HomeMy WebLinkAboutPLANS Deck 1078 Pine Knoll Dr 2024-06-256x6 post
2x6 @
3-2x8 rim
3-2x8 rim
2-2x8 rim this side unless noted otherwise
4x4 (min.)
posts, typ.
2-2x10 notch top of post for bearing,
(2) 1/2" through bolts
3-2x8 rim nailed w/ (3) 12d nails @ 16" o.c. each ply,
notch post 3" to bear partial on rim,
(2) 1/2" through bolts
2x8 blocking over beams
PERGOLA & DECK SECTION
Simpson H2.5 clips @ rafters
or 8" timberlok into 2x10 below
2x4@ 6" o.c. w/ 5" timberlok into 2x6 below
6x6, 45 degree angle braces at top of post, extend 2'-0" horizontal
from post, attach to post & top 2-2x10 beam
w/ (2) 1/2" through bolts each end, typ. (4) locations
4x4 ex. posts, ex.
post bases, ex.
beam attachments
Simpson A23,
Simpson #9x2 1/2"
through facia/blocking,
Simpson #9x 1 1/2" to
rafter
Provide (4) Simpson DTT1Z lateral connectors for this portion of the deck
evenly spaced and within 24" of the deck ends/corners.
Lag into the house lower wall top plate.
No additional lateral connectors
required for this side of the deck,
existing beams provide adequate
lateral connection
BUIILDING CODE INFORMATION:
2021 IBC/IRC
Deck Dead Load = 10 psf
Deck Live Load = 60 psf
Ground Snow Load = 68 psf (7,790' elev.)
Wind Speed Vult = 175 mph, Exp. C
Seismic Design Category B
GENERAL NOTES:
1. All deck framing shall be pressure treated and shall be southern yellow pine #1 or better.
Pergola framing to be cedar or redwood..
2. Existing foundations were inspected and determined to be adequate for the deck replacement project.
3. Field verify existing rim board condition. Replace as necessary with 2x8 ledger board attached to
the house with (2) ledgerloks @ 16" o.c.
Simpson H2.5 clips
each joist to ex. beam
Ex. 4x beam
4/16/2024
APPROVED by SAFEbuilt;
2021 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
04/26/2024
PERMIT #24-EP-00123
Field Copy
Print out legibly & in color and have on-site for inspector
REVIEWED BY SAFEbuilt - 4/26/2024 - BY PBland
PERGOLAS REQUIRED
TO BE 50% OPEN
SITE PLAN REVIEWED
FOR BUILDING
COMPLIANCE
NO PORTION OF ANY BUILDING OR
STRUCTURE SHALL ENCROACH INTO
OR OVER AN EASEMENT LINES
Guardrail is required for deck walking
surfaces that are 30" or more above grade
Guardrails and the support of the Guardrail
shall be constructed per R507.10 of the
2021 IRC
In accordance with Manufacturers installation requirementsPlastic Composite