HomeMy WebLinkAboutPLANS 561 Big Thompson Ave EG America Store 2021-02-12THE BUILDING SHALL BE IN COMPLIANCE WITH THE MOST R ECENT VERSION OF THE FOLLOWING CODES:
PROJECT CODE INFORMATION
2018 INTERNATIONAL BUILDING CODE
2018 INTERNATIONAL MECHANICAL CODE
2018 INTERNATIONAL PLUMBING CODE
2018 INTERNATIONAL ENERGY CONSERVATION CODE
2017 NFPA 70 NATIONAL ELECTRICAL CODE
2009 AMERICANS WITH DISABILITIES ACT (ADA)
2013 NFPA 13 INSTALLATION OF SPRINKLER SYSTEMS
O.S.H.A
2018 INTERNATIONAL FIRE CODE
2018 INTERNATIONAL EXISTING BUILDING CODE
OCCUPANCY CLASS
OCCUPANCY CLASS
MERCANTILE
SECTION
M
NOTES
CONVENIENCE STORE
SQUARE FOOTAGE
OCC.SQ. FT.SECTION
192
NOTES% OF AREA
8%
TOTAL 2,221 100%
CONSTRUCTION TYPE
TYPE
STRUCTURAL FRAME
BEARING WALLS (EXT)
SECTION
VB
NOTESRATING
BEARING WALLS (INT)
NON-BEARING WALLS (EXT)
FLOOR CONSTRUCTION
NON-BEARING WALLS (INT)
FIRE PROTECTION SYSTEMS
ELEMENT REQUIRED
SPRINKLER SYSTEM
SECTION
NO
NOTESPROVIDED
NO
ELEMENT
AREA
REMODEL M
PORT. FIRE EXTINGUISHERS YES YES
FIRE ALARM & DETECTION NO NO
-
-
-
-
-
-
-
EXISTING
VERIFY W/ LOCAL CODE
UNDER 500 OCCUPANTS
IBC -309
IBC CHAP. 5
IBC TABLE
601
IBC -903
IBC -906
IBC -907
PLUMBING FIXTURES
FIXTURE REQUIRED
WATER CLOSETS
LAVATORIES
SECTION
1
BATHTUBS / SHOWERS
DRINKING FOUNTAINS
SERVICE SINK
OCCUPANTS
24
1
NONE
1 PER 1000
1
EXCEPT. IPC 410.4 REST. PROVIDES WATER DISP.
IPC -403.1
AREA OF WORK
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
SEPARATE FACILITIES SHALL NOT BE REQUIRED
IN MERCANTILE OCCUPANCIES IN WHICH THE
MAXIMUM OCCUPANT LOAD IS 100 OR FEWER
EXISTING BUILDING INFO
AREA TYPE
EXISTING / RENOVATION
SECTION
ALTERATION
LEVEL 2
NOTES
RENOVATION OF EXISTING BUILDING
SCHRADER OIL (M)
IEBC -801.3
PROVIDED
3
2,029UNALTERED M
2
0
1
92%
EG AMERICA (M)
2,221 SF
AREA OF WORK
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:43 PM
12322-034
G001
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
CO
V
E
R
S
H
E
E
T
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
VICINITY PLAN KEY PLAN
TRUENORTH
INDEX OF DRAWINGS
SHEET NO. DESCRIPTION
COVER
G001 COVER SHEET
G002 EGRESS PLAN
G003 SYMBOLS AND ABBREVIATIONS
G004 ACCESSIBILITY STANDARDS
G005 RESPONSIBILITY SCHEDULE
DEMOLITION
D100 DEMOLITION PLAN
ARCHITECTURAL
A150 FIXTURE PLAN
A151 EQUIPMENT SCHEDULE
A160 CASEWORK PLAN & DETAILS
PLUMBING
P001 PLUMBING SPECIFICATIONS
P110 SANITARY PIPING PLAN
REFRIGERATION
R100 REFRIGERATION PLAN AND SCHEDULES
ELECTRICAL
E001 ELECTRICAL SPECIFICATIONS
E110 POWER PLAN
E501 ELECTRICAL DETAILS
SCOPE OF WORK
GENERAL
DEMOLITION, RELOCATION AND INSTALLATION OF NEW
CONVENIENCE EQUIPMENT FOR FOOD SERVICE. CASEWORK AN D
UTILITY UPDATES AS REQUIRED TO ACCOMMODATE.
CIVIL / SITE
NONE.
ARCHITECTURAL
DEMO AND INSTALLATION OF NEW EQUIPMENT.
DEMO EXISTING AND INSTALLATION OF NEW CASEWORK.
MECHANICAL
NEW EXHAUST FAN OVER OVENS.
ELECTRICAL
PROVIDE NEW/MODIFY POWER TO NEW CONVENIENCE
EQUIPMENT AND RELOCATED EQUIPMENT.
INSTALL NEW POWER AS REQUIRED FOR NEW CONDENSING
UNITS
PLUMBING
INSTALL NEW/MODIFY EXISTING SANITARY AND WATER SUPP LY
TO NEW AND RELOCATED EQUIPMENT.
INSTALL NEW WATER FILTER SYSTEM.
INSTALL NEW CONDENSING UNITS AS REQUIRED FOR NEW DR INK
EQUIPMENT
PROJECT DIRECTORY
PROJECT ADDRESS
ARCHITECT
561 BIG THOMPSON AVE.,
ESTES PARK, CO 80517
LARSON DESIGN GROUP
ARCHITECT: ROBERT J. GEHR, AIA, NCARB
CONTACT PROJECT MANAGER: BRENT DRESSLER
1000 COMMERCE PARK DR.
SUITE 201
WILLIAMSPORT, PA 17701
TEL: 570-323-6603
FAX: 570-323-9902
ELECTRICAL ENGINEER
KEITH ISNER, PE
CONTACT PROJECT MANAGER: BRENT DRESSLER
1000 COMMERCE PARK DR.
SUITE 201
WILLIAMSPORT, PA 17701
TEL: 570-323-6603
FAX: 570-323-9902
PLUMBING ENGINEER
MATTHEW NEALIS, PE
CONTACT PROJECT MANAGER: BRENT DRESSLER
1000 COMMERCE PARK DR.
SUITE 201
WILLIAMSPORT, PA 17701
TEL: 570-323-6603
FAX: 570-323-9902
561 BIG THOMPSON AVE., ESTES PARK, CO 80517
EG AMERICA STORE #750828
561 BIG THOMPSON AVE.,
ESTES PARK
STEAMER DR
B I G T H O M P S O N A V E
TRUE
NORTH
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
02/12/2021
2.4"
0.212
34"
170
A
EX. EM
EXIT SIGN
EX. EM
EXIT SIGN
B
2.4"
0.212
34"
170
WALK-IN COOLER
BOH
OFFICE
SALES
CHECKOUT
WOMEN'S RESTROOM MEN'S RESTROOM
1
EX. EM LIGHT
EX. EM LIGHT
EGRESS PLAN LEGEND
10"
0.250
34"
170
PROVIDED CLEAR OPENING
WIDTH
WIDTH PER OCCUPANT
LOAD FACTOR (1005.1)
REQUIRED OPENING WIDTH
OCCUPANT LOAD
ATTRIBUTED TO EXIT
TRAVEL ROUTE FROM SPACE TO EXIT
EXIT DOOR WITH PANIC HARDWARE &
TACTILE SIGNAGE
OPENING CAPACITY
FIRE EXTINGUISHERFE
MEANS OF EGRESS
DOORS 36" MINIMUM
44" MIN AT STOCKROOM AISLE
(NON-SPRINKLERED)TRAVEL DISTANCE
ELEMENT REQUIRED PROVIDEDNOTES
75 FT MAX
0.20" PER
OCCUPANT FOR
EACH MEANS
OF EGRESS
REQUIRED 4.8"
1-49 OCCUPANTS = 1 EXITTOTAL EXITS 1 EXIT
EGRESS MAY PASS THROUGH RECEIVING
AREAS AND STOCKROOMS IN M OCCUPANCIES
(VERIFY W/ LOCAL CODE)
EXIT ACCESS INTERVENING
SPACES
68"
2 EXITS
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
DA
T
E
CO
M
M
E
N
T
S
BY
CH
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:
\
U
s
e
r
s
\
M
S
c
o
t
t
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
R
K
_
C
O
_
C
en
t
r
a
l
_
M
s
c
o
t
t
8
D
D
T
S
.
r
v
t
2/
1
1
/
2
0
2
1
6
:
0
8
:
2
1
P
M
12322-034
G002
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
EG
R
E
S
S
P
L
A
N
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
OCCUPANCY IBC TABLE 1004.1.1
OCCUPANCY S.F. TYPE
S.F.PER
PERSON S.F UNIT
KITCHEN, COMMERCIAL 200 GROSS
BUSINESS 100 GROSS
MERCANTILE 60 GROSS
STORAGE 300 GROSS
UNOCCUPIED 0
EGRESS PATHS
EXIT PATH EXIT PATH DISTANCE
'A'
'B'
TOTAL PATH LENGTH - 73'-7"
TOTAL PATH LENGTH - 49'-2"
KEYED NOTES
1 G.C. TO FURNISH & INSTALL NEW FIRE EXTINGUISHERS AS REQ'D BY
LOCAL CODES. WHEN MOUNTING ADJACENT TO DOOR OPENING,
MAINTAIN 12" CLEAR TO DOOR OPENING FOR ADA COMPLIANCE. FINAL
LOCATION, MOUNTING HEIGHT, & QUANTITY BY FIRE INSPECTOR. G.C. TO
VERIFY FIRE MARSHALL REQUIREMENTS FOR INSPECTION & TAGGING.
SCALE:1/4" = 1'-0"G002
1 EGRESS PLAN
X
OCCUPANT LOAD - EG AMERICA
NAME AREA OCCUPANCY SF PERSON PERSONS
BUSINESS
OFFICE 34 SF BUSINESS 100 1
CHECKOUT 109 SF BUSINESS 100 2
KITCHEN, COMMERCIAL
BOH 283 SF KITCHEN, COMMERCIAL 200 2
MERCHANTILE
SALES 1060 SF MERCHANTILE 60 18
STORAGE
WALK-IN COOLER 230 SF STORAGE 300 1
UNOCCUPIED
WOMEN'S RESTROOM 125 SF UNOCCUPIED 0
MEN'S RESTROOM 119 SF UNOCCUPIED 0
1961 SF 24TOTALS(NET SQUARE FOOTAGE)
GENERAL NOTES
A. G.C. TO PROVIDE SIGNAGE FOR EVERY ROOM OR SPACE IN THE ASSEMBLY
OCCUPANCIES SHOWING THE OCCUPANT LOAD OF THE ROOM O R SPACE
POSTED IN A CONSPICUOUS PLACE NEAR THE MAIN EXIT OR EXIT ACCESS
DOORWAYS. COORDINATE WITH LOCAL INSPECTOR.
B. ALL EGRESS DOORS SHALL BE EQUIPPED WITH PANIC HA RDWARE, OR WILL
NOT BE PROVIDED WITH A LOCK OR LATCH.
C. ALL REQUIRED EXIT DOORS TO HAVE EMERGENCY LIGHTING AND EXIT SIGNS.
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
02/12/2021
SYMBOLS
WALL LEGENDHATCH PATTERNS
ACOUSTIC TILE
ASPHALT
ROOFING
INSULATION
CONCRETE
(CAST-IN-PLACE
OR PRECAST)
CONCRETE
MASONRY
EARTH OR BACKFILL
CONCRETE
(FINISHED)
BRICK
FINISH WOOD
GLASS
RIGID
INSULATION
WOOD
STEEL
PLYWOOD
GRANULAR
SUBBASE
FIRE RATINGS
EXISTING OR NEW LOW WALL ASSEMBLY
NEW STUD WALL ASSEMBLY
DEMOLISHED WALL OR
BULKHEAD ABOVE
1-HOUR FIRE RATED ASSEMBLY
2-HOUR FIRE RATED ASSEMBLY
3-HOUR FIRE RATED ASSEMBLY
4-HOUR FIRE RATED ASSEMBLY
1
0
A0.0
0
A0.0
CALLOUT BUBBLE SECTION & DETAIL
MARKER
KEY
NOTE
A
WINDOW
TAG
100
DOOR
TAG
1
DEMO
KEY
NOTE
REVISION NOTE
& CLOUD
1
COLUMN
GRID TAG
1
WALL
TAG
D
AC
B
A0.0
0
EXTERIOR
ELEVATION
MARKER
INTERIOR
ELEVATION
MARKER
DRAWING NUMBER
SHEET NUMBER
ROOM NAME
00
ROOM NAME
& NUMBER
FIRST FLOOR
100.00'
FLOOR
ELEVATION
TAG
0
A0.0
1
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:47 PM
12322-034
G003
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
SY
M
B
O
L
S
A
N
D
A
B
B
R
E
V
I
A
T
I
O
N
S
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
@ AT
& AND
A AMPERE, COMPRESSED AIR
A/C AIR CONDITIONING
AB ANCHOR BOLT
ABAN ABANDON(ED)
ABT ABOUT
ABUT ABUTMENT
ABV ABOVE
AC ALTERNATING CURRENT
ACC ACCESSIBLE
ACI AMERICAN CONCRETE INSTITUTE
ACS ACCESS
ACT ACOUSTICAL CEILING TILE
ADDL ADDITIONAL
ADDM ADDENDUM
ADH ADHESIVE
ADJ ADJACENT, ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AGGR AGGREGATE
AHD AHEAD
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE
OF STEEL CONSTRUCTION
ALT ALTERNATE
ALUM ALUMINUM
AMER STD AMERICAN STANDARD
ANC ANCHOR, ANCHORAGE
ANOD ANODIZED
APPD APPROVED
APPROX APPROXIMATE
APPV APPROVE
ARCH ARCHITECT, ARCHITECTURAL
ARR ARRANGEMENT
ASAP AS SOON AS POSSIBLE
ASSY ASSEMBLY
ASTM AMERICAN SOCIETY OF TESTING
AND MATERIALS
AUTO AUTOMATIC
AUX AUXILIARY
AVG AVERAGE
AWG AMERICAN WIRE GAGE
AWS AMERICAN WELDING SOCIETY
AZ AZIMUTH
B/B BACK TO BACK
BC BOLT CIRCLE
BD BOARD
BFILL BACK FILL
BITUM BITUMINOUS
BK BACK
BL BASE LINE, BUILDING LINE
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM, BENCH MARK
BOC BOTTOM OF CURB
BOD BOTTOM OF DUCT
BOF BOTTOM OF FOOTING
BOP BOTTOM OF PIPE
BOS BOTTOM OF STEEL
BOT BOTTOM
BOW BOTTOM OF WALL
BP BASE PLATE
BRCG BRACING
BRG BEARING
BRG PL BEARING PLATE
BRK BRICK
BRKT BRACKET
BS BOTH SIDES
BSMT BASEMENT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BTWN BETWEEN
BVL BEVELED
A
B
C
C TO C CENTER TO CENTER
CANTIL CANTILEVER
CAP CAPACITY
CB CATCH BASIN
CBORE COUNTERBORE
CC CUBIC CENTIMETER
CCTV CLOSED CIRCUIT TELEVISION
CLSM CONTROLLED LOW STRENGTH
MATERIAL
CEM CEMENT
CER CERAMIC
CERTS CERTIFICATES
CFM CUBIC FOOT (FEET) PER
MINUTE
CFS CUBIC FOOT (FEET) PER
SECOND
CG CENTER OF GRAVITY
CHFR CHAMFER
CHKD CHECKED, CHECKERED
CLG HT CEILING HEIGHT
CI CAST IRON
CIP CAST-IN-PLACE, CAST IRON
PIPE
CJ CONSTRUCTION JOINT
CL CENTER LINE
CLG CEILING
CLJ CONTROL JOINT
CLO CLOSET
CLR CLEAR, CLEARANCE
CLWG CLEAR WIRE GLASS
CM CENTIMETER
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO CLEAR OPENING
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONN CONNECTION, CONNECTOR
CONSTR CONSTRUCTION
CONT CONTINUE, CONTINUATION,
CONTINUOUS
COORD COORDINATE
CORP CORPORATE, CORPORATION
CORR CORRIDOR, CORRUGATED
CPT CARPET
CRS COLD ROLLED STEEL
CS CARBON STEEL
CSK COUNTERSINK
CSMT CASEMENT
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTJ CONTRACTION JOINT
CTR CENTER
CTW CERAMIC TILE WAINSCOT
CTWALK CATWALK
CU COPPER
CU IN CUBIC INCH
CU FT CUBIC FEET
CU M CUBIC METER
CU MM CUBIC MILLIMETER
CUB CUBICLE
CU YD CUBIC YARD
CYL CYLINDER
D DEEP, DEPTH, PENNY(NAIL)
DB DRY BULB
DBL DOUBLE
DC DIRECT CURRENT
DDC DIRECT DIGITAL CONTROL
DEG DEGREE
DEMO DEMOLISH. DEMOLITION
DET DETAIL
DF DRINKING FOUNTAIN
DFT DRY FILM THICKNESS
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL, DIAGRAM
DIFF DIFFERENCE
DIM DIMENSION
DL DEAD LOAD
DMPR DAMPER
DN DOWN
DOM DOMESTIC
DP DEW POINT
DR DOOR
DS DISCONNECT SWITCH,
DOWNSPOUT
DWG DRAWING
E EAST
EA EACH
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EER ENERGY EFFICIENCY RATIO
EF EACH FACE
EFF EFFICIENCY
EJ EXPANSION JOINT
EL EACH LAYER, ELEVATION
ELEC ELECTRIC/ELECTRICAL
ELEV ELEVATOR
EMB EMBANKMENT
EMBED EMBEDMENT
EMER EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EOD EDGE OF DECK
EOS EDGE OF SLAB
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
ERV ENERGY RECOVERY
VENTILATOR
ES EACH SIDE, EDGE OF
SHOULDER, ELECTROSTATIC
ESP EXTERNAL STATIC PRESSURE
EVAP EVAPORATOR
EW EACH WAY
EWC ELECTRIC WATER COOLER
EXC EXCAVATE
EXP EXPANSION
EXIST EXISTING
EXT EXTERNAL, EXTERIOR
EXT GR EXTERIOR GRADE
D
FA FIRE ALARM
FB FLAT BAR
FC BRK FACE BRICK
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
CONNECTION
FDMPR FIRE DAMPER
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF EL FINISHED FLOOR ELEVATION
FGL FIBERGLASS
FIN FINISHED
FIN FLR FINISHED FLOOR
FL FLOOR LINE
FLA FULL LOAD AMPS
FLG FLANGE, FLOORING
FLJ FLOOR JOIST
FLR FLOOR
FLR PL FLOOR PLATE
FOC FACE OF CONCRETE
FOF FACE OF FINISH
FOM FACE OF MASONRY
FOS FACE OF STUDS
FPM FOOT (FEET) PER MINUTE
FPS FOOT (FEET) PER SECOND
FR FRAME
FRP FIBER REINFORCED PLASTIC
FS FAR SIDE, FEDERAL
SPECIFICATION
FT FOOT (FEET)
FTG FOOTING
FVNR FULL VOLTAGE
NoN-REVERSING
FVR FULL VOLTAGE REVERSING
G GIRDER, GROUND, GROUND
WIRE, NATURAL GAS
GA GAUGE OR GAGE
GAB GRADED AGGREGATE BASE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GF GROUND FACE
GFCI/GFI GROUND FAULT CIRCUIT
INTERRUPTION
GL GIRT LINE, GLASS
GROUND LEVEL
GND GROUND
GOVT GOVERNMENT
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPS GALLONS PER SECOND
GR GRADE
GR BM GRADE BEAM
GRTG GRATING
GT GIRDER TRUSS, GROUT
GWB GYPSUM WALLBOARD
GWR GLYCOL WATER RETURN
GWS GLYCOL WATER SUPPLY
H HIGH
HC HOLLOW CORE
HCA HEADED CONCRETE ANCHOR
HDR HEADER
HDW HARDWARE
HDWD HARDWOOD
HEX HEXAGONAL
HEX HD HEXAGONAL HEAD
HG HOT GAS, HEAT GAIN,
MERCURY
HGR HANGER
HK HOOK
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSE POWER
HPS HIGH PRESSURE SODIUM
HPT HIGH POINT
HS HIGH STRENGTH
HSB HIGH STRENGTH BOLT
HSS HOLLOW STRUCTURAL SHAPE
HT HEIGHT
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
HVY HEAVY
HW HOT WATER
HWR HOT WATER RETURN
HWS HOT WATER SUPPLY
HWY HIGHWAY
HZ HERTZ
IBC INTERNATIONAL BUILDING
CODE
IBO INSTALLED BY OTHERS
ID INSIDE DIAMETER
IE THAT IS
IF INSIDE FACE
IJ ISOLATION JOINT
IN INCH
INC INCORPORATED, INCREASE
INCL INCLUDE
INFO INFORMATION
INSUL INSULATE/INSULATION
INTMD INTERMEDIATE
INT INTERIOR
IPS IRON PIPE SIZE
IR INSIDE RADIUS
J-BOX JUNCTION BOX
JAN CLO JANITOR'S CLOSET
JST JOIST
JT JOINT
K KIP (THOUSAND POUNDS)
KB KNEE BRACE
KFT THOUSAND FT POUNDS
KLF KIPS PER LINEAR FOOT
KO KNOCK OUT
KPL KICK PLATE
KSI KIPS PER SQUARE INCH
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVAR
KW KILOWATT
H
L LEFT
LAD LADDER
LAM LAMINATE
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LG LENGTH
LH LEFT HAND
LL LIVE LOAD
LLBB LONG LEG BACK TO BACK
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDE, LONGITUDINAL
LPCR LOW PRESSURE CONDENSATE RETURN
LPS LOW PRESSURE STEAM
LPT LOW POINT
LS LUMP SUM
LVL LAMINATED VENEER LUMBER, LEVEL
LVR LOUVER
LWC LIGHTWEIGHT CONCRETE
LWIC LIGHTWEIGHT INSULATING CONCRETE
MAINT MAINTENANCE
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MBTUH THOUSAND BRITISH THERMAL
UNITS PER HOUR
MC MECHANICAL CONTRACTOR
MOMENT CONNECTION
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MECH MECHANICAL
MED MEDIUM
MEMB MEMBRANE
MEZZ MEZZANINE
MFD MANUFACTURED
MFR MANUFACTURER
MH MANHOLE
MI MALLEABLE IRON, MILE
MIL ONE THOUSANDTH INCH
MIN MINIMUM
MISC MISCELLANEOUS
MLDG MOLDING, MOULDING
MLO MAIN LUGS ONLY
MM MILLIMETER
MO MASONRY OPENING
MR MOISTURE RESISTANT
MTD MOUNTED
MTL METAL
MV MERCURY VAPOR
N NORTH
NA NOT APPLICABLE
NAAMM NATIONAL ASSOCIATION OF
ARCHITECTURAL METAL MFR.
NATL NATIONAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE, NECESSARY
NEMA NATIONAL ELECTRICAL
NF MANUFACTURERS ASSOCIATION
NESC NATIONAL ELEC SAFETY CODE
NF NEAR FACE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPT NATIONAL TAPER PIPE (THREAD)
NS NEAR SIDE
NTS NOT TO SCALE
OA OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFM OUTSIDE FACE OF MASONRY
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OR OUTSIDE RADIUS
OSB ORIENTED STRAND BOARD
OSHA OCCUPATIONAL SAFETY AND
HEALTH ADMINISTRATION
OVHD OVERHEAD
OWJ OPEN-WEB JOIST
OZ OUNCE
/ PER (BETWEEN WORDS)
P PUMP
PAR PARALLEL
PB PUSH BUTTON
PBO PROVIDED BY OTHERS
PC PLUMBING CONTRACTOR
PIECE
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PEC PHOTO ELECTRIC CELL
PERF PERFORATED
PERP PERPENDICULAR
PH PHASE
PIBO PROVIDED AND INSTALLED
BY OTHERS
PL PLATE, PROPERTY LINE
PLAM PLASTIC LAMINATE
PLF POUNDS PER LINEAR FOOT
PL GL PLATE GLASS
PLYWD PLYWOOD
PMF PRE-MOLDED FILLER,
PROBABLE MAXIMUM FLOOD
PNL PANEL
PR PAIR
PREFIN PREFINISHED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH
ABSOLUTE
PSIG POUNDS PER SQUARE INCH
GAGE
PT PAINT, PRESSURE TREATED
PTD PAINTED
PTN PARTITION
PTW PRESSURE TREATED WOOD
PVC POINT OF VERTICAL
CURVE, POLYVINYL CHLORIDE
N
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QT QUARRY TILE, QUART
QTY QUANTITY
R RADIUS, RISER
RA RETURN AIR
RC REINFORCED CONCRETE
RD ROOF DRAIN
RE: REFER TO
RECPT RECEPTACLE
REINF REINFORCING
REM REMOVABLE
REQD REQUIRED
REV REVISION
RFG ROOFING
RH RIGHT HAND
RM ROOM
RO ROUGH OPENING
RPM REVOLUTIONS PER MINUTE
RT RIGHT
RTU ROOFTOP UNIT
RWC RAINWATER CONDUCTOR
S SOUTH
(S) SLOPES
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SENS SENSIBLE
SHN SHOWN
SHT SHEET
SHT MTL SHEET METAL
SHTHG SHEATHING
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SLBB SHORT LEG BACK TO
BACK
SP SPACE (D) (S)
SPEC SPECIFICATION
SPF SPRUCE-PINE-FIR
SQ SQUARE
SQ FT SQUARE FOOT
SQ IN SQUARE INCH
SQ MI SQUARE MILE
SS SANITARY SEWER
SST STAINLESS STEEL
STD STANDARD
STL STEEL
STIF STIFFENER
STIR STIRRUP
STOR STORAGE
STRUCT STRUCTURAL
SQ YD SQUARE YARD
SYMM SYMMETRICAL
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TB TOWEL BAR
TC TERRA COTTA, TOP CHORD
TEMP TEMPORARY
THD THREAD
THK THICKNESS
THRES THRESHOLD
THRU THROUGH
TO TOP OF
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOG TOP OF GRATING
TOJ TOP OF JOIST
TOS TOP OF STEEL
TRS TRUSS
TRTD TREATED
TS TUBE STEEL
TOD TOP OF DUCT
TOW TOP OF WALL
TV TELEVISION
TYP TYPICAL
UGND UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORIES
UN UNLESS NOTED
UNC UNIFIED COARSE THREAD
UNEX UNEXCAVATED
UNFIN UNFINISHED
UNF UNIFIED FINE THREAD
UNIV UNIVERSAL
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VENT, VOLT, VOLTAGE
VAR VARIABLE, VARIATION,
VARIES
VAV VARIABLE AIR VOLUME BOX
VB VACUUM BREAKER, VINYL BASE
VCB VACUUM CIRCUIT BREAKER
VINYL COVER BASE
VCT VINYL COMPOSITION TILE
VEL VELOCITY
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VIN VINYL
VSD VARIABLE SPEED DRIVE
VTR VENT THRU ROOF
T
E
ABBREVIATIONS
F
G
I
J
K
L
M
O
P
Q
R
S
U
V
W
X
Y
Z
NOTE:NOT ALL ABBREVIATIONS AND SYMBOLS MAY
BE USED IN THIS PROJECT. THIS SHEET IS
PROVIDED FOR GENERAL REFERENCE ONLY
W WASTE, WATT, WEST, WIDE
W/ WITH
W/O WITHOUT
WB WET BULB, WOOD BASE
WBL WOOD BLOCKING
WC WATER CLOSET
WD WOOD
WF WIDE FLANGE
WG WATER GAUGE, WIRE GUARD
WH WATER HEATER
WHM WATT HOUR METER
WL WIND LOAD
WO WALL OPENING,
WHERE OCCURS, WORK ORDER
WP WORK POINT
WSCT WAINSCOT
WU WINDOW UNIT
WWR WELDED WIRE REINFORCING
X BY (BETWEEN DIMENSIONS)
XBRA CROSS BRACING
XMFR TRANSFORMER
XS EXTRA STRING
XXS DOUBLE EXTRA STRONG
YD YARD
ZD ZONE DAMPER
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
02/12/2021
EXIT
18"
MIN.
FRONT APPROACH
HINGE APPROACHLATCH APPROACH
TWO HINGED
DOORS IN
SERIES
TWO HINGED
DOORS IN
SERIES
DOORS AT
OPPOSITE
WALLS
PULL SIDE
PUSH SIDE
*
60
"
M
I
N
.
44
"
M
I
N
.
36" MIN.
54" MIN.
44
"
M
I
N
.
6
0
"
M
I
N
.
24" MIN.
48
"
M
I
N
.
18"
MIN.
48
"
M
I
N
.
MIN.12"
MIN.
18"
MIN.
48
"
M
I
N
.
60
"
M
I
N
.
48
"
M
I
N
.
24"
EXTERIOR
18"
INTERIOR
12"
PROVIDE THIS ADDITIONAL
SPACE IF THE DOOR HAS
BOTH A LATCH AND A
CLOSER
PROVIDE THIS
ADDITIONAL SPACE IF
THE DOOR HAS BOTH
A LATCH AND A CLOSER
48" MIN. IF DOOR HAS BOTH
A LATCH AND A CLOSER
PUSH SIDE
PULL SIDE
PUSH SIDE
PULL SIDE
LETTERS AND NUMBERS:
THE CHARACTERS AND BACKGROUND OF SIGNS SHALL BE EGGSHELL, MATTE,
A DARK BACKGROUND OR DARK CHARACTERS ON A LIGHT BACKGROUND.
BRAILLE SHALL BE CONTRACTED (GRADE 2) BRAILLE AND SHALL COMPLY
WITH SECTION 703.4. (ICC/ANSI SEC. 703.4.1)
BRAILLE SHALL BE BELOW THE CORRESPONDING TEXT. IF TEXT IS
MULTILINED, BRAILLE SHALL BE PLACED BELOW THE ENTIRE TEXT. BRAILLE
SHALL BE SEPARATED 3/8" (9.5 MM) MIN. FROM ANY OTHER TACTILE
SIGN LOCATIONS:
LOCATION FOR SUCH SIGNAGE SHALL BE SO THAT A PERSON MAY
APPROACH WITHIN 3" (76 MM)OF THE SIGNAGE WITHOUT ENCOUNTERING
ADDITIONAL DIRECTIONAL SIGNS ALONG ACCESSIBLE PATH OF TRAVEL
ARE REQUIRED. (ICC/IBC SEC. 1110)
BUILDINGS REMODELED TO PROVIDE ACCESSIBLE SANITARY FACILITIES
FOR PUBLIC USE SHALL HAVE INFORMATION POSTED IN THE LOBBY AS
PART OF THE BUILDING DIRECTORY.
INTERNATIONAL SYMBOL OF ACCESSIBILITY:
STANDARD USED TO IDENTIFY ACCESSIBLE FACILITIES.
WHITE FIGURE ON BLUE BACKGROUND, COLOR # 15090 ON
FEDERAL STANDARD # 595A.
WHEN ENFORCING AGENCY DETERMINES, IF APPROPRIATE, SPECIAL
DESIGNS AND COLORS MAY BE APPROVED.
BRAILLE: (ICC/ANSI TABLE 703.4.3)
DOTS TO BE 0.09" (2.3 MM) TO 0.1" (1.5 MM) ON CENTER IN EACH CELL.
0.241" (6.1 MM) TO 0.3" (7.6 MM) SPACE BETWEEN CELLS HORIZONTALLY.
DOTS RAISED 0.025" (0.6 MM) TO 0.037" (0.9 MM) ABOVE BACKGROUND.
5.
7.
11.
12.
13.
14.
15.
16
17.
19.
UPPERCASE, SANS-SERIF OR SIMPLE SERIF AND SHALL BE ACCOMPANIED
LETTERS AND NUMERALS SHALL BE RAISED 1/32" (0.8 MM) MINIMUM,1.
WITH GRADE 2 BRAILLE. RAISED CHARACTERS SHALL BE AT LEAST 5/8"
LETTERS AND NUMBERS ON SIGNS SHALL HAVE A WIDTH-TO-HEIGHT
RATIO BETWEEN 3:5 AND 1:1 AND A STROKE WIDTH-TO-HEIGHT RATIO
BETWEEN 1:5 AND 1:10. (ADAAG SEC. 4.30.2)
4.
CHARACTERS AND NUMBERS ON SIGNS SHALL BE SIZED ACCO RDING TO
THE VIEWING DISTANCE FROM WHICH THEY ARE TO BE READ. THE MINIMUM
HEIGHT IS MEASURED USING AN UPPER CASE X. LOWER CASE CHARACTERS
ARE PERMITTED. (ADAAG SEC. 4.30.3)
6.
(ADAAG SEC. 4.30.5)
AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS REQUIRED, TO BE VISIBLE
WITH A SIGN DISPLAYING THE INTERNATIONAL SYMBOL OF ACCESSIBILITY
LEADING TO AN ACCESSIBLE ROUTE OF TRAVEL SHALL BE IDENTIFIED
PERSONS WITH DISABILITIES AND AT EVERY MAJOR JUNCTION ALONG OR
ALL BUILDING ENTRANCES THAT ARE ACCESSIBLE TO AND U SABLE BY9.
TO PERSONS ALONG APPROACHING PEDESTRIAN WAYS. (ICC/IBC SEC. 1110)
WHERE PERMANENT IDENTIFICATION IS PROVIDED FOR ROOM S AND SPACES,
SIGNS SHALL BE INSTALLED ON THE WALL ADJACENT TO THE LATCH SIDE
OF THE DOOR. WHERE THERE IS NO WALL SPACE TO THE LATCH SIDE OF
THE DOOR, INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACE ON
THE NEAREST ADJACENT WALL. MOUNTING HEIGHT SHALL BE 60" (1525 MM)
10.
ABOVE THE FINISH FLOOR TO THE CENTERLINE OF THE SIG N. MOUNTING
PROTRUDING OBJECTS OR STANDING WITHIN THE SWING OF A DOOR.
1/
3
2
"
RESTROOMSWOMENMEN
INTERNATIONAL SYMBOLS FOR
ACCESSIBILITY
RAISED
GENERAL RESTROOM SIGNAGE
PROPORTIONS FOR
INTERNATIONAL SYMBOLS FOR
ACCESSIBILITY
INTERNATIONAL TDD
SYMBOL
INTERNATIONAL SYMBOL OF
ACCESS FOR HEARING
IMPAIRED
(16 MM) HEIGHT, BUT NO HIGHER THAN 2" (50 MM). PICTOGRAMS SHALL BE
ACCOMPANIED BY THE EQUIVALENT VERBAL DESCRIPTION PLACED DIRECTLY
BELOW THE PICTOGRAM. THE BORDER DIMENSIONS OF THE PICTOGRAM
SHALL BE 6" (152 MM) MINIMUM IN HEIGHT. (ADAAG SEC. 4.30.4)
OR OTHER NON-GLARE FINISH. CHARACTERS AND SYMBOLS SHALL
CONTRAST WITH THEIR BACKGROUND - EITHER LIGHT CHARACTERS ON
8.
CHARACTERS AND 3/8" (9.5 MM) MIN. FROM RAISED BORDERS AND
DECORATIVE ELEMENTS. BRAILLE PROVIDED ON ELEVATOR CAR CONTROLS
SHALL BE SEPARATED 3/16" (4.8 MM) MIN. EITHER DIRECTLY BELOW OR
ADJACENT TO THE CORRESPONDING RAISED CHARACTERS OR SYMBOLS.
(ICC/ANSI SEC. 703.4.4)
(ADAAG SEC. 4.30.6)
0.395" (10.0 MM) TO 0.4" (10.2 MM) SPACE BETWEEN CELLS HORIZONTALLY.18.
DOTS BASE DIAMETER TO BE 0.059" (1.5 MM) TO 0.063" (1.6 MM).20.
AREA OF
REFUGE
60
"
M
I
N
I
M
U
M
18"MIN
EQ EQ
CLEAR
18
"
M
I
N
EQ EQ
DOOR LATCH SIDE
CL
E
A
R
PROVIDE TACTILE
SIGNAGE AS PER ANSI
CODE SECTION 703
TACTILE SIGNAGE MOUNTING HEIGHTS
48
"
M
I
N
I
M
U
M
MOUNTED SIGNAGE:
A. DOOR MOUNTED SIGNAGE:
1.(UNISEX) -12" DIAMETER CIRCLE 1/4" THICK WITH 1/4" THICK
TRIANGLE SUPERIMPOSED WITHIN CIRCLE.
2.THE CHARACTERS AND BACKGROUND OF THE SIGN IS
EGGSHELL, MATTE, OR OTHER NON-GLARE FINISH AND THE
COLOR AND THE CONTRAST OF THE SIGN DISTINCTIVELY
CONTRASTS WITH THE COLOR AND CONTRAST OF THE DOOR.
3.SIGNS ARE CENTERED ON THE DOOR 60" FROM THE FLOOR.
B. WALL MOUNTED SIGNS
1.THE INTERNATIONAL SYMBOL OF ACCESSIBILITY IS INSTALLED
ON THE WALL ADJACENT TO THE LATCH SIDE OF THE DOOR.
THE BORDER DIMENSION SHALL BE A MINIMUM OF 6" IN HEIGHT.
NOTE: IF NO WALL SPACE IS AVAILABLE, SIGN IS TO BE PLACED
ON THE NEAREST ADJACENT WALL, PREFERABLY ON RIGHT.
2.VERBAL DESCRIPTION AS TO REST ROOM USAGE (I.E. MEN'S
REST ROOM) IS TO BE PLACED DIRECTLY BELOW THE SYMBOL
OF ACCESSIBILITY.
3.THE CHARACTER AND BACKGROUND OF THE SIGN IS
EGGSHELL, MATTE, OR OTHER NON -GLARE FINISH AND THE
COLOR AND THE CONTRAST OF THE SIGN DISTINCTIVELY
CONTRASTS WITH THE COLOR OF THE WALL.
NOTE: THE REQUIRED COLOR OF THE SYMBOL OF ACCESSIBILITY
CONSISTS OF A WHITE FIGURE ON A BLUE BACKGROUND.
4.SIGNS ARE CENTERED ON THE WALL 60" FROM THE FLOOR.
5.LETTERS AND NUMERALS ARE RAISED 1/32", SANS-SERIF
UPPERCASE CHARACTERS AND ARE ACCOMPANIED BY GRADE
2 BRAILLE. CHARACTERS ARE MINIMUM 5/8" HIGH AND A
MAXIMUM OF 2" HIGH.
6.MOUNTING LOCATION ALLOWS A PERSON TO APPROACH
WITHIN 3" OF THE SIGN WITHOUT ENCOUNTERING PROTRUDING
OBJECTS OR STANDING WITHIN THE SWING OF A DOOR.
12" MIN.
12
"
M
I
N
.
60
"
M
I
N
I
M
U
M
WOMEN
TEXT NOT IN PICTOGRAM
FIELD (5/8" TO 2" TALL)
GRADE 2 BRAILLE
SYMBOL OF
ACCESSIBILITY
TO COMPLY WITH 703.7
PICTOGRAM TO COMPLY
WITH 703.6
REQUIRED ADA SIGNAGE
WALL-SIGNAGE (TYP.)
6"
M
I
N
.
DI
M
.
T
O
TA
C
T
I
L
E
CH
A
R
A
C
T
E
R
6"
M
I
N
.
+/- 9"
EXIT ROUTE
6"
M
I
N
.
+/- 9"
1/
2
"
M
A
X
.
TRANSITION BETWEEN FLOOR FINISHES
DOOR THRESHOLD
LEVEL CHANGES
1/
4
"
M
A
X
.
1/
2
"
M
A
X
PI
L
E
H
E
I
G
H
T
NOTES:
1/2" MAXIMUM TOTAL HEIGHT WITH 1/4" MAXIMUM VERTICA L
CHANGE AT EDGE.
1:2 SLOPED BEVEL REQUIRED IF LEVEL CHANGE IS OVER
1.
2.
2
1
COMPRESSED CARPET 1/4" MAX.
BELOW THRESHOLD FIN. FLOOR
THRESHOLD
1/4" VERTICAL.
1/
2
"
M
A
X
1/
4
"
M
A
X
LEVEL
LEVEL CHANGES OF MORE THAN 1/2" MUST BE RAMPED AND3.
COMPLY WITH RAMP REQUIREMENTS.
2
1
FIG (A) FIG (B)
FIG (C) FIG (D)
27
"
MA
X
>
2
7
"
27
"
MA
X
.
ACCESSIBLE
WIDTH
27
"
MA
X
LOBBY
CANE RANGE
4" MAX.ANY AMOUNT
80
"
M
I
N
.
12" MAX.CANE RANGE
POST
HIGH FORWARD REACH LIMIT
MAXIMUM FORWARD REACH OVER AN OBSTRUCTION
CLEAR FLOOR
SPACE
PARALLEL
APPROACH
HIGH AND LOW
SIDE REACH LIMITS
SIDE REACH OVER AN OBSTRUCTION
(X)
48
"
M
A
X
.
48"
(X)
(Y
)
(Z)
48"
48"
30
"
30
"
48"
(Z)
15
"
M
I
N
.
48
"
M
A
X
.
48
"
30"
46
"
M
A
X
.
>10" MIN.
24" MAX.30"
15
"
M
I
N
.
34
"
M
A
X
.
48
"
M
A
X
.
10"
MAX.30"
34
"
M
A
X
.
NOTES:
X SHALL BE < 25 INCHES; Z SHALL BE > X.
WHEN X < 20 INCHES, THEN Y SHALL BE 48 INCHES MAXIM UM.
WHEN X IS > 20 TO 25 INCHES, THEN Y SHALL BE 44 INC HES MAXIMUM.
1.
2.
3.
URINALS
40
"
M
A
X
3
6
"
34
"
15"
17
"
15"15"
40
"
34
"
27
"
17"
9"
M
I
N
.
*
5
9
"
MI
N
I
M
U
M
60"
MINIMUM
48
"
MI
N
I
M
U
M
30"
MINIMUM
48
"
MI
N
I
M
U
M
30"
MINIMUM
4" MAX
42
"
MI
N
I
M
U
M
*
5
9
"
MI
N
I
M
U
M
60"
MINIMUM
4"
M
A
X
36"
42
"
MI
N
I
M
U
M
60
"
MI
N
I
M
U
M
9"
M
I
N
6"MIN
MA
X
MA
X
MA
X
MA
X
MI
N
MIN
8" MIN KNEE
CLEARANCE
6" MAX TOE
CLEARANCE
VERIFY KNEE &
TOE CLEARANCES
WITH SPECIFIED
FIXTURE RE: MECH
VERIFY KNEE &
TOE CLEARANCES
WITH SPECIFIED
FIXTURE RE: MECH
TO
B
O
T
T
O
M
O
F
RE
F
L
E
C
T
I
V
E
S
U
R
F
A
C
E
* 56" AT WALL-HUNG TOILETS
ALT DOOR
LOCATION
6" TOE KICK
SPACE (TYP)
NO FIXTURE
MAY OVERLAP
CLEARANCE
PARTITION
℄
℄
℄
℄
17
"
-
1
9
"
MAX
12"42"
39"-41"
39
"
-
4
1
"
18
"
M
I
N
.
T.
O
.
B
A
R
33
"
-
3
6
"
24"12"
36"
T.
O
.
B
A
R
33
"
-
3
6
"
18"
℄
℄
48
"
C
L
E
A
R
2'
-
0
"
15"
MIN.
15"
MIN.
36
"
T
O
S
P
O
U
T
27
"
M
I
N
.
42
"
T
O
S
P
O
U
T
15"15"
4'-0"
1.THE SPOUT SHALL PROVIDE A FLOW OF WATER AT
LEAST 4" HIGH SO AS TO ALLOW THE INSERTION OF A
CUP OR GLASS UNDER THE FLOW OF WATER.
DRINKING FOUNTAIN NOTES FOR LOW DRINKING FOUNTAIN:
2.CONTROLS SHALL BE FRONT MOUNTED OR SIDE MOUNTED
NEAR THE FRONT EDGE. SPOUTS SHALL BE NO HIGHER
THAN 36" MEASURED FROM THE FLOOR OR GROUND
SURFACES TO THE SPOUT OUTLET.
3.WALL AND POST MOUNTED CANTILEVERED UNITS SHALL HAVE
A CLEAR KNEE SPACE BETWEEN THE BOTTOM OF THE
APRON AND THE FLOOR OR GROUND AT LEAST 27" HIGH,
30" WIDE, AND 17-19" DEEP. SUCH UNITS SHALL HAVE A
MINIMUM CLEAR FLOOR SPACE 30" X 48" TO ALLOW A
PERSON IN A WHEEL- CHAIR TO APPROACH THE UNIT
FACING FORWARD.
4.THE FOLLOWING KNEE CLEARANCE IS REQUIRED UNDERNEATH
THE FOUNTAIN: 27" MIN. FROM THE FLOOR TO THE
UNDERSIDE OF THE FOUNTAIN WHICH EXTENDS 8" MIN.
MEASURED FROM THE FRONT EDGE UNDERNEATH THE
FOUNTAIN BACK TOWARDS THE WALL; IF A MIN. 9" OF TOE
CLEARANCE IS PROVIDED, A MAX. OF 6" OF THE 48" OF
CLEAR FLOOR SPACE REQUIRED AT THE FIXTURE MAY
EXTEND INTO THE TOE SPACE.
LOWHIGH
DRINKING
FOUNTAIN
DRINKING FOUNTAIN
ELEVATION
DRINKING
FOUNTAIN PLAN
30"x48"
CLEAR
FLOOR
AREA
4'
-
0
"
W
I
N
G
W
A
L
L
S
LAVATORY CLEARANCEURINAL CLEARANCEWATER CLOSET
CLEARANCE
WATER CLOSET STALL
CLEARANCE
LAVATORIESWATER CLOSET WATER CLOSET STALL
TOE CLEARANCE
URINALS LAVATORIES
18"x36"
MIRRORA
2010
STANDARDS
603.3
TOILET SEAT
COVER
DISPENSER
B
2010
STANDARDS
308
ELECTRIC
HAND DRYERC
2010
STANDARDS
308
COAT
HOOKD
2010
STANDARDS
213.3.7, 603.4
& 308
SOAP
DISPENSERE
2010
STANDARDS
308
SANITARY NAPKIN
DISPOSAL
(WOMEN'S ONLY)
F
2010 ADA STANDARDS
OF ACCESSIBLE
DESIGN, SEE
SECTIONS 604.7 & 609.3
BABY CHANGING
STATIONG
2010 STANDARDS
305 & 308
HEIGHT OF SHELF IN
DOWN POSITION 34"
MAX AFF
H TOILET TISSUE
DISPENSER
2010 ADA STANDARDS
OF ACCESSIBLE
DESIGN, SEE
SECTIONS 604.7 & 609.3
DOOR PULLS AT
TOILET PARTITIONSI
2010 STANDARDS
404.2.7 & 604.8.2.2
COORDINATE w/
PARTITION MFG
74
"
M
I
N
.
40
"
M
A
X
B
O
T
RE
F
L
E
C
T
I
V
E
SU
R
F
A
C
E
TI
D
I
S
P
E
N
S
E
R
48
"
M
A
X
40
"
T
O
S
E
N
S
O
R
48
"
M
A
X
EQ.EQ.
48
"
M
A
X
.
OP
E
R
A
T
O
R
36
"
+
/
-
MA
X
.
15
"
16"℄
TO
B
O
T
30
1
/
2
"
MIN.
15"
7"-9"℄
32"40"
2'-8" CLEAR90°3.
1.
2.
CLOSERS THE MAXIMUM EFFORT TO OPERATE DOORS CANNOT
EXCEED 8.5 POUNDS FOR EXTERIOR DOORS AND 5 POUNDS F OR
INTERIOR DOORS. REQUIRED FIRE DOORS MAY REQUIRED UP TO 15
POUNDS PRESSURE. THE PRESSURE IS TO BE MEASURED AT RIGHT
ANGLES TO HINGED DOORS AND AT THE CENTER PLANE OF S LIDING
OR FOLDING DOORS. COMPENSATING DEVICES OR AUTOMATIC
DOOR OPERATORS MAY BE UTILIZED TO MEET THE REQUIREM ENTS.
IF A DOOR HAS A CLOSER, THEN THE SWEEP PERIOD OF TH E
CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN POSIT ION OF
70 DEGREES, THE DOOR WILL TAKE AT LEAST 3 SECONDS T O MOVE
TO A POINT 3 INCHES (75 mm) FROM THE LATCH, MEASURE D TO THE
LEADING EDGE OF THE DOOR.
THRESHOLD THRESHOLDS ARE REQUIRED TO BE NO MORE
THAN 1/2 INCH HIGH. BEVEL OR SLOPE THE EXPOSED EDGE AT AN
ANGLE NOT EXCEEDING 45 DEGREES SO THAT NO SINGLE VE RTICAL
CHANGE OF ELEVATION EXCEEDS 1/4" INCH.
EXIT DOORS, TOILET ROOM AND CHANGING ROOM DOOR
TO BE OPERABLE FROM INSIDE WITHOUT SPECIAL
KNOWLEDGE, FORCE OR NEED OF KEY.
SEE SPECIFICATION SHEET FOR RESPONSIBILITIES.
ALL HARDWARE TO BE LEVER TYPE.
ENTRANCE SIGNS ALL BUILDINGS ENTRANCES THAT ARE
ACCESSIBLE TO AND USABLE BY PHYSICALLY HANDICAPPED
PERSONS SHALL BE IDENTIFIED WITH AT LEAST ONE STAND ARD
SIGN AND WITH ADDITIONAL DIRECTIONAL SIGNS, AS REQU IRED,
TO BE VISIBLE TO PERSONS ALONG APPROACHING PEDESTRIAN
WAYS.
HARDWARE HAND ACTIVATED DOOR OPENING HARDWARE IS
REQUIRED TO BE CENTERED BETWEEN 30 AND 44 INCHES HIGH.
LATCHING AND LOCKING DOORS THAT ARE HAND ACTIVATED AND
WHICH ARE IN A PATH OF TRAVEL HAVE TO BE OPERABLE W ITH A
SINGLE EFFORT BY LEVER TYPE HARDWARE, BY PANIC BARS , PUSH-
PULL ACTIVATING BARS, OR OTHER HARDWARE DESIGNED TO
PROVIDE PASSAGE WITHOUT REQUIRING THE ABILITY TO GR ASP
THE OPENING HARDWARE. LOCKED EXIT DOORS ARE REQUIRE D TO
OPERATE AS DESCRIBED ABOVE IN THE DIRECTION OF EGRE SS.
DOORS
ENTRANCES ALL PRIMARY ENTRANCES TO BUILDINGS AND
FACILITIES ARE REQUIRED TO BE MADE ACCESSIBLE. A PR IMARY
ENTRANCE IS DEFINED AS, "...ANY ENTRANCE TO A FACILITY
WHICH HAS A SUBSTANTIAL FLOW OF PEDESTRIANS TO ANY
SPECIFIC MAJOR FUNCTION OF THE FACILITY." REVOLVING DOORS
CAN NOT BE USED AS A REQUIRED ENTRANCE FOR THE
HANDICAPPED. RECESSED DOORMATS ARE REQUIRED TO BE
ANCHORED TO PREVENT INTERFERENCE WITH WHEELCHAIR TR AFFIC.
DOOR WIDTHS & HEIGHTS REQUIRED EXIT DOORWAYS ARE
REQUIRED TO HAVE A CLEAR OPENING NOT LESS THAN 32
INCHES WIDE. FOR HINGED DOORS, THE OPENING IS MEASU RED
WITH THE DOOR AT A 90 DEGREE ANGLE FROM ITS CLOSED
POSITION. AT LEAST ONE OF A PAIR OF DOORS, INCLUDIN G
AUTOMATIC DOORS, HAS TO PROVIDE THE 32 INCH CLEAR
OPENING. DOOR HEIGHTS ARE REQUIRED TO BE A MINIMUM OF
80 INCHES.
LEVER 2'-6"
TO 3'-8" A.F.F.
HARDWARE
LEVER OR U SHAPED
HANDLE MOUNTED AT
10" MIN. BOTTOM
RAIL
34" TO 48" AFF
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:49 PM
12322-034
G004
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
AC
C
E
S
S
I
B
I
L
I
T
Y
S
T
A
N
D
A
R
D
S
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
SCALE: 1/4" = 1'-0"G004
1 REQUIRED DOOR CLEARANCES
SCALE:NTSG004
2 TACTILE SIGNAGE & SYMBOLS
SCALE:NTSG004
3 THRESHOLDS & LEVEL CHANGES
SCALE:NTSG004
4 PROTUDING OBJECTS
SCALE:NTSG004
5 REACH REQUIREMENTS
SCALE: 1/4" = 1'-0"G004
6 TOILET ROOM FIXTURE HEIGHTS & CLEARANCES
SCALE: 1/4" = 1'-0"G004
7 ACCESSORY MOUNTING DIAGRAMS
SCALE: 1/4" = 1'-0"G004
8 DOOR/HARDWARE DETAIL
ACCESSIBILITY REQUIREMENTS
1. ALL CONSTRUCTION SHALL BE COMPLETED IN STRICT
ACCORDANCE WITH THE DESIGN GUIDELINES
ESTABLISHED BY THE 2010 ADA STANDARDS FOR
ACCESSIBLE DESIGN (2010 STANDARDS) AND ALL STATE
AND LOCAL ACCESSIBILITY CODE REQUIREMENTS.
2. UTILIZE EXTREME CARE TO ENSURE THAT ALL
TOLERANCES, DIMENSIONS, AND CLEARANCES ARE
CONSTRUCTED ACCURATELY.
3. TAKE ANY AND ALL ACTIONS NECESSARY TO CORRECT
CONDITIONS WHICH ARE IN THE OPINION OF THE STATE
ACCESSIBILITY INSPECTOR IN VIOLATION OF
GUIDELINES AS THE DIRECT & SOLO RESULT OF
DEVIATIONS FROM THE CONSTRUCTION DOCUMENTS
OR INADEQUATE CONSTRUCTION CONTROL &, OR
TOLERANCES.
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
02/12/2021
██ RESPONSIBILITY SCHEDULE - FEBRUARY 01, 2021
GENERAL DEMOLITION NOTES
1.
ALL WORK SHALL BE PROVIDED (SUPPLIED AND INSTALLED) BY CONTRACTOR UNLESS OTHERWISE NOTED IN THIS SCHEDULE OR ELSEWHERE IN THE DRAWINGS.
ALL MENTION THROUGHOUT THIS SET OF "OWNER" SHALL BE IN REFERENCE TO CUMBERLAND FARMS.
ALL MENTION THROUGHOUT THIS SET OF "OTHERS" SHALL BE IN REFERENCE TO CUMBERLAND FARMS SUPPLIED VENDOR/CONTRACTOR.
CONTRACTOR SHALL BE RESPONSIBILE FOR COORDINATION OF INSTALLATION OF ALL ITEMS ON JOB SITE.***
DIVISION
ITEM
DIVISION 2 - EXISTING CONDITIONS
ENVIRONMENTAL REMEDIATION
DEMOLITION
DIVISION 3 - CONCRETE
REINFORCED CONCRETE FOOTINGS
AND FOUNDATIONS
REINFORCED CONCRETE FLOOR SLAB
REINFORCED CONCRETE SIDEWALK
DIVISION 4 - MASONRY
EXTERIOR STONE VENEER WAINSCOT
PRECAST CONCRETE CAP
DIVISION 5 - METALS
STRUCTURAL STEEL (BEAMS,
COLUMNS, ETC.)
ANCHOR BOLTS AND LEVELING
PLATES (BY STEEL FABRICATOR
ANCHOR BOLT TEMPLATES (BY STEEL
FABRICATOR)
DIVISION 6 - WOOD, PLASTICS AND COMPOSITES
INTERIOR/EXTERIOR WOOD
BLOCKING FOR ALL ACCESSORIES
CDX PLYWOOD SHEATHING
WOOD FRAMING
PRE-ENGINEERED WOOD TRUSSES
VINYL RAILING SYSTEM
SYNTHETIC WOOD TRIM AND
SYNTHETIC WOOD SOFFIT PANELS
PRE MANUFACTURED
FIBERGLASS COLUMN SHROUD
RESTROOM/HAND SINK ACCESSORY
FIRE RETARDANT WOOD BLKG
DIVISION 7 - THERMAL AND MOISTURE PROTECTION
THERMAL INSULATION/ AIR/ VAPOR
BARRIER
ROOFING SYSTEM PENETRATIONS
ROOFING SYSTEM (BOTH PITCHED AND
FLAT ROOFS) STANDING SEAM ROOF,
EPDM AND ASPHALT SHINGLES
SNOW GUARDS (METAL ROOFS
ONLY U.N.O.)
METAL ROOF EDGE
ALUM GUTTERS AND DOWNSPOUTS
VINYL SOFFIT PANELS
EXTERIOR SIDING
DIVISION 8 - OPENINGS
ALUM WINDOW AND ENTRY DOOR
SYSTEM
INSULATED GLAZING, INSULATED
METAL PANEL
DOORS, FRAMES, FINISHING AND VINYL
CLAD WINDOWS
DOOR HARDWARE
ELIASON DOOR AND HARDWARE
ELIASON HM FRAME
DIVISION 9 - FINISHES
SUSP CEILING GRID AND HANGERS
SUSP CEILING TILE
INTERIOR VALANCE GRAPHICS
FLOOR TILE (LVT-1) (WHERE SPECIFIED)
FLOOR TILE (FT-2) (WHERE SPECIFIED)
FLOOR TILE (FT-3) (WHERE SPECIFIED)
WT-1, WT-2, WT-3 (RETAIL AND
RESTROOMS)
TILE ADHESIVES, GROUT AND OTHER
INSTALLATION ACCESSORIES
VINYL COVE BASE
VINYL COVE BASE ADHESIVE, VCT
FLOOR TILE AND ADHESIVE
CONC FLOOR SEALER
FRP WALL PANELS (WP-1), TRIM,
ADHESIVES AND SEALANT @ UTILITY
/ RECEIVING AREAS AND
FRP CLG PANELS (WP-4), TRIM,
ADHESIVES AND SEALANT @ HOT FOODS
PREP CLG
██
██
██
██
WALK IN FREEZER CONDENSERS
/ EVAPORATORS **
WALK IN COOLER CONDENSER /
EVAPORATORS **
SODA/ICE DISPENSER CONDENSER
SANDWICH COOLER CONDENSER
FBD DISPENSER CONDENSER
UPRIGHT FREEZER CONDENSER
██
██
██
██
██
██
██
██
██
██
██
██
██
FRP WALL PANELS (WP-5) TRIM,
ADHESIVES AND SEALANT @ BEER CAVE
(FL, VT, NH, NY, ME STATES ONLY)
FRP WALL PANELS (WP-6,7,8,9) TRIM,
ADHESIVES AND SEALANT @ RENOVATION
PROJECTS (WHERE OCCURS)
INTERIOR PAINT (AS SPECIFIED IN
FINISH SCHEDULE)
EXTERIOR PAINT (AS SPECIFIED IN
FINISH SCHEDULE)
GYPSUM BOARD, CORNER AND J BEADS
TAPE & MUD
METAL STUDS
EPOXY FLOORING
WALK-OFF MAT (CPT-1), AS SPECIFIED
IN FLOOR FINISH SCHEDULE
DIVISION 10 - SPECIALTIES
FIRE EXTINGUISHERS
TOILET PARTITIONS
VANITY MIRRORS
TOILET ACCESSORIES (EXCLUDING
MIRRORS)
DIGITAL MENU BOARDS
INTERIOR SIGNAGE
DIVISION 11 - EQUIPMENT
EQUIPMENT UNLESS NOTED
OTHERWISE ON EQUIPMENT SCHEDULE
MILLWORK UNLESS NOTED OTHERWISE
ON A160
██
██
GONDOLAS
SHELVING
PATIO FENCE
PATIO UMBRELLA AND PICNIC TABLES
MOTORIZED ROLLER SHADES
DIVISION 22 - PLUMBING
PLUMBING FIXTURES (EXCEPT FOR
WALL HYDRANTS, FLOOR SINKS, FLOOR
DRAINS, GREASE TRAPS, AND DRINKING
FOUNTAINS WHERE THEY OCCUR)
WALL HYDRANTS, FLOOR SINKS, FLOOR
DRAINS, GREASE TRAPS AND DRINKING
FOUNTAINS WHERE THEY OCCUR
PLUMBING PIPING AND CONNECTIONS
COFFEE BAR AND CHILL ZONE
PLUMBING
██
██
██
██
██
██
WALK-IN FREEZER CONDENSER
PLUMBING
WALK-IN FREEZER PLUMBING
WALK-IN COOLER PLUMBING
WALK-IN COOLER CONDENSER
PLUMBING
SODA/ICE DISPENSER CONDENSER
PLUMBING
SANDWICH COOLER CONDENSER
PLUMBING
██
██
██
██
██
FBD DISPENSER CONDENSER
PLUMBING
UPRIGHT FREEZER CONDENSER
PLUMBING
CONDENSATE REMOVAL PUMP AND ALL
PIPING
NATURAL GAS PIPING AND
CONNECTIONS
PROPANE (WHEN OCCURS)
DIVISION 23 - HVAC
HVAC DIFFUSERS, DUCTWORK AND
HANGERS
HVAC EXHAUST FANS
HVAC EQUIPMENT
██
██
██
██
██
██
ELECTRICAL WIRING (OUTLETS AND
LIGHTING)
LOW VOLTAGE COMMUNICATION
WIRING FOR REFRIGERATION UNITS
DISCONNECTS FOR
REFRIGERATION UNITS
LIGHTING FIXTURE SUPPORT
CABLES
LIGHT FIXTURES: EXCEPT SERVICE
WALL SCONCES AT ROOF DECK
CEILING MOUNTED SPEAKER
WIRING
██
██
██
██
POS POWER AND DATA
HEAT AND SMOKE DETECTORS
HVAC EXHAUST FANS POWER
ATM PATH LINE AND POWER
WALK-IN COOLER/FREEZER
ELECTRICAL AND LOW VOLTAGE WIRING
UPRIGHT FREEZERS ELECTRICAL
COFFEE BAR/ CHILL ZONE ELECTRICAL
ELECTRICAL WIRING FOR
COOLER/FREEZER DOORS
ELECTRICAL PANELS / CIRCUIT
BREAKERS
ELECTRICAL CT CABINET
FIRE SUPPRESSION ELECTRICAL
██
██
GAS CONTROLLER EQUIPMENT AND
PANELS
DIVISION 27 - COMMUNICATIONS
CEILING MOUNTED SPEAKERS
CCTV SYSTEM
POS SYSTEM
██
DIVISION 28 - ELECTRICAL SAFETY & SECURITY
NOT USED
DIVISION 31- EARTHWORK
SITEWORK
██
██
██
██
██
██
██
██
██
DIVISION 32 - EXTERIOR IMPROVEMENTS
NOT USED
DIVISION 33- UTILITIES
SEWER / WATER / GAS
██
10.
██
██
██
██
██
██
██
██
██
██
██
██
9.
5.
SUPPLIED AND
INSTALLED BY
OTHERS
SUPPLIED BY
OWNER
INSTALLED BY
OTHERS*
SUPPLIED BY
OWNER
INSTALLED BY
CONTRACTOR
SUPPLIED BY
CONTRACTOR
INSTALLED BY
CONTRACTOR
DIVISION
ITEM
██
FRP WALL PANELS (WP-6), TRIM,
ADHESIVES AND SEALANT @ COFFEE
COUNTER AND HOT FOODS AREAS
SUPPLIED AND
INSTALLED BY
OTHERS
SUPPLIED BY
OWNER
INSTALLED BY
OTHERS*
██
SUPPLIED BY
OWNER
INSTALLED BY
CONTRACTOR
SUPPLIED BY
CONTRACTOR
INSTALLED BY
CONTRACTOR
DIVISION
ITEM
CUSTOM HVAC RETURN DIFFUSER
ASSEMBLIES @ COFFEE BAR AND HOT
FOODS (WHERE OCCURS)
DIVISION 26 - ELECTRICAL
SUPPLIED AND
INSTALLED BY
OTHERS
SUPPLIED BY
OWNER
INSTALLED BY
OTHERS*
SUPPLIED BY
OWNER
INSTALLED BY
CONTRACTOR
SUPPLIED BY
CONTRACTOR
INSTALLED BY
CONTRACTOR
4.
██
2.
3.
KNOW AND UNDERSTAND THE SCOPE OF WORK
DEPICTED ON THE CONSTRUCTION DOCUMENTS.
UTILIZE ADDITIONAL DRAWINGS FOR OBTAINING ALL
INFORMATION REQUIRED.
PROVIDE DEMOLITION WORK SHOWN ON THE
DRAWINGS AND RELATED INCIDENTAL
DEMOLITION WORK REQUIRED TO COMPLETE NEW
CONSTRUCTION WORK.
CONTRACTOR IS RESPONSIBLE FOR OBTAINING ALL
NECESSARY PERMITS. CONTRACTOR IS
RESPONSIBLE FOR COORDINATION WITH LOCAL
UTILITIES AND BUILDING TENANTS REGARDING
UTILITIES AND SERVICE DISCONNECTS.
THE SCOPE OF DEMOLITION SHOWN ON THE
CONTRACT DOCUMENTS REPRESENTS THE BEST
EFFORTS OF THE DESIGN TEAM TO DOCUMENT THE
EXTENT OF DEMOLITION. NOT ALL WALLS,
PARTITIONS, FIXTURES, EQUIPMENT, STRUCTURAL
FRAMING, AND BUILDING SYSTEMS HAVE BEEN
SHOWN ON PLANS. THE CONTRACTOR SHALL
PARTICIPATE IN A SITE WALK THRU PRIOR TO
ESTIMATING DEMOLITION SCOPE OF WORK AND
FAMILIARIZE THEMSELVES WITH THE SCOPE.
FIELD VERIFY EXISTING CONDITIONS PRIOR TO THE
START OF DEMOLITION OPERATIONS. BRING ANY
DISCREPANCIES WHICH MAY AFFECT DEMOLITION
OR NEW CONSTRUCTION WORK TO THE ATTENTION
OF THE ARCHITECT FOR REVIEW.
6. DO NOT ALTER THE STRUCTURAL INTEGRITY OF THE
EXISTING BUILDING OR ITS ASSEMBLIES UNLESS
SPECIFICALLY NOTED OTHERWISE. PROVIDE ALL
MEANS NECESSARY TO PROTECT THE STRUCTURE
DURING CONSTRUCTION. SUCH MEASURES SHALL
INCLUDE, BUT SHALL NOT BE LIMITED TO
TEMPORARY BRACING AND SHORING REQUIRED TO
PERFORM THE WORK. FOR LOADS DUE TO
CONSTRUCTION EQUIPMENT, BEARING WALLS, ETC.,
THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
SHORING, SHEETING, AND BRACING OF
EXCAVATIONS ADJACENT TO EXISTING
STRUCTURES AND UTILITIES SO THAT NO
HORIZONTAL MOVEMENT OR VERTICAL SETTLEMENT
OCCURS.
7. ITEMS LISTED FOR REMOVAL AND STORAGE ARE
THE RESPONSIBILITY OF THE CONTRACTOR.
CONTRACTOR SHALL COORDINATE WITH THE
OWNER'S REPRESENTATIVE FOR METHOD OF
STORAGE AND PROVIDE PRICING ASSOCIATED
WITH REMOVAL, STORAGE, PROTECTION, AND RE-
INSTALLATION.
8. CONTRACTOR SHALL COORDINATE DIRECTLY WITH
OWNER'S REPRESENTATIVE FOR SALVAGE OF
PRODUCTS, EQUIPMENT, FINISHES, FIXTURES, ETC.
INDICATED TO BE REMOVED. CONTRACTOR TO
PROVIDE FOR REMOVAL, SALVAGE, TRANSPORT,
ETC. AS REQUIRED.
REMOVE ENTIRE WALL ASSEMBLY INDICATED TO BE
DEMOLISHED, INCLUDING CONCEALED ELEMENTS
WITHIN PARTITIONS AND ABOVE-CEILING
CONSTRUCTION UNLESS NOTED OTHERWISE.
PROTECT EXISTING CONSTRUCTION TO REMAIN
FROM DAMAGE DURING DEMOLITION AND/OR NEW
CONSTRUCTION OPERATIONS. CONDUCT
DEMOLITION OPERATIONS SO AS TO MINIMIZE THE
DEVELOPMENT AND SPREAD OF DUST.
11.
12.
REMOVE DEMOLITION MATERIALS FROM THE SITE
PROMPTLY AND DISPOSE OF LEGALLY OFF-SITE
WITH DOCUMENTATION.
UPON REMOVAL OF FINISH MATERIALS INDICATED
OR REQUIRED, PREPARE SUBSTRATE TO RECEIVE
NEW FINISH. REFER ALSO TO ROOM FINISH
SCHEDULE FOR NEW MATERIAL(S). REPAIR ANY
EXISTING DAMAGE, OR DAMAGE ARISING FROM
DEMOLITION OPERATIONS, TO MATCH EXISTING AND
AS NEEDED FOR INSTALLATION OF NEW FINISH(ES).
13. PATCH AND REPAIR DAMAGE ARISING FROM
DEMOLITION OPERATIONS TO FLOOR, WALL, AND
CEILING SURFACES TO MATCH EXISTING ADJACENT
SURFACES. PATCH CHIPPED OR SPALLED
CONCRETE CAUSED BY PARTITION REMOVAL.
REMOVE ANY EXTRANEOUS MATERIALS AND PATCH
TO MATCH ADJACENT SURFACES.
14. MAINTAIN MEANS OF EGRESS AND KEEP FULLY
SEPARATE FROM CONSTRUCTION AREA AT ALL
TIMES.
15.
16.
PATCH AND REPAIR OPENINGS AND/OR
PENETRATIONS THROUGH EXISTING FIRE-RATED
ASSEMBLIES AND SMOKE BARRIER ASSEMBLIES
(WHERE THEY OCCUR).
AT UNEVEN AREAS AND DEPRESSIONS IN EXISTING
CONCRETE FLOOR CONSTRUCTION, PROVIDE
CEMENTITIOUS UNDERLAYMENT AS REQUIRED TO
PROVIDE SUITABLE BASE CONDITION FOR NEW
FINISH(ES) AND NEW CONSTRUCTION.
██17. COORDINATE TIMING AND HOURS OF DEMOLITION
OPERATIONS WITH THE OWNER'S SCHEDULE AND
AUTHORITIES HAVING JURISDICTION.
18. MINIMIZE NOISE FROM DEMOLITION OPERATIONS.
19.
*
**
***
****
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF THE WORK FOR
ALL ITEMS IN THIS COLUMN.
CONTRACTOR SHALL INSTALL CONDENSING UNIT AND PROVIDE POWER
DISCONNECT SWITCH; CONTRACTOR WILL MAKE FINAL CONNECTIONS TO
CONDENSER.
CONTRACTOR SHALL RECEIVE ALL DROP SHIP ITEMS.
CONCRETE MASONRY UNITS, WHEN REQUIRED, SHALL BE SUPPLIED AND
INSTALLED BY THE CONTRACTOR.
21.
20.
SAWCUT SLABS ON GRADE WHERE REQUIRED TO
INSTALL NEW CONDUIT, PIPING, ETC. REFER ALSO
TO MECHANICAL AND ELECTRICAL DRAWINGS.
PATCH AND REPAIR SLABS TO MATCH EXISTING.
SEE STRUCTURAL FOR SLABS TO BE REPLACED.
CORE EXISTING FLOOR SLAB CONSTRUCTION
WHERE REQUIRED FOR INSTALLATION OF REQUIRED
CONDUIT, PIPING, ETC. REFER ALSO TO MECHANICAL
AND ELECTRICAL DRAWINGS. PROVIDE UL-RATED
FIRE SAFING ASSEMBLIES AT ALL SUCH
CONDITIONS.
CONDUCT DEMOLITION OPERATIONS TO PREVENT
INJURY OR DAMAGE TO ADJACENT BUILDING AREAS.
ENSURE SAFE PASSAGE OF PEOPLE AROUND
SELECTIVE DEMOLITION AREA. PROTECT WALLS,
CEILINGS, FLOORS, AND OTHER FINISH WORK THAT
ARE TO REMAIN AND ARE EXPOSED DURING
SELECTIVE DEMOLITION OPERATIONS. COVER AND
PROTECT FURNISHINGS AND EQUIPMENT THAT
HAVE NOT BEEN REMOVED. DO NOT BLOCK ANY
EXITS DURING CONSTRUCTION OPERATIONS.
22.
23.
██
██
██
██
██
██
24.
25.
CLEAN ADJACENT STRUCTURES AND
IMPROVEMENTS OF DUST, DIRT, AND DEBRIS
CAUSED BY SELECTIVE DEMOLITION AND NEW
CONSTRUCTION OPERATIONS.
IN WALLS TO BE REFINISHED, REMOVE EXISTING
MISCELLANEOUS ACCESSORIES TO FACILITATE
INSTALLATION OF NEW FINISHES. PATCH, REPAIR,
AND PREP WALLS TO RECEIVE NEW FINISHES. ITEMS
REMOVED TO BE SALVAGED AND GIVEN BACK TO
THE OWNER.
ALL DEMOLITION EFFORTS SHALL BE COORDINATED
WITH THE HAZARDOUS MATERIALS ABATEMENT
CONTRACTOR AND THEIR SCOPE OF DEMOLITION.
EXISTING CONSTRUCTION MAY CONTAIN ASBESTOS-
CONTAMINATED PRODUCTS. MATERIALS THOUGHT
TO CONTAIN ASBESTOS MUST BE INSPECTED BY AN
EPA-CERTIFIED INSPECTOR CAPABLE OF SAMPLING
FOR THE EXISTENCE OF ASBESTOS. WORK SHALL BE
DONE IN ACCORDANCE WITH THE MOST CURRENT
OSHA REGULATIONS AND DISPOSED OF IN
ACCORDANCE WITH CURRENT EPA REGULATIONS.
26. EXISTING CONSTRUCTION MAY CONTAIN LEAD-
CONTAMINATED PRODUCTS. MATERIALS THOUGHT
TO CONTAIN LEAD MUST BE INSPECTED BY AN EPA-
CERTIFIED INSPECTOR CAPABLE OF SAMPLING FOR
THE EXISTENCE OF LEAD WORK SHALL BE DONE IN
ACCORDANCE WITH THE MOST CURRENT OSHA
REGULATIONS AND DISPOSED OF IN ACCORDANCE
WITH CURRENT EPA REGULATIONS.
6.
DIVISION 3 - CONCRETE
- STEEL REINFORCING FOR FOUNDATION
- CONCRETE MIX DESIGN FOR FOUNDATIONS,
FOOTINGS AND SLABS
2.
DIVISION 6 - WOOD, PLASTICS & COMPOSITES
- PRE-ENGINEERED WOOD TRUSSES
- PRODUCT DATA, INCLUDING DESIGN
PROPERTIES, FOR A LL MANUFACTURED
WOOD BEAMS AND COLUMNS
- WOOD CONNECTORS
DIVISION 7 - THERMAL & MOISTURE PROTECTION
- MEMBRANE ROOFING SYSTEM COMPONENTS
- ROOFING SHINGLES
- THERMAL INSULATION
DIVISION 8 - OPENINGS
- HM DOORS AND FRAMES
- WOOD DOORS
- HARDWARE
- ALUMINUM STOREFRONT
- GLASS AND GLAZING ITEMS
- VINYL CLAD WINDOWS
- HORIZONTAL SLIDING DOORS
DIVISION 9 - FINISHES
- EXTERIOR SIDING AND TRIM
DIVISION 22 - PLUMBING
- PLUMBING FIXTURES; FLOOR DRAINS, FLOOR
SINKS, CLEANOUTS, WALL HYDRANTS AND
GREASE TRAPS
DIVISION 23 - HVAC
- DIFFUSERS AND GRILLES
- COMMISSIONING AND BALANCING
DIVISION 26 - ELECTRICAL
- CPI ELECTRIC PANELS
- FIRE ALARM SYSTEM COMPONENTS
INCLUDING BUT NOT LIMITED TO; FIRE ALARM
PANEL, BATTERY(SIZED BASED ON CALCS),
CALCULATIONS, WIRELESS COMMUNICATOR
BOX(IF ALLOWED BY AHJ), ANNUNCIATOR,
PULL, SMOKE, HEAT, DUCT(AND REMOTE TEST
STATION), MONITOR MODULES(MONITOR
ANSUL/SUPPRESSION, AND SPRINKLER
FLOW/TAMPER IF APPLICABLE), NOTIFICATION
DEVICES(CEILING, WALL MOUNTED AND
WEATHER PROOF BOXES FOR
REFRIGERATION) AND FIRE ALARM WIRE
SPECIFICATIONS
1.SPRAY FOAM INSULATION:
- BASE PRODUCT: ICYNENE OPEN CELL SPRAY
FOAM INSULATION LDC50.
- TOP COAT: CD315 THERMAL BARRIER PAINT
USE @ UNDERSIDE OF ROOF, GABLE END AT
ATTIC WALLS.
14.
15.
16.
8.
GENERAL NOTES
1. ALL WORK SHALL CONFORM TO ALL
GOVERNING CODES AND ORDINANCES UNDER
WHICH THEY ARE PERFORMED. WHERE
CONFLICTS OCCUR, THE MOST STRINGENT
EQUIPMENTS SHALL BE MET. REFER TO
PROJECT DATA.
THE G.C. SHALL COORDINATE ALL
STRUCTURAL, MECHANICAL AND PLUMBING
SYSTEMS PRIOR TO THE START OF
CONSTRUCTION.
3. THE G.C. SHALL OBTAIN ALL PERMITS AND
INSPECTIONS NECESSARY TO ENSURE
ISSUANCE OF AN OCCUPANCY PERMIT UPON
COMPLETION OF THE WORK.
4. THE G.C. SHALL MAINTAIN ALL INSURANCE
REQUIRED BY OWNER AND/ OR
GOVERNMENTAL AUTHORITIES AND SHALL
PROVIDE PROOF OF SUCH INSURANCE AS
REQUIRED.
5.
6.
7.
THE G.C. SHALL BE RESPONSIBLE FOR
BRACING ALL WORK DURING CONSTRUCTION.
THE DRAWINGS MAY NOT BE TO SCALE.
REFER TO PLANS, SECTIONS, AND DETAILS
FOR DIMENSIONS.
THE G.C. SHALL VERIFY ALL DIMENSIONS AND
ELEVATIONS BEFORE COMMENCING
CONSTRUCTION AND REPORT ALL
DISCREPANCIES TO THE ARCHITECT BEFORE
PROCEEDING. THE CONTRACTOR SHALL ALSO
BE RESPONSIBLE TO CHECK ALL DIMENSIONS
AND DETAILS ON SHOP DRAWINGS BEFORE
SUBMISSION TO THE ARCHITECT.
THE ELECTRICAL CONTRACTOR SHALL
COORDINATE WITH THE OWNER ALL
LOCATIONS FOR RECEPTACLES, SWITCHES AND
DIMMERS, POS, CABLE AND TELEPHONE PRIOR
TO THE START OF CONSTRUCTION.
9.
10.
ALL EXTERIOR LIGHTING AND WET AREA
LIGHTING TO INCLUDE MANUFACTURER'S
WATER TIGHT HOUSINGS.
THE G.C. IS RESPONSIBLE TO COORDINATE
THE INSTALLATION OF ALL CEILING
DIFFUSERS, EMERGENCY SIGNAGE, LIGHTING,
ACCESS PANELS, ETC TO FULLY COMPLETE
THE SCOPE OF WORK.
11. THE G.C. SHALL PROVIDE AND COORDINATE
WITH THE ELECTRICAL CONTRACTOR AND
THE FIRE DEPARTMENT ALL LOCATIONS FOR
EXIT SIGNS, EMERGENCY LIGHTING, FIRE
EXTINGUISHERS, FIRE ALARM PULL STATIONS,
HORN STROBES, ETC.
12.
13.
ALL DIMENSIONS ARE FROM FINISH FACE OF
GYPSUM BOARD, CONCRETE OR MASONRY
UNLESS NOTED OTHERWISE.
PROVIDE PRESSURE TREATED WOOD AT ALL
FRAMING LOCATIONS WHERE WOOD IS IN
CONTACT WITH CONCRETE.
ALL PENETRATIONS THROUGH RATED WALL
ASSEMBLIES SHALL BE TREATED WITH AN
APPROVED "FIRESTOP" MATERIAL TO MEET
THE SPECIFIED WALL CONSTRUCTION.
USE MOISTURE RESISTANT WALL BOARD IN
LIEU OF GYPSUM WALLBOARD AT ALL WET
LOCATIONS.
THESE PLANS HAVE BEEN PREPARED IN
ACCORDANCE WITH ALL LOCAL, STATE AND
FEDERAL REQUIREMENTS, AS WELL AS
CUMBERLAND FARMS' POLICIES FOR
HANDICAP ACCESSIBILITY. ALTHOUGH THESE
PLANS IN SOME CASES MAY EXCEED THE
MINIMAL LOCAL, STATE OR FEDERAL
REQUIREMENTS, STRICT COMPLIANCE BY THE
CONTRACTOR WITH THESE PLANS IS
MANDATORY. ANY DEVIATION FROM THESE
PLANS WILL BE AT THE SOLE DISCRETION,
RESPONSIBILITY, AND LIABILITY OF THE
CONSTRUCTION.
SITE INSPECTION SCHEDULE
1.
2.
SITE INSPECTIONS ARE REQUIRED FOR ALL
PROJECTS IN ALL STATES. SEE LIST BELOW
FOR REQUIREMENTS BY STATE.
FINAL AFFIDAVITS ARE REQUIRED FOR
PROJECTS IN MA AND RI ONLY. CONTROLLED
CONSTRUCTION INSPECTIONS WILL NEED TO
BE PERFORMED TO PROVIDE FINAL
AFFIDAVITS UPON PROJECT COMPLETION.
3.
4.
THE G.C. TO CONTACT EACH DISCIPLINE FOR
ALL INSPECTIONS AND PROVIDE ONE WEEK
MINIMUM NOTICE FOR ALL INSPECTIONS.
STRUCTURAL INSPECTIONS - PERFORMED BY
STRUCTURAL ENGINEER: MA AND RI ONLY
- FOOTINGS AND FOUNDATIONS
- FINAL FRAMING INSPECTION:
ROUGH EXTERIOR FRAMING WITH EXTERIOR
PLYWOOD AT WALLS AND ROOF EXPOSED
TO INSPECT NAILING PATTERNS. TRUSSES
VISIBLE FOR INSPECTION OF CONNECTIONS
TO BEARING POINTS AND HURRICANE CLIPS.
ALL OTHER STATES:
- FINAL FRAMING INSPECTION:
ROUGH EXTERIOR FRAMING WITH EXTERIOR
PLYWOOD AT WALLS AND ROOF EXPOSED TO
INSPECT NAILING PATTERNS. TRUSSES
VISIBLE FOR INSPECTION OF CONNECTIONS
TO BEARING POINTS AND HURRICANE CLIPS.
5. ARCHITECTURAL INSPECTIONS - PERFORMED
BY ARCHITECT:
- INTERIOR ROUGH FRAMING INCLUDING
COMPLETED ELECTRICAL AND PLUMBING
ROUGH-IN PRIOR TO INSULATION AND
SHEETROCK INSTALL.
- FINAL INSPECTION UPON CONSTRUCTION
COMPLETION FOR AFFIDAVIT. THE SPACE
SHOULD BE READY FOR OCCUPANCY WITH
LIFE SAFETY AND ALL ADA CODE ITEMS IN
PLACE.
MECHANICAL/PLUMBING/ELECTRICAL
INSPECTION - PERFORMED BY MEP ENGINEER:
- FINAL INSPECTION UPON CONSTRUCTION
COMPLETION FOR AFFIDAVIT. THE SPACE
SHOULD BE READY FOR OCCUPANCY WITH
LIFE SAFETY AND ALL ADA CODE ITEMS IN
PLACE.
SHOP DRAWING SUBMITTAL LIST
██
██
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:50 PM
12322-034
G005
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
RE
S
P
O
N
S
I
B
I
L
I
T
Y
S
C
H
E
D
U
L
E
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
02/12/2021
11 22
± 19' - 7"
3
4
5
6
77
8
CHECKOUT
WOMENS' RESTROOM MENS' RESTROOM
SALES
WALK-IN
COOLER
(8 DOORS)
BOH/ OFFICE AREA
9
SYMBOL DESCRIPTION
DEMO LEGEND
EXISTING WALLS/FIXTURES TO BE REMOVED
EXISTING WALLS TO REMAIN
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:42 PM
12322-034
D100
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
DE
M
O
L
I
T
I
O
N
P
L
A
N
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
SCALE: 1/4" = 1'-0"D100
1 DEMOLITION PLAN
DEMOLITION NOTES
A. CONTRACTOR BID TO BE BASED ON EXISTING CONDITION.
B. ALL DEMOLITION WORK INVOLVING ELECTRICAL, OR PLUMBING WORK MUST COMPLY WITH ALL APPLICABLE
CODES IN REGARD TO THESE ITEMS.
C. CONTRACTOR IS TO PROTECT ALL EXISTING CONDITIONS THAT ARE TO REMAIN FROM DAMAGE DURING
DEMOLITION PHASE OF WORK. ITEMS DAMAGED ARE TO BE REPAIRED BY THE CONTRACTOR AT HIS EXPENSE.
D. CONTRACTOR IS TO VERIFY WITH THE TENANT WHICH ITEMS TO BE REMOVED WILL REMAIN THE PROPERTY OF
THE TENANT. DISPOSE OF OR STORE SUCH ITEMS AS DIRECTED.
E. COORDINATE ALL PLUMBING, AND ELECTRICAL DEMO WITH RESPECTIVE PLUMBING AND ELECTRICAL SHEETS.
F. CONTRACTOR TO REMOVE ALL FIXTURES NOT BEING REUSED IN FIXTURE PLAN. PROTECT AND STORE DURING
CONSTRUCTION. COORDINATE WITH OWNER FOR RELOCATION OF UNUSED EQUIPMENT.
KEYED NOTES
1 REMOVE EXISTING NOVELTY MUGS DISPLAY, AND STRAW BOX/HOLDER IF STILL EXISTING AT TIME OF DEMOLITION. PROTECT
DURING DEMO/CONSTRUCTION AND COORDINATE W/ OWNER.
2 REMOVE EXISTING REESES CHOCOLATE, SOUR PATCH CANDY, KITKAT CHOCOLATE, AND TEA DISPLAYS IF STILL EXISTING AT
TIME OF DEMOLITION. PROTECT DURING DEMO/CONSTRUCTION AND COORDINATE W/ OWNER.
3 DEMO ENTIRE COUNTERTOP. PULL EXISTING CABINETS FORWARD, AND PREP FOR FILLER. REF: A160.
4 REMOVE EXISTING SODA BIBS, CO2 TANKS, AND ADJOINING LINES. COORDINATE STORAGE W/ OWNER. REMOVE ALL ASSOCIATED
PLUMBING AND ELECTRICAL NOT BEING REUSED BACK TO SOURCE. PATCH AND REPAIR AFFECTED WALL SURFACES AS
REQUIRED.
5 REMOVE EXISTING BANG/STAR ENERGY DRINK RACK IF STILL EXISTING AT TIME OF DEMOLITION. PROTECT DURING
DEMO/CONSTRUCTION AND COORDINATE W/ OWNER.
6 REMOVE EXISTING GRINDS DISPLAY IF STILL EXISTING AT TIME OF DEMOLITION. PROTECT DURING DEMO/CONSTRUCTION AND
COORDINATE W/ OWNER.
7 REMOVE EXISTING NOVELTY CUPS, GRANDMA'S PASTRY, EXTRA/BOOST ENERGY DRINKS, AND OREO DISPLAYS IF STILL
EXISTING AT TIME OF DEMOLITION. PROTECT DURING DEMO/CONSTRUCTION AND COORDINATE W/ OWNER.
8 REMOVE EXISTING JOHNSON'S CORNER DISPLAY IF STILL EXISTING AT TIME OF DEMOLITION. PROTECT DURING
DEMO/CONSTRUCTION AND COORDINATE W/ OWNER.
9 REMOVE TILE BASE AS REQUIRED ON SIDE TO ALLOW RELOCATED CASEWORK.
X CASEWORK GENERAL NOTE:
G.C. TO COORDINATE WITH EG THIRD PARTY
CASEWORK VENDOR AS REQUIRED FOR ANY
PATCH/REPAIR NEEDED TO EXISTING CASEWORK. ALL
NEW AND EXISTING CASEWORK TO BE RE-SURFACED
BY THIRD PARTY VENDOR.
GENERAL NOTE - ALL STORE DISPLAY FIXTURES
G.C. IS TO COORDINATE REMOVAL, STORAGE, AND
RELOCATION OF ALL EXISTING STORE DISPLAY
FIXTURES THAT ARE AFFECTED BY PROPOSED SCOPE
OF WORK W/ TENANT AND FINAL MERCHANDISE PLAN.
CASEWORK RECONFIGURATION NOTE:
G.C. TO NOTIFY THE AOR IF THE NOTED CASEWORK TO
GET MODIFIED CANNOT BE RECONFIGURED PER DWG'S
D100 & A160
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
GENERAL NOTE - ALL EQUIPMENT
ITEMS INDICATED FOR REMOVAL ON DEMO PLAN SHALL
BE COORDINATED WITH THE FIXTURE PLAN AND
SCHEDULE FOR REMOVAL, STORAGE, AND
RELOCATION.
ALL EQUIPMENT NOT BEING RELOCATED TO BE
COORDINATED WITH OWNER FOR TEMPORARY
STORAGE AND PICK UP.
02/12/2021
EX. SHELVINGCHECKOUT
WOMENS' RESTROOM MENS' RESTROOM
SALES
WALK-IN
COOLER
(8 DOORS)
BOH/ OFFICE AREA
EX. LOTTERY
EX. AIR
COMPRESSOR
(26 GAL)
SLOPED DOWNSLOPED DOWN
EX. DUMPSTER
EX. BOLLARD
EX. BOLLARD
EX. CONDENSOR
EX. BOLLARD
(TYP.)
EX. COOLER
CONDENSOR
EX. KEROSENE
PUMP
EX. BOLLARD (TYP.)
EX. ICE MACHINE
EX. BOLLARD (TYP.)
EX. RAISED
CONCRETE SLAB
ROOF OVERHANG
ABOVE
DS
DS
DS DS
DS
DS
EX. CONDENSOR
EX.
DISCONNE
CTS
EX. VENT
PIPING
EX. AIR COMPRESSOR
LINE THROUGH WALL
EX. VENT
THROUGH WALL
EX. BULKHEAD
ABOVE
EX. COLUMN
WRAP (TYP.)
EX. COLUMN (TYP.)
EX. COLUMN
WRAP (TYP.)
EX. PHONE BOOTH
EX. EMERGENCY
PUMP SHUT -OFF
SL
O
P
E
D
D
O
W
N
J13 (x3)
J13
(x8)
J13
(x8)
J
J
J
J
J
J
J
J
A10
A10
B12A
P8
M5
K1
K1
K6
K3
B25
E1
C10
C12AC9
F10
F10
F8
F7
C10A
F16
EL
E
C
.
&
T
E
L
E
/
C
O
M
M
.
S
E
R
V
I
C
E
S
B7
P3
T3
T4
P1
P2A
EX. HEAT
PUMP
P4
EX. WATER
METER
G2
G1
J1 C6J1
CO
F
F
E
E
B
A
R
EX. LIVE BAIT
EX. DISPLAY
FE
G8
E9
E10
E13
E4
F10
F2
(x2)
F3 (x4)
C1
F5
C9A
C7
B15
C4
C26
HOT FOODS & CONDIMENTS
1' - 0"3' - 0"8' - 6"
J14
J14
J14
J14
M1
1
2
2
3
4
55
J14 (x4)
C27
ABV
6
7
EX
.
C
I
G
A
R
E
T
T
E
/
T
O
B
A
C
C
O
D
I
S
P
L
A
Y
S
EX. OVERHEAD
CIGARETTE RACK
EX. TOBACCO
DISPLAY
4'
-
2
"
EX.
CONCRETE
PAD
NEW CONCRETE PAD
G2
8
ABV
C1c
C3
7
SYMBOL DESCRIPTION
LEGEND
NEW WALL CONSTRUCTION
EXISTING EQUIPMENT/CASEWORK TAG
NEW EQUIPMENT/CASEWORK TAGXX
XX
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
DA
T
E
CO
M
M
E
N
T
S
BY
CH
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:
\
U
s
e
r
s
\
M
S
c
o
t
t
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
R
K
_
C
O
_
C
en
t
r
a
l
_
M
s
c
o
t
t
8
D
D
T
S
.
r
v
t
2/
1
1
/
2
0
2
1
6
:
0
4
:
4
0
P
M
12322-034
A150
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
FI
X
T
U
R
E
P
L
A
N
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
KEYED NOTES
1 CO2 VENDOR TO SUPPLY/INSTALL CO2 TANK AND SERVICE LINE INTO THE
BUILDING AS INDICATED. LINE TO BE COORDINATED WITH G.C. AND CONCEALED
THROUGHOUT BUILDING UNTIL CONNECTION AT SODA BIB RACK.
2 G.C. TO INSTALL SODA BIB RACK AND ALL REQUIRED LINES TO EQUIPMENT. LINES
TO BE ROUTED THROUGH WALLS AND CASEWORK AS NEEDED TO REMAIN
CONCEALED. PATCH/REPAIR ALL AFFECTED SURFACES.
3 G.C. TO INSTALL CONCRETE EQUIPMENT PAD AND INSTALL 6'-0" HIGH CHAIN LINK
FENCE ENCLOSURE FOR CO2 TANK WITH LOCKING GATE. FENCE TO HAVE
PRIVACY SLATS TO MATCH ADJACENT EXTERIOR WALL COLOR. G.C. TO SEAL AND
WEATHERPROOF OPENING FOR CO2 LINE AFTER CO2 TANK INSTALLATION.
4 G.C. TO INSTALL (1) NEW BOLLARD TO MATCH EXISTING.
5 G.C. TO INSTALL NEW CONDENSING UNITS ON THE AREA INDICATED. REF R100.
6 G.C. TO OPEN UP THE WALL AS REQUIRED TO RUN THE NEW PLUMBING. PATCH
AND REPAIR AS REQUIRED. FINISHES TO MATCH EXISTING. SEE SHEET P110 FOR
MORE INFO.
7 G.C. TO INSTALL 3 5/8" STUD WALL (16" O.C.) TO SUPPORT REAR OF NEW
COUNTER.
8 G.C. TO REPAIR TILE BASE AS REQUIRED AFTER REINSTALLING CASEWORK.
X
SCALE:1/4" = 1'-0"A150
1 FIXTURE PLAN
NOTE: REFER TO SHEET A151 FOR EQUIPMENT SCHEDULE.
REFER TO SHEET A160 FOR CASEWORK SCHEDULE.
A. CAULK ALL COUNTERTOP "FOOTBALLS" TO THE COUNTER TO
PREVENT LIQUID FROM INFILTRATING THE METAL BASE. US E
CLEAR SILICONE CAULKING. (BY G.C.)
B.UPRIGHT COOLERS/FREEZERS ARE SHIPPED WITH HINGES ON THE
RIGHT SIDE. GENERAL CONTRACTOR TO MODIFY DOOR SWING ON
UPRIGHTS TO MATCH PLAN AS SHOWN.
EQUIPMENT PLAN GENERAL NOTES:
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
GENERAL NOTE - ALL EQUIPMENT
ITEMS INDICATED FOR REMOVAL ON DEMO PLAN SHALL BE
COORDINATED WITH THE FIXTURE PLAN AND SCHEDULE FOR
REMOVAL, STORAGE, AND RELOCATION.
ALL EQUIPMENT NOT BEING RELOCATED TO BE COORDINATED WITH
OWNER FOR TEMPORARY STORAGE AND PICK UP.
02/12/2021
EG - EQUIPMENT SCHEDULE
ITEM #
QTY DESCRIPTION MANUFACTURER MODEL NOTES
SUPPLIED BY OWNER
& INSTALLED BY
EG/CF THIRD
PARTY VENDOR CONTRACTOR
A-WALK-IN COOLER/FREEZER
B-REFRIGERATION
B25 1 ICE CREAM NOVELTY EXISTING EXISTING
C - FOOD SERVICE EQUIPMENT
C9 1 CONDIMENT BAR CREATIVE SERVING CH196-CF •
C10 1 HEATED CONDIMENT DISPENSER TBD TBD
C10A 1 CHIPS HOLDER
E - CHILL ZONE EQUIPMENT
E1 1 ICE/SODA DISPENSER CORNELIUS
#IDC 621058656/PIDC
PRO255BCH20B8FS115 w/
IY0594N-161 ice maker
E9 1 BAG-IN-BOX PFI STOCKMASTER
E10 1 BIB AIR COMPRESSOR PUMA
LA-5706 (PROVIDE AS PART
OF E9)
F - COFFEE EQUIPMENT
F2 2 COFFEE/TEA BREWER BUNN ITCB-DV 35700.0055
F5 1 6 FLAVOR CAPPUCCINO MACH W/ HOT WATER CURTIS PCGT6
F7 1 MILK AND CREAM DISPENSER SURESHOT AC220-SS •
F8 1 FLAVOR SHOT DISPENSER SURESHOT ACFC-10-14
G - STORE FURNISHINGS
G1 1 SWIVEL TASK CHAIR EXISTING EXISTING
G2 3 FILE CABINET
G8 1 FIRE EXTINGUISHER
J - STORE SHELVING
J 8 EXISTING COOLER WIRE RACK EXISTING EXISTING
J1 2 EXISTING STORAGE SHELVING EXISTING EXISTING
K - CASHIER EQUIPMENT
K1 2 EXISTING POS TERMINAL EXISTING
K3 1 LOTTERY TERMINAL EXISTING
K6 1 ELECTRONIC SAFE EXISTING
M - MISCELLANEOUS
M5 1 ATM MACHINE EXISTING EXISTING
P - PLUMBING EQUIPMENT
P8 1 HAND SINK EXISTING EXISTING
NOTE: AREAS IN HATCH INDICATE EXISTING EQUIPMENT PROPOSED TO BE REUSED.
C4 1 HOT SANDWICH SLIDE
F10 3 DUAL SOFT HEAT COFFEE BREWER BUNN DUAL SH DBC 33500.0001 •
INCLUDES (2) 1.5 GALLON
SERVER EACHUSE FACTORY
SUPPLIED 90DEG WATER
SUPPLY FITTING
EXISTING EXISTING
EXISTING
EXISTING
T3 1 PAPER TOWEL DISPENSER
EXISTING EXISTING
T4 1 SOAP DISPENSER EXISTING EXISTING
E4 1 FROZEN BEVERAGE DISPENSER
B12a 1 UPRIGHT COOLER - 2 DOOR (SANDWICH)
EXISTING
J13 19 GONDOLA SHELVING EXISTING EXISTING
HATCO HZMS-30D
EXISTING EXISTING
P3 1 HAND SINK (WALL MOUNT) EXISTING EXISTING
P2A 1 MOP SINK EXISTING EXISTING
A10 2
GLASS DISPLAY - 4 DOOR -
MEDIUM TEMP (COOLER)EXISTING EXISTING
P1 1 3-BAY SINK EXISTING EXISTING
F3 4 39600.0083
B7 1 UPRIGHT STORAGE FREEZER
C6 1 ACCELERATED WARMING OVEN MERRYCHEF e4S-CF •
P4 1 WATER HEATER EXISTING EXISTING
F16 1 ICE DISPENCER/MAKER EXISTING EXISTING
EXISTING EXISTING
FBD#774 4-HEADTAYLOR COMPANY
C12A 1 HEATED PIZZA DISPLAY CABINET HATCO FSD-1X
C1b 1 ROLLER GRILL
•
•
•
•
E13 1 CO2 TANK CARBO-MIZER 450
•
•
•
ICE TEA/COFFEE DISPENSER
•
BUNN •
EXISTING EXISTING
B15 1 U/C CONVERTABLE REFRIGERATOR/FREEZER RANDELL FX-2WSA AT OVENS
TBD TBD
C9A 1 CONDIMENT RACK •TBD TBD
•
•
C7 1 MICROWAVE OVEN EXISTING EXISTING
C26 1 PASTRY CASE ROSETTO BD125 •
•
EXISTING EXISTING
•
ELECTRICAL PLUMBING
VOLTAGE WATTS/
AMPS
OUTLET/
BREAKER
115/60/1 7.8 A
NEMA 5-15P/
20A 1P
WIRE
(3) 12 AWG
SANITARY DOMESTIC
120/60/1 3.0 A NEMA 5-15P/
20A 1P (3) 12 AWG
120/60/1 8.5 A NEMA 5-15P/
20A 1P (3) 12 AWG
115/60/1 14.2 A WIRED/
20A 1P (3) 10 AWG
115/60/1 2.0 A
(3) 12 AWG
115/60/1 8.5 A
NEMA 5-15P/
20A 1P (3) 12 AWG
208/60/2 or
240/60/2 15.6 A NEMA L6-30R/
30A 2P (3) 10 AWG
208/60/2 or
240/60/2 12.0 A WIRED/
15A 2P (3) 12 AWG
1" IW 3/8" FW
WIRED/
15A 1P
1" IW 3/8" DFW
3/8" DFW
115/60/1 11.53 A
DUPLEX/
20A 1P (3) 12 AWG
120/60/1 14.0 A NEMA 5-15P/
20A 1P (3) 12 AWG 1/4" DFW
120/60/1 15.0 A NEMA 5-15P/
20A 1P (3) 12 AWG 1/4" DFW
120/60/1 1.0 A NEMA 5-15P/
15A 1P (3) 12 AWG
120/60/1 1.0 A
NEMA 5-15P/
15A 1P (3) 12 AWG
208/60/2 or
240/60/2 29.1 A NEMA 14-50R/
50A 2P
(3) 8 AWG
(1) 10 AWG 1/4" DFW
V.I.F.V.I.F. V.I.F. V.I.F.
RELOCATED
208/60/2 or
240/60/2 7.5 A NEMA 6-30P/
30A 1P (3) 10 AWG
V.I.F.V.I.F. V.I.F. V.I.F.
11.3 A NEMA L14-20P/
20A 1P120/60/1 (4) 12 AWG
EXHAUST FAN NEEDED REF: SHEET
E501
120/60/1 12.0 A NEMA 5-15P/
20A 1P (3) 12 AWG
C27 1 EXHAUST FAN FANTECH FG 8XL INLINE REFERENCE SHEET E501 FOR LOCATION 120/60/1 5.8 A WIRED/20A 1P (3) 12 AWG
ICE
CU-3
SODA
DISPENSER
CU-4
PROVIDED AS PART OF E9
M1 1 6 FT CHAIN LINK FENCE W/ PRIVACY SLATS &
GATE
PRIVACY SLAT COLOR TO MATCH ADJACENT
FINISHES. SEE PLAN FOR FENCE/GATE
DIMENSIONS SUPPLIED AND INSTALLED BY
CONTRACTOR
•
J14 8 DISPLAY SHELVING EXISTING EXISTING
P1A 1 WATER FILTER EVERPURE EV9328-06
REFERENCE SHEET P110 FOR LOCATION •
C1c 1 SNEEZE GUARD
EXISTING EXISTING V.I.F.V.I.F. V.I.F. V.I.F.
C3 1 BUN WARMER
EXISTING EXISTING V.I.F.V.I.F. V.I.F. V.I.F.
•
•
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:40 PM
12322-034
A151
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
EQ
U
I
P
M
E
N
T
S
C
H
E
D
U
L
E
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
02/12/2021
CHECKOUT
WOMENS' RESTROOM MENS' RESTROOM
SALES
WALK-IN
COOLER
(8 DOORS)
BOH/ OFFICE AREA
DS
DS
DS DS
DS
DS
H1
EL
E
C
.
&
T
E
L
E
/
C
O
M
M
.
S
E
R
V
I
C
E
S
H14
H36
H5
H6
H19
H22
(x2)
H20
3' - 3"
A160
2
± 8"
± 1' - 8"
± 19' - 7"
EXISTING CUP
AND LID
HOLDERS
± 7' - 0"
H8
SYMBOL DESCRIPTION
LEGEND
EXISTING CASEWORK TAG
NEW CASEWORK TAGXX
XX
NEW SOLID SURFACE COUNTERTOP
EG - CASEWORK SCHEDULE
ITEM # QTY DESCRIPTION MANUFACTURER MODEL
SUPPLIED AND
INSTALLED BY
CONTRACTOR
H - BUILDING CASEWORK (BY MILLWORK VENDOR)
H1 1 CASHWRAP
H5 1 COFFEE BAR/PREP TABLE
SUPPLIED BY OWNER
AND INSTALLED BY
CONTRACTOR
NOTE: AREAS IN HATCH INDICATE EXISTING CASEWORK TO BE REUSED.
EXISTING. NEW WRAP
CABINETS (BY OTHERS).EXISTING
EXISTING
H36 1
HOT FOODS TABLE
H6 1 CHILL ZONE/HOTFOOD COUNTER
H14 1 MANAGER'S DESK EXISTING EXISTING
•
•
H19 1
COFFEE/TEA SHROUD (x4)
•
•
H20 1
TEA RACK
H22 2
FIT IT RACK
ADVANCE TABCO: TKSS-305
OR APPROVED ALTERNATE
EXISTING. NEW WRAP
CABINETS (BY OTHERS).
RELOCATED EXISTING CABINETS.
NEW COUNTER TOP. NEW WRAP ON
CABINETS (BY OTHERS). REF: SHEET
A160 FOR DETAILS
EXISTING
H8 1 LID HOLDER •
NOTE:
1. MATERIALS LISTED IN SCHEDULE DO NOT NECESSARILY APPEAR IN DRAWINGS.
MILLWORK FINISH SCHEDULE
SOLID SURFACE COUNTER TOPSS-1 TO MATCH EXISTING BY MILLWORK VENDORTO MATCH EXISTING
WASTE
PULL RELOCATED CABINETS
FORWARD AND INSTALL NEW
COUNTER TOP TO MATCH
DEPTH INDICATED FOR NEW
EQUIPMENT
NEW SS-1 COUNTER TOP
± 19' - 7"
REMOVE ALL EXISTING VINYL
BASE OVER CASEWORK ON
WALL
FINISH TO BE WRAPPED BY
THIRD PARTY
PULL RELOCATED CABINETS
FORWARD AND INSTALL NEW
COUNTER TOP TO MATCH
DEPTH INDICATED FOR NEW
EQUIPMENT
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:\Users\MScott\Documents\EG_750828_ESTAS-PARK_CO_Central_Mscott8DDTS.rvt
2/11/2021 6:04:41 PM
12322-034
A160
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
CA
S
E
W
O
R
K
P
L
A
N
&
D
E
T
A
I
L
S
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
SCALE: 1/4" = 1'-0"A160
1 CASEWORK PLAN
CASEWORK RECONFIGURATION NOTE:
G.C. TO NOTIFY THE AOR IF THE NOTED
CASEWORK TO GET MODIFIED CANNOT BE
RECONFIGURED PER DWG'S D100 & A160
CASEWORK GENERAL NOTE:
G.C. TO COORDINATE WITH THIRD PARTY
CASEWORK VENDOR AS REQUIRED FOR ANY
PATCH/REPAIR NEEDED TO EXISTING
CASEWORK/COUNTERTOPS. ALL NEW AND
EXISTING CASEWORK TO BE RE-SURFACED
BY THIRD PARTY VENDOR.
0
2/12/21
ORIGINAL PERMIT SUBMISSION
BD
MS
SCALE:1" = 1'-0"A160
2 CHILL ZONE/HOTFOOD COUNTER (H6) ELEV.
02/12/2021
E.CUTTING, PATCHING AND DRILLING
1.PATCH AND FINISH TO MATCH ADJACENT AREAS THAT HAVE BEEN CUT, DAMAGED OR MODIFIED AS A RESULT OF THE
INSTALLATION OF THE MECHANICAL SYSTEMS.
2.EXACT LOCATION OF ROOF TOP MECHANICAL UNITS SHALL B E APPROVED BY THE STRUCTURAL ENGINEER.
CONTRACTOR SHALL FURNISH AND INSTALL ALL SUPPLEMENT AL SUPPORT STEEL FOR EQUIPMENT AND ROOF
PENETRATIONS AFTER APPROVAL OF STRUCTURAL ENGINEER.
INSULATION
A.PLUMBING INSULATION (AS MANUFACTURED BY OWENS CORNING, KNAUF, SCHULLER OR CERTAINTEED)
1.INSULATE ALL ABOVE GRADE HOT AND COLD WATER PIPING WITH MOLDED FIBER GLASS HAVING AN ALL SERVICE JACKE T.
B.INSULATION THICKNESS SCHEDULE: 1) LESS THAN 2" DIAM ETER PIPE: 1" THICK -HW AND 1/2" THICK -CW; 2) 2"-8" DIAMETER
PIPE: 1-1/2" THICK.
1.INSULATE ALL ABOVE -GRADE, HORIZONTAL RAIN CONDUCTORS AND ROOF DRAIN SU MPS WITH ONE (1) INCH THICK MOLDED
FIBER GLASS HAVING TYPE ASJ JACKET AND MANUFACTURED BY OWENS -CORNING FIBERGLASS COMPANY.
2.INCLUDE INSULATION OF FITTINGS AND VALVES. KEEP VAP OR BARRIERS INTACT. APPLY TO MANUFACTURER'S
RECOMMENDATIONS.
PIPING AND VALVES
A.GENERAL
1.LABEL ALL PIPING AND SHOW DIRECTION OF FLOW EVERY 20 FEET ON CENTER.
B.CONNECTIONS TO EQUIPMENT
1.PROVIDE VALVED WATER CONNECTION FOR EQUIPMENT.
2.INCLUDE ACCESSORIES REQUIRED BY CODE, DRAWING OR MA NUFACTURER'S INSTRUCTIONS.
C.SANITARY AND STORM SEWERS
1.PVC PIPING SHALL NOT BE INSTALLED UNLESS PERMITTED BY CODE.
2.SANITARY/STORM SEWER AND VENT MATERIAL SHALL BE AS FOLLOWS:
D.ABOVE GRADE SANITARY/STORM SEWER AND VENT MATERIAL SHALL BE AS FOLLOWS: (EXISTING TIE -IN FOR ROOF DRAIN IS
SCH 40 PVC)
1.NO -HUB CAST IRON PIPE CISPI 1 -301 -78.
2.PVC -DWV PLASTIC ASTM D1785 WITH ASTM D2665 DWV SOLVENT WELD SOCKET FITTINGS.
3.SCHEDULE 40 GALVANIZED STEEL PIPE, ASTM A120 -83 WITH CAST IRON SCREWED FITTINGS ANSI B16.22 1983.
E.SITE STORM AND SANITARY SEWERS
1.UP TO 15" -PVC PLASTIC ASTM D3034 SDR 35 WITH ASTM D3212 GASKE T JOINTS.
F.DOMESTIC WATER PIPING
1.INSTALL DOMESTIC WATER PIPING AS INDICATED ON DRAWINGS. INCLUDE ALL FITTINGS, VALVES, HANGERS AND
OTHER ACCESSORIES INCLUDING WATER METER AND BACKFLO W PREVENTER. EXTEND DOMESTIC WATER PIPING TO
ALL FIXTURES AND EQUIPMENT REQUIRED FOR COMPLETE IN STALLATION.
1.INCLUDE UNIONS, OR OTHER DISCONNECT MEANS, STOPS OR VALVES FOR ISOLATION OF FIXTURES AND EQUIPMENT.
VALVES TO BE FULLY COMPATIBLE WITH PIPING FOR SERVICE INTENDED AS MANUFACTURED BY NIBCO, CRANE OR
MILWAUKEE. INCLUDE HOSE OR DRAIN VALVES AT LOW POIN TS WHERE FIXTURES CANNOT BE USED FOR DRAINAGE.
2.DOMESTIC WATER PIPING SHALL BE AS FOLLOWS:
a.ABOVE GRADE -TYPE "L" HARD COPPER ASTM B88-832 WITH WROUGHT COPPER FITTINGS ASTM B16.22 1980 A ND
NON -LEAD OR ANTIMONY SOLDER JOINTS.
b.BELOW GRADE -TYPE "K" SOFT COPPER WITHOUT JOINTS.
c.FLUSH, VENT AND SANITIZE ALL WATER PIPING WITH CHLO RINE AS REQUIRED PER AWWA, LOCAL BUILDING
DEPARTMENT AND HEALTH DEPARTMENT CODES.
d.DOMESTIC HOT AND COLD WATER PIPING UNDER CONCRETE F LOOR TO BE COVERED WITH SAND SO THAT
PIPING WILL NOT BECOME EMBEDDED IN THE FLOOR SLAB.
4.ALL PIPING UNDER CONCRETE FLOOR SHALL BE TYPE "K" S OFT COPPER, CONTINUOUS. NO SPLICES OR FITTINGS WILL
BE ALLOWED.
5.EXTREME CAUTION MUST BE TAKEN SO THAT NO COPPER PIP ING AND INSULATION UNDER CONCRETE FLOORS
BECOMES CRUSHED, CUT, SPLIT OR DEFORMED DURING THE POURING OF THE FLOOR SLAB.
6.ALL PIPING UNDER CONCRETE FLOORS SHALL BE COVERED INSIDE A PVC PIPE
G.PIPE SUPPORTS
1.PIPE SUPPORTS FOR HOT PIPE SHALL BE ANVIL FIG. 181 OR EQUAL.
2.PIPE SUPPORTS FOR NATURAL GAS SHALL BE ANVIL FIG. 260 OR EQUAL.
GENERAL REQUIREMENTS
A.GENERAL
1.CONFORM TO ALL GENERAL AND SPECIAL CONDITIONS OF CO NTRACT AS SPECIFIED BY SITE ENGINEER ’S AND/OR
OWNER.
2.VISIT SITE, CHECK FACILITIES AND CONDITIONS AND MAK E ALL NECESSARY OBSERVATIONS AND MEASUREMENTS.
NOTE CONDITIONS UNDER WHICH WORK IS TO BE PERFORMED AND TAKE ALL ITEMS INTO CONSIDERATION IN BID.
3.SYSTEMS ARE TO BE COMPLETE AND WORKABLE IN ALL RESP ECTS, PLACED IN OPERATION AND PROPERLY
ADJUSTED.
4.CONTRACTOR SHALL PROVIDE HIS OWN CLEAN -UP, REMOVAL AND LEGAL DISPOSAL OF ALL RUBBISH DAILY .
5.CONTRACTOR SHALL PROTECT HIS WORK, HIS EXISTING AND ADJACENT PROPERTY AGAINST WEATHER.
6.CONTRACTOR SHALL PROTECT HIS WORK, MATERIALS, APPAR ATUS AND FIXTURES FROM DAMAGE. ANY WORK
DAMAGED BY FAILURE TO PROVIDE PROTECTION REQUIRED, SHALL BE REMOVED AND REPLACED WITH NEW MATERIAL
AT THE CONTRACTOR'S EXPENSE.
7.ARRANGE FOR AND OBTAIN OWNER'S AND INSURANCE REPRES ENTATIVE'S PERMISSION FOR ANY SERVICE
SHUTDOWNS.
8.THE CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR CON STRUCTION MEANS, METHODS, SEQUENCES OF
CONSTRUCTION AND THE SAFETY OF WORKMEN.
9.NO PIPING, DUCTWORK, WIRING, ETC. SHALL BE INSTALLE D OR ROUTED ABOVE ELECTRICAL PANELS AND EQUIPMENT.
10.THE CONTRACTOR SHALL COORDINATE AND OBTAIN A WRITTE N APPROVAL IDENTIFYING THE ELECTRICAL
CHARACTERISTICS OF ALL MECHANICAL EQUIPMENT PRIOR T O ORDERING OF EQUIPMENT. NO ADDITIONAL PAYMENT
WILL BE MADE FOR LACK OF CONTRACTOR COORDINATION OF ELECTRICAL CHARACTERISTICS.
11.DURING CONSTRUCTION THE CONTRACTOR MAY UNCOVER AN E XISTING CONDITION THAT WILL HAVE TO BE
MODIFIED. ANY SUCH WORK WHICH COMES UNDER THE JURIS DICTION OF THIS CONTRACTOR SHALL BE DONE BY THIS
CONTRACTOR WITHOUT EXTRA COST TO THE OWNER, AS THOUGH FULLY DETAILED ON PLANS AND/OR DES CRIBED
IN THE SPECIFICATIONS.
12.ALL DIMENSIONS, MEASUREMENTS AND PROJECT CONDITIONS SHALL BE CHECKED AND VERIFIED IN THE FIELD BY
THE CONTRACTOR. REFER ALL DIFFERENCES, IN WRITING, TO THE OWNER'S REPRESENTATIVE FOR CONSIDERATION
PRIOR TO PROCEEDING WITH THE WORK. THE CONTRACTOR SHALL BEAR THE COST OF RECTIFYING WORK NOT
APPROVED BY THE OWNER'S REPRESENTATIVE, CAUSED BY L ACK OF COORDINATION AND OR NOTIFICATION.
13.INSTALL ALL EQUIPMENT IN FULL ACCORDANCE WITH LOCAL CODE REQUIREMENTS, OTHER SPECIFICATION SECTION
REQUIREMENTS, AND MANUFACTURER RECOMMENDATIONS.
B.CODES, PERMITS, STANDARDS AND REGULATIONS
1.CONFORM TO ALL APPLICABLE CODES (LOCAL, STATE, NATIONAL CODES, NFPA, OSHA, ETC.). GOVERNMENT
REGULATIONS, UTILITY COMPANY REQUIREMENTS, AND APPL ICABLE STANDARDS.
2.OBTAIN PERMITS AND PAY ALL FEES, ARRANGE FOR ALL RE QUIRED INSPECTIONS AND APPROVALS.
C.DRAWINGS
1.THE SYSTEMS AS SHOWN ON PLUMBING DRAWINGS ARE DIAGR AMMATIC. CONFIRM ALL DIMENSIONS BY FIELD
MEASUREMENT.
2.THE EXACT LOCATIONS FOR FIXTURES, EQUIPMENT AND PIP ING WHICH IS NOT COVERED BY DRAWINGS, SHALL BE
OBTAINED FROM THE SITE ENGINEER ’S OR HIS REPRESENTATIVE IN THE FIELD AND THE WORK SHALL BE LAID OUT
ACCORDINGLY.
D.BASE EQUIPMENT, MATERIALS AND SUBSTITUTIONS.
1.ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE OF D EFECTS AND U.L. LABELED.
2.BASE BID MANUFACTURERS ARE INCLUDED IN THE SPECIFIC ATIONS OR LISTED IN THE NAME OR MAKE OF ANY
ARTICLE, DEVICE, MATERIAL, FORM OF CONSTRUCTION, FIXTURE, ETC. STATED IN THIS SPECIFICATIONS, WHETHER OR
NOT THE WORDS "OR APPROVED EQUAL" ARE USED, SHALL B E KNOWN AS A "STANDARD".
3.ALL PROPOSALS SHALL BE BASED ON "STANDARDS" SPECIFIED.
4.THE EQUIPMENT SCHEDULES ON THE DRAWINGS INDICATE MA NUFACTURERS EQUIPMENT MODEL NUMBERS THAT
THIS DESIGN HAS BEEN BASED ON. THE USE OF OTHER MAN UFACTURES EQUIPMENT THAT IS LISTED AS ACCEPTABLE
ALTERNATES AND REFLECTS ANY ADDITIONAL COST OF SUCH CHANGES SHALL BE PAID BY THE CONTRACTOR.
5.SUBSTITUTIONS ARE SUBJECT TO THE APPROVAL OF THE OW NER. IF A SUBSTITUTION IS SUBMITTED, IT IS THE
CONTRACTOR'S RESPONSIBILITY TO EVALUATE IT AND CERT IFY THAT THE SUBSTITUTION IS EQUIVALENT IN ALL
RESPECTS TO THE BASE SPECIFICATIONS.
6.COORDINATE ALL APPROVED SUBSTITUTIONS. ANY COSTS R ESULTING FROM SUBSTITUTION SHALL BE THE
RESPONSIBILITY OF AND PAID FOR BY THE CONTRACTOR. A PPROVED SHOP DRAWINGS DO NOT ABSOLVE THIS
CONTRACTOR FROM THIS RESPONSIBILITY.
E.ALL EQUIPMENT SHALL BE INSTALLED IN FULL ACCORDANCE WITH THE MANUFACTURER'S DATA AND INSTALLATION
INSTRUCTIONS. IT IS THIS CONFORM THESE REQUIREMENT S PRIOR TO STARTING WORK.
F.WARRANTY
1.FULLY WARRANT ALL MATERIALS, EQUIPMENT AND WORKMANS HIP FOR (1) YEAR FROM DATE OF ACCEPTANCE.
2.EXTEND ALL MANUFACTURERS' WARRANTIES TO OWNER.
3.REPAIR OR REPLACE WITHOUT CHARGE TO THE OWNER ALL ITEMS FOUND DEFECTIVE DURING THE WARRANTY
PERIOD. IN THE CASE OF REPLACEMENT OR REPAIR DUE TO FAILURE WITHIN THE WARRANTY PERIOD, THE WARRANTY
ON THAT PORTION OF THE WORK SHALL BE EXTENDED FOR A MINIMUM PERIOD OF ONE (1) YEAR FROM THE DATE OF
SUCH REPLACEMENT OR REPAIR.
G.SHOP DRAWING SUBMITTALS
1.SUBMIT SHOP DRAWINGS FOR PLUMBING SYSTEMS, INCLUDIN G BUT NOT LIMITED TO FIXTURES AND EQUIPMENT WITH
ADEQUATE DETAILS AND SCALES TO CLEARLY SHOW CONSTRU CTION. INDICATE THE OPERATING CHARACTERISTICS
FOR EACH REQUIRED ITEM. CLEARLY IDENTIFY EACH ITEM ON THE SUBMITTAL AS TO MARK, LOCATION AND USE, USIN G
SAME IDENTIFICATION AS PROVIDED ON THE CONSTRUCTION DOCUMENTS.
2.CONTRACTOR SHALL REVIEW AND INDICATE HIS APPROVAL O F EACH SHOP DRAWINGS PRIOR TO SUBMITTAL FOR
REVIEW. SHOP DRAWINGS WILL NOT BE REVIEWED BY THE E NGINEER UNLESS THE CONTRACTOR'S APPROVAL IS
NOTED. DO NOT START WORK OR FABRICATION UNTIL SHOP DRAWINGS HAVE BEEN REVIEWED BY THE ENGINEER AND
RETURNED TO THE CONTRACTOR.
3.SUBMITTALS WILL BE REVIEWED ONLY FOR GENERAL COMPLIANCE WITH THE CONTRACT DOCUMENTS AND NOT FOR
DIMENSIONS OR QUANTITIES. THE SUBMITTAL REVIEW SHA LL NOT RELIEVE THE CONTRACTOR OF RESPONSIBILITY
FOR PURCHASE OF ANY ITEM IN FULL COMPLIANCE WITH TH E CONTRACT DOCUMENTS OR ITS COMPLETE AND PROPER
INSTALLATION.
4.WHERE SUBMITTALS VARY FROM THE CONTRACT REQUIREMENT S, THE CONTRACTOR SHALL CLEARLY INDICATE ON
SUBMITTAL OR ACCOMPANYING DOCUMENTS THE NATURE AND REASON FOR THE VARIATIONS.
5.EACH MANUFACTURER OR HIS REPRESENTATIVE MUST CHECK THE APPLICATION OF HIS EQUIPMENT AND CERTIFY AT
TIME OF SHOP DRAWING SUBMITTAL THAT THE EQUIPMENT S PECIFIED HAS BEEN PROPERLY APPLIED AND CAN BE
INSTALLED, SERVICED AND MAINTAINED WHERE INDICATED ON THE DRAWINGS. ADVISE ENGINEER IN WRITING WITH
SUBMITTAL DRAWINGS OF ANY POTENTIAL PROBLEMS. THE M ANUFACTURER SHALL BE RESPONSIBLE FOR ANY
CHANGES THAT MIGHT BE NECESSARY BECAUSE OF PHYSICAL CHARACTERISTICS OF EQUIPMENT THAT HAVE NOT
BEEN CALLED TO THE ENGINEER'S ATTENTION AT THE TIME OF SUBMITTAL.
BASIC MATERIALS AND METHODS
A.GENERAL
1.THIS SECTION INCLUDES BASIC PLUMBING MATERIALS AND METHODS TO COMPLEMENT OTHER SECTIONS IN THIS
SPECIFICATION AND REQUIREMENTS INDICATED ON THE MEC HANICAL DRAWINGS.
B.SUPPORTS AND HANGERS
1.INSTALL HANGERS, SUPPORTS, CLAMPS AND ATTACHMENTS A S REQUIRED TO PROPERLY SUPPORT PIPING FROM
BUILDING STRUCTURE. THE INSTALLATION SHALL COMPLY WITH THE REQUIREMENTS OF MSS SP -69 AND SP -89.
C.ESCUTCHEONS
1.FIT ALL PIPE PASSING THROUGH WALLS, FLOORS OR CEILINGS IN FINISHED ROOMS WITH STEEL OR BRASS
ESCUTCHEONS. WHERE SURFACE IS TO RECEIVE A PAINT F INISH, MAKE ESCUTCHEONS PRIME PAINTED; OTHERWISE
MAKE ESCUTCHEONS NICKEL OR CHROME PLATED. WHERE PIPING IS INSULATED, FIT ESCUTCHEONS OUTSIDE
INSULATION.
D.IDENTIFYING DEVICES AND LABELS
1.PROVIDE METAL EQUIPMENT NAMEPLATES PERMANENTLY FAST ENED TO EQUIPMENT W ITH PERATIONAL DATA
ENGRAVED OR STAMPED.
2.IDENTIFY ALL PIPES AND VALVES UNEXPOSED AREAS, AND ACCESSIBLE CEILINGS AND SHAFTS.
3.COLOR CODE IDENTIFICATION BANDS OR MARKER BACKGROUN DS TO IDENTIFY CONTENTS OF PIPE AND DIRECTION
OF FLOW LOCATED NEAR EACH VALVE AND FITTING, ON BO TH SIDES OF PIPE PASSING THROUGH WALLS AND ON LONG
RUNS AT NOT OVER 20 FOOT INTERVALS.
PLUMBING SYSTEMS AND EQUIPMENT
A.GENERAL
1.CONTRACTORS BIDDING THIS PROJECT SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH ALL CONDITIONS
AFFECTING THEIR WORK. SUBMISSION OF A BID ON THIS P ROJECT SHALL BE CONSTRUED AS HAVING SUCH
KNOWLEDGE.
2.VERIFY EXACT CONDITIONS IN FIELD AND COORDINATE WIT H THESE DRAWINGS AND OTHER TRADES BEFORE
BEGINNING NEW WORK.
3.DETERMINE EXACT LOCATIONS FOR ALL EQUIPMENT, PIPING , CONDUITS AND DUCTWORK IN FIELD.
4.COORDINATE WORK OF THIS CONTRACT WITH OTHER TRADES. CONFLICTS SHALL IMMEDIATELY BE BROUGHT TO THE
ATTENTION OF THE SITE ENGINEER ’S. SITE ENGINEER ’S RESOLUTION TO CONFLICTS SHALL BE FINAL.
5.ANY DISCREPANCIES BETWEEN WHAT IS SHOWN ON DRAWINGS OR SPECIFIED AND THE ACTUAL CONDITIONS IN THE
FIELD SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE SITE ENGINEER ’S BEFORE PROCEEDING.
6.BUILDING AND SURFACES DAMAGED DURING INSTALLATION S HALL BE REPAIRED, REPLACED, AND/OR RESTORED TO
ORIGINAL CONDITION AFTER COMPLETION OF WORK AND BEFORE ACCEP TANCE BY OWNER.
B.EQUIPMENT
1.PLUMBING CONTRACTOR TO FURNISH ALL PLUMBING EQUIPME NT INDICATED AND/OR SCHEDULED ON THE DRAWINGS
COMPLETE WITH BASES, ISOLATORS, SUPPORTS AND OTHER REQUIRED ACCESSORIES,
2.INSTALL COMPLETE AND PLACE IN PROPER OPERATION PER MANUFACTURER'S RECOMMENDATIONS, LUBRICATE AND
ADJUST AS REQUIRED. FURNISH AND INSTALL CLEAN SET O F FILTERS PRIOR TO BALANCING.
3.EQUIPMENT TO BE MADE AND MODEL AS SCHEDULED UNLESS ALTERNATE EQUIPMENT OF EQUIVALENT QUALITY AND
PERFORMANCE IS SUBMITTED AS A SUBSTITUTION PRIOR TO BIDDING. ALL SUBSTITUTIONS ARE SUBJECT TO
ACCEPTANCE WITHOUT QUALIFICATION BY OWNER, ENGINEER AND SITE ENGINEER ’S.
PLUMBING INSTRUMENTS AND CONTROLS
A.GENERAL
1.AFTER INSTALLATION, CHECK ALL EQUIPMENT AND PERFORM START UP IN ACCORDANCE WITH THE
MANUFACTURER'S INSTRUCTIONS.
2.ALL PIPING SHALL BE TESTED AND FREE OF LEAKS AS REQ UIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION.
3.WORK THAT IS SCHEDULED TO BE CONCEALED OR INSULATED SHALL REMAIN UNCOVERED UNTIL REQUIRED TESTS
HAVE BEEN COMPLETED. IF THE CONSTRUCTION SCHEDULE REQUIRES, ARRANGE FOR TESTS ON SECTIONS OF THE
SYSTEM AT A TIME.
4.BALANCE ALL SYSTEMS, CALIBRATE CONTROLS, CHECK FOR PROPER OPERATION AND SEQUENCE UNDER ALL
CONDITIONS AND MAKE ALL NECESSARY ADJUSTMENTS.
5.INSTRUCT OWNER IN OPERATION OF SYSTEMS AND SUBMIT O PERATING AND MAINTENANCE MANUAL FOR ALL
EQUIPMENT AND SYSTEMS.
6.SUBMIT AIR AND WATER BALANCE REPORT FROM INDEPENDEN T AABC OR NEBB CERTIFIED SUBCONTRACTOR FOR
ALL AIR AND WATER SYSTEMS PER AABC OR NEBB STANDARD S.
TESTING, ADJUSTING, AND BALANCING
A.BALANCING, START UP AND INSTRUCTIONS
1.AFTER EQUIPMENT IS PLACED IN OPERATION, SYSTEMS SH ALL BE BALANCED WITH REPORT SUBMITTED TO OWNER.
2.START UP AND PLACE ALL SYSTEMS IN OPERATION AND TAG ALL SWITCHES AND CONTROLS WITH PERMANENT
LABELS INSTRUCT OWNER ON PROPER OPERATION AND PREVE NTATIVE MAINTENANCE OF SYSTEM.
3.AS PART OF THE FINAL INSPECTION PROCESS, THE GENERA L CONTRACTOR SHALL SCHEDULE AND PAY FOR A COMPLETE
SEWER LINE VIDEO INSPECTION. PROVIDE A DVD COPY OF THE ENTIRE VIDEO INSPECTION TO THE OWNER.
COLD WATER
HOT WATER
DESCALE FILTERED WATER
FILTERED WATER
SANITARY WASTE
GREASE WASTE
VENT
SHUT OFF VALVE
CHECK VALVE
HUB DRAIN
FLOOR SINK
EG EQUIPMENT TAG
V
GW
W
FW
DFW
XX
PLUMBING LEGEND
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
DA
T
E
CO
M
M
E
N
T
S
BY
CH
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
C:
\
U
s
e
r
s
\
j
l
i
l
l
e
y
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
R
K
_
C
O
_
Ce
n
t
r
a
l
_
j
l
i
l
l
e
y
@
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
.
r
v
t
2/
1
2
/
2
0
2
1
2
:
2
0
:
3
6
P
M
12322-034
P001
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
PL
U
M
B
I
N
G
S
P
E
C
I
F
I
C
A
T
I
O
N
S
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
PLUMBING FIXTURE SCHEDULE
MARK DESCRIPTION MANUFACTURER MODEL #
CONNECTIONS ACCESSORIES NOTES ALTERNATE
MANUFACTURERSVENT WASTE FW DFW
E1 ICE/SODA DISPENSER CORNELIOUS 621058657 - 1" IW 3/8" (2) 3/8" -A, B NONE
E4 FROZEN BEVERAGE DISPENSER TAYLOR COMPANY FBD# 12-7462 - 1" IW 3/8" - -A, B NONE
F2 COFFEE/TEA BREWER BUNN ITCB 35700 - - - 1/4" -A NONE
F5 6 FLAVOR CAPPUCCINO MACH CURTIS PCGT6 - - - 1/4" -A NONE
F10 DUAL SOFT HEAT COFFEE BREWER BUNN 33500 - - - 1/4" -A NONE
A. PROIVDE BALL VALVE AND WATTS SD -2 CHECK VALVE ON FILTERED WATER SUPPLY, PROVIDE FEM ALE NPT VALVE DOWNSTREAM OF VB FOR
CONNECTION OF EQUIPMENT.
B. PROVIDE FULL SIZE DRAIN LINE FROM EQUIPMENT. END OVER DRAIN.
02/12/2021
2
B
3
C
A
1 4
E1
F10
E4
F2
F5
ALL VALVES SHALL BE FULL PORT WITH
STAINLESS STEEEL BALL AND STEM
NOTE: ROUTE COLD WATER PIPING
THROUGH HOLES PROVIDED WITH
MILLWORK OR DRILL NEW HOLES
THROUGH EXISITNG MILLWORK AS
REQ'D. . PIPING SHALL BE INSTALLED
BELOW ELECTRICAL AND TIGHT TO
BACK OF CABINET.
NOTE: PIPES SHOWN OFFSET FOR
CLARITY, ALL PIPES SHALL BE TIGHT TO
BACK OF CABINETRY.
ALL PIPING SHALL BE INSULATED WITH 1-1/2"
FIBERGLASS INSULATION WITH FACTORY
APPLIED JACKET. ALL FITTINGS AND VALVES
SHALL BE PROVIDED WITH INSULATION AND
WHITE PREMOLDED PVC INSULATION
COVERS
PC TO LABEL ALL WATER PIPING WITH
APPROPRIATE "FW" & "DFW" TAGS.
INCLUDE LABEL FOR BYPASSES.
NOTE: REMOVE EXISTING WATER FILTER
SYSTEM (WFS) IF EXISTING. INSTALL
NEW. REF PLAN FOR LOCATION
ALL PLUMBING LINES TO BE ENCLOSED
WITHIN WALLS, MILLWORK, OR ABOVE
CEILING NO EXPOSED PLUMBING LINES.
WFS
ROUTE DRAIN LINE FROM
ICE/SODA DISPENSER
ALONG REAR OF THE
MILLWORK & THROUGH
WALL. SLOPE DRAIN LINE A
MIN. OF 1/8" PER FOOT
TOWARD THE POINT OF
TERMINATION. PROVIDE A
CLEANOUT AT EVERY
CHANGE IN DIRECTION.
TERMINATE OVER EXISTING
NEAREST FLOOR SINK WITH
THE CODE REQUIRED MIN.
AIR GAP.
EXTEND NEW 1" CW LINE FROM
WATER FILTER SYSTEM TO
EXISITNG CW LINE 1" OR
LARGER
(EVERPURE MODEL EV9328-06)
RE: 3/P110
1/2" FW DROP. PROVIDE WATTS
MODEL SD -2 ON EACH CONNECTION
TO BEVERAGE EQUIPMENT. FACTORY
SUPPLIED 90° ELBOW SHALL BE
UTILIZED FOR FINAL CONNECTION TO
EQUIPMENT. (TYP)
DRAIN LINE FROM BACK
OF ICE/SODA DISPENSER
& TROUGH DRAIN.
1" FW
1" DFW1" DFW
ABOVE
CEILING
RUN DFW LINE DOWN
DEDICATED LEGRAND
VERTICAL DROP WIREMOLD.
FASTEN TO COUNTER AND
TO CEILING. DFW LINES TO
RUN THROUGH ISLAND,&
CONNECT TO FIXTURES.
1" DFW
SCALE: NTS
HUB DRAIN DETAIL (IF AS REQ'D)
P110
2
SCALE: NTS
TYPICAL WATER FILTER DETAIL
P110
3
ICE MACHINE
DRAINS
CUT 45 DEG. DRIP TIP (TYP)
2"x3" REDUCER
1-1/2"x2" REDUCER
1-1/2" INDIRECT DRAIN TO
FLOOR SINK
1" REDUCED PRESSURE BACKFLOW
PREVENTER APOLLO # 40-2 -SERIES.
PIPE DRAIN DISCHARGE TO NEAREST
FLOOR DRAIN. EXACT LOCATION TO
BE DETERMINED IN FIELD.
TO FROZEN AND FOUNTAIN
BEVERAGE MACHINES AT
CHILL ZONES
1" FW TO ICE MACHINE,
COFFEE MACHINES, TEA
MACHINES, ETC.SCALE
INHIBITOR
FULL SIZE BY
PASS -NORMALLY
CLOSED
UNION (TYP.)
PRESSURE REDUCING
VALVE SET TO ICE
CUBER AND/OR
COFFEE MAKERS'
MANUFACTURER
BALL
VALVE
(TYP.)
EVERPURE MODEL
EV9328 -06, AND
REMOVABLE
REPLACEMENT
FILTER CARTRIDGES
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
C:
\
U
s
e
r
s
\
j
l
i
l
l
e
y
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
R
K
_
C
O
_
Ce
n
t
r
a
l
_
j
l
i
l
l
e
y
@
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
.
r
v
t
2/
1
2
/
2
0
2
1
2
:
2
0
:
3
8
P
M
12322-034
P110
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
SA
N
I
T
A
R
Y
P
I
P
I
N
G
P
L
A
N
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
PLUMBING GENERAL NOTES
A. ALL PLUMBING LINES NOT BEING REUSED TO BE REMOVED OR CAPPED OFF
BELOW SLAB, WITHIN WALL, OR ABOVE CEILING.
B. CONTRACTOR TO VERIFY ALL EXISTING LINES PRIOR TO ANY REMOVAL OR
INSTALLATION.
C. THE PLUMBING SYSTEMS (SANITARY, WASTE DISTRIBUTION) AND ALL
ASSOCIATED EQUIPMENT WILL BE INSTALLED AND MAINTAINED IN
ACCORDANCE WITH THE FULL REQUIREMENTS OF THE PLUMBING CODE (2018
IPC).
D. NOT USED.
E. ALL HOT AND COLD WATER PIPING LOCATED ABOVE CEILING AREAS BUT BELOW
ROOF INSULATION SHALL BE INSULATED WITH 3/4" FIBERGLASS LOW PRESSURE
TYPE WITH DUAL TEMPERATURE JACKET. ALL HOT AND COLD WATER PIPING
LOCATED OUTSIDE OF BUILDING INSULATION ENVELOPE SHALL BE INSULATED
TO THICKNESS SPECIFIED IN INSULATION SCHEDULE SHOWN ON THIS SHEET.
ALL UNDERGROUND PIPES LOCATED INSIDE BUILDING TO BE ENCASED IN
FLEXIBLE POLYETHYLENE.
F. NOT USED.
G. PROVIDE SEPARATE SHUT-OFF VALVES FOR ALL EQUIPMENT AND PLUMBING
FIXTURES REQUIRING WATER CONNECTIONS.
H. PROVIDE COUPLINGS TO ALL EQUIPMENT AS REQUIRED.
I. NOT USED.
J. PROVIDE CATEGORY III STAINLESS STEEL VENT AS SPECIFIED BY
MANUFACTURER. LAST PORTION OF PIPE SHALL EXTEND A MINIMUM OF 36"
ABOVE ROOF SURFACE.
K. PROVIDE BACKFLOW PREVENTER ON COFFEE MAKERS, ICE MACHINE AND
OTHER WATER LINES AS REQUIRED BY LOCAL CODES.
L. PROVIDE WOOD BLOCKING AS REQUIRED FOR FIXTURES AND PIPING.
M. NOT USED.
N. FILTERED WATER AT THE VEGETABLE PREP SINK IS OPTIONAL. UNFILTERED
COLD WATER MAY BE USED IN ITS PLACE.
O. APPROVED WATER FILTER SYSTEMS:
A. EVERPURE MODEL #EV9328-06 OR SELECTO SCIENTIFIC MODE #MF620CC.
NOTE: PROVIDE LIME INHIBITOR AS MAY BE REQUIRED.
B. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL WATER FILTER FOR
FOUNTAIN DRINKS AT THE BAG-IN-BOX WALL. VERIFY FILTER REQUIREMENTS
WITH COKE VENDER.
P. CUTTING AND NOTCHING OF 2x4 BEARING WALL NOT TO EXCEED 7/8". BORED
HOLES IN 2x4 BEARING WALLS NOT TO EXCEED 2-1/8".
Q. PE PIPING TO BE USED UNLESS NOT ALLOWED BY LOCAL CODES.
R. PLUMBING CONTRACTOR TO PROVIDE WATER FILTER FOR DRINK SYSTEM.
COORDINATE REQUIREMENTS WITH THE EQUIPMENT SUPPLIER.
S. INSTALL INDIRECT WASTE WITH AN AIR GAP AT A MINIMUM OF 2 TIMES THE
DIAMETER OF THE LARGEST WASTE PIPING.
T. NOT USED.
U. NOT USED.
V. NOT USED.
W. NOT USED.
X. HEAT TAPE IS PROVIDED BY WALK-IN-BOX MANUFACTURER AND INSTALLED BY
ELECTRICAL CONTRACTOR. IT IS TO BE SELF-LIMITING TYPE, "FROSTEX" OR
EQUAL.
Y. ALL VALVES TO BE LOCATED OVER ACCESSIBLE CEILING. DO NOT LOCATE OVER
GWB CEILING OR OTHER INNACCESSIBLE AREAS.
Z. ALL HOT, COLD, AND RECIRCULATION WATER PIPING TO BE INSULATED. REF
SPECIFICATION SHEET.
SCALE: 1/4" = 1'-0"
1 SANITARY / DOMESTIC WATER PIPING PLAN
P100
INSTALL SHUTOFF VALVES ON INLET OF EACH
PLUMBING FIXTURE, AND ELSEWHERE AS
INDICATED. FOR SHUTOFF VALVES 2 INCHES
AND SMALLER, USE GATE OR BALL VALVES;
FOR SHUTOFF VALVES 2-1/2" INCHES AND
LARGER, USE GATE OR BUTTERFLY VALVES.
REFER TO SPECIFICATION FOR MORE
INFORMATION.
INSTALL INDIRECT WASTE WITH AN AIR GAP
AT A MINIMUM OF 2 TIMES THE DIAMETER OF
THE LARGEST WASTE PIPING.
1. ALL PIPING CONNECTIONS SHOWN ARE APPROXIMATE ONLY. THE
PLUMBING CONTRACTOR SHALL COORDINATE WITH CUMBERLAN D
FARMS INC. (CFI) FOR THE EXACT LOCATIONS AND REQUIR EMENTS OF
ALL PIPING DROPS AND FINAL CONNECTIONS, AS WELL AS ALL VALVES.
THIS SHALL BE DONE PRIOR TO ANY INSTALLATION OF ANY PLUMBING
SYSTEMS ASSOCIATED WITH THE FOOD SERVICE.
2. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR ALL FINAL
PLUMBING CONNECTIONS TO ALL FOOD SERVICE EQUIPMENT
REQUIRING PLUMBING. ALL FINAL CONNECTIONS SHALL BE
COORDINATED WITH THE FOOD SERVICE CONTRACTOR PRIOR TO
INSTALLATION. ALL FINAL PLUMBING CONNECTIONS TO ALL FOOD
SERVICE EQUIPMENT SHALL BE IN ACCORDANCE WITH THAT
EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.
3. THE TERM "FOOD SERVICE EQUIPMENT" SHALL INCLUDE ALL FIXTURES,
FAUCETS, SINKS, COOKING EQUIPMENT, ICE MAKERS, COFF EE MAKERS
AND ANY EQUIPMENT OR FIXTURE IN THE FOOD SERVICE TH AT
REQUIRES PLUMBING CONNECTIONS.
4. ALL FINAL WATER CONNECTIONS SHALL BE PROVIDED WITH SHUT OFF
VALVES OR SERVICE STOPS.
5. THE PLUMBING CONTRACTOR SHALL BE RESPONSIBLE FOR OB TAINING
ALL FOOD SERVICE EQUIPMENT DRAWINGS AND CUT SHEET
INFORMATION AND TO PERFORM ALL COORDINATION WITH CFI AND
ARCHITECT SO AS TO FAMILIARIZE THEMSELVES WITH EVER Y PIECE OF
FOOD SERVICE EQUIPMENT REQUIRING PLUMBING CONNECTIO NS. ALL
FINAL CONNECTION POINTS, VALVE REQUIREMENTS AND DIM ENSIONS
SHALL BE DETERMINED AS A RESULT OF THIS COORDINATIO N. THE
PLUMBING DRAWINGS SHALL NOT BE USED FOR DIMENSIONIN G OF ANY
DRAIN, VENT, WATER OR GAS PIPING.
6. THE PLUMBING CONTRACTOR SHALL RUN ALL INDIRECT WAST E PIPING
FROM FOOD SERVICE EQUIPMENT TO INDIRECT WASTE AT FLOOR
DRAINS AND FLOOR SINKS. THE PLUMBING CONTRACTOR SHA LL
COORDINATE WITH THE FOOD SERVICE CONTRACTOR FOR ALL
REQUIRED INDIRECT WASTE DRAINS. INDIRECT WASTE PIPING FROM
FOOD SERVICE EQUIPMENT SHALL BE COPPER.
7. NOT USED.
8. PRIOR TO THE COMMENCEMENT OF ANY PLUMBING WORK, THE
PLUMBING CONTRACTOR SHALL COORDINATE A MEETING WITH THE
FOOD SERVICE CONTRACTOR AND CONSULTANT, THE ARCHITE CT, THE
OWNER'S REPRESENTATIVE AND THE OWNER. THE PURPOSE O F THE
MEETING WILL BE FOR THE PLUMBING CONTRACTOR TO PRES ENT THE
PROPOSED LOCATIONS OF ALL FLOOR PENETRATIONS AND
UNDERFLOOR PIPING TO THE OWNER AND TO COORDINATE TH E
LOCATIONS OF ALL FLOOR PENETRATION AND UNDERFLOOR P IPING
THAT WILL BE INSTALLED INTO THE SPACE BELOW THE FOO D SERVICE
FLOOR. NO PLUMBING WORK SHALL BEGIN UNTIL THE OWNER HAS
REVIEWED AND APPROVED ALL FLOOR PENETRATIONS AND
UNDERFLOOR PIPING INSTALLATIONS.
9. ALL FOOD SERVICE EQUIPMENT, FIXTURES AND FAUCETS SH ALL BE
FURNISHED BY CFI. ALL EQUIPMENT AND FIXTURES SHALL BE
INSTALLED BY THE PLUMBING CONTRACTOR. ALL FAUCETS FOR
FIXTURES AND EQUIPMENT SHALL BE INSTALLED BY THE PL UMBING
CONTRACTOR. ALL FAUCET AND FIXTURE TRIM, DRAINS, WA STES,
SERVICE STOPS, P -TRAPS, WASTE ARMS, WATER SUPPLIES, SINK
STRAINERS, TAILPIECES AND ALL PLUMBING TRIM ASSOCIA TED WITH
FOOD SERVICE FIXTURES, FAUCETS AND EQUIPMENT INCLUD ING ALL
FINAL CONNECTIONS SHALL BE FURNISHED AND INSTALLED BY THE
PLUMBING CONTRACTOR.
10. THE PLUMBING CONTRACTOR SHALL BE COMPLETELY RESPONS IBLE
FOR THE INSTALLATION OF ALL FOOD SERVICE SINKS, FAU CETS AND
ALL EQUIPMENT REQUIRING PLUMBING CONNECTIONS.
FOOD SERVICE NOTES
02/12/2021
CU -3 CU -4
C -3
C -4
UC -4
FBD
UC -3
ICE MAKER
2
3
1
2
C-4
C-3
RSL & RLL UP TO
CONDENSER
LOCATION AT
EXTERIOR.
SEAL & WATERPROOF
REFRIGERATION LINES
OPENINGS AT WALL
PENATRATIONS.
TYPICAL
LIQUID
LINE
INSULATION
SUCTION
LINE
INSULATION
UNISTRUT
CUSH-A-CLAMP FIRMLY
CLAMPED TO PIPE
(TYP)
PVC JACKET FOR ALL
REFRIGERATION LINES
EXTERIOR TO BUILDING (TYP)
ELEVATION
PIPING INSULATION
(BEYOND)
SUCTION LINE
BOLT
UNISTRUT P-1000 (GALVANIZED)
WALL OR BUILDING STRUCTURE
PLAN
LIQUID
LINE
CUSH-A-CLAMP FIRMLY
CLAMPED TO PIPE
(TYP)
3" MAX
TOP BEAM
CLAMP TYP
TOP CHORD OF JOIST
ROOF
THREADED ROD
TYP
LOADS MUST BE
HUNG WITHIN 3"
OF PANEL POINTS
BOTTOM OF
STRUCTURE
1 5/8"x1 5/8" GALVANIZED
UNISTRUT P-1000, 10'-0"
MAXIMUM ON CENTERS
TIGHT TO
UNISTRUT
NOTE: FOR OVERHEAD LINES, UNISTRUT HORIZONTAL, TRAP EZE
HUNG FOR PIPING BEHIND CASES, UNISTRUT VERTICAL,
WALL-MOUNTED
PIPING INSULATION
SUCTION LINE
SCHEDULE 40 PVC PIPE
AT EACH NYLON WIRE TIE,
APPROX 10" LONG (INNER
DIAMETER OF PVC PIPE
APPROX. SAME AS OD OF
INSULATION)
PIPING INSULATION
LIQUID LINE
SUPPORT TO BE LOCATED
< 1'-0" FROM DROP
HORIZONTAL REFRIGERANT
LINE SUPPORT. REF DETAIL.LIQUID
LINE (TYP)
SUCTION
LINE (TYP)
INTERMEDIATE SUCTION
LINE TRAP (PLACE TRAP
AT MIDPOINT OF RISER)
BASE TRAP
PROJECT NO.:
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
La
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
NO
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
C:
\
U
s
e
r
s
\
j
l
i
l
l
e
y
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
R
K
_
C
O
_
Ce
n
t
r
a
l
_
j
l
i
l
l
e
y
@
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
.
r
v
t
2/
1
2
/
2
0
2
1
2
:
2
0
:
4
0
P
M
12322-034
R100
75
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
56
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
EG
A
M
E
R
I
C
A
L
L
C
RE
F
R
I
G
E
R
A
T
I
O
N
P
L
A
N
A
N
D
S
C
H
E
D
U
L
E
S
16
5
F
l
a
n
d
e
r
s
R
o
a
d
We
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
SCALE: 1/8" = 1'-0"R100
1 REFRIGERATION PLAN
A. ALL EQUIPMENT RACKS AND SUPPORTS BY OTHERS.
B. ALL EQUIPMENT SHALL BE INSTALLED ACCORDING TO MANUF ACTURER'S GUIDELINES AND INSTALLATION CLEARANCES.
C. REFER TO ARCH DWGS FOR EQUIPMENT RACK DETAIL.
D. REFER TO MANUFACTURER'S LITERATURE FOR CLEARANCE RE QUIREMENTS.
E. REFRIGERANT LIQUID AND SUCTION PIPING SHALL BE SIZE D BY EQUIPMENT MANUFACTURER (TYPICAL).
F. FBD FROZEN BEVERAGE, SANDWICH COOLER AND ICE DISPEN SER RSL PIPING RUNS, RLL PIPING RUNS, AND REMOTE A CCU'S
ARE SHOWN FOR COORDINATION PURPOSES ONLY. EQUIPMENT IS BY OTHERS. RSL AND RLL PIPING AND SIZING SHALL BE
ACCORDING TO MANUFACTURER'S RECOMMENDATIONS.
G. ALL TUBING REFRIGERANT LINES SHALL BE TYPE L HARD D RAWN OR TYPE L SOFT DRAWN COPPER ASTM B280 REFRIGER ANT
GRADE. BRAIDED LINE SETS SHALL ONLY BE PERMITTED AS SHOWN ON PLANS.
H. ALL REFRIGERANT LINE SETS SHALL BE INSULATED WITH A RMCELL AP ARMAFLEX TUBE INSULATION. TO THE THICKNES S AS
SHOWN IN THE INSULATION THICKNESS SCHEDULES IN THIS SHEET.
I. REFRIGERATION DRAWINGS ARE PROVIDED AS AN AID TO BIDDING AND TO INDICATE DESIRED ROUTING OF REFRIGERATION
LINES. CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR CORRECT INSTALLATION OF PIPING AND ACCESSORIES TO
PROVIDE A COMPLETE AND FULLY OPERATING SYSTEM.
J. PROVIDE 1" CONDENSATE DRAIN PIPE FROM EACH UNIT COO LER TO DRAIN LINE PROVIDED BY PLUMBING. SEE PLUMBIN G
DRAWINGS FOR LOCATION. REFER TO SPECIFICATION FOR P IPE COPPER TYPE.
K. EXACT LOCATION AND LENGTH OF RSL & RLL PIPING RUNS TO EQUIPMENT SHALL BE DETERMINED IN FIELD. FINAL SIZES TO
BE DETERMINED BY FINAL ROUTING.
L. REFRIGERATION CIRCUITS ARE SHOWN AS ONE (1) LINE ON PLANS BUT CONSIST OF BOTH LIQUID AND SUCTION LINES .
M. PROVIDE INTERMEDIATE SUCTION LINE TRAP IN WALL OR V OID SPACE AT THE MIDPOINT OF A SUCTION LINE DROP WH ICH
EXCEEDS 16 FT.
N. AT ALL POINTS WHERE SUCTION LINES RISE 48" OR MORE, PROVIDE A SHORT RADIUS SUCTION LINE TRAP AT THE BA SE OF
THE RISER.
REFRIGERATION GENERAL NOTES:
SCALE: NTSR100
2 VERTICAL REFRIGERANT LINE SUPORT
SCALE: NTSR100
3 MULTIPLE REFRIGERANT LINE TRAPEZE HANGER
SCALE: NTSR100
4 SINGLE SYSTEM INTERMEDIATE SUCTION LINE TRAP
NOTES:
*BASED ON NORMAL DESIGN CONDITIONS OF 85°F AND 70% RH.
EQUIVALENT FEET OF PIPE DUE TO VALVE AND FITTING FR ICTION
COPPER TUBE, O.D., TYPE "L"
GLOBE VALVE (OPEN)
ANGLE VALVE (OPEN)
90° TURN THROUGH TEE
TEE (STRAIGHT THROUGH)
OR SWEEP BELOW
90° ELBOW OR REDUCING
TEE (STRAIGHT THROUGH)
1/2
14
7
3
0.75
1
5/8
16
9
4
1
2
7/8
22
12
5
0.15
2
1-1/8
28
15
6
2
3
1-3/8
36
18
8
2.5
4
1-5/8
42
21
9
3
4
2-1/8
57
28
12
3.5
5
2-5/8
69
34
14
4
7
3-1/8
83
42
17
5
8
3-5/8
99
49
20
6
10
4-1/8
118
57
22
7
12
5-1/8
138
70
28
9
14
6-1/8
168
83
34
11
16
NOTES:
*BASED ON SEVERE DESIGN CONDITIONS OF 90°F AND 80% RH.
INSULATION THICKNESS BASED
ON NORMAL DESIGN
CONDITIONS*
3/8" ID THROUGH 1-1/8" ID
OVER 1-1/8" ID THROUGH 2-1/8" ID
OVER 2-1/8" ID THROUGH 2-5/8" ID
OVER 2-5/8" ID THROUGH 6" IPS
35°F
(2°C)
NOM 1/2"
NOM 1/2"
NOM 1/2"
NOM 3/4"
LINE TEMPERATURE
0°F
(-18°C)
NOM 3/4"
NOM 1"
NOM 1"
NOM 1"
-20°F
(-29°C)
NOM 1"
NOM 1"
NOM 1-1/4"
NOM 1-1/4"
INSULATION THICKNESS BASED
ON SEVERE DESIGN
CONDITIONS*
3/8" ID THROUGH 1-1/8" ID
OVER 1-5/8" ID THROUGH 3-5/8" ID
OVER 3-5/8" ID THROUGH 6" IPS
35°F
(2°C)
NOM 1"
NOM 1"
NOM 1"
LINE TEMPERATURE
0°F
(-18°C)
NOM 1-1/2"
NOM 1-1/2"
NOM 1-1/2"
-20°F
(-29°C)
NOM 1-1/2"
NOM 1-3/4"
NOM 2"
1. PROVIDE AND INSTALL 6'-0" LENGTH OF FLEXIBLE, BRAIDED RSL & RLL AT FBD
DISPENSERS TO ALL UNITS TO BE PULLED FORWARD FOR AC CESS.
2. CONCEAL RSL & RLL VERTICAL DROPS IN WALL.
3. PROVIDE AND INSTALL 3'-0" LENGTH OF FLEXIBLE, BRAIDED RSL & RLL AT
CHILLZONE ICE MAKER TO ALLOW UNITS TO BE PULLED FOR WARD FOR ACCESS.
KEY NOTES:
ALL PRODUCTS ON THIS SCHEDULE ARE FURNISHED BY OWNER AND INSTALLED BY CONTRACTOR
AIR COOLED CONDENSING UNIT SCHEDULE
MARK AREA SERVED MANUFACTURER MODEL
CAPACITY
MBH
ELECTRICAL DATA
REFRIGE
RANT
CON. PIPE SIZE OPERATING
WEIGHT
(LBS)VOLTS PHASE MCA MOCP LIQUID SUCTION
GENERAL NOTES (APPLIED TO ALL UNITS)
1. REFRIGERANT SHALL BE SIZED BY MANUFACTURER'S RECOMM ENDATIONS BASED ON FIELD CONDITIONS.
2. PROVIDE DRYER, SIGHT GLASS AND SUCTION ACCUMULATOR.
3. DISCONNECT TO BE PROVIDED BY ELECTRICAL CONTRACTOR.
C-3
C-4
RCU FOR CHILLZONE ICE
RCU FOR FBD
MANITOWOC ICE
KIRWAN
JCT0500-161
589050
R-410A
R-404A
76
200
5/16"
3/8" 3/8"
1/2"
19
6.9
208V
120V
1
1
12A
2A
15A
15A
REFRIGERATION SCHEDULE
ALL PRODUCTS ON THIS SCHEDULE ARE FURNISHED BY OWNE R AND INSTALLED BY CONTRACTOR
CIRCUIT INFORMATION
CIRCUIT
No.
C-3
C-4
AREA
SERVED
RCU FOR CHILL ZONE ICE
RCU FOR FBD
EVAP
(°F)
-30°
-30°
Est. Dev.
Length (ft)
45
36
PIPE SIZE
Liquid
3/8"
3/8"
Suction
* 1/2"
* 5/8"
MANUFACTURER
MANITOWOC ICE
KIRWAN
MODEL
JCT0500-161
589050
* DISCHARGE LINE FROM COMPRESSOR TO REMOTE CONDENSE R ON ROOF. COMPRESSOR LOCATED INSIDE THE BUILDING.
GENERAL NOTES (APPLIES TO ALL UNITS):
1.
2.
3.
REFRIGERANT PIPING SHALL BE SIZED BY MANUFACTURER'S RECOMMENDATIONS BASED ON FIELD CONDITIONS.
PROVIDE ECM MOTOR
DISCONNECT TO BE PROVIDED BY ELECTICAL SUBCONTRACTO R.
REFRIG-
ERANT
R-410A
R-404A
CFM
EVAPORATOR
CAPACITY
BTU/Hr
6,900
19,000
ELECTRICAL DATA
VOLTS PHASE Watts MCA MOCP
3/8" 5/8"
CON. PIPE SIZE
LIQUID SUCTION
120 1 200 15 30
120 1 200 15 30
02/12/2021
PROJECT NO.:
L
a
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
L
a
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
N
O
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:
\
U
s
e
r
s
\
K
s
w
a
r
t
z
l
a
n
d
e
r
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
RK
_
C
O
_
C
e
n
t
r
a
l
_
K
S
w
a
r
t
z
l
a
n
d
e
r
.
r
v
t
2/
1
1
/
2
0
2
1
9
:
4
6
:
1
0
A
M
12322-034
E001
7
5
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
5
6
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
E
G
A
M
E
R
I
C
A
L
L
C
E
L
E
C
T
R
I
C
A
L
S
P
E
C
I
F
I
C
A
T
I
O
N
S
1
6
5
F
l
a
n
d
e
r
s
R
o
a
d
W
e
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
EXISTING WORK
A. PRIOR TO CONSTRUCTION & INSTALLATION, CONTRACTOR TO VERIFY EXISTING CONDITIONS
AND NOTIFY ARCHITECT/ENGINEER OF CONFLICTS OR CONDITIONS WHICH INTERFERE WITH
INSTALLATION AS SET FORTH IN CONTRACT DOCUMENTS.
B. CONTRACTOR RESPONSIBLE FOR ALL NEW FLOOR OPENINGS, EXCAVATIONS, AND
PENETRATIONS,UNLESS SPECIFICALLY NOTED. UNLESS SPECIFICALLY NOTED, UPON
COMPLETION, ALL PENETRATIONS TO BE SEALED TO MAINTAIN FIRE RATING AS SPECIFIED ON
ARCHITECTURAL DRAWINGS.
C. ALL CUTTING AND PATCHING SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS
CLEARLY INDICATED AS PART OF ANOTHER PRIME CONTRACT.
D. COORDINATE ANY NEW ROOF PENETRATIONS WITH THE OTHER TRADES.
E. REMOVE, RELOCATE, AND EXTEND EXISTING INSTALLATIONS TO ACCOMMODATE NEW
CONSTRUCTION.
F. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND
EXTENSION WORK.
G. MAINTAIN ACCESS TO EXISTING BOXES AND OTHER INSTALLATIONS REMAINING ACTIVE AND
REQUIRING ACCESS. MODIFY INSTALLATION OR PROVIDE ACCESS PANEL.
H. EXTEND EXISTING RACEWAY AND BOX INSTALLATIONS USING MATERIALS AND METHODS
COMPATIBLE WITH EXISTING ELECTRICAL INSTALLATIONS, OR AS SPECIFIED.
I. CLEAN AND REPAIR EXISTING COMPONENTS TO REMAIN OR TO BE REINSTALLED.
J. PROVIDE ACCESS TO EXISTING WIRING CONNECTIONS REMAINING ACTIVE AND REQUIRING
ACCESS. MODIFY INSTALLATION OR INSTALL ACCESS PANEL.
K. EXTEND EXISTING CIRCUITS USING MATERIALS AND METHODS COMPATIBLE WITH EXISTING
ELECTRICAL INSTALLATIONS, OR AS SPECIFIED.
L. RING OUT CIRCUITS IN EXISTING PANEL AFFECTED BY THE WORK. WHERE ADDITIONAL
CIRCUITS ARE NEEDED, REUSE CIRCUITS AVAILABLE FOR REUSE. INSTALL NEW BREAKERS.
M. TAG UNUSED CIRCUITS AS SPARE AND SWITCH BREAKER TO THE "OFF" POSITION.
N. WHERE EXISTING CIRCUITS ARE INDICATED TO BE REUSED, USE SENSING MEASURING
DEVICES TO VERIFY CIRCUITS FEEDING PROJECT AREA OR ARE NOT IN USE.
O. PROVIDE NEW UPDATED DIRECTORIES WHERE MORE THAN THREE CIRCUITS HAVE BEEN
MODIFIED OR REWIRED.
P. IDENTIFY SALVAGE ITEMS IN COOPERATION WITH OWNER. REMOVE AND PROTECT ITEMS TO
BE SALVAGED AND TURN OVER TO OWNER.
Q. CAREFULLY REMOVE EQUIPMENT, MATERIALS, OR FIXTURES WHICH ARE TO BE REUSED.
MINOR ELECTRICAL DEMOLITION
A. DEMOLITION DRAWINGS ARE BASED ON CASUAL FIELD OBSERVATION AND EXISTING RECORD
DOCUMENTS. REPORT DISCREPANCIES TO ARCHITECT/ENGINEER BEFORE DISTURBING
EXISTING INSTALLATION.
B. CEASE OPERATIONS IMMEDIATELY WHEN STRUCTURE APPEARS TO BE IN DANGER AND
NOTIFY ARCHITECT/ENGINEER. DO NOT RESUME OPERATIONS UNTIL DIRECTED.
C. VERIFY WIRING AND EQUIPMENT INDICATED TO BE DEMOLISHED SERVE ONLY ABANDONED
FACILITIES.
D. PROVIDE TEMPORARY EGRESS SIGNAGE AND EMERGENCY LIGHTING.
E. DISCONNECT ELECTRICAL SYSTEMS IN WALLS, FLOORS, AND CEILINGS SCHEDULED FOR
REMOVAL. REMOVE CONDUIT, WIRE, BOXES, AND FASTENING DEVICES TO AVOID ANY
INTERFERENCE WITH NEW INSTALLATION.
F. INSTALL TEMPORARY WIRING AND CONNECTIONS TO MAINTAIN EXISTING SYSTEMS IN
SERVICE DURING CONSTRUCTION.
G. REMOVE EXPOSED ABANDONED WIRE, CABLE, CONDUIT, GROUNDING AND BONDING
COMPONENTS, FASTENERS AND SUPPORTS, AND ELECTRICAL IDENTIFICATION
COMPONENTS, INCLUDING ABANDONED COMPONENTS ABOVE ACCESSIBLE CEILING
FINISHES. CUT EMBEDDED CONDUITS AND SUPPORT ELEMENTS FLUSH WITH WALLS AND
FLOORS. PATCH SURFACES DAMAGED BY REMOVAL OF EXISTING COMPONENTS.
H. DISCONNECT ABANDONED CIRCUITS AND OUTLETS AND REMOVE ABANDONED RACEWAY,
OUTLETS, BOXES, WIRE, AND CABLE INCLUDING ABOVE ACCESSIBLE CEILING FINISHES. CUT
RACEWAY FLUSH WITH WALLS AND FLOORS, AND PATCH SURFACES. REMOVE CONCEALED
ABANDONED RACEWAY TO ITS SOURCE.
I. RECONNECT EQUIPMENT BEING DISTURBED BY RENOVATION WORK AND REQUIRED FOR
CONTINUED SERVICE TO NEAREST AVAILABLE PANEL. REMOVE, RELOCATE, AND EXTEND
EXISTING INSTALLATIONS TO ACCOMMODATE NEW CONSTRUCTION.
J. REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED DURING DEMOLITION AND
EXTENSION WORK.
K. CLEAN AND REPAIR EXISTING EQUIPMENT TO REMAIN (AFFECTED BY THE SCOPE OF THE
PROJECT) OR TO BE REINSTALLED.
L. PROTECT AND RETAIN POWER TO EXISTING ACTIVE EQUIPMENT REMAINING.
M. CAP ABANDONED EMPTY CONDUIT AT BOTH ENDS AND MARK AS SPARE.
RACEWAY AND BOXES
A. PROVIDE RACEWAY AND BOXES LOCATED AS INDICATED, AND AT OTHER LOCATIONS REQUIRED
FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE WITH
REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE LOCATIONS
UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING SYSTEM.
B. UNDERGROUND MORE THAN 5 FEET OUTSIDE FOUNDATION WALL: PROVIDE SCHEDULE 80 PVC.
PROVIDE CAST METAL BOXES OR NONMETALLIC HANDHOLES WHERE REQUIRED.
C. UNDERGROUND WITHIN 5 FEET FROM FOUNDATION WALL: PROVIDE RIGID STEEL CONDUIT OR
THICKWALL NONMETALLIC CONDUIT (SCHEDULE 80 PVC). PROVIDE CAST METAL OR
NONMETALLIC BOXES.
D. IN OR UNDER SLAB ON GRADE: PROVIDE THICK WALL NONMETALLIC CONDUIT. PROVIDE CAST OR
NONMETALLIC METAL BOXES.
E. OUTDOOR LOCATIONS, ABOVE GRADE: PROVIDE RIGID STEEL CONDUIT. PROVIDE CAST METAL
OR NONMETALLIC OUTLET, PULL, AND NEMA-3R RATED JUNCTION BOXES.
F. IN SLAB ABOVE GRADE: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST
NONMETALLIC BOXES.
G. WET AND DAMP LOCATIONS: PROVIDE THICKWALL NONMETALLIC CONDUIT. PROVIDE CAST
METAL OR NONMETALLIC OUTLET, NEMA-3R RATED JUNCTION, AND PULL BOXES. PROVIDE FLUSH
MOUNTING OUTLET BOX IN FINISHED AREAS.
H. CONCEALED DRY LOCATIONS: PROVIDE ELECTRICAL METALLIC TUBING. PROVIDE SHEET-METAL
BOXES. PROVIDE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS. PROVIDE HINGED
ENCLOSURE FOR LARGE PULL BOXES.
I. MINIMUM RACEWAY SIZE: 3/4 INCH UNLESS OTHERWISE SPECIFIED.
J. ARRANGE RACEWAY AND BOXES TO MAINTAIN HEADROOM AND PRESENT NEAT APPEARANCE.
GROUP RELATED RACEWAY; SUPPORT USING CONDUIT RACK; PROVIDE SPACE ON EACH FOR 25
PERCENT ADDITIONAL RACEWAYS.
K. RACEWAY ROUTING IS SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. ROUTE TO
COMPLETE WIRING SYSTEM.
L. DO NOT SUPPORT RACEWAY WITH WIRE, PERFORATED PIPE STRAPS, CEILING SUPPORT WIRES
OR OTHER PIPING SYSTEMS.
M. ROUTE EXPOSED & ABOVE ACCESSIBLE CEILINGS RACEWAY PARALLEL AND PERPENDICULAR TO
WALLS.
N. DO NOT CROSS CONDUITS IN SLAB.
O. INSTALL NO MORE THAN EQUIVALENT OF THREE 90 DEGREE BENDS BETWEEN BOXES. INSTALL
CONDUIT BODIES TO MAKE SHARP CHANGES IN DIRECTION, AS AROUND BEAMS. INSTALL
FACTORY ELBOWS FOR BENDS IN METAL CONDUIT LARGER THAN 2 INCH SIZE.
P. AVOID MOISTURE TRAPS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW POINTS IN
CONDUIT SYSTEM.
Q. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES
SEISMIC, CONTROL AND EXPANSION JOINTS.
R. INSTALL SUITABLE PULL STRING OR CORD IN EACH EMPTY RACEWAY EXCEPT SLEEVES AND
NIPPLES.
S. CLOSE ENDS AND UNUSED OPENINGS IN WIREWAY.
T. INSTALL PULL BOXES AND JUNCTION BOXES ABOVE ACCESSIBLE CEILINGS AND IN UNFINISHED
AREAS ONLY.
U. IN ACCESSIBLE CEILING AREAS: INSTALL OUTLET AND JUNCTION BOXES NO MORE THAN 6 INCHES
FROM CEILING ACCESS PANEL OR FROM REMOVABLE RECESSED LUMINAIRE.
V. LOCATE FLUSH MOUNTING BOX IN MASONRY WALL TO REQUIRE CUTTING OF MASONRY UNIT
CORNER ONLY. COORDINATE MASONRY CUTTING TO ACHIEVE NEAT OPENING.
W. DO NOT INSTALL FLUSH MOUNTING BOX BACK-TO-BACK IN WALLS; INSTALL WITH MINIMUM 6
INCHES SEPARATION. INSTALL WITH MINIMUM 24 INCHES SEPARATION IN ACOUSTIC RATED
WALLS.
X. DO NOT FASTEN BOXES TO CEILING SUPPORT WIRES OR OTHER PIPING SYSTEMS.
Y. SUPPORT BOXES INDEPENDENTLY OF CONDUIT.
Z. USE FLUSH MOUNTING OUTLET BOX IN FINISHED AREAS.
AA. SET FLOOR BOXES LEVEL AND FLUSH WITH FINISH FLOORING MATERIAL
AB. INSTALL CONDUIT TO PRESERVE FIRE RESISTANCE RATING OF PARTITIONS AND OTHER
ELEMENTS.
AC. ROUTE CONDUIT THROUGH ROOF OPENINGS FOR PIPING AND DUCTWORK OR THROUGH
SUITABLE ROOF JACK WITH PITCH POCKET
AD. ALIGN ADJACENT WALL MOUNTED OUTLET BOXES FOR SWITCHES, THERMOSTATS, AND SIMILAR
DEVICES.
GROUNDING SYSTEMS
A. GROUNDING SYSTEM RESISTANCE: 25 OHMS.
B. GROUNDING SYSTEMS:
1. MECHANICAL CONNECTORS: BRONZE CONNECTORS, SUITABLE FOR GROUNDING AND
BONDING APPLICATIONS, IN CONFIGURATIONS REQUIRED FOR PARTICULAR
INSTALLATION.
C. EXOTHERMIC CONNECTIONS: EXOTHERMIC MATERIALS, ACCESSORIES, AND TOOLS FOR
PREPARING AND MAKING PERMANENT FIELD CONNECTIONS BETWEEN GROUNDING SYSTEM
COMPONENTS.
D. WIRE: STRANDED COPPER.
E. GROUNDING ELECTRODE CONDUCTOR: SIZE TO MEET NFPA 70 AND LOCAL MUNICIPALITY
REQUIREMENTS.
F. INSTALLATION:
1. EQUIPMENT GROUNDING CONDUCTOR: INSTALL SEPARATE, INSULATED CONDUCTOR
WITHIN EACH FEEDER AND BRANCH CIRCUIT RACEWAY. TERMINATE EACH END ON
SUITABLE LUG, BUS, OR BUSHING.
2. DO NOT FASTEN SUPPORTS TO PIPES, DUCTS, MECHANICAL EQUIPMENT, OR CONDUIT.
3. OBTAIN PERMISSION FROM ARCHITECT/ENGINEER BEFORE USING POWDER-ACTUATED
ANCHORS OR DRILLING OR CUTTING STRUCTURAL MEMBERS.
HANGERS AND SUPPORTS
A. ANCHORS & FASTENERS TO BE CORROSION RESISTANT.
B. ANCHOR AND FASTEN ELECTRICAL PRODUCTS TO BUILDING ELEMENTS AND FINISHES AS
FOLLOWS:
1. CONCRETE STRUCTURAL ELEMENTS: PROVIDE EXPANSION ANCHORS.
2. STEEL STRUCTURAL ELEMENTS: PROVIDE BEAM CLAMPS AND SPRING STEEL CLIPS.
3. CONCRETE SURFACES: PROVIDE EXPANSION ANCHORS.
4. HOLLOW MASONRY, PLASTER, AND GYPSUM BOARD PARTITIONS: PROVIDE TOGGLE
BOLTS AND HOLLOW WALL FASTENERS.
5. SOLID MASONRY WALLS: PROVIDE EXPANSION ANCHORS.
6. SHEET METAL: PROVIDE SHEET METAL SCREWS.
7. WOOD ELEMENTS: PROVIDE WOOD SCREWS.
C. SUPPORTS:
1. FABRICATE SUPPORTS FROM STRUCTURAL STEEL OR FORMED STEEL MEMBERS. RIGIDLY
WELD MEMBERS OR INSTALL HEXAGON HEAD BOLTS TO PRESENT NEAT APPEARANCE
WITH ADEQUATE STRENGTH AND RIGIDITY. INSTALL SPRING LOCK WASHERS UNDER
NUTS.
2. INSTALL SURFACE MOUNTED CABINETS AND PANELBOARDS WITH MINIMUM OF FOUR
ANCHORS.
3. IN WET AND DAMP LOCATIONS INSTALL STEEL CHANNEL SUPPORTS TO STAND CABINETS
AND PANELBOARDS 1 INCH OFF WALL.
4. INSTALL SHEET METAL CHANNEL TO BRIDGE STUDS ABOVE AND BELOW CABINETS AND
PANELBOARDS RECESSED IN HOLLOW PARTITIONS.
BUILDING WIRE AND CABLE
A. PROVIDE PRODUCTS AS FOLLOWS:
1. SOLID CONDUCTOR FOR FEEDERS AND BRANCH CIRCUITS 10 AWG AND SMALLER.
2. STRANDED CONDUCTORS FOR CONTROL CIRCUITS.
3. CONDUCTOR NOT SMALLER THAN #12 AWG FOR POWER AND LIGHTING CIRCUITS.
4. CONDUCTOR NOT SMALLER THAN #16 AWG FOR CONTROL CIRCUITS.
5. 10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER THAN 75
FEET.
6. 10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER THAN 200
FEET.
B. WIRING METHODS: PROVIDE THE FOLLOWING WIRING METHODS:
1. CONCEALED DRY INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN
INSULATION, IN RACEWAY.
2. ABOVE ACCESSIBLE CEILINGS: USE ONLY BUILDING WIRE, TYPE THHN/THWN
INSULATION, IN RACEWAY.
3. WET OR DAMP INTERIOR LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN
INSULATION, IN RACEWAY.
4. UNDERGROUND LOCATIONS: USE ONLY BUILDING WIRE, TYPE THHN/THWN INSULATION,
IN RACEWAY.
C. WIRE AND CABLE ROUTING INDICATED IS APPROXIMATE UNLESS DIMENSIONED. INCLUDE
WIRE AND CABLE LENGTHS WITHIN 10 FT OF LENGTH SHOWN.
D. COMPLETELY AND THOROUGHLY SWAB RACEWAY BEFORE INSTALLING WIRE.
E. NEATLY TRAIN AND LACE WIRING INSIDE BOXES, EQUIPMENT, AND PANELBOARDS.
F. SPECIAL TECHNIQUES--BUILDING WIRE IN RACEWAY:
1. PULL CONDUCTORS INTO RACEWAY AT SAME TIME.
2. INSTALL BUILDING WIRE 4 AWG AND LARGER WITH PULLING EQUIPMENT.
G. SPECIAL TECHNIQUES - CABLE:
1. PROTECT EXPOSED CABLE FROM DAMAGE.
2. SUPPORT CABLES ABOVE ACCESSIBLE CEILING, USING SPRING METAL CLIPS OR CABLE
TIES TO SUPPORT CABLES FROM STRUCTURE OR CEILING SUSPENSION SYSTEM. DO
NOT REST CABLE ON CEILING PANELS.
3. USE SUITABLE CABLE FITTINGS AND CONNECTORS.
H. SPECIAL TECHNIQUES - DIRECT BURIAL CABLE:
1. TRENCH AND BACKFILL FOR DIRECT BURIAL CABLE INSTALLATION. INSTALL WARNING
TAPE ALONG ENTIRE LENGTH OF DIRECT BURIAL CABLE, WITHIN 3 INCHES OF GRADE.
2. USE SUITABLE DIRECT BURIAL CABLE FITTINGS AND CONNECTORS.
I. SPECIAL TECHNIQUES - WIRING CONNECTIONS:
1. CLEAN CONDUCTOR SURFACES BEFORE INSTALLING LUGS AND CONNECTORS.
2. MAKE SPLICES, TAPS, AND TERMINATIONS TO CARRY FULL AMPACITY OF CONDUCTORS
WITH NO PERCEPTIBLE TEMPERATURE RISE.
3. TAPE UNINSULATED CONDUCTORS AND CONNECTORS WITH ELECTRICAL TAPE TO 150
PERCENT OF INSULATION RATING OF CONDUCTOR.
4. INSTALL SPLIT BOLT CONNECTORS OR MULTI-TAP BLOCKS FOR COPPER CONDUCTOR
SPLICES AND TAPS, 6 AWG AND LARGER.
5. INSTALL SOLDERLESS PRESSURE CONNECTORS WITH INSULATING COVERS FOR
COPPER CONDUCTOR SPLICES AND TAPS, 8 AWG AND SMALLER.
6. INSTALL INSULATED SPRING WIRE CONNECTORS WITH PLASTIC CAPS FOR COPPER
CONDUCTOR SPLICES AND TAPS, 10 AWG AND SMALLER.
7. TERMINATE EXISTING ALUMINUM CONDUCTORS WITH TIN-PLATED, ALUMINUM-BODIED
COMPRESSION CONNECTORS ONLY. FILL WITH ANTI-OXIDANT COMPOUND BEFORE
INSTALLING CONDUCTOR.
8. INSTALL SUITABLE REDUCING CONNECTORS OR MECHANICAL CONNECTOR ADAPTORS
FOR CONNECTING ALUMINUM CONDUCTORS TO COPPER CONDUCTORS.
J. GROUND CONDUCTORS:
1. FOR 6 AWG AND SMALLER: GREEN.
2. FOR 4 AWG AND LARGER: IDENTIFY WITH GREEN TAPE AT BOTH ENDS AND VISIBLE
POINTS INCLUDING JUNCTION BOXES.
K. ALL WIRING SHALL BE #12 CU UNLESS SPECIFIED OTHERWISE.
IDENTIFICATION
A. IDENTIFY ELECTRICAL COMPONENTS AS FOLLOWS:
1. ENGRAVED LAMINATED PLASTIC NAMEPLATE FOR EACH ELECTRICAL DISTRIBUTION,
CONTROL EQUIPMENT ENCLOSURE, AND COMMUNICATION CABINET.
2. CLOTH TYPE WIRE MARKER FOR EACH CONDUCTOR AT PANELBOARD GUTTERS, AND PULL BOXES.
3. RACEWAY MARKER FOR EACH RACEWAY WHERE IT STUBS ABOVE THE CEILING OR BELOW THE
FLOOR.
4. UNDERGROUND WARNING TAPE ALONG LENGTH OF EACH UNDERGROUND RACEWAY OR CABLE,
3" BELOW FINISHED GRADE. TAPE TO BE 4-INCH WIDE PLASTIC TAPE, DETECTABLE TYPE, COLORED
YELLOW WITH SUITABLE WARNING LEGEND DESCRIBING BURIED ELECTRICAL LINES.
PANELBOARDS
A. MANUFACTURERS:
1. EATON/CUTLER-HAMMER.
2. GE ELECTRICAL.
3. SIEMENS/ITE.
4. SQUARE D MODEL.
B. BOLT-ON CIRCUIT BREAKER TYPE, DISTRIBUTION ,LIGHTING AND APPLIANCE BRANCH CIRCUIT PANELBOARD.
C. PANELBOARD BUS: COPPER CURRENT CARRYING COMPONENTS, RATINGS AS INDICATED ON DRAWINGS. FURNISH
COPPER GROUND BUS IN EACH PANELBOARD; FURNISH INSULATED GROUND BUS AS INDICATED ON DRAWINGS.
D. MINIMUM INTEGRATED SHORT CIRCUIT RATING: 22,000 AMPERES RMS SYMMETRICAL FOR 240 VOLT
PANELBOARDS; 65,000 AMPERES RMS SYMMETRICAL FOR 480 VOLT PANELBOARDS.
E. MOLDED CASE CIRCUIT BREAKERS: NEMA AB 1, BOLT-ON TYPE THERMAL MAGNETIC TRIP CIRCUIT BREAKERS,
WITH COMMON TRIP HANDLE FOR ALL POLES, LISTED AS TYPE SWD FOR LIGHTING CIRCUITS, TYPE HACR FOR
AIR CONDITIONING EQUIPMENT CIRCUITS, CLASS A GROUND FAULT INTERRUPTER CIRCUIT BREAKERS AS
INDICATED ON DRAWINGS. DO NOT USE TANDEM CIRCUIT BREAKERS.
F. ENCLOSURE: NEMA PB 1, TYPE 1
G. CABINET BOX: 6 INCHES DEEP, 20 INCHES WIDE FOR 240 VOLT AND LESS PANELBOARDS, 20 INCHES WIDE FOR
480 VOLT PANELBOARDS.
H. CABINET FRONT: SURFACE DOOR-IN-DOOR TYPE, FASTENED WITH HINGE AND LATCH, HINGED DOOR WITH
FLUSH LOCK, METAL DIRECTORY FRAME, FINISHED IN MANUFACTURER'S STANDARD GRAY ENAMEL. OUTER
PANELBOARD TRIMS SHALL COVER ALL LIVE PARTS. SWITCHING DEVICE HANDLES SHALL BE ACCESSIBLE.
I. SURFACE TRIMS SHALL BE SAME HEIGHT AND WIDTH AS BOX. FLUSH TRIMS SHALL OVERLAP THE BOX BY 3/4 OF AN
INCH ON ALL SIDES.
J. INSTALL RECESSED PANELBOARDS FLUSH WITH WALL FINISHES.
K. HEIGHT: 6 FEET TO TOP OF PANELBOARD; INSTALL PANELBOARDS TALLER THAN 6 FEET WITH BOTTOM NO MORE
THAN 4 INCHES ABOVE FLOOR.
L. INSTALL FILLER PLATES FOR UNUSED SPACES IN PANELBOARDS.
M. PROVIDE TYPED CIRCUIT DIRECTORY FOR EACH BRANCH CIRCUIT PANELBOARD PER ARICHTECTURAL ROOM
DESIGNATIONS. REVISE DIRECTORY TO REFLECT CIRCUITING CHANGES TO BALANCE PHASE LOADS.
N. MARK UNUSED CIRCUIT BREAKERS AS SPARE AND SWITCH TO OFF POSITION.
O. MEASURE STEADY STATE LOAD CURRENTS AT EACH PANELBOARD FEEDER; REARRANGE CIRCUITS IN
PANELBOARD TO BALANCE PHASE LOADS TO WITHIN 20 PERCENT OF EACH OTHER. MAINTAIN PROPER PHASING
FOR MULTI-WIRE BRANCH CIRCUITS.
P. LIGHTING PANELBOARDS, 6'-6" FROM FLOOR TO TOP.
WALL PLATES
A. MANUFACTURERS:
1. PASS & SEYMOUR LEGRAND, TAYMAC 20510 (WEATHERPROOF-IN-USE), HUBELL (BELL/RACO), LEVITON, GENERAL ELECTRIC.
B. INSTALL DECORATIVE PLATES ON SWITCH, RECEPTACLE, AND BLANK OUTLETS IN FINISHED AREAS. DECORATIVE COVER PLATE: NYLON.
C. INSTALL JUMBO SIZE PLATES FOR OUTLETS INSTALLED IN MASONRY WALLS. JUMBO COVER PLATE: NYLON.
D. WEATHERPROOF COVER PLATE (RECEPTACLE): IMPACT RESISTANT PLASTIC PLATE WITH HINGED AND GASKETED DEVICE COVER. COVER
TO BE RATED FOR WET LOCATION WHILE IN USE, AND TO BE LOCKABLE.
E. WEATHERPROOF COVER PLATE (SWITCH): GASKETED CAST METAL PLATE WITH HINGED AND GASKETED DEVICE COVER OR LEVER
SWITCH MECHANISM. (P&S CA-31G/HUBBELL/BELL/RACO 5125 OR EQUAL)
F. KITCHEN AREAS: 302/430 STAINLESS STEEL, WEATHERPROOF FOR STARTUPS.
G. INSTALL GALVANIZED (STAMPED) STEEL PLATES ON OUTLET BOXES AND JUNCTION BOXES IN UNFINISHED AREAS, ABOVE ACCESSIBLE
CEILINGS, AND ON SURFACE MOUNTED OUTLETS.
H. INSTALL DEVICES PLUMB AND LEVEL.
I. INSTALL SWITCHES WITH OFF POSITION DOWN.
J. INSTALL RECEPTACLES WITH GROUNDING POLE ON TOP, OR TO THE LEFT (IF MOUNTED HORIZONTALLY.
K. CONNECT WIRING DEVICE GROUNDING TERMINAL TO OUTLET BOX WITH BONDING JUMPER AND BRANCH CIRCUIT EQUIPMENT GROUNDING
CONDUCTOR.
L. CONNECT WIRING DEVICES BY WRAPPING SOLID CONDUCTOR AROUND SCREW TERMINAL. INSTALL STRANDED CONDUCTOR FOR BRANCH
CIRCUITS 10 AWG AND SMALLER. WHEN STRANDED CONDUCTORS ARE USED IN LIEU OF SOLID, USE CRIMP ON FORK TERMINALS FOR DEVICE
TERMINATIONS. DO NOT PLACE BARE STRANDED CONDUCTORS DIRECTLY UNDER DEVICE SCREWS.
M. ADJUST DEVICES AND WALL PLATES TO BE FLUSH AND LEVEL.
HIGH INTENSITY DISCHARGE (HID) BALLASTS
A. MANUFACTURERS:
1. VENTURE LIGHTING INTERNATIONAL INC OPTI-WAVE.
2. ADVANCE TRANSFORMER.
3. OSRAM SYLVANIA.
4. GE/MAGNETEK.
B. PRODUCT DESCRIPTION: ANSI C82.4, HIGH PRESSURE SODIUM, SUITABLE FOR LAMP SPECIFIED WITH UNIVERSAL VOLTAGE.
C. PRODUCT DESCRIPTION: ANSI C82.4 PULSE START METAL HALIDE LAMP BALLAST, SUITABLE FOR LAMP SPECIFIED, WITH UNIVERSAL/MULTI-TAP
VOLTAGE CAPABILITIES. PROVIDE PULSE START SYSTEM, WITH THE BULB AND THE BALLAST AS THE SYSTEM.
FLOURESCENT LAMPS
A. MANUFACTURERS:
1. PHILIPS LIGHTING COMPANY ALTO PLUS, OSRAM SYLVANIA ECOLOGIC, GE LIGHTING ECOLUX
HID LAMPS
A. MANUFACTURERS:
1. VENTURE LIGHTING INTERNATIONAL INC UNI-FORM, PHILIPS LIGHITNG COMPANY, SYLVANIA, GE LIGHTING
B. HID LAMPS TO BE SELF EXTINGUISHING TYPE.
C. HID LAMPS TO MEET FEDERAL STANDARD 21 CFR 1040.30 AND TO HAVE A TWO YEAR WARRANTY.
LED LIGHT FIXTURES
A. MANUFACTURERS:
1. AS SPECIFIED IN LIGHT FIXTURE SCHEDULE.
B. CRI OF 80. CCT OF 4000K
C. RATED LAMP LIFE OF MIN. 50,000 HRS
D. LAMPS DIMMABLE FROM 100 PERCENT TO 0 PERCENT OF MAXIMUM LIGHT OUTPUT
E. INTERNAL DRIVER
F. NOMINAL OPERATING VOLTAGE 120/277V AC
EMERGENCY FLOURESCENT LIGHTING
A. MANUFACTURERS:
1. AS SPECIFIED BY LIGHT FIXTURE SCHEDULE.
B. PRODUCT DESCRIPTION: SELF-CONTAINED INCANDESCENT (HALOGEN) EMERGENCY LIGHTING UNIT, WITH SELF-TEST DIAGNOSTICS.
C. BATTERY: 12 VOLT, NICKEL-CADMIUM TYPE, WITH 1.5 HOUR CAPACITY.
D. BATTERY CHARGER: DUAL-RATE TYPE, WITH SUFFICIENT CAPACITY TO RECHARGE DISCHARGED BATTERY TO FULL CHARGE WITHIN TWELVE
HOURS.
E. LAMPS: 12 WATT MINIMUM, SEALED BEAM TYPE IN NICKEL OR CHROME PLATED STEEL HOUSING.
F. HOUSING: WHITE PLASTIC.
G. INDICATORS: LAMPS TO INDICATE AC ON AND RECHARGING. VOLTMETER TO INDICATE BATTERY VOLTAGE.
H. TEST SWITCH: TRANSFERS UNIT FROM EXTERNAL POWER SUPPLY TO INTEGRAL BATTERY SUPPLY.
I. AIM AND ADJUST LAMP FIXTURES TO PROVIDE OPTIMAL COVERAGE.
EMERGENCY LED LIGHTING
A. MANUFACTURERS:
1. AS SPECIFIED BY LIGHT FIXTURE SCHEDULE.
B. PRODUCT DESCRIPTION: SELF-CONTAINED LED EMERGENCY LIGHTING UNIT, WITH SELF-TEST DIAGNOSTICS.
C. BATTERY: 12 VOLT, NICKEL-CADMIUM TYPE, WITH 1.5 HOUR CAPACITY.
D. BATTERY CHARGER: DUAL-RATE TYPE, WITH SUFFICIENT CAPACITY TO RECHARGE DISCHARGED BATTERY TO FULL CHARGE WITHIN TWELVE
HOURS.
E. HOUSING: WHITE PLASTIC.
F. INDICATORS: LAMPS TO INDICATE AC ON AND RECHARGING. VOLTMETER TO INDICATE BATTERY VOLTAGE.
G. TEST SWITCH: TRANSFERS UNIT FROM EXTERNAL POWER SUPPLY TO INTEGRAL BATTERY SUPPLY.
H. AIM AND ADJUST LAMP FIXTURES TO PROVIDE OPTIMAL COVERAGE.
I. PROVIDE SEPARATE UN-SWITCHED LEG TO ALL EMERGENCY LIGHT FIXTURES CONTAINING EMERGENCY BALLASTS.
EXIT SIGNS
A. MANUFACTURERS:
1. AS SPECIFIED IN LIGHT FIXTURE SCHEDULE.
B. PRODUCT DESCRIPTION: EXIT SIGN FIXTURE, WITH SELF-TEST DIAGNOSTICS.
C. FACE: STENCIL FACE WITH RED LETTERS.
D. DIRECTIONAL ARROWS: UNIVERSAL TYPE FOR FIELD ADJUSTMENT.
E. MOUNTING: AS INDICATED ON DRAWINGS OR UNIVERSAL, FOR FIELD SELECTION.
F. BATTERY: 12 VOLT, NICKEL-CADMIUM TYPE, WITH 1.5 HOUR CAPACITY.
G. BATTERY CHARGER: DUAL-RATE TYPE, WITH SUFFICIENT CAPACITY TO RECHARGE DISCHARGED BATTERY TO FULL CHARGE WITHIN TWELVE
HOURS.
H. LAMPS: LED.
I. INPUT VOLTAGE: 120 VOLTS.
G. POSITION EXIT SIGN DIRECTIONAL ARROWS AS INDICATED ON DRAWINGS.
ENCLOSED SWITCHES
A. MANUFACTURERS:
1. CUTLER-HAMMER.
2. SQUARE D.
3. GE ELECTRICAL.
4. SIEMENS.
B. PRODUCT DESCRIPTION: NEMA KS 1, TYPE HD WITH EXTERNALLY OPERABLE HANDLE INTERLOCKED TO PREVENT
OPENING FRONT COVER WITH SWITCH IN ON POSITION, ENCLOSED LOAD INTERRUPTER KNIFE SWITCH. HANDLE
LOCKABLE IN OFF POSITION, WITH PROVISIONS FOR THREE PADLOCKS.
C. SWITCH MECHANISM: TO BE QUICK-MAKE, QUICK-BREAK SUCH THAT, DURING NORMAL OPERATION OF THE SWITCH,
THE OPERATION OF THE CONTACTS SHALL NOT BE CAPABLE OF BEING RESTRAINED BY THE OPERATING HANDLE
AFTER THE CLOSING OR OPENING ACTION OF THE CONTACTS HAS STARTED.
D. FUSE CLIPS: DESIGNED TO ACCOMMODATE NEMA FU 1, CLASS R, J FUSES.
E. ENCLOSURE: NEMA CONFIGURATION TO MEET CONDITIONS
1. INTERIOR DRY LOCATIONS: TYPE 1.
2. EXTERIOR LOCATIONS: TYPE 3R.
3. INDUSTRIAL LOCATIONS: TYPE 4X.
F. SERVICE ENTRANCE: SWITCHES IDENTIFIED FOR USE AS SERVICE EQUIPMENT ARE TO BE LABELED FOR THIS
APPLICATION. FURNISH SOLID NEUTRAL ASSEMBLY AND EQUIPMENT GROUND BAR.
G. FURNISH SWITCHES WITH ENTIRELY COPPER CURRENT CARRYING PARTS.
H. SWITCH RATING: HORSEPOWER RATED FOR AC AS INDICATED ON DRAWINGS.
I. SHORT CIRCUIT CURRENT RATING: 200,000 RMS SYMMETRICAL AMPERES WHEN USED WITH OR PROTECTED BY
CLASS R OR CLASS J FUSES (30-600 AMPERE SWITCHES EMPLOYING APPROPRIATE FUSE REJECTION SCHEMES).
J. HEIGHT: 5 FEET TO OPERATING HANDLE.
K. INSTALL FUSES FOR FUSIBLE DISCONNECT SWITCHES.
WIRING DEVICES
A. MANUFACTURERS:
1. PASS & SEYMOUR LEGRAND, HUBELL, LEVITON, GENERAL ELECTRIC.
B. PRODUCT DESCRIPTION: NEMA WD 1, HEAVY-DUTY, AC ONLY SPECIFICATION GRADE SWITCH/RECEPTACLE. ALL
DEVICES TO BE SPECIFICATION GRADE OR BETTER.
C. BODY / HANDLE: PLASTIC WITH TOGGLE HANDLE. COLOR TO MATCH WALL FINISHES.
D. RATINGS: MATCH BRANCH CIRCUIT AND LOAD CHARACTERISTICS, MINIMUM 20A.
E. GFCI RECEPTACLE: CONVENIENCE RECEPTACLE WITH INTEGRAL GROUND FAULT CIRCUIT INTERRUPTER TO MEET
REGULATORY REQUIREMENTS.
F. WP RECEPTACLE: (WEATHERPROOF) TO BE GFI PROTECTED.
ELECTRICAL SPECIFICATIONS
A. ALL ELECTRICAL WORK TO CONFORM TO:
1. NFPA 70 (NATIONAL ELECTRIC CODE) - CURRENT VERSION
2. NECA (NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION) - STANDARD OF INSTALLATION
3. NETA ATS (INTERNATIONAL ELECTRICAL TESTING ASSOCIATION) - ACCEPTANCE TESTING
SPECIFICATIONS FOR ELECTRICAL POWER DISTRIBUTION EQUIPMENT AND SYSTEMS.
4. NFPA 72 (NATIONAL FIRE PROTECTION ASSOCIATION - NATIONAL FIRE ALARM CODE).
5. ALL APPLICABLE LOCAL CODES.
B. ALL WORK SHOWN ON THIS DRAWING IS THE RESPONSIBILITY OF THE CONTRACTOR, UNLESS
CLEARLY INDICATED AS PART OF ANOTHER PRIME CONTRACT.
C. PROVIDE TEMPORARY POWER REQUIRED FOR ALL TRADES.
D. MATCH OWNERS EXISTING STANDARD EQUIPMENT.
E. COORDINATE WORK TO MINIMIZE OUTAGE DURATION.
F. OBTAIN ALL REQUIRED PERMITS & INSPECTIONS.
G. PROVIDE FOR ELECTRICAL INSPECTIONS AND SUBMIT REPORTS TO THE OWNER.
H. SUBMIT O&M MANUALS TO OWNER UPON COMPLETION OF WORK.
I. PROVIDE TRAINING SESSION FOR DESIGNATED MAINTENEANCE PERSONNEL.
J. PROVIDE SUBMITTALS FOR ALL ELECTRICAL EQUIPMENT, EXCLUDING WIRE, CONDUIT, AND
FASTENERS.
1. HANDHOLES.
2. PANELBOARDS - SHOP DRAWINGS (INDICATE OUTLINE AND SUPPORT POINT DIMENSIONS,
VOLTAGE, MAIN BUS AMPACITY, INTEGRATED SHORT CIRCUIT AMPERE RATING, CIRCUIT
BREAKER AND FUSIBLE SWITCH ARRANGEMENT AND SIZES) AND CATALOG DATA SHOWING
SPECIFIED FEATURES OF STANDARD PRODUCTS.
3. ENCLOSED SWITCHES - SWITCH RATINGS AND ENCLOSURE DIMENSIONS.
4. DEVICES - MANUFACTURER'S CATALOG INFORMATION SHOWING DIMENSIONS, COLORS, AND
CONFIGURATIONS.
5. LUMINAIRES (INCLUDING EMERGENCY & EXIT FIXTURES) - CATALOG INFORMATION SHOWING
DIMENSIONS, RATINGS, AND PERFORMANCE DATA.
K. SELECT MATERIALS, SIZES, AND TYPES OF ANCHORS, FASTENERS, AND SUPPORTS TO CARRY
LOADS OF EQUIPMENT AND RACEWAY, INCLUDING WEIGHT OF WIRE AND CABLE IN RACEWAY.
SEALING AND FIREPROOFING
A. INSTALL FIRESTOPPING TO MAINTAIN ALL RATINGS AT ALL FIRE SEPARATIONS.
B. FIRE RATED SURFACE:
1. SEAL OPENING AT AS FOLLOWS:
C. INSTALL 12 GAGE STEEL SLEEVE THROUGH OPENING AND EXTENDING BEYOND MINIMUM OF 1 INCH ON EACH SIDE
OF BUILDING ELEMENT.
D. SIZE SLEEVE ALLOWING MINIMUM OF 1 INCH VOID BETWEEN SLEEVE AND BUILDING ELEMENT.
E. PACK VOID WITH BACKING MATERIAL.
F. SEAL ENDS OF SLEEVE WITH UL LISTED FIRE RESISTIVE SILICONE COMPOUND TO MEET FIRE RATING OF
STRUCTURE PENETRATED.
1. WHERE CABLE TRAY, BUS, CABLE BUS, CONDUIT, WIREWAY, OR TROUGH PENETRATES FIRE RATED
SURFACE, INSTALL FIRESTOPPING PRODUCT IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTRUCTIONS.
G. NON-RATED SURFACES:
1. SEAL OPENING THROUGH NON-FIRE RATED ROOF OPENING AS FOLLOWS:
H. INSTALL 12 GAGE STEEL SLEEVE THROUGH OPENING AND EXTENDING BEYOND MINIMUM OF 1 INCH ON EACH SIDE
OF BUILDING ELEMENT.
I. SIZE SLEEVE ALLOWING MINIMUM OF 1 INCH VOID BETWEEN SLEEVE AND BUILDING ELEMENT.
J. INSTALL TYPE OF FIRESTOPPING MATERIAL RECOMMENDED BY MANUFACTURER.
1. EXTERIOR WALL OPENINGS BELOW GRADE: ASSEMBLE RUBBER LINKS OF MECHANICAL SEAL TO SIZE OF
CONDUIT AND TIGHTEN IN PLACE, IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
INTERIOR LUMINAIRES
A. ALL FIXTURES TO BE SPECIFICATION GRADE OR BETTER.
B. PERFORMANCE REQUIREMENTS: FOR AREAS OF ASSEMBLY, SUBMIT POINT-BY-POINT LIGHT LEVEL CALCULATIONS TO VERIFY COMPLIANCE
WITH DESIGN LEVELS.
C. PROVIDE COMPLETE INTERIOR LUMINAIRE ASSEMBLIES, WITH FEATURES, OPTIONS, AND ACCESSORIES AS SCHEDULED.
D. INSTALL SUSPENDED LUMINAIRES USING PENDANTS SUPPORTED FROM SWIVEL HANGERS OR CABLE SUPPORTS. INSTALL PENDANT
LENGTH REQUIRED TO SUSPEND LUMINAIRE AT INDICATED HEIGHT.
E. SUPPORT LUMINAIRES LARGER THAN 2 X 4 FOOT SIZE INDEPENDENT OF CEILING FRAMING.
F. INSTALL SURFACE MOUNTED LUMINAIRES PLUMB AND ADJUST TO ALIGN WITH BUILDING LINES AND WITH EACH OTHER. SECURE TO
PREVENT MOVEMENT.
G. EXPOSED GRID CEILINGS: SUPPORT SURFACE-MOUNTED LUMINAIRES ON GRID CEILING DIRECTLY FROM BUILDING. FASTEN SURFACE
MOUNTED LUMINAIRES TO CEILING GRID MEMBERS USING BOLTS, SCREWS, RIVETS, OR SUITABLE CLIPS.
H. INSTALL RECESSED LUMINAIRES TO PERMIT REMOVAL FROM BELOW.
I. INSTALL RECESSED LUMINAIRES USING ACCESSORIES AND FIRESTOPPING MATERIALS TO MEET REGULATORY REQUIREMENTS FOR FIRE
RATING.
J. INSTALL CLIPS TO SECURE RECESSED GRID-SUPPORTED LUMINAIRES IN PLACE.
K. CONNECT LUMINAIRES TO BRANCH CIRCUIT OUTLETS USING FLEXIBLE CONDUIT. MAXIMUM LENGTH FIXTURE WHIP TO BE 5 FEET.
L. MAKE WIRING CONNECTIONS TO BRANCH CIRCUIT USING BUILDING WIRE WITH INSULATION SUITABLE FOR TEMPERATURE CONDITIONS
WITHIN LUMINAIRE.
M. INSTALL SPECIFIED LAMPS IN EACH LUMINAIRE.
N. AIM AND ADJUST LUMINAIRES TO PROVIDE LIGHT LEVELS CONSISTENT WITH DESIGN.
FLOURESCENT BALLASTS
A. MANUFACTURERS:
1. ADVANCE TRANSFORMER.
2. OSRAM SYLVANIA QUIKTRONIC.
3. GE/MAGNETEK.
B. PRODUCT DESCRIPTION: HIGH FREQUENCY ELECTRONIC BALLAST, INSTANT START, LESS THAN 20 PERCENT THD, SUITABLE FOR LAMPS
SPECIFIED, WITH VOLTAGE TO MATCH LUMINAIRE VOLTAGE.
02/12/2021
ELECTRICAL CONTRACTOR (EC) - GENERAL NOTES:
A. ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE AND OTHER APPLICABLE CODES AND STANDARDS.
B. ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/NOTED
OTHERWISE.
C. INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR AIR CONDITIONING SYSTEMS AS SHOWN/NOTED ON THE
DRAWINGS AND PER OTHER APPLICABLE DRAWINGS/INSTRUCTIONS. REFERENCE MECHANICAL DRAWINGS.
D. WIRE SIZE SHALL BE #12 (MINIMUM) UNLESS OTHERWISE NOTED. WIRE SIZES SMALLER THAN #6 AWG SHALL BE THHN/THWN. #6 AWG WIRE AND
LARGER SHALL BE THW, UNLESS NOTED OTHERWISE.
E. WIRE (CONDUCTOR) COLORS SHALL BE AS PER APPLICABLE CODES.
F. ALL CONDUCTORS SHALL BE COPPER.
G. ALL CONDUCTORS SHALL BE RUN IN CONDUIT, EXCEPT LOW VOLTAGE CONTROL AND COMMUNICATIONS CABLES.
H. ALL MATERIALS SHALL BE UL APPROVED.
I. ALL BRANCH CIRCUITS, EXCEPT INTERIOR LIGHTING, EXTERIOR BUILDING SIGNS, PARAPET LIGHTING AND SOFFIT LIGHTING TO HAVE A GREEN
EQUIPMENT GROUNDING CONDUCTOR SIZED AS PER NEC 250-122.
J. PVC (SCHEDULE 40) PERMITTED BELOW SLAB AND BELOW GRADE ONLY.
K. IT IS INTENDED THAT AN EQUIPMENT GROUND CONDUCTOR (GREEN) SHALL BE RUN IN POWER CIRCUIT CONDUITS WHETHER OR NOT THE
CONDUIT IS PVC.
L. ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRING.
M. NEW TYPEWRITTEN PANEL DIRECTORY SHALL BE FURNISHED AFTER JOB IS COMPLETED REFLECTING ALL AS BUILT CONDITIONS.
N. ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
O. ALL DATA EQUIPMENT TO BE FED BY A DEDICATED CIRCUIT WHICH CONSISTS OF A POWER CIRCUIT THAT FEEDS THIS TYPE OF EQUIPMENT ONLY
WITH A SEPARATE GREEN GROUNDING CONDUCTOR CARRIED ALL THE WAY BACK TO THE PANEL TO BE CONNECTED TO THE GROUNDING
SYSTEM.
P. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
Q. EC SHALL VERIFY INTERIOR DECOR THEME TO BE USED AND COORDINATE WITH SAID THEME.
R. EC SHALL INSTALL AND CONNECT WIRING TO ALL SIGNS.
S. EC TO COORDINATED ROUGHING-IN TO ALL EQUIPMENT WITH EQUIPMENT SUPPLIER PRIOR TO INSTALLING CONDUITS.
T. ALL CONDUIT RUNS TO KITCHEN EQUIPMENT SHALL BE RUN ABOVE CEILING.
U. MAINTAIN 12" CLEARANCE BETWEEN P.O.S. COMMUNICATION CONDUITS AND LIGHTING FIXTURES AS WELL AS POWER CONDUITS..
V. CUTTING AND NOTCHING OF 2x4 BEARING WALL FRAMING NOT TO EXCEED 7/8". BORING HOLES IN 2x4 BEARING WALL FRAMING NOT TO EXCEED 2
1/8".
NOTE:
GFCI RECEPTACLES ARE
REQUIRED PER CURRENT
NEC CODES.
A
B
NEMA L6-30R: 215V/245V, 30A, 2-POLE 3 WIRE GROUNDING
NEMA L14-50R: 120V/240V, 50A, 2-POLE 3 WIRE GROUNDING
REF: SHEET A151 FOR ADDITIONAL ELECTRICAL INFORMATION.
SPECIAL RECEPTACLE LEGEND
C NEMA 6-30P: 215V/245V, 30A, 2-POLE 3 WIRE GROUNDING
NEMA 5-15P: 115V/120V, 20A, 1-POLE 3 WIRE GROUNDING
NOTES:
1.PROVIDE CIRCUIT TO NEAREST AVAILABLE PANEL WITH SPACE
AND CAPACITY.
2.METER PANEL TO ENSURE THAT PANEL WILL BE LOADED TO
LESS THAN 80% OF CAPACITY ONCE NEW LOADS ARE ADDED.
CU-3 CU-4
30A/NF/2P3W30A/NF/2P3W
WP
E1
C10
C12AC9
F8
F7
C27
E10
E4
F10
F2
(x2)
F5
B15
C4
C6
EXISTING ELECTRICAL PANELS
ARE EXISTING TO REMAIN
1
C C
C1
C7
A
B
B
B
90" AFF
48" AFF
48" AFF
18" AFF
48" AFF
________________________________
E501
9
T
T
GROUND CONDUCTOR REQUIRED IN ALL CONDUITS
SUBSCRIPT INDICATES PANEL AND CIRCUIT NO.
GROUND FAULT CIRCUIT INTERRUPTING
CONDUIT RUN WITH ARROW DENOTING HOMERUN.
BUT NOT INDICATED
WEATHERPROOF
ABOVE FINISHED FLOOR.
ISOLATED GROUND
A.F.F.
I.G.
W.P.
GFCI
A-3
SINGLE RECEPTACLE HUBBELL #5361-I
TOGGLE SWITCH - SINGLE POLE HUBBELL #1221-I
TELEPHONE OUTLET WITH BUSHED HOLE COVERPLATE
DUPLEX RECEPTACLE HUBBELL #5362-I
208V, 3∅ - #8420
208V, 1∅ - #5352-I
TRANSFORMER
REAR DOOR ALARM
208V RECEPTACLE HUBBELL
BUZZER / BELL
JUNCTION OR GANG BOX
CABLE TELEVISION OUTLET
PUSHBUTTON SWITCH
ABBREVIATIONS
SYMBOL LEGEND
DETAIL DESCRIPTION
T
J
SYMBOL DESCRIPTION
LEGEND
NEW EQUIPMENT/CASEWORK TAG
RE: A151
XX
EXISTING EQUIPMENT/CASEWORK TAG
RE: A151
NOTE: EC TO VERIFY EXISTING
REQUIREMENTS AND CAPTURE EXISTING
CIRCUITS IF AVAILABLE OR INSTALL NEW
AS REQUIRED.
XX
PROJECT NO.:
L
a
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
L
a
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
N
O
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:
\
U
s
e
r
s
\
K
s
w
a
r
t
z
l
a
n
d
e
r
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
RK
_
C
O
_
C
e
n
t
r
a
l
_
K
S
w
a
r
t
z
l
a
n
d
e
r
.
r
v
t
2/
1
1
/
2
0
2
1
9
:
4
6
:
1
1
A
M
12322-034
E110
7
5
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
5
6
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
E
G
A
M
E
R
I
C
A
L
L
C
P
O
W
E
R
P
L
A
N
1
6
5
F
l
a
n
d
e
r
s
R
o
a
d
W
e
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
SCALE:3/16" = 1'-0"E110
1 POWER PLAN
1. PROVIDE 20AMP 120VOLT 1 PHASE CIRCUIT TO NEAREST AVAILABLE PANEL WITH
SPACE AND CAPACITY. CONTRACTOR SHALL METER PANEL TO ENSURE THAT
PANEL WILL BE LOADED TO LESS THAN 80% OF CAPACITY ONCE NEW LOAD IS
ADDED. CIRCUITING SHALL BE 2#12 & 1#12 GROUND IN 3/4" CONDUIT.
KEY NOTES:
02/12/2021
INTAKE GRILLE
EXHAUST FAN CABINET
CONNECTING DUCTWORK
EXHAUST GRILLE W/WALL CAP AND
INSECT SCREEN
SCALE: NTS
CONDUIT PENETRATION
E501
1
SCALE: NTS
BUCK BOOST TRANSFORMER FOR FBD
E501
2
SCALE: NTS
CONDUIT MOUNTING
E501
3
SCALE: NTS
WATER TIGHT CONDUIT PENETRATION
E501
5
SCALE: NTS
TYPICAL WALL-MOUNTED QUAD
E501
6
SCALE: NTS
CONDUIT ROOF PENETRATION
E501
7
ANCHOR
CONDUIT
FINISHED
GRADE
2"
WATERTIGHT
MECHANICAL
SEAL AS SPECIFIED
WATER STOP
BOLTS WITH
CONCRETE
INSERTS (TYP)
12"
STRUCTURAL
FLOOR SLAB
GALVANIZED STEEL
SLEEVE, DIAMETER AS
REQUIRED BY SEAL
MANUFACTURER
5" MIN.CONDUIT CLAMP, SIZE
AS REQURIED (TYP)
9" MIN.
NOTE:
1. EC TO VERIFY ALL PENETRATION METHODS WITH ROOF MANUFACTURER.
PLASTIC END CAPS
(TYP)
1" MIN. 1" (TYP)
TRAPEZE MOUNTED
TO NEXT
OUTLET
OR PANEL
(TYP)
HUNG CEILING
3/4" CONDUIT TO ABOVE HUNG
CEILING 2#12,1#12GND BY
ELECTRICAL CONTRACTOR
1/2" MIN. FULL
THREADED ROD
(TYP)
CHANNEL
UNISTRUT
P1001 OR EQUAL
JAMB NUT & FLAT
PLATE FITTING (TYP)
MAX
.
3"
(TYP)
WALL MOUNTED
CONDUIT CLAMP, SIZE
AS REQUIRED (TYP)
GALVANIZED
MACHINE
SCREW AND
CONCRETE
INSERT
CEILING OR WALL MOUNTED
CONCRETE INSERT
6" MIN.
GENERIC ROOF
CONSTRUCTION
ACTUAL
CONDITIONS WILL
VARY
NON-SHRINK
GROUT (2"
THICK)
4"
4"
2 PLY
BITUMINOUS
STRIPPING
CHANNEL,
UNISTRUT
P1001 OR EQUAL
1" (TYP)
CONDUIT
CAST MALLEABLE IRON
SPACER AND ONE HOLE
STRAP
POURABLE
SEALANT
(2" THICK)
16OZ LEAD COATED COPPER
PITCH POCKET, SOLDER ALL
JOINTS, SET IN BED OF
MASTIC
PRESSURE TREATED WOOD
BLOCKING TO MATCH
INSULATION THICKNESS (TYP)
SLOPE
DISTANCE OF BUCK-BOOST:
FROM 0' TO 50'-0" MAX
2#10, 1#10GND, 3/4" C
DISTANCE OF BUCK-BOOST:
FROM 50'-0" TO 100'-0"MAX.
2#8, 1#8GND, 3/4" C
WATERTIGHT
SEAL
AS SPECIFIED
BRICK OR CMU WALL
(1) DEDICATED
CIRCUIT
PER BUCK-BOOST
REFER TO E110
FOR CIRCUIT #
(1) SPECIALTY
OUTLET
PER FBD
NEMA L630P
CHILLZONE
FROZEN
BEVERAGE
DISPENSER
(FBD)℄
CPI PANEL
REFER TO A150
FOR FBD
QUANTITIES AND
LAYOUT.
CONDUIT
GROUT SLEEVE IN A
NEAT
AND WORKMANLIKE
MANNER
WITH SMOOTH
SURFACES
RECEIVING/
UTILITY
(1) BUCK-BOOST
TRANSFORMER PER
FBD MACHINE.
MANUF:ACME
MODEL:T-1-81051
PROVIDED BY CFI;
INSTALLED BY
GC/ELECTRICAL
CONTRACTOR.
TO BE INSTALLED
DIRECTLY ABOVE CPI
CABINET.
OPENING IN BRICK OR
CMU SHALL HAVE
EDGES
AS SMOOTH AND
STRAIGHT AS
POSSIBLE
PVC SLEEVE WITH
WATERSTOP,
DIAMETER AS
REQUIRED BY SEAL
MANUFACTURER
PACK AND SEAL
4
'
-
0
"
SEQUENCE OF OPERATION
RANCO
ETC-11200
WRAP 3/8" WIDE PLASTIC
STRIP AROUND SENSOR AND
FASTEN TO CEILING CONTROL
CABLE
8'-0" SOFFIT
TEMP
SENSOR
7'-2" AFF
MILLWORK
FILLER PANEL
FLOOR
MILLWORK FILLER PANEL
INTERIOR
WALL
PARTITION
WALL THERMOSTAT BY OTHERS.
PLACE AT 6" BELOW CEILING. SEE
M100 FOR LOCATION. SET POINT
80°F (ADJ)
OVEN
REMOTE HEAT SPACE
TEMPERATURE SENSOR
BELOW SOFFIT.
OUTPUT
CONTROL CABLE
WRAP 3/8" WIDE
PLASTIC STRIP
AROUND SENSOR
AND FASTEN TO
CEILING
T
8'-0" SOFFIT
TS
WALL THERMOSTAT AS SHOWN ON
PLANS. PLACE AT 6" BELOW CEILING.
EXHAUST FAN SHALL BE CONTROLLED BY SPACE THERMOSTAT. THE EXHAUST FAN
SHALL ENERGIZE AND RUN AS NEEDED TO SATISFY SPACE THERMOSTAT SETPOINT.
THERMOSTAT SETTING SHALL BE DETERMINED BY EG/CUMBERLAND FARMS.
TRUSS
TO
EF-1
RUN CONTROL CABLE
IN CONDUIT
APPLICATION TABLE
EXHAUST FAN
EF-1
T
WALL THERMOSTAT AS
SHOWN ON PLANS. PLACE
6" BELOW CEILING TS
REMOTE HEAT SPACE
TEMPERATURE SENSOR
EF-1
STYLEDUCT SIZE
AIR DEVICE SCHEDULE
NOTESSYM.SIZE TYPE
GENERAL NOTES:
ALL ALUMINUM CONSTRUCTION.
EG-1 EXHAUST AIR 12"∅24X24 OWNWER PROVIDED REMOVABLE FILTER
12"ø/ 320
EG-1
8"ø
12"ø 8"ø
EF-1
CONTRACTOR TO PROVIDE AND INSTALL
EXHAUST FAN AND DUCT ABOVE CEILING.
PENATRATE VENT THROUGH EXTERIOR
WALL AVOIDING EXISTING CONDUIT AND
WIRING. REF: DETAIL 9/E501
T
PROVIDE AND INSTALL NEW WALL
THERMOSTAT WHERE INDICATED.
PROJECT NO.:
L
a
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
Ar
c
h
i
t
e
c
t
s
E
n
g
i
n
e
e
r
s
S
u
r
v
e
y
o
r
s
SHEET NO.:
1
0
0
0
C
o
m
m
e
r
c
e
P
a
r
k
D
r
i
v
e
S
u
i
t
e
2
0
1
W
i
l
l
i
a
m
s
p
o
r
t
,
P
A
1
7
7
0
1
P
H
O
N
E
5
7
0
.
3
2
3
.
6
6
0
3
T
O
L
L
F
R
E
E
8
7
7
.
3
2
3
.
6
6
0
3
F
A
X
5
7
0
.
3
2
3
.
9
9
0
2
w
w
w
.
l
a
r
s
o
n
d
e
s
i
g
n
g
r
o
u
p
.
c
o
m
L
a
r
s
o
n
D
e
s
i
g
n
G
r
o
u
p
It is a violation of the law for any
person, unless acting under the
direction of a licensed Architect,
Engineer or Land Surveyor, to
alter an item in any way. Plans,
maps, specifications, studies,
and reports not containing a red
ink seal imprint on the cover
sheet accompanied by an
original signature by the licensed
professional may have been
fraudulently altered and shall
not be considered an original
copy. Copyright Protected 2021,
Larson Design Group.
R
N
O
.
D
A
T
E
C
O
M
M
E
N
T
S
B
Y
C
H
K
D
IS
S
U
E
/
R
E
V
I
S
I
O
N
S
D:
\
U
s
e
r
s
\
K
s
w
a
r
t
z
l
a
n
d
e
r
\
D
o
c
u
m
e
n
t
s
\
E
G
_
7
5
0
8
2
8
_
E
S
T
A
S
-
P
A
RK
_
C
O
_
C
e
n
t
r
a
l
_
K
S
w
a
r
t
z
l
a
n
d
e
r
.
r
v
t
2/
1
1
/
2
0
2
1
9
:
4
6
:
1
3
A
M
12322-034
E501
7
5
0
8
2
8
E
s
t
e
s
P
a
r
k
,
C
O
5
6
1
B
I
G
T
H
O
M
P
S
O
N
A
V
E
.
,
E
S
T
E
S
P
A
R
K
,
C
O
8
0
5
1
7
E
G
A
M
E
R
I
C
A
L
L
C
E
L
E
C
T
R
I
C
A
L
D
E
T
A
I
L
S
1
6
5
F
l
a
n
d
e
r
s
R
o
a
d
W
e
s
t
b
o
r
o
u
g
h
,
M
A
0
1
5
8
1
SCALE:12" = 1'-0"E501
4 CEILING EXHAUST VENT DETAIL
EXHAUST FAN SCHEDULE
MARK MANUFACTURER MODEL #
FAN ELECTRICAL
WEIGHT NOTES/
ACCESSORIESCFM (TOTAL) T.S.P ("WC)
FAN
WATTS VOLTAGE
EF-1 FANTECH
NOTES:
1. UPON START-UP VERIFY THAT THE EXHAUST FAN CURRENT SENSOR IS SET TO THE MOTOR AMPERAGE. IF IT IS NECESSARY TO ADJUST THE
AMPERAGE OF THE EXHAUST HOOD FAN MOTOR, THE FAN MOTOR CURRENT SENSOR MUST BE RESET BY THE ELECTRICAL CONTRACTOR AS
FOLLOWS: ADJUST UNDERCURRENT POTENTIOMETER TO MINIMUM (CLOCKWISE IS MAXIMUM.) APPLY CURRENT. ONCE CURRENT IS
STABILIZED, INCREASE UNDERCURRENT POT UNTIL RED LED LIGHTS. WITHIN SEVEN SECONDS TURN DOWN UNTIL RED LIGHT TURNS OFF. IF A
LIGHT REMAINS ON FOR MORE THAN TEN SECONDS, DISCONNECT SUPPLY VOLTAGE TO RESET. SEE MANUFACTURERS
OPERATION-INSTALLATION INSTRUCTIONS THAT SHIP WITH THE FAN. WITH LIMITED BUILDING PRESSURE, THE ±10% TOLERANCE IS NOT
ACCEPTABLE. SET CFM AS SPECIFIED. ENSURE THAT EXHAUST FAN PULLEY IS ADJUSTED FOR PROPER ALIGNMENT.
SCALE:12" = 1'-0"E501
8 OVEN EXHAUST FAN
SCALE:3/8" = 1'-0"E501
9 OVEN EXHAUST PLAN
02/12/2021