HomeMy WebLinkAboutPLANS Basement 655 Aspen Ave 2024-04-24All habitable space requires
heat supply and pressure relief.
Fire Block per section R302.11 -
See Handout
Drywall under stairs Min 1/2" if enclosed as
storage - walls, under-stair surface & any
soffit (R302.7)
Basement Finish Insulation:
Continuous Insulation = R15
OR
Cavity framing Insulation = R19
on exterior walls
All work shall be performed by
Licensed Contractors OR by the
homeowner residing in the dwelling.
DO NOT COVER WORK UNTIL IT HAS BEEN
APPROVED BY INSPECTION -
IF YOU HAVE FAILED A ROUGH INSPECTION
YOU MUST HAVE AN APPROVED REINSPECTION
BEFORE YOU COVER THE WORK UP.
Provide Tamper Resistant Receptacles
Float all walls - use treated sill
plates (recommended)
All rooms to be AFCI - except bath,
utility and unfinished rooms
SEE HANDOUTS FOR
ADDITIONAL CODE NOTES
AND GUIDANCE
Min. one window and well to meet
egress requirements for each
sleeping room - See Handout
max window sill height 44"
Per NEC 210.8 - All basement receptacles
(finished or not) except for permanently
installed fire or burglar alarms shall be
GFCI Protected.
Closet lights to conform to E4003.12
The entire building must be provided with
Smoke Detectors/CO Alarms - see handout
KEEP ALL PERMIT DOCUMENTS
TOGETHER & ON-SITE FOR
INSPECTORS REVIEW
PLANS AND CONSTRUCTION SHALL MEET
THE 2021 IRC, 2021 IECC, 2023 NEC AND
ALL APPLICABLE MUNICIPAL CODES &
ORDINANCES
PERMIT #24-EP-00091
Field Copy
Print out legibly & in color and have on-site for inspector
REVIEWED BY SAFEbuilt - 4/2/2024 - BY PBland
AP
P
R
O
V
E
D
b
y
S
A
F
E
b
u
i
l
t
;
20
2
1
I
n
t
e
r
n
a
t
i
o
n
a
l
C
o
d
e
s
Su
b
j
e
c
t
t
o
i
n
s
p
e
c
t
i
o
n
a
n
d
c
o
m
p
l
i
a
n
c
e
t
o
a
l
l
Re
l
e
v
a
n
t
,
a
d
o
p
t
e
d
B
u
i
l
d
i
n
g
&
M
u
n
i
c
i
p
a
l
Co
d
e
s
04
/
0
2
/
2
0
2
4
Document Published by SAFEbuilt, Inc. 5.10.2019 2 of 2
Ceiling Heights:
If the finished ceiling will be less than 7’, please consult your
Building Department.
Smoke Alarms:
Smoke alarms are required in all basements. If the finished
basement contains a sleeping room, a smoke alarm must be
installed on the ceiling or wall in the sleeping room and in the
hallway or area within 15’ of the sleeping room. Smoke alarms
added to satisfy the above requirements must be hard-wired with
a battery backup and interconnected with existing smoke alarms.
Smoke alarms are required to be hardwired and interconnected
in new AND existing bedrooms, halls and on each level.
CO Detectors: C/O detectors shall be installed outside of each
separate sleeping area within 15’ of the bedrooms. Detectors
may be battery operated, plug in type or combination smoke/co
detectors hard wired into the houses electrical system.
Insulation: Check with your local building department for
minimum exterior wall insulation requirements.
Fuel Burning Appliances:
Furnaces and water heaters cannot be located in a bed-room or
bathroom unless appliances are installed in a dedicated
enclosure in which all combustion air is taken directly from
outdoors and a weather stripped solid door equipped with an
approved self closing device is installed. If the furnace and water
heater are being enclosed, adequate combustion air must be
provided for these appliances to operate properly. A
minimum of 30” clear working space must be provided
in front of furnaces and water heaters. Maintenance or
PAGE 2
removal of each appliance must be possible without removing the
other or disturbing walls, piping, valves, wiring and junction boxes.
Fire Blocking:
Fire Blocking must be installed in concealed spaces of wood-furred
walls at the ceiling level, at 10’ intervals along the length of the wall
and at all interconnections of concealed vertical and horizontal
spaces such as intersection of stud walls and soffits or dropped
ceilings. A detail of typical fire blocking is included in this handout.
Fire blocks may be constructed of 2” lumber, 3/4” plywood or
particle board, 1/2” gypsum board or fiberglass insulation 16”
minimum in height, securely fastened.
Space under Stairs:
If the area under the stairs is enclosed useable space accessed by
a door or access panel, protect the walls and ceiling with 1/2”
gypsum board.
Bathrooms:
Toilets must be provided with a minimum of 21” in front of the toilet
and 15” from the center of the toilet to any sidewall or other
obstruction. Showers shall have a minimum inside dimension of
900 square inches. A ventilation fan is required in toilet rooms and
bathrooms with unopenable windows. The fan must be vented to
the exterior of the building and not to terminate within 3’ of an
opening into the building.
Sample Floor
RESIDENTIAL BASEMENT FINISH
Floor Joist Install
before
Fireblock here
Or here Minimum R-15
Insulation
Fireblock here
Or here
Or here
Existing concrete foundation
Fireblock concealed spaces of furred walls and soffits at
10 foot intervals along the length of the wall. Nail to
wall stud and hold tight to concrete foundation wall
from floor to ceiling.
Fill remaining gaps at top
New 2x4 perimeter
2x4 or
16”
insula-
tion
securely
Typical soffit
Finish
materi-
Basement Finish Requirements
Emergency Escapes:
All basements and sleeping
rooms must have an emergency
escape window or exterior door.
Emergency escape windows
with a sill height below grade
must be provided with an emer-
gency escape window as well as
ladder. For details on Emergen-
cy escape windows, see Section
R310 of the International Resi-
dential Code.
Sample Construction Details
Emergency Escapes:
All basements and sleeping
rooms must have an emergency
escape window or exterior door.
Emergency escape windows with
a sill height below grade must be
provided with a window well and
a ladder if the window well is
deeper than 44”. For details on
Emergency escape windows, see
Section R310 of the International
Residential Code.
BASEMENT FINISH HANDOUTNOTE: ANY NEW WINDOW
CUTS INTO FOUNDATION
REQUIRES ENGINEERING
Electrical outlets:
Receptacles shall be installed so that no point measured horizontally along the
floor line of any wall space is more than 6' from a receptacle outlet (E3901.2.1)
New 2x4 interior partition
Wall finish
40d nails every 24 inches through bottom plate into floor plate.
Pre-drill holes in bottom plate for 40d nails
Min. 1 1/2 inch void space
Pressure treated 2x4 floor plate anchored to floor slab
Spacer -- same thickness as wall finish material
Base moulding
nailed to spacer
only
Revision Date 9/23/2019
REQUIRED INSPECTIONS FOR RESIDENTIAL BASEMENT FINISH
All of the following must be inspected prior to covering.
Inspections labeled “Rough-in” and those labeled “Final” should be grouped.
Underground plumbing (Applicable if plumbing under slab added or moved)
Rough-in plumbing (Applicable if new plumbing added)
Rough-in electrical
Rough-in mechanical (Applicable if new duct work or heating appliances added)
Rough-in framing 1
Rough-in gas piping (Applicable if new gas line ran for an appliance) -10 pound
air test required on any new gas piping
Insulation (must be inspected prior to covering)
Poured Shower Pan (Applicable if membrane style pan installed)
Final plumbing (Applicable if new plumbing added)
Final electrical
Final mechanical (Applicable if new duct work or heating appliances added)
Final building 1
1 Note: Rough-in framing and final building will not be signed off until the plumbing, electrical, and
mechanical work has been approved.