HomeMy WebLinkAboutPLANS 951 Black Canyon Dr Basement Finish 2019PP..OO.. BBOOXX 22006666 FFOORRTT CCOOLLLLIINNSS,, CCOO.. 8800552222 997700--447722--55666677
DN
SB3021
SB3021
3DB1521
FHB21LRB363DB21
SB36 2DB15
TRASHDW3DB24 3DB24FHB21L FHB9R
SB3021
SB3021
3DB1521
FHB21LRB363DB21
SB36 2DB15
TRASHDW3DB24 3DB24FHB21L FHB9R
OTC302493
W421224 W2139R W2139LW3627
6068
3068FD
180703068
64310MU 64310MU 3068
5068
5068
5068
5068
64310MU
3068
3068
3068
3068 3068
3068
4568
E1E1
7 1/2"6'-4"
1'-0 1/2"1'-3"
2'9"2'-3 1/2"6'-4"3'-2 1/2"1'-8"3'8"
10"
2'3'-1 1/2"3'-3"2'3'-3"1'-6"3'2'18'1'-6"
20'-1 1/2"5'-5"6'-7 1/2"7'-4 1/2"5'-11 1/2"8'-6"26'
80'
21'-6"3'1'-6"3'-5 1/2"6'-4"2'-3"
26'12'-0 1/2"2'-5"2'-4 1/2"11'-10"5'-4"8'8'4'
2'
14'
14'
30'
15'-6"
2'
6'-6"
30'
4'
2'
2'-6 1/4"
2'
5 3/4"
6'
6"
2'
6"
8 3/4"
12'-6 1/2"
8 3/4"
3'-6"
3'-11 1/4"12'-10 1/2"6'-10 1/4"
25'-7" X 23'-3"
1419 SQ FT
7'-9" X 11'-8"
11'-5" X 15'-3"
2'-1" X 11'-7"2'-1" X 11'-7"
3'-8" X 1'-4"
11'-5" X 15'-3"
4'-3" X 7'-3"
6'-7" X 7'-8"
21'-3" X 16'-0"
5'-8" X 7'-7"
16'-3" X 6'-7"
LIVING AREA
GARAGEBEDROOM 1 BEDROOM 2
STAIRWELL
CLOSET
BATH 1 VANITY 1
CLOSET CLOSET
UTILITY
DECK
NEW DECK
LINEN
NEW CONCRETE FP SURROUND (COLOR TBD)
NEW CONCRETE COUNTERTOP SURFACE (COLOR TBD)
COUNTERTOP OVERHANG 15" D X 12'10 W X 36" H
(MATERIAL TBD)
Project
Date
Scale
Sheet
No.Revision/Issue Date
PROJECT:
PPLLAANN NNOOTTEESS::
BUILDER RESERVES THE RIGHT TO
MAKE ANY AND ALL CHANGES DUE TO
CODE REQUIREMENTS,
CONSTRUCTABILITY, HOA
REQUIREMENTS, AND OR SUBSTITUTE
ANY MATERIAL FOR A MATERIAL OF
EQUAL OR GREATER VALUE AT THEIR
SOLE AND ABSOLUTE DISCRETION.
ALL MEASUREMENTS ARE
APPROXIMATE. COMMERCIAL
SPACES WILL BE BUILT IN
SUBSTANTIAL ACCORDANCE WITH
THESE PLANS CHANGES THAT ARE
NOT A SUBSTANTIAL DEVIATION FROM
THE PLAN ARE NOT GROUNDS TO
CANCEL THE CONTRACT.
A 1
10/9/2019
1/4" = 1'-0"
ESTES PARK, COLORADO
RODRIGUEZ REMODEL
951 BLACK CANYON DR.
REMODEL
MAIN FLOOR PLAN
SCALE: 1/4" = 1'-0"
MAIN
FLOOR
PLAN
Per response letter this deck
will not be constructed at this
time. Protection from fall is
required at this opening
Windows to comply with R308
APPROVED by SAFEbuilt;
2015 International Codes
Subject to inspection and compliance to all
Relevant, adopted Building & Municipal
Codes
12/18/2018
REVIEWED BY ______________________
CONSTRUCTION TYPE _______________
OCCUPANCY CLASSIFICATION ________
SPRINKLERED ______________________
12/10/2019
This structure must comply
with the requirements of the
2017 National Electrical Code
LLA
VB
R3
No
Reviewed by
SAFEbuilt
12/10/2019
PP..OO.. BBOOXX 22006666 FFOORRTT CCOOLLLLIINNSS,, CCOO.. 8800552222 997700--447722--55666677
S
S
SB3021 3DB2421SB3021SB30213DB2421SB3021
WH
64310MU
30686068
3068
30683068
3068
64310MU 64310MU
2668
2668
6068
UP
E1E1
7 1/2"
6'-4"
1'-0 1/2"8 1/2"
2'
1'-3 1/2"
5'-7"2'17'-8 1/2"
25'-3 1/2"6'-10"7'-5"7'-0 1/2"7'-7"25'-10"
80'
6'-4"4'-8 1/2"4'-7 1/2"6'-4"3'-3"
40'-6"14'-2 1/2"5'-3 1/2"8'8'4'
80'
2'-6 1/2"
2'
5 3/4"
6'
5 3/4"
2'
6"
8 3/4"
12'-6 1/2"
8 3/4"
2'
14'
14'
30'
24'
30'
4'
20'-11" X 26'-6"
1477 SQ FT
25'-3" X 22'-9"
10'-11" X 13'-7"
3'-3" X 1'-4"
13'-11" X 10'-3"
6'-6" X 6'-9"
6'-11" X 13'-0"
7'-2" X 6'-10"
11'-1" X 3'-0"6'-7" X 3'-0"
2'-0" X 6'-7"
LIVING AREA
UNEXCAVATEDFAMILY
BEDROOM 4
VANITY 2
UTILITY
BATH 2
BEDROOM 3
LINEN
(3) SHELVES
HALLCLOSET
CLOSET
4" RAISED STEP
4" RAISED STEP
Project
Date
Scale
Sheet
No.Revision/Issue Date
PROJECT:
PPLLAANN NNOOTTEESS::
BUILDER RESERVES THE RIGHT TO
MAKE ANY AND ALL CHANGES DUE TO
CODE REQUIREMENTS,
CONSTRUCTABILITY, HOA
REQUIREMENTS, AND OR SUBSTITUTE
ANY MATERIAL FOR A MATERIAL OF
EQUAL OR GREATER VALUE AT THEIR
SOLE AND ABSOLUTE DISCRETION.
ALL MEASUREMENTS ARE
APPROXIMATE. COMMERCIAL
SPACES WILL BE BUILT IN
SUBSTANTIAL ACCORDANCE WITH
THESE PLANS CHANGES THAT ARE
NOT A SUBSTANTIAL DEVIATION FROM
THE PLAN ARE NOT GROUNDS TO
CANCEL THE CONTRACT.
A 2
1/4" = 1'-0"
REMODEL
BASEMENT FLOOR PLAN
SCALE: 1/4" = 1'-0"
BASEMENT
FLOOR
PLAN
10/9/2019
ESTES PARK, COLORADO
RODRIGUEZ REMODEL
951 BLACK CANYON DR.
General Notes:
-All rooms to be AFCI except bath, utility and
unfinished rooms
-Bath, utility and unfinished rooms to be GFCI
-Backwater valves to remain accessible
-1/2” dry wall req’d for enclosed usable space
under stairs
-Smoke alarms req’d in each sleeping room
-Smoke/CO alarms req’d w/in 15’vicinity of
bedroom exteriors
-Min 1 emergency escape and rescue opening
req’d per bedroom
2015 IECC sec. R402.4.4
Appliances must be direct vent
(combustion and exhaust) or the
mechanical equipment must be located
within a room entirely isolated from the
rest of the building's thermal envelope in
accordance with sec. R402.4.4
Reviewed by
SAFEbuilt
12/10/2019
Reviewed by
SAFEbuilt
12/10/2019
PP..OO.. BBOOXX 22006666 FFOORRTT CCOOLLLLIINNSS,, CCOO.. 8800552222 997700--447722--55666677
DN
R
DW GD
RRR
T
R
CO/SD
GFCI
DM
GFCIGFCI
DM
DM
7'6'-9"9'-11"
1'-5"5'5'8'-3 1/2"
1419 SQ FT
LIVING AREA
GARAGEBEDROOM 1 BEDROOM 2
STAIRWELL
CLOSET
BATH 1 VANITY 1
CLOSET CLOSET
UTILITY
DECK
NEW DECK
LINEN
Project
Date
Scale
Sheet
No.Revision/Issue Date
PROJECT:
PPLLAANN NNOOTTEESS::
BUILDER RESERVES THE RIGHT TO
MAKE ANY AND ALL CHANGES DUE TO
CODE REQUIREMENTS,
CONSTRUCTABILITY, HOA
REQUIREMENTS, AND OR SUBSTITUTE
ANY MATERIAL FOR A MATERIAL OF
EQUAL OR GREATER VALUE AT THEIR
SOLE AND ABSOLUTE DISCRETION.
ALL MEASUREMENTS ARE
APPROXIMATE. COMMERCIAL
SPACES WILL BE BUILT IN
SUBSTANTIAL ACCORDANCE WITH
THESE PLANS CHANGES THAT ARE
NOT A SUBSTANTIAL DEVIATION FROM
THE PLAN ARE NOT GROUNDS TO
CANCEL THE CONTRACT.
E 1
1/4" = 1'-0"
REMODEL
ELECTRICAL
MAIN FLOOR
PLAN
10/9/2019
ELECTRICAL MAIN FLOOR PLAN
SCALE: 1/4" = 1'-0"
ESTES PARK, COLORADO
RODRIGUEZ REMODEL
951 BLACK CANYON DR.
General Residential Electrical Requirements
- Smoke detectors required inside and outside all
bedrooms.
- Min. one smoke detector required on each level.
- Carbon monoxide detectors required within 15' of
all bedrooms throughout home.
- All outlets less than 5'6" AFF to be tamper
resistant.
- All circuits arc-fault except bathrooms and
unfinished areas.
- Min. (2) 20A, dedicated, GFCI/AFCI protected,
small appliance, countertop circuits required in
kitchens.
- Min. (1) 20A, dedicated, GFCI protected outlet
required within 36" of all lavs.
- Garage circuits to be dedicated, 20A, and GFCI
protected.
- Laundry circuit to be 20A, GFCI protected.
- All GFCI devices must be readily accessible.
- Crawlspace lighting circuits to be GFCI protected.
- Service receptacles required within 25' of all
appliances.
Reviewed by
SAFEbuilt
12/10/2019
PP..OO.. BBOOXX 22006666 FFOORRTT CCOOLLLLIINNSS,, CCOO.. 8800552222 997700--447722--55666677
WH
UP
GFCIGFCI
R R
3
3
GFCI
C5/TV
R
R R
RR
R
R
R
R
R
DM
1477 SQ FT
LIVING AREA
UNEXCAVATEDFAMILY
BEDROOM 4
VANITY 2
UTILITY
BATH 2
BEDROOM 3
LINEN
HALLCLOSET
CLOSET
Project
Date
Scale
Sheet
No.Revision/Issue Date
PROJECT:
PPLLAANN NNOOTTEESS::
BUILDER RESERVES THE RIGHT TO
MAKE ANY AND ALL CHANGES DUE TO
CODE REQUIREMENTS,
CONSTRUCTABILITY, HOA
REQUIREMENTS, AND OR SUBSTITUTE
ANY MATERIAL FOR A MATERIAL OF
EQUAL OR GREATER VALUE AT THEIR
SOLE AND ABSOLUTE DISCRETION.
ALL MEASUREMENTS ARE
APPROXIMATE. COMMERCIAL
SPACES WILL BE BUILT IN
SUBSTANTIAL ACCORDANCE WITH
THESE PLANS CHANGES THAT ARE
NOT A SUBSTANTIAL DEVIATION FROM
THE PLAN ARE NOT GROUNDS TO
CANCEL THE CONTRACT.
ELECTRICAL BASEMENT PLAN
SCALE: 1/4" = 1'-0"
1/4" = 1'-0"
REMODEL
ELECTRICAL
BASEMENT
PLAN
10/9/2019
E 2
ESTES PARK, COLORADO
RODRIGUEZ REMODEL
951 BLACK CANYON DR.
General Residential Electrical Requirements
- Smoke detectors required inside and outside all
bedrooms.
- Min. one smoke detector required on each level.
- Carbon monoxide detectors required within 15' of
all bedrooms throughout home.
- All outlets less than 5'6" AFF to be tamper
resistant.
- All circuits arc-fault except bathrooms and
unfinished areas.
- Min. (2) 20A, dedicated, GFCI/AFCI protected,
small appliance, countertop circuits required in
kitchens.
- Min. (1) 20A, dedicated, GFCI protected outlet
required within 36" of all lavs.
- Garage circuits to be dedicated, 20A, and GFCI
protected.
- Laundry circuit to be 20A, GFCI protected.
- All GFCI devices must be readily accessible.
- Crawlspace lighting circuits to be GFCI protected.
- Service receptacles required within 25' of all
appliances.
Reviewed by
SAFEbuilt
12/10/2019