HomeMy WebLinkAboutAFFIDAVIT United Test and Balance Remodel 130 Stanley Ave 2023-09-13 Semper Fidelis Veteran Owned and Operated Certified Testing, Adjusting, and Balancing Report Project Information Project Name: Twin Owls Motor Lodge Address: 700 N. St Vrain Ave. Estes Park, CO 80517 Elevation: 7,522 ft. Certified Report Date: September 13, 2023 Report Revision Information Reviewing Supervisor Signature Contractor Information Contractor: Everest Mechanical Mechanical Engineer: Architect: Company Certification Information Alnor EBT Micromanometer EBT-731: May 2023 Alnor Hydronic Manometer HM675: May 2023 Fluke 323 True RMS Clamp meter: May 2023 United Test and Balance 10440 Bradford Rd. Unit C Littleton, CO 80127Revision Date: 09/20/2023 Semper Fidelis Veteran Owned and Operated Warranty Information Dear Customer, As we try to build our customer base and ensure your complete satisfaction on every project United Test and Balance would like to extend a 180 Day warranty policy for every project. The terms of the warranty are listed below: United Test and Balance does hereby warrant the above-mentioned completed project for a period of 180 Days from the date of the issued Certified Test and Balance Report. That said work shall remain free from all defects in workmanship and material, and that it shall comply with all the specific requirements of the Specifications and other Contract Documents governing the Testing, Adjusting, and Balancing. It is understood and agreed upon that in the event of defects and the necessity of making repairs, the Owner and/or Contractor will immediately notify United Test and Balance in writing of its conditions and shall give the contractor reasonable time, 30 days, in which to make said repairs. If any person, firm, or corporation other than United Test and Balance has, since the completion of the above work, performed or attempted to perform any repairs to the Mechanical Systems then this warranty will become null and void. This warranty does not cover any repairs made by anyone other than United Test and Balance or one of its authorized representatives. Thank you for the opportunity to work with you on this project and we look forward to working with you in the future. Sincerely, Jeremy Merrill Jeremy Merrill Owner T.A.B.B. Certified Supervisor Semper Fidelis Veteran Owned and Operated Abbreviation Index AC Air Conditioning Unit AHU Air Handling Unit AMP or A Ampere APD Air Pressure Drop ATMOS Atmosphere BHP Brake Horsepower BTU British Thermal Unit BTUH BTU per Hour CFM Cubic Feet per Minute CHW Chilled Water CHWR Chilled Water Return CHWS Chilled Water Supply CT Cooling Tower CUH Cabinet Unit Heater CWR Condenser Water Return CWS Condenser Water Supply DB Dry Bulb (Temperature) DEG or ° Degree DP or ΔP Differential Pressure ΔT Differential Temperature (E) Existing EA Exhaust Air EAT Entering Air Temperature EF Exhaust Fan ER Exhaust Register ERV Energy Recovery Ventilator ESP External Static Pressure EWT Entering Water Temperature °F Fahrenheit FPB Fan Power Box FCU Fan Coil Unit FLA Full Load Amps FPM Feet per Minute FT. Feet HD. Head HP Horsepower HWR Hot Water Return HWS Hot Water Supply HZ Hertz (Cycles per Second) IN. Inches KEF Kitchen Exhaust Fan KW Kilowatt LAT Leaving Air Temperature LB Pound LWT Leaving Water Temperature MA Mixed Air MAX Maximum MIN Minimum MAU Make-Up Air N/A No Access Nom. Eff. Nominal Efficiency OSA Outside Air OD | ID Outside Diameter | Inside Diameter P Pump PD Pressure Drop PF Power Factor PFPB Parallel Fan Power Box PH Phase PSI Pounds per Square Inch RA Return Air RET Return RG Return Grille RH Relative Humidity RPM Revolutions per Minute RTU Roof-Top Unit SA Supply Air SD Supply Diffuser SP Static Pressure SF Service Factor SFPB Series Fan Power Box sq. ft. Square Feet T-1|T-2 |T-3 Terminal 1|Terminal 2|Terminal 3 TEMP or ° Temperature TSP Total Static Pressure T-Stat Thermostat V Volts VAV Variable Air Volume VFD Variable Frequency Drive VP Velocity Pressure WB Wet Bulb Temperature W.C. Water Column W.G. Water Gauge Table Of ContentsPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Table Of Contents 1 Make-Up Air Unit......................................................................................................................................................1 1.1 MAU-01..............................................................................................................................................................1 1.2 MAU-01/MAU-01................................................................................................................................................1 2 Energy Recovery Unit..............................................................................................................................................3 2.1 ERV-01...............................................................................................................................................................3 2.2 ERV-02...............................................................................................................................................................4 3 Fan Coil....................................................................................................................................................................6 3.1 F-01....................................................................................................................................................................6 3.2 F-01/F-01............................................................................................................................................................6 3.3 F-02....................................................................................................................................................................7 3.4 F-02/F-02............................................................................................................................................................8 4 Fan Unit....................................................................................................................................................................9 4.1 EF-01A...............................................................................................................................................................9 4.2 EF-01B...............................................................................................................................................................9 4.3 EF-01C...............................................................................................................................................................9 4.4 KEF-01...............................................................................................................................................................10 4.5 KEF-02...............................................................................................................................................................10 5 Twin Owls Motor Lodge Mechanical Final.pdf..........................................................................................................11 United Test and Balance Page 1 of 15 Make-Up Air UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:9/20/2023 SYSTEM/UNIT: MAU-01 Unit Data Unit Manufacturer Captive Air Unit Model Number A2-D.250-20D Unit Serial Number 5838738 4/21/2023 Design ESP Supply 1.0 in. wc. MAU-01/Filter Filter Type Evap Filter Qty - S1 1 Filter Size - S1 30 X 36 X 12 Test Data Design Airflow 3200 CFM Actual Airflow 3420 CFM Design Outside Airflow 3200 CFM Actual Outside Airflow 3420 CFM Motor Data MAU-01/Supply Fan Motor Manufacturer Teco Motor Frame 182T Motor HP 3 HP Motor RPM 1755 RPM Motor Rated Volts 230/460 Volts Motor Phase 3 Motor FL Amps 8.6/4.3 Amps Motor Service Factor 1.15 Nominal Efficiency 89.5 % Motor Power Factor 87.5 % Sheave Data MAU-01/Supply Fan Motor Sheave Model Direct Drive Final Data MAU-01/Supply Fan Motor Volts T1-T2 213 Volts Motor Amps T1 8.5 Amps Tested By:Sean Ryan Date:9/20/2023 SYSTEM/UNIT: MAU-01/MAU-01 Test Pressures Final Filter SP In -0.19 in. w.c. Final Filter SP Out NA in. w.c. DX Coil SP In NA in. w.c. DX Coil SP Out -0.69 in. w.c. Supply Fan SP In -0.69 in. w.c. Supply Fan SP Out NA in. w.c. Gas Heat Exchanger SP In NA in. w.c. Gas Heat Exchanger SP Out 0.42 in. w.c. Static Pressure Profile United Test and Balance Page 2 of 15 Make-Up Air UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff. Hood Hood 1950 2608 134 2142 110 Outlet-01 SD 625 72 12 625 100 Outlet-02 SD 625 741 119 653 104 Totals:-3200 3421 107 3420 107 MAU-01 Supply Outlet Summary United Test and Balance Page 3 of 15 Energy Recovery UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:8/17/2023 SYSTEM/UNIT: ERV-01 Unit Data Unit Manufacturer Panasonic Unit Model Number FV-20VEC1 Unit Serial Number 2108 Unit Type Air to Air ERV-01/EF Filter Filter Type Pleated Merv 13 Filter Qty - S1 2 Filter Size - S1 6 x 26 x 1 ERV-01/SF Filter Filter Type Pleated Merv 13 Filter Qty - S1 2 Filter Size - S1 6 x 26 x 1 Test Data Supply Fan Design 125 CFM Supply Fan Actual 132 CFM Outside Air Design 125 CFM Outside Air Actual 131 CFM Exhaust Fan Design 125 CFM Exhaust Fan Actual 137 CFM Motor Data ERV-01/Exhaust Fan Motor Manufacturer Direct Drive Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 2.30 Amps ERV-01/Supply Fan Motor Manufacturer Direct Drive Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 2.30 Amps Sheave Data ERV-01/Exhaust Fan Motor Sheave Model Direct Drive ERV-01/Supply Fan Motor Sheave Model Direct Drive Final Data ERV-01/Exhaust Fan Design RPM NA RPM Actual RPM NA RPM Motor Operating Hz 60 Motor Volts T1-T2 118 Volts Motor Amps T1 1.8 Amps ERV-01/Supply Fan Design RPM NA RPM Actual RPM NA RPM Motor Operating Hz 60 Motor Volts T1-T2 118 Volts Motor Amps T1 1.8 Amps Test Pressures S/Fan HEX SP In NA in. wc S/Fan HEX SP Out NA in. wc S/F Fan SP In NA in. wc S/F Fan SP Out 0.14 in. wc S/Fan Filter In -0.35 in. wc S/Fan Filter Out NA in. wc E/F Fan SP In NA in. wc E/F Fan SP Out 0.25 in. wc E/F HEX SP In NA in. wc E/F HEX SP Out NA in. wc E/F Filter In -0.23 in. wc United Test and Balance Page 4 of 15 Energy Recovery UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:8/17/2023 SYSTEM/UNIT: ERV-02 Log:ERV-02 9/13/2023 Jeremy Merrill There are no balancing dampers installed for both exhaust and supply registers, unit set for overall total. Unit Data Unit Manufacturer Panasonic Unit Model Number FV-20VEC1 Unit Serial Number 2108 Unit Type Air to Air ERV-02/EF Filter Filter Type Pleated Merv 13 Filter Qty - S1 1 Filter Size - S1 6 x 26 x 1 ERV-02/SF Filter Filter Type Pleated Merv 13 Filter Qty - S1 1 Filter Size - S1 6 x 26 x 1 Test Data Supply Fan Design 175 CFM Supply Fan Actual 176 CFM Outside Air Design 175 CFM Outside Air Actual 176 CFM Exhaust Fan Design 175 CFM Exhaust Fan Actual 179 CFM Motor Data ERV-02/Exhaust Fan Motor Manufacturer Direct Drive Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 2.3 Amps ERV-02/Supply Fan Motor Manufacturer Direct Drive Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 2.3 Amps Sheave Data ERV-02/Exhaust Fan Motor Sheave Model Direct Drive ERV-02/Supply Fan Motor Sheave Model Direct Drive Final Data ERV-02/Exhaust Fan Design RPM NA RPM Actual RPM NA RPM Motor Volts T1-T2 117 Volts Motor Amps T1 1.7 Amps ERV-02/Supply Fan Design RPM NA RPM Actual RPM NA RPM Motor Volts T1-T2 117 Volts Motor Amps T1 1.7 Amps Test Pressures S/Fan HEX SP In NA in. wc S/Fan HEX SP Out NA in. wc S/F Fan SP In NA in. wc S/F Fan SP Out 0.02 in. wc S/Fan Filter In -0.49 in. wc S/Fan Filter Out NA in. wc E/F Fan SP In NA in. wc E/F Fan SP Out 0.48 in. wc E/F HEX SP In NA in. wc E/F HEX SP Out NA in. wc E/F Filter In -0.06 in. wc E/F Filter Out NA in. wc United Test and Balance Page 5 of 15 Energy Recovery UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff. Outlet-01 SD 25 55 220 27 108 Outlet-02 SD 25 55 220 24 96 Outlet-03 SD 90 62 69 89 99 Outlet-04 SD 35 0 0 36 103 Totals:-175 172 98 176 101 ERV-02 Supply Outlet Summary System/Unit Inlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff. Inlet-01 ER 25 55 220 55 220 Inlet-02 ER 25 40 160 40 160 Inlet-03 ER 90 49 54 49 54 Inlet-04 ER 35 35 100 35 100 Totals:-175 179 102 179 102 ERV-02 Exhaust Inlet Summary United Test and Balance Page 6 of 15 Fan CoilPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:9/20/2023 SYSTEM/UNIT: F-01 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC5B100E211120 Unit Serial Number 0822A46848 Design ESP Supply 0.4 in. wc Test Data Design Airflow 1600 CFM Actual Airflow 1622 CFM Motor Data Motor Manufacturer Info taken off tag (NAC) Motor Type Direct Drive Motor HP 1 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor FL Amps 12.6 Amps Motor Service Factor 1.00 Sheave Data Motor Sheave MFG Direct Drive Final Data Motor Volts T1-T2 114 Volts Tested By:Sean Ryan Date:9/20/2023 SYSTEM/UNIT: F-01/F-01 Test Pressures Final Filter SP In -0.19 in. w.c. Final Filter SP Out NA in. w.c. DX Coil SP In NA in. w.c. DX Coil SP Out NA in. w.c. Supply Fan SP In NA in. w.c. Supply Fan SP Out NA in. w.c. Gas Heat Exchanger SP In NA in. w.c. Gas Heat Exchanger SP Out 0.10 in. w.c. Static Pressure Profile United Test and Balance Page 7 of 15 Fan CoilPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff. Outlet-01 SD 225 334 148 229 102 Outlet-02 SD 50 102 204 55 110 Outlet-03 SD 450 399 89 462 103 Outlet-04 SD 425 435 102 420 99 Outlet-05 SD 450 388 86 456 101 Totals:-1600 1658 104 1622 101 F-01 Supply Outlet Summary Tested By:Sean Ryan Date:9/18/2023 SYSTEM/UNIT: F-02 Unit Data Unit Manufacturer Carrier Unit Model Number 59SC5B100E211120 Unit Serial Number 4821A60429 Design ESP Supply 0.4 in. wc F-02/Air Filter Filter Type Pleated Filter Qty - S1 1 Filter Size - S1 20x25x4 Test Data Design Airflow 1600 CFM Actual Airflow 1469 CFM Motor Data Motor Manufacturer Direct Drive Motor Type Direct Drive Motor HP 1 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor FL Amps 12.6 Amps Motor Service Factor 1.00 Sheave Data Motor Sheave MFG Direct Drive Final Data Design RPM NA RPM Motor Volts T2-T3 113 Volts United Test and Balance Page 8 of 15 Fan CoilPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:9/18/2023 SYSTEM/UNIT: F-02/F-02 Test Pressures Final Filter SP In 0.19 in. w.c. Final Filter SP Out NA in. w.c. DX Coil SP In NA in. w.c. DX Coil SP Out NA in. w.c. Supply Fan SP In NA in. w.c. Supply Fan SP Out NA in. w.c. Gas Heat Exchanger SP In NA in. w.c. Gas Heat Exchanger SP Out 0.14 in. w.c. Static Pressure Profile System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff. Outlet-01 SD 200 180 90 182 91 Outlet-02 SD 200 110 55 185 93 Outlet-03 SD 200 82 41 179 90 Outlet-04 SD 200 121 61 180 90 Outlet-05 SD 200 152 76 191 96 Outlet-06 SD 150 180 120 136 91 Outlet-07 SD 150 60 40 139 93 Outlet-08 SD 150 155 103 142 95 Outlet-09 SD 150 205 137 135 90 Totals:-1600 1245 78 1469 92 F-02 Supply Outlet Summary United Test and Balance Page 9 of 15 Fan UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:8/17/2023 SYSTEM/UNIT: EF-01A Log:EF-01A 8/17/2023 Sean Ryan Unit is set to its highest speed setting. No further adjustments can be made. Unit Data Fan Manufacturer Panasonic Fan Model Number FV-0511VQ1 Fan Serial Number 10505M Design ESP 0.125 in. wc Test Data Design Airflow 100 CFM Actual Airflow 75 CFM Motor Data Motor Manufacturer Info taken off tag (NA) Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 0.17 Amps Motor Service Factor 1.00 Final Data Design RPM NA RPM Actual RPM NA RPM Motor Volts T1-T2 117 Volts Motor Amps T1 0.13 Amps Tested By:Sean Ryan Date:8/17/2023 SYSTEM/UNIT: EF-01B Unit Data Fan Manufacturer Panasonic Fan Model Number FV-0511VKS2 Fan Serial Number 21208M Design ESP 0.125 in. wc Test Data Design Airflow 100 CFM Actual Airflow 92 CFM Motor Data Motor Manufacturer Info taken off tag (NAC) Final Data Design RPM NA RPM Actual RPM NA RPM Motor Volts T1-T2 117 Volts Motor Amps T1 .013 Amps Tested By:Sean Ryan Date:9/18/2023 SYSTEM/UNIT: EF-01C Unit Data Fan Manufacturer Panasonic Fan Model Number FV-0511VKS2 Fan Serial Number 21125M Design ESP 0.125 in. wc Test Data Design Airflow 100 CFM Actual Airflow 91 CFM Motor Data Motor Manufacturer Info taken off tag (NAC) Motor Frame Not Listed Motor Rated Volts 120 Volts Motor Phase 1 Motor FL Amps 0.27 Amps Motor Service Factor 1.00 Final Data Motor Volts T1-T2 114 Volts Motor Amps T1 0.2 Amps United Test and Balance Page 10 of 15 Fan UnitPROJECT: LOCATION: Twin Owls Motor Lodge Estes, CO 23-3430PROJECT #: DATE: CONTACT: AUTHOR: 9/20/2023 Jeremy Merrill Jeremy Merrill Tested By:Sean Ryan Date:9/18/2023 SYSTEM/UNIT: KEF-01 Unit Data Fan Manufacturer Captive-Aire Fan Model Number DU180HFA Fan Serial Number 5838738 Design ESP 1.75 in. wc Test Data Design Airflow 2500 CFM Actual Airflow 2678 CFM Motor Data Motor Manufacturer Techo Motor Frame 182T Motor RPM 1755 RPM Motor Rated Volts 230/460 Volts Motor Phase 3 Motor FL Amps 8.6/4.3 Amps Motor Service Factor 1.15 Nominal Efficiency 89.5 % Power Factor 87.5 Final Data Motor Volts T1-T2 211 Volts Motor Amps T1 5.8 Amps Tested By:Sean Ryan Date:9/18/2023 SYSTEM/UNIT: KEF-02 Unit Data Fan Manufacturer Captive-Aire Fan Model Number DU50FHA Fan Serial Number 5838738 Design ESP 0.75 in. wc Test Data Design Airflow 700 CFM Actual Airflow 736 CFM Motor Data Motor Manufacturer Telco Green Motor HP 1/2 HP Motor RPM 1800 RPM Motor Rated Volts 208-277 Volts Motor Phase 1 Motor FL Amps Not Listed Amps Motor Service Factor 1.00 Final Data Motor Volts T1-T2 212 Volts Motor Amps T1 2.1 Amps United Test and Balance Page 11 of 15 Page 12 of 15 Page 13 of 15 ERV-01 ERV-02 1 2 3 4 1 2 3 4 1 1 F-02 Page 14 of 15 KEF-01 KEF-02 F-02 1 2 F-01 EF-01B EF-01A 1 2 Page 15 of 15 KEF-01 KEF-02 EF-01C MAU-01 F-02 F-01 1 2 3 4 5 67 8 9 3 4 5