Certified Testing, Adjusting, and Balancing Report
Project Information
Project Name: Twin Owls Motor Lodge
Address: 700 N. St Vrain Ave.
Estes Park, CO 80517
Elevation: 7,522 ft.
Certified Report Date: September 13, 2023
Report Revision Information
Reviewing Supervisor Signature
Contractor Information
Contractor: Everest Mechanical
Mechanical Engineer:
Architect:
Company Certification Information
Alnor EBT Micromanometer EBT-731: May 2023
Alnor Hydronic Manometer HM675: May 2023
Fluke 323 True RMS Clamp meter: May 2023
United Test and Balance
10440 Bradford Rd. Unit C
Littleton, CO 80127Revision Date: 09/20/2023
Semper Fidelis
Veteran Owned and Operated
Warranty Information
Dear Customer,
As we try to build our customer base and ensure your complete satisfaction on every project
United Test and Balance would like to extend a 180 Day warranty policy for every project. The
terms of the warranty are listed below:
United Test and Balance does hereby warrant the above-mentioned completed project for a
period of 180 Days from the date of the issued Certified Test and Balance Report. That said work
shall remain free from all defects in workmanship and material, and that it shall comply with all
the specific requirements of the Specifications and other Contract Documents governing the
Testing, Adjusting, and Balancing.
It is understood and agreed upon that in the event of defects and the necessity of making repairs,
the Owner and/or Contractor will immediately notify United Test and Balance in writing of its
conditions and shall give the contractor reasonable time, 30 days, in which to make said repairs.
If any person, firm, or corporation other than United Test and Balance has, since the completion
of the above work, performed or attempted to perform any repairs to the Mechanical Systems
then this warranty will become null and void. This warranty does not cover any repairs made by
anyone other than United Test and Balance or one of its authorized representatives.
Thank you for the opportunity to work with you on this project and we look forward to
working with you in the future.
Sincerely,
Jeremy Merrill
Jeremy Merrill
Owner
T.A.B.B. Certified Supervisor
Semper Fidelis
Veteran Owned and Operated
Abbreviation Index
AC Air Conditioning Unit
AHU Air Handling Unit
AMP or A Ampere
APD Air Pressure Drop
ATMOS Atmosphere
BHP Brake Horsepower
BTU British Thermal Unit
BTUH BTU per Hour
CFM Cubic Feet per Minute
CHW Chilled Water
CHWR Chilled Water Return
CHWS Chilled Water Supply
CT Cooling Tower
CUH Cabinet Unit Heater
CWR Condenser Water Return
CWS Condenser Water Supply
DB Dry Bulb (Temperature)
DEG or ° Degree
DP or ΔP Differential Pressure
ΔT Differential Temperature
(E) Existing
EA Exhaust Air
EAT Entering Air Temperature
EF Exhaust Fan
ER Exhaust Register
ERV Energy Recovery Ventilator
ESP External Static Pressure
EWT Entering Water Temperature
°F Fahrenheit
FPB Fan Power Box
FCU Fan Coil Unit
FLA Full Load Amps
FPM Feet per Minute
FT. Feet
HD. Head
HP Horsepower
HWR Hot Water Return
HWS Hot Water Supply
HZ Hertz (Cycles per Second)
IN. Inches
KEF Kitchen Exhaust Fan
KW Kilowatt
LAT Leaving Air Temperature
LB Pound
LWT Leaving Water Temperature
MA Mixed Air
MAX Maximum
MIN Minimum
MAU Make-Up Air
N/A No Access
Nom. Eff. Nominal Efficiency
OSA Outside Air
OD | ID Outside Diameter | Inside Diameter
P Pump
PD Pressure Drop
PF Power Factor
PFPB Parallel Fan Power Box
PH Phase
PSI Pounds per Square Inch
RA Return Air
RET Return
RG Return Grille
RH Relative Humidity
RPM Revolutions per Minute
RTU Roof-Top Unit
SA Supply Air
SD Supply Diffuser
SP Static Pressure
SF Service Factor
SFPB Series Fan Power Box
sq. ft. Square Feet
T-1|T-2 |T-3 Terminal 1|Terminal 2|Terminal 3
TEMP or ° Temperature
TSP Total Static Pressure
T-Stat Thermostat
V Volts
VAV Variable Air Volume
VFD Variable Frequency Drive
VP Velocity Pressure
WB Wet Bulb Temperature
W.C. Water Column
W.G. Water Gauge
Table Of ContentsPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Table Of Contents
1 Make-Up Air Unit......................................................................................................................................................1
1.1 MAU-01..............................................................................................................................................................1
1.2 MAU-01/MAU-01................................................................................................................................................1
2 Energy Recovery Unit..............................................................................................................................................3
2.1 ERV-01...............................................................................................................................................................3
2.2 ERV-02...............................................................................................................................................................4
3 Fan Coil....................................................................................................................................................................6
3.1 F-01....................................................................................................................................................................6
3.2 F-01/F-01............................................................................................................................................................6
3.3 F-02....................................................................................................................................................................7
3.4 F-02/F-02............................................................................................................................................................8
4 Fan Unit....................................................................................................................................................................9
4.1 EF-01A...............................................................................................................................................................9
4.2 EF-01B...............................................................................................................................................................9
4.3 EF-01C...............................................................................................................................................................9
4.4 KEF-01...............................................................................................................................................................10
4.5 KEF-02...............................................................................................................................................................10
5 Twin Owls Motor Lodge Mechanical Final.pdf..........................................................................................................11
United Test and Balance
Page 1 of 15
Make-Up Air UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:9/20/2023
SYSTEM/UNIT: MAU-01
Unit Data
Unit Manufacturer Captive Air
Unit Model Number A2-D.250-20D
Unit Serial Number 5838738 4/21/2023
Design ESP Supply 1.0 in. wc.
MAU-01/Filter
Filter Type Evap
Filter Qty - S1 1
Filter Size - S1 30 X 36 X 12
Test Data
Design Airflow 3200 CFM
Actual Airflow 3420 CFM
Design Outside Airflow 3200 CFM
Actual Outside Airflow 3420 CFM
Motor Data
MAU-01/Supply Fan
Motor Manufacturer Teco
Motor Frame 182T
Motor HP 3 HP
Motor RPM 1755 RPM
Motor Rated Volts 230/460 Volts
Motor Phase 3
Motor FL Amps 8.6/4.3 Amps
Motor Service Factor 1.15
Nominal Efficiency 89.5 %
Motor Power Factor 87.5 %
Sheave Data
MAU-01/Supply Fan
Motor Sheave Model Direct Drive
Final Data
MAU-01/Supply Fan
Motor Volts T1-T2 213 Volts
Motor Amps T1 8.5 Amps
Tested By:Sean Ryan
Date:9/20/2023
SYSTEM/UNIT: MAU-01/MAU-01
Test Pressures
Final Filter SP In -0.19 in. w.c.
Final Filter SP Out NA in. w.c.
DX Coil SP In NA in. w.c.
DX Coil SP Out -0.69 in. w.c.
Supply Fan SP In -0.69 in. w.c.
Supply Fan SP Out NA in. w.c.
Gas Heat Exchanger SP In NA in. w.c.
Gas Heat Exchanger SP Out 0.42 in. w.c.
Static Pressure Profile
United Test and Balance
Page 2 of 15
Make-Up Air UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff.
Hood Hood 1950 2608 134 2142 110
Outlet-01 SD 625 72 12 625 100
Outlet-02 SD 625 741 119 653 104
Totals:-3200 3421 107 3420 107
MAU-01 Supply Outlet Summary
United Test and Balance
Page 3 of 15
Energy Recovery UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:8/17/2023
SYSTEM/UNIT: ERV-01
Unit Data
Unit Manufacturer Panasonic
Unit Model Number FV-20VEC1
Unit Serial Number 2108
Unit Type Air to Air
ERV-01/EF Filter
Filter Type Pleated Merv 13
Filter Qty - S1 2
Filter Size - S1 6 x 26 x 1
ERV-01/SF Filter
Filter Type Pleated Merv 13
Filter Qty - S1 2
Filter Size - S1 6 x 26 x 1
Test Data
Supply Fan Design 125 CFM
Supply Fan Actual 132 CFM
Outside Air Design 125 CFM
Outside Air Actual 131 CFM
Exhaust Fan Design 125 CFM
Exhaust Fan Actual 137 CFM
Motor Data
ERV-01/Exhaust Fan
Motor Manufacturer Direct Drive
Motor Rated Volts 120 Volts
Motor Phase 1
Motor FL Amps 2.30 Amps
ERV-01/Supply Fan
Motor Manufacturer Direct Drive
Motor Rated Volts 120 Volts
Motor Phase 1
Motor FL Amps 2.30 Amps
Sheave Data
ERV-01/Exhaust Fan
Motor Sheave Model Direct Drive
ERV-01/Supply Fan
Motor Sheave Model Direct Drive
Final Data
ERV-01/Exhaust Fan
Design RPM NA RPM
Actual RPM NA RPM
Motor Operating Hz 60
Motor Volts T1-T2 118 Volts
Motor Amps T1 1.8 Amps
ERV-01/Supply Fan
Design RPM NA RPM
Actual RPM NA RPM
Motor Operating Hz 60
Motor Volts T1-T2 118 Volts
Motor Amps T1 1.8 Amps
Test Pressures
S/Fan HEX SP In NA in. wc
S/Fan HEX SP Out NA in. wc
S/F Fan SP In NA in. wc
S/F Fan SP Out 0.14 in. wc
S/Fan Filter In -0.35 in. wc
S/Fan Filter Out NA in. wc
E/F Fan SP In NA in. wc
E/F Fan SP Out 0.25 in. wc
E/F HEX SP In NA in. wc
E/F HEX SP Out NA in. wc
E/F Filter In -0.23 in. wc
United Test and Balance
Page 4 of 15
Energy Recovery UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:8/17/2023
SYSTEM/UNIT: ERV-02
Log:ERV-02 9/13/2023 Jeremy Merrill There are no balancing dampers installed for both
exhaust and supply registers, unit set for overall total.
Unit Data
Unit Manufacturer Panasonic
Unit Model Number FV-20VEC1
Unit Serial Number 2108
Unit Type Air to Air
ERV-02/EF Filter
Filter Type Pleated Merv 13
Filter Qty - S1 1
Filter Size - S1 6 x 26 x 1
ERV-02/SF Filter
Filter Type Pleated Merv 13
Filter Qty - S1 1
Filter Size - S1 6 x 26 x 1
Test Data
Supply Fan Design 175 CFM
Supply Fan Actual 176 CFM
Outside Air Design 175 CFM
Outside Air Actual 176 CFM
Exhaust Fan Design 175 CFM
Exhaust Fan Actual 179 CFM
Motor Data
ERV-02/Exhaust Fan
Motor Manufacturer Direct Drive
Motor Rated Volts 120 Volts
Motor Phase 1
Motor FL Amps 2.3 Amps
ERV-02/Supply Fan
Motor Manufacturer Direct Drive
Motor Rated Volts 120 Volts
Motor Phase 1
Motor FL Amps 2.3 Amps
Sheave Data
ERV-02/Exhaust Fan
Motor Sheave Model Direct Drive
ERV-02/Supply Fan
Motor Sheave Model Direct Drive
Final Data
ERV-02/Exhaust Fan
Design RPM NA RPM
Actual RPM NA RPM
Motor Volts T1-T2 117 Volts
Motor Amps T1 1.7 Amps
ERV-02/Supply Fan
Design RPM NA RPM
Actual RPM NA RPM
Motor Volts T1-T2 117 Volts
Motor Amps T1 1.7 Amps
Test Pressures
S/Fan HEX SP In NA in. wc
S/Fan HEX SP Out NA in. wc
S/F Fan SP In NA in. wc
S/F Fan SP Out 0.02 in. wc
S/Fan Filter In -0.49 in. wc
S/Fan Filter Out NA in. wc
E/F Fan SP In NA in. wc
E/F Fan SP Out 0.48 in. wc
E/F HEX SP In NA in. wc
E/F HEX SP Out NA in. wc
E/F Filter In -0.06 in. wc
E/F Filter Out NA in. wc
United Test and Balance
Page 5 of 15
Energy Recovery UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff.
Outlet-01 SD 25 55 220 27 108
Outlet-02 SD 25 55 220 24 96
Outlet-03 SD 90 62 69 89 99
Outlet-04 SD 35 0 0 36 103
Totals:-175 172 98 176 101
ERV-02 Supply Outlet Summary
System/Unit Inlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff.
Inlet-01 ER 25 55 220 55 220
Inlet-02 ER 25 40 160 40 160
Inlet-03 ER 90 49 54 49 54
Inlet-04 ER 35 35 100 35 100
Totals:-175 179 102 179 102
ERV-02 Exhaust Inlet Summary
United Test and Balance
Page 6 of 15
Fan CoilPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:9/20/2023
SYSTEM/UNIT: F-01
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC5B100E211120
Unit Serial Number 0822A46848
Design ESP Supply 0.4 in. wc
Test Data
Design Airflow 1600 CFM
Actual Airflow 1622 CFM
Motor Data
Motor Manufacturer Info taken off tag (NAC)
Motor Type Direct Drive
Motor HP 1 HP
Motor Rated Volts 115 Volts
Motor Phase 1
Motor FL Amps 12.6 Amps
Motor Service Factor 1.00
Sheave Data
Motor Sheave MFG Direct Drive
Final Data
Motor Volts T1-T2 114 Volts
Tested By:Sean Ryan
Date:9/20/2023
SYSTEM/UNIT: F-01/F-01
Test Pressures
Final Filter SP In -0.19 in. w.c.
Final Filter SP Out NA in. w.c.
DX Coil SP In NA in. w.c.
DX Coil SP Out NA in. w.c.
Supply Fan SP In NA in. w.c.
Supply Fan SP Out NA in. w.c.
Gas Heat Exchanger SP In NA in. w.c.
Gas Heat Exchanger SP Out 0.10 in. w.c.
Static Pressure Profile
United Test and Balance
Page 7 of 15
Fan CoilPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff.
Outlet-01 SD 225 334 148 229 102
Outlet-02 SD 50 102 204 55 110
Outlet-03 SD 450 399 89 462 103
Outlet-04 SD 425 435 102 420 99
Outlet-05 SD 450 388 86 456 101
Totals:-1600 1658 104 1622 101
F-01 Supply Outlet Summary
Tested By:Sean Ryan
Date:9/18/2023
SYSTEM/UNIT: F-02
Unit Data
Unit Manufacturer Carrier
Unit Model Number 59SC5B100E211120
Unit Serial Number 4821A60429
Design ESP Supply 0.4 in. wc
F-02/Air Filter
Filter Type Pleated
Filter Qty - S1 1
Filter Size - S1 20x25x4
Test Data
Design Airflow 1600 CFM
Actual Airflow 1469 CFM
Motor Data
Motor Manufacturer Direct Drive
Motor Type Direct Drive
Motor HP 1 HP
Motor Rated Volts 115 Volts
Motor Phase 1
Motor FL Amps 12.6 Amps
Motor Service Factor 1.00
Sheave Data
Motor Sheave MFG Direct Drive
Final Data
Design RPM NA RPM
Motor Volts T2-T3 113 Volts
United Test and Balance
Page 8 of 15
Fan CoilPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:9/18/2023
SYSTEM/UNIT: F-02/F-02
Test Pressures
Final Filter SP In 0.19 in. w.c.
Final Filter SP Out NA in. w.c.
DX Coil SP In NA in. w.c.
DX Coil SP Out NA in. w.c.
Supply Fan SP In NA in. w.c.
Supply Fan SP Out NA in. w.c.
Gas Heat Exchanger SP In NA in. w.c.
Gas Heat Exchanger SP Out 0.14 in. w.c.
Static Pressure Profile
System/Unit Outlet Type Design Airflow Prelim Airflow % Prelim Diff.Final Airflow % Final Diff.
Outlet-01 SD 200 180 90 182 91
Outlet-02 SD 200 110 55 185 93
Outlet-03 SD 200 82 41 179 90
Outlet-04 SD 200 121 61 180 90
Outlet-05 SD 200 152 76 191 96
Outlet-06 SD 150 180 120 136 91
Outlet-07 SD 150 60 40 139 93
Outlet-08 SD 150 155 103 142 95
Outlet-09 SD 150 205 137 135 90
Totals:-1600 1245 78 1469 92
F-02 Supply Outlet Summary
United Test and Balance
Page 9 of 15
Fan UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:8/17/2023
SYSTEM/UNIT: EF-01A
Log:EF-01A 8/17/2023 Sean Ryan Unit is set to its highest speed setting. No further
adjustments can be made.
Unit Data
Fan Manufacturer Panasonic
Fan Model Number FV-0511VQ1
Fan Serial Number 10505M
Design ESP 0.125 in. wc
Test Data
Design Airflow 100 CFM
Actual Airflow 75 CFM
Motor Data
Motor Manufacturer Info taken off tag (NA)
Motor Rated Volts 120 Volts
Motor Phase 1
Motor FL Amps 0.17 Amps
Motor Service Factor 1.00
Final Data
Design RPM NA RPM
Actual RPM NA RPM
Motor Volts T1-T2 117 Volts
Motor Amps T1 0.13 Amps
Tested By:Sean Ryan
Date:8/17/2023
SYSTEM/UNIT: EF-01B
Unit Data
Fan Manufacturer Panasonic
Fan Model Number FV-0511VKS2
Fan Serial Number 21208M
Design ESP 0.125 in. wc
Test Data
Design Airflow 100 CFM
Actual Airflow 92 CFM
Motor Data
Motor Manufacturer Info taken off tag (NAC)
Final Data
Design RPM NA RPM
Actual RPM NA RPM
Motor Volts T1-T2 117 Volts
Motor Amps T1 .013 Amps
Tested By:Sean Ryan
Date:9/18/2023
SYSTEM/UNIT: EF-01C
Unit Data
Fan Manufacturer Panasonic
Fan Model Number FV-0511VKS2
Fan Serial Number 21125M
Design ESP 0.125 in. wc
Test Data
Design Airflow 100 CFM
Actual Airflow 91 CFM
Motor Data
Motor Manufacturer Info taken off tag (NAC)
Motor Frame Not Listed
Motor Rated Volts 120 Volts
Motor Phase 1
Motor FL Amps 0.27 Amps
Motor Service Factor 1.00
Final Data
Motor Volts T1-T2 114 Volts
Motor Amps T1 0.2 Amps
United Test and Balance
Page 10 of 15
Fan UnitPROJECT:
LOCATION:
Twin Owls Motor Lodge
Estes, CO
23-3430PROJECT #:
DATE:
CONTACT:
AUTHOR:
9/20/2023
Jeremy Merrill
Jeremy Merrill
Tested By:Sean Ryan
Date:9/18/2023
SYSTEM/UNIT: KEF-01
Unit Data
Fan Manufacturer Captive-Aire
Fan Model Number DU180HFA
Fan Serial Number 5838738
Design ESP 1.75 in. wc
Test Data
Design Airflow 2500 CFM
Actual Airflow 2678 CFM
Motor Data
Motor Manufacturer Techo
Motor Frame 182T
Motor RPM 1755 RPM
Motor Rated Volts 230/460 Volts
Motor Phase 3
Motor FL Amps 8.6/4.3 Amps
Motor Service Factor 1.15
Nominal Efficiency 89.5 %
Power Factor 87.5
Final Data
Motor Volts T1-T2 211 Volts
Motor Amps T1 5.8 Amps
Tested By:Sean Ryan
Date:9/18/2023
SYSTEM/UNIT: KEF-02
Unit Data
Fan Manufacturer Captive-Aire
Fan Model Number DU50FHA
Fan Serial Number 5838738
Design ESP 0.75 in. wc
Test Data
Design Airflow 700 CFM
Actual Airflow 736 CFM
Motor Data
Motor Manufacturer Telco Green
Motor HP 1/2 HP
Motor RPM 1800 RPM
Motor Rated Volts 208-277 Volts
Motor Phase 1
Motor FL Amps Not Listed Amps
Motor Service Factor 1.00
Final Data
Motor Volts T1-T2 212 Volts
Motor Amps T1 2.1 Amps
United Test and Balance
Page 11 of 15
Page 12 of 15
Page 13 of 15
ERV-01
ERV-02
1
2
3
4
1
2
3
4
1
1
F-02
Page 14 of 15
KEF-01
KEF-02
F-02
1
2
F-01
EF-01B
EF-01A
1
2
Page 15 of 15
KEF-01
KEF-02
EF-01C
MAU-01
F-02
F-01
1 2 3 4 5
67
8 9
3 4 5