November 30, 2016
RLH Engineering, Inc.
541 East Garden Drive, Unit S
Windsor, Colorado 80550
Attn: Mr. Chuck Jordan (cjordan@rlhengineering.com)
Owner’s Representative for EVRPD
Re: Construction Observation and Testing Services – Submittal No. 2
Proposed Estes Valley Community Center – North of Existing Aquatics Center
690 Big Thompson Avenue - Southeast of Manford Drive and Community Drive
Estes Park, Colorado
EEC Project No. 1164046
Mr. Jordan:
As requested, during the period October 24 through November 19, 2016, Earth Engineering
Consultants, LLC (EEC) personnel provided construction observation and testing services for the
proposed Estes Valley Community Center project planned for construction at 690 Big Thompson
Avenue in Estes Park, Colorado. The services provided during the referenced period were on a part-
time/as-needed basis and included field density testing and laboratory testing of roadway improvement
subgrade, aggregate base course (HMA) and hot mix asphalt (HMA) pavement materials, proof roll
observations of prepared subgrade and ABC sections, as well as testing of cast-in-place concrete for
the referenced project. The results of the site observations and testing services completed by EEC
personnel during the referenced period are included with this report.
Observation, Field Density, and Laboratory Testing Services
During the referenced period, EEC personnel performed field density tests on roadway improvement
subgrade and ABC materials which were prepared/placed and compacted as described herein, prior to
and/or during our site visits. The field density tests were completed at random locations and elevations
within the areas tested and were performed in general accordance with ASTM Specification D6938.
The field density test results and approximate locations of each test completed during the referenced
period are shown on the attached summary sheet and associated site diagrams. The field density test
results conformed to the project specific compaction requirement of at least 95% of standard Proctor
maximum dry density (ASTM D698).
During the referenced period, EEC personnel obtained a representative sample of the imported ABC
pavement materials (EEC Sample ID “C”) for laboratory evaluation of the moisture-density
relationship and classification of the materials. Laboratory testing performed included standard
4396 G REENFIELD D RIVE
W INDSOR, C OLORADO80550
(970) 545-3908 FAX (970) 663-0282
www.earth-engineering.com
Earth Engineering Consultants, LLC
EEC Project No. 1164046
Estes Valley Community Center – Estes Park, Colorado
November 30, 2016
Page 2
Proctor density (ASTM Specification D698), Atterberg limits (ASTM Specification D4318) and
washed sieve analysis (ASTM Specifications C117 and C136) tests.
Summary of Laboratory Compaction Characteristics and Classification of Soils
Standard Proctor Density Soil Classification
Sample ID
Optimum Moisture Maximum Dry LiquidPlastic % (-) No. 200
Description
Content, % Density, PCF LimitIndex Sieve
ABC – Silty, Sand with
C 9.5 130.0 NL NP 16.8
Gravel (SM-SW)
Proof roll observations of the prepared subgrade and ABC materials were also performed on October
28, 2016, and November 1, and 2, 2016 along the interior roadway alignments with minimal
deflections and/or rutting/pumping conditions observed. The subgrade and ABC sections appeared
suitable for placement of the subsequent hot mix asphalt (HMA) pavement materials, which was
placed on November 2, and 3, 2016, results of which are provided herein.
Hot Mix Asphalt (HMA) Paving Observations and Testing
During the referenced period, EEC personnel observed paving operations and obtained a sample of the of
the approved Grading S pavement materials from the site during paving operations of the on-site pavement
improvements as described herein. Laboratory testing for the collected HMA samples included
determination of the binder content (by means of the ignition oven ASTM Specification D6307) and
washed sieve analysis of the extracted aggregates (ASTM Specifications C117 and C136). The percent
asphaltic cement (AC) content and extracted aggregate gradation, as presented herein, were performed
without an ignition oven calibration of the aggregate and AC materials used to produce the Grading S
HMA materials. The uncorrected HMA laboratory test results were within the acceptable oil content range
for each mix (i.e., within (+/-) 0.3% of optimum AC content). For the extracted aggregate portion, the
results generally were within the approved job mix formula tolerances for the Martin Marietta (MM)
Grading S Mix ID Nos. 5493. Results of the laboratory tests completed by EEC personnel are indicated on
the attached summary sheets.
After compaction of the HMA pavement materials, EEC personnel performed density tests on the in-place
pavement materials using a nuclear moisture-density gauge. The density tests were completed at random
locations as shown on the enclosed summary sheet within the pavement improvement areas, and were
performed in general accordance with ASTM Specification D2950. Results of the field density tests
completed during the referenced period are indicated on the attached summary sheet. Those test results
were within the project compaction requirements of 92% to 96% of the material’s maximum theoretical
specific gravity (Rice Value) as provided by MM.
EARTH ENGINEERING CONSULTANTS, LLC
SUMMARY OF FIELD DENSITY TESTS
Project Name:New Community CenterProject No: 1164046
Location: Estes Park, ColoradoDate: November 2016
Proctor DesignationABC
Maximum Dry Density (pcf)126.5123.7130.0
Optimum Moisture Content (%)10.0%10.0%9.5%
Required Moisture VarianceN/AN/AN/A
Required Percent Compaction95%95%95%
Laboratory MethodASTM D-698ASTM D-698ASTM D-698
Compliance with
Field Test Results
Project Specs
Approximate Test Location / Notes
Moisture %Comp.
Elev. / Lift Material Percent Dry
(Pass / (Pass /
No.(Proctor)MoistureDensity
Fail)Fail)
2110/251Curb & Gutter Subgrade - See DiagramFSGA7.5%123.5-2.5%98%N/APass
2210/252Curb & Gutter Subgrade - See DiagramFSGA6.9%124.1-3.1%98%N/APass
2310/253Curb & Gutter Subgrade - See DiagramFSGA6.8%123.8-3.2%98%N/APass
encountered undisutrbed granite bedrock
2410/261Curb & Gutter Subgrade - See DiagramFSGPass
2510/262Curb & Gutter Subgrade - See DiagramFSGB4.9%126.5-5.1%102%N/APass
2610/263Curb & Gutter Subgrade - See DiagramFSGB6.4%120.8-3.6%98%N/APass
2710/264Curb & Gutter Subgrade - See DiagramFSGB6.9%121.2-3.1%98%N/APass
2811/11Street Subgrade - See Diagram-0.5A4.0%123.7-6.0%98%N/APass
2911/21Base - See DiagramFSGC6.9%129.3-2.6%99%N/APass
3011/22Base - See DiagramFSGC5.3%128.0-4.2%98%N/APass
3111/23Base - See DiagramFSGC6.9%125.2-2.6%96%N/APass
3211/24Base - See DiagramFSGC6.4%125.4-3.1%96%N/APass
3311/25Base - See DiagramFSGC6.5%128.1-3.0%99%N/APass
3411/26Base - See DiagramFSGC6.9%125.1-2.6%96%N/APass
3511/27Base - See DiagramFSGC6.5%129.5-3.0%100%N/APass
3611/28Base - See DiagramFSGC5.3%130.5-4.2%100%N/APass
3711/29Base - See DiagramFSGC5.9%127.8-3.6%98%N/APass
3811/210Base - See DiagramFSGC7.1%128.1-2.4%99%N/APass
3911/151Roadway Subgrade - STA 0+70, S of Center-1.0A3.6%120.8-6.4%95%N/APass
4011/152Roadway Subgrade - STA 1+15, N of Center-2.0A5.6%125.1-4.4%99%N/APass
4111/153Roadway Subgrade - STA 1+70, Center-1.0A6.6%119.9-3.4%95%N/APass
4211/154Roadway Subgrade - STA 2+20, N of Center-1.5A4.8%119.8-5.2%95%N/APass
4311/155Roadway Subgrade - STA 2+70, S of Center-1.0A3.0%120.6-7.0%95%N/APass
4411/156Roadway Subgrade - STA 3+20, N of Center-1.5A5.2%122.8-4.8%97%N/APass
4511/157Roadway Subgrade - STA 3+50, Center-1.0A6.3%123.3-3.7%97%N/APass
4611/158Roadway Subgrade - STA 3+90, Center-1.0A5.8%122.9-4.2%97%N/APass
4711/159Street Subgrade - STA 0+70, 20' N of Center-0.5B6.3%123.8-3.7%100%N/APass
4811/1510Street Subgrade - STA 1+20, 20' N of Center-2.0B5.3%122.6-4.7%99%N/APass
4911/1511Street Subgrade - STA 1+65, 5' N of Center-1.5B8.3%124.1-1.7%100%N/APass
5011/1512Street Subgrade - STA 2+20, 20' N of Center-2.0B8.1%121.5-1.9%98%N/APass
5111/1513Street Subgrade - STA 2+60, 20' N of Center-1.5B8.1%121.0-1.9%98%N/APass
5211/161Street Subgrade - STA 0+70, 10' N of CenterFSGB5.9%128.0-4.1%103%N/APass
5311/162Street Subgrade - STA 1+30, CenterFSGB6.9%126.6-3.1%102%N/APass
5411/163Street Subgrade - STA 1+70, 15' N of CenterFSGB6.3%127.6-3.7%103%N/APass
5511/164Street Subgrade - STA 2+20, 10' S of CenterFSGB8.3%127.3-1.7%103%N/APass
5611/165Street Subgrade - STA 2+70, 10' N of Center-1.5B6.6%124.4-3.4%101%N/APass
5711/166Street Subgrade - STA 3+20, 10' N of Center-2.0B6.3%126.3-3.7%102%N/APass
10
7
7
11
8 HC8
HC
10
44
7
12
15
7
4 HC4
HC
9
9
4 HC
4
4
HC
Field Density Test Location Diagram
New Community Center - Estes Park, Colorado
EEC Project #: 1164046
Fill, Subgrade, & Aggregate Base
EARTH ENGINEERING CONSULTANTS, LLC
Earth Engineering Consultants, LLC
Summary of Laboratory Classification/ Moisture-Density Relationship
145
Material Designation:
C
Sample Location:
LG Everist Pit Class 5
LG Everist Pit Class 5
Description:
140
Atterberg Limits (ASTM D-4318)
Liquid Limit:
No Limit (NL)
Plastic Limit:
Non Plastic (NP)
135
Plasticity Index:
Non Plastic (NP)
Passing No. 200 Sieve (AASHTO T 11/ASTM C 117):16.8%
130
Standard Proctor (ASTM D-698)
Maximum Dry Density:
130.0 pcf
9.5%
Optimum Moisture Content:
125
Curves for 100% Saturation
For Specific Gravity Equal to:
120
2.80
2.70
115
2.60
110
Dry Density (Pounds per Cubic Foot)
105
100
95
90
05101520253035
Percent Moisture
Rock Correction (AASHTO T 224)
RetainedOptimum Moisture Content
Proctor DesignationMaximum Dry Density (pcf)
3/4"(%)
0%O125.08.0
10%O-10126.97.2
20%O-20128.86.4
30%O-30130.95.6
Project:New Community Center - Estes Park Recreation and Park District
Estes Park, Colorado
Project No:1164046
DateNovember 2016
Earth Engineering Consultants, LLC
Summary of Laboratory Gradation Test
100%
90%
80%
70%
60%
50%
40%
Percent Finer by Weight
30%
20%
10%
0%
1001010.10.010.001
Grain Size in Millimeters
Sieve SizePercent Passing
No. 469%
No. 1055%
No. 4030%
No. 20016.8%
Material Designation:C
Sample Location:LG Everist Pit Class 5
Material Description:LG Everist Pit Class 5
Project:New Community Center - Estes Park Recreation and Park District
Estes Park, Colorado
Project No:1164046
DateNovember 2016
EARTH ENGINEERING CONSULTANTS, LLC
SUMMARY OF ASPHALT DENSITY TESTS
Project Name:New Community Center - Estes Park Recreation & Park DistrictProject No: 1164046
Location:Estes Park, ColoradoDate:November 2016
Material Designation
S
Rice Value
153.0
Compliance With
Field Test Results
Project Specifications
Approximate Test Location/Notes
Measured Gauge RequiredPass or
Lift No.DensityCorrection% Comp.Fail
See Diagram
111/211stS142.20.0142.293%92-96%Pass
See Diagram
211/221stS141.30.0141.392%92-96%Pass
See Diagram
311/231stS146.20.0146.296%92-96%Pass
See Diagram
411/241stS141.20.0141.292%92-96%Pass
See Diagram
511/251stS144.70.0144.795%92-96%Pass
See Diagram
611/261stS143.40.0143.494%92-96%Pass
See Diagram
711/271stS146.30.0146.396%92-96%Pass
See Diagram
811/281stS142.10.0142.193%92-96%Pass
See Diagram
911/291stS143.10.0143.194%92-96%Pass
See Diagram
1011/2101stS144.40.0144.494%92-96%Pass
See Diagram
1111/2111stS142.20.0142.293%92-96%Pass
See Diagram
1211/311stS140.40.0140.492%92-96%Pass
See Diagram
1311/321stS140.50.0140.592%92-96%Pass
See Diagram
1411/331stS142.10.0142.193%92-96%Pass
See Diagram
1511/341stS140.60.0140.692%92-96%Pass
See Diagram
1611/351stS141.00.0141.092%92-96%Pass
See Diagram
1711/361stS142.10.0142.193%92-96%Pass
See Diagram
1811/371stS144.50.0144.594%92-96%Pass
10
7
7
11
8 HC8
HC
10
44
7
12
15
7
4 HC4
HC
9
9
4 HC
4
4
HC
Field Density Test Location Diagram
New Community Center - Estes Park, Colorado
EEC Project #: 1164046
Asphalt Surfacing
EARTH ENGINEERING CONSULTANTS, LLC
EARTH ENGINEERING CONSULTANTS, LLC
SUMMARY OF ASPHALT EXTRACTION/GRADATION TEST RESULTS
November 2, 2016Martin Marietta
Date Sampled:Supplier
Access roadway to School 5493
Sample Location:Mix ID No.:
Grading:S75
Truck No.:
9:15 AM1st
Sample Time:Lift:
QUANTITATIVE EXTRACTION (ASTM D-2172 METHOD B)
ASPHALTIC CEMENT CONTENT (%)SPECIFICATION
5.5%5.2%+/-0.3%
GRADATION OF EXTRACTED AGGREGATE (ASTM C 136 & C 117)
SIEVE SIZEPERCENT PASSINGSPECIFICATION
1 1/2"100%100%
1"100%100%
3/4"100%90%--100%
82%
1/2"94%--94%
3/8"86%74%--86%
No. 466%60%--70%
No. 849%39%--49%
No. 1640%
No. 3025%18%--26%
No. 5017%
No. 10010%
No. 2007.2%
3.8%--7.8%
Project:
New Community Center - Estes Park Recreation & Park District
Location:Estes Park, Colorado
EEC Project No.:1164046.1
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
GENERAL INFORMATION
Placement Date:10/24/2016Test No.:2
Placement Location:Curb & Gutter - Upper Road, STA 1+35
Concrete Supplier:Martin MariettaType of Placement:Tailgate
Ticket Number:39007574Truck Number:233
Mix Code:CD4405 Water Added on Site:None
Batch Time:7:28 AMSample Time:8:00 AMYards:10of10
Required 28 Day Compressive Strength (psi):4500EEC Technician:GG
Comments:
FIELD TEST DATA
TESTRESULTSSPECIFICATIONS
Slump (in)ASTM C1433"
Air Content (%)ASTM C2315.1%
Unit Weight (pcf)ASTM C138145.0----
Concrete Temperature (deg F)ASTM C10647090° Max
Air Temperature at Placement (deg F)48----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Average
MaximumCylinderCylinderCompressiveCompressive
SpecimenDateAgeApplied LoadHeightDiameterAreaFailureStrengthStrength
2
NumberTested(days)(lbs)(in)(in)(in)Type(psi)(psi)
2B10/31/167664908412.57Shear52905290
2D11/21/1628838208412.57Shear6670
6550
2D111/21/1628816608412.57Shear6500
2D211/21/1628813508412.57Shear6470
Project:New Community Center - Estes Park Recreation and Park District
Project Number:1164046Report Distribution:
RLH Engineering - Chuck Jordan: cjordan@rlhengineering.com
Adolfson & Peterson Construction - Mr. Tom Purcell tpurcell@a-p.com
Adolfson & Peterson Construction - Mr. Quintin Quimby qquimby@a-p.com
Adolfson & Peterson Construction - Mr. Jason Heustis jheustis@a-p.com
Adolfson & Peterson Construction - Mr. Les Fernando lfernando@a-p.com
Adolfson & Peterson Construction - Mr. Josh Cohen jcohen@a-p.com
OLC - Mr. Robert McDonald (rmcdonald@olcdesigns.com)
Martin & Martin - Mr. Ed Sabia (ESabia@martinmartin.com)
Martin Marietta
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
GENERAL INFORMATION
Placement Date:10/24/2016Test No.:3
Placement Location:Curb & Gutter - Along Manford Drive
Concrete Supplier:Martin MariettaType of Placement:Tailgate
Ticket Number:39007578Truck Number:212
Mix Code:CD4405 Water Added on Site:None
Batch Time:11:01 AMSample Time:11:35 AMYards:10of10
Required 28 Day Compressive Strength (psi):4500EEC Technician:GG
Comments:
FIELD TEST DATA
TESTRESULTSSPECIFICATIONS
Slump (in)ASTM C1434.25"
Air Content (%)ASTM C2316.9%
Unit Weight (pcf)ASTM C138142.6----
Concrete Temperature (deg F)ASTM C10646190° Max
Air Temperature at Placement (deg F)63----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Average
MaximumCylinderCylinderCompressiveCompressive
SpecimenDateAgeApplied LoadHeightDiameterAreaFailureStrengthStrength
2
NumberTested(days)(lbs)(in)(in)(in)Type(psi)(psi)
3B10/31/167654808412.57Shear52105210
3D11/21/1628764508412.57Shear6080
5910
3D111/21/1628729908412.57Shear5810
3D211/21/1628733008412.57Shear5830
Project:New Community Center - Estes Park Recreation and Park District
Project Number:1164046Report Distribution:
RLH Engineering - Chuck Jordan: cjordan@rlhengineering.com
Adolfson & Peterson Construction - Mr. Tom Purcell tpurcell@a-p.com
Adolfson & Peterson Construction - Mr. Quintin Quimby qquimby@a-p.com
Adolfson & Peterson Construction - Mr. Jason Heustis jheustis@a-p.com
Adolfson & Peterson Construction - Mr. Les Fernando lfernando@a-p.com
Adolfson & Peterson Construction - Mr. Josh Cohen jcohen@a-p.com
OLC - Mr. Robert McDonald (rmcdonald@olcdesigns.com)
Martin & Martin - Mr. Ed Sabia (ESabia@martinmartin.com)
Martin Marietta
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
GENERAL INFORMATION
Placement Date:10/26/2016Test No.:4
Placement Location:Sidewalk - Lower Rd & Along Manford Dr
Concrete Supplier:Martin MariettaType of Placement:Tailgate
Ticket Number:39007595Truck Number:212
Mix Code:CD4405 Water Added on Site:7 gals
Batch Time:7:33 AMSample Time:8:15 AMYards:10of40
Required 28 Day Compressive Strength (psi):4500EEC Technician:GG
Comments:
FIELD TEST DATA
TESTRESULTSSPECIFICATIONS
Slump (in)ASTM C1435.5"
Air Content (%)ASTM C2316.1%
Unit Weight (pcf)ASTM C138143.0----
Concrete Temperature (deg F)ASTM C10646890° Max
Air Temperature at Placement (deg F)46----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Average
MaximumCylinderCylinderCompressiveCompressive
SpecimenDateAgeApplied LoadHeightDiameterAreaFailureStrengthStrength
2
NumberTested(days)(lbs)(in)(in)(in)Type(psi)(psi)
4B11/02/167663808412.57Shear52805280
4D11/23/1628713408412.57Shear5680
5830
4D111/23/1628770608412.57Shear6130
4D211/23/1628713908412.57Shear5680
Project:New Community Center - Estes Park Recreation and Park District
Project Number:1164046Report Distribution:
RLH Engineering - Chuck Jordan: cjordan@rlhengineering.com
Adolfson & Peterson Construction - Mr. Tom Purcell tpurcell@a-p.com
Adolfson & Peterson Construction - Mr. Quintin Quimby qquimby@a-p.com
Adolfson & Peterson Construction - Mr. Jason Heustis jheustis@a-p.com
Adolfson & Peterson Construction - Mr. Les Fernando lfernando@a-p.com
Adolfson & Peterson Construction - Mr. Josh Cohen jcohen@a-p.com
OLC - Mr. Robert McDonald (rmcdonald@olcdesigns.com)
Martin & Martin - Mr. Ed Sabia (ESabia@martinmartin.com)
Martin Marietta
EARTH ENGINEERING CONSULTANTS, LLC
REPORT OF CAST-IN-PLACE CONCRETE TESTS
GENERAL INFORMATION
Placement Date:10/27/2016Test No.:5
Placement Location:Sidewalk - Along Manford Dr
Concrete Supplier:Martin MariettaType of Placement:Tailgate
Ticket Number:39007608Truck Number:225
Mix Code:CD4405 Water Added on Site:4 gals
Batch Time:7:49 AMSample Time:8:20 AMYards:10of30
Required 28 Day Compressive Strength (psi):4500EEC Technician:GG
Comments:
FIELD TEST DATA
TESTRESULTSSPECIFICATIONS
Slump (in)ASTM C1435"
Air Content (%)ASTM C2317.1%
Unit Weight (pcf)ASTM C138141.0----
Concrete Temperature (deg F)ASTM C10646590° Max
Air Temperature at Placement (deg F)61----
Comments:
COMPRESSIVE STRENGTH OF FIELD CAST TEST SPECIMENS (ASTM C39/C31)
Average
MaximumCylinderCylinderCompressiveCompressive
SpecimenDateAgeApplied LoadHeightDiameterAreaFailureStrengthStrength
2
NumberTested(days)(lbs)(in)(in)(in)Type(psi)(psi)
5B11/03/167540808412.57Shear43004300
5D11/24/1628675408412.57Shear5370
5440
5D111/24/1628706808412.57Shear5620
5D211/24/1628669408412.57Shear5330
Project:New Community Center - Estes Park Recreation and Park District
Project Number:1164046Report Distribution:
RLH Engineering - Chuck Jordan: cjordan@rlhengineering.com
Adolfson & Peterson Construction - Mr. Tom Purcell tpurcell@a-p.com
Adolfson & Peterson Construction - Mr. Quintin Quimby qquimby@a-p.com
Adolfson & Peterson Construction - Mr. Jason Heustis jheustis@a-p.com
Adolfson & Peterson Construction - Mr. Les Fernando lfernando@a-p.com
Adolfson & Peterson Construction - Mr. Josh Cohen jcohen@a-p.com
OLC - Mr. Robert McDonald (rmcdonald@olcdesigns.com)
Martin & Martin - Mr. Ed Sabia (ESabia@martinmartin.com)
Martin Marietta