
R9
P1
RP1B-1
P1EM
RP1B-1
P1
RP1B-1
P1EM
RP1B-1
D1
RP1B-1
D1
RP1B-1
D1EM
RP1B-1
D1
RP1B-1
R1
R1R1
R1
R1
W3EM
RP2B-12 X1
X1
X2
X2
X1
X1
X1
P1
P1
P1
P1
X1
X2
P5
RP1B-3
P5
RP1B-3
P5
RP1B-3
P5
RP1B-3
P5
RP1B-3
D1
RP1B-1
D1EM
RP1B-1
D1
RP1B-1D1
RP1B-1
X1
L2
W1W1
P6
RP1B-1
P6
RP1B-1
P6
RP1B-1
D1
D1
RG1
W2
W2
W2
W2
RG10
RG14
RG8
RG14
R2
R2
P1
P1
P1
P1
P6
RP1B-1
P6
RP1B-1
P6
RP1B-1
P6
RP1B-1
P6
RP1B-1
P1
RP1B-1
P1EM
RP1B-1
11'-6" AFF
P1
RP1B-1
P1
RP1B-1
P1EM
RP1B-1
P1
RP1B-1
P6
RP1B-1
P6
RP1B-1
P1EM
RP1B-1
P1
RP1B-1
P1EM
RP1B-1
D1
RP1B-1
C1
RP1B-4
C1
RM1
RP1B-2
RM2
RP1B-2
RM2
RP1B-2
RM2
RP1B-2
RM1
RP1B-2
R1
D1
RP1B-1
D1EM
RP2B-12
P1
RP2B-12
P1EM
RP2B-12
EW3EM
RP1B-7
9'-6"
EW3EM
RP1B-7
9'-6"
UC1
D1EM
RP1B-1
D1
RP1B-1
D1
RP1B-1
aD1 aD1
aD1
aD1 aD1
bD1
bD1
bD1
bD1
bD1
F1
C2
j
C3
f
C4
c
P8
eD5
d
D5EM
d
D5
d
D5
a
D5
a
D5EM
a
D5
a
D5
a
D5
a
D5
a
D5EM
a
D5
a
D5
a
P9
b
P9
b
D2
d
D2
d
D2
d
D2
a
D2
a
D2
a
D5
g
D5EM
g
D5
g
D6
g
D6EM
g
D6
g
D6
g
D6
g
D6
g
D2
g
D2
g
D2
g
R9
R9
R9
R9
R9
R9
D1
X1
X1
X1F1
EST1
RP1B-7
EST1
RP1B-7
EST1
RP1B-7
EST1
RP1B-7
EP1
EP1
EP1EM
EP1
EP1EM
EP1
P1EM
RP1B-1
P1EM
RP1B-1
L4
RP1B-1
L4
RP1B-1
EW3EM
RP1B-7
EW2
RP1B-7
F1
HL1B- 12
a
HL1B- 12
bHL1B- 14
a
HL1B- 14
b
HL1B- 14
c
RCD3
a,b,c
a,b
F1
VSC1
RCD1
VSC2
VSC1
RCD1
VS1
(TYP.)
VSC1
OSC2
OSC2
LVKS
(TYP.)
RCD4
RCD4
RCD4
VSC4
VSC4
VSC4
TS
RCD2
VSC1
D1EM
RP1B-1
D1EM
RP1B-5
D1
RP1B-5
D1
RP1B-5
D1
RP1B-5
P9
h
P9
h
HL1B- 8
HL1B- 8
HL1B- 8
HL1B- 8
HL1B- 10
HL1B- 10
HL1B- 10
HL1B- 11
HL1B- 11
HL1B- 11
HL1B- 11
HL1B- 11
LP1B- 77
LP1B- 77
LP1B- 77
LP1B- 77
HL1B- 12
HL1B- 12
HL1B- 14
VSC1
VSC1
HL1B- 11
D5
d
D5
d
D5
d
D5
d
D5EM
d
D5
d
D5
d
D5
g
D5
g
D5
g
D5
g
D5EM
g
D5
g
D5
g
D6
d
D6EM
d
D6
d
D6
d
D6
a
D6EM
a
D6
a
D6
a
D6
a
D6
a
a,b,c
d,e,f
g,h,j
EW3EM
RP1B-7
9'-6"
P3
RP1B-5
P3EM
RP1B-5
P3
RP1B-5
DAYLIGHT ZONE
63W
DAYLIGHT ZONE
63W
DAYLIGHT ZONE
42W
DAYLIGHT ZONE
42W
DAYLIGHT ZONE
132W
DAYLIGHT ZONE
111W
DAYLIGHT ZONE
30W
bD1
D1
D1
VSC2
LP1B- 75
VSC2
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/8" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
7
:
2
7
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
LIGHTING PLAN -
LOWER LEVEL
E112
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
GENERAL NOTES
A ALL FIXTURES WITH HATCHING AND/OR DESIGNATED AS 'EM' SHALL BE
PROVIDED WITH INTEGRAL BATTERY BACKUP. BATTERY SHALL ENGAGE ONLY
AFTER COMPLETE LOSS OF POWER TO THE CIRCUIT.
B CIRCUIT ALL EMERGENCY LIGHTING AND EXIT SIGNS TO NEAREST LINE
VOLTAGE CIRCUIT, AHEAD OF ALL SWITCH LEGS.
UNLESS OTHERWISE NOTED, ALL CIRCUIT NUMBER INDICATED ON THIS SHEET
SHALL REFER TO CIRCUIT ORIGINATING IN PANELBOARDS OR RELAY PANELS
BASED ON THE FOLLOWING CONVENTION, (THIS SHEET ONLY):
TBD-# = CIRCUIT TO 'TBD'
C
REFER TO LIGHTING CONTROLS SCHEDULES AND DIAGRAMS, SHEET E402 & E403,
FOR MORE INFORMATION.
D
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1/8" = 1'-0"1 LOWER LEVEL LIGHTING PLAN
VS S
VS
S
VS
S
VS
S
VS
S
VS
S
O
SC
VS
S
VS S T
DD
VS
S
K
K
O
SC
O
SC
OSC
D
VS
S
VS
S
RC
RC
WS1
WS6
O
SC
A
B
9 10
L
3 4 6 7 A1
A4
AB
A5
8
AE
AD
AH
AC
C
D
E
F
G
K
A2
A3
AG
AF
7.96.4
A.1
B.7
H
J
J.3
5
M/P GROUP EX
262
ST.
263
CARDIO
261
LOBBY
202
MEN
203
WOMEN
204
DESK STAFF
272
IT
274
LAN
276
ELEC
282 COPY
278
WATER & FIRE ENTRY
273
CONFERENCE
275
MARKET
277
ASST
279
EXEC DIR
281
HR
283
FACILITY DIR
285
FINANCE
287
TEMP
284
EXIT STAIR
S10
bD1
bD1
bD1
aL2 bD1
bD1
bD1
bD1
F1
F1
F1
R1
R1
R1 R1
R9
R9
R1
R1
D4
RP2B-2 D1EM
RP2B-2
R2EM
RP2B-1
R2
RP2B-1
R2EM
RP2B-1
R2
RP2B-1
R2EM
RP2B-1
R2
RP2B-1
R2EM
RP2B-1
R2
RP2B-1
R2
RP2B-1
D1
D1EM
D1
D1EM
D1
H1EM
RP2B-7
H1
RP2B-6
H1
RP2B-6
H1
RP2B-6
H1
RP2B-6
H1EM
RP2B-7
H1
RP2B-6
H1
RP2B-6
H1
RP2B-6
H1EM
RP2B-7
H1EM
RP2B-9
H1
RP2B-8
H1
RP2B-8
H1EM
RP2B-9
H1EM
RP2B-9
H1
RP2B-8
H1
RP2B-8
H1
RP2B-8
H1
RP2B-8
H1
RP2B-8
R9
F1
R2
R2
R2
R2
R1
R1
R1
R1
R1
R1
R1
R1 R1
R1
R1
R1
R1
R1
R1
R1
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3EM
RP2B-5
P3
RP2B-5
P3
RP2B-5
P3
RP2B-5
W3EM
RP2B-12
W3EM
RP2B-12
X1
X1
X1
X1
D1
R9
D1
RP2B-2
D1
RP2B-2
D1
RP2B-2
D1EM
RP2B-2
D1
RP2B-2
D1
RP2B-2
P1EM
RP2B-12
P1
RP2B-12
R20EM
RP2B-10
R20
RP2B-10
R20
RP2B-10
RG8
RG8
RG6
RG6
W2
P5
RP2B-3
P5
RP2B-3P5
RP2B-3
C1
P1EM
RP2B-2
P1
RP2B-2
P1
RP2B-2
R16A
R16A
R13A R13A
R16A
R20
R20
R15A
R15EM
RP2B-10
W2
UC1
P1
RP2B-5
X1
ST.
263a
a
b
CF1
R13A
CF1 CF1
CF1
1
a,b
VSC1
RCD1
LVKS
(TYP.)
RCD2
VSC2
VS1
(TYP.)
TS
OSC2
OSC2
VSC1
a,bHL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
HL2B- 2
LP2B- 3
LP2B- 3
LVD1
(TYP.)
HL2B- 12
HL2B- 12
HL2B- 12
DAYLIGHT ZONE
59W
DAYLIGHT ZONE
59W
DAYLIGHT ZONE
59W
DAYLIGHT ZONE
45W
DAYLIGHT ZONE
50W
DAYLIGHT ZONE
100W
DAYLIGHT ZONE
50W
DAYLIGHT ZONE
50W
DAYLIGHT ZONE
50W
T2
RP2B-13
T2
RP2B-13
LP2B- 5
LP1B-75
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/8" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
7
:
4
8
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
LIGHTING PLAN -
UPPER LEVEL -
NORTH
E113
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
1/8" = 1'-0"1 UPPER LEVEL LIGHTING PLAN - NORTH
GENERAL NOTES
A ALL FIXTURES WITH HATCHING AND/OR DESIGNATED AS 'EM' SHALL BE
PROVIDED WITH INTEGRAL BATTERY BACKUP. BATTERY SHALL ENGAGE ONLY
AFTER COMPLETE LOSS OF POWER TO THE CIRCUIT.
B CIRCUIT ALL EMERGENCY LIGHTING AND EXIT SIGNS TO NEAREST LINE
VOLTAGE CIRCUIT, AHEAD OF ALL SWITCH LEGS.
UNLESS OTHERWISE NOTED, ALL CIRCUIT NUMBER INDICATED ON THIS SHEET
SHALL REFER TO CIRCUIT ORIGINATING IN PANELBOARDS OR RELAY PANELS
BASED ON THE FOLLOWING CONVENTION, (THIS SHEET ONLY):
TBD-# = CIRCUIT TO 'TBD'
C
REFER TO LIGHTING CONTROLS SCHEDULES AND DIAGRAMS, SHEET E402 & E403,
FOR MORE INFORMATION.
D
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 SPEED CONTROL FOR FANS IN LOCATION INDICATED. ALL FANS TO BE
CONTROLLED SIMULTANEOUSLY. SPEED WALL CONTROLLER SPECIFICATION
HAS BEEN PROVIDED AS PART OF THE LIGHTING FIXTURE SPECIFICATION,
REFER THE LIGHTING FIXTURE SCHEDULE FOR ADDITIONAL INFORMATION.
3
OSC
OS
S
OSC
3
3
3
K K
K
K
OSC
3
3
D
OSC
K
K
OSC
OSC
OSC
OSC
OSC
OSC
OSC
OSC
VSS
VS
S
OSC
OSC OSC
OSC
OSC
OSC
OSCOSC
OSC
VS
S
VS S
OSC
OSC
D
D
D
D
RC
RC
PC
PC
OSC
OSC
OSC
OSC
K
K
WS6
WS
7
RC
PC
PC
E14
EB
EC
ED
EE
EF
2
Q
9
10
10
EH
1
L
P
M
3 4 6 7
A4
A5
8
M.6
AH
N
7.96.4
NJ
5
EW3EM
EW3EM
EW3EM
RP2A-12
EW2
RP2A-11EW3EM
RP2A-12
EW3EM
RP2A-12
KID WATCH
288
INDOOR PLAY
205
OFFICE
206
KIDS T
207
JAN
229
M. TOILETS
233
W. SHOWERS
222
W. TOILETS
223
ACR3
216CHG
215
ACR2
214
FAM CHANGING
212
ACR1
213
PARTY
211
LOBBY
202 VESTIBULE
201
CIRC
259
W. LOCKERS
221
GUARDS
258
POOL OFFICE
256
GUARD CHG
257POOL STORAGE
255
POOL MECH
253
ELEC
254
EXIST CHEM
A115
EXIST POOL EQUIP
A114
EXIST POOL MECH
A112 EXIST LAUNDRY
A111
EXIST ELEC
A113
FOYER
A101
MECHANICAL
A102
M. SHOWERS
232
POOL STORAGE
A108
EXIST NATATORIUM
A110
EXIST POOL DECK
A109
W. TEAM LOCKERS
A106
M. TEAM LOCKER
A107
ACTIVITY POOL
001
ISLAND
265
ALT WATER SLIDE
002
M. LOCKERS
231
R1 R1
R1
R1D3
D1
D1
W1
W4
RP2A-10
W4
RP2A-10
W4
RP2A-10
F3
bR2
bR2
bR2bR2
bR2
bR2
aP4
aP4
aP4
aP4
aP4
aP4
aP4
aP4
aP4
aP4
R6R8
R5
R3
R4
R7
R4
R6
R5
F1
F1 F1
W4
RP2A-10
W4
RP2A-10
W4
RP2A-10
D3
D3D3D3
H2
b
H2EM
RP2A-2
H2
RP2A-2
H2
RP2A-2
H2
RP2A-2
H2EM
RP2A-2
H2
RP2A-2
H2
RP2A-1
H2
RP2A-1
H2
RP2A-1
H2EM
RP2A-1
H2
RP2A-1
H2
RP2A-1H2
a
H2
b
H2EM
RP2A-3
H2
RP2A-3
H2
RP2A-3
H2
a
H2
RP2A-2
H2EM
RP2A-2
H2
RP2A-2
H2
RP2A-2
R14 R12
R13EMR13
R14R12
R13R13EM
R13EM
R12R14
R13
R13EM
R11
R12
R13EM
R11
R13EM
R13EM
R11
R11
R11
R2
RP2B-2
R2
RP2B-2
X1
X1
X1
X1
D3
X1
X1
RG10
RG6
RG4
D1
D1
R1
D1EM
X1
D1
D1
D1EM
D1EM
D1
D1EM
D1
X1
D3
D3
D3
D3
D3
D3
D3
D3
D1
D1EM
D1
RG87RG15
R12
R12EM
RG6 RG6
D3 D3
D1
D1EMD1
D3D1
D1EM
RG15
D1
D1EM
D1 D1
D1 D1EM
1
1 1
1
1
1
1
P7
RP2B-11
P7
RP2B-11
P7
RP2B-11
P1
RP2B-2
19'-6"
P1
RP2B-2
22'-0"
P1
RP2B-2
22'-0"
P1
RP2B-2
22'-0"
P1
RP2B-2
22'-0"
P1EM
RP2B-2
22'-0"
P1EM
RP2B-2
21'-0"
P1
RP2B-2
21'-0"
P1
RP2B-2
21'-0"P1
RP2B-2
21'-0"
P1EM
RP2B-2
19'-6"
P1
RP2B-2
19'-6"
P1
RP2B-2
19'-6"
P1
RP2B-2
22'-0"
P1
RP2B-2
22'-0"
D1
RP2B-2
D1
RP2B-2
D1
RP2B-2
D1EM
RP2B-2
D1
RP2B-2
D1
RP2B-2
R12EM
R14
R12EMR11R11R10
R12
R11
R13EM
R11
R13
R10
R11
R10
R11
R12
VESTIBULE
A104
EXIST POOL DECK
A109
M. LOCKERS 2
A103
RG12
D1EM
D1
D1EM
D1
D1EM
D1EMD3
D3
D3
D3
D1EM
D1 D1EM D1 D1EM D1
D3D3
D3D3
R15R14R13EM
R12
R12 R11 R10
R13EM
R11R11
RG8
RG14
F2 F2
F2
F2
P1
RP2A-10
P1EM
RP2A-10
P1
RP2A-10
X1
X1D7EM
RP2A-10D7
RP2A-10
D7
RP2A-10
X1
F1
F3
F3
F3
R1 R1
F1 F1
W1
D1
W2 W2 W2
W2
W2
W2
W2
W2
W2
W2
RG15
W2
W2
W2
R12
R14
R12EM
R16
W2
D3
D1EM
W1
W1
D1EM
D3
D1
D1
D1EM
D3
W1
D1
D1 D1
C1
Y1
Y1
D1
H2
RP2A-2
H2
RP2A-1
H2EM
RP2A-1
D7
RP2A-2
D7
RP2A-2
HL2B- 13
a
HL2B- 13
b
HL2B- 13
a
HL2B- 13
b
a,b
RCD2
RCD1
VS1
(TYP.)
LVD1
(TYP.)
LVKS
(TYP.)
VSC1
VSC3
OSC3
OSC2
PC1
OSC3
OSC2
OSC2
OSC2
OSC2
OSC2
OSC2
OSC2
OSC2
OSC2
VSC2
OSC2
OSC2
OSC2
OSC3
VSC2
VSC1
D1
RP2B-2
D1
RP2B-2
D1
RP2B-2
HL2B- 13
LP2A- 35
HL2B- 18
LP2A- 35
LP2A- 35LP2A- 77
LP2A- 77
LP2A- 77
LP2A- 77 LP2A- 77
X1
X1
X1
a,b
RCD2
HL2B- 17
D1
EW2EM
RP2A-11
EW2
RP2A-11
EW3EM
DAYLIGHT ZONE
356W
DAYLIGHT ZONE
356W
DAYLIGHT ZONE
31W
DAYLIGHT ZONE
45W
DAYLIGHT ZONE
30W
Y1
D1
D1
D1
D1
D1
D1
D1
D1
D1
D1 D1 D1
D1 D1 D1
D1 D1 D1 D1
D1D1
EW3EM
2
2
LVKS
LP2A- 79
LP2A- 79
HL2B- 18HL2B- 18HL2B- 18
HL2B- 18
HL2B- 18
LP2A- 77
F3 F3
F3F3F3F3F3
2
3
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/8" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
8
:
5
4
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
LIGHTING PLAN -
UPPER LEVEL -
SOUTH
E114
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
1/8" = 1'-0"1 UPPER LEVEL LIGHTING PLAN - SOUTH
GENERAL NOTES
A ALL FIXTURES WITH HATCHING AND/OR DESIGNATED AS 'EM' SHALL BE
PROVIDED WITH INTEGRAL BATTERY BACKUP. BATTERY SHALL ENGAGE ONLY
AFTER COMPLETE LOSS OF POWER TO THE CIRCUIT.
B CIRCUIT ALL EMERGENCY LIGHTING AND EXIT SIGNS TO NEAREST LINE
VOLTAGE CIRCUIT, AHEAD OF ALL SWITCH LEGS.
UNLESS OTHERWISE NOTED, ALL CIRCUIT NUMBER INDICATED ON THIS SHEET
SHALL REFER TO CIRCUIT ORIGINATING IN PANELBOARDS OR RELAY PANELS
BASED ON THE FOLLOWING CONVENTION, (THIS SHEET ONLY):
TBD-# = CIRCUIT TO 'TBD'
C
REFER TO LIGHTING CONTROLS SCHEDULES AND DIAGRAMS, SHEET E402 & E403,
FOR MORE INFORMATION.
D
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 NO NEW WORK IN THIS AREA. EXISTING LIGHTING AND CONTROLS TO
REMAIN.
2 EXISTING LIGHT TO BE REPLACED WITH NEW FIXTURE TYPE INDICATED,
UTILIZE EXISTING WIRING AND CONTROLS.
3 LIGHTING ROOM CONTROLLER TO BE NETWORKED TO CENTRAL LIGHTING
CONTROL SYSTEM RELAY PANEL TO ALLOW ALL CONTROLLER
RELAYS/ZONES TO BE CONTROLLED WITH NATATORIUM LIGHTING (RELAY
RP1A-3) VIA WALLSTATION CONTROLS AND AUTOMATIC TIME-CLOCK.
POINT
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
F17
F18
F19
F21
F22
F23
F24
F25
F26
F27
F28
F29
F30
F31
F32
F33
F34
F35
F36
F37
F38
F39
F40
LOCATION
DESCRIPTION
UTILITY XFMR
MSD
MDC
(E)PEU
(E)H1
(E)TL1 PRI
(E)TL1 SEC
(E)L1
(E)H2
(E)TL2 PRI
(E)TL2 SEC
(E)L2
HA2A
TAA PRI
TAA SEC
LA2A
TPA PRI
TPA SEC
LP2A
HM2A
HM2B
HL2B
T2B PRI
T2B SEC
LP2B
TBT PRI
TBT SEC
LT2B
RTU 1
RTU 2
RTU 3
ELEV 1
HM1B
HL1B
T1B PRI
T1B SEC
LP1B
T1K PRI
T1K SEC
LK1B
LENGTH (L)
(ft)
130
15
170
85
5
0
5
85
5
0
5
5
10
0
18
10
0
22
20
260
250
15
0
5
28
0
10
180
160
165
225
285
300
10
0
5
20
0
5
VOLTAGE
(EL-L)
480
480
480
480
480
208
208
480
480
208
208
480
480
208
208
480
208
208
480
480
480
480
208
208
480
208
208
480
480
480
480
480
480
480
208
208
480
208
208
VOLTAGE
(EL-N)
--
277
277
277
277
277
120
120
277
277
120
120
277
277
120
120
277
120
120
277
277
277
277
120
120
277
120
120
277
277
277
277
277
277
277
120
120
277
120
120
PHASE
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
WIRE
SIZE
500
500
2X
2X
6
1
1
1
6
1
1
3X
4
1X
1X
1
250
250
3X
4X
3X
2X
3X
3X
4
1X
1X
1X
2
2X
1X
4X
3X
2X
3X
3X
4
1X
1X
CONDUCTOR
MATERIAL
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
COPPER
CONDUCTOR
TYPE
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
THREE SINGLE CONDUCTORS
CONDUIT
MATERIAL
NONMAGNETIC
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
STEEL
VOLTAGE
CLASS
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
600V
C
VALUE
--
26706
22185
10755
10755
2425
7292
7292
7292
2425
7292
7292
12843
3806
8924
8924
7292
16483
16483
12843
15082
12843
10755
12843
12843
3806
8924
8924
8924
5906
10755
8924
15082
12843
10755
12843
12843
3806
8924
8924
# OF PARALLEL
RUNS
--
7
7
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
2
1
2
2
1
1
1
1
1
1
1
1
2
1
2
2
1
1
1
Isc AVAILABLE
UPSTREAM
--
45,200
40,596
40,029
40,029
18,692
16,410
16,410
40,029
14,916
13,426
13,426
40,029
38,935
28,438
28,438
40,029
33,411
33,411
40,029
40,029
40,029
11,470
10,844
10,844
11,470
8,793
8,793
40,029
40,029
40,029
40,029
40,029
40,029
10,733
10,360
10,360
10,733
8,918
8,918
f
L-L
--
0.11
0.01
2.28
1.14
0.14
0.00
0.09
1.68
0.11
0.00
0.08
0.03
0.37
0.00
0.48
0.20
0.00
0.37
0.11
2.49
1.41
0.06
0.00
0.02
0.30
0.00
0.08
2.91
3.91
2.22
3.64
2.73
1.69
0.04
0.00
0.02
0.20
0.00
0.04
M
L-L
--
0.90
0.99
0.30
0.47
0.88
1.00
0.91
0.37
0.90
1.00
0.93
0.97
0.73
1.00
0.68
0.83
1.00
0.73
0.90
0.29
0.42
0.95
1.00
0.98
0.77
1.00
0.92
0.26
0.20
0.31
0.22
0.27
0.37
0.97
1.00
0.98
0.83
1.00
0.96
Isc
AT EQUIP
(I3ph) OR (IL-L)
45,200
40,596
40,029
12,193
18,692
16,410
16,410
15,004
14,916
13,426
13,426
12,470
38,935
28,438
28,438
19,245
33,411
33,411
24,364
35,983
11,470
16,639
10,844
10,844
10,656
8,793
8,793
8,126
10,229
8,148
12,447
8,624
10,733
14,898
10,360
10,360
10,189
8,918
8,918
8,562
POINT
F0
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10
F11
F12
F13
F14
F15
F16
F17
F18
F19
F21
F22
F23
F24
F25
F26
F27
F28
F29
F30
F31
F32
F33
F34
F35
F36
F37
F38
F39
F40
FAULT CURRENT CALCULATION SCHEDULE
T
X0 X1
2000N
TO UTILITY
PLATTE RIVER POWER AUTHORITY
(PRPA) PAD MOUNTED UTILITY
2000 KVA TRANSFORMER (ACTUAL
SIZE BASED UPON UTILITY
DISCRESION)
277/480V, 3 PH, 4W
MAIN DISTRIBUTION CENTER (MDC)
2000A, 277/480V, 3PH, 4-WIRE, NEMA 1, 65KAIC RATED
M
GFP
2000A/3P
LSIG
RE:2/E400
N
G
PRPA UTILITY NEMA 3R
CONNECTION CT
CABINET & MAIN SERVICE
DISCONNECT (MSD)
2000NG
SPD
10
0
A
/
3
P
PANEL
'HM2B'
225NG
X21
T
XFMR
XFMR
PANEL
'LP2B'
'T2B'
112.5KVA
X25
X23
X24
22
5
A
/
3
P
X2
(E)
PANEL
'H1'
17
5
A
/
3
P
UPPER LEVEL
(E)
PEU
RTU
1
12
5
A
/
3
P
MECH
RTU
2
90
A
/
3
P
MECH
25
0
A
/
3
P
SP
A
C
E
10
0
A
/
3
P
SP
A
C
E
EX
T
E
R
I
O
R
RE
C
R
E
A
T
I
O
N
B
U
I
L
D
I
N
G
IN
T
E
R
I
O
R
T
XFMR
XFMR
PANEL
'LA2A'
'TAA'
30KVA
X15
X13
X14
22
5
A
/
3
P
SP
A
R
E
1
GRADE
PRPA ENERGY METER
T
(E)
(E)
(E)
PANEL
'L1'
'TL1'
30KVA
X7
X5
X6
(E)
PANEL
'H2'
10
0
A
/
3
P
T
(E)
(E)
(E)
PANEL
'L2'
'TL2'
30KVA
X11
X9
X10
17
5
A
/
3
P
175NG 175NG 100NG
PANEL
'HA2A'
225NG
X12
22
5
A
/
3
P
PANEL
'HM2A'
225NG
X19
22
5
A
/
3
P
PANEL
'HL2B'
400NG
X22
22
5
A
/
3
P
PANEL
'HM1B'
225NG
T
XFMR
XFMR
PANEL
'LP1B'
'T1B'
112.5KVA
X37
X35
X36
40
0
A
/
3
P
10
0
A
/
3
P
PANEL
'HL1B'
100NG
T
XFMR
XFMR
PANEL
'LK1B'
'T1K'
30KVA
X40
X38
X39
LOWER LEVEL
T
XFMR
XFMR
PANEL
'LP2A'
12
5
A
/
3
P
'TPA'
75KVA
X18
X16
X17
1" CONDUIT
T
XFMR
XFMR
PANEL
'LT2B'
'TBT'
30KVA
X28
X26
X27
2
2
RTU
3
17
5
A
/
3
P
MECH
X3
X4 X8
X29 X30 X31
X33 X34
10
0
A
/
3
25
0
A
/
3
P
SP
A
C
E
10
0
A
/
3
P
SP
A
C
E
ELEV
1
MECH
X32
5#1, 2"C
FEEDER SCHEDULE
KEY/
AMPS
SERVICE ENTRANCE FEEDERS
400N
600N
800N
1000N
1200N
1600N
2000N
2500N
3000N
3500N
4000N
EQUIPMENT FEEDERS
20NG
30NG
40NG
50NG
60NG
70NG
80NG
90NG
100NG
110NG
125NG
150NG
175NG
200NG
225NG
250NG
300NG
350NG
400NG
450NG
500NG
600NG
700NG
800NG
1000NG
1200NG
1600NG
2000NG
GROUNDING CONDUCTORS
G8
G6
G4
G2
G10
G20
G30
NOTES:
1.
2.
3.
FEEDER CONDUIT
AND CONDUCTORS
2[4#3/0, 2"C]
2[4#350, 3"C]
2[4#500, 3-1/2"C]
3[4#400, 3-1/2"C]
4[4#350, 3"C]
5[4#400, 3-1/2"C]
6[4#400, 3-1/2"C]
7[4#500, 3-1/2"C]
8[4#500, 3-1/2"C]
10[4#500, 3-1/2"C]
11[4#500, 3-1/2"C]
4#12, #12G, 3/4"C
4#10, 1#10G, 3/4"C
4#8, 1#10G, 1"C
4#6, 1#10G, 1-1/4"C
4#4, 1#10G, 1-1/4"C
4#4, 1#8G, 1-1/4"C
4#3, 1#8G, 1-1/4"C
4#2, 1#8G, 1-1/2"C
4#1, 1#8G, 1-1/2"C
4#1, 1#6G, 2"C
4#1/0, 1#6G, 2"C
4#1/0, 1#6G, 2"C
4#2/0, 1#6G, 2"C
4#3/0, 1#6G, 2-1/2"C
4#4/0, 1#4G, 2-1/2"C
4#250, 1#4G, 3"C
4#350, 1#4G, 3"C
4#500, 1#3G, 3-1/2"C
2[4#3/0, 1#3G, 2-1/2"C]
2[4#4/0, 1#2G, 2-1/2"C]
2[4#250, 1#2G, 3"C]
2[4#350, 1#1G, 3"C]
2[4#500, 1#1/0G, 3-1/2"C]
2[4#500, 1#1/0G, 3-1/2"C]
3[4#400, 1#2/0G, 3-1/2"C]
4[4#350, 1#3/0G, 3"C]
5[4#400, 1#4/0G, 3-1/2"C]
6[4#400, 1#250G, 3-1/2"C]
1#8, 3/4" C
1#6, 3/4" C
1#4, 3/4" C
1#2, 3/4" C
1-1/0, 3/4" C
1-2/0, 3/4" C
1-3/0, 3/4" C
FEEDER FOR SECONDARY OF SEPARATELY DERIVED
SYSTEM (SDS). GROUND SIZE PER NEC 250.66.
ALL CONDUCTORS ARE SINGLE CONDUCTOR COPPER THWN
UNLESS NOTED OTHERWISE. AMPACITY BASED ON
NEC TABLE 310.16.
ALL CONDUITS ARE EMT UNLESS NOTED OTHERWISE, FILL RATIOS
BASED ON NEC ANNEX C TABLE C1.
KEY/
AMPS
SDS XFMR FEEDERS (NOTE 1)
30S
50S
100S
150S
250S
400S
500S
800S
1000S
1600S
2500S
20G
30G
40G
50G
60G
70G
80G
90G
100G
110G
125G
150G
175G
200G
225G
250G
300G
350G
400G
450G
500G
600G
700G
800G
1000G
1200G
1600G
2000G
ABBREVIATIONS
MECH
XFMR
FEEDER CONDUIT
AND CONDUCTORS
4#10, 1#8G, 3/4"C
4#6, 1#8G, 1-1/4"C
4#1, 1#6G, 1-1/2"C
4#1/0, 1#6G, 2"C
4#250, 1#2G, 3"C
2[4#3/0, 1#2G, 2"C]
2[4#250, 1#1/0G, 3"C]
2[4#500, 1#2/0G, 3-1/2"C]
3[4#400, 1#4/0G, 3-1/2"C]
5[4#400, 1#350G, 3-1/2"C]
7[4#500, 1#500G, 3-1/2"C]
3#12, #12G, 3/4"C
3#10, 1#10G, 3/4"C
3#8, 1#10G, 1"C
3#6, 1#10G, 1"C
3#4, 1#10G, 1"C
3#4, 1#8G, 1-1/4"C
3#3, 1#8G, 1-1/4"C
3#2, 1#8G, 1-1/4"C
3#1, 1#8G, 1-1/2"C
3#1, 1#6G, 1-1/2"C
3#1/0, 1#6G, 1-1/2"C
3#1/0, 1#6G, 1-1/2"C
3#2/0, 1#6G, 2"C
3#3/0, 1#6G, 2"C
3#4/0, 1#4G, 2"C
3#250, 1#4G, 2-1/2"C
3#350, 1#4G, 2-1/2"C
3#500, 1#3G, 3"C
2[3#3/0, 1#3G, 2"C]
2[3#4/0, 1#2G, 2"C]
2[3#250, 1#2G, 2-1/2"C]
2[3#350, 1#1G, 2-1/2"C]
2[3#500, 1#1/0G, 3"C]
2[3#500, 1#1/0G, 3"C]
3[3#400, 1#2/0G, 3"C]
4[3#350, 1#3/0G, 3"C]
5[3#400, 1#4/0G, 3"C]
6[3#400, 1#250G, 3"C]
SEE MECH SCHEDULE
SEE XFMR SCHEDULE
PANEL
HL1A
M = MECHANICAL
L = LIGHTING
P = POWER
T = TELECOM
A = AQUATICS
K = KITCHEN
H = 480/277V
L = 208/120V
A = RISER A
B = RISER B
# = FLOOR SERVED
1 = LOWER LEVEL
2 = UPPER LEVEL
KVA
RATING
3
6
9
15
30
45
75
112.5
150
225
300
500
750
PRIMARY
FLA
3.6
7.2
10.8
18.1
36.1
54.2
90.3
135.4
180.5
270.8
361.0
601.7
902.5
SECONDARY
FLA
8.3
16.7
25.0
41.7
83.3
125.0
208.3
312.5
416.7
625.0
833.3
1388.9
2083.3
PRIMARY
PROTECTION
15A/3P
15A/3P
15A/3P
25A/3P
45A/3P
70A/3P
125A/3P
175A/3P
225A/3P
350A/3P
450A/3P
750A/3P
1200A/3P
PRIMARY
FEEDER
3#12, 1#12G, 3/4"C
3#12, 1#12G, 3/4"C
3#12, 1#12G, 3/4"C
3#10, 1#10G, 3/4"C
3#6, 1#10G, 1"C
3#4, 1#8G, 1-1/4"C
3#1, 1#6G, 1-1/2"C
3#2/0, 1#6G, 2"C
3#4/0, 1#4G, 2"C
3#500MCM, 1#3G, 3"C
2[3#4/0, 1#2G, 2"C]
2[3#500MCM, 1#1/0G, 3"C]
3[3#350MCM, 1#3/0G, 3"C]
SECONDARY
PROTECTION
15A/3P
20A/3P
30A/3P
50A/3P
100A/3P
150A/3P
250A/3P
400A/3P
500A/3P
800A/3P
1000A/3P
1600A/3P
2500A/3P
SECONDARY
FEEDER
4#12, 1#8G, 3/4"C
4#12, 1#8G, 3/4"C
4#10, 1#8G, 3/4"C
4#6, 1#8G, 1-1/4"C
4#1, 1#6G, 1-1/2"C
4#1/0, 1#6G, 2"C
4#250MCM, 1#2G, 3"C
2[4#3/0, 1#2G, 2-1/2"C]
2[4#250MCM, 1#1/0G, 3"C]
2[4#500MCM, 1#2/0G, 3-1/2"C]
3[4#400MCM, 1#3/0G, 3-1/2"C]
5[4#400MCM, 1#3/0G, 3-1/2"C]
7[4#500MCM, 1#3/0G, 3-1/2"C]
DERIVED
GROUND CONDUCTOR
1#8, 3/4"C
1#8, 3/4"C
1#8, 3/4"C
1#8, 3/4"C
1#8, 3/4"C
1#6, 3/4"C
1#2G, 3/4"C
1#1/0G, 3/4"C
1#1/0G, 3/4"C
1#2/0G, 3/4"C
1#3/0G, 3/4"
1#3/0G, 3/4"
1#3/0G, 3/4"
APPROX. DIMENSIONS
HIGH
15
15
20
28
33
33
37
42
46
48
52
60
74
WIDE
15
15
20
23
24
30
32
36
36
48
48
56
56
DEEP
11
11
15
17
18
20
24
24
24
30
31
36
41
APPROX.
WEIGHT
140LBS
145LBS
245LBS
285LBS
369LBS
590LBS
750LBS
1050LBS
1350LBS
2000LBS
2350LBS
3450LBS
3950LBS
TRANSFORMER SCHEDULE
GROUNDING ELECTRODE SYSTEMS NOTES
1 METAL UNDERGROUND WATER PIPE - MAKE CONNECTION TO METAL
UNDERGROUND WATER PIPE INDIRECT CONTRACT WITH THE EARTH FOR 10' OR
AND ELECTRICALLY CONTINUOUS TO THE POINTS OF CONNECTION TO THE
GROUNDING ELECTRODE CONDUCTOR AND BONDING CONDUCTORS.
CONNECTION POINT TO BE AT A MAXIMUM OF 5' OF THE POINT OF ENTRANCE ON
THE INTERIOR OF THE BUILDING.
2 BUILDING STEEL - THE METAL FRAME OF THE BUILDING OR STRUCTURE, WHERE
ANY OF THE FOLLOWING METHODS ARE USED TO MAKE AN EARTH CONNECTION:
A. AT LEAST ONE STRUCTURAL METAL MEMBER THAT IS IN
DIRECT CONTACT WITH THE EARTH FOR 10' OR MORE, WITH
OR WITHOUT CONCRETE ENCASEMENT.
B. HOLD-DOWN BOLTS SECURING THE STRUCTURAL STEEL COLUMN THAT
ARE CONNECTED TO A CONCRETE ENCASED ELECTRODE THAT COMPLIES
WITH 250.52(A)(3) AND IS LOCATED IN THE SUPPORT FOOTING OR
FOUNDATION. THE HOLD-DOWN BOLTS SHALL BE CONNECTED TO THE
CONCRETE-ENCASED ELECTRODE BY WELDING, EXOTHERMIC WELDING,
THE USUAL STEEL TIE WIRES, OR OTHER APPROVED MEANS.
3 UFER GROUND (CONCRETE-ENCASED ELECTRODE) - AN ELECTRODE ENCASED BY
AT LEAST 2" OF CONCRETE, LOCATED WITHIN AND NEAR THE BOTTOM OF A
CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT WITH EARTH,
CONSISTING OF AT LEAST 20' OF ONE OR MORE BARE OR ZINC GALVANIZED OR
OTHER ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS
OF NOT LESS THAN 1/2" IN DIAMETER, OR CONSISTING OF AT LEAST 20' OF BARE
COPPER CONDUCTOR NOT SMALLER THAN NO. 4 AWG. REINFORCING BARS SHALL
BE PERMITTED TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR
OTHER EFFECTIVE MEANS.
4 GROUND ROD - ROD IS TO BE 8FT IN LENGTH AND SHALL BE MADE OF IRON
OR STEEL AT LEAST 5/8" DIAMETER. INSTALLATION METHODS FOR GROUND
ROD SHALL BE IN COMPLIANCE WITH THE NEC SUCH THAT AT LEAST 8' OF
LENGTH IS IN CONTACT WITH THE EARTH.
GENERAL GROUNDING NOTES
1 ALL CABLES TO BE TERMINATED ONTO BUS BAR WITH TWO HOLE
COMPRESSION LUGS AND ATTACHED TO BUS BAR WITH TAB
COMPRESSION BELLEVILLE WASHERS AND TORK BOLT ASSEMBLY.
2 ALL GROUND CONNECTORS SHALL BE STRANDED.
3 ALL BUS BARS SHALL BE ATTACHED TO SURFACE WITH NON-
CONDUCTIVE STAND-OFFS.
4 GROUND BUS BAR AND GROUNDING SYSTEM SHALL BE UL
LISTED AND COMPLY WITH MANUFACTURERS INSTALLATION
INSTRUCTIONS.
PRINCIPAL GROUND POINT (PGP)
CU
GROUND BAR
INTERNAL TO 'MSD'
TELECOMMUNICATIONS
GROUND BAR ('TMGB-1')
IN LAN #276
XFMR INTERNAL GROUND BAR(S)
TYPICAL ALL TRANSFORMERS
INTERSYSTEM'S
BONDING
BRIDGE PER NEC
250.94
EXTERNAL TO 'MDC'
G20
G20
XFMR
G4G30
CWP
UFER
G30
BLDG
STEEL
G6
GND
ROD
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
NTS
10
/
3
1
/
2
0
1
6
1
1
:
2
5
:
2
8
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
ONE-LINE DIAGRAM
E400
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NTS1ELECTRICAL ONE-LINE DIAGRAM
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
1 TRANSIENT VOLTAGE SURGE SUPPRESSION UNIT IS TO BE
'LEA INTERNATIONAL' #LSP300-277/480-3Y. REFER TO
MANUFACTURER'S SPECIFICATIONS FOR EXACT
INSTALLATION INSTRUCTIONS. DO NOT EXCEED
MANUFACTURER'S RECOMMENDED LEAD LENGTHS.
2 TRANSFORMER LOCATED REMOTELY FROM PRIMARY
DISCONNECTING MEANS. PROVIDE LOCKABLE PRIMARY
OVERCURRENT PROTECTION DEVICE AND FIELD MARK
LOCATION ON TRANSFORMER PER NEC 450.14. REFER TO
UPSTREAM PANEL SCHEDULE FOR MORE INFORMATION.
NTS3PANELBOARD NAMING CONVENTION
NTS5GROUNDING DIAGRAM
(*) EXISTING LOADS TAKEN FROM PREVIOUS ENGINEERING DOCUMENTS
DATED 11-2007.
THEREFORE THE 2000A SERVICE IS JUSTIFIED.
Total Est. Demand:1222 A
Total Conn.:1203 A
Total Est. Demand:1016 kVA
Total Conn. Load:1000 kVA
@ 480/277V, 3PH 1203 A
TOTAL NEW LOAD 999933 VA
FUTURE AQUATICS EQUIP 40 kVA 48 A
ELEVATOR 32 kVA 38 A
RTU-3 152 kVA 183 A
RTU-2 58 kVA 69 A
RTU-1 76 kVA 92 A
'HL1B' 7 kVA 9 A
'HM1B' 72 kVA 86 A
'HL2B' 23 kVA 27 A
'HM2B' 92 kVA 111 A
'HM2A' 63 kVA 76 A
'LP2A' (VIA 'TPA') 75 kVA 91 A
'HA2A' 120 kVA 145 A
(E) 'H2' (*) 35 kVA 42 A
(E) 'H1' (*) 97 kVA 116 A
(E) PEU (*) 57 kVA 68 A
LOAD DESCRIPTION Load LOAD (AMPS)
MAIN DISTIRUBTION CENTER (2500A, 480/277V, 3PH, 4W)
LOAD SUMMARY MDC
2ND FLOOR
LAN #276
FACP
SECURITY
FACP
ELEV
1
11
KEYNOTE LEGEND
1. NEW (1) 3" PVC CONDUIT ROUTED 30" BELOW GRADE FOR CONNECTION
TO SITE TELEPHONE SERVICE POINT. ELECTRICAL CONTRACTOR
SHALL VERIFY CONDUIT SIZING AND QUANTITY WITH SERVICE
PROVIDER PRIOR TO INSTALLATION.
2. NEW (1) 2" PVC CONDUIT ROUTED 30" BELOW GRADE FOR FUTURE
CONNECTION TO SITE FIBER OPTIC SERVICE POINT. ELECTRICAL
CONTRACTOR SHALL VERIFY CONDUIT SIZING AND QUANTITY WITH
SERVICE PROVIDER PRIOR TO INSTALLATION.
3. NEW (1) 3" PVC CONDUIT ROUTED 30" BELOW GRADE FOR CONNECTION
TO SITE CATV SERVICE POINT. ELECTRICAL CONTRACTOR SHALL
VERIFY CONDUIT SIZING AND QUANTITY WITH SERVICE PROVIDER
PRIOR TO INSTALLATION.
4. MAIN TELEPHONE TERMINAL BOARD 'MTTB' SHALL CONSIST OF 3/4
INCH, FIRE-RETARDANT TREATED PLYWOOD INSTALLED FLOOR TO
CEILING IN ROOM, FOR LENGTHS AS INDICATED ON THE PLAN
DRAWINGS. ALL RECEPTACLE DEVICES SHOWN IN BACKBOARD ON
PLANS SHALL BE FLUSH MOUNT, UON.
5. NEW TYPICAL WORK AREA COMMUNICATIONS OUTLET FOR
STRUCTURED CABLE TERMINATIONS. PROVIDE 2-INCH DEEP, 2-GANG
BOX WITH 1-GANG PLASTER RING. PROVIDE 1" CONDUIT TO
ACCESSIBLE CEILING AND BUSH END. RECEPTACLE FACEPLATE, JACK,
CABLING, AND TERMINATIONS BY OTHERS.
6. NEW TYPICAL WORK AREA OUTLET FOR CABLE TV TERMINATION.
PROVIDE 2-INCH DEEP, 2-GANG BOX WITH 1-GANG PLASTER RING.
PROVIDE 1-1/4" CONDUIT TO ACCESSIBLE CEILING AND BUSH END.
CATV RECEPTACLE FACEPLATE, JACK, CABLING, AND TERMINATIONS
BY OTHERS.
7. PROVIDE GREEN COPPER GROUNDING CONDUCTOR (TYPICAL)
BETWEEN GROUNDING BUSSES AS INDICATED ON GROUNDING DETAIL
5/E400.
8. ROUTE (1) 1/2" CONDUIT FOR FIRE ALARM CONTROL PANEL
COMMUNICATIONS CABLING RACEWAY.
9. ROUTE (1) 1/2" CONDUIT FOR SECURITY CONTROL PANEL
COMMUNICATIONS CABLING RACEWAY.
10. PROVIDE (1) 3/4"C WITH PULL WIRE TO ELEVATOR CONTROL PANEL FOR
ELEVATOR COMMUNICATIONS CABLING RACEWAY. CABLING SHALL BE
FURNISHED BY OTHERS.
11. INTERSYSTEM'S GROUNDING BRIDGE (IGB) AS REQUIRED BY NEC
250.94. LOCATED EXTERNAL TO THE MAIN SERVICE GROUND
EQUIPMENT. REFER TO 5/E400 FOR GROUNDING ONE-LINE DIAGRAM.
12. TELECOMMUNICATIONS MAIN GROUNDING BAR 'TMGB'.
KEY VALUE KEYNOTE TEXT
GENERAL NOTES
12
A. PROVIDE EMT FOR ALL CABLING ROUTED THROUGH AREAS WITH EXPOSED STRUCTURAL CEILINGS
AND THROUGH INACCESSIBLE CEILINGS. COORDINATE CONDUIT SIZE REQUIREMENTS WITH CABLE
INSTALLER.
B. ALL EXPOSED CONDUIT SHALL BE CONCEALED TO THE EXTENT POSSIBLE, AND SHALL BE INSTALLED
PARALLEL AND CLOSE TO STRUCTURAL MEMBERS. PAINT CONDUIT TO MATCH ADJACENT FINISHES.
C. PROVIDE PULLCORD FOR ALL CONDUIT INSTALLED FOR CABLE.
D. PROVIDE PULLBOXES AS REQUIRED BY CABLE INSTALLER FOR RUNS EXCEEDING MAXIMUM PULL
DISTANCE, AS IDENTIFIED BY CABLE INSTALLER.
E. PROVIDE SLEEVES AND CONDUIT BETWEEN FLOORS FOR ROUTING OF CABLE. COORDINATE CONDUIT
SIZE WITH CABLE INSTALLER. COORDINATE LOCATION OF RACEWAY WITH ARCHITECT AND CABLE
INSTALLER.
F. ALL CONDUIT AND CABLING IN CRAWL SPACE IS TO BE SUPPORTED BY AND TIGHT TO STRUCTURE
ABOVE. WHERE CONDUIT TRANSITIONS FROM BEING SUPPORTED BY STRUCTURE INTO SOIL, ADD
LOOP AND/OR FLEXIBLE CONDUIT FOR FLEXIBILITY AND TO ALLOW FOR ANTICIPATED SOIL MOVEMENT.
G. REFER TO SPECIFICATIONS FOR FULL CONDUIT REQUIREMENTS. HOWEVER, NOTE THAT ALL
UNDERGROUND CONDUIT BENDS ARE TO BE GALVANIZED RIGID CONDUIT. UNDERGROUND CONDUIT
EXTENDING ABOVE SLAB IS ALSO TO BE GALVANIZED RIGID CONDUIT.
3
1
56
56
10
7
2
8
94
8
TSTS TS
FS FS TSFS FS
MAXIMUM 5'-0"
CONTROL
BY DIV. 26
DUCT DETECTOR
REMOTE TEST
STATION
BY DIV. 26
BY DIV. 26
PANEL
BY DIV. 26
ALARM
FIRE
DAMPERS PRIOR TO BID.
ALL MECHANICAL PLANS
NOTIFY ENGINEER OF ANY
FOR LOCATIONS OF ALL POWERED
RESPONSIBLE FOR REVIEWING
ELECTRICAL CONTRACTOR IS
RELAY BY DIV. 26
NORMALLY CLOSED
WIRING BY DIV. 26
120 V. ELECTRIC DAMPER
TO 120V POWER SUPPLY
BY DIV. 23
SMOKE/FIRE DAMPER
ACTUATOR, BY DIV. 23
DUCT
CEILING
DISCREPANCIES.
S T
S S
FAA
DIALER
POWER
REMOTE
SUPPLY
TELEPHONE
FACP
1. THIS IS A FULLY ADDRESSIBLE VOICE EVACUATION TYPE SYSTEM WITH EACH
DEVICE HAVING A DISTINCT 'ADDRESS'.
2. PROVIDE NON-POWER LIMITING, PLENUM RATED WIRING. INSTALL IN EMT
WHERE WIRING IS ROUTED THROUGH HAZARDOUS LOCATIONS, EXPOSED
STRUCTURAL CEILINGS, INACCESSIBLE CEILINGS, AND BETWEEN AREAS
SEPARATED BY MULTI-STORY ATRIUMS. ALL RACEWAY COMPONENTS
SHALL BE PAINTED RED.
3. PROVIDE DUCT DETECTION FOR ALL AIR-HANDLING EQUIP- MENT
OPERATING WITH A RETURN CAPACITY EXCEEDING 2000CFM, SUPPLY
CAPACITY EXCEEDING 15,000CFM WITH COMMON DUCT SERVING
MULTIPLE FLOORS, AND ADDITION- ALLY AS REQUIRED BY LOCAL CODES.
4. SPRINKLER SYSTEM IS A DESIGN-BUILD CONTRACT. COORD- INATE WITH
SPRINKLER CONTRACTOR FOR QUANTITIES AND LOCATIONS OF ALL
FLOW AND TAMPER SWITCHES, AND FOR LOCATION OF FIRE HORN/LIGHT
AT EXTERIOR OF BLDG. INSTALL WITH 20% SPARE CAPACITY ON ALL
INITIATING AND INDICATING APPLIANCE CIRCUITS.
5. PROVIDE 120V CIRCUIT AND LOW-VOLTAGE FIRE ALARM CONTROL
CIRCUIT TO ALL SMOKE DAMPERS. COORDINATE LOCATIONS WITH
MECHANICAL CONTRACTOR PRIOR TO BID.
6. COORDINATE ALL SEQUENCING OF OPERATIONS WITH LOCAL FIRE
DEPARTMENT.
7. ALL DEVICES INSTALLED IN DAMP, WET OR EXTERIOR LOCATIONS
SHALL BE FURNISHED WITH WP HOUSINGS. ALL DEVICES
INSTALLED IN GYMNASIUMS SHALL BE FURNISHED WITH
MANUFACTURER'S STANDARD WIRE GUARD PROTECTION DEVICES.
8. SYSTEM SHALL TRANSMIT REQUIRED FIRE ALARM SIGNALS TO
CENTRAL MONITORING AGENCY (SELECTED BY OWNER) VIA
DIALER PROVIDED IN FIRE ALARM CONTROL PANEL.
9. PROVIDE SUFFICIENT SPARE CAPACITY FOR FUTURE TENANT
FINISH AREAS. PROVIDE ALL NECESSARY EXPANSION CARDS AND
REMOTE POWER SUPPLIES.
10. THE ELECTICAL CONTRACTOR SHALL INCLUDE IN HIS BID AN
ADDITIONAL 10% SPARE STROBES AND HORN/STROBES,
INCLUDING INSTALLATION, AS MAY BE REQUIRED BY AHJ.
GO INTO ALARM, THE RESPECTIVE ELEVATOR WILL RETURN
DAMPERS WILL OPERATE WHEN THE FOLLOWING CONDITIONS OCCURS.
SUBSEQUENTLY, IF THE THERMAL DETECTOR IN THE ELEVATOR ROOM GOES INTO ALARM,
THE POWER TO THE ELEVATOR CONTROLLER WILL BE DISCONNECTED VIA A SHUNT TRIP
TO THEIR PRIMARY LEVEL OR SECONDARY LEVEL AND LOCK-OUT; THE LEVEL WILL
WHEN THE SMOKE DETECTORS IN THE LOBBIES, ELEVATOR SHAFT OR EQUIPMENT ROOM
DEPEND UPON IF THE ELEVATOR LOBBY DETECTOR SENSES ANY SMOKE AT THE
THE SUPPLY OR RETURN DUCT DETECTOR OF THE RESPECTIVE AIR HANDLING UNIT GOES INTO ALARM.
FIRE/SMOKE DAMPERS SHALL BE CLOSED BY ACTUATION OF A SMOKE DETECTOR INSTALLED IN DUCT
WORK WITHIN 5' OR SPOT-TYPE DETECTOR INSTALLED WITHIN 5', REFER TO PLANS TYPE AND LOCATION.
BUILDING ENTRY
LOCATED AT MAIN
GRAPHIC MAP NEXT TO FAA
INSTALL A FRAMED, MYLAR
SEQUENCE OF OPERATION FOR ELEVATOR RECALL:
SEQUENCE OF OPERATION FOR SMOKE DAMPERS:
CIRCUIT BREAKER.
RESPECTIVE LOBBY.
NOTES:
2.
1.
2.
1.
LOWER LEVEL
ON ALARM CONDITION
TO SECURITY PANEL
TYPICAL
DAMPERS
FOR SMOKE COORDINATE EXACT QUANTITY
OF
ZONES WITH FIRE SPRINKLER
CONTRACTOR
@ OS&Y
WP
AT
FACP
MAIN ZONE
1/2" CONDUIT
TO MTTB
ZONE ZONE
DEDICATED 120V
20A CIRCUIT
UPPER LEVEL
TYPICAL
TO SOUND SYSTEMS
FOR MUTING (PAGING
SYSTEMS OVERRIDE)
120 VOLT
SHUT-DOWN
FOR MECH
GENERAL FIRE ALARM SYSTEM NOTE:
THE FIRE ALARM DEVICES SHOWN ARE FOR GENERAL LAYOUT AND
GUIDELINES ONLY. THE AWARDED FIRE ALARM CONTRACTOR IS TO PROVIDE A
COMPLETE SET OF SHOP DRAWINGS FOR SUBMITTAL AND APPROVAL BY THE
AUTHORITY HAVING JURISDICTION. THESE DOCUMENTS ARE TO INCLUDE THE
FOLLOWING INFORMATION:
1. SHOP DRAWINGS MUST BE PREPARED AND SIGNED BY A MINIMUM OF
A NICET FIRE ALARM LEVEL III CERTIFIED INDIVIDUAL.
2. COMPLETE RISER DIAGRAM SHOWING ALL DEVICES BY FLOOR/AREA
AS CONNECTED TO THE CIRCUIT, DEVICE ADDRESSES, WIRE COLOR
CODING SCHEDULE, WIRE COUNT, WIRE TYPE AND CONDUIT FILL
WITH CALCULATIONS SHOWN.
3. PROVIDE A SEQUENCE OF OPERATION (INPUT/OUTPUT MATRIX) IN
COMPLIANCE WITH THE NFPA 72 ANNEX MATERIAL. THE
INFORMATION PROVIDED IN THE SEQUENCE OF OPERATION MUST BE
SPECIFIC TO THE PROJECT. GENERIC SEQUENCE OF OPERATIONS
WILL NOT BE ACCEPTED.
4. IDENTIFY THE TYPE OF SYSTEM, I.E. CENTRAL, REMOTE,
PROPRIETARY, ETC.
5. IDENTIFY THE TYPE OF AUDIBLE NOTIFICATION: TEMPORAL, STEADY,
CODED, VOICE, ETC.
6. IDENTIFY THE TYPE OF VISUAL NOTIFICATION: PUBLIC OR PRIVATE
MODE.
7. PROVIDE A WIRING LEGEND SPECIFIC TO TYPES USED FOR THE
PROJECT. IDENTIFY IF WIRING IS ENCLOSED IN CONDUIT, OPEN
WIRING, PLENUM WIRING, POWER LIMITED OR NON-POWER LIMITED
8. PROVIDE AN EQUIPMENT LIST WITH MANUFACTURER, PART NUMBER,
BACK BOX AND SYMBOL USED TO IDENTIFY THE COMPONENT. IF
THERE IS INSUFFICIENT SPACE FOR WIRING LEGEND, EQUIPMENT
LIST AND SYMBOL LEGEND ON THE TITLE SHEET, THAN INSERT AN
ADDITIONAL SHEET.
9. COMPLETE RISER DIAGRAM SHOWING ALL DEVICES BY FLOOR/AREA
AS CONNECTED TO THE CIRCUIT, DEVICE ADDRESSES, WIRE COLOR
CODING SCHEDULE, WIRE COUNT, WIRE TYPE AND CONDUIT FILL
WITH CALCULATIONS SHOWN.
10. DETAIL SHEET INCLUDING THE FOLLOWING; CIRCUIT WIRING
DIAGRAM, DEVICE/APPLIANCE MOUNTING HEIGHT PROFILE, TYPICAL
DEVICE AND ANCILLARY DEVICE WIRING, AND THE INTERFACE OF
FIRE SAFETY CONTROL FUNCTIONS.
11. PROVIDE VOLTAGE DROP CALCULATIONS FOR EACH CIRCUIT
SHOWING WIRE SIZE, CIRCUIT LOAD AND VOLTAGE DROP.
12. PROVIDE AUDIO CIRCUIT POWER LOSS CALCULATIONS
13. VOLTAGE DROP CALCULATIONS MUST BE PERFORMED USING THE
OUTPUT CIRCUIT VOLTAGE WHEN THE INPUT VOLTAGE TO THE
CONTROL PANEL IS 85% OF ITS NAME PLATE VOLTAGE. (NFPA 72,
2002 ED., SECTION 4.4.4.1(1))
14. PROVIDE RESISTANCE VALUES WITH SUPPORTING DATA SHEETS OR
PROVIDE NEC VALUES AND REFERENCE.
15. INDICATE METHOD USED AND SHOW ALL FORMULAS/EQUATIONS.
16. PROVIDE STAND-BY BATTERY CALCULATIONS FOR EACH CONTROL
PANEL, SUB PANEL, MONITORING STATION TRANSMITTER, POWER
SUPPLY OR ANY COMPONENT REQUIRING SECONDARY POWER.
17. SHOW LOCATION OF ALL FIRE ALARM INITIATING DEVICES AND
NOTIFICATION APPLIANCES WITH TEMPERATURE, DECIBLE AND
CANDELA RATINGS, WHEN APPLICABLE.
RECALL
FOR ELEVATOR
S S POWER
REMOTE
SUPPLY
TYPICAL
120 VOLT
SHUTDOWN
FOR MECH
RECALL
FOR ELEVATOR
S S
MECH
T/S
ROOF LEVEL
TYPICAL. REFER TO PLANS FOR
EXACT QUANTITY.
S T
TYPICAL
RECALL
FOR ELEVATOR
TO (E) FACP
EVAC AMP
VOICE
S
VECP
VOICE EVAC
CONTROL PANEL
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
NTS
10
/
3
1
/
2
0
1
6
1
1
:
3
6
:
0
8
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
DIAGRAMS
E401
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
1/8" = 1'-0"1 FIRE SMOKE DAMPER DETAIL
NTS2LOW VOLTAGE RISER DIAGRAM
NTS3FIRE ALARM RISER DIAGRAM1
DLM Wall Switch
LMSW-Series
LMRJ Series Pre-Terminated
Cables or CAT5e. Free
Topology
& Splitter Acceptable
(As Needed)
Lighting
Load
(a)
Lighting
Load
(b)
Yel
Red
Re
d
Neutral Wht
Neutral Wht
Lighting
Load
(c)
*DLM Occupancy
Sensor
*NOTE:
Corner mount Sensor
shown with pigtail &
supplied coupler. Ceiling
mount Sensor has two
RJ45 ports.
Unswitched
Hot Blk
120/277
LMRJ-C8
Coupler
LMRC-102
Dual Relay On/Off
Room Controller
LMRC-101
Single Relay On/Off
Room Controller
Unswitched
Hot Blk
120/277
ADDITIONAL ROOM
CONTROLLERS AS
REQUIRED PER
QUANTITY OF ZONES
IN ROOM
Red
Yel
Lighting
Load
(c)
Blu
Lighting
Load
(a)
Lighting
Load
(b)
Vi
o
Gr
y
Vio
Gry
Vio
Gry
Vio
Gry
Vi
o
Gr
y
Vi
o
Gr
y
Class 2 0-10 Volt
Control Wiring
0-10VDC Dimming
Ballast required.
LMRJ Series Pre-Terminated
Cables or CAT5e. Free
Topology
& Splitter Acceptable
120/230/277
Hot Blk
Neutral Wht
LMRC-213
Dimming Room
Controller
LMLS-500
Photosensor
RJ45 Port
(Typical)
LMDM-101 Dimming Switches
with LMSW-103 Scene Switch
Red
Red
Common
+24VDC
Control Output
Hot
Neutral
Blk
Wht
120VAC
277VAC
BZ-150
Br
o
w
n
Bl
a
c
k
Gr
e
y
Or
a
n
g
e
Re
d
Bl
u
e
Cap
Cap
Auto
ON
Man
ON
COM
SW1
LVSW-101
Low Voltage
Switch Input
Fixture A
Sensor
Ceiling/Wall
24VDC
Any
*To
Additional
Sensor(s)
Any Line
Voltage
Occupancy
Sensor Using
Terminals
Any Line
Voltage
Occupancy
Sensor Using
Terminals
Load
Load
Line
Neutral
Ground
Load
Line
Neutral
GroundNeutral
Hot
Neutral
LOCAL
OFF
SWITCH
QUANTITY AS NECESSARY
T
'RP2A'120V
WATTSTOPPER
MAIN LEVEL
ELECTRICAL ROOM
EC
PROVIDED
CAT6
CABLING
NOTE:
THIS SCHEMATIC SHOWS AN INTENT OF THE EQUIPMENT CONNECTIONS FOR THE OVERALL CONTROL OF THE
BUILDING PUBLIC AREA LIGHTING SYSTEMS. IT DOES NOT REPRESENT ACTUAL WIRING DIAGRAMS. THE
ELECTRICAL CONTRACTOR MUST COORDINATE WITH THE LIGHTING CONTROL MANUFACTURER AND SUBMIT THE
ACTUAL WIRE DIAGRAMS FOR EQUIPMENT INTERCONNECTION AS PART OF THE SUBMITTAL PROCESS.
120V
BACNETIP INTEGRATION
ADJACENT TO 'RP1'
EC PROVIDED CAT6 CABLING
32 RELAY
PANEL
'WS6'
CARDIO
'WS7'
POOL LIFEGUARD
'WS8'
XXX
'RP2B'
WATTSTOPPER
MAIN LEVEL SATELITTE ELEC
32 RELAY
PANEL
'RP1B'
WATTSTOPPER
LOWER LEVEL
ELEC ROOM 109
32 RELAY
PANEL
PC NATATORIUM PHOTOCELL
(OPEN LOOP)
FOR PRICING ASSUME
QUANTITY OF (4)
'WS1'
LOBBY
RECEPTION DESK
'WS2'
LOUNGE
RECEPTION DESK
'WS3'
FITNESS
'WS4'
GYM
'WS5'
MAINTENANCE
ENTRY
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/8" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
9
:
2
0
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
LIGHTING CONTROL
SCHEDULES AND
DIAGRAMS
E402
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
1/8" = 1'-0"1
LIGHTING CONTROL DIAGRAM - CEILING VACANCY SENSOR AND
DIMMING
1/8" = 1'-0"2 LIGHTING CONTROL DIAGRAM - DAYLIGHT HARVEST
1/8" = 1'-0"3 LIGHTING CONTROL DIAGRAM - CEILING SENSORS, VACANCY MODE
1/8" = 1'-0"4 LIGHTING CONTROL DIAGRAM - CEILING OCCUPANCY SENSORS
1/8" = 1'-0"5 LIGHTING CONTROL ONE-LINE DIAGRAM & DETAILS
LIGHTING CONTROL DEVICES
TYPE DESCRIPTION MANUFACTURER CATALOGUE PROGRAMMING REQUIREMENTS NOTES
LVD1 LOW-VOLTAGE DIMMING WALL SWITCH (ROOM CONTROLLER
CONFIGURATION)
WATTSTOPPER LMDM-100 SERIES
LVKS LOW-VOLTAGE KEYED SWITCH TBD TBD
OSC2 CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WATTSTOPPER DT-300 SERIES AUTO-ON, AUTO-OFF AFTER 30 MINUTES
OSC3 CORNER-MOUNT DUAL TECHNOLOGY OCCUPANCY SENSOR WATTSTOPPER DT-200 SERIES AUTO-ON, AUTO-OFF AFTER 30 MINUTES
PC1 LOW-VOLTAGE, OPEN-LOOP PHOTOSENSOR WATTSTOPPER LMLS-500 MAINTAIN MINIMUM SETPOINT OF 35 FC AT
FINISHED FLOOR.
RCD1 SINGLE RELAY ROOM CONTROLLER, 0-10V DIMMING WATTSTOPPER LMRC-211 RE: E402
RCD2 DUAL RELAY ROOM CONTROLLER, 0-10V DIMMING WATTSTOPPER LMRC-212 RE: E402
RCD3 3-RELAY ROOM CONTROLLER, 0-10V DIMMING WATTSTOPPER LMRC-213 RE: E402
RCD4 MULTI-ZONE ROOM CONTROLLER, 0-10V DIMMING (COMMUNITY
ROOM)
CRESTRON GLPAC8-3OS-TS-X(
*)-XX-EXP ZONE
RE: E403, PROVIDE EPANSION FOR (1) ADDITIONAL
SWITCHED ZONE. (*)EC SHALL COORDINATE SHADE
MOTOR TYPE WITH APPROVED MOTORIZED SHADE
EQUIPMENT SHOP DRAWINGS PRIOR TO PURCHASE.
TS WALL TIMER SWITCH WATTSTOPPER TBD MANUAL ON, AUTO-OFF PER TIMER
SELECTION
VS1 SINGLE RELAY WALL MOUNTED DUAL TECHNOLOGY VACANCY
SENSOR
WATTSTOPPER DSW-301 SERIES MANUAL ON, AUTO-OFF AFTER 30 MINUTES
VSC1 CEILING MOUNTED DUAL TECHNOLOGY DLM VACANCY SENSOR
(ROOM CONTROLLER CONFIGURATION)
WATTSTOPPER LMDC-100 SERIES MANUAL ON, AUTO-OFF AFTER 30 MINUTES
VSC2 CELING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR WATTSTOPPER DT-300 SERIES MANUAL ON, AUTO-OFF AFTER 30 MINUTES
VSC3 CORNER-MOUNT DUAL TECHNOLOGY DLM VACANCY SENSOR WATTSTOPPER LMDX-100 MANUAL ON, AUTO-OFF AFTER 30 MINUTES
VSC4 CEILING MOUNTED DUAL TECHNOLOGY VACANCY SENSOR
(COMMUNITY ROOM)
CRESTRON GLS-ODT-C-2000 MANUAL ON, AUTO-OFF AFTER 30 MINUTES RE: E403
DIN-PWS50
DIN-AP2
Serial RS-232 To Shade Control (if Required)
CEN-SW-POE-5
TSW-750TSW-750TSW-750
GLPAC-DIM8
120VAC SUPPLY
120VAC SHADES
SWITCHED (UP/DOWN)
GLS-PART GLS-PART
GLS-SIM GLS-SIM
CRESNET CABLE: (1) PAIR #
18AWG, (1) TWISTED PAIR
22AWG (1) SHIELD
(TS1) (TS1) (TS1)
CRESNET CABLE: (1) PAIR #
18AWG, (1) TWISTED PAIR
22AWG (1) SHIELD DIN-IN-2X18
COMMUNITY ROOMS
CAT5 CAT5
COMMUNITY ROOMS:
THE INTENT FOR THIS SPACE IS HAVE A FULLY
AUTOMATED CONTROL FOR THE FOLLOWING
COMPONENTS: PARTITIONS, SHADES AND LIGHTS.
A/
V
SY
S
T
E
M
TBD
LI
G
H
T
I
N
G
SY
S
T
E
M
S
AMBIENT LIGHTING: (3) ZONES OF 0-10V
FULLY DIMMABLE FIXTURES. FIXTURES
SHALL ACT AS (3) ZONES WHEN PARTITIONS
ARE CLOSED, (2) ZONES WHEN A SINGLE
PARTITION IS CLOSED, AND (1) ZONE WHEN
PARTITIONS ARE OPEN.
ACCENT/COVE LIGHTING: (3) ZONES OF
0-10V FULLY DIMMABLE FIXTURES.
FIXTURES SHALL ACT AS (3) ZONES WHEN
PARTITIONS ARE CLOSED, (2) ZONES WHEN
A SINGLE PARTITION IS CLOSED, AND (1)
ZONE WHEN PARTITIONS ARE OPEN.
WHEN A PARTITION IS OPEN THE SYSTEM
SHALL TREAT THE SPACES ADJACENT TO
OPEN PARTION AS A SINGLE ROOM (IE WHEN
PARTITION IS OPEN ADJACENT ROOM
AMBIENT LIGHTING CONTROL SHALL ACT AS
A SINGLE ZONE).PA
R
T
I
T
I
O
N
S
DECORATIVE PENDANT LIGHTING: (3) ZONES
OF SWITCHED LIGHTING. FIXTURES SHALL
ACT AS (3) ZONES WHEN PARTITIONS ARE
CLOSED, (2) ZONES WHEN A SINGLE
PARTITION IS CLOSED, AND (1) ZONE WHEN
PARTITIONS ARE OPEN.
CONTROL SYSTEM GENERAL NOTES:
1 ALL EQUIPMENT SHOWN ON THESE DETAILS IS
MANUFACTURERED BY CRESTRON.
THESE ONE-LINE DIAGRAMS ARE FOR
CONCEPT ONLY. THESE ARE NOT INTENDED
TO BE USED AS WIRING DIAGRAMS.
EC SHALL CONFIRM ALL PARTS & PIECES WITH
MANUFACTURER PRIOR TO ORDER TO
ENSURE THE FUNCTIONALITY OF THE SYSTEM
MATCHES THE ITEMS OUTLINED IN THE
"INTENT" PORTION OF THESE NOTES.
INTERNAL TIMECLOCK SHALL BE SET TO BE
TURNED ON 30 MIN PRIOR TO OPENING UNTIL 1
HOUR AFTER CLOSE, WITH 2 HOUR OVERRIDE
OPTIONS FROM THE TOUCHSCREEN PANELS.
2
3
4
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
NTS
10
/
3
1
/
2
0
1
6
1
1
:
3
9
:
3
8
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
Checker
Author
10-31-2016
16003
LIGHTING CONTROL
DIAGRAMS
E403
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NTS1COMMUNITY ROOMS CONTROL SYSTEM DIAGRAM
RELAY PANEL - RP1B
RELAY
SWITCH ID RELAY DESCRIPTION CONT. SEQUENCE
RELAY
VOLTAGE PANEL CKT #
RP1B-1 LOUNGE LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 7
RP1B-2 RECEPTION DESK RECESSED LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 7
RP1B-3 RECEPTION DESK PENDANT LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 7
RP1B-4 RECEPTION DESK COVE LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 9
RP1B-5 STRENGTH/HALL LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 13
RP1B-6 UNDER TRACK LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 15
RP1B-7 EXTERIOR BUILDING LIGHTING - NORTH AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL1B 16
RP1B-8 MONUMENT SIGN AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
120 V LP1B 83
RELAY PANEL - RP2A
RELAY
SWITCH ID RELAY DESCRIPTION CONT. SEQUENCE
RELAY
VOLTAGE PANEL CKT #
RP2A-1 NATATORIUM LIGHTING - SOUTH AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 16
RP2A-2 NATATORIUM LIGHTING - NORTHEAST AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 15
RP2A-3 NATATORIUM LIGHTING - WEST AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 17
RP2A-4 EXTERIOR SITE POLE LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO SUNSET,
AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF BUSINESS
277 V HL2B 22
RP2A-5 EXTERIOR SITE PEDESTRIAN LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO SUNSET,
AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF BUSINESS
277 V HL2B 20
RP2A-6 EXTERIOR SITE POLE LIGHTING -
SECURITY
AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO SUNSET,
AUTO-OFF VIA TIMECLOCK 30 MINUTES AFTER SUNRISE
277 V HL2B 22
RP2A-7 EXTERIOR SITE PEDESTRIAN LIGHTING -
SECURITY
AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO SUNSET,
AUTO-OFF VIA TIMECLOCK 30 MINUTES AFTER SUNRISE
277 V HL2B 20
RP2A-8 EXTERIOR BOLLARD LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO SUNSET,
AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF BUSINESS
277 V HL2B 20
RP2A-9 EXTERIOR BOLLARD LIGHTING -
SECURITY
AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO SUNSET,
AUTO-OFF VIA TIMECLOCK 30 MINUTES AFTER SUNRISE
277 V HL2B 20
RP2A-10 NATATORIUM FOYER & ENTRY
CORRIDOR
AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HA2A 19
RP2A-11 EXTERIOR BUILDING LIGHTING - EAST AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HA2A 21
RP2A-12 EXTERIOR BUILDING LIGHTING - WEST AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HA2A 21
RP2A-13 POOL LIGHTS AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
120 V LP2A 34
RELAY PANEL - RP2B
RELAY
SWITCH ID RELAY DESCRIPTION CONT. SEQUENCE
RELAY
VOLTAGE PANEL CKT #
RP2B-1 OFFICE CORRIDOR LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 2
RP2B-2 LOBBY LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 4
RP2B-3 LOBBY RECEPTION DESK LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 4
RP2B-5 ABOVE TRACK LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 7
RP2B-6 NORTH GYM LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 8
RP2B-7 NORTH GYM LIGHTING - EMERGENCY AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 9
RP2B-8 SOUTH GYM LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 10
RP2B-9 SOUTH GYM LIGHTING - EMERGENCY AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 11
RP2B-10 CARDIO LINEAR LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 7
RP2B-11 LOBBY LARGE PENDANT LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 4
RP2B-12 STAIR LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
277 V HL2B 6
RP2B-13 LOBBY RECEPTION DESK LIGHTING AUTO-ON VIA TIMECLOCK 30 MINUTES PRIOR TO START OF
BUSINESS, AUTO-OFF VIA TIMECLOCK 1 HOUR AFTER CLOSE OF
BUSINESS.
120 V LP2B 84
WS1 BUTTON CONFIGURATION
BUTTON RELAYS CONTROLLED
'LOUNGE' RP1B-1
'RECPT. DESK' RP1B-2,3,4
'STRENGTH'
RP1B-6
RP1B-5
'LOWER TRACK'
RP2B-6,7,8,9'GYM'
TBDSPARE
A.
B.
C.
D.
E.
F.
G.
H.
I.
MECHANICAL EQUIPMENT GENERAL NOTES
REFER TO MECHANICAL PLANS FOR SPECIFIC EQUIPMENT LOCATIONS AND REQUIREMENTS.
PRIOR TO ROUGH-IN, COORDINATE ALL MECHANICAL EQUIPMENT POWER AND CONNECTION REQUIREMENTS WITH MECHANICAL CONTRACTOR'S FINAL SHOP DRAWINGS.
PROVIDE ALL 120V CONTROL WIRING, REFER TO SPECIFICATIONS FOR FURTHER CONTROL WIRING CLARIFICATION.
FOR ANY VAV SYSTEM COORDINATE POWER REQUIREMENTS WITH MECHANICAL CONTRACTOR AND PROVIDE 120V CONNECTIONS AT EACH VAV BOX, OR AT CENTRAL CONTROL PANEL LOCATION(S) AS REQUIRED. IF EXACT
QUANTITIES AND LOCATIONS FOR CONTROL PANELS ARE NOT KNOWN AT BID TIME, E.C. IS TO INCLUDE ONE 120V CONNECTION AT EACH VAV DEVICE IN THE BASE BID PRICE AND PROVIDE A CREDIT DURING CONSTRUCTION IF LESS
CONNECTIONS ARE REQUIRED.
EXTERIOR DISCONNECT SWITCHES ARE TO BE PROVIDED AS NEMA 3R EQUIPMENT UNLESS OTHERWISE NOTED.
PROVIDE WEATHERPROOF 120 VOLT GFCI RECEPTACLES WITHIN 25' OF ALL ROOFTOP HEATING, VENTILATING, AND AIR CONDITIONING EQUIPMENT. CIRCUIT TO SPARE CIRCUIT ON NEAREST 120V PANELBOARD OR AS INDICATED ON
PLANS.
PROVIDE DUCT DETECTION ON ALL RETURN AIR SYSTEMS OF 2,000 CFM OR GREATER, AND FOR ALL SUPPLY AIR SYSTEMS 15,000 CFM OR GREATER, INCLUDING THOSE SYSTEMS SERVING MULTIPLE FLOORS. PROVIDE ADDITIONAL
DUCT DETECTORS AND INSTALL REMOTE INDICATOR LIGHTS AS REQUIRED BY LOCAL AUTHORITY HAVING JURISDICTION.
FOR ANY BOILER MECHANICAL SYSTEM, E.C. IS TO PROVIDE AN EMERGENCY PUSHBUTTON OFF AND ANY CONTROL WIRING REQUIRED. COORDINATE EXACT REQUIREMENTS WITH MECHANICAL CONTRACTOR AND EQUIPMENT PRIOR
TO INSTALLATION.
EC TO PROVIDE HAND/OFF/AUTO STARTERS FOR ALL MOTORS WHEN NOT INDICATED AS TO BE PROVIDED BY THE MECHANICAL CONTRACTOR ON THE MECHANICAL PLANS. SIZE OF STARTER TO BE BASED UPON SIZE OF MOTOR
HORSEPOWER INDICATED.
GENERAL NOTES
SPECIFIC NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
UNIT POWERED FROM DSCU-1.
TIE INTO LOCAL LIGHTING OCCUPANCY SENSOR SWITCH.
PROVIDE SEPERATE PRICING FOR ELECTRICAL CONNECTIONS FOR MECHANICAL ALTERNATE UNIT AS NOTED ON MECHANICAL DRAWINGS, PER ALTERNATE #2.
PROVIDE (1) 120V, 20AMP CIRCUIT FOR CONTROL PANEL. EC SHALL PROVIDE ELECTRICAL CONNECTIONS FOR CONTROL PANELS, POOL CONTRACTOR TO PROVIDE WIRING TO PUMPS AS INDICATED ON MECHANICAL DRAWINGS.
COORDINATE FAN SPEED SWITCH CONNECTION REQUIREMENTS PRIOR TO ROUGH-IN.
EC SHALL PROVIDE FIRE ALARM TIE-IN TO CEILING FAN CONTROLS CONTRACTOR FOR FIRE ALARM SYSTEM SHUT DOWN OF CEILING FAN UPON ACTIVATION OF FIRE ALARM CONDITION. CEILING FAN CONTROLS CONTACTOR SHALL BE
FURNISHED AND INSTALLED BY MECHANICAL CONTRACTOR AND WIRED BY EC. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MECHANICAL DRAWINGS PRIOR TO ROUGH-IN.
EC SHALL CONFIRM OVERCURRENT PROTECTION FOR ELEVATOR IS COORDINATED WITH MANUFACTURER'S SHOP DRAWING SUBMITTALS, FOR THE ACTUAL EQUIPMENT TO BE INSTALLED. ELEVATOR CONTROLLER LOCATED IN
MANUFACTUER POWER CONTROL PANEL WITH 80A/3P SHUNT TRIP CIRCUIT BREAKER. COODRINATE AUXILLARY CONTACTS WITH MANUFACTURER'S APPROVED ELEVATOR SHOP DRAWINGS FOR FIRE ALARM RECALL CAPABILITY.
BOILER SHALL BE PROVIDED WITH 'EPO' TYPE SWITCH FOR EMERGENCY SHUT DOWN OF BOILER POWER. EPO SWITCH FURNISHED AND INSTALLED BY TEMPERATURE CONTROLS CONTRACTOR AND WIRED BY EC. COORDINATE EXACT
CONNECTION REQUIREMENTS AND MOUNTING LOCATION WITH MECHANICAL DRAWINGS PRIOR TO ROUGH-IN.
EC SHALL INTERCONNECT SHUNT TRIP BREAKER WITH MECHANICAL EXHAUST HOOD, PROVIDE CONTROLS AS NOTED IN MECHANICAL DRAWINGS.
POOL EQUIPMENT NOTES
A PROVIDE 120V CONTROL WIRING AS REQUIRED PER POOL EQUIPMENT SCHEDULE ON POOL DRAWINGS.
B REFER TO POOL DRAWINGS FOR EQUIPMENT LOCATIONS.
C FIELD VERIFY ALL EQUIPMENT LOADS, VOLTAGES, AND RECOMMENDED FUSE SIZING PRIOR TO ENERGIZING CIRCUIT.
D THE ELECTRICAL CONTRACTOR SHALL REVIEW ALL AQUATICS PLANS AND PROVIDE ALL WORK AS CALLED OUT TO BE COMPLETED BY THE ELECTRICAL CONTRACTOR. COORDINATE WITH POOL CONTRACTOR.
E ALL DISCONNECTS SHALL BE NEMA 3R RATED WITH NON-METALLIC ENCLOSURE AND STAINLESS STEEL HARDWARE FOR CORROSION RESISTANCE.
F MOTORS REQUIRING STARTERS SHALL UTILIZE COMBINATION START/DISCONNECT. STARTERS SHALL BE NON-REVERSING WITH NEMA SIZE AS LISTED. ALL STARTERS SHALL UTILIZE CIRCUIT BREAKERS FOR OVERCURRENT PROTECTION. UNITS
NOTED TO BE CONTROLLED WITH VFD SHALL BE PROVIDED AS A COMBINATION VFD/DISCONNECT, SPECIFIED IN AQUATICS DRAWINGS.
G PROVIDE FLEXIBLE CONDUIT CONNECTION AT ALL PUMP MOTORS, MINIMUM 18" IN LENGTH.
H WHERE MOTOR IS WITHIN SIGHT (PER THE DEFINITION OF THE NEC) OF THE MCC, THE INDICATED DISCONNECT SWITCH IS NOT REQUIRED.
I ALL MOTORS GREATER THAN 7.5 HORSEPOWER ARE TO BE PROVIDED WITH THREE PHASE PROTECTION.
J ELECTRICAL CONTRACTOR SHALL REFERENCE POOL WIRING DIAGRAMS AND SEQUENCE OF OPERATIONS FOR INTERLOCKS PROVIDED ON THE AQUATIC DESIGNERS DRAWINGS.
L PROVIDE CLEARLY LABELED EMERGENCY SHUTOFF BUTTONS FOR THE PURPOSE OF STOPPING THE MOTORS THAT PROVIDE POWER TO ALL NON-FILTRATION PUMPS PER POOL ENGINEER. EMERGENCY SHUTOFF BUTTON LOCATIONS SHALL BE COORDINATED
WITH THE OWNER OR THE OWNER'S RISK MANAGEMENT CONSULTANT.
M EC SHALL REFER TO THE POOL CONSTRUCTION DRAWINGS FOR DELINEATION OF RESPONSIBILITIES BETWEEN POOL AND ELECTRICAL CONTRACTORS FOR WHO FURNISHES AND INSTALLS POOL EQUIPMENT, AS WELL AS WHO PROVIDES LINE, LOW VOLTAGE, AND
CONTROL WIRING CONNECTIONS.
1 ANTICIPATED FUTURE INSTALLATION OF EQUIPMENT, PROVIDED FOR APPROXIMATE ELECTRICAL LOAD USAGE TO ACCOMODATE FUTURE LOADS ON NEW SERVICE/PANELS.
GENERAL NOTES
SPECIFIC NOTES
2 REFER TO PLANS FOR EPO/TIMER JUNCTION BOX LOCATIONS AND CONDUIT REQUIREMENTS FOR FUTURE INSTALLATION PER AQUATICS DRAWINGS.
3 EC SHALL PROVIDE A COMBINATION MOTOR STATER WITH "START-STOP" BUTTONS AND VARIABLE FREQUENCY DRIVE WITH MANUAL BYPASS.
4 WET NICHE POOL LIGHT LOCATION. LIGHT NICHE PROVIDED AND INSTALLED BY POOL CONTRACTOR. NICHE SHALL BE GROUNDED/BONDED BY THE ELECTRICAL CONTRACTOR. WET NICHE LUMINAIRES SHALL BE FURNISHED BY THE POOL CONTRACTOR AND
INSTALLED BY THE ELECTRICAL CONTRACTOR. WATERTIGHT CONDUIT, POOL RATED JUNCTION BOXES, CONTROLS, AND GFI PROTECTION SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR IN ACCORDANCE WITH NEC ARTICLE #680.
5 ACID PUMP 1 SHALL BE FED FROM CHEMICAL CONTROLLER 1. CORD PLUGS INTO CHEMICAL CONTROLLER RECEPTACLE. RE: AQUATICS.
6 RE: RELAY PANEL RP2A FOR CIRCUITING INFORMATION
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
As indicated
10
/
3
1
/
2
0
1
6
1
1
:
1
9
:
5
0
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
SCHEDULES
E500
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
MECHANICAL SCHEDULE
KEY
EQUIPMENT DESCRIPTION LOAD ELECTRICAL MOCP FEEDER DISCONNECT PANEL CIRCUIT NOTES
B 1 BOILER 12 FLA 120 V/1-1440 VA 15 2#12, #12G, 3/4"C $TO LP2A 4 8
B 2 BOILER 12 FLA 120 V/1-1440 VA 15 2#12, #12G, 3/4"C $TO LP2A 5 8
B 3 BOILER 12 FLA 120 V/1-1440 VA 15 2#12, #12G, 3/4"C $TO LP2A 6 8
CF 1 CEILING FAN 1070 VA 480 V/3-1070 VA 15 3#12, #12G, 3/4"C INTEGRAL HM2B 1,3,5 6
CF 2 CEILING FAN 1070 VA 480 V/3-1070 VA 15 3#12, #12G, 3/4"C INTEGRAL HM2B 1,3,5 6
CF 3 CEILING FAN 900 VA 480 V/3-900 VA 15 3#12, #12G, 3/4"C INTEGRAL HM2A 14,16,18 6
CF 4A CEILING FAN (ALTERNATE) 850 VA 480 V/3-850 VA 15 3#12, #12G, 3/4"C INTEGRAL HM2A 21,23,25 3,6
CF 5A CEILING FAN (ALTERNATE) 850 VA 480 V/3-850 VA 15 3#12, #12G, 3/4"C INTEGRAL HM2A 22,24,26 3,6
CP 1 CIRCULATION PUMP 1/6 HP 120 V/1-528 VA 15 2#12, #12G, 3/4"C 30A/1P LP2A 7
CP 2 CIRCULATION PUMP 1/6 HP 120 V/1-528 VA 15 2#12, #12G, 3/4"C 30A/1P LP2A 8
CP 3 CIRCULATION PUMP 1/6 HP 120 V/1-528 VA 15 2#12, #12G, 3/4"C 30A/1P LP2A 9
CUH 1 CABINET UNIT HEATER 2.24 FLA 120 V/1-269 VA 15 2#12, #12G, 3/4"C $TO LP2A 13
CUH 2 CABINET UNIT HEATER 2.24 FLA 120 V/1-269 VA 15 2#12, #12G, 3/4"C $TO LP2A 13
CUH 3 CABINET UNIT HEATER 2.24 FLA 120 V/1-269 VA 15 2#12, #12G, 3/4"C $TO LP1B 3
CUH 4 CABINET UNIT HEATER 2.24 FLA 120 V/1-269 VA 15 2#12, #12G, 3/4"C $TO LP1B 1
CUH 5 CABINET UNIT HEATER 4.88 FLA 120 V/1-586 VA 15 2#12, #12G, 3/4"C $TO LP1B 1
DSCU 1 DUCTLESS SPLIT SYSTEM CONDENSING UNIT 15.6 FLA 208 V/2-3245 VA 20 2#12, #12G, 3/4"C 30A/2P LP2B 2,4
DSIU 1 DUCTLESS SPLIT SYSTEM INDOOR UNIT -- 208 V/1-0 VA -- -- --1
EF 1 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 15
EF 2 EXHAUST FAN 1 HP 208 V/2-1840 VA 20 2#12, #12G, 3/4"C INTEGRAL LP2A 69,71
EF 3 EXHAUST FAN 81 W 120 V/1-81 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 3 2
EF 4 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 18
EF 5 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 19
EF 6 EXHAUST FAN 1 HP 208 V/2-1664 VA 15 2#10, #10G, 3/4"C INTEGRAL LP2A 14,16
EF 7 EXHAUST FAN 135 W 120 V/1-135 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 1 2
EF 8 EXHAUST FAN 135 W 120 V/1-135 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 1 2
EF 9 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 6
EF 10 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 7
EF 11 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 8
EF 12 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 9
EF 13 EXHAUST FAN 3.3 FLA 120 V/1-348 VA 15 2#12, #12G, 3/4"C INTEGRAL LP1B 76
EF 14 EXHAUST FAN 3/4 HP 120 V/1-1656 VA 25 2#10, #10G, 3/4"C INTEGRAL LP2A 20
EF 15 EXHAUST FAN 1/4 HP 120 V/1-696 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 10
EF 16 EXHAUST FAN 1.1 FLA 120 V/1-128 VA 15 2#12, #12G, 3/4"C INTEGRAL LK1B 19
EF 17 EXHAUST FAN 1 HP 208 V/2-1664 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 73,75
ELEV 1 ELEVATOR 20 HP 480 V/3-31868 VA 100 3#1, 1#6G, 1-1/2"C 100A/3P MDC 15 7
GWH 1 GAS WATER HEATERS 2 A 120 V/1-240 VA 15 2#12, #12G, 3/4"C $TO LP2A 11
GWH 2 GAS WATER HEATERS 2 A 120 V/1-240 VA 15 2#12, #12G, 3/4"C $TO LP2A 11
GWH 3 GAS WATER HEATERS 2 A 120 V/1-240 VA 15 2#12, #12G, 3/4"C $TO LP2A 11
KH 1 KITCHEN HOOD 15 FLA 120 V/1-1800 VA 20 2#12, #12G, 3/4"C INTEGRAL LK1B 21 9
MAU 1 GAS FIRED MAKE-UP-AIR UNIT 4.24 FLA 480 V/3-3525 VA 15 3#12, #12G, 3/4"C 30A/3P HM2A 13,15,17
P 1 PUMP 1.5 HP 480 V/3-2494 VA 15 3#12, #12G, 3/4"C 30A/3P HM2A 1,3,5
P 2 PUMP 1.5 HP 480 V/3-2494 VA 15 3#12, #12G, 3/4"C 30A/3P HM2A 7,9,11
PDU 1A NATATORIUM DEHUMIDIFICATION/HEAT RECOVERY UNIT
- ALTERNATE
31.2 FLA 480 V/3-25908 VA 50 3#6, 1#10G, 1"C 60A/3P HM2A 8,10,12 3
PDU 2 NATATORIUM DEHUMIDIFICATION/HEAT RECOVERY UNIT 29.1 FLA 480 V/3-25908 VA 40 3#8, 1#10G, 1"C 60A/3P HM2A 2,4,6
PP 1 IN-LINE PUMP 2/5 HP 120 V/1-1176 VA 20 2#12, #12G, 3/4"C $TO LP2A 10
RTU 1 ROOF TOP UNIT 91.7 FLA 480 V/3-76235 VA 125 4#1/0,1#6G, 1-1/2"C INTEGRAL MDC 12
RTU 2 ROOF TOP UNIT 69.2 FLA 480 V/3-57530 VA 90 4#2, 1#8G, 1-1/2"C INTEGRAL MDC 13
RTU 3 ROOF TOP UNIT 183.3 FLA 480 V/3-152388 VA 225 4#4/0, 1#4G, 2-1/2"C INTEGRAL MDC 14
SE 1,2 SEWAGE EJECTOR PUMP 1/2 HP 120 V/1-1176 VA 20 2#12, #12G, 3/4"C 30A/1P LA2A 2 4
SP 1 SUMP PUMP 1/2 HP 120 V/1-1176 VA 20 2#12, #12G, 3/4"C 30A/1P LP1B 74 4
TF 1 TRANSFER FAN 81 W 120 V/1-350 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2B 1 5
TF 2 TRANSFER FAN 285 W 120 V/1-350 VA 15 2#12, #12G, 3/4"C INTEGRAL LP1B 17 5
TF 3 TRANSFER FAN 350 W 120 V/1-350 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 3 5
UH 1 UNIT HEATER 0.8 FLA 120 V/1-96 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 13 5
UH 2 UNIT HEATER 0.8 FLA 120 V/1-96 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 13 5
UH 3 UNIT HEATER 0.8 FLA 120 V/1-96 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 13 5
UH 4 UNIT HEATER 0.8 FLA 120 V/1-96 VA 15 2#12, #12G, 3/4"C INTEGRAL LP1B 3 5
UH 5 UNIT HEATER 0.8 FLA 120 V/1-96 VA 15 2#12, #12G, 3/4"C INTEGRAL LP1B 1 5
UH 6 UNIT HEATER 0.8 FLA 120 V/1-96 VA 15 2#12, #12G, 3/4"C INTEGRAL LP2A 17 5
POOL EQUIPMENT SCHEDULE
KEY # LOAD EQUIPMENT DESCRIPTION
ELECTRICAL
DATA MOCP FEEDER DISCONNECT STARTER
AUX
CONTACTS PANEL CIRCUIT NOTES
AC 1 15 A DEFENDER FILTER AIR COMPRESSOR 120 V/1-1800 VA 20 2#12, #12G, 3/4"C NEMA 5-20R LA2A 4
AP 1 1/30 HP ACID PUMPS 120 V/1-120 VA 20 PROVIDED CORD/PLUG LA2A 6 5
CC 1 10 A CHEMICAL CONTROLLER 120 V/1-1200 VA 20 2#12, #12G, 3/4"C NEMA 5-20R LA2A 7
CCBP 1 1/2 HP CLEAR COMFORT BOOSTER PUMP 1 120 V/1-1176 VA 20 2#12, #12G, 3/4"C $TO LA2A 1
CCEB 1 1/2 HP CHEMICAL CABINET EXHAUST BLOWER 1 120 V/1-1176 VA 20 2#12, #12G, 3/4"C $TO LA2A 8
CCEB 2 1/2 HP CHEMICAL CABINET EXHAUST BLOWER 2 120 V/1-1176 VA 20 2#12, #12G, 3/4"C $TO LA2A 9
CCS 1 10 A CLEAR COMFORT SUPPLIMENTAL TREATMENT 120 V/1-1200 VA 20 2#12, #12G, 3/4"C $TO LA2A 12
CH 1 15 A PPG CHLORINATOR 120 V/1-1800 VA 20 2#12, #12G, 3/4"C $TO LA2A 11
CP 1 40 HP LEISURE POOL CURRENT PUMP 1 480 V/3-41430 VA 90 3#2, 1#8G, 1-1/4"C 100A/3P NEMA TYPE 3 (1) NC, (1) NO HA2A 8,10,12 3
CP 2 40 HP LEISURE POOL CURRENT PUMP 2 480 V/3-41430 VA 90 3#2, 1#8G, 1-1/4"C 100A/3P NEMA TYPE 3 (1) NC, (1) NO HA2A 13,15,17 3
ECH 3 100 W EXISTING POOL CHLORINATOR 120 V/1-100 VA 20 2#12, #12G, 3/4"C $TO LA2A 15
FC 1 20 A DEFENDER FILTER CONTROLLER 1 120 V/1-1800 VA 20 2#12, #12G, 3/4"C NEMA 5-20R LA2A 3
LAP 1 5 HP LEISURE AMENITY PUMP 1 480 V/3-6057 VA 15 3#12, #12G, 3/4"C 30A/3P NEMA TYPE 0 (1) NC, (1) NO HA2A 1,3,5 3
LAP 2 5 HP LEISURE AMENITY PUMP 2 480 V/3-6057 VA 15 3#12, #12G, 3/4"C 30A/3P NEMA TYPE 0 (1) NC, (1) NO HA2A 2,4,6 3
LCP 1 7.5 HP LEISURE CIRCULATION PUMP 480 V/3-8769 VA 20 3#12, #12G, 3/4"C 30A/3P NEMA TYPE 1 (1) NC, (1) NO HA2A 7,9,11 3
LH 1 15 A LEISURE HEATER 120 V/1-1800 VA 20 2#12, #12G, 3/4"C $TO LA2A 5
WN A 100 W LEISURE POOL WET NICHE LIGHTING 120 V/1-100 VA 20 2#12, #12G, 3/4"C RELAY 4,5
FUTURE POOL EQUIPMENT SCHEDULE
KEY # LOAD EQUIPMENT DESCRIPTION ELECTRICAL DATA MOCP FEEDER DISCONNECT NOTES
AP 2 1/30 HP ACID PUMPS (FUTURE) 120 V/1-120 VA 20 -- -- 1
CC 2 10 A CHEMICAL CONTROLLER (FUTURE) 120 V/1-1200 VA 20 -- -- 1
CCBP 2 1/2 HP CLEAR COMFORT BOOSTER PUMP 2 (FUTURE) 120 V/1-1176 VA 20 -- -- 1
CCS 2 10 A CLEAR COMFORT SUPPLIMENTAL TREATMENT (FUTURE) 120 V/1-1200 VA 20 -- -- 1
CH 2 15 A PPG CHLORINATOR (FUTURE) 120 V/1-1800 VA 20 ---- 1
FC 2 20 A DEFENDER FILTER CONTROLLER 2 (FUTURE) 120 V/1-1800 VA 20 -- -- 1
SCP 1 3 HP SPA CIRCULATION PUMP (FUTURE) 480 V/3-3828 VA 15 -- -- 1,2
SH 1 15 A SPA HEATER (FUTURE) 120 V/1-1800 VA 20 -- -- 1
SJB 1 3 HP SPA JET AIR BLOWER (FUTURE) 480 V/3-3828 VA 15 -- -- 1
SJP 1 5 HP SPA JET PUMP (FUTURE) 480 V/3-6057 VA 15 -- -- 1,2
SLCP 1 15 HP SLIDE CIRCULATION PUMP (FUTURE) 480 V/3-16737 VA 15 -- -- 1,2
A.
B.
C.
LIGHTING FIXTURE NOTES
ALL FLUORESCENT LAMPS TO BE 3500K COLOR TEMPERATURE AND A MINIMUM OF 82CRI, UNLESS NOTED OTHERWISE.
ALL REFLECTOR LAMPS TO BE PROVIDED AS WIDE FLOOD DISTRIBUTION, UNLESS NOTED OTHERWISE.
ALL FLUORESCENT LUMINAIRES THAT UTILIZE DOUBLE-ENDED LAMPS AND CONTAIN BALLASTS THAT CAN BE SERVICED IN PLACE SHALL HAVE A DISCONNECTING MEANS AS DESCRIBED IN NEC 410.130(G).
GENERAL NOTES
SPECIFIC NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
COORDINATE EXACT MOUNTING WITH CEILING TYPE AT ALL LOCATIONS. COORDINATE RECESSED FIXTURE DEPTH AND CLEARANCE IN FIELD PRIOR TO PURCHASE.
MANUFACTURER SHALL PROVIDE (1) LED BAR ROTATED AND AIMED UPWARD SO THAT CENTER BAR POSITION IS AIMED INDIRECTLY AT CEILING. COORDINATE CUSTOM SPECIFICATION WITH MANUFACTURER PRIOR
TO PURCHASE.
PROVIDE SORRA 5.6 WATT MR16 GU10 REPLACEMENT LAMP(S) (3000K, 85CRI, 36 DEGREE FLOOD) OR APPROVED EQUAL, AS REQUIRED.
PROVIDE 3-BAR FIXTURE WITH (2) HIGH OUTPUT BARS AIMED DIRECTLY DOWN AND TOWARD CENTER OF POOL AND (1) STANDARD OUTPUT BAR AIMED INDIRECTLY. COORDINATE EXACT BAR SPECIFICATION,
LOCATIONS AND AIMING WITH MANUFACUTURER AND APPROVED SHOP DRAWINGS PRIOR TO PURCHASE.
NOT USED.
NOT USED.
PROVIDE LIGHTING/MOUNTING DIRECTION #2. DIRECT AWAY FROM WALL AS REQUIRED PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
COORDINATE CUSTOM SUSPENDED CABLE/STEM LENGTH AT EACH LOCATION PRIOR TO PURCHASE.
COORDINATE EXACT FIXTURE MOUNTING HEIGHT WITH ARCHITECT PRIOR TO ROUGH-IN.
COORDINATE EXACT FIXTURE LENGTH WITH PLANS AND VERIFY WITH ARCHITECT PRIOR TO PURCHASE. COORDINATE EXACT DRIVER SPECIFCIATION, QUANTITY AND MAX RUN LENGTH WITH FINAL CONNECTED
FIXTURE LENGTH AND POWER REQUIREMENTS. PROVIDE ALL REQUIRED PARTS AND COMPONENTS INCLUDING CONNECTORS AND MOUNTING HARDWARE FOR A FULLY FUNCTIONAL INSTALLED SYSTEM AS
INDICATED.
PROVIDE BODINE ELIS-100 DIMMING EMERGENCY INVERTER OR APPROVED EQUAL FOR EMERGENCY FIXTURE OPERATION.
NATATORIUM LIGHTING FIXTURE AND ALL ASSOCIATED HOUSING, HARDWARE, AND COMPONENTS EXPOSED TO ENVIRONMENT SHALL BE PROVIDED WITH NATATORIUM RATED FINISH SUITABLE FOR INTENDED USE
IN CORROSIVE NATATORIUM ENVIRONMENT. MANUFACTURER SHALL PROVIDE 10-YEAR WARRANTY ON ENTIRE FIXTURE INCLUDING LED DRIVER AND BOARDS FOR USE IN NATATORIUM..
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
1/8" = 1'-0"
10
/
3
1
/
2
0
1
6
1
1
:
1
9
:
5
9
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
VRP, ESN
TPK, KM
10-31-2016
16003
ELECTRICAL
SCHEDULES
E501
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER CATALOGUE NUMBER VOLTAGE
LAM
P
QUA
N.
LAMP
WATTAGE LAMP
MAX
WATTAGE DIMMING LOCATION
BOF/RFD/
OFH NOTES
W1 DECORATIVE OIL RUBBED BRONZE VANITY
FIXTURE
EUROPHASE 23278-011 120V 3 5 W LED 15 VA NA SURFACE
WALL
W2 DECORATIVE OIL RUBBED BRONZE VANITY
FIXTURE
EUROPHASE 23277-014 120V 2 5 W LED 10 VA NA SURFACE
WALL
3,9
W3EM 4' LINEAR WALL MOUNT D/I LED W/EM BATTERY HE WILLIAMS WMAUD-4-L32-835-AF-EM/1OW-DRV-UNV 277V 1 81 W LED 81 VA NA SURFACE
WALL
10'-0"AFG 9
W4 4' LINEAR WALL MOUNT DIRECT/INDIRECT LED ALERA LIGHTING LP7-OA-4-35-ML-40-WM-E-U-MW 277V 1 44 W LED 44 VA NA SURFACE
WALL
X1 CAST ALUMINUM GREEN LED EXIT SIGN,
UNIVERSAL MOUNT
HE WILLIAMS EXIT/CA-G-AF-BA-EM-SDT 277V 1 4 W LED 4 VA NA SURFACE
X2 CAST ALUMINUM GREEN LED EXIT SIGN,
UNIVERSAL MOUNT W/ WIREGUARD
HE WILLIAMS EXIT/CA-G-AF-BA-EM-SDT-WG 277V 1 4 W LED 4 VA NA SURFACE
Y1 EMERGENCY EGRESS LIGHT HE WILLIAMS EMER/PAR-WHT-WG 277V 2 5 W LED 10 VA NA SURFACE
WALL
EA1 LED AREA POLE LIGHT, SINGLE HEAD TYPE III KIM LIGHTING 1A-AR3P70-80L4K 277V 1 187 W LED 187 VA POLE
GROUND
+25'-0" AFG
EA2 LED AREA POLE LIGHT, SINGLE HEAD TYPE V KIM LIGHTING 1A-AR5P70-80L4K 277V 1 188 W LED 188 VA POLE
GROUND
+25'-0" AFG
EB3 LED BOLLARD STERNBERG LIGHTING BL4-ML360-SV1-32L45T3R-F-MDL05-UBT 277V 1 39 W LED 39 VA GROUND +4'-0" AFG
EB4 LED PIER BASE MOUNT STERNBERG LIGHTING PB-ML360-SV1-32L45T5-F-MDL03-UBT 277V 1 39 W LED 39 VA SURFACE +4'-0" AFG
EP1 6" EXTERIOR LED CYLINDER PENDANT
DOWNLIGHT
CONTECH CYL6-2-35K-MVD-P-X-M-CLR-BZ-CSK12-(BZ) 277V 1 14 W LED 14 VA PENDANT
CEILING
8
EP1EM 6" EXTERIOR LED CYLINDER PENDANT
DOWNLIGHT W/ EM BATTERY
CONTECH CYL6-2-35K-MVD-P-X-M-CLR-BZ-CSK12-(BZ);
PROVIDE (1) BODINE ELI-S-100 EM LIGHTING
INVERTER
277V 1 14 W LED 14 VA PENDANT
CEILING
8
EP5 LED PEDESTRIAN POLE LIGHT, SINGLE HEAD,
TYPE V
STERNBERG LIGHTING PT-ML660-SV1-60L45T5-MDL03-UBT 277V 1 70 W LED 70 VA POLE
GROUND
+15'-0" AFG
EST1 LED RECESSED STEP-LIGHT BEGA 22272 277V 1 7 W LED 7 VA RECESSED
WALL
+2' AFG 9
EW1 SMALL LED WALL SCONCE KIM LIGHTING 1W-BNM-18L3KUV-DB 277V 1 20 W LED 20 VA SURFACE
WALL
+8'-0" AFG 9
EW2 LARGE LED DECORATIVE WALL SCONCE KIM LIGHTING 1W-BNS1-H3-E35-60L-3K-277-DB 277V 1 64 W LED 64 VA SURFACE
WALL
+15'-0" AFG 9
EW2EM LARGE LED DECORATIVE WALL SCONCE KIM LIGHTING 1W -BNS1-H3-E35-60L-3K-277-DB; PROVIDE (1)
BODINE ELI-S-100 EM LIGHTING INVERTER
277V 1 64 W LED 64 VA SURFACE
WALL
+15'-0" AFG
EW3EM EXTERIOR LED WALLPACK HE WILLIAMS VWPV-L30-730-T3-DBZ-SDGL-EM/4W-DIM-UNV UNIV 1 37 W LED 37 VA SURFACE
WALL
+10'-0" AFG 9
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER CATALOGUE NUMBER VOLTAGE
LAM
P
QUA
N.
LAMP
WATTAGE LAMP
MAX
WATTAGE DIMMING LOCATION
BOF/RFD/
OFH NOTES
C1 LED TAPELIGHT & DRIVER(S) CONTECH TLT-12-2-35-XX; (2)TLP12VH60277 277V -- 2 W LED 84 VA TBD SURFACE 10
C2 LED COVE TAPELIGHT - COMMUNITY ROOM CONTECH TLT-12-2-35-XX; (1)TLP12VH60277; TLPDIM10V 277V -- 2 W LED 40 VA 0-10V SURFACE 10
C3 LED COVE TAPELIGHT - COMMUNITY ROOM CONTECH TLT-12-2-35-XX; (1)TLP12VH60277; TLPDIM10V 277V -- 2 W LED 36 VA 0-10V SURFACE 10
C4 LED COVE TAPELIGHT - COMMUNITY ROOM CONTECH TLT-12-2-35-XX; (1)TLP12VH60277; TLPDIM10V 277V -- 2 W LED 40 VA 0-10V SURFACE 10
CF1 52" BLADE FAN MODERN FAN CO FLO-XX-52-XX-NL-009B 120V -- 76 W -- 76 VA -- PENDANT
CEILING
9'-11" BOF
D1 6" LED DOWNLIGHT PRESCOLITE LBP6-6LBP-11L-35-WH UNIV 1 12 W LED 12 VA 0-10V RECESSED
CEILING
D1EM 6" LED DOWNLIGHT WITH REMOTE EMERGENCY
BATTERY INVERTER
PRESCOLITE LBP6-6LBP-11L-35-WH; PROVIDE ADDITIONAL $100
PER FIXTURE MATERIAL PRICING ALLOWANCE
FOR EMERGENCY LIGHTING INVERTER
UNIV 1 12 W LED 12 VA 0-10V RECESSED
CEILING
D2 4" LED DOWNLIGHT PRESCOLITE LF4LEDG4-4LFLED5G4-35K-WT-B24 277V 1 15 W LED 15 VA 0-10V RECESSED
CEILING
1
D3 4" LED DOWNLIGHT WET LISTED WILA LIGHTING 621-4-XTM19-10LM-35K-83-DA60-120-10V-NC-WETD 120V 1 15 W LED 15 VA 0-10V RECESSED
CEILING
D4 6" LED RECESSED WALLWASHER DOWNLIGHT PRESCOLITE LBP6-6LBP-11L-35-WH-WW 277V 1 12 W LED 12 VA 0-10V RECESSED
CEILING
D5 6" LED RECESSED DOWNLIGHT, ADJUSTABLE
SLOPED CEILING, 3500K
PRESCOLITE LFA6LEDG4-6LFALED6G4-35K-WFL45-6C3-SS-WT-B
24
277V 1 21 W LED 21 VA 0-10V RECESSED
CEILING
7-5/8" RFD
D5EM 6" LED RECESSED DOWNLIGHT, ADJUSTABLE
SLOPED CEILING, 3500K, EM INVERTER
PRESCOLITE LFA6LEDG4-6LFALED6G4-35K-WFL45-6C3-SS-WT-B
24-LPS SERIES; PROVIDE ADDITIONAL $100 PER
FIXTURE MATERIAL PRICING ALLOWANCE FOR
EMERGENCY LIGHTING INVERTER
277V 1 21 W LED 21 VA 0-10V RECESSED
CEILING
7-5/8" RFD 11
D6 6" LED DOWNLIGHT, LEVEL GRID CEILING PRESCOLITE LF6LEDG4-6LFLED5G4-35K-WT-B24 277V 1 21 W LED 21 VA 0-10V RECESSED
CEILING
7-5/8" RFD
D6EM 6" LED DOWNLIGHT, LEVEL GRID CEILING,
INTEGRAL EM BATTERY
PRESCOLITE LF6LEDG4-6LFLED5G4-35K-WT-B24-EM 277V 1 21 W LED 21 VA 0-10V RECESSED
CEILING
7-5/8" RFD 11
D7 6" HIGH-ABUSE LED DOWNLIGHT FOR
NATATORIUM APPLICATION
KENALL HRDL6L-19L-35K8-DV-DCC-FW-CSS-TTG UNIV 1 19 W LED 19 VA 0-10V RECESSED
CEILING
6.95" RFD
D7EM 6" HIGH-ABUSE LED DOWNLIGHT FOR
NATATORIUM APPLICATION W/ EM BATTERY
KENALL HRDL6L-19L-35K8-DV-DCC-FW-CSS-TTG-LEL UNIV 1 19 W LED 19 VA 0-10V RECESSED
CEILING
6.95" RFD
F1 4'-0" LED LENSED STRIPLIGHT COLUMBIA LIGHTING LCL-4-35-ML-E-U-S18 UNIV 1 53 W LED 53 VA NA PENDANT
CEILING
F2 8'-0" LED LENSED STRIPLIGHT COLUMBIA LIGHTING LCL-8-35-ML-E-U-S18 UNIV 1 106 W LED 106 VA NA PENDANT
CEILING
F3 4'-0" LED ENCLOSED & GASKETED STRIP COLUMBIA LIGHTING LXEN-4-35-LW-RFA-E-U-XEHC UNIV 1 37 W LED 37 VA NA PENDANT
CEILING
H1 LED GYM HIGH-BAY LUX DYNAMICS LED-GYM-4-UNV-835-HO-LPDW-4'-CUSTOM 277V 1 356 W LED 356 VA 0-10V PENDANT
CEILING
2,8
H1EM LED GYM HIGH-BAY, EMERGENCY BATTERY LUX DYNAMICS LED-GYM-4-UNV-835-HO-EM-LPDW-4'-CUSTOM 277V 1 356 W LED 356 VA 0-10V PENDANT
CEILING
2,8
H2 LED NATATORIUM ARCHITECTURAL HIGH-BAY LUX DYNAMICS LED-WAVE-3-UNV-TOP-835-(2)HO-(1)SO-H4P10-LA
DW-4'-NAT
277V 1 226 W LED 226 VA 0-10V PENDANT
CEILING
4,8
H2EM LED NATATORIUM ARCHITECTURAL HIGH-BAY,
EMERGENCY
LUX DYNAMICS LED-WAVE-3-UNV-TOP-835-(2)HO-(1)SO-EM-H4P10-
LADW-4'-NAT
277V 1 226 W LED 226 VA 0-10V PENDANT
CEILING
4,8
L1A LED SUSPENDED LINEAR WAVE CONVEX BARBICAN 19-4W-3H-CC-16-144R-LF-221-ACW-MFM-SDL-WHT-
6WLF-277V-3500K-80CRI-DB0-10V
277V 1 75 W LED 75 VA 0-10V SUSPENDED
CEILING
12'-0" AFF
L1B LED SUSPENDED LINEAR WAVE CONCAVE BARBICAN 19-4W-3H-CV-16-144R-LF-221-ACW-MFM-SDL-WHT-
6WLF-277V-3500K-80CRI-DB0-10V
277V 1 75 W LED 75 VA 0-10V SUSPENDED
CEILING
12'-0" AFF
L2 LED SUSPENDED LINEAR D/I ALERA LIGHTING LP7-OA-12-35-ML-40-CM-24-ED-U-ZT 277V 1 132 W LED 132 VA 0-10V SUSPENDED
CEILING
L4 4' LED WALL-GRAZE, CABLE MOUNT SUSPENSION
AIMED DOWNWARD TOWARD WALL
INSIGHT LIGHTING MC-6-35K-15-D-PNS-X-48"-REM-NO-BL;
C1/100/PWR/277
277V 1 36 W LED 36 VA NA SUSPENDED
CEILING
9
P1 6" LED CYLINDER PENDANT DOWNLIGHT CONTECH CYL6-2-35K-MVD-CF-P-CLR 277V 1 14 W LED 14 VA 0-10V PENDANT
CEILING
8
P1EM 6" LED CYLINDER PENDANT DOWNLIGHT, W/
INTEGRAL EM BATTERY
CONTECH CYL6-2-35K-MVD-CF-P-CLR; PROVIDE (3) BODINE
ELI-S-100 EM INVERTERS
277V 1 14 W LED 14 VA 0-10V PENDANT
CEILING
8
P3 17" LED PENDANT, FROSTED LENS LOWBAY DELRAY LIGHTING IL7800-750-W35-2 277V 1 50 W LED 50 VA 0-10V PENDANT
CEILING
P3EM 17" LED PENDANT, FROSTED LENS LOWBAY, W/
EM BATTERY PACK
DELRAY LIGHTING IL7800-750-W35-2-EM 277V 1 50 W LED 50 VA 0-10V PENDANT
CEILING
P4 6" LED CYLINDER PENDANT DOWNLIGHT,
CUSTOM COLOR FINISH
CONTECH CYL6-2-35K-MVD-CF-P-CLR-CUSTOM COLOR 277V 1 14 W LED 14 VA 0-10V PENDANT
CEILING
13'-0" BOF 8
P5 DECORATIVE INDUSTRIAL PENDANT HUBBARDTON FORGE 161065-82-ZM349 12V 1 50 W T4 INC 50 VA NA PENDANT
CEILING
P6 DECORATIVE INDUSTRIAL RLM PENDANT BARN LIGHT ELECTRIC C-WHS18-PC-615-SBK-100-WG-615-LED-1250D-300
0K-120V-277V-0-10V
277V 1 48 W LED 48 VA 0-10V PENDANT
CEILING
P7 LARGE SCALE DECORATIVE LOBBY PENDANT EVERGREEN DBL-CYLP35X24-2MED-9-HO-MSH 277V 1 120 W TBD 120 VA TBD PENDANT
CEILING
P8 LARGE 5' DECORATIVE DRUM PENDANT LUMETTA P56017-F3-D865-LED6-277-CXX3 277V 6 19 W LED 113 VA 0-10V PENDANT
CEILING
8
P9 SMALL 3' DECORATIVE DRUM PENDANT LUMETTA P53414-F3-D865-LED3-277-CXX3 277V 3 19 W LED 57 VA 0-10V PENDANT
CEILING
8
R1 2X4 LED D/I TROFFER HE WILLIAMS AT1-24-L55-835-D-DRV-UNV 277V 1 59 W LED 59 VA NA RECESSED
CEILING
R2 2X2 LED D/I TROFFER HE WILLIAMS AT1-22-L30-835-D-DRV-UNV 277V 1 31 W LED 31 VA NA RECESSED
CEILING
R2EM 2X2 LED D/I TROFFER W/ INTEGRAL EM BATTERY HE WILLIAMS AT1-22-L30-835-D-EM/10W-DRV-UNV 277V 1 31 W LED 31 VA NA RECESSED
CEILING
R3 2x2 RECESSED 1" DROP LENS FIXTURE 3G LIGHTING 3G-RKU2401-L2-30K-277-DIM-GC1-DD1 277V 1 31 W LED 28 VA 0-10V RECESSED
CEILING
R4 2x2 RECESSED 2" DROP LENS FIXTURE 3G LIGHTING 3G-RKU2401-L2-30K-277-DIM-GC1-DD2 277V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
R5 2x2 RECESSED 3" DROP LENS FIXTURE 3G LIGHTING 3G-RKU2401-L2-30K-277-DIM-GC1-DD3 277V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
R6 2X2 RECESSED 4" DROP LENS FIXTURE 3G LIGHTING 3G-RKU2401-L2-30K-277-DIM-GC1-DD4 277V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
R7 2X2 RECESSED 5" DROP LENS FIXTURE 3G LIGHTING 3G-RKU2401-L2-30K-277-DIM-GC1-DD5 277V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
R8 2x2 FLUSH LENS FIXTURE FOCAL POINT 3G-RKU2401-L2-30K-277-DIM-GC1-FL 277V 1 31 W LED 31 VA 0-10V RECESSED
CEILING
R9 2'x4' LENSED LED TROFFER, WET RATED,
GASKETED
HE WILLIAMS 50G-S24-L35/835-F-AF12125-DRV-277 277V 1 34 W LED 34 VA 0-10V RECESSED
CEILING
R10 2' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-2'-B-8-35-F-120V-SC-C1 120V 1 9 W LED 9 VA 0-10V RECESSED
CEILING
R11 4' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-4'-B-8-35-F-120V-SC-C1 120V 1 18 W LED 18 VA 0-10V RECESSED
CEILING
R12 6' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-6'-B-8-35-F-120V-SC-C1 120V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
R12EM 6' LINEAR RECESSED LED SLOT FIXTURE, W/ EM
BATTERY
FINELITE HP-4-R-6'-B-8-35-F-120V-SC-C1-EM BATTERY 120V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
R13 8' LINEAR RECESSED LED SLOT FIXTURE (120V) FINELITE HP-4-R-8'-B-8-35-F-120V-SC-C18 120V 1 37 W LED 37 VA 0-10V RECESSED
CEILING
R13A 8' LINEAR RECESSED LED SLOT FIXTURE (277V) FINELITE HP-4-R-8'-B-8-35-F-277V-SC-C18 277V 1 37 W LED 37 VA 0-10V RECESSED
CEILING
R13EM 8' LINEAR RECESSED LED SLOT FIXTURE, W/ EM
BATTERY
FINELITE HP-4-R-8'-B-8-35-F-120V-SC-C1-EM BATTERY 120V 1 37 W LED 37 VA 0-10V RECESSED
CEILING
R14 10' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-10'-B-8-35-F-120V-SC-C1 120V 1 46 W LED 46 VA 0-10V RECESSED
CEILING
R15 15' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-15'-B-8-35-F-120V-SC-C1 120V 1 69 W LED 69 VA 0-10V RECESSED
CEILING
R15A 15' LINEAR RECESSED LED SLOT FIXTURE (277V) FINELITE HP-4-R-15'-B-8-35-F-277V-SC-C1 277V 1 69 W LED 69 VA 0-10V RECESSED
CEILING
R15EM 15' LINEAR RECESSED LED SLOT FIXTURE, W/ EM
BATTERY
FINELITE HP-4-R-15'-B-8-35-F-120V-SC-C1-EM BATTERY 120V 1 69 W LED 69 VA 0-10V RECESSED
CEILING
R16 16' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-16'-B-8-35-F-120V-SC-C1 120V 1 74 W LED 74 VA 0-10V RECESSED
CEILING
R16A 16' LINEAR RECESSED LED SLOT FIXTURE (277V) FINELITE HP-4-R-16'-B-8-35-F-277V-SC-C1 277V 1 74 W LED 74 VA 0-10V RECESSED
CEILING
R20 20' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-20'-B-8-35-F-277V-SC-C1 277V 1 92 W LED 92 VA 0-10V RECESSED
CEILING
R20EM 20' LINEAR RECESSED LED SLOT FIXTURE, W/ EM
BATTERY
FINELITE HP-4-R-20'-B-8-35-F-277V-SC-C1-EM BATTERY 277V 1 92 W LED 92 VA 0-10V RECESSED
CEILING
R22 22' LINEAR RECESSED LED SLOT FIXTURE FINELITE HP-4-R-22'-B-8-35-F-277V-SC-C1 277V 1 101 W LED 101 VA 0-10V RECESSED
CEILING
R22EM 22' LINEAR RECESSED LED SLOT FIXTURE, W/ EM
BATTERY
FINELITE HP-4-R-22'-B-8-35-F-277V-SC-C1-EM BATTERY 277V 1 101 W LED 101 VA 0-10V RECESSED
CEILING
RG1 11' CONTINOUS RECESSED LINEAR LED SLOT
FIXTURE W/ MITERED CORNER
FINELITE HP-4-R-11'-B-8-35-F-120V-FA-SC-C4 120V 1 51 W LED 51 VA 0-10V RECESSED
CEILING
RG4 4' LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-4'-B-8-35-F-120V-C1 120V 1 18 W LED 18 VA 0-10V RECESSED
CEILING
RG6 6' LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-6'-B-8-35-F-120V-C1 120V 1 28 W LED 28 VA 0-10V RECESSED
CEILING
RG8 8' LED RECESSED LINEAR REGRESSED LENS FINELITE HP-4-RG-8'-B-8-35-F-120V-C1 120V 1 37 W LED 37 VA 0-10V RECESSED
CEILING
RG10 10' LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-10'-B-8-35-F-120V-C1 120V 1 46 W LED 46 VA 0-10V RECESSED
CEILING
RG12 12' LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-12'-B-8-35-F-120V-C1 120V 1 55 W LED 55 VA 0-10V RECESSED
CEILING
RG14 14' LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-14'-B-8-35-F-120V-C1 120V 1 64 W LED 64 VA 0-10V RECESSED
CEILING
RG15 15' LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-15'-B-8-35-F-120V-C1 120V 1 69 W LED 69 VA 0-10V RECESSED
CEILING
RG87 8'-7" LED RECESSED LINEAR, REGRESSED LENS FINELITE HP-4-RG-8'-7"-B-8-35-F-120V-C1 120V 1 41 W LED 41 VA 0-10V RECESSED
CEILING
RM1 RECESSED MULTIPLE, SINGLE HEAD LED 3G LIGHTING 3G-RC2LED-10-S-30K-40D-277V-DIM-BT-BG-BK 277V 1 10 W LED 10 VA 0-10V RECESSED
CEILING
RM2 RECESSED MULTIPLE, DOUBLE HEAD LED 3G LIGHTING 3G-RC1LED-10-S-30K-40D-277V-DIM-BT-BG-BK 277V 2 10 W LED 20 VA 0-10V RECESSED
CEILING
T1 6'-0" LED TRACK CONTECH CTL-8070-F-35-D-P; LT-6-P 120V 4 9 W LED 36 VA MLV SUSPENDED
CEILING
12'-0" BOF 9
T2 6'-0" LED TRACK CONTECH CTL-8070-F-35-D-P; LT-6-P 120V 4 9 W LED 36 VA MLV SUSPENDED
CEILING
UC1 UNDERCABINET LED TAPELIGHT PRIMUS LIGHTING ALX4-SP-LED-35K-12-R-IM-W-X' 120V 1 3 W LED NA SURFACE 10
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
10
/
3
1
/
2
0
1
6
1
1
:
2
0
:
0
6
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
Checker
Author
10-31-2016
16003
ELECTRICAL
SCHEDULES
E502
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:158 A
EQUIPMENT:10020 VA 10020 VA TOTAL CONN.:145 A
MOTOR:108447 VA 118805 VA TOTAL EST. LOAD:131001 VA
RECEPTACLE:1080 VA 1080 VA TOTAL CONN. LOAD:120424 VA
LIGHTING:877 VA 1096 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:148 A 145 A 143 A
Total Load:40813 VA 40071 VA 39501 VA
41 -- BUSSED SPACE -- --0 4920 -- -- ---- 42
39 -- BUSSED SPACE -- -- 0 5076 -- -- ---- 40
37 -- BUSSED SPACE -- -- 0 5908 3 45 PANEL 'LA2A' VIA TAA L; E; ... 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 28
25 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 26
23 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 24
21 L L 20 1 414 0 -- -- BUSSED SPACE -- 22
19 L NATATORIUM FOYER AND ENTRY LIGHTING 20 1 324 0 -- -- BUSSED SPACE -- 20
17 -- ---- --13810 0 1 20 SPARE -- 18
15 -- ---- -- 13810 0 1 20 SPARE -- 16
13 M LEISURE CURRENT PUMP #2 (CP-2) 90 3 13810 0 1 20 SPARE -- 14
11 -- ---- --2923 13810 -- -- ---- 12
9 -- ---- -- 2923 13810 -- -- ---- 10
7 M LEISURE CIRCULATION PUMP (LCP-1) 20 3 2923 13810 3 90 LEISURE CURRENT PUMP #1 (CP-1) M 8
5 -- ---- --2019 2019 -- -- ---- 6
3 -- ---- -- 2019 2019 -- -- ---- 4
1 M LEISURE AMENITY PUMP #1 (LAP-1) 15 3 2019 2019 3 15 LEISURE AMENITY PUMP #2 (LAP-2) M 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:
MOUNTING:SURFACE WIRES:4 MAINS RATING:225 A
SUPPLY FROM:MDC PHASES:3 MAINS TYPE:MLO
LOCATION:ELEC 254 VOLTS:480/277 Wye A.I.C. RATING:42,000 AIC
PANEL: HA2A
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:45 A
EQUIPMENT:10020 VA 10020 VA TOTAL CONN.:44 A
MOTOR:4704 VA 4998 VA TOTAL EST. LOAD:16223 VA
RECEPTACLE:1080 VA 1080 VA TOTAL CONN. LOAD:15904 VA
LIGHTING:100 VA 125 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:49 A 43 A 41 A
Total Load:5908 VA 5076 VA 4920 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 28
25 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 26
23 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 24
21 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 22
19 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 20
17 -- SPARE 20 1 0 0 1 20 SPARE -- 18
15 L CHLORINATOR - EXISTING POOL (ECH-3) 20 1 100 0 1 20 SPARE -- 16
13 R RECPTS - POOL MECH RM 20 1 1080 100 1 20 SE-1 AND SE-2 CONTROL PANEL E 14
11 E PPG CHLORINATOR (CH-1) 20 1 1800 1200 1 20 CLEAR COMFORT SUPP TREATMENT (CCS-1) E 12
9 M CHEM CAB EXHAUST BLOWER #2 (CCEB-2) 20 1 1176 200 1 20 AUTO FILL CONTROLLERS E 10
7 E CHEMICAL CONTROLLER (CC-1) 20 1 1200 1176 1 20 CHEM CAB EXHAUST BLOWER #1 (CCEB-1) M 8
5 E LEISURE POOL HEATER (LH-1) 20 1 1800 120 1 20 ACID PUMP (AP-1) E 6
3 E DEFENDER FILTER CONTROLLER (FC-1) 20 1 1800 1800 1 20 DEFENDER FILTER AIR COMPRESSOR (AC-1) E 4
1 M CLEAR COMFORT BOOSTER PUMP #1... 20 1 1176 1176 1 20 SEWAGE EJECTOR PUMP (SE-1,2) M 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:100 A
MOUNTING:SURFACE WIRES:4 MAINS RATING:100 A
SUPPLY FROM:TAA PHASES:3 MAINS TYPE:MCB
LOCATION:ELEC 254 VOLTS:120/208 Wye A.I.C. RATING:22,000 AIC
PANEL: LA2A
(*) PROVIDE GFCI PROTECTED CIRCUIT BREAKER.
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:205 A
EQUIPMENT:16716 VA 16716 VA TOTAL CONN.:206 A
MOTOR:37995 VA 38715 VA TOTAL EST. LOAD:73866 VA
RECEPTACLE:14760 VA 12380 VA TOTAL CONN. LOAD:74315 VA
LIGHTING:4844 VA 6055 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:195 A 210 A 227 A
Total Load:23388 VA 24945 VA 26982 VA
83 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 84
81 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 82
79 L LIGHTING RESTROOMS 20 1 734 0 -- -- BUSSED SPACE -- 80
77 L (*)LIGHTING WOMENS LOCK. & FAM.... 20 1 1559 1000 1 20 HAND DRYER - FAM CHANGING M 78
75 -- ---- -- 832 1000 1 20 HAND DRYER - FAM CHANGING M 76
73 M EF-17 15 2 832 1000 1 20 HAND DRYER - W TOILET 223 M 74
71 -- ---- --920 1000 1 20 HAND DRYER - M TOILETS 233 M 72
69 M EF-2 30 2 920 1500 1 20 FIRE ACCORDIAN DOOR SYSTEM M 70
67 E (*) POOL VACUUM 30 1 1400 500 1 20 VAV CONTROLS TRANSFORMER E 68
65 R RECPTS - POOL AREA, EXTERIOR 20 1 900 1260 1 20 RECPTS - POOL AREA, EXTERIOR R 66
63 R RECPTS - CIRC, FOYER, CUARD CHG 20 1 540 720 1 20 RECPTS - POOL OFFICE R 64
61 E MICROWAVE - GUARDS ROOM 20 1 1000 1000 1 20 REFRIGERATOR - GUARDS ROOM E 62
59 R RECPTS - GUARDS ROOM 20 1 1440 1400 1 30 (*) POOL VACUUM E 60
57 M (*) SUIT SPINNER 20 1 1600 1600 1 30 (*) POOL VACUUM E 58
55 E EWC - MENS LOCKER 20 1 500 900 1 20 RECPTS - MENS LOCKER, MECH A102 R 56
53 -- ---- --1440 360 1 20 AC RECPTS - MENS LOCKER R 54
51 M HAIR DRYER - MENS LOCKER 20 2 1440 1000 1 20 HAND DRYER - MENS LOCKER M 52
49 -- ---- -- 1440 1440 -- -- ---- 50
47 M HAIR DRYER - MENS LOCKER 20 2 1440 1440 2 20 HAIR DRYER - WOMENS LOCKER M 48
45 R RECPTS - WOMENS LOCKER 20 1 900 500 1 20 EWC - WOMENS LOCKER E 46
43 R AC RECPTS - WOMENS LOCKER 20 1 360 360 1 20 AC RECPTS - WOMENS LOCKER R 44
41 M HAND DRYER - WOMENS LOCKER 30 1 1000 1000 1 30 HAND DRYER - WOMENS LOCKER M 42
39 M HAND DRYER - MENS LOCKER 30 1 1000 1440 -- -- ---- 40
37 R RECPTS - FAMILY CHANGING 20 1 1080 1440 2 20 HAIR DRYER - WOMENS LOCKER M 38
35 L (*)LIGHTING MENS LOCKERS 231 20 1 1351 1080 1 20 RECPTS - ROOM 206, 207, 229 R 36
33 R RECPTS - KID WATCH 20 1 900 1200 1 20 (*) POOL LIGHTS L 34
31 R RECEPTS - ROOM 202, 211, 201 20 1 720 1080 1 20 RECPTS - INDOOR PLAY R 32
29 M MOTORIZED DOOR OPENER - VESTIBULE 201 30 1 1000 1000 1 20 MOTORIZED DOOR OPENER - VESTIBULE 201 M 30
27 E MICROWAVE - PARTY ROOM 20 1 1000 1000 1 20 REFRIGERATOR - PARTY ROOM E 28
25 M DISPOSAL - PARTY ROOM 20 1 1176 360 1 20 AC RECPTS - PARTY ROOM R 26
23 R RECPTS - ROOF 20 1 720 1080 1 20 RECPTS - ROOF R 24
21 E HEAT TRACE 20 1 400 350 1 20 HEAT TRACE E 22
19 M EF-5 15 1 696 1656 1 25 EF-14 M 20
17 E UH-6 20 1 96 696 1 15 EF-4 M 18
15 M EF-1 15 1 696 832 -- -- ---- 16
13 E; M UH-1, UH-2, UH-3, CUH-1, CUH-2 15 1 826 832 2 25 EF-6 M 14
11 E GWH-1, GWH-2, GWH-3 15 1 720 200 1 20 TEMPERATURE CONTROL PANEL E 12
9 M CP-3 15 1 528 1176 1 20 PP-1 M 10
7 M CP-1 15 1 528 528 1 15 CP-2 M 8
5 E B-2 15 1 1440 1440 1 20 B-3 E 6
3 M EF-3, TF-3 15 1 431 1440 1 15 B-1 E 4
1 E RP2A 20 1 500 500 1 20 FACP E 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:250 A
MOUNTING:SURFACE WIRES:4 MAINS RATING:400 A
SUPPLY FROM:TPA PHASES:3 MAINS TYPE:MCB
LOCATION:ELEC 254 VOLTS:120/208 Wye A.I.C. RATING:42,000 AIC
PANEL: LP2A
(*) ELECTRICAL EQUIPMENT INDICATED AND ASSOCIATED W ITH THIS SCOPE OF WORK SHALL BE SEPERATELY PRICED AS PART OF ALTERNATE #2.
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:83 A
EQUIPMENT:TOTAL CONN.:76 A
MOTOR:62930 VA 69407 VA TOTAL EST. LOAD:69407 VA
RECEPTACLE:TOTAL CONN. LOAD:62930 VA
LIGHTING:
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:76 A 76 A 76 A
Total Load:20977 VA 20977 VA 20977 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- CF-4A SHUNT TRIP -- -- 0 0 -- -- CF-5A SHUNT TRIP -- 28
25 -- ---- -- 283 283 -- -- ---- 26
23 -- ---- --283 283 -- -- ---- 24
21 M CF-4A 15 3 283 283 3 15 CF-5A M 22
19 -- SPARE 20 1 0 0 -- -- CF-3 SHUNT TRIP -- 20
17 -- ---- --1175 300 -- -- ---- 18
15 -- ---- -- 1175 300 -- -- ---- 16
13 M MAU-1 15 3 1175 300 3 15 CF-3 M 14
11 -- ---- --831 8636 -- -- ---- 12
9 -- ---- -- 831 8636 -- -- ---- 10
7 M P-2 15 3 831 8636 3 50 PDU-1A (*)M 8
5 -- ---- --831 8636 -- -- ---- 6
3 -- ---- -- 831 8636 -- -- ---- 4
1 M P-1 20 3 831 8636 3 40 PDU-2 M 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:
MOUNTING:SURFACE WIRES:4 MAINS RATING:225 A
SUPPLY FROM:MDC PHASES:3 MAINS TYPE:MLO
LOCATION:ELEC 254 VOLTS:480/277 Wye A.I.C. RATING:42,000 AIC
PANEL: HM2A
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
10
/
3
1
/
2
0
1
6
1
1
:
2
0
:
1
2
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
Checker
Author
10-31-2016
16003
ELECTRICAL
SCHEDULES
E503
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:101 A
EQUIPMENT:48305 VA 48305 VA TOTAL CONN.:111 A
MOTOR:16940 VA 17208 VA TOTAL EST. LOAD:84185 VA
RECEPTACLE:26640 VA 18320 VA TOTAL CONN. LOAD:92167 VA
LIGHTING:282 VA 353 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:115 A 112 A 107 A
Total Load:31738 VA 30928 VA 29501 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 28
25 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 26
23 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 24
21 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 22
19 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 20
17 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 18
15 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 16
13 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 14
11 -- SPARE 20 1 0 6440 -- -- ---- 12
9 -- SPARE 20 1 0 6440 -- -- ---- 10
7 -- CF-1, CF-2 SHUNT TRIP -- -- 0 9120 3 45 TBT E; R 8
5 -- ---- --713 22348 -- -- ---- 6
3 -- ---- -- 713 23775 -- -- ---- 4
1 M CF-1, CF-2 15 3 713 21905 3 175 T2B L; E; ... 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:
MOUNTING:SURFACE WIRES:4 MAINS RATING:225 A
SUPPLY FROM:MDC PHASES:3 MAINS TYPE:MLO
LOCATION:ELEC 282 VOLTS:480/277 Wye A.I.C. RATING:65,000 AIC
PANEL: HM2B
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:173 A
EQUIPMENT:30805 VA 30805 VA TOTAL CONN.:189 A
MOTOR:14800 VA 15050 VA TOTAL EST. LOAD:62278 VA
RECEPTACLE:22140 VA 16070 VA TOTAL CONN. LOAD:68027 VA
LIGHTING:282 VA 353 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:183 A 199 A 187 A
Total Load:21905 VA 23775 VA 22348 VA
125 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 126
123 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 124
121 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 122
119 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 120
117 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 118
115 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 116
113 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 114
111 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 112
109 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 110
107 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 108
105 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 106
103 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 104
101 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 102
99 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 100
97 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 98
95 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 96
93 -- SPARE 20 1 0 0 1 20 SPARE -- 94
91 -- SPARE 20 1 0 0 1 20 SPARE -- 92
89 -- SPARE 20 1 0 0 1 20 SPARE -- 90
87 E IRRIGATION CONTROLLER 20 1 500 0 1 20 SPARE -- 88
85 E VAV CONTROLS TRANSFORMER 20 1 500 500 1 20 FIRE SMOKE DAMPER E 86
83 R RECPTS - EXTERIOR SERPENTINE WALL 20 1 900 72 1 20 LOBBY LIGHTING L 84
81 M HAND DRYER - W TEAM LOCKER 20 1 1000 900 1 20 RECPTS - PARKING LOT R 82
79 R RECPTS - W TEAM LOCKER 20 1 360 540 1 20 RECPTS - W TEAM LOCKER, EXTERIOR R 80
77 R RECPTS - POOL STORAGE, M TEAM LOCKER 20 1 900 1000 1 20 HAND DRYER - M TEAM LOCKER M 78
75 R RECEPTS - LOBBY 20 1 900 200 1 20 DOOR HOLD - VESTIBULE A104 E 76
73 R AC RECPTS - COPY 278 20 1 540 900 1 20 RECEPTS - POOL, PARTY ROOM R 74
71 R RECPTS - LAP TRACK 20 1 1440 360 1 20 RECPTS - TRACK R 72
69 R RECPTS - LOBBY FRONT DESK 20 1 1080 540 1 20 RECPTS - ROOM 123, 202 R 70
67 M GYM DIVIDER CURTAIN 20 1 800 200 1 20 LAP TIMER E 68
65 M VOLLEYBALL SLEEVE NORTH 20 1 800 800 1 20 VOLLEYBALL SLEEVE SOUTH M 66
63 M BASKETBALL LIFT SOUTH 20 1 800 800 1 20 BASKETBAL LIFT SOUTHWEST M 64
61 M BASKETBALL LIFT NORTHEAST 20 1 800 800 1 20 BASKETBALL LIFT SOUTHEAST M 62
59 M BASKETBALL LIFT NORTHWEST 20 1 800 800 1 20 BASKETBALL LIFT NORTH M 60
57 R RECPTS - CARDIO, GROUP EX 20 1 1080 1260 1 20 RECPTS - GROUP EX R 58
55 E FLOOR BOX - CARDIO 20 1 750 500 1 20 EWC - CARDIO E 56
53 E FLOOR BOX - CARDIO 20 1 750 750 1 20 FLOOR BOX - CARDIO E 54
51 R RECPTS - ROOM 203, 204, 273, LOBBY 20 1 900 750 1 20 FLOOR BOX - CARDIO E 52
49 R RECPTS - ROOM 278, 282 20 1 1080 540 1 20 RECPTS - DESK STAFF R 50
47 R AC RECPTS - ADMIN 271 20 1 540 1000 1 20 COPIER - ROOM 278 E 48
45 E PROJECTOR - CONFERENCE 275 20 1 1000 500 1 20 MOTORIZED SCREEN - CONFERENCE 275 M 46
43 E MICROWAVE - CONFERENCE 275 20 1 1000 180 1 20 AC RECPT - CONFERENCE 275 R 44
41 R RECPTS - CONFERENCE 275 20 1 1080 1000 1 20 REFRIGERATOR - CONFERENCE 275 E 42
39 R RECPTS - EXEC DIR 281 20 1 1260 1080 1 20 RECPTS - ROOM 279, 277 R 40
37 R RECPTS - FINANCE 287 20 1 1080 1440 1 20 RECPTS - ROOM 285, 283 R 38
35 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 36
33 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 34
31 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 32
29 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 30
27 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 28
25 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 26
23 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 24
21 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 22
19 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 20
17 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 18
15 E FITNESS EQUIPMENT 20 1 750 750 1 20 FITNESS EQUIPMENT E 16
13 R RECPTS - ROOF 20 1 540 720 1 20 RECPTS - ROOF R 14
11 E HEAT TRACE 20 1 1460 200 1 20 HEAT TRACE E 12
9 M EF-12 15 1 696 696 1 15 EF-15 M 10
7 M EF-10 15 1 696 696 1 15 EF-11 M 8
5 M CEILING FANS M/P GROUP EX 262 20 1 1000 696 1 15 EF-9 M 6
3 L LIGHTING RESTROOMS 203, 204 20 1 210 1623 -- -- ---- 4
1 M EF-7, EF-8, TF-1 15 1 620 1623 2 20 DSCU-1 E 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:400 A
MOUNTING:SURFACE WIRES:4 MAINS RATING:400 A
SUPPLY FROM:T2B PHASES:3 MAINS TYPE:MCB
LOCATION:ELEC 282 VOLTS:120/208 Wye A.I.C. RATING:22,000 AIC
PANEL: LP2B
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:37 A
EQUIPMENT:TOTAL CONN.:30 A
MOTOR:TOTAL EST. LOAD:31005 VA
RECEPTACLE:TOTAL CONN. LOAD:24804 VA
LIGHTING:24804 VA 31005 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:31 A 41 A 18 A
Total Load:8186 VA 10822 VA 5084 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- SPARE 20 1 0 0 1 20 SPARE -- 30
27 -- SPARE 20 1 0 0 1 20 SPARE -- 28
25 -- SPARE 20 1 0 0 1 20 SPARE -- 26
23 -- SPARE 20 1 0 53 1 20 LIGHTING ELEVATOR SHAFT L 24
21 -- SPARE 20 1 0 2061 1 20 LIGHTING EXTERIOR SITE AREA L 22
19 -- SPARE 20 1 0 1083 1 20 LIGHTING EXTERIOR PEDESTRIAN &... L 20
17 L LIGHTING NATATORIUM EAST 20 1 1582 1437 1 20 LIGHTING EQUIP RMS, GUARDS L 18
15 L LIGHTING NATATORIUM NORTHEAST 20 1 2524 1808 1 20 LIGHTING NATATORIUM SOUTH L 16
13 L LIGHTING INDOOR PLAY 20 1 534 0 1 20 SPARE -- 14
11 L LIGHTING SOUTH GYM EMERGENCY 20 1 1068 683 1 20 LIGHTING M/P GROUP EX 262 L 12
9 L LIGHTING NORTH GYM 131 20 1 1068 2492 1 20 LIGHTING SOUTH GYM L 10
7 L LIGHTING ABOVE TRACK 20 1 1945 2492 1 20 LIGHTING NORTH GYM 131 L 8
5 -- SPARE 20 1 0 261 1 20 LIGHTING EXIT STAIR 133 L 6
3 -- SPARE 20 1 0 869 1 20 LIGHTING LOBBY L 4
1 -- SPARE 20 1 0 2133 1 20 LIGHTING CONFERENCE/OFFICES L 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:
MOUNTING:SURFACE WIRES:4 MAINS RATING:225 A
SUPPLY FROM:MDC PHASES:3 MAINS TYPE:MLO
LOCATION:ELEC 282 VOLTS:480/277 Wye A.I.C. RATING:22,000 AIC
PANEL: HL2B
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
10
/
3
1
/
2
0
1
6
1
1
:
2
0
:
1
8
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
Checker
Author
10-31-2016
16003
ELECTRICAL
SCHEDULES
E504
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:74 A
EQUIPMENT:27411 VA 27411 VA TOTAL CONN.:86 A
MOTOR:11682 VA 12270 VA TOTAL EST. LOAD:61421 VA
RECEPTACLE:32040 VA 21020 VA TOTAL CONN. LOAD:71709 VA
LIGHTING:576 VA 720 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:97 A 85 A 79 A
Total Load:26762 VA 23189 VA 21758 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 28
25 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 26
23 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 24
21 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 22
19 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 20
17 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 18
15 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 16
13 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 14
11 -- SPARE 20 1 0 0 1 20 SPARE -- 12
9 -- SPARE 20 1 0 0 1 20 SPARE -- 10
7 -- SPARE 20 1 0 0 1 20 SPARE -- 8
5 -- ---- --19678 2080 -- -- ---- 6
3 -- ---- -- 17849 5340 -- -- ---- 4
1 L; E; ... T1B 175 3 20598 6164 3 45 T1K E; R; M 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:
MOUNTING:SURFACE WIRES:4 MAINS RATING:225 A
SUPPLY FROM:MDC PHASES:3 MAINS TYPE:MLO
LOCATION:ELEC 109 VOLTS:480/277 Wye A.I.C. RATING:65,000 AIC
PANEL: HM1B
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:12 A
EQUIPMENT:TOTAL CONN.:10 A
MOTOR:TOTAL EST. LOAD:10240 VA
RECEPTACLE:TOTAL CONN. LOAD:8192 VA
LIGHTING:8192 VA 10240 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:16 A 4 A 8 A
Total Load:4316 VA 978 VA 2135 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 28
25 -- SPARE 20 1 0 0 1 20 SPARE -- 26
23 -- SPARE 20 1 0 0 1 20 SPARE -- 24
21 -- SPARE 20 1 0 0 1 20 SPARE -- 22
19 -- SPARE 20 1 0 0 1 20 SPARE -- 20
17 -- SPARE 20 1 0 0 1 20 SPARE -- 18
15 L LIGHTING GYM 131 20 1 300 252 1 20 LIGHTING L 16
13 L LIGHTING STRENGTH 20 1 1034 585 1 20 LIGHTING HP GROUP EX 124 L 14
11 L LIGHTING ROOMS 107, 111, 109, 105, 104, 106 20 1 1125 1010 1 20 LIGHTING RM 115, 116, 118, 113, 112, 122, 121 L 12
9 L LIGHTING RECEPTION DESK LOUNGE 102 20 1 84 342 1 20 LIGHTING COMMUNITY KITCHEN L 10
7 L LIGHTING LOUNGE 102 20 1 1075 1623 1 20 LIGHTING COMMUNITY ROOMS L 8
5 -- SPARE 20 1 0 0 1 20 SPARE -- 6
3 -- SPARE 20 1 0 0 1 20 SPARE -- 4
1 -- SPARE 20 1 0 0 1 20 SPARE -- 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:
MOUNTING:SURFACE WIRES:4 MAINS RATING:100 A
SUPPLY FROM:MDC PHASES:3 MAINS TYPE:MLO
LOCATION:ELEC 109 VOLTS:480/277 Wye A.I.C. RATING:22,000 AIC
PANEL: HL1B
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:136 A
EQUIPMENT:17915 VA 17915 VA TOTAL CONN.:161 A
MOTOR:9754 VA 10342 VA TOTAL EST. LOAD:48917 VA
RECEPTACLE:29880 VA 19940 VA TOTAL CONN. LOAD:58125 VA
LIGHTING:576 VA 720 VA
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:174 A 149 A 166 A
Total Load:20598 VA 17849 VA 19678 VA
125 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 126
123 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 124
121 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 122
119 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 120
117 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 118
115 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 116
113 -- SPARE 20 1 0 0 1 20 SPARE -- 114
111 -- SPARE 20 1 0 0 1 20 SPARE -- 112
109 -- SPARE 20 1 0 0 1 20 SPARE -- 110
107 -- SPARE 20 1 0 0 1 20 SPARE -- 108
105 -- SPARE 20 1 0 0 1 20 SPARE -- 106
103 -- SPARE 20 1 0 0 1 20 SPARE -- 104
101 -- SPARE 20 1 0 0 1 20 SPARE -- 102
99 -- SPARE 20 1 0 0 1 20 SPARE -- 100
97 -- SPARE 20 1 0 0 1 20 SPARE -- 98
95 -- SPARE 20 1 0 0 1 20 SPARE -- 96
93 -- SPARE 20 1 0 0 1 20 SPARE -- 94
91 -- SPARE 20 1 0 0 1 20 SPARE -- 92
89 -- SPARE 20 1 0 0 1 20 SPARE -- 90
87 -- SPARE 20 1 0 0 1 20 SPARE -- 88
85 -- SPARE 20 1 0 0 1 20 SPARE -- 86
83 L LTG - MONUMENT SIGN 20 1 100 0 1 20 SPARE -- 84
81 R RECPT - ELEV MECH 118 20 1 180 0 1 20 SPARE -- 82
79 E VAV CONTROLS TRANSFORMER 20 1 500 600 1 20 ELEVATOR CAB E 80
77 L L MEN 105 20 1 476 500 1 20 FIRE SMOKE DAMPER E 78
75 L; R RECPTS - ELEVATOR PIT 20 1 180 348 1 20 EF-13 M 76
73 E CONTROL PANEL - GYM DIVIDER, HOOP ADJ 20 1 400 1176 1 20 SP-1 M 74
71 E DOOR HOLD - EXIT STAIR S10 20 1 200 200 1 20 DOOR HOLD - EMPLOYEE ENTRANCE E 72
69 R RECPTS - GYM NORTH 20 1 720 1260 1 20 RECPTS - GYM STORAGE, EXTERIOR R 70
67 E RECPT - GYM SCOREBOARD 20 1 500 1540 1 20 RECPTS - GYM SOUTH E; R 68
65 E GYM SCOREBOARD 20 1 500 180 1 20 RECPT - GYM SCOREBOARD R 66
63 M RECPT - MP GROUP EX FAN 20 1 500 1080 1 20 RECPTS - STRENGTH 123 R 64
61 R RECPTS - MP GROUP EX 20 1 900 500 1 20 RECPT - MP GROUP EX FAN M 62
59 R DED RECPT - GAMES 20 1 180 1080 1 20 RECPTS - MP GROUP EX R 60
57 R DED RECPT - GAMES 20 1 180 180 1 20 DED RECPT - GAMES R 58
55 R DED RECPT - GAMES 20 1 180 180 1 20 DED RECPT - GAMES R 56
53 R DED RECPT - GAMES 20 1 180 180 1 20 DED RECPT - GAMES R 54
51 R DED RECPT - GAMES 20 1 180 1000 1 20 PROJECTOR - JR GOLF E 52
49 E EWC - STRENGTH 20 1 500 360 1 20 RECPTS - JR GOLF R 50
47 R AC RECPT - KID WATCH 288 20 1 180 1000 1 20 PROJECTOR - GOLF SIMULATOR E 48
45 R RECPTS - MECH 116, STRENGTH 20 1 1080 540 1 20 RECPTS - JR GOLF R 46
43 E SUMP PUMP CONTROL PANEL 20 1 200 360 1 20 RECPTS - JR GOLF R 44
41 M MOTORIZED SCREEN - CLASSROOM 114 20 1 500 1080 1 20 RECPTS - STRENGTH 123 R 42
39 R RECPTS - KITCHEN 112, CLASSROOM 20 1 1440 900 1 20 RECPTS - RECV/STOR, MECH R 40
37 -- ---- -- 2500 360 1 20 AC RECPT - CLASSROOM 114 R 38
35 E RANGE - KITCHEN 112 30 2 2500 1000 1 20 PROJECTOR - CLASSROOM 114 E 36
33 M DISPOSAL - KITCHEN 112 20 1 1176 180 1 20 AC RECPT - KITCHEN 112 R 34
31 E REFRIGERATOR - KITCHEN 112 20 1 1000 180 1 20 MICROWAVE - KITCHEN 112 R 32
29 M MOTORIZED DOOR OPENER - VESTIBULE 101 20 1 2352 180 1 20 AC RECPT - KITCHEN 112 R 30
27 R RECPTS - STRENGTH 20 1 900 180 1 20 AC RECPT - KITCHEN 112 R 28
25 R RECPTS - LOUNGE, ELEC 109 20 1 900 2352 1 20 MOTORIZED DOOR OPENER - VESTIBULE 101 M 26
23 R RECPTS - LOUNGE DESK 20 1 1080 500 1 20 EWC - STRENGTH E 24
21 R RECPTS - STAFF ROOM 107 20 1 900 720 1 20 RECPTS - LOUNGE DESK R 22
19 R RECPTS - STAFF ROOM 107 20 1 1080 900 1 20 RECPTS - P&R DIRECTOR R 20
17 M TF-2 15 1 350 900 1 20 RECPTS - STAFF ROOM 107 R 18
15 E FIREPLACE IGNITION SWITCH 20 1 500 720 1 20 RECPTS - RESTROOMS 104, 105 R 16
13 E EWC - LOUNGE 20 1 500 180 1 20 FLOOR BOX - LOUNGE R 14
11 M MOTORIZED SCREEN - COMMUNITY ROOM 20 1 500 1620 1 20 RECPTS - LOUNGE R 12
9 R FLOOR BOXES - COMMUNITY ROOM 20 1 360 1000 1 20 PROJECTOR - COMMUNITY ROOM E 10
7 R FLOOR BOXES - COMMUNITY ROOM 20 1 360 360 1 20 FLOOR BOXES - COMMUNITY ROOM R 8
5 R RECPTS - COMMUNITY ROOM 20 1 1080 1080 1 20 RECPTS - COMMUNITY ROOM R 6
3 E CUH-3, UH-4 15 1 365 1080 1 20 RECPTS - COMMUNITY ROOM, EXTERIO R 4
1 E CUH-4, CUH-5, UH-5 15 1 950 1080 1 20 RECPTS - COMMUNITY ROOM R 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:400 A
MOUNTING:SURFACE WIRES:4 MAINS RATING:400 A
SUPPLY FROM:T1B PHASES:3 MAINS TYPE:MCB
LOCATION:ELEC 109 VOLTS:120/208 Wye A.I.C. RATING:14,000 AIC
PANEL: LP1B
AE DESIGN
Integrated Lighting and Electrical Solutions
1900 Wazee Street #350 Denver, CO 80202 303.296.3034
aedesign-inc.com
SCALE:
ISSUE DATE:
DRAWN BY:
REV'D BY:
PROJECT #:
0123456789101112
A
B
C
D
E
F
G
H
I
J
O H L S O N L A V O I E
C O L L A B O R A T I V E
616 EAST SPEER BOULEVARD
DENVER, COLORADO
80203
T: 303.294.9244
F: 303.294.9440
www.olcdesigns.com
0123456789101112
SHEET #:
SHEET TITLE:
NO. DATE: TITLE/PURPOSE:
6.
5.
4.
3.
2.
1.
7.
8.
9.
10.
11.
12.
10-31-16 PERMIT SET
Project #: 3256.00
10-31-2016
10
/
3
1
/
2
0
1
6
1
1
:
2
0
:
1
9
A
M
C:
\
U
s
e
r
s
\
t
k
i
e
l
t
y
\
D
o
c
u
m
e
n
t
s
\
3
2
5
6
.
0
0
-
E
V
C
C
E
l
e
c
C
e
n
t
ra
l
_
t
k
i
e
l
t
y
@
a
e
d
e
s
i
g
n
-
i
n
c
.
c
o
m
.
r
v
t
ES
T
E
S
V
A
L
L
E
Y
C
O
M
M
U
N
I
T
Y
C
E
N
T
E
R
Checker
Author
10-31-2016
16003
ELECTRICAL
SCHEDULES
E505
66
0
C
O
M
M
U
N
I
T
Y
D
R
I
V
E
ES
T
E
S
P
A
R
K
,
C
O
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:39 A
EQUIPMENT:9496 VA 9496 VA TOTAL CONN.:38 A
MOTOR:1928 VA 2378 VA TOTAL EST. LOAD:14034 VA
RECEPTACLE:2160 VA 2160 VA TOTAL CONN. LOAD:13584 VA
LIGHTING:
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:56 A 49 A 17 A
Total Load:6164 VA 5340 VA 2080 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 30
27 -- SPARE 20 1 0 0 -- -- BUSSED SPACE -- 28
25 -- SPARE 20 1 0 0 1 20 SPARE -- 26
23 -- KH-1 SHUNT TRIP SPACE -- --0 0 1 20 SPARE -- 24
21 M KH-1 20 1 1800 0 1 20 SPARE -- 22
19 M EF-16 15 1 128 0 1 20 SPARE -- 20
17 R AC RECPT - COMMUNITY KITCHEN 20 1 540 0 1 20 SPARE -- 18
15 R AC RECPT - COMMUNITY KITCHEN 20 1 180 180 1 20 AC RECPT - COMMUNITY KITCHEN R 16
13 E REFRIGERATOR - COMMUNITY KITCHEN 20 1 1000 360 1 20 AC RECPT - COMMUNITY KITCHEN R 14
11 R AC RECPT - COMMUNITY KITCHEN 20 1 180 1000 1 20 REFRIGERATOR - COMMUNITY KITCHEN E 12
9 -- ---- -- 1000 1000 -- -- ---- 10
7 E OVEN - COMMUNITY KITCHEN 30 2 1000 1000 2 30 OVEN - COMMUNITY KITCHEN E 8
5 R AC RECPT - COMMUNITY KITCHEN 20 1 180 180 1 20 AC RECPT - COMMUNITY KITCHEN R 6
3 R AC RECPT - COMMUNITY KITCHEN 20 1 180 1000 1 20 MICROWAVE - COMMUNITY KITCHEN E 4
1 R AC RECPT - COMMUNITY KITCHEN 20 1 180 2496 1 30 DISHWASHER - COMMUNITY KITCHEN E 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:100 A
MOUNTING:SURFACE WIRES:4 MAINS RATING:100 A
SUPPLY FROM:T1K PHASES:3 MAINS TYPE:MCB
LOCATION:ALT KITCHEN 142 VOLTS:120/208 Wye A.I.C. RATING:22,000 AIC
PANEL: LK1B
NOTES:
KITCH EQUIP:TOTAL EST. DEMAND:61 A
EQUIPMENT:17500 VA 17500 VA TOTAL CONN.:61 A
MOTOR:TOTAL EST. LOAD:22000 VA
RECEPTACLE:4500 VA 4500 VA TOTAL CONN. LOAD:22000 VA
LIGHTING:
CCT TYPE:LOAD DEMAND LOAD PANEL TOTALS
LEGEND
Total Amps:76 A 54 A 54 A
Total Load:9120 VA 6440 VA 6440 VA
41 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 42
39 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 40
37 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 38
35 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 36
33 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 34
31 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 32
29 -- BUSSED SPACE -- --0 0 -- -- BUSSED SPACE -- 30
27 -- BUSSED SPACE -- -- 0 0 -- -- BUSSED SPACE -- 28
25 -- SPARE 20 1 0 0 1 20 SPARE -- 26
23 -- SPARE 20 1 0 0 1 20 SPARE -- 24
21 -- SPARE 20 1 0 0 1 20 SPARE -- 22
19 E TWISTLOCK RECPT - LAN IT RACK 30 1 2500 0 1 20 SPARE -- 20
17 E TWISTLOCK RECPT - LAN IT RACK 30 1 2500 2500 1 30 TWISTLOCK RECPT - LAN IT RACK E 18
15 E TWISTLOCK RECPT - LAN IT RACK 30 1 2500 2500 1 30 TWISTLOCK RECPT - LAN IT RACK E 16
13 E TWISTLOCK RECPT - LAN IT RACK 30 1 2500 2500 1 30 TWISTLOCK RECPT - LAN IT RACK E 14
11 R QUAD RECPT - LAN IT RACK 20 1 360 360 1 20 QUAD RECPT - LAN IT RACK R 12
9 R QUAD RECPT - LAN IT RACK 20 1 360 360 1 20 QUAD RECPT - LAN IT RACK R 10
7 R QUAD RECPT - LAN 20 1 360 360 1 20 QUAD RECPT - LAN IT RACK R 8
5 R QUAD RECPT - LAN 20 1 360 360 1 20 QUAD RECPT - LAN R 6
3 R QUAD RECPT - LAN 20 1 360 360 1 20 QUAD RECPT - LAN R 4
1 R RECPTS - IT ROOM 20 1 540 360 1 20 QUAD RECPT - LAN R 2
CKT
CCT
TYPE LOAD DESCRIPTION TRIP POLES
A B C
POLES TRIP LOAD DESCRIPTION
CCT
TYPE CKT
Notes:
ENCLOSURE:TYPE 1 MCB RATING:100 A
MOUNTING:SURFACE WIRES:4 MAINS RATING:100 A
SUPPLY FROM:TBT PHASES:3 MAINS TYPE:MCB
LOCATION:LAN 276 VOLTS:120/208 Wye A.I.C. RATING:10,000 AIC
PANEL: LT2B