Loading...
HomeMy WebLinkAboutREPORT Test Adjust Balance Harmony B-9494 1600 Fish Hatchery 2015-07-13 Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave., Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 CERTIFIED TEST, ADJUST, AND BALANCE REPORT DATE 7/13/15 PROJECT Harmony Foundation, Inc. Admissions/Detox & Dining Hall 1600 Fish Hatchery Road Estes Park, CO ARCHITECT BASIS Architecture, P.C. 1692 Big Thompson Ave., Unit 100 Estes Park, CO ENGINEER The CE Group 400 Remington Street, Suite A Ft. Collins, CO CONTRACTOR Academy Heating & Cooling 4562 Denrose Court, Unit 5 Fort Collins, CO Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 – Eaton, CO 80615 Phone (970) 454-5351 – Fax (970) 454-5391 PROJECT: Harmony Foundation, Inc. Admissions/Detox & Dining Hall ADDRESS: 1600 Fish Hatchery Road Estes Park, CO The data presented in this report is an exact record of the system performance and was obtained in accordance with NEBB Standard Procedures. Any variances from design quantities which exceed NEBB tolerances are noted throughout the report. The air distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:7/13/15 The hydronic distribution systems have been tested & balanced and final adjustments have been made in accordance with NEBB “Procedural Standards for Testing, Adjusting & Balancing of Environmental Systems” and the project specifications. NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. REG. NO.: 2389 CERTIFIED BY: David C. Reichel DATE:7/13/15 SUBMITTED & CERTIFIED BY NEBB TAB FIRM: Lawrence H. Finn & Associates, Inc. TAB SUPERVISOR: David C. Reichel REG. NO.: 2389 SIGNATURE: DATE: 7/13/15 CERTIFICATION EXPIRATION DATE: 3/31/2016 Table of Contents Instrument Calibration Report Abbreviation Report Roof Top Unit - Admissions / Detox Fan Unit - Admissions / Detox Duct Traverse - Admissions / Detox Roof Top Unit - Dining Hall Fan Unit - Dining Hall Kitchen Hood - Dining Hall Prints - Admissions / Detox Prints - Dining Hall 2 3 4 22 29 31 35 41 43 53 Page 1 of 61 Project: Harmony Foundation, Inc. - Admissions/Detox & Dining Hall Manufacturer Model Serial Application Cal. Date Alnor HM-680 70552109 Hydronic Press. & Diff. Press. 1/16/2014 Alnor HM-680 70750150 Hydronic Press. & Diff. Press. 10/24/2013 Alnor HM-680 70838501 Hydronic Press. & Diff. Press. 4/18/2014 Alnor HM-680 71021246 Hydronic Press. & Diff. Press. 8/27/2013 Alnor HM-680 71043011 Hydronic Press. & Diff. Press. 6/10/2015 Alnor HM-680 91139097 Hydronic Press. & Diff. Press. 4/10/2015 Cooper SH66A 92711016 Temperature 4/10/2015 Extech 461895 Q394479 Rotation Measurement 4/15/2014 Extech 461895 Q083481 Rotation Measurement 1/9/2014 Extech 461895 Q247569 Rotation Measurement 3/26/2014 Extech 461895 Q331990 Rotation Measurement 11/4/2014 Extech 461895 Q477125 Rotation Measurement 3/26/2014 Extech 461895 Q477126 Rotation Measurement 8/29/2013 Extech 461895 Q527632 Rotation Measurement 4/8/2015 Extech 461895 Q590099 Rotation Measurement 9/23/2014 Extech RH390 9099221 Temperature / Humidity 4/9/2015 Fluke 335 96960004 Electrical Measurement 3/25/2014 Fluke 335 89352454 Electrical Measurement 1/9/2014 Fluke 336 97110539R Electrical Measurement 8/27/2013 Fluke 336 97110538R Electrical Measurement 3/26/2014 Fluke 335 92008180 Electrical Measurement 11/4/2014 Fluke 374 15460133 Electrical Measurement 4/18/2014 Fluke 374 20030351 Electrical Measurement 4/8/2015 Fluke 374 20030354 Electrical Measurement 9/23/2014 Shortridge ADM-860C M05789 Digital Manometer 1/17/2014 Shortridge ADM-860C M06821 Digital Manometer 5/2/2014 Shortridge ADM-860C M07352 Digital Manometer 4/7/2015 Shortridge ADM-860C M09123 Digital Manometer 8/27/2013 Shortridge ADM-860C M09134 Digital Manometer 5/4/2014 Shortridge ADM-860C M09347 Digital Manometer 3/26/2014 Shortridge ADM-860C M10144 Digital Manometer 11/18/2014 Shortridge ADM-860C M10371 Digital Manometer 4/2/2014 Shortridge ADM-860C M11448 Digital Manometer 8/6/2014 Shortridge HDM-300 W02060 Hydronic Press. & Diff. Press. 5/13/2014 Shortridge HDM-250 W09198 Hydronic Press. & Diff. Press. 9/26/2014 Shortridge HDM-250 W98020 Hydronic Press. & Diff. Press. 4/8/2015 REMARKS: Not all equipment shown was used on this project. Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 INSTRUMENT CALIBRATION REPORT Page 2 of 61 Project: Harmony Foundation, Inc. - Admissions/Detox & Dining Hall Symbol Description Symbol Description A Airflow (L/S) NS Not Shown AF Air Foil NT No Information Tag ANA Access Not Available OD Outside Diameter BI Backward Incline RPM Revolution Per Minute CD Ceiling Diffuser SD Supply Diffuser CFM Airflow (Cubic Feet / Minute) SNKL Snorkel DD Direct Drive SP Static Pressure Des Design SPD Static Pressure Drop DWDI Double Width Double Inlet SR Supply Register EF Exhaust Fan SWSI Single Width Single Inlet EG Exhaust Grille T Temperature ( C ) ER Exhaust Register T Temperature ( F ) ESP External Static Pressure TSP Total Static Pressure FC Forward Curve VFD Variable Frequency Drive GPM Waterflow (Gallons / Minute) VS Variable Speed HC Heat Coil W Waterflow (L/S) HER Heat Exchanger HRC Heat Recovery Hz Hertz ID Inside Diameter In. WC Inches of Water Column NA Not Applicable NI Not Installed NIC Not In Contract NM Not Measurable NPT No Pressure Tap NR Not Readable REMARKS: Lawrence H. Finn & Associates, Inc. 55 S. Elm Ave, Suite 220 - Eaton, CO 80615 Phone (970) 454-5351 - Fax (970) 454-5391 ABBREVIATION REPORT Page 3 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: July 10, 2015 SYSTEM/UNIT: RTU-01 AREA: Tested By: Joe Castanon Unit Data Unit Manufacturer Trane Unit Model Number YHD240F3RVA030HE1A1A Unit Serial Number 144610526D Unit Discharge Vertical/Down RTU-01 / Supply Fan Fan Type Forward Curve Fan Size 14" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Plenum RTU-01 / Filter Bank Filter Manufacturer Airguard Filter Type Pleated Filter Quantity 12 Filter Size 20x20x2 Starter Data RTU-01 / Supply Fan Installed Thermal VFD Test Data Total CFM Design 9000 CFM Total CFM Actual 9113 CFM Outside Air CFM Design 2550 CFM Outside Air CFM Actual 2611 CFM Return Air CFM Design 6450 CFM Return Air CFM Actual 6502 CFM RTU-01 / Supply Fan Fan RPM Actual 896 RPM Motor Volts 1 212 Volts Motor Volts 2 212 Volts Motor Volts 3 211 Volts Motor Amps 1 15.0 Amps Motor Amps 2 15.1 Amps Motor Amps 3 15.1 Amps VFD Speed 60.0 HZ Motor Data RTU-01 / Supply Fan Motor Manufacturer Marathon Motor Frame 184TZ Motor HP 7.5 HP Motor RPM 3470 RPM Motor Rated Volts 208-230 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 20-17.6 Amps Motor Service Factor 1.15 Nominal Efficiency 87.5 % Power Factor 90.5 Sheave Data RTU-01 / Supply Fan Motor Sheave Make Browning Motor Sheave Model VP56 Motor Sheave Diam.5-1/4 in. Motor Sheave Bore 1-1/8 in. Motor Operating Diameter 4-1/2 in. Fan Sheave Make Browning Fan Sheave Model Fixed Fan Sheave Diam.19 in. Fan Sheave Bore 1-3/16 in. Number of Belts 1 Belt Size BX81 Sheave Center Line 21 in. Test Pressures Fan SP In Actual -0.52 in. wc Fan SP Out Actual 0.91 in. wc OA Damper Pos Actual 30 % RA Damper Pos Actual 70 % Unit External SP Design 1.0 in. wc Unit External SP Actual 1.02 in. wc Filter/Coil SP In -0.11 in. wc Filter/Coil SP Out -0.52 in. wc 9-Jun-15 Duct SP setpoint = 0.7 in. H20 RTU-01 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 4 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-1A AREA: Men's Sleeping Area Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF06 VAV Address 8 Box Inlet Size 6 In. K Factor - 1 0.85 Fan Des. Volts 115 Fan Des. Amps 4.5 Term Box Test Data Max Des. CFM 225 CFM Max Act. CFM 463 CFM Min Des. CFM 34 CFM Min Act. CFM 35 CFM Heat Des. CFM 225 CFM Heat Act. CFM 462 CFM Act. Fan Volts 123 Act. Fan Amps 0.4 Fan Des. CFM 225 CFM Fan Act. CFM 463 CFM Fan Act. RPM 1 % RTU-01 / FT-1A Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Men's Sleeping Area D 8x6Outlet-01 20915720975157 Men's Sleeping Area D 8x6Outlet-02 20315220375152 Men's Sleeping Area D 8x6Outlet-03 20515420575154 ----- 225 463 463Totals : 206 %206 % 22-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-1A Joe Castanon* Notes Final Report L.H. Finn and Associates Page 5 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-1B AREA: Women's Sleeping Area Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF06 VAV Address 9 Box Inlet Size 6 In. K Factor - 1 0.87 Fan Des. Volts 115 Fan Des. Amps 4.5 Term Box Test Data Max Des. CFM 225 CFM Max Act. CFM 497 CFM Min Des. CFM 34 CFM Min Act. CFM 35 CFM Heat Des. CFM 225 CFM Heat Act. CFM 497 CFM Act. Fan Volts 123 Act. Fan Amps 0.4 Fan Des. CFM 225 CFM Fan Act. CFM 497 CFM Fan Act. RPM 1 % RTU-01 / FT-1B Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Women's Sleeping Area D 8x6Outlet-01 22717022775170 Women's Sleeping Area D 8x6Outlet-02 21716321775163 Women's Sleeping Area D 8x6Outlet-03 21916421975164 ----- 225 497 497Totals : 221 %221 % 20-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-1B Joe Castanon* Notes Final Report L.H. Finn and Associates Page 6 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-1C AREA: Exam Room Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF06 VAV Address 13 Box Inlet Size 6 In. K Factor - 1 0.70 Fan Des. Volts 115 Fan Des. Amps 4.5 Term Box Test Data Max Des. CFM 175 CFM Max Act. CFM 224 CFM Min Des. CFM 27 CFM Min Act. CFM 30 CFM Heat Des. CFM 175 CFM Heat Act. CFM 224 CFM Act. Fan Volts 123 Act. Fan Amps 0.4 Fan Des. CFM 175 CFM Fan Act. CFM 224 CFM Fan Act. RPM 1 % RTU-01 / FT-1C Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Conference Room A 24x24Outlet-01 127127196100196 Exam Room A 24x24Outlet-02 12997817561 ----- 175 257 224Totals : 147 %128 % 18-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-1C Joe Castanon* Notes Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-1D AREA: Staff Lounge Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF06 VAV Address 17 Box Inlet Size 6 In. K Factor - 1 0.90 Fan Des. Volts 115 Fan Des. Amps 4.5 Term Box Test Data Max Des. CFM 225 CFM Max Act. CFM 224 CFM Min Des. CFM 34 CFM Min Act. CFM 35 CFM Heat Des. CFM 225 CFM Heat Act. CFM 224 CFM Act. Fan Volts 123 Act. Fan Amps 1.3 Fan Des. CFM 225 CFM Fan Act. CFM 224 CFM Fan Act. RPM 1 % RTU-01 / FT-1D Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Staff Lounge A 24x24Outlet-01 100224124225280 ----- 225 280 224Totals : 124 %100 % * Notes Final Report L.H. Finn and Associates Page 7 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 22, 2015 SYSTEM/UNIT: RTU-01 / FT-2A AREA: Men's Bathroom Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF08 VAV Address 5 Box Inlet Size 8 In. K Factor - 1 1.05 Fan Des. Volts 115 Fan Des. Amps 6.5 Term Box Test Data Max Des. CFM 375 CFM Max Act. CFM 442 CFM Min Des. CFM 57 CFM Min Act. CFM 58 CFM Heat Des. CFM 375 CFM Heat Act. CFM 442 CFM Act. Fan Volts 123 Act. Fan Amps 0.4 Fan Des. CFM 375 CFM Fan Act. CFM 442 CFM Fan Act. RPM 1 % RTU-01 / FT-2A Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Private Bathroom B 12x12Outlet-01 1239216075120 Men's Bathroom A 24x24Outlet-02 117350109300327 ----- 375 447 442Totals : 119 %118 % 18-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-2A Joe Castanon* Notes Final Report L.H. Finn and Associates Page 8 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-2B AREA: Women's Bathroom Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF08 VAV Address 12 Box Inlet Size 8 In. K Factor - 1 1.05 Fan Des. Volts 115 Fan Des. Amps 6.5 Term Box Test Data Max Des. CFM 375 CFM Max Act. CFM 436 CFM Min Des. CFM 57 CFM Min Act. CFM 58 CFM Heat Des. CFM 375 CFM Heat Act. CFM 436 CFM Act. Fan Volts 123 Act. Fan Amps 0.5 Fan Des. CFM 375 CFM Fan Act. CFM 436 CFM Fan Act. RPM 1 % RTU-01 / FT-2B Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Women's Bathroom A 24x24Outlet-01 116348102300306 Private Bathroom B 12x12Outlet-02 1178821275159 ----- 375 465 436Totals : 124 %116 % 20-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-2B Joe Castanon* Notes Final Report L.H. Finn and Associates Page 9 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 22, 2015 SYSTEM/UNIT: RTU-01 / FT-2C AREA: Engagement Counselor Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF08 VAV Address 24 Box Inlet Size 8 In. K Factor - 1 1.35 Fan Des. Volts 115 Fan Des. Amps 6.5 Term Box Test Data Max Des. CFM 450 CFM Max Act. CFM 450 CFM Min Des. CFM 68 CFM Min Act. CFM 70 CFM Heat Des. CFM 450 CFM Heat Act. CFM 450 CFM Act. Fan Volts 123 Act. Fan Amps 0.4 Fan Des. CFM 450 CFM Fan Act. CFM 450 CFM Fan Act. RPM 1.8 % RTU-01 / FT-2C Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Office A 24x24Outlet-01 98245226250566 Engagement Counselor A 24x24Outlet-02 103205229200457 ----- 450 1,023 450Totals : 227 %100 % * Notes Final Report L.H. Finn and Associates Page 10 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 22, 2015 SYSTEM/UNIT: RTU-01 / FT-3A AREA: Living Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 6 Box Inlet Size 10 In. K Factor - 1 1.30 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 600 CFM Max Act. CFM 697 CFM Min Des. CFM 90 CFM Min Act. CFM 92 CFM Heat Des. CFM 600 CFM Heat Act. CFM 697 CFM Act. Fan Volts 123 Act. Fan Amps 0.8 Fan Des. CFM 600 CFM Fan Act. CFM 697 CFM Fan Act. RPM 1 % RTU-01 / FT-3A Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Living C 10x10Outlet-01 117352117300352 Living C 10x10Outlet-02 115345115300345 ----- 600 697 697Totals : 116 %116 % 18-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-3A Joe Castanon* Notes Final Report L.H. Finn and Associates Page 11 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-3B AREA: Semi-Private Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 7 Box Inlet Size 10 In. K Factor - 1 1.28 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 650 CFM Max Act. CFM 663 CFM Min Des. CFM 98 CFM Min Act. CFM 102 CFM Heat Des. CFM 650 CFM Heat Act. CFM 663 CFM Act. Fan Volts 123 Act. Fan Amps 0.8 Fan Des. CFM 650 CFM Fan Act. CFM 663 CFM Fan Act. RPM 1 % RTU-01 / FT-3B Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Private B 24x24Outlet-01 100751047578 Private B 12x12Outlet-02 100751007575 Semi-Private A 24x24Outlet-03 105131103125129 Men's Sleeping Area D 8x6Outlet-04 10212791125114 Semi-Private A 24x24Outlet-05 100125117125146 Men's Sleeping Area D 8x6Outlet-06 10413094125117 ----- 650 659 663Totals : 101 %102 % * Notes Final Report L.H. Finn and Associates Page 12 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-3C AREA: Semi-Private Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 10 Box Inlet Size 10 In. K Factor - 1 1.22 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 650 CFM Max Act. CFM 713 CFM Min Des. CFM 98 CFM Min Act. CFM 100 CFM Heat Des. CFM 650 CFM Heat Act. CFM 713 CFM Act. Fan Volts 123 Act. Fan Amps 0.8 Fan Des. CFM 650 CFM Fan Act. CFM 713 CFM Fan Act. RPM 1 % RTU-01 / FT-3C Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Private B 24x24Outlet-01 113851217591 Private B 12x12Outlet-02 11183837562 Semi-Private A 24x24Outlet-03 1081357312591 Women's Sleeping Area D 8x6Outlet-04 106133164125205 Semi-Private A 24x24Outlet-05 107134141125176 Women's Sleeping Area D 8x6Outlet-06 114143124125155 ----- 650 780 713Totals : 120 %110 % 20-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-3C Joe Castanon* Notes Final Report L.H. Finn and Associates Page 13 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 22, 2015 SYSTEM/UNIT: RTU-01 / FT-3D AREA: Living Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 11 Box Inlet Size 10 In. K Factor - 1 1.30 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 600 CFM Max Act. CFM 668 CFM Min Des. CFM 90 CFM Min Act. CFM 91 CFM Heat Des. CFM 600 CFM Heat Act. CFM 668 CFM Act. Fan Volts 123 Act. Fan Amps 0.7 Fan Des. CFM 600 CFM Fan Act. CFM 668 CFM Fan Act. RPM 1 % RTU-01 / FT-3D Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Living C 10x10Outlet-01 114342114300342 Living C 10x10Outlet-02 109326109300326 ----- 600 668 668Totals : 111 %111 % 18-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-3D Joe Castanon* Notes Final Report L.H. Finn and Associates Page 14 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 22, 2015 SYSTEM/UNIT: RTU-01 / FT-3E AREA: Office Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 18 Box Inlet Size 10 In. K Factor - 1 1.20 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 1000 CFM Max Act. CFM 1031 CFM Min Des. CFM 150 CFM Min Act. CFM 155 CFM Heat Des. CFM 1000 CFM Heat Act. CFM 1031 CFM Act. Fan Volts 123 Act. Fan Amps 1.8 Fan Des. CFM 1000 CFM Fan Act. CFM 1031 CFM Fan Act. RPM 16% % RTU-01 / FT-3E Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Office A 24x24Outlet-01 10420788200175 Office A 24x24Outlet-02 10420763200125 Office A 24x24Outlet-03 10320675200150 Office A 24x24Outlet-04 10420798200196 Hall A 24x24Outlet-05 10220481200161 ----- 1,000 807 1,031Totals : 81 %103 % * Notes Final Report L.H. Finn and Associates Page 15 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-3F AREA: Meeting Room Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 21 Box Inlet Size 10 In. K Factor - 1 1.17 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 650 CFM Max Act. CFM 677 CFM Min Des. CFM 98 CFM Min Act. CFM 100 CFM Heat Des. CFM 650 CFM Heat Act. CFM 677 CFM Act. Fan Volts 123 Act. Fan Amps 1.7 Fan Des. CFM 650 CFM Fan Act. CFM 677 CFM Fan Act. RPM 7 % RTU-01 / FT-3F Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Meeting Room A 24x24Outlet-01 10233190325294 Meeting Room A 24x24Outlet-02 10634681325262 ----- 650 556 677Totals : 86 %104 % * Notes Final Report L.H. Finn and Associates Page 16 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 22, 2015 SYSTEM/UNIT: RTU-01 / FT-3G AREA: Reception Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 22 Box Inlet Size 10 In. K Factor - 1 1.13 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 600 CFM Max Act. CFM 742 CFM Min Des. CFM 90 CFM Min Act. CFM 93 CFM Heat Des. CFM 600 CFM Heat Act. CFM 742 CFM Act. Fan Volts 123 Act. Fan Amps 0.8 Fan Des. CFM 600 CFM Fan Act. CFM 742 CFM Fan Act. RPM 1 % RTU-01 / FT-3G Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Retail A 24x24Outlet-01 12424769200138 Public Entry A 24x24Outlet-02 124124160100160 Reception D 8x6Outlet-03 124186221150332 Reception D 8x6Outlet-04 123185213150320 ----- 600 950 742Totals : 158 %124 % 18-May-15 Lowest obtainable airflow. Adjustment for fan at lowest setting. RTU-01 / FT-3G Joe Castanon* Notes Final Report L.H. Finn and Associates Page 17 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / FT-3H AREA: Office Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VSEF10 VAV Address 25 Box Inlet Size 10 In. K Factor - 1 1.13 Fan Des. Volts 115 Fan Des. Amps 10.1 Term Box Test Data Max Des. CFM 1000 CFM Max Act. CFM 1040 CFM Min Des. CFM 150 CFM Min Act. CFM 153 CFM Heat Des. CFM 1000 CFM Heat Act. CFM 1040 CFM Act. Fan Volts 123 Act. Fan Amps 1.7 Fan Des. CFM 1000 CFM Fan Act. CFM 1040 CFM Fan Act. RPM 17 % RTU-01 / FT-3H Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Office A 24x24Outlet-01 10320561200121 Office A 24x24Outlet-02 10120270200140 Office A 24x24Outlet-03 10320570200139 Office A 24x24Outlet-04 10721353200105 Hall A 24x24Outlet-05 10821570200140 ----- 1,000 645 1,040Totals : 65 %104 % * Notes Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / VAV-1A AREA: Exam Room Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VCCF06 VAV Address 4 Box Inlet Size 6 In. K Factor - 1 1.17 Term Box Test Data Max Des. CFM 175 CFM Max Act. CFM 179 CFM Min Des. CFM 50 CFM Min Act. CFM 52 CFM RTU-01 / VAV-1A Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Conference Room A 24x24Outlet-01 105105128100128 Exam Room A 24x24Outlet-02 99741117583 ----- 175 211 179Totals : 121 %102 % * Notes Final Report L.H. Finn and Associates Page 18 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / VAV-1B AREA: Meet + Greet Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VCCF06 VAV Address 23 Box Inlet Size 6 In. K Factor - 1 1.57 Term Box Test Data Max Des. CFM 300 CFM Max Act. CFM 303 CFM Min Des. CFM 50 CFM Min Act. CFM 53 CFM RTU-01 / VAV-1B Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Meet + Greet A 24x24Outlet-01 99198138200275 See Print B 12x12Outlet-02 105105220100220 ----- 300 495 303Totals : 165 %101 % * Notes Test Date: July 07, 2015 SYSTEM/UNIT: RTU-01 / VAV-2A AREA: Hall Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VCCF08 VAV Address 14 Box Inlet Size 8 In. K Factor - 1 1.18 Term Box Test Data Max Des. CFM 700 CFM Max Act. CFM 693 CFM Min Des. CFM 50 CFM Min Act. CFM 52 CFM RTU-01 / VAV-2A Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit B 12x12Outlet-01 106531985099 B 12x12Outlet-02 9648965048 B 12x12Outlet-03 102511325066 B 12x12Outlet-04 100501745087 A 24x24Outlet-05 991972720053 B 12x12Outlet-06 98195115200230 A 24x24Outlet-07 99995310053 ----- 700 636 693Totals : 91 %99 % * Notes Final Report L.H. Finn and Associates Page 19 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 15, 2015 SYSTEM/UNIT: RTU-01 / VAV-2B AREA: Women's Waiting Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VCCF08 VAV Address 16 Box Inlet Size 8 In. K Factor - 1 1.33 Term Box Test Data Max Des. CFM 600 CFM Max Act. CFM 615 CFM Min Des. CFM 50 CFM Min Act. CFM 59 CFM Heat Des. CFM NA CFM Heat Act. CFM NA CFM RTU-01 / VAV-2B Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Men's Waiting C 10x10Outlet-01 100301183300550 Women's Waiting C 10x10Outlet-02 10531489300267 ----- 600 817 615Totals : 136 %103 % * Notes Test Date: June 09, 2015 SYSTEM/UNIT: RTU-01 / VAV-3A AREA: Hall Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VCCF08 VAV Address 19 Box Inlet Size 8 In. K Factor - 1 1.29 Term Box Test Data Max Des. CFM 375 CFM Max Act. CFM 368 CFM Min Des. CFM 350 CFM Min Act. CFM 349 CFM Heat Des. CFM 200 CFM Heat Act. CFM 199 CFM RTU-01 / VAV-3A Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Hall A 24x24Outlet-01 100751207590 Staff Lockers B 12x12Outlet-02 102511185059 Staff Lockers B 12x12Outlet-03 96481165058 Office A 24x24Outlet-04 9514370150105 Hall B 12x12Outlet-05 10251965048 ----- 375 360 368Totals : 96 %98 % * Notes Final Report L.H. Finn and Associates Page 20 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: May 20, 2015 SYSTEM/UNIT: RTU-01 / VAV-3B AREA: Admission Tested By: Joe Castanon Unit Data Manufacturer Trane Model Number VCEF08 VAV Address 20 Box Inlet Size 8 In. K Factor - 1 1.37 Term Box Test Data Max Des. CFM 650 CFM Max Act. CFM 652 CFM Min Des. CFM 350 CFM Min Act. CFM 353 CFM Heat Des. CFM 200 CFM Heat Act. CFM 205 CFM RTU-01 / VAV-3B Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Admission A 24x24Outlet-01 99197147200293 Business Center A 24x24Outlet-02 103258160250400 Admission A 24x24Outlet-03 99197117200233 ----- 650 926 652Totals : 142 %100 % * Notes Final Report L.H. Finn and Associates Page 21 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-01 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-093BE Fan Serial Number K14-000000135272 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 450 CFM Total CFM Actual 447 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 120 Volts Motor Amps 1 2.8 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.35 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer McMillan Electric Motor HP 1/4 HP Motor RPM 300-1800 RPM Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.3 Amps Sheave Data Motor Sheave Make Direct Drive EF-01 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Private Bathroom E 8x8Inlet-A 1011017010070 Women's Bathroom E 8x8Inlet-B 9898112100112 Women's Bathroom E 8x8Inlet-C 9797121100121 Women's Bathroom E 8x8Inlet-D 99741007575 Women's Bathroom E 8x8Inlet-E 103771167587 ----- 450 465 447Totals : 103 %99 % * Notes Final Report L.H. Finn and Associates Page 22 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-02 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-073B Fan Serial Number K14-000000135259 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 200 CFM Total CFM Actual 202 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 123 Volts Motor Amps 1 1.3 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.3 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer Twin City Motor Frame 48 Motor HP 1/8 HP Motor RPM 1650/1500/1350 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.7 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Make Direct Drive EF-02 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Exam Room E 8x8Inlet-A 9999119100119 Conference Room E 8x8Inlet-B 103103133100133 ----- 200 252 202Totals : 126 %101 % * Notes Final Report L.H. Finn and Associates Page 23 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-03 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-092B Fan Serial Number K14-000000136328 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 350 CFM Total CFM Actual 307 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 1.2 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.3 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer Twin City Motor Frame 48 Motor HP 1/8 HP Motor RPM 1140 RPM Motor Rated Volts 115/208-230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.6/0.9-0.8 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Make Direct Drive EF-03 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Bath E 8x8Inlet-A 88888210082 Staff Bath E 8x8Inlet-B 8383140100140 Staff Lockers E 8x8Inlet-C 8967497537 Staff Lockers E 8x8Inlet-D 9269697552 ----- 350 311 307Totals : 89 %88 % 7-Jul-15 Maximum obtainable airflow. Fan is on high speed. EF-03 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 24 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-04 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-083BE Fan Serial Number K14-000000135262 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 300 CFM Total CFM Actual 298 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 2.9 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.35 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer McMillan Electric Motor HP 1/4 HP Motor RPM 300-1800 RPM Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.3 Amps Sheave Data Motor Sheave Make Direct Drive EF-04 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Med.E 8x8Inlet-A 9974757556 Med.E 8x8Inlet-B 10075847563 Med.E 8x8Inlet-C 101761077580 Med.E 8x8Inlet-D 97731177588 ----- 300 287 298Totals : 96 %99 % * Notes Final Report L.H. Finn and Associates Page 25 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-05 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-073B Fan Serial Number K14-000000135260 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 200 CFM Total CFM Actual 194 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 1.4 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.3 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer Twin City Motor Frame 48 Motor HP 1/8 HP Motor RPM 1650/1500/1350 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.7 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Make Direct Drive EF-05 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Exam Room E 8x8Inlet-A 95959210092 Conference Room E 8x8Inlet-B 9999102100102 ----- 200 194 194Totals : 97 %97 % * Notes Final Report L.H. Finn and Associates Page 26 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-06 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-093BE Fan Serial Number K14-000000135273 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 500 CFM Total CFM Actual 392 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 3.0 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.35 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer McMillan Electric Motor HP 1/4 HP Motor RPM 300-1800 RPM Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.3 Amps Sheave Data Motor Sheave Make Direct Drive EF-06 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Men's Bathroom E 8x8Inlet-A 78786710067 Men's Bathroom E 8x8Inlet-B 76767610076 Janitor E 8x8Inlet-C 78391225061 Private Bathroom E 8x8Inlet-D 80803810038 Men's Bathroom E 8x8Inlet-E 7959877565 Men's Bathroom E 8x8Inlet-F 80601157586 ----- 500 393 392Totals : 79 %78 % 7-Jul-15 Maximum obtainable airflow. Fan is on high speed. EF-06 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 27 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-07 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-073B Fan Serial Number K14-000000135261 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 200 CFM Total CFM Actual 206 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 120 Volts Motor Amps 1 1.4 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.3 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer Twin City Motor Frame 48 Motor HP 1/8 HP Motor RPM 1650/1500/1350 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.7 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Make Direct Drive EF-07 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Bath E 8x8Inlet-A 101101125100125 Bath E 8x8Inlet-B 1051059210092 ----- 200 217 206Totals : 109 %103 % * Notes Final Report L.H. Finn and Associates Page 28 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Duct Traverse Test Date: July 10, 2015 SYSTEM/UNIT: RTU-01 North Branch Tested By: Joe Castanon Unit Data Type of Traverse Rectangle Outer Height 22 in. Outer Width 52 in. Air Flow Area 6.94 sq. ft. Number Of Rows 9 Readings Per Row 4 Total Readings 36 Hole Position 2 Left Hole Position 1 Bottom Final Data Sum of Readings 35312 FPM Average Reading 981 FPM Actual Total Flow 6808 CFM NOTES: Duct Traverse Data Points Final Report L.H. Finn and Associates Page 29 of 61 PROJECT: Harmony Foundation, Inc. - Admissions/Detox LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Duct Traverse Test Date: July 10, 2015 SYSTEM/UNIT: RTU-01 South Branch Tested By: Joe Castanon Unit Data Type of Traverse Rectangle Outer Height 16 in. Outer Width 28 in. Air Flow Area 2.52 sq. ft. Number Of Rows 5 Readings Per Row 4 Total Readings 20 Hole Position 2 Left Hole Position 1 Bottom Insulation Width 1 in. Final Data Sum of Readings 18296 FPM Average Reading 915 FPM Actual Total Flow 2305 CFM NOTES: Duct Traverse Data Points Final Report L.H. Finn and Associates Page 30 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: July 10, 2015 SYSTEM/UNIT: MAU-01 AREA: Tested By: Joe Castanon Unit Data Unit Manufacturer Captive Aire Unit Model Number A3-IBT-600-300-300-G18 Unit Serial Number 2223028 Unit Discharge Vertical/Down MAU-01 / Supply Fan Fan Type Forward Curve Fan Size 16" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal MAU-01 / Filter Bank Filter Manufacturer Airguard Filter Type MERV 13 Filter Quantity 15 Filter Size 16x20x2 Starter Data MAU-01 / Supply Fan Installed Thermal Internal Test Data Total CFM Design 5825 CFM Total CFM Actual 5214 CFM MAU-01 / Supply Fan Fan RPM Actual 863 RPM Motor Volts 1 210 Volts Motor Volts 2 209 Volts Motor Volts 3 210 Volts Motor Amps 1 9.0 Amps Motor Amps 2 9.3 Amps Motor Amps 3 9.3 Amps VFD Speed 60 HZ Motor Data MAU-01 / Supply Fan Motor Manufacturer WEG Motor Frame 56HZ Motor HP 3 HP Motor RPM 1725 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 9.49-8.58/4.29 Amps Motor Service Factor 1.15 Nominal Efficiency 81.5 % Power Factor 79 Sheave Data MAU-01 / Supply Fan Motor Sheave Make PRP Motor Sheave Model 2VP42 Motor Sheave Diam.4 in. Motor Sheave Bore 7/8 in. Motor Operating Diameter 4 in. Fan Sheave Make PRP Fan Sheave Model 2BK80 Fan Sheave Diam.8 in. Fan Sheave Bore 1-3/16 in. Number of Belts 2 Belt Size BX55 Sheave Center Line 20 in. Test Pressures Fan SP In Actual -0.23 in. wc Fan SP Out Actual 0.18 in. wc Unit External SP Actual 0.25 in. wc Filter SP In -0.07 in. wc Filter SP Out -0.23 in. wc Final Report L.H. Finn and Associates Page 31 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: July 10, 2015 SYSTEM/UNIT: MAU-01 (Cont.) AREA: Tested By: Joe Castanon MAU-01 Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Trays/Trash G 8x6Outlet-01 89133147150220 Kitchen H 24x24Outlet-02 8734791400364 Dish A 24x24Outlet-03 96191121200242 See Print A 24x24Outlet-04 8717370200139 See Print A 24x24Outlet-05 9118159200118 Staff Lockers B 12x12Outlet-06 9246765038 Dry Storage G 12x10Outlet-07 9337398400393 Staff Restroom B 12x12Outlet-08 94471285064 Food Service Director C 24x24Outlet-09 95119150125188 Storage G 8x6Outlet-10 91181199200397 See Print A 24x24Outlet-11 9191351100351 Men's Restroom B 12x12Outlet-12 9017967200133 Women's Restroom B 12x12Outlet-13 9218379200157 Kitchen H 24x24Outlet-14 9035975400300 Kitchen Plenum 144x16Outlet-15 8926117229502120 ----- 5,825 5,224 5,214Totals : 90 %90 % 10-Jul-15 Maximum obtainable airflow. Motor operating at full load Amps. MAU-01 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 32 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: July 10, 2015 SYSTEM/UNIT: RTU-01 AREA: Tested By: Joe Castanon Unit Data Unit Manufacturer Trane Unit Model Number YHD210F3RVA030AE1A1A Unit Serial Number 144610502D Unit Discharge Vertical/Down RTU-01 / Supply Fan Fan Type Forward Curve Fan Size 16" ID Fan Class 1 Fan Arrangement DWDI Fan Discharge Horizontal RTU-01 / Filter Bank Filter Manufacturer Airguard Filter Type MERV 13 Filter Quantity 12 Filter Size 20x20x2 Starter Data RTU-01 / Supply Fan Installed Thermal VFD Test Data Total CFM Design 7875 CFM Total CFM Actual 7941 CFM Outside Air CFM Design 3100 CFM Outside Air CFM Actual 3173 CFM Return Air CFM Design 4775 CFM Return Air CFM Actual 4768 CFM RTU-01 / Supply Fan Fan RPM Actual 807 RPM Motor Volts 1 212 Volts Motor Volts 2 211 Volts Motor Volts 3 212 Volts Motor Amps 1 11.3 Amps Motor Amps 2 11.5 Amps Motor Amps 3 11.2 Amps VFD Speed 60 HZ Motor Data RTU-01 / Supply Fan Motor Manufacturer Marathon Motor Frame NA Motor HP 5 HP Motor RPM 3450 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 13.4-12.6/6.3 Amps Motor Service Factor 1.15 Nominal Efficiency 86.5 % Power Factor 85 Sheave Data RTU-01 / Supply Fan Motor Sheave Make Browning Motor Sheave Model 1VP50 Motor Sheave Diam.4-3/4 in. Motor Sheave Bore 7/8 in. Motor Operating Diameter 4-1/2 in. Fan Sheave Make Browning Fan Sheave Model Fixed Fan Sheave Diam.18-3/4 in. Fan Sheave Bore 1-3/16 in. Number of Belts 1 Belt Size BX81 Sheave Center Line 22-1/2 in. Test Pressures Fan SP In Actual -0.34 in. wc Fan SP Out Actual 0.28 in. wc OA Damper Pos Actual 40 % RA Damper Pos Actual 60 % Unit External SP Design 1.0 in. wc Unit External SP Actual 0.36 in. wc Filter/Coil SP In -0.08 in. wc Filter/Coil SP Out -0.34 in. wc Final Report L.H. Finn and Associates Page 33 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Roof Top Unit Test Date: July 10, 2015 SYSTEM/UNIT: RTU-01 (Cont.) AREA: Tested By: Joe Castanon RTU-01 Supply Outlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Dining Hall A 24x24Outlet-01 10437362360223 Dining Hall A 24x24Outlet-02 9433944360157 Dining Hall A 24x24Outlet-03 10337163360227 Dining Hall A 24x24Outlet-04 9735062360224 Dining Hall A 24x24Outlet-05 10336956360202 Dining Hall A 24x24Outlet-06 10437555360198 Dining Hall A 24x24Outlet-07 9433960360217 Dining Hall A 24x24Outlet-08 10035957360206 See Print A 24x24Outlet-09 9927302750 Dining Hall A 24x24Outlet-10 10337161360221 Dining Hall A 24x24Outlet-11 10136459360212 Entry A 24x24Outlet-12 10220452200103 Dining Hall A 24x24Outlet-13 10437657360205 Dining Hall A 24x24Outlet-14 10136564360231 Dining Hall A 24x24Outlet-15 10437463360228 Dining Hall A 24x24Outlet-16 10337161360220 Entry A 24x24Outlet-17 10120202000 Dining Hall A 24x24Outlet-18 10337056360201 Dining Hall A 24x24Outlet-19 1013652436087 A 24x24Outlet-20 9534303600 A 24x24Outlet-21 9534356360201 A 24x24Outlet-22 10437403600 A 24x24Outlet-23 10337164360230 ----- 7,875 3,793 7,941Totals : 48 %101 % RTU-01 Return Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Dining Hall I 34x34Inlet-A 5722645739502264 Dining Hall I 34x34Inlet-B 6425046439252504 ----- 7,875 4,768 4,768Totals : 61 %61 % * Notes Final Report L.H. Finn and Associates Page 34 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-01 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-110B Fan Serial Number K14-000000135258 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Internal Test Data Total CFM Design 800 CFM Total CFM Actual 648 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 123 Volts Motor Amps 1 1.1 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.25 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer Twin City Motor Frame 48 Motor HP 1/8 HP Motor RPM 1140 RPM Motor Rated Volts 115/208-230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.6-0.9/0.8 Amps Sheave Data Motor Sheave Make Direct Drive EF-01 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Women's Restroom B 8x8Inlet-A 8216379200158 Women's Restroom B 8x8Inlet-B 7815675200150 Men's Restroom B 8x8Inlet-C 8216378200155 Men's Restroom B 8x8Inlet-D 8316697200193 ----- 800 656 648Totals : 82 %81 % 7-Jul-15 Lowest obtainable airflow. Fan is direct drive. EF-01 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 35 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 08, 2015 SYSTEM/UNIT: EF-02 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-093BE Fan Serial Number K14-000000135275 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Rheostat Test Data Total CFM Design 400/200 CFM Total CFM Actual 391/199 CFM Fan RPM Actual Low RPM Motor Volts 1 123 Volts Motor Amps 1 1.2 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.375 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer McMillan Electric Motor Frame NA Motor HP 1/4 HP Motor RPM 300-1800 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.3 Amps Sheave Data Motor Sheave Make Direct Drive EF-02 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Staff Restroom D 8x8Inlet-A 9999179100179 Staff Lockers D 8x8Inlet-B 9797173100173 Trays/Trash D 8x8Inlet-C 98195148200296 ----- 400 648 391Totals : 162 %98 % * Notes Final Report L.H. Finn and Associates Page 36 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-03 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DCRU-092B Fan Serial Number K14-000000135257 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal Internal Test Data Total CFM Design 300 CFM Total CFM Actual 223 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 123 Volts Motor Amps 1 1.0 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Design 0.25 in. wc Total SP Actual NA in. wc Motor Data Motor Manufacturer Twin City Motor Frame 48 Motor HP 1/8 HP Motor RPM 1140 RPM Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.6 Amps Motor Service Factor 1.0 Sheave Data Motor Sheave Make Direct Drive EF-03 Exhaust Inlet Summary % Final Deviation % Prelim Deviation Maximum Final Prelim Reading Maximum Design AK Factor Size LxW / DOutlet Type Area ServedSystem / Unit Dish D 10x10Inlet-A 7422374300223 ----- 300 223 223Totals : 74 %74 % 7-Jul-15 Maximum obtainable airflow. Fan is direct drive. EF-03 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 37 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 07, 2015 SYSTEM/UNIT: EF-04 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Twin City Fan Fan Model Number DSI-080AE Fan Serial Number K14-000000135340 Fan Type Inline Fan Class 1 Fan Arrangement SWSI Fan Discharge Horizontal Starter Data Installed Thermal Internal Test Data Total CFM Design 150 CFM Total CFM Actual 311 CFM Fan RPM Actual Direct Drive RPM Motor Volts 1 121 Volts Motor Amps 1 1.0 Amps SP In Actual 0 in. wc SP Out Actual 0.20 in. wc Total SP Design 0.25 in. wc Total SP Actual 0.20 in. wc Motor Data Motor HP 1/4 HP Motor Rated Volts 115 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.9 Amps Sheave Data Motor Sheave Make Direct Drive 7-Jul-15 Lowest obtainable airflow. No speed control installed. EF-04 Joe Castanon* Notes Final Report L.H. Finn and Associates Page 38 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 10, 2015 SYSTEM/UNIT: EF-08 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Captive Aire Fan Model Number NCA24HPFA Fan Serial Number 2223028 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal VFD Test Data Total CFM Design 2306 CFM Total CFM Actual 2318 CFM Fan RPM Actual 653 RPM Motor Volts 1 212 Volts Motor Volts 2 211 Volts Motor Volts 3 212 Volts Motor Amps 1 3.4 Amps Motor Amps 2 3.2 Amps Motor Amps 3 3.4 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Actual NA in. wc VFD Speed 38.0 Hz. Motor Data Motor Manufacturer WEG Motor Frame 56HZ Motor HP 2 HP Motor RPM 1740 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 6.88-6.22/3.11 Amps Motor Service Factor 1.15 Nominal Efficiency 78.5 % Power Factor 77 Sheave Data Motor Sheave Make PRP Motor Sheave Model 2VL40 Motor Sheave Diam.3-3/4 in. Motor Operating Diameter 3-1/2 in. Motor Sheave Bore 7/8 in. Fan Sheave Make PRP Fan Sheave Model Fixed Fan Sheave Diam.5-3/4 in. Fan Sheave Bore 1 in. Number of Belts 2 Belt Size BX25 in. Sheave Center Line 6-3/4 in. * Notes Final Report L.H. Finn and Associates Page 39 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Fan Unit Test Date: July 10, 2015 SYSTEM/UNIT: EF-08.1 AREA: Tested By: Joe Castanon Unit Data Fan Manufacturer Captive Aire Fan Model Number NCA24HPFA Fan Serial Number 2223028 Fan Type Backward Incline Fan Class 1 Fan Arrangement SWSI Fan Discharge Upblast Starter Data Installed Thermal VFD Test Data Total CFM Design 2406 CFM Total CFM Actual 2400 CFM Fan RPM Actual 696 RPM Motor Volts 1 212 Volts Motor Volts 2 211 Volts Motor Volts 3 211 Volts Motor Amps 1 2.9 Amps Motor Amps 2 2.9 Amps Motor Amps 3 2.8 Amps SP In Actual ANA in. wc SP Out Actual 0 in. wc Total SP Actual NA in. wc VFD Speed 43.0 Hz. Motor Data Motor Manufacturer WEG Motor Frame 56H Motor HP 1.5 HP Motor RPM 1745 RPM Motor Rated Volts 208-230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 5.09-4.60/2.30 Amps Motor Service Factor 1.15 Nominal Efficiency 80 % Power Factor 75 Sheave Data Motor Sheave Make PRP Motor Sheave Model VL40 Motor Sheave Diam.3-3/4 in. Motor Operating Diameter 3-1/2 in. Motor Sheave Bore 5/8 in. Fan Sheave Make Power Drive Fan Sheave Model AK59 Fan Sheave Diam.5-3/4 in. Fan Sheave Bore 1 in. Number of Belts 1 Belt Size AX25 in. Sheave Center Line 6 in. * Notes Final Report L.H. Finn and Associates Page 40 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Kitchen Hood Test Date: July 10, 2015 SYSTEM/UNIT: Kitchen Hood-01 Tested By: Joe Castanon Unit Data Hood Manufacturer Captive Aire Hood Model Number 5430 ND-2 Hood Serial Number 2166490 Exhaust Section Design Exhaust Airflow 2406 CFM Calculated Exhaust Airflow 2400 CFM Total Filters Height 20.00 in. Total Filters Width 90.00 in. Total Filter Area 12.50 Sq Ft Total Readings - Exhaust 6 Sum of Readings - Exhaust 1150 FPM Avg Velocity - Exhaust 192 FPM Exhaust Readings EA-Reading001 180 FPM EA-Reading002 191 FPM EA-Reading003 196 FPM EA-Reading004 204 FPM EA-Reading005 188 FPM EA-Reading006 191 FPM Filter Data Filter Manufacturer Captive Aire Filter Model Number 200 Filter Type Baffle Filter Quantity 6 Filter Size 20x16x2 Supply Section Calculated Supply Airflow 0 CFM Sum of Readings - Supply 0 FPM Avg Velocity - Supply 0 FPM NOTES: Final Report L.H. Finn and Associates Page 41 of 61 PROJECT: Harmony Foundation, Inc. - Dining Hall LOCATION: Estes Park, CO DATE: 7/13/2015 CONTACT: Joe Castanon Kitchen Hood Test Date: July 10, 2015 SYSTEM/UNIT: Kitchen Hood-02 Tested By: Joe Castanon Unit Data Hood Manufacturer Captive Aire Hood Model Number 5430 ND-2 Hood Serial Number 2166490 Exhaust Section Design Exhaust Airflow 2306 CFM Calculated Exhaust Airflow 2318 CFM Total Filters Height 20.00 in. Total Filters Width 105.00 in. Total Filter Area 14.58 Sq Ft Total Readings - Exhaust 7 Sum of Readings - Exhaust 1112 FPM Avg Velocity - Exhaust 159 FPM Exhaust Readings EA-Reading001 137 FPM EA-Reading002 158 FPM EA-Reading003 168 FPM EA-Reading004 169 FPM EA-Reading005 169 FPM EA-Reading006 163 FPM EA-Reading007 148 FPM Filter Data Filter Manufacturer Captive Aire Filter Model Number 200 Filter Type Baffle Filter Quantity 7 Filter Size 16x20x2 Supply Section Calculated Supply Airflow 0 CFM Sum of Readings - Supply 0 FPM Avg Velocity - Supply 0 FPM NOTES: Final Report L.H. Finn and Associates Page 42 of 61 MXX X PIPE OR DUCT OFFSET DOWN PIPE OR DUCT OFFSET UP X % DN. UP PIPE OR DUCT SLOPE IN DIRECTION OF FLOW (NEGATIVE % DEPICTS SLOPING DOWN, POSITIVE % DEPICTS SLOPING UP) TEE OFF TOP OF PIPE OR DUCT TEE OFF BOTTOM OF PIPE OR DUCT PIPE OR DUCT ELBOW UP PIPE OR DUCT ELBOW DOWN PIPE OR DUCT REDUCER (CONCENTRIC UNLESS OTHERWISE NOTED) ABOVE FINISHED FLOOR SHEET NUMBER PLAN, DIAGRAM, OR RISER NUMBER AFF TOP OF UNITT.O.U BOTTOM OF UNITB.O.U TOP OF PIPET.O.P. BOTTOM OF PIPEB.O.P. MECHANICAL CONTRACTORMC PLUMBING CONTRACTORPC GENERAL CONTRACTORGC ELECTRICAL CONTRACTOREC FIRE ALARM CONTRACTORFAC FIRE SPRINKLER CONTRACTORFSC POINT OF CONNECTION NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: INDEX, LEGEND, QUAL. NOTES & CRITERIA M0 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 MECHANICAL DRAWING LIST SHEET NUMBER SHEET NAME 100% CD M0 INDEX, LEGEND, QUAL. NOTES & CRITERIA 03/28/14 M0.1 SCHEDULES 03/28/14 M0.2 SCHEDULES 03/28/14 M100 LEVEL ONE HVAC PLAN 03/28/14 M200 ATTIC HVAC PLAN 03/28/14 M300 MECHANICAL ROOF PLAN 03/28/14 M400 DETAILS 03/28/14 M401 SECTIONS 03/28/14 M402 CONTROL SEQUENCES 03/28/14 M500 MECHANICAL ISOMETRICS 03/28/14 1.THE GENERAL CONTRACTOR IS TO OBTAIN ALL PERMITS, PATENT RIGHTS, AND LICENSES THAT ARE REQUIRED FOR PERFORMING THE WORK UNDER ALL LAWS, ORDINANCES, RULES AND REGULATIONS, OR ORDERS OF ANY OFFICER AND/OR GOVERNING BODY, HAVING JURISDICTION FOR THE WORK UNDER THIS SECTION. THE CONTRACTOR IS TO GIVE ALL NOTICES NECESSARY IN CONNECTION WITH, PAY ALL FEES RELATING TO AND ALL COSTS AND EXPENSES INCURRED ON ACCOUNT OF THE WORK UNDER THIS SECTION. NO WORK IS TO BE COVERED BEFORE INSPECTION BY THE JURISDICTIONAL INSPECTOR AND THE OWNER'S REPRESENTATIVE. POST PERMITS AS REQUIRED. 2.THE CONTRACT DOCUMENTS ARE DIAGRAMMATIC, SHOWING CERTAIN PHYSICAL RELATIONSHIPS WHICH MUST BE ESTABLISHED WITHIN THE MECHANICAL WORK AND ITS INTERFACE WITH OTHER WORK. SUCH ESTABLISHMENT IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACT DOCUMENTS INDICATE THE AVAILABLE INFORMATION ON EXISTING UTILITIES AND SERVICES, AND ON NEW SERVICES TO BE PROVIDED TO THE PROJECT BY UTILITY COMPANIES AND AGENCIES. COORDINATE ALL UTILITY INTERRUPTIONS WITH THE OWNER AND THE UTILITY COMPANY. PLAN WORK SO THAT THESE INTERRUPTIONS ARE KEPT TO A MINIMUM. 3.THE EQUIPMENT INDICATED ON THE CONTRACT DOCUMENTS REPRESENT A STANDARD OF QUALITY TO BE MAINTAINED. SUBSTITUTIONS MAY BE SUBMITTED TO THE ENGINEER FOR REVIEW. THIS SUBMITTAL REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS (WHICH ARE TO BE CORRELATED AT THE JOB SITE), FABRICATION PROCESSES, MEANS, METHODS AND TECHNIQUES OF CONSTRUCTION, COORDINATION OF HIS WORK WITH THAT OF ALL OTHER TRADES AND THE SATISFACTORY PERFORMANCE OF HIS WORK IN A SAFE AND SATISFACTORY MANNER. ALL EQUIPMENT AND MATERIALS ARE TO BE NEW AND UNUSED AND INSTALLED BY ONLY QUALIFIED PERSONNEL. THE CONTRACTOR IS TO INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS, IN ADDITION TO ANY STATE AND LOCAL CODES THAT MAY APPLY. WORKMANSHIP: ALL LABOR IS TO BE CAREFULLY SKILLED FOR THIS KIND OF WORK, THOROUGH IN ALL RESPECTS AND UNDER THE DIRECTION OF A COMPETENT FOREMAN. 4.SUBMIT (6) COPIES OF SHOP DRAWINGS ON ALL EQUIPMENT AND MATERIALS FOR ENGINEERS REVIEW. SUBMITTAL INFORMATION IS TO INDICATE ALL PERFORMANCE DATA (RATED FOR THE ALTITUDE OF THIS PROJECT) THAT COMPLIES WITH THE SCHEDULED DATA. LIST ALL DEVIATIONS AND REASONS FOR DEVIATION. SUBMITTALS WITHOUT PROPER INFORMATION WILL BE IMMEDIATELY REJECTED. SHOP DRAWINGS IN PDF FORMAT MAY BE SUBMITTED ELECTRONICALLY FOR REVIEW. 5.EQUIPMENT FURNISHED UNDER THIS CONTRACT IS TO HAVE A PERMANENT LABEL CLEARLY INDICATING THE MAINTENANCE TO BE PERFORMED TO MAINTAIN THE EQUIPMENT IN EFFICIENT OPERATING CONDITION. EQUIPMENT SUPPLIERS ARE TO FURNISH THE FULL AND PARTIAL INPUT AND OUTPUT CAPACITIES TO ENABLE THE DETERMINATION OF COMPLIANCE WITH THE ENERGY CONSERVATION CODE. 6.SUBMIT THREE TYPED AND BOUND COPIES OF OPERATING AND MAINTENANCE MANUALS PRIOR TO SCHEDULING SYSTEMS DEMONSTRATION FOR THE OWNER. MANUALS ARE TO HAVE INDEX WITH TAB DIVIDERS FOR EACH MAJOR EQUIPMENT SECTION TO FACILITATE LOCATING INFORMATION ON A SPECIFIC PIECE OF EQUIPMENT. ALPHABETICAL LIST OF SYSTEM COMPONENTS, WITH THE NAME, ADDRESS AND 24 HOUR TELEPHONE NUMBER OF THE COMPANY RESPONSIBLE FOR SERVICING EACH ITEM DURING THE FIRST YEAR OF OPERATION. 7.DELIVERY AND STORAGE OF MATERIALS: PROVIDE FOR THE SAFETY AND GOOD CONDITION OF ALL MATERIALS AND EQUIPMENT UNTIL FINAL ACCEPTANCE BY THE OWNERS REPRESENTATIVE PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE AND PROVIDE ADEQUATE AND PROPER STORAGE FACILITIES DURING THE PROGRESS OF THE WORK. REPLACE ALL DAMAGED AND DEFECTIVE WORK BEFORE FILING APPLICATION FOR FINAL ACCEPTANCE. 8.BEFORE SUBMITTING HIS BID, THE CONTRACTOR FOR THE WORK UNDER THIS SECTION IS TO CAREFULLY STUDY ALL DRAWINGS, AND MAKE A CAREFUL EXAMINATION OF THE PREMISES. HE IS TO DEFINITELY DETERMINE IN ADVANCE, THE METHODS OF INSTALLATION AND CONNECTING THE APPARATUS AND THE MEANS TO BE PROVIDED FOR GETTING THE EQUIPMENT INTO PLACE, AFTER AWARD OF THE CONTRACT, NO SUBSEQUENT ALLOWANCES WILL BE MADE TO THE CONTRACTOR DUE TO HIS FAILURE TO COMPLY WITH THE ABOVE REQUIREMENTS AND ANY OTHER CONDITIONS AFFECTING THE INSTALLATION AND COMPLETION OF ALL WORK. 9.ACCURATELY RECORD ALL CHANGES TO THE CONTRACT DOCUMENTS ON ONE SET OF DRAWINGS. TRANSMIT THE INFORMATION TO THE ENGINEER. 10.FURNISH WRITTEN CERTIFIED GUARANTEE, IN ACCEPTANCE FORM, TO THE OWNER AGAINST DEFECTIVE WORKMANSHIP, MATERIALS AND OPERATING EQUIPMENT. IN ADDITION TO THE GUARANTEES REQUIRED ELSEWHERE. ALL WORK, MATERIALS AND EQUIPMENT PROVIDED UNDER THE MECHANICAL SECTIONS ARE TO BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE WORK BY THE OWNER. THE CONTRACTOR UNDER THIS GUARANTEE IS TO BE RESPONSIBLE FOR ALL DAMAGE TO ANY PART OF THE PREMISES CAUSED BY EQUIPMENT AND MATERIALS FURNISHED UNDER THIS SECTION. PROVIDE CERTIFICATES FOR ALL EQUIPMENT HAVING WARRANTIES IN EXCESS OF (1) YEAR. 11.ALL WORK AND MATERIALS ARE TO BE IN FULL ACCORDANCE WITH CURRENT SAFETY ORDERS OF THE DIVISION OF INDUSTRIAL SAFETY, THE NATIONAL ELECTRIC CODE, LOCAL BUILDING CODES, THE INTERNATIONAL MECHANICAL CODE, THE INTERNATIONAL PLUMBING CODE, THE INTERNATIONAL BUILDING CODE AND OTHER APPLICABLE CODES, LAWS OR REGULATIONS OF BODIES LAWFULLY EMPOWERED AND HAVING JURISDICTION OVER THIS PROJECT. NOTHING IN THE PLANS OR THESE SPECIFICATIONS IS TO BE CONSTRUED AS TO PERMIT WORK NOT CONFORMING TO THESE CODES. 12.RESOLVE ALL QUESTIONS, DISCREPANCIES OR CONFLICTS WITH ENGINEER BEFORE ANY EQUIPMENT IS ORDERED, MATERIALS FABRICATED OR SYSTEMS INSTALLED. 13.PROVIDE IDENTIFICATION TAGS FOR ALL SCHEDULED EQUIPMENT. 14.COORDINATE THE INSTALLATION OF MECHANICAL SYSTEMS WITH OTHER TRADES AND PROVIDE OFFSETS AS NECESSARY TO ACCOMMODATE STRUCTURE AND OTHER TRADES. 15.M.C. TO PROVIDE ALL NECESSARY MOTOR STARTERS WITH REQUIRED AUXILIARY CONTACTS FOR CONTROLS FOR THE EQUIPMENT THEY ARE RESPONSIBLE FOR. COORDINATE WITH E.C. TO INSTALL AND WIRE. M.C. TO PROVIDE & INSTALL ALL NECESSARY LOW VOLTAGE WIRING. 16.PROVIDE ACCESS PANELS IN CEILINGS AND/OR DUCTWORK WHERE REQUIRED FOR ACCESS TO ALL MOTORS, CONTROLS, FIRE DAMPERS, SMOKE / FIRE DAMPERS, BALANCING DAMPERS, AND VALVES. 17.LEVEL ALL EQUIPMENT CURBS / BASES PRIOR TO INSTALLATION OF ANY EQUIPMENT. 18.SEAL ALL WALL AND ROOF PENETRATIONS WATERTIGHT WITH SILICONE CAULKING AND BACKER ROD. U.L. CLASSIFIED AND FM APPROVED SEALANTS ARE TO BE USED AT ALL PENETRATIONS OF RATED WALLS, CEILINGS AND FLOORS. 19.COORDINATE TO PROVIDE ALL THE MISCELLANEOUS SUPPORT AND FRAMING REQUIRED FOR THE MECHANICAL EQUIPMENT. 20.COORDINATE AND VERIFY ALL OPENINGS IN STRUCTURAL WALLS, ABOVE CEILINGS, AND FLOORS WITH THE STRUCTURAL CONTRACTOR. 21.PROVIDE EQUIPMENT VIBRATION ISOLATION FROM STRUCTURE AND ASSOCIATED DUCT/PIPE SYSTEMS. 22.ALL BALANCING IS TO BE COMPLETED BY A QUALIFIED AND CERTIFIED TECHNICIAN, WITH (5) OR MORE YEARS EXPERIENCE IN TESTING, ADJUSTING, AND BALANCING HVAC SYSTEMS. ADJUST DAMPERS AS NECESSARY TO OBTAIN AIR QUANTITIES SHOWN. PROVIDE COMPLETE WRITTEN TEST AND BALANCE REPORT INDICATING QUANTITIES AT INLET AND OUTLET. USE VOLUME DAMPERS FOR ALL REGISTERS FOR BALANCING OF THE SYSTEMS. AIR DISTRIBUTION IS TO BE BALANCED FOR WITHIN 5% OF INDICATED CFM'S. 23.ALL DUCT, PIPE, AND EQUIPMENT LOCATIONS INDICATED ON THESE DOCUMENTS ARE FOR REFERENCE ONLY AND ARE TO BE USED AS A GUIDE. ALL ELEVATIONS AND FLOOR TO FLOOR HEIGHTS ARE TO BE VERIFIED PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY DUCT OR PIPING SYSTEM. TOP OF DUCT (TOD) AND BOTTOM OF DUCT (BOD) ELEVATIONS INDICATED INCLUDE AN ALLOWANCE FOR DUCT FLANGES AND INSULATION. 24.THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE MECHANICAL REQUIREMENTS FOR ALL CUTTING AND PATCHING OF EXISTING FACILITIES TO BE COMPLETED BY THE GENERAL CONTRACTOR OR OTHERS. 25.REFRIGERANT PIPING SIZES 2 1/2" AND SMALLER SHALL BE COPPER TUBE, TYPE "L", ANNEALED, WITH WROUGHT COPPER FITTINGS AND BRAZED JOINTS. REFRIGERANT DISCHARGE PIPING: 1 1/2" FIBERGLASS USE FLEXIBLE UNICELLULAR PIPE INSULATION ON REFRIGERANT DISCHARGE PIPING ABOVE ROOF EXPOSED TO THE ELEMENTS. 26.PRINCIPAL TEMPERATURE CONTROL SYSTEM WILL BE PACKAGED ELECTRONIC / ELECTRIC DDC CONTROLS WITH SPACE MOUNTED ZONE SENSORS. GENERAL MECHANICAL NOTES AND OUTLINE SPECIFICATIONS 1.ALL SUPPLY AND RETURN DUCTWORK UNLESS SPECIFICALLY INDICATED IS TO BE IN ASTM A527 LOCK FORMING QUALITY GALVANIZED SHEET METAL WITH ASTM A525 G90 ZINC COATING INSTALLED IN ACCORDANCE WITH CHAPTER 6 OF THE CURRENT ADOPTED VERSION OF IMC AND THE SMACNA DUCT CONSTRUCTION STANDARDS, FOR PRESSURE CLASS "A" FOR 3" SP AND ABOVE, CLASS "B" FOR 2" TO 3" SP AND CLASS "C" FOR 1/4" TO 2" SP, WITH "HARD CAST" SEALED JOINTS. THE USE OF PRESSURE SENSITIVE TAPE WILL NOT BE ACCEPTABLE. DIMENSIONS SHOWN ARE AIRWAY (INSIDE CLEAR) DIMENSIONS. M.C. IS RESPONSIBLE FOR MAKING ALLOWANCES FOR LINER THICKNESS (WHERE APPLICABLE) FOR SHEET METAL DIMENSIONS. 2.INSTALL FULL SIZE CONDENSATE DRAIN WITH TRAP SEAL DEPTH EQUAL TO 1.5 x UNIT TOTAL STATIC PRESSURE FOR EACH COOLING COIL. 3.ALL TYPE "B" VENTS ARE TO HAVE JOINTS SEALED WITH "HARD CAST". THE USE OF PRESSURE SENSITIVE TAPE TO SEAL JOINTS WILL NOT BE ACCEPTABLE. 4.INTERNALLY INSULATE ALL NEW SUPPLY AIR AND RETURN AIR DUCTS THAT ARE INSTALLED OUTSIDE OF THE BUILDING OR IN UN-CONDITIONED SPACES WITH INSULATION HAVING A MINIMUM "R" VALUE OF 8.0. INTERNALLY INSULATE ALL NEW SUPPLY AIR AND RETURN AIR DUCT MAINS THAT ARE INSTALLED IN A CONDITIONED SPACE WITH MINIMUM 1" THICK FLEXIBLE FIBERGLASS, EQUAL TO JOHNS MANSVILLE (LINEACOUSTIC RC). ALL INSULATION IS TO HAVE MINIMUM INSTALLED "R" VALUE OF 5.0, FLAME SPREAD RATING OF 25 OR LESS, SMOKE DEVELOPED RATING OF 50 OR LESS AND BE RATED FOR OPERATING TEMPERATURES UP TO 250° F. DUCT LINERS ARE TO HAVE AN ACRYLIC COATING ON SURFACE IN CONTACT WITH THE AIR STREAM AND AN ANTI- MICROBIAL COATING TO PROHIBIT THE GROWTH OF FUNGUS AND BACTERIA. WRAP ALL ROUND SUPPLY DUCTS. DUCT WRAP IS TO HAVE AN ALUMINUM FOIL FACING. EXTERNALLY INSULATE ALL ENVIRONMENTAL EXHAUST AND CLOTHES DRYER EXHAUST DUCTS IN UNHEATED SPACES WITH MIN. R-8 INSULATION 5.ALL DUCT PENETRATIONS THRU FIRE RATED WALLS, FLOORS, DEMISING WALLS TO HAVE APPROVED AUTOMATIC FIRE DAMPERS OR TO PROVIDE APPROPRIATE FIRE RATED SHAFTS FOR ALL SUCH PENETRATIONS. VERIFY WITH IBC / IMC AND RESPECTIVE CITY. 6.ALL CONCEALED, ROUND SUPPLY AIR DUCTS 12" AND SMALLER ARE TO BE GALVANIZED SHEET METAL SNAP-LOCK. ROUND SUPPLY DUCT GREATER THAN 12" IS TO BE GALVANIZED SHEETMETAL SPIRAL. PROVIDE 1" FIBERGLASS INSULATION WRAP. INSULATED FLEXIBLE DUCT MAY BE USED FOR THE CONNECTION TO THE AIR OUTLET PROVIDED THE LENGTH OF THE FLEXIBLE DUCT DOES NOT EXCEED 6 LINEAR FEET. 7.ALL BRANCH DUCT CONNECTIONS TO AIR OUTLETS AND AIR INLETS ARE TO BE THE SAME SIZE AS THE DEVICE NECK UNLESS SHOWN OTHERWISE ON THE DRAWINGS. 8.ALL GENERAL EXHAUST AND OUTSIDE AIR DUCTWORK IS TO BE GALVANIZED SHEET METAL WITH NO DUCT LINERS. GENERAL DUCTWORK NOTES AND OUTLINE SPECIFICATIONS DESIGN CRITERIA PROJECT SITE:ESTES PARK, CO PROJECT ELEVATION:7,522 FEET SUMMER OUTSIDE:90 DEGREES DB / 60 DEGREES WB WINTER OUTSIDE:-15 DEGREES DB EXTERIOR CONSTRUCTION "U" VALUES WALLS:0.0333 ROOF:0.0204 GLAZING 0.3300 CODES:2009 INTERNATIONAL BUILDING CODE 2009 INTERNATIONAL MECH. CODE W / AMENDMENTS 2009 INTERNATIONAL PLUMBING CODE * OUTSIDE AIR VENTILATION CALCULATION ARE ASHRAE 62.1 2007 COMPLIANT. GENERAL SYMBOL LEGEND DUCTWORK SYMBOL LEGEND TT OS TEMPERATURE TRANSMITTER OCCUPANCY SENSOR ARCHITECTURAL BACKGROUND INCORPORATED INTO MECHANICAL DRAWINGS PROVIDED BY BASIS ARCHITECTURE ON AUGUST 5TH, 2013. T T S S(X HR) SD RT NOTE: FIRST DIMENSION LISTED OF RECTANGULAR DUCT DIMENSIONS REFERENCES THE TOP SIDE OF THE DUCT. ALL DUCT DIMENSIONS ARE AIRWAY (INSIDE CLEAR) DIMENSIONS. D 30"x15" 1830 (3) DUCT OFFSET UP (IN DIRECTION OF FLOW) SUPPLY, RETURN, EXHAUST DUCTS DN SUPPLY, RETURN, EXHAUST DUCTS UP DUCT OFFSET DOWN (IN DIRECTION OF FLOW) THERMOSTAT, PNEUMATIC RETURN AIR SUPPLY AIR TOP OF DUCT BOTTOM OF DUCT EXHAUST AIR MANUAL (OPPOSED BLADE) VOLUME DAMPER UP DN R.A. S.A. T.O.D. E.A. B.O.D. MVD RELIEF AIR FRESH AIR MAKE UP AIR RL.A. F.A. M.A. MOTORIZED DAMPER, OPPOSED BLADE SHOWN COMBUSTION AIRC.A. DUCT MOUNTED SMOKE DETECTOR SMOKE DAMPER COMBINATION FIRE/SMOKE DAMPER (X HOUR RATED) (X HR)FIRE RADIATION DAMPER (X HOUR RATED) HIGH EFF. TAKE-OFF WITH MANUAL LOCKABLE DAMPER THERMOSTAT, ELECTRIC DUCTWORK WITH FLEXIBLE CONNECTION SENSOR (CD - CARBON DIOXIDE, CM - CARBON MONOXIDE, N - NITROGEN, RT - REMOTE TEMPERATURE) MITERED ELBOW WITH TURNING VANES AND SPLITTER TEE WITH TURNING VANES. SPIRAL DUCTWORK (ROUND UNLESS OTHERWISE NOTED AS OVAL ON PLANS) SUPPLY AIR OUTLET - CEILING AND SIDEWALL (NOTE: CEILING DIFFUSERS WILL ONLY HAVE FLOW ARROWS IF DISCHARGE DIRECTION IS CRITICAL). RETURN AIR INLET - DUCTED CEILING GRILLE, CEILING GRILLE TO RETURN PLENUM, AND SIDEWALL GRILLE. GRILLE, REGISTER, OR DIFFUSER TAG. DEVICE TYPE "D", 30"x15" NECK SIZE, 1830 CFM, TYPICAL OF 3. (NOTE: IF QUANTITY IS BLANK TAG PERTAINS TO ONE. IF CFM IS BLANK, CFM IS NOT CRITICAL/BALANCING IS NOT REQ'D. GRILLE TAG FOR GRILLES THAT ARE OF TYPICAL SIZE, WHICH IS LISTED IN THE GRD SCHEDULE. D DUCTWORK WITH ACOUSTICAL LINER (THICKNESS LABELED IN PARENTHESIS) UN-LINED DUCTWORK (SEE SPECIFICATIONS FOR DUCT WRAP REQUIREMENTS)24"x12" 24"x12" (1") Page 43 of 61 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: SCHEDULES M0.1 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 TYPE MANUF. MODEL DESCRIPTION NOTES A TITUS OMNI SUPPLY DIFFUSER 24"x24" FACE WITH FIXED SQUARE PANEL, STEEL CONSTRUCTION, RADIAL DAMPER. 1,2,3 B TITUS OMNI SUPPLY DIFFUSER 12"x12" FACE WITH FIXED SQUARE PANEL, STEEL CONSTRUCTION, RADIAL DAMPER. 1,2,3 C TITUS 272 RL SUPPLY REGISTER, 10"x10" DOUBLE DEFLECTION, 3/4" BLADE SPACING, STEEL CONSTRUCTION, OPPOSED BLADE DAMPER. 1,2 D TITUS 272 RL SUPPLY REGISTER, 8"x6" DOUBLE DEFLECTION, 3/4" BLADE SPACING, STEEL CONSTRUCTION, OPPOSED BLADE DAMPER. 1,2 E TITUS 50 F EXHAUST GRILLE, 12"x12" ALUMINUM CORE GRID, ALUMINUM FRAME, OPPOSED BLADE DAMPER. 1,2,3 F TITUS 50 F RETURN GRILLE, 24"x24" ALUMINUM CORE GRID, ALUMINUM FRAME, OPPOSED BLADE DAMPER. 1,2,3 G TITUS 23 RL RETURN REGISTER, 3/4" BLADE SPACING, STEEL CONSTRUCTION.1,2 GRILLE, REGISTER AND DIFFUSER SCHEDULE NOTES: 1. FACTORY STANDARD WHITE FINISH. 2. REFER TO DRAWINGS FOR NECK SIZE AND AIR QUANTITY. 3. REFER TO ARCHITECTURAL DRAWING FOR CEILING TYPE AND LOCATION OF ALL GRD'S. FT 1 PRICE FDCGQ 2006 0-400 (30) 15% 1.25 0.40 0.55 1/8 208/3 1 A 6 12"x10" 51 / 60 48 / 57 46 / 54 37 / 47 28 / 37 24 / 33 55 / 67 57 / 63 54 / 60 46 / 52 40 / 47 35 / 42 208/3 2.0 125 N 1 THRU 17 A THRU G FT 1 FT 2 PRICE FDCGQ 2008 401-700 (60) 15% 1.25 0.40 0.55 1/4 208/3 2 A 8 12"x10" 55 / 64 54 / 63 55 / 63 49 / 58 34 / 44 33 / 45 64 / 72 60 / 66 55 / 61 52 / 59 46 / 52 41 / 48 208/3 3.5 125 N 1 THRU 17 A THRU G FT 2 FT 3 PRICE FDCGQ 4010 701-1100 (105) 15% 1.25 0.40 0.55 1/2 208/3 3 A 10 14"x12" 62 / 70 60 / 69 59 / 67 50 / 61 42 / 54 40 / 53 67 / 75 64 / 71 59 / 65 58 / 65 51 / 58 43 / 50 208/3 5.5 150 N 1 THRU 17 A THRU G FT 3 SERIES FAN TERMINAL BOX SCHEDULE NOTES: STANDARD FEATURES: 1. LEFT HAND/RIGHT HAND REVERSIBLE CASING. 2. HEAVY DUTY 20 GAUGE ZINC COATED STEEL CASING. 3. 1" COATED FIBERGLASS (1.5 LB. DENSITY) INTERNAL INSULATION. 4. INSULATED/GASKETED ACCESS PANELS WITH QUICK RELEASE LATCHES. 5. SP300 MULTI-POINT, CENTER AVERAGING VELOCITY PRESSURE SENSOR AT PRIMARY AIR INLET. 6. SINGLE NEMA 1 ENCLOSURE FOR FAN AND DAMPER CONTROLS WITH ONE COVER TO ACCESS BOTH. CFM RANGETAG MANUF. MODEL PRIMARY MIN. SET POINT INLET SP ("WC) MAX ESP ("WC) MAX TSP ("WC) MTR. HP.VOLTS/PH FULL LOAD AMPS. DISCH. SIZE MAX. DISCHARGE SOUND POWER LEVELS (dB) AT LOW CFM/ HIGH CFM 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz MAX. RADIATED SOUND POWER LEVELS (dB) AT LOW CFM/ HIGH CFM 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz WEIGHT (LBS) EMERG. POWER OPTIONS 7. PRESSURE INDEPENDENT ELECTRONIC CONTROL. 8. DIRECT DRIVE ECM MOTOR WITH SPEED CONTROL. 9. BUILT-IN BACKWARD ROTATION PREVENTION. 10. FORWARD CURVED BLOWER. 11. FAN AND MOTOR VIBRATION ISOLATION. 12. BUILT IN MOTOR OVERLOAD PROTECTION. 13. HEATING COIL AT DISCHARGE OF BOX. 14. PRIMARY INLET EQUALIZATION BAFFLE FOR NOISE REDUCTION. 15. INTEGRAL 36" LONG ENHANCED INLET ATTENUATOR. 16. INTEGRAL 36" DISCHARGE ATTENUATOR SECTION. 17. SOUND POWER LEVELS INCLUDE ALL ACCESSORY AFFECTS. FACTORY INSTALLED OPTIONS: A. 1" DISPOSABLE FILTER ON R.A. INLET. (2 SETS) B. PRIMARY VOLTAGE HOT LEG FUSE. C. INLET ATTENUATOR WITH TOP OPENING. FIELD INSTALLED OPTIONS: D. 120V-24V TRANSFORMER FOR CONTROLS BY T.C.C. E. REMOTE MOUNTED PROGRAMMABLE (NATIVE BACNET COMPATIBLE) CONTROLLING DIGITAL THERMOSTAT WITH UNOCCUPIED OVER-RIDE AND LCD SCREEN BY T.C.C. F. "NATIVE" BACNET CONTROL PANEL AND INTERFACE BY T.C.C. G. SPRING HANGER BRACKETS. HEATING COIL VOLTS/ PH KW - MAX. ESP IS STATIC PRESSURE LOSS DOWNSTREAM OF DISCHARGE SILENCER (WHERE APPLICABLE) AND UPSTREAM OF INLET ATTENUATOR. - MAX. TSP = MAX. ESP + FILTER, INLET ATTENUATOR, INTERNAL BOX LOSSES, HEATING COIL, AND SILENCER (WHERE APPLICABLE). - SEE PLANS FOR ACTUAL AIRFLOWS AND VARIATIONS OF PRIMARY MIN. SET POINTS. SHUT-OFF VARIABLE VOLUME BOX SCHEDULE NOTES: STANDARD FEATURES: 1. 22 GAUGE ZINC COATED STEEL CABINET. 2. INSULATED (1/2" FIBERGLASS) CABINET. 3. GASKETED TIGHT SHUT OFF PRIMARY AIR DAMPER BLADE. 4. LEFT/RIGHT HAND CONFIGURATION (SEE PLANS) WITH INTEGRAL GAUGE TAPS. 5. PRICE SP300 MULTI- POINT VELOCITY PRESSURE SENSOR AT PRIMARY AIR INLET. 6. PRESSURE INDEPENDENT ELECTRONIC CONTROL. TAG MANUF. MODEL CFM RANGE @ 1" INLET SP MAX. DISCHARGE SOUND POWER LEVELS (dB) AT LOW CFM/ HIGH CFM 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz MAX. RADIATED SOUND POWER LEVELS (dB) AT LOW CFM/ HIGH CFM 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz WEIGHT (LBS) EMERG. POWER NOTES FACTORY INSTALLED OPTIONS: A. 1/2" COATED FIBERGLASS CABINET INSULATION. B. 1" COATED FIBERGLASS CABINET INSULATION. C. DOUBLE WALL CABINET WITH INSULATION AND SOLID INTERNAL WALL. D. DOUBLE WALL CABINET WITH INSULATION AND PERFORATED INTERNAL WALL. E. DOUBLE WALL WITH FOIL FACED INSULATION AND PERFORATED INTERNAL WALL. F. DOUBLE WALL WITH INSULATION, WOVEN FABRIC, AND PERFORATED INTERNAL WALL. FIELD INSTALLED OPTIONS: G. REMOTE MOUNTED PROGRAMMABLE (NATIVE BACNET COMPATIBLE) DDC THERMOSTAT WITH UNOCCUPIED OVER-RIDE & LCD SCREEN BY T.C.C. H. CONTROLS (NATIVE BACNET) INTERFACE BY TCC. I. CONTROLS ENCLOSURE BY TCC. J. DAMPER ACTUATOR BY TCC. K. DISCHARGE ATTENUATOR. VAV 1 PRICE SDVQ-06 0-450 50 0.40 50 / 58 45 / 55 42 / 51 33 / 41 25 / 30 24 / 20 50 / 57 39 / 48 35 / 44 29 / 38 26 / 33 22 / 27 6 12x8 25 N 1 THRU 6 A,H THRU J VAV 1 VAV 2 PRICE SDVQ-08 451-800 50 0.40 54 / 60 51 / 57 47 / 52 40 / 45 31 / 36 25 / 29 55 / 60 45 / 51 38 / 43 33 / 38 29 / 33 30 / 33 8 12x10 35 N 1 THRU 6 A,H THRU J VAV 2 PRIMARY MIN. CFM MAX. PD. ("WC) INLET SIZE " DIA DISCH. SIZE OPTIONS - ACTUAL AIRFLOW OF EACH DEVICE WILL BE LISTED ON THE PLANS. - IF MIN. SET POINT IS HIGHER THAN WHAT IS LISTED ABOVE FOR ANY GIVEN DEVICE, IT WILL BE LISTED ON THE PLANS. - TCC IS RESPONSIBLE FOR COORDINATING NUMBER AND LOCATIONS OF 120V TO 24V TRANSFORMERS FOR CONTROLS WITH E.C. GENERAL NOTES: INLET SIZE " DIA NOTES GENERAL NOTES: TAG TAG ROOF TOP UNIT SCHEDULE BULB TYPE 100% O.A. ECONOMIZER. 3. INTEGRATED MICROPROCESSOR BASED DRY 18. DIRECT DRIVE INDUCED DRAFT BURNER. 19. DIRECT SPARK IGNITION. 20. STAINLESS STEEL TUBULAR HEAT EXCHANGER. 8. INTEGRAL SPRING ISOLATORS ON COMPRESSORS. 9. COMPRESSOR ANTI-CYCLE TIMER. RTU-1 TAG NOTES: QTY TRANE YHD240 MANUFAC.MODEL CENTIF. FC---1 9,000 TYPESIZE CFM 11. COMPRESSOR PRESSURE SAFETY SWITCH WITH AUTOMATIC RESET. MAX OA 21. FLAME PROVING SWITCH. 6. COMPRESSOR MOTOR THERMAL AND CURRENT OVERLOADS. 10. REFRIGERANT SERVICE VALVES ON COMPRESSOR. 2,5501" 2.9 ECON. MIN OA SUPPLY FAN DATA ESP TSP 10.0 BELT 921 NAT. GAS DRIVEHP RPM TYPE FUEL 5. SINGLE POINT POWER CONNECTION. 324/243400/300 MBH OUTPUT HEATING COIL DATA @ 7,522 FT. ELEVATION MBH INPUT ( F) EAT 3/4" DX. 226 ( F) LAT CONN. GAS TYPE COIL TOTAL COMPRESSORS 17. INSULATED (2" FIBERGLASS) CABINET. LAT 52209 ROWS/FINS COOLING COIL DATA @ 7,522 FT. ELEVATION SENS.EAT 410a95 SCROLL REFG. TYPE°F AMB TYPE 2 TAW 20x20x2/ 4/4 QTY. FILTERS TYPEQTY SIZE 1 THRU 27208/3 120 150 V/PH UNIT MCA MOCP UNIT 102,400 MIN. UNIT EER(LBS) OP. WEIGHT NOTES RTU-1 TAG 40 4/15 A,B,F,H,I,J, M THRU V. OPTIONS 22. HIGH TEMPERATURE SWITCH. 1. DDC/VAV CONTROLS. 2. SUPPLY FAN VARIABLE FREQUENCY DRIVE W/BYPASS 4. FULLY MODULATION OA AND RA DAMPERS 7. COMPRESSOR CRANKCASE HEATER. 12. DUAL INDEPENDENT REFRIGERANT CIRCUITS/INTERTWINED EVAPORATOR COIL. 13. LIQUID LINE SERVICE VALVE FILTER DRIER AND THERMAL EXPANSION VALVE. 14. ALUMINUM FIN/COPPERTUBE EVAPORATOR COIL. 15. PILLOW-BLOCK FAN SHAFT BEARINGS. 16. FULLY MODULATING GAS VALVE. 23. ALUMINIZED STEEL SLOPED CONDENSATE DRAIN PAN. @S.L. IN NEMA 1 ENCLOSURE. 125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz MAX. DISCHARGE SOUND POWER LEVELS (dB) AT HIGH CFM WITH ACOUSTICAL CURB 83 83 83 85 79 78 8073 20x25x2 A. HOT GAS BYPASS TO EVAPORATOR INLET ON EACH COMPRESSOR. FACTORY INSTALLED OPTIONS: Q.18" TALL FACTORY ACOUSTICAL ROOF CURB FIELD INSTALLED OPTIONS: R. CONDENSER COIL HAIL GUARDS. S. ECONOMIZER O.A. HOOD WITH BIRDSCREEN. WITH INTEGRAL VIBRATION ISOLATION RAILS. D. BACNET INTERFACE MODULE. B. HINGED (INSULATED) ACCESS DOORS. C. RETURN FAN VFD WITH BYPASS IN NEMA 1 ENCLOSURE DOORS. E. DOUBLE WALL CONSTRUCTION. F. SUCTION LIQUID AND DISCHARGE I. ULTRA LOW LEAK O.A./E.A./R.A. DAMPERS G. S.S. FLUE STACK H. REPLACEABLE CORE FILTER DRIERS J. MERV 14 CARTRIDGE FILTERS. K. LIQUID AND DISCHARGE SERVICE VALVES SERVICE VALVES L. NON-FUSED DISCONNECT SWITCH T. 120V CONVENIENCE OUTLET (WIRED BY E.C.) SHUT-OFF VARIABLE VOLUME BOX W/ ELECTRIC COIL SCHEDULE FIELD INSTALLED OPTIONS:FACTORY INSTALLED OPTIONS: OPTIONS TAGNOTESPOWER EMERG. N 1 THRU 63512x10 MIN. CFM CFM RANGE @TAG NOTES: MANUF. MODEL 7" RND0.40350351-650VAV-3 1" INLET SP PRICE SDV5 MIN./MAX. DISCHARGE NC MIN./MAX. RADIATED NC INLET SIZE DISCH. SIZE WEIGHT (LBS) MAX. PD. ("WC) PRICE SP300 MULTI- POINT VELOCITY PRESSURE SENSOR AT PRIMARY AIR INLET. PRESSURE INDEPENDENT ELECTRONIC CONTROL. GASKETED TIGHT SHUT- OFF PRIMARY AIR DAMPER BLADE. LEFT/RIGHT HAND CONFIGURATION (SEE PLANS) WITH INTEGRAL GAUGE TAPS. 4. 5. 6. 3. 2. 1.1/2" COATED FIBERGLASS CABINET INSULATION.A. 1" COATED FIBERGLASS CABINET INSULATION.B. G. H. J. CONTROLS (NATIVE BACNET) INTERFACE BY TCC. L. DAMPER ACTUATOR BY TCC.K. CONTROLS ENCLOSURE BY TCC. DISCHARGE ATTENUATOR. -SOUND POWER PERFORMANCE RESULTING IN DASHED (--) ARE BELOW SIGNIFICANCE AS OUTLINED BY THE AHRI880-2011 STANDARD. -ACTUAL AIRFLOW OF EACH DEVICE WILL BE LISTED ON THE PLANS. -IF MIN. SET POINT IS HIGHER THAN WHAT IS LISTED ABOVE FOR ANY GIVEN DEVICE, IT WILL BE LISTED ON THE PLANS. -TCC IS RESPONSIBLE FOR COORDINATING NUMBER AND LOCATIONS OF 120V TO 24V TRANSFORMERS FOR CONTROLS WITH E.C. B, H THRU L C. D.DOUBLE WALL CABINET WITH INSULATION AND PERFORATED INTERNAL WALL. E.DOUBLE WALL WITH FOIL FACED INSULATION AND PERFORATED INTERNAL WALL. F.DOUBLE WALL WITH INSULATION, WOVEN FABRIC, AND PERFORATED INTERNAL WALL. 22 GAUGE ZINC COATED STEEL CABINET. INSULATED (1/2" FIBERGLASS) CABINET. DOUBLE WALL CABINET WITH INSULATION AND SOLID INTERNAL WALL.. REMOTE MOUNTED PROGRAMMABLE (NATIVE BACNET COMPATIBLE) DDC THERMOSTAT WITH UNOCCUPIED OVER-RIDE & LCD SCREEN BY T.C.C. VAV-3 PRIMARY STANDARD FEATURES: GENERAL NOTES: REHEAT CFM CAPACITY kW VOLTS STEPS CURRENT AMPS EAT °F LAT °F -- -- 200 1.52 208/3 1 4.16 55 400 HP. 5 24. FOIL FACED CABINET INSULATION. U. CO2 SENSOR IN MAIN R.A. DUCT. V. SMOKE DETECTOR IN R.A. M. VFD DUTY RATED SUPPLY FAN MOTOR. N. MODULATING GAS (5:1 TURN DOWN). O. POWERED EXHAUST FAN WITH VFD. 1 ENCLOSURE DOORS. 25. 5-YEAR COMPRESSOR AND HEAT EXCHANGER WARRANTY. 26. 3-STAGE COOLING. 27. SUPPLY FAN MOTOR SHAFT GROUNDING RING. UNITCFM S.P. 6000 0.50 P. U.L. LISTED FOR DUAL POINT POWER. FAN AND BURNER ON E-POWER. Page 44 of 61 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: SCHEDULES M0.2 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 EXHAUST FAN SCHEDULE ALL ALUMINUM CONSTRUCTION. BIRDSCREEN. FACTORY INSTALLED OPTIONS:ALUMINUM MOTOR COVER 4. ADJUSTABLE MOTOR PULLEY. 5. MOTOR VIBRATION ISOLATORS. NEMA 1 DISCONNECT SWITCH. 3. INTERNAL CONDUIT CHASE. BACKWARD INCLINED ALUMINUM FAN WHEEL. SERVICELOCATIONTAG NOTES: 2. 1. MANUF. MODEL 6. FAN DATA DIAM. (IN) E.S.P. (IN W.C.)CFM TOTAL TYPE MAX SONES MAX RPM MOUNT B. A.14" PRE-FABRICATED ROOF CURB OPTIONS FIELD INSTALLED OPTIONS: H.P. MOTOR DATA DRIVE VOLTS/PH D. OP. WT. (LBS) EMERG. POWER NOTES TAG C. ALUMINUM BACKDRAFT DAMPER. 7. HEAVY GAUGE GALVANIZED STEEL HOUSING. CUE-090-VGROOFEF-1 GREENHECK 9.50.35450 CENTRIF. UPBLAST 1,300 CURB5.5 A,B,C,D,G1/6DIRECT 115/1 50 N 1 THRU 6 EF-1WOMENS DETOX RESTROOMS CUE-070-DROOFEF-2 GREENHECK 7.00.30200 CENTRIF. UPBLAST 1,550 CURB4.5 1/30 115/1 35 N 1 THRU 6 EF-2WOMENS CONF RM/ EXAM RM ROOFEF-3 GREENHECK EF-3MEETING RM RR/ STAFF BATH CUE-080-VGROOFEF-4 GREENHECK 0.35300 CENTRIF. UPBLAST 1,550 CURB7.0 1/30 115/1 33 N 1 THRU 6 EF-4MED ROOMS ROOFEF-5 GREENHECK EF-5MENS CONF RM/ EXAM RM 200 CENTRIF. UPBLAST CURB N 1 THRU 6 CUE-080-D 0.30350 CENTRIF. UPBLAST 1,550 CURB7.0 1/20 115/1 35 N 1 THRU 6 ROOFEF-6 GREENHECK EF-6MENS DETOX RESTROOMS CUE-090-VG 0.35500 CENTRIF. UPBLAST 1,300 CURB5.5 1/6 115/1 50 N 1 THRU 6 EXTENDED BASE SOUND CURB WITH INTERNAL BAFFLES.E. SOLID STATE SPEED CONTROLLER INSTALLEDF. DOWNSTREAM OF DISCONNECT SWITCH UNDER MOTOR COVER. ROOF GREENHECK EF-7CUE-070-D 200 CENTRIF. UPBLAST CURB N 1 THRU 6BU BATHSEF-7 DIRECT DIRECT DIRECT DIRECT DIRECT DIRECT CUE-070-D 0.30 1,550 4.5 1/30 115/1 35 0.30 1,550 4.5 1/30 115/1 35 FACTORY INSTALLED OPTIONS: BUILT-IN SNAP ACTING THERMOSTAT. BUILT-IN DISCONNECT SWITCH.3. 4. 5. 2. NOTES: 1. HIGH TEMPERATURE CUT OUT SWITCH WITH MANUAL RESET. 16 GAUGE FRONT BAR GRILLE. STEEL SHEATHED FINNED ELEMENT. FAN OFF DELAY. 18 GAUGE STEEL HOUSING. B. A. FIELD INSTALLED OPTIONS: FULL RECESSED MOUNTING FRAME.C. 4" SURFACE MOUNTING FRAME.D. WALL CABINET UNIT HEATER SCHEDULE MBHLOCATIONTAGMANUFACTURER MODEL TYPE CFM OPTIONSAMPSKW HP VOLTS/PH OP. WT. (LBS) MOUNTING NOTES TAG CUH-1 MARKEL CUH-110.2F3425T RECESSED 245 A, B, C3.0 --- 208/1 14.4 VERTICAL 41 1 THRU 5NORTH & EAST VESTIBULES ELECTRIC BASEBOARD HEATER SCHEDULE B. INTEGRAL DISCONNECT SWITCH. WATTS FACTORY INSTALLED OPTIONS: A. INTEGRAL UNIT MOUNTED LINE VOLTAGE THERMOSTAT. MANUFACTURER 6. PRE-WIRED J-BOX. 4. STEEL TUBULAR ELEMENT. LOCATIONTAG SERVICE 3. HEAVY DUTY CONSTRUCTION. 2. 16 GAUGE FRONT COVER. 1. WALL MOUNTED.NOTES: 5. ALUMINUM FINS. MODEL TYPE LENGTH 8. AUTOMATIC HIGH TEMP. CUT OUT SWITCH. 7. BUILT-IN WIREWAY. OPTIONSEMERG.VOLTS/PH BTU/H NOTESPWR.TAG EBB-1 EBB-1A, BN1 TO 8255075040"F2907-040SW SURFACE MOUNTEDMARKEL 208/1WATER ENTRY WATER ENTRY ELECTRIC RADIANT PANEL HEATER SCHEDULE RADIANT SURFACE.INSULATION. 4.6. 5. GRAPHITE HEATING ELEMENT. CRYSTALLINE PRE-WIRED J-BOX. 1.3. 2. NOTES:24 GAUGE STEEL BACK. 1" HIGH TEMPERATURE FIBERGLASS 22 GAUGE STEEL FRONT COVER. OPTIONSEMERG. PWR.NOTES B,CN1 TO 6 RP-1 TAGBTU/H B. A. VOLTS/PH 2550120/1 SIZETYPE 24"X48" 750 WATTS WALL MOUNTED 24V SENSOR BY T.C.C. EXTRUDED ALUMINUM SURFACE MOUNTING FRAME. FIELD INSTALLED OPTIONS: MODEL CP7501 SERVICE MANUFACTURER AZTEC (QMARK) TAG LOCATION RP-1 RECESSED MOUNTEDDETOX RESTROOMS C. 120V LINE VOLTAGE ROOM THERMOSTAT. DETOX RESTROOMS 7.0 8.0 7.0 7.0 9.5 CUH-2 MARKEL CUH-210.2SURFACE6333DMOUNT230 A, B, D3.0 --- 208/1 15.4 VERTICAL 99 1 THRU 5SOUTH VESTIBULE A,B,C,D,F A,B,C,D,F A,B,C,D,G A,B,C,D,F A,B,C,D,G A,B,C,D,F ECM MOTOR FOR 2-SPEED OPERATION FROM BAS.G. Page 45 of 61 CUH 1 CUH 2 1 RP 3 (650) FT 2 (375) FT 3 (650) FT 3 (1000) FT 1 (225) FT M401M100 1 M401 M100 2 3 (600) FT 8"ØA125 8"ØA125 6"ØB75 8"ØA125 8"ØA125 10"ØA225 6"ØA75 8"ØA200 8"ØA100 1 (175) VAV 10"x10" 10 " ø 8"ØA200 8"ØA200 8"ØA200 8"ØA200 8"ØA200 8"ØB100 1 (300) VAV 8"ØA200 10"ØA250 2 (650) VAV 12"x12" 8"ØA200 8"ØA100 12"ØA325 8"x6"D 150 8"ØA200 8"ØA200 8"ØA200 8"ØA200 14"x14" 6"ØB50 10 " x 1 0 " 10"x10" 1 (375) VAV 6"ØB50 6"ØB50 8"x8" 8"ØA200 6"ØB50 26"x20" S.A. 10"x10"C 300 (2) 10 " x 1 0 " 8"ØA200 8" x 8 " 6"ØA75 8"ØA100 1 (175) VAV 6"ØA75 26"x14" S.A. 26 " x 1 4 " S . A . 30"x14" S.A. 8"ØB200 12 " ø 12 " x 1 2 " 10"x10"C 300 1 RP 2 (375) FT 3 (600) FT 10"x10"C 300 (2) 10"ØA300 10 " x 1 0 " 1 RP 1 RP 8"ØA200 10"ØA250 14"x14" 10"ØA300 8"ØA100 10"x10" 3 (1000) FT 8"ØA200 8"ØA150 8"x8"E 75 8"x8"E 75 8"x8"E 100 8"x8"E 100 12"ø E.A. 6"ØB50 (2) 8"x8"E 100 8"x8"E 100 8"x8"E 100 8"x8"E 100 8"x8"E 100 10 " x 1 0 " 8"x8"E 75 8"x8"E 1008"x8"E 75 8"x8"E 100 8"x8"E 100 8"x8"E 75 8"x8"E 75 8" ø 8"x8"E 100 8"x8"E 100 8"x8"E 75 8"x8"E 75 2 (600) VAV 12 " x 1 2 " TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT TT 1 1 1 1 1 1 1 1 1 1 1 2 (450) FT TT 11 1 (225) FT 1 (225) FT 12"x12" 12"x12" 8" ø E . A . 8"x8"E 100 6"ØB50 8"x6"D 75 (3) 8"x6"D 75 (3) 8"ø 10"x10" 10 " x 1 0 " 12"x12"G 0 10 " x 1 0 " 12"x12"G 0 M401M100 3 S S 1 SD 12"x12" 8"x8" 8"x8" 6"ØB75 TT TT 6"ØB75 DN DN 3 (650) FT 2 2 CUH 1 DN DN DN DN 3 3 30"x14" S.A. UP 1 4 1 EBB SD 1 1 3 3 4 4 1 1 8"x8"E 100 8"x8"E 50 4 4 4 1 SEMI-PRIVATE SEMI-PRIVATE LIVING WOMEN'S BATHROOM LOCKERS/ CHANGING AREA PRIVATE BATHROOM WOMEN'S SLEEPING AREA MEN'S SLEEPING AREA SEMI-PRIVATE SEMI-PRIVATE LIVING PRIVATE PRIVATE NURSE'S STATION HALL PRIVATE BATHROOM LOCKERS/ CHANGING AREA MEN'S BATHROOM MECH/ SPRINKLER JAN PHONE EXAM RM CONF RM HALL MEN'S ENTRY MEN'S WAITING WOMEN'S WAITING CONF RM EXAM RM HALL WOMEN'S ENTRY STAFF LOUNGE OFFICE OFFICE OFFICE OFFICE MEETING ROOM STG BATH HALL OFFICE STAFF BATH HALL STAFF LOCKERS STAFF LOCKERS RETAILADMISSION BUSINESS CENTER MEET + GREET OFFICE ADMISSION ENGAGEMENT COUNSELOROFFICEOFFICEOFFICE OFFICE BATH BATH COURTYARD COURTYARD MED MED MED MED A B B.6 C D D.6 E E.3 F G H I I.1 1 2 3 4 4.1 5 5.9 6 7 8 9 RECEPTION 12"x12" 4 4 SD 30"x20" R.A. 8"ø E.A. 8"ø E.A. F F F F F FFF F F F F F F F F F F F F 10"x10"C 300 F F F F 2 (700) VAV F F DN DNF DN 50"x20" S.A. 5 6 3"ø E.A. 3"ø O.A. 3 7 26"x40" S.A. 5 M401 M100 4 5 26"x14" S.A. 12"x12" 2 1 5 DN DN 1 8 1 12"ØA325 2 14"x14" 12"x8" 4 4 F F 4 4 4 4 12"x12" 10"x10" 10"x10" 4 12"x12"G 0 8"x6"D 125 (2) 8"x6"D 125 (2) 12"x12" 6"ø E.A. 2 6"ØB75 2 6"ØB75 9 3 12"ø E.A.10"ø E.A. 8"ø E.A. 10"ø E.A. 10"ø E.A. 8"ø E.A. 8"ø E.A. 8"ø E.A. 8"ø E.A. 8"ø E.A. 8"ø E.A.10"ø E.A. 10"ø 8"x8" M400 7 (TYP) M400 3 12"x6"G 0 12"x12"G 300 - - - - - - - - - - - - - - - 10"x10"G 0 10"x10"G 0 - - - - - - T T 10 11 11 PUBLIC ENTRY 8 8 3"ø E.A. 3"ø O.A.9 12 8"x6"D 150 3 (600) FT M400 1 12"x12" 6"ØB75 13 8"x8"E 75 8"x8"E 75 M500 1 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: LEVEL ONE HVAC PLAN M100 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 2' 8'1' 4' 3/16" = 1'-0" LEVEL ONE HVAC PLAN 1. INLET DUCT TO VAV/FAN TERMINALS SHALL BE SAME AS CONNECTION SIZE UNLESS NOTED OTHERWISE. GENERAL MECHANICAL NOTES KEY NOTES 1 PACK END OF DUCT WITH 4" LINACOUSTIC INSULATION. 2 COORDINATE 24" X 24" ACCESS PANEL, RE: ARCHITECTURAL. 3 RE: ARCHITECTURAL DRAWINGS FOR SOFFIT TO CONCEAL DUCTWORK. 4 COORDINATE TO PROVIDE MINIMUM 1" UNDERCUT OF DOOR. 5 MITERED 90 DEG. ELBOW WITH AIR FOIL TYPE TURNING VANES. 6 TRANSFER AIR DUCT THROUGH SMOKE BARRIER TO JOIN PLENUMS. 28"X28" OPENINGS ON TOP OF DUCT. 7 TRANSITION VERTICAL SUPPLY DUCT FROM RTU TO VERTICAL SUPPLY TRUNK SIZE NOTED. 8 PROVIDE K-27 DOUBLE WALL DUCTWORK AT THIS LOCATION. (INDICATED BY HATCH) 9 3" DIA. CPVC COMBUSTION AIR AND 3" CPVC FLUE. 10 PROVIDE TITUS OMNI OPTIONAL DIRECTIONS BLOW CLIPS (MODEL DB) AT THIS LOCATION TO CONVERT TO A 2-WAY BLOW. 11 PROVIDE TITUS OMNI OPTIONAL DIRECTIONS BLOW CLIPS (MODEL DB) AT THIS LOCATION TO CONVERT TO A 3-WAY BLOW. 12 ROOF ACCESS AREA. RE: ARCH DWGS. 13 SPLITTER TEE WITH AIR FOIL TURNING VANES IN MAIN S.A. DUCT. 70%/30% SPLIT WITH 70% OF AIR BEING DIRECTED TOWARDS THE NORTH. PLAN NORTH Page 46 of 61 M401M100 1 M401 M100 2 8"ø E.A.8"ø E.A. 12"ø E.A. 8"ø E.A. 12"ø E.A. 12"ø E.A. 12"ø E.A. 10"ø E.A. 12"ø E.A. 14"ø E.A. 10"ø E.A. 10"ø E.A. 14"ø E.A. 10"ø E.A. 10"ø E.A. 14"ø E.A. 12"ø E.A. A B B.6 C D D.6 E E.3 F G H I I.1 1 2 3 4 4.1 5 5.9 6 7 8 9 8"ø E.A. 8"ø E.A. 8"ø E.A. DN 50"x20" R.A. 3"ø E.A. 3"ø O.A. 1 1 2 3 M401 M100 4 4 2 4 5 M400 4 M400 1 1 1 1 1 1 6 6 6 6 6 6 7 7 7 7 7 8 8 8 9 3" V 3" V 10 10 50"x20" R.A. 50"x20" R.A. S S 3"ø O.A. 3"ø E.A. 3 7 7 11 12"ø E.A. 6"ø E.A. 6 6 6 6 6 M500 1 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: ATTIC HVAC PLAN M200 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 4' 16'2' 8' 3/16" = 1'-0" ATTIC HVAC PLAN KEY NOTES 1 MIN. 26" GAUGE CONSTRUCTION. 2 50" X 20" RETURN BOOT OPENING ON TOP OF DUCT. 3 DWH COMBUSTION AIR AND FLUE UP TO CONCENTRIC VENT ON ROOF. 4 PACK END OF DUCT WITH 4" LINACOUSTIC INSULATION. 5 PROVIDE BEVELED TAP TO BE INSTALLED FACING THE DIRECTION OF AIRFLOW. 6 DUCT WITH RADIATION DAMPER AT RATED PENETRATION. (RE: M100 FOR CONTINUATION.) 7 E.A. DUCT UP AND TRANSITION TO EF INLET ON ROOF. 8 AREA WITHIN BOUNDARY IS PLENUM SPACE. AREA OUTSIDE OF BOUNDARY IS ATTIC SPACE. 9 20"X50" R.A. DUCT UP AND TRANSITION TO UNIT CONNECTION. 10 PROVIDE K-27 DOUBLE WALL DUCTWORK AT THIS LOCATION. (INDICATED BY HATCH) 11 ROOF ACCESS AREA. RE: ARCH DWGS. PLAN NORTH Page 47 of 61 M401M100 1 M401 M100 2 EF 1 EF 3 EF 4 EF 5 EF 6 EF 2 EF 7 AHU 1 M401M100 3 A B B.6 C D D.6 E E.3 F G H I I.1 1 2 3 4 4.1 5 5.9 6 7 8 9 3' - 0" 5' - 0" 4' - 0" 5' - 8" 1 2 3 4 5 M401 M100 4 6 M400 6 3" V 3" V 7 7 6 M400 2 M400 4 M400 5 (TYP) M400 1 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: MECHANICAL ROOF PLAN M300 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 2' 8'1' 4' 3/16" = 1'-0" MECHANICAL ROOF PLAN KEY NOTES 1 RE: STRUCTURAL DWGS. FOR AHU CONCRETE PAD DETAILS. 2 RE: ARCH FOR LOCATION AND DETAIL INTEGRATION OF SKYLIGHTS. 3 ALL EXHAUST FANS ON 14" CURBS. 4 RE: ARCH. DWGS. FOR LOCATION OF ROOF ACCESS. 5 COORDINATE TOP OF FLU EXTENSIONS KIT TO BE LEVEL WITH TOP OF AREA WELL WALLS. 6 CONCENTRIC VENT TERMINATION KIT. 7 3" V THROUGH ROOF. PLAN NORTH Page 48 of 61 MIN. 1" CLEARANCE TO COMBUSTIBLES. 3" DIA. PVC INTAKE/ COMBUSTION AIR ROOF DECK 39" 3" DIA. PVC VENT/EXHAUST 4 1/2" DIA. 21" FLASHING 1-3/16" 1-1/2" ELASTOMERIC SEALANT ELASTOMERIC SEALANT INSULATION ROOFING HV A C D U C T 12" MIN. 4" MIN. SCREW CURB FLASHING TO TOP OF CURB BLOCKING. M.C. TO PROVIDE AND INSTALL DUCT FLASHING. M.C. TO PROVIDE AND INSTALL CURB FLASHING. G.C. TO EXTEND ROOF MEMBRANE OVER TOP OF CURB BLOCKING. TREATED WOOD BLOCKING BY G.C. ROOF DECK STEEL ANGLE AT PERIMETER OF OPENING BY G.C. RE: STRUCT. OPENING IN TOP OF DUCT, TYP. OF 2. WALL WITH ACOUSTICAL INSULATION RE: ARCH SEE PLANS FOR LIFE SAFETY DAMPER REQUIREMENTS AT WALL PENETRATION H SEE PLANS FOR DUCT AND OPENING DIMENSIONS. INSTALL WITH 1" "LINACOUSTIC" LINER UNLESS OTHERWISE NOTED ON PLANS L = 4 x H * * - 10'-0" MAX. ADJUST AS NECESSARY FOR SPACE AVAILABLE LINED ENDCAP, TYP. OF 2. 5'-0", TYPICAL 10'-0" ALL BRANCH TAKE-OFFS TO CONNECT TO UNLINED PORTION OF SHEET METAL TRUNK DUCT UNLESS OTHERWISE NOTED ON PLANS "PRIMARY" AIR SUPPLY DUCT. SEE PLANS FOR SIZE. WRAP PER SPECIFICATIONS "SECONDARY" AIR INLET ATTENUATOR (FACTORY ASSEMBLED AND INSTALLED) WITH FILTER RACK ON TOP FILTER ACCESS CONTROLS ACCESS PACK END CAP OF DISCHARGE TRUNK DUCT WITH 2" "LINACOUSTIC" INSULATION MOTOR ACCESS VALVE & COIL ACCESS 3'-0" CHANGE IN DIRECTION FITTINGS (SPLITTER TEE WITH TURNING VANES OR RADIUS'D ELOW) W/IN FIRST 10'-0" OF TRUNK DUCTWORK TO BE LINED WITH 1" "LINACOUSTIC" LINER. 3'-0" LONG SHEET METAL TRUNK DUCT WITH 1" "LINACOUSTIC" LINER OR DISCHARGE SILENCER. REFER TO PLANS AND/OR SCHEDULE FOR DISCH. SILENCER REQUIREMENTS. SH E E T M E T A L D U C T W I T H 1" " L I N A C O U S T I C " L I N E R UN - L I N E D SH E E T M E T A L DU C T REFER TO PLANS AND/OR SCHEDULE FOR DISCHARGE SELENCER REQUIREMENTS WRAP UN-LINED DUCTWORK PER SPECIFICATIONS. 3'-0" FILTER ACCESS CONTROLS ACCESS MOTOR ACCESS VALVE & COIL ACCESS "SECONDARY" AIR INLET ATTENUATOR (FACTORY ASSEMBLED AND INSTALLED) WITH FILTER RACK ON TOP "PRIMARY" AIR SUPPLY DUCT. SEE PLANS FOR SIZE. WRAP PER SPECIFICATIONS PACK END CAP OF DISCHARGE TRUNK DUCT WITH 2" "LINACOUSTIC" INSULATION SHEET METAL DUCT WITH 1" "LINACOUSTIC" LINER UN-LINED SHEET METAL DUCT ALL BRANCH TAKE-OFFS TO CONNECT TO UNLINED PORTION OF SHEET METAL TRUNK DUCT UNLESS OTHERWISE NOTED ON PLANS WRAP UN-LINED DUCTWORK PER SPECIFICATIONS. 6" RTU'S AND MAU STEEL ANGLE AT PERIMETER OF OPENING. RE: STRUCT. CONCRETE PAD COORD. LOCATION OF OPENING W/ G.C. METAL CURB. FURNISHED WITH UNIT WRAP CURB WITH RIGID BOARD INSULATION SCREWED INTO CURB SEALANT & BACKER ROD MEMBRANE FLASHING FULLY ADHERED TO INSULATION W/ BONDING ADHESIVE LAP SEALANT. METAL DECK SHEET METAL FLANGE 6"Ø E.A. DUCT. MIN. 1" CLEARANCE TO BE FIRE CAULKED. 1 HR. LID1 HR. LID UNION 1 2 3 1 2 3 DISTANCE EQUAL TO A NEGATIVE STATIC PRESSURE (IN. W .C.) +1" OR POSITIVE STATIC PRESSURE (IN. W.C.) +1". SEE MECH. SCHEDULES FOR STATIC PRESSURE INFORMATION. MINIMUM DISTANCE EQUAL TO NEGATIVE STATIC PRESSURE (IN. W.C.) +1". OR A POSITIVE STATIC PRESSURE (IN. W.C.) +1". MINIMUM DRAIN PIPE SIZE EQUAL TO CONNECTION PROVIDED WITH EQUIPMENT. EQUIPMENT PAD UNIT CASING TO APPROVED LOCATION 1" AIR GAP FULL SIZE VENT/PRIMER OPENING CLEANOUT WITH PLUG DRAIN CONNECTION NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: DETAILS M400 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 SCALE:NOT TO SCALE1CONCENTRIC VENT SCALE:NOT TO SCALE4RECTANGULAR DUCT CURB SCALE:NOT TO SCALE3TRANSFER AIR "U" BOOT SCALE:NOT TO SCALE7FAN TERMINAL ATTENUATION SCALE:NOT TO SCALE5CONCRETE PAD ROOF CURB SCALE:NOT TO SCALE2E.A. DUCT THRU LID SCALE:NOT TO SCALE6COIL DRAIN PAN PIPING Page 49 of 61 FIRST FLOOR 100' - 0" MECH WELL 118' - 11 1/2" M401 M100 2B.6 C D D.6 E M401 M100 4 20"x76" R.A. 26"x66" S.A. 26"x40" S.A. 20"x50" R.A. 20"x50" R.A. 50"x20" S.A. 1 2 3 44 5 6 12"ø E.A. 8"ø E.A. 8"ø E.A. M400 5 M400 4 1 11 EF 4 EF 2 AHU 1 FIRST FLOOR 100' - 0" MECH WELL 118' - 11 1/2" M401M100 1 M401M100 3 4 4.1 5 5.9 6 7 M400 2 7 12"ø E.A.10"ø E.A.14"ø E.A. 12"x12" S.A. 3 (650) FT 1 (225) FT EF 1 EF 4 EF 5 EF 6 EF 3 6 6"ø S.A. FIRST FLOOR 100' - 0" MECH WELL 118' - 11 1/2" M401 M100 2 B B.6 1 2 "x 1 2 " 12"x12" 6"ø 3 (650) FT 8 6"ø 8"x8"8"x6"D 125 8"x6"D 125 FIRST FLOOR 100' - 0" MECH WELL 118' - 11 1/2" M401M100 1 4 4.1 5 5.9 6 926"x20" S.A. 12"ø S.A. 8"ø S.A. 3 (600) FT 3 (600) FT 10"ø E.A. 10"ø E.A. 14"ø E.A. 12"ø E.A. 10"ø E.A. 12"ø E.A. 20"x50" R.A. 10 10 10 12"ø E.A. 8"ø S.A. NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: SECTIONS M401 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 SCALE: 3/16" = 1'-0" 1 AHU SUPPLY AND RETURN DUCT DETAIL KEY NOTES 1 PROVIDE K-27 DOUBLE WALL DUCTWORK AT THIS LOCATION. (INDICATED BY HATCH) 2 TRANSITION VERTICAL SUPPLY DUCT FROM RTU TO VERTICAL SUPPLY TRUNK SIZE NOTED. 3 COORDINATE TOP OF FLU EXTENSIONS KIT TO BE LEVEL WITH TOP OF AREA WELL WALLS. 4 COORDINATE WITH AHU MANUFACTURES' CUT SHEET TO VERIFY VERTICAL SUPPLY AND RETURN AIR DUCT LOCATIONS. 5 RE: STRUCTURAL DWGS. FOR PAD HEIGHT. 6 ALL EXHAUST FANS ON 14" CURBS. 7 E.A. DUCT UP AND TRANSITION TO EF INLET ON ROOF. 8 RE: ARCHITECTURAL DRAWINGS FOR SOFFIT TO CONCEAL DUCTWORK. 9 50" X 20" RETURN BOOT OPENING ON TOP OF DUCT. 10 AREA WITHIN BOUNDARY IS PLENUM SPACE. AREA OUTSIDE OF BOUNDARY IS ATTIC SPACE. 11 SPLITTER TEE WITH AIR FOIL TURNING VANES IN MAIN S.A. DUCT. 70%/30% SPLIT WITH 70% OF AIR BEING DIRECTED TOWARDS THE NORTH. SCALE: 3/16" = 1'-0" 2 EXHAUST FAN DETAIL SCALE: 3/16" = 1'-0" 3 NORTH DETAIL SCALE: 3/16" = 1'-0" 4 PLENUM SPACE UNDER MECH. WELL DETAIL Page 50 of 61 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: CONTROL SEQUENCES M402 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 UNOCCUPIED SCHEDULE OVERRIDE. (INCLUDED BUT NOT PRESENTLY UTILIZED). TEMPERATURE/PRESSURE TRENDING CAPABILITY FOR ALL SUITES RTU CONTROL SEQUENCES RTU CONTROL SEQUENCES (CONTINUED) MISC. CONTROL SEQUENCES * ALL DAMPER POSITIONS REFERENCED AS % RELATE TO % OF FULL LOAD/MAX FAN CFM.* ALL TEMPERATURE SET POINTS TO BE ADJUSTABLE.* ALL TIME DURATIONS TO BE ADJUSTABLE.* ALL PRESSURE SET POINTS TO BE ADJUSTABLE* AN OUTSIDE AIR TEMPERATURE SENSOR TO LIMIT THE VENTILATION AIR TO "MINIMUM" AS SCHEDULED AT TEMPERATURES HIGHER THAN 90 DEGREES AND LOWER THAN 0 DEGREES. THIS CONTROL SEQUENCE TO BE OVER-RIDDEN IF EITHER ONE OF THE LAB EXHAUST FANS (LEF-1 OR LEF-2 IS ON. * * * * * * * * * * * * THE VARIABLE AIR VOLUME PACKAGED ROOF TOP AIR HANDLING UNIT IS PRIMARILY DESIGNED FOR COOLING, HOWEVER, HEATING IS PROVIDED IN THE UNIT FOR CONDITIONING RELATIVE HIGH VOLUMES OF OUTSIDE AIR DURING LOW COOLING LOAD PERIODS AS WELL AS FOR TEMPERING THE REQUIRED OUTSIDE AIR AND NIGHT SET BACK (IF NEEDED). THE SUPPLY AIR TEMPERATURE SET POINT IS RESET FROM SPACE DEMAND WHICH PROVIDES HIGHER VENTILATION RATES IN THE SPACES WHICH IMPROVES THE AIR QUALITY. THE AMOUNT OF "VENT" OUTSIDE AIR VOLUME IS MAINTAINED AT A CONSTANT FLOW DURING ALL SPEEDS OF THE SUPPLY FAN. THE VOLUME OF OUTSIDE AIR MAY BE HIGHER THEN MINIMUM THROUGH THE AIRSIDE ECONOMIZER. TEMPERATURE CONTROL IS PROVIDED BY A COOLING COIL, A GAS FIRED HEATING SECTION FOR TEMPERING THE REQUIRED OUTSIDE AIR, AN AIRSIDE ECONOMIZER, AND HEATING COILS AT EACH OF THE FT BOXES *RTU-1 TO PROVIDE 9,000 CFM. *TOTAL SUPPLY AIR FLOW MONITORING TO BE ACHIEVED BY AIR FLOW MONITORING GRIDS EQUAL TO AIR MONITOR CORP VOLU-PROBE/FI AT INLET OF SUPPLY FAN. *A UNIT MOUNTED SMOKE DETECTOR IN THE RETURN AIR SECTION FOR RTU-1 TO SHUT DOWN THE SUPPLY FAN UPON DETECTION OF SMOKE / PRODUCTS OF COMBUSTION. DIRECT DIGITAL CONTROL (DDC) TECHNOLOGY TO BE USED TO PROVIDE FUNCTIONS NECESSARY FOR CONTROL OF MECHANICAL SYSTEMS ON THIS PROJECT AS INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND SEQUENCE OF OPERATION. FURNISH AND INSTALL REQUIRED DDC ELEMENTS AND ALL ASSOCIATED INTERLOCKS COMMUNICATION AND 24 VOLT WIRING INCLUDING STEP DOWN TRANSFORMERS AND 120V WIRING WHERE NOT COVERED BY ELECTRICAL CONTRACTOR. THE RTU VARIABLE AIR VOLUME CONTROL SYSTEM IS AN INTEGRATED DIRECT DIGITAL CONTROL SYSTEM WITH THE REMOTE CONTROL PANEL LOCATED IN JANITORIAL ROOM. THIS CONTROL PANEL COMMUNICATES WITH LOCAL MICROPROCESSOR BASED CONTROLLERS AT EACH FAN TERMINAL (FT) BOX, VARIABLE AIR VOLUME (VAV) BOX, AND THE CONTROLLER AT THE RTU. BUILT-IN FEATURES INCLUDE: * * * * * * * * OUTSIDE AIR, SUPPLY AND RETURN AIR TEMPERATURE FOR THE RTU SUPPLY AIR TOTAL CFM OUTSIDE AIR TOTAL CFM DISCHARGE AIR TEMPERATURE MIXED AIR TEMPERATURE SUPPLY DUCT DISCHARGE HIGH PRESSURE AND SUPPLY FAN STATUS FILTER PRESSURE DROP NOTE: COORDINATE WITH OWNERS REPRESENTATIVE/BUILDING OPERATOR TO PROVIDE ALL REQUESTED MAPPABLE MONITORING AND CONTROL POINTS DDC CONTROLLER WITH LCD DISPLAY TO DISPLAY THE FOLLOWING FOR EACH RTU: SETPOINT AND CONTROL PARAMETERS FULLY ADJUSTABLE EITHER FROM THE REMOTE CONTROL PANEL, OR FROM A REMOTE LOCATION VIA AN ETHERNET CONNECTION. GENERAL APPLICATION CONTROLLER, NETWORK CONTROLLER COMMUNICATION AND SYSTEM FAILURES ARE DISPLAYED AT THE CENTRAL PANEL AS AN ALARM. THESE ALARMS/ALERTS CAN BE SENT TO A REMOTE SUPERVISOR LOCATION AT THE OWNER'S DIRECTION. A SINGLE CO2 SENSOR LOCATED IN THE MAIN RETURN AIR DUCT AT THE RTU TO MAINTAIN A 400 PPM DIFFERENTIAL BETWEEN THE O.A. AND R.A. O.A DAMPER TO MODULATE BETWEEN THE MINIMUM AND VENT POSITIONS IN CONJUNCTION WITH THE RETURN AIR DAMPER AT LEVELS ABOVE THE DIFFERENTIAL. * * * * * * * * * * * * * * * * * * * * * * * * *BUILDING STATIC PRESSURE TO BE SENSED AT THE RETURN AIR CEILING CAVITY WITH RESPECT TO THE OUTSIDE. *THE RELIEF/EXHAUST FAN TO REMAIN OFF AND ITS ASSOCIATED DAMPER TO REMAIN FULLY CLOSED UNTIL THE BUILDING STATIC PRESSURE RAISES ABOVE THE 0.025" W.C. SET POINT AT WHICH POINT, MODULATE THE RELIEF DAMPER FULLY OPEN TO MAINTAIN THE SET POINT. IF DAMPER IF FULLY OPEN AND THE BUILDING PRESSURE IS ABOVE SET POINT FOR MORE THAN 15 MINUETS, START AND RAMP UP POWER EXHAUST/RELIEF FAN THROUGH ITS VFD. PERIMETER ZONES AND ZONES WITH HEATING REQUIREMENTS WILL UTILIZE SERIES TYPE (CONSTANT AIR FLOW) FAN-POWERED BOXES WITH INTEGRAL ELECTRIC HEATING COILS. ALL BOX CONTROLLERS TO BE PRESSURE INDEPENDENT, STAND-ALONE ELECTRONIC DDC. IN THE EVENT OF A COMMUNICATION FAILURE WITH THE MAIN RTU CONTROLLER, ALL SET POINTS TO BE MAINTAINED AT THE VAV, FT BOXES. REFER TO THE MECHANICAL FLOOR PLANS FOR SENSOR MOUNTING LOCATIONS FOR ALL VAV/LPVAV, FT TERMINAL UNIT SENSORS. MODULATE THE SUPPLY FAN VFD'S TO MAINTAIN A MINIMUM OF 1.00" WC. POSITIVE SUPPLY DUCT PRESSURE WITH RESPECT TO REMOTE DUCT SENSING REFERENCES. THE DUCT SENSING REFERENCES TO BE LOCATED DOWNSTREAM FROM THE FANS APPROXIMATELY 2/3'S THE DISTANCE OF THE DUCT RUN. WHEN COMBINATION FIRE/SMOKE DAMPERS ARE USED, LOCATED AN ADDITIONAL SENSING POINT IMMEDIATELY UPSTREAM OF THE DAMPER IN THE SAME RUN. SEE THE MECHANICAL DRAWINGS FOR LOCATIONS. THE TRANSMITTER TO BE LOCATED IN A STRAIGHT PIECE OF DUCT TO PREVENT FALSE SIGNALS TRANSMITTED TO THE VARIABLE FREQUENCY DRIVES. PROVIDE A HIGH LIMIT DUCT STATIC PRESSURE TRANSMITTER IN EACH MAJOR SUPPLY DUCT TO SHUT DOWN THE SUPPLY FAN AT 3.0" WC. THE MIXED AIR CONTROLLER TO MODULATE THE OUTSIDE AIR AND RETURN AIR DAMPERS TO MAINTAIN A MIXED AIR SET POINT 2 DEGREES BELOW THE DISCHARGE AIR SET POINT. WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW THE DISCHARGE AIR TEMPERATURE SET POINT. THE MIXED AIR CONTROL TO REVERT TO THE MINIMUM OSA AIR VOLUME CONTROL SET POINT WHEN THE OUTSIDE AIR TEMPERATURE IS GREATER THAN THE DISCHARGE AIR TEMPERATURE SET POINT. OUTSIDE AIR TO BE UTILIZED FOR COOLING IN WINTER BEFORE ANY MECHANICAL COOLING IS INITIATED. THE OSA AIR VOLUME CONTROLLER TO MODULATE THE DAMPERS TO MAINTAIN THE MINIMUM OSA AIR VOLUME SET POINT AS WELL AS TO MAINTAIN THE BUILDING PRESSURE SET POINT (0.025" W.C.) THE BOXES PROVIDE TERMINAL ZONE TEMPERATURE CONTROL BY VARYING THE VOLUME OF COLD AIR DELIVERED TO THE ZONE. *PROVIDE SPACE OCCUPANCY SENSOR FOR EACH LT BOX. THE PRIMARY AIR DAMPER TO MODULATE TO MAINTAIN THE SPACE COOLING SET POINT OF 75 DEGREES +/- 1 DEGREE BY RESETTING THE PRIMARY AIR VELOCITY CONTROL POINT BETWEEN MINIMUM AND MAXIMUM VELOCITY SET POINTS . THE FAN TO OPERATE CONTINUOUSLY IN THE "OCCUPIED" MODE WHEN THE RESPECTIVE ROOM/SPACE IS OCCUPIED, AS DETERMINED BY THE SPACE OCCUPANCY SENSOR. THE ELECTRIC HEATING COIL SCR CONTROL TO MODULATE TO MAINTAIN THE SPACE HEATING SET POINT OF 73 DEGREES +/- 1 DEGREE. THE PRIMARY AIR DAMPER TO MODULATE TO MAINTAIN THE SPACE COOLING SET POINT OF 75 DEGREES +/- 1 DEGREE BY RESETTING THE PRIMARY AIR VELOCITY CONTROL POINT BETWEEN MINIMUM AND MAXIMUM VELOCITY SET POINTS. *(30) MINUTES AFTER OCCUPANCY IS NO LONGER SENSED AND THE RESPECTIVE RTU REMAINS IN THE OCCUPIED MODE, FAN POWERED BOX TO SWITCH INTO "STAND-BY" MODE. *"OCCUPIED" SPACE HEATING/COOLING TEMPERATURE SETPOINTS TO BE MAINTAINED. *PRIMARY AIR VALVE TO CLOSE TO MIN. POSITION. FAN TO CYCLE ON/OFF AS FIRST STAGE HEATING/COOLING. HEATING COIL TO CYCLE FOR SECOND STAGE HEATING. PRIMARY AIR VALVE TO MODULATE OPEN/CLOSED FOR SECOND STAGE COOLING. * * *TOTAL OUTSIDE AIR FLOW MONITORING TO BE ACHIEVED BY OUTSIDE AIR MONITOR EQUAL TO AIR MONITOR CORP VOLU-FLOW/OAM WITH CONTROL MODULE MOUNTED INSIDE OF UNIT CASING. PROVIDE TEMPERATURE TRANSMITTER DIRECTLY UPSTREAM OF THE HEATING SECTION FOR MONITORING AND CONTROL OF FULL MODULATING GAS HEAT TO MAINTAIN A MINIMUM OF 45°. IF MIXED AIR DROPS BELOW 40°, OVERRIDE SEQUENCE AND REVERT O.A. DAMPERS TO "VENT" OA POSITION AND ALARM. LOW TEMP ALARM FROM MIXED AIR TEMP SUPPLY FAN FAIL HIGH SUPPLY AIR DUCT PRESSURE HIGH SUCTION RETURN FAN PRESSURE FILTER PRESSURE DROP (SET AT 1.00" WC.) ALL SAFETY ALARMS TO HAVE AUTOMATIC RESET. SAFETY ALARMS TO BE DISPLAYED AT THE CONTROLLER: PROGRAMMABLE TIME CLOCK TO SCHEDULE OCCUPIED/UNOCCUPIED HOURS. 100% AIR ECONOMIZER FOR FREE COOLING. SET UP/SET BACK TEMPERATURES (INCLUDED BUT NOT PRESENTLY UTILIZED). ADAPTIVE OPTIMAL START/STOP (INCLUDED BUT NOT PRESENTLY UTILIZED). DUCT STATIC PRESSURE CONTROL. BUILDING STATIC PRESSURE CONTROL DAMPER NORMAL (AKA FAIL) POSITIONS: OUTSIDE AIR DAMPER: CLOSED (NC) RETURN AIR DAMPER: OPEN (NO) NOTES: DESIGN INTENT: GENERAL: THE SCHEDULED OPERATION TIME IS 24 HOUR. WHEN THE SUPPLY FAN IS OFF, ALL DAMPERS TO GO TO "NORMAL" POSITIONS. WHEN A START IS COMMANDED: SUPPLY FAN TO ENERGIZE AND SLOWLY RAMP UP TO MAINTAIN A DUCT STATIC PRESSURE SET POINT. SUPPLY STATIC PRESSURE CONTROL: DISCHARGE AIR TEMPERATURE CONTROL: STAGE ON THE HEATING AND COOLING IN SEQUENCE TO MAINTAIN A 55 DEGREE DISCHARGE AIR SET POINT. RESET THE DISCHARGE AIR SET POINT FROM THE AVERAGE VAV/LPVAV, FT/LPFT TERMINAL UNIT COOLING DEMAND AS FOLLOWS: AVG. VAV BOX % COOLING DEMAND DISCHARGE AIR SET POINT (DEGREES) 70 55 50% OR BELOW 90% OR ABOVE MIXED AIR DAMPER CONTROL: MIXED AIR TEMPERATURE CONTROL: OSA VOLUME CONTROL: A. D. C. B. A. RELIEF/EXHAUST FAN DAMPER SEQUENCE: TERMINAL UNIT CONTROL - VAV AND FT BOXES: DESIGN INTENT: PRIMARY AIR DAMPERS ARE SET FOR 15% OR 20% MINIMUM (SEE SCHEDULES), UNLESS OTHERWISE SPECIFICALLY NOTED ON PLANS. GENERAL: COOLING CONTROL FOR ALL VAV BOXES: SERIES TYPE FAN POWERED BOXES: OCCUPANCY SENSORS OVER-RIDE AT THE SPACE MOUNTED SENSOR TO BE SET FOR 3 HOURS. A. *ELECTRIC BASEBOARD HEATER : INTEGRAL LINE VOLTAGE STATS. EBB-1 SERVING MECH/SPRINKLER SET AT 60° *CABINET UNIT HEATERS : INTEGRAL LINE VOLTAGE STATS. CUH-1 SERVING ENTRT VESTIBULES SET AT 65° *EXHAUST FANS : EF-1,4,6: RUN CONTINUOUSLY ON HIGH CFM BETWEEN 8AM AND 8PM AND ON LOW CFM FROM 8:01PM TO 7:59AM. SCHEDULE TIMES WITH OWNER. *RADIANT PANEL HEATERS : RP-1 SERVING MENS AND WONENS BATHROOM AREAS TO MAINTAIN 70° SPACE TEMPERATURE *DOMESTIC HOT WATER CIRCULATION PUMP : CP-1 START/STOP 30 MINUTES BEFORE/AFTER BUILDING "OCCUPIED" SCHEDULE. SCHEDULE TIMES WITH OWNER. *RELIEF AIR/ POWER EXHAUST DAMPER: CLOSED (NC) *ALL SERIES TYPE FAN TERMINAL UNIT FANS TO START BEFORE THE MAIN SUPPLY AIR FAN (UNLESS SPECIFICALLY SEQUENCED TO REMAIN OFF) TO ENSURE THE PROPER TERMINAL FAN ROTATION. COORDINATE TO ENSURE FT UNITS INCLUDE FAN ANTI-BACKWARD ROTATION FEATURE. *PROVIDE 120V/24V CONTROL TRANSFORMER FOR POWER TO ALL VAV BOXES. SEE ELECTRICAL DRAWINGS FOR LOCATIONS OF J-BOXES IN CEILING PLENUM. * * * * * * * * * * * * * * FIELD CONTROLLER(S) RTU-1 SF F A N T R A C K I N G SC CONTROLLER CO M M 120V E-POWER EF-5 EF-6 EF-7 START/STOP STATUS START/STOP HI/LO STATUS START/STOP STATUSEF-4 START/STOP HI/LO STATUS EF-3 START/STOP STATUS EF-2 START/STOP STATUS T EF-1 START/STOP HI/LO STATUS FSD STATUS S S S S S 12 0 V E - P O W E R OA / R A D A M P E R S COMM BUILDING PRESSURER BOX 1 RELAY DOMESTIC HOT WATER CIRC. PUMP 120V POWER OWNER PC/TABLET (WEB BASED BROWSING AND CONTROL) (TOTAL 5) MECH. CONTROL SYSTEM CONCEPT ARCHITECTURE P OCC OCC OCC OCC EF-2,3,5,7: OCC. SENSORS START/STOP. FAN TO DELAY "OFF" FOR 15 MINUTES. OCC. SENSORS FOR MULTIPLE ROOMS TO BE WIRED IN PARALLEL. "A" • OCCUPANCY SENSORS IN (4) OFFICES ON THE SOUTH SIDE TO BE WIRED ON PARALLEL TO FT-3 SERVING THOSE ROOMS. • OCCUPANCY SENSORS FOR ENGAGEMENT COUNSELOR AND OFFICE AT S.E. CORNER TO BE WIRED IN PARALLEL TO FT-2 SERVING THOSE ROOMS. • OCCUPANCY SENSOR FOR MEET AND GREET TO BE WIRED TO VAV-1 SERVING THAT SPACE. • OCCUPANCY SENSOR FOR BOTH ADMISSIONS AND BUSINESS CENTER TO BE WIRED IN PARALLEL TO VAV-3 SERVING THOSE SPACES. • OCCUPANCY SENSOR FOR RETAIL AND RECEPTION TO BE WIRED IN PARALLEL TO FT-2 SERVING THOSE SPACES. • OCCUPANCY SENSOR FOR MEETING ROOM TO BE WIRED IN PARALLEL TO FT-2 SERVING THAT SPACE. • OCCUPANCY SENSOR FOR HALL OUTSIDE LOCKER ROOMS AND INTERIOR OFFICE TO BE WIRED IN PARALLEL TO VAV-3 SERVING THOSE SPACES. • OCCUPANCY SENSOR FOR (4) OFFICES ON THE NORTH TO BE WIRED IN PARALLEL TO FT-3 SERVING THOSE ROOMS. "B" • THE SCHEDULED "UN-OCCUPIED" CYCLE ONLY AFFECTS THE VAV/FT BOXES SERVING THE ADMINISTRATIVE AREAS (PRIMARILY ALL AREAS EAST OF COLUMN "E"). PRIMARY AIR DAMPER TO GO TO ITS MINIMUM POSITION, FANS TO TURN "OFF". • ON A WALL FOR HEAT IN THE "UN-OCCUPIED" SCHEDULE VAV BOX TO OPEN TO 50% OR FT BOX FAN TO START AND ELECTRIC HEAT TO STAGE "ON". COMBINATION FIRE/SMOKE DAMPER CONTROL SEQUENCE COMBINATION TYPE FIRE/SMOKE (FS) DAMPERS WHERE CALLED FOR ON THE DRAWINGS TO BE 120V RATED. THESE DAMPERS WILL BE WIRED BY THE DIVISION 26 CONTRACTOR AND CONTROLLED BY IT'S DUCT MOUNTED SMOKE DETECTOR. ALL FIRE/SMOKE DAMPERS TO HAVE RESEATABLE LINK, CEILING MOUNTED INDICATOR (OPEN/CLOSED) LED LIGHT PACKAGE WITH CONTACT SWITCH SO ITS OPEN/CLOSE POSITION CAN BE SEEN BY THE BAS. INDICATOR LIGHT PACKAGE TO BE LOCATED DIRECTLY BELOW EACH ASSEMBLY. LABEL EACH ASSEMBLY. COMBINATION TYPE FIRE/SMOKE DAMPER TO BE EQUAL TO "GREENHECK" FSD-212 UL APPROVED WITH CLASS II LEAKAGE AND RATED FOR 4" W.G. MINIMUM AND FAIL CLOSED POSITION. ALL DAMPERS TO BE WIRED TOGETHER. OPERATION: • WHEN POWER IS 'ON' THROUGH THE N.C. CONTACT OF THE UPSTREAM DUCT MOUNTED SMOKE DETECTOR, THE GREEN LIGHT WILL ILLUMINATE INDICATING THAT THE DAMPER IS OPEN. • WHEN POWER IS 'OFF' THROUGH THE N.O. CONTACT AT THE SMOKE DETECTOR, THE DAMPER CLOSES/MAKES THE DAMPER END SW ITCH. THE "OPEN" GREEN LIGHT GOES "OFF", AND THE "CLOSED" RED LIGHT GOES "ON". • BAS TO PROVIDE SIGNAL TO INTERRUPT 24V CONTROL POW ER TO EXERCISE DAMPERS ON A MONTHLY BASIS, ON SUNDAY AT MIDNIGHT. ALLOW ENOUGH TIME FOR DAMPERS TO FULLY CLOSE AND RE-OPEN BEFORE THE NEXT FLOOR'S DAMPERS. CLOSED (RED) OPEN (GREEN) R TO OTHER DAMPER/DETECTOR ASSEMBLIES ON FLOOR 24V FROM TCP/BAS N.C. FAS CONTACT N.O. N.C. DUCT SMOKE DETECTOR UPSTREAM OF DAMPER INDICATOR LIGHT PACKAGE (N.O.) FIRE/SMOK E DAMPER M 120V S-1DAMPER END SWITCH (MAKE ON CLOSE) FIRE/SMOKE DAMPER WIRING CONCEPT PO W E R E X H *IN E-POWER RTU-1 FAN TO RUN CONTINUOUSLY TO MAINTAIN BUILDING TEMPERATURES. ALL PRIMARY AIR DAMPERS AT VAV AND FT BOXES TO GO TO 75% OPEN AND RTU FAN TO RAMP UP TO 100%. BURNER TO MODULATE TO PROVIDE MINIMUM 80° DISCHARGE AIR TEMPERATURE. "C" • SENSORS IN ADMINISTRATION AREAS NOTES IN "A" AS WELL AS NURSES STATION, AND BOTH CONFERENCE/EXAM AREAS, TO HAVE DISPLAY AND THUMB WHEEL ADJUSTMENT. • SENSORS IN PATIENT/CLIENT SLEEPING AREAS, (WING AREAS, WOMEN'S AND MEN'S BATHROOM AREAS) TO BE SENSORS AND ONLY ADJUST THROUGH THE BAS. COMMTO /FROM DINING COMMTO /FROM EDUCATION Page 51 of 61 1 2 "x 1 2 " S .A . 12"ø E.A. 8"ø E.A. 5 0 "x 2 0 " S .A . 26"x20" S.A. 12"ø E.A. 1 2 "ø E .A . 1 0 "ø E .A . 1 2 "ø E .A . 6 "ø S .A . 8 "ø S .A . 1 2 "ø S .A . 1 2 "ø S .A . 5 0 "x 2 0 " R .A . 26"x40" S.A. 20"x50" R.A. 2 6 "x 1 4 " S .A . 8"ø E.A. 10"ø E.A. 26"x14" S.A. 10"ø E.A. 14"ø E.A. 1 4 "ø E .A .1 0 "ø E .A . 12"x12" S.A. 8 "ø S .A . 8"ø S.A. 8"ø S.A. 8 "ø S .A . 1 2 "x 1 2 " S .A . 2 (375) FT 3 (600) FT 3 (650) FT 1 (225) FT 1 (225) FT 3 (650) FT 2 (375) FT 1 (175) VAV 2 (600) VAV 1 (175) VAV 2 (700) VAV 8"x8" S.A.8 "ø E .A . 8 "ø E .A . 8 "ø E .A . 8 "ø E .A . 8 "ø S .A . 8"x8" S.A. 8 "ø S .A . 8 "ø S .A . 6 "ø S .A . 8 "ø S .A . NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: MECHANICAL ISOMETRICS M500 Ha r m o n y F o u n d a t i o n , I n c Ad m i s s i o n s / D e t o x 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 1' 4'6" 2' M500 1PLENUM SPACE UNDER MECH. WELL Page 52 of 61 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: INDEX, LEGEND, QUAL. NOTES & CRITERIA M0 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 SHEET NUMBER SHEET NAME 100% CD M0 INDEX, LEGEND, QUAL. NOTES & CRITERIA 03/28/14 M0.1 SCHEDULES 03/28/14 M100 FIRST FLOOR HVAC PLAN 03/28/14 M101 HVAC ENLARGED PLAN 03/28/14 M200 MECHANICAL ROOF PLAN 03/28/14 M300 DIAGRAMS 03/28/14 M400 CONTROLS 03/28/14 M401 CONTROLS 03/28/14 M500 SECTIONS 03/28/14 DESIGN CRITERIA PROJECT SITE: ESTES PARK, CO PROJECT ELEVATION: 7,500 FEET SUMMER OUTSIDE: 90 DEGREES DB / 65 DEGREES WB WINTER OUTSIDE: -30 DEGREES DB EXTERIOR CONSTRUCTION "U" VALUES WALLS: 0.0333 ROOF: 0.0204 GLAZING 0.33 CODES: 2009 INTERNATIONAL BUILDING CODE 2009 INTERNATIONAL MECH. CODE W / AMENDMENTS 2009 INTERNATIONAL PLUMBING CODE * OUTSIDE AIR VENTILATION CALCULATION ARE ASHRAE 62.1 2007 COMPLIANT. GENERAL SYMBOL LEGEND DUCTWORK SYMBOL LEGEND OS TEMPERATURE TRANSMITTER OCCUPANCY SENSOR ARCHITECTURAL BACKGROUND PROVIDED BY BASIS ARCHITECTURE P.C. ON 02/24/14. FOOD SERVICE BACKGROUND PROVIDED BY TUNDRA DESIGN GROUP ON 02/11/14. T S S(X HR) SD RT FIRST DIMENSION LISTED OF RECTANGULAR DUCT DIMENSIONS REFERENCES THE TOP SIDE OF THE DUCT. ALL DUCT DIMENSIONS ARE AIRWAY (INSIDE CLEAR) DIMENSIONS. D 30"x15" 1830 (3) DUCT OFFSET UP (IN DIRECTION OF FLOW) SUPPLY, RETURN, EXHAUST DUCTS DN SUPPLY, RETURN, EXHAUST DUCTS UP DUCT OFFSET DOWN (IN DIRECTION OF FLOW) THERMOSTAT, PNEUMATIC SUPPLY AIR RETURN AIR EXHAUST AIR FRESH AIR RELIEF AIR MAKE UP AIR COMBUSTION AIR TOP OF DUCT BOTTOM OF DUCT MANUAL (OPPOSED BLADE) VOLUME DAMPER S.A. R.A. E.A. F.A. RL.A. M.A. C.A. T.O.D. B.O.D. MVD MOTORIZED DAMPER, OPPOSED BLADE SHOWN DUCT MOUNTED SMOKE DETECTOR SMOKE DAMPER COMBINATION FIRE/SMOKE DAMPER (X HOUR RATED) (X HR)FIRE DAMPER (X HOUR RATED) HIGH EFF. TAKE-OFF WITH MANUAL LOCKABLE DAMPER THERMOSTAT, ELECTRIC DUCTWORK WITH FLEXIBLE CONNECTION SENSOR (CD - CARBON DIOXIDE, CM - CARBON MONOXIDE, N - NITROGEN, RT - REMOTE TEMPERATURE) MITERED ELBOW WITH TURNING VANES AND SPLITTER TEE WITH TURNING VANES. SPIRAL DUCTWORK (ROUND UNLESS OTHERWISE NOTED AS OVAL ON PLANS) SUPPLY AIR OUTLET - CEILING AND SIDEWALL (NOTE: CEILING DIFFUSERS WILL ONLY HAVE FLOW ARROWS IF DISCHARGE DIRECTION IS CRITICAL). RETURN AIR INLET - DUCTED CEILING GRILLE, CEILING GRILLE TO RETURN PLENUM, AND SIDEWALL GRILLE. GRILLE, REGISTER, OR DIFFUSER TAG. DEVICE TYPE "D", 30"x15" NECK SIZE, 1830 CFM, TYPICAL OF 3. (NOTE: IF QUANTITY IS BLANK TAG PERTAINS TO ONE. IF CFM IS BLANK, CFM IS NOT CRITICAL/BALANCING IS NOT REQ'D. GRILLE TAG FOR GRILLES THAT ARE OF TYPICAL SIZE, WHICH IS LISTED IN THE GRD SCHEDULE.D DUCTWORK WITH ACOUSTICAL LINER (THICKNESS LABELED IN PARENTHESIS) UN-LINED DUCTWORK (SEE SPECIFICATIONS FOR DUCT WRAP REQUIREMENTS)24"x12" 24"x12" (1") UP DN NOTE: MXX X PIPE OR DUCT OFFSET DOWN PIPE OR DUCT OFFSET UP PIPE OR DUCT SLOPE IN DIRECTION OF FLOW (NEGATIVE % DEPICTS SLOPING DOWN, POSITIVE % DEPICTS SLOPING UP) PIPE OR DUCT ELBOW DOWN PIPE OR DUCT ELBOW UP TEE OFF BOTTOM OF PIPE OR DUCT TEE OFF TOP OF PIPE OR DUCT PIPE OR DUCT REDUCER (CONCENTRIC UNLESS OTHERWISE NOTED) SHEET NUMBER PLAN, DIAGRAM, OR RISER NUMBER TOP OF UNIT BOTTOM OF UNIT TOP OF PIPE BOTTOM OF PIPE ABOVE FINISHED FLOOR MECHANICAL CONTRACTOR PLUMBING CONTRACTOR GENERAL CONTRACTOR ELECTRICAL CONTRACTOR FIRE ALARM CONTRACTOR FIRE SPRINKLER CONTRACTOR T.O.U B.O.U. T.O.P. B.O.P. AFF MC PC GC EC FAC FSC POINT OF CONNECTION MECHANICAL SHEET LIST X % UP DN 24" Ø T TT MANUAL TWIST TIMERTT 1. THE GENERAL CONTRACTOR IS TO OBTAIN ALL PERMITS, PATENT RIGHTS, AND LICENSES THAT ARE REQUIRED FOR PERFORMING THE WORK UNDER ALL LAWS, ORDINANCES, RULES AND REGULATIONS, OR ORDERS OF ANY OFFICER AND/OR GOVERNING BODY, HAVING JURISDICTION FOR THE WORK UNDER THIS SECTION. THE CONTRACTOR IS TO GIVE ALL NOTICES NECESSARY IN CONNECTION WITH, PAY ALL FEES RELATING TO AND ALL COSTS AND EXPENSES INCURRED ON ACCOUNT OF THE WORK UNDER THIS SECTION. NO WORK IS TO BE COVERED BEFORE INSPECTION BY THE JURISDICTIONAL INSPECTOR AND THE OWNER'S REPRESENTATIVE. POST PERMITS AS REQUIRED. 2. THE CONTRACT DOCUMENTS ARE DIAGRAMMATIC, SHOWING CERTAIN PHYSICAL RELATIONSHIPS WHICH MUST BE ESTABLISHED WITHIN THE MECHANICAL WORK AND ITS INTERFACE WITH OTHER WORK. SUCH ESTABLISHMENT IS THE EXCLUSIVE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACT DOCUMENTS INDICATE THE AVAILABLE INFORMATION ON EXISTING UTILITIES AND SERVICES, AND ON NEW SERVICES TO BE PROVIDED TO THE PROJECT BY UTILITY COMPANIES AND AGENCIES. COORDINATE ALL UTILITY INTERRUPTIONS WITH THE OWNER AND THE UTILITY COMPANY. PLAN WORK SO THAT THESE INTERRUPTIONS ARE KEPT TO A MINIMUM. 3. THE EQUIPMENT INDICATED ON THE CONTRACT DOCUMENTS REPRESENT A STANDARD OF QUALITY TO BE MAINTAINED. SUBSTITUTIONS MAY BE SUBMITTED TO THE ENGINEER FOR REVIEW. THIS SUBMITTAL REVIEW IS FOR GENERAL CONFORMANCE WITH THE DESIGN CONCEPT OF THE PROJECT AND GENERAL COMPLIANCE WITH THE INFORMATION GIVEN IN THE CONTRACT DOCUMENTS. ANY ACTION SHOWN IS SUBJECT TO THE REQUIREMENTS OF THE PLANS AND SPECIFICATIONS. CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS (WHICH ARE TO BE CORRELATED AT THE JOB SITE), FABRICATION PROCESSES, MEANS, METHODS AND TECHNIQUES OF CONSTRUCTION, COORDINATION OF HIS WORK WITH THAT OF ALL OTHER TRADES AND THE SATISFACTORY PERFORMANCE OF HIS WORK IN A SAFE AND SATISFACTORY MANNER. ALL EQUIPMENT AND MATERIALS ARE TO BE NEW AND UNUSED AND INSTALLED BY ONLY QUALIFIED PERSONNEL. THE CONTRACTOR IS TO INSTALL ALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS, IN ADDITION TO ANY STATE AND LOCAL CODES THAT MAY APPLY. WORKMANSHIP: ALL LABOR IS TO BE CAREFULLY SKILLED FOR THIS KIND OF WORK, THOROUGH IN ALL RESPECTS AND UNDER THE DIRECTION OF A COMPETENT FOREMAN. 4. SUBMIT (6) COPIES OF SHOP DRAWINGS ON ALL EQUIPMENT AND MATERIALS FOR ENGINEERS REVIEW. SUBMITTAL INFORMATION IS TO INDICATE ALL PERFORMANCE DATA (RATED FOR THE ALTITUDE OF THIS PROJECT) THAT COMPLIES WITH THE SCHEDULED DATA. LIST ALL DEVIATIONS AND REASONS FOR DEVIATION. SUBMITTALS WITHOUT PROPER INFORMATION WILL BE IMMEDIATELY REJECTED. SHOP DRAWINGS IN PDF FORMAT MAY BE SUBMITTED ELECTRONICALLY FOR REVIEW. 5. EQUIPMENT FURNISHED UNDER THIS CONTRACT IS TO HAVE A PERMANENT LABEL CLEARLY INDICATING THE MAINTENANCE TO BE PERFORMED TO MAINTAIN THE EQUIPMENT IN EFFICIENT OPERATING CONDITION. EQUIPMENT SUPPLIERS ARE TO FURNISH THE FULL AND PARTIAL INPUT AND OUTPUT CAPACITIES TO ENABLE THE DETERMINATION OF COMPLIANCE WITH THE ENERGY CONSERVATION CODE. 6. SUBMIT THREE TYPED AND BOUND COPIES OF OPERATING AND MAINTENANCE MANUALS PRIOR TO SCHEDULING SYSTEMS DEMONSTRATION FOR THE OWNER. MANUALS ARE TO HAVE INDEX WITH TAB DIVIDERS FOR EACH MAJOR EQUIPMENT SECTION TO FACILITATE LOCATING INFORMATION ON A SPECIFIC PIECE OF EQUIPMENT. ALPHABETICAL LIST OF SYSTEM COMPONENTS, WITH THE NAME, ADDRESS AND 24 HOUR TELEPHONE NUMBER OF THE COMPANY RESPONSIBLE FOR SERVICING EACH ITEM DURING THE FIRST YEAR OF OPERATION. 7. DELIVERY AND STORAGE OF MATERIALS: PROVIDE FOR THE SAFETY AND GOOD CONDITION OF ALL MATERIALS AND EQUIPMENT UNTIL FINAL ACCEPTANCE BY THE OWNERS REPRESENTATIVE PROTECT ALL MATERIALS AND EQUIPMENT FROM DAMAGE AND PROVIDE ADEQUATE AND PROPER STORAGE FACILITIES DURING THE PROGRESS OF THE WORK. REPLACE ALL DAMAGED AND DEFECTIVE WORK BEFORE FILING APPLICATION FOR FINAL ACCEPTANCE. 8. BEFORE SUBMITTING HIS BID, THE CONTRACTOR FOR THE WORK UNDER THIS SECTION IS TO CAREFULLY STUDY ALL DRAWINGS, AND MAKE A CAREFUL EXAMINATION OF THE PREMISES. HE IS TO DEFINITELY DETERMINE IN ADVANCE, THE METHODS OF INSTALLATION AND CONNECTING THE APPARATUS AND THE MEANS TO BE PROVIDED FOR GETTING THE EQUIPMENT INTO PLACE, AFTER AWARD OF THE CONTRACT, NO SUBSEQUENT ALLOWANCES WILL BE MADE TO THE CONTRACTOR DUE TO HIS FAILURE TO COMPLY WITH THE ABOVE REQUIREMENTS AND ANY OTHER CONDITIONS AFFECTING THE INSTALLATION AND COMPLETION OF ALL WORK. 9. ACCURATELY RECORD ALL CHANGES TO THE CONTRACT DOCUMENTS ON ONE SET OF DRAWINGS. TRANSMIT THE INFORMATION TO THE ENGINEER. 10. FURNISH WRITTEN CERTIFIED GUARANTEE, IN ACCEPTANCE FORM, TO THE OWNER AGAINST DEFECTIVE WORKMANSHIP, MATERIALS AND OPERATING EQUIPMENT. IN ADDITION TO THE GUARANTEES REQUIRED ELSEWHERE. ALL WORK, MATERIALS AND EQUIPMENT PROVIDED UNDER THE MECHANICAL SECTIONS ARE TO BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE OF THE WORK BY THE OWNER. THE CONTRACTOR UNDER THIS GUARANTEE IS TO BE RESPONSIBLE FOR ALL DAMAGE TO ANY PART OF THE PREMISES CAUSED BY EQUIPMENT AND MATERIALS FURNISHED UNDER THIS SECTION. PROVIDE CERTIFICATES FOR ALL EQUIPMENT HAVING WARRANTIES IN EXCESS OF (1) YEAR. 11. ALL WORK AND MATERIALS ARE TO BE IN FULL ACCORDANCE WITH CURRENT SAFETY ORDERS OF THE DIVISION OF INDUSTRIAL SAFETY, THE NATIONAL ELECTRIC CODE, LOCAL BUILDING CODES, THE INTERNATIONAL MECHANICAL CODE, THE INTERNATIONAL PLUMBING CODE, THE INTERNATIONAL BUILDING CODE AND OTHER APPLICABLE CODES, LAWS OR REGULATIONS OF BODIES LAWFULLY EMPOWERED AND HAVING JURISDICTION OVER THIS PROJECT. NOTHING IN THE PLANS OR THESE SPECIFICATIONS IS TO BE CONSTRUED AS TO PERMIT WORK NOT CONFORMING TO THESE CODES. 12. RESOLVE ALL QUESTIONS, DISCREPANCIES OR CONFLICTS WITH ENGINEER BEFORE ANY EQUIPMENT IS ORDERED, MATERIALS FABRICATED OR SYSTEMS INSTALLED. 13. PROVIDE IDENTIFICATION TAGS FOR ALL SCHEDULED EQUIPMENT. 14. COORDINATE THE INSTALLATION OF MECHANICAL SYSTEMS WITH OTHER TRADES AND PROVIDE OFFSETS AS NECESSARY TO ACCOMMODATE STRUCTURE AND OTHER TRADES. 15. M.C. TO PROVIDE ALL NECESSARY MOTOR STARTERS WITH REQUIRED AUXILIARY CONTACTS FOR CONTROLS FOR THE EQUIPMENT THEY ARE RESPONSIBLE FOR. COORDINATE WITH E.C. TO INSTALL AND WIRE. M.C. TO PROVIDE & INSTALL ALL NECESSARY LOW VOLTAGE WIRING. 16. PROVIDE ACCESS PANELS IN CEILINGS AND/OR DUCTWORK WHERE REQUIRED FOR ACCESS TO ALL MOTORS, CONTROLS, FIRE DAMPERS, SMOKE / FIRE DAMPERS, BALANCING DAMPERS, AND VALVES. 17. LEVEL ALL EQUIPMENT CURBS / BASES PRIOR TO INSTALLATION OF ANY EQUIPMENT. 18. SEAL ALL WALL AND ROOF PENETRATIONS WATERTIGHT WITH SILICONE CAULKING AND BACKER ROD. U.L. CLASSIFIED AND FM APPROVED SEALANTS ARE TO BE USED AT ALL PENETRATIONS OF RATED WALLS, CEILINGS AND FLOORS. 19. COORDINATE TO PROVIDE ALL THE MISCELLANEOUS SUPPORT AND FRAMING REQUIRED FOR THE MECHANICAL EQUIPMENT. 20. COORDINATE AND VERIFY ALL OPENINGS IN STRUCTURAL WALLS, ABOVE CEILINGS, AND FLOORS WITH THE STRUCTURAL CONTRACTOR. 21. PROVIDE EQUIPMENT VIBRATION ISOLATION FROM STRUCTURE AND ASSOCIATED DUCT/PIPE SYSTEMS. 22. ALL BALANCING IS TO BE COMPLETED BY A QUALIFIED AND CERTIFIED TECHNICIAN, WITH (5) OR MORE YEARS EXPERIENCE IN TESTING, ADJUSTING, AND BALANCING HVAC SYSTEMS. ADJUST DAMPERS AS NECESSARY TO OBTAIN AIR QUANTITIES SHOWN. PROVIDE COMPLETE WRITTEN TEST AND BALANCE REPORT INDICATING QUANTITIES AT INLET AND OUTLET. USE VOLUME DAMPERS FOR ALL REGISTERS FOR BALANCING OF THE SYSTEMS. AIR DISTRIBUTION IS TO BE BALANCED FOR WITHIN 5% OF INDICATED CFM'S. 23. ALL DUCT, PIPE, AND EQUIPMENT LOCATIONS INDICATED ON THESE DOCUMENTS ARE FOR REFERENCE ONLY AND ARE TO BE USED AS A GUIDE. ALL ELEVATIONS AND FLOOR TO FLOOR HEIGHTS ARE TO BE VERIFIED PRIOR TO FABRICATION AND/OR INSTALLATION OF ANY DUCT OR PIPING SYSTEM. TOP OF DUCT (TOD) AND BOTTOM OF DUCT (BOD) ELEVATIONS INDICATED INCLUDE AN ALLOWANCE FOR DUCT FLANGES AND INSULATION. 24. THE MECHANICAL CONTRACTOR IS RESPONSIBLE FOR COORDINATING THE MECHANICAL REQUIREMENTS FOR ALL CUTTING AND PATCHING OF EXISTING FACILITIES TO BE COMPLETED BY THE GENERAL CONTRACTOR OR OTHERS. 25. REFRIGERANT PIPING SIZES 2 1/2" AND SMALLER SHALL BE COPPER TUBE, TYPE "L", ANNEALED, WITH WROUGHT COPPER FITTINGS AND BRAZED JOINTS. REFRIGERANT DISCHARGE PIPING: 1 1/2" FIBERGLASS USE FLEXIBLE UNICELLULAR PIPE INSULATION ON REFRIGERANT DISCHARGE PIPING ABOVE ROOF EXPOSED TO THE ELEMENTS. 26. PRINCIPAL TEMPERATURE CONTROL SYSTEM WILL BE PACKAGED ELECTRONIC / ELECTRIC DDC CONTROLS WITH SPACE MOUNTED ZONE SENSORS. GENERAL MECHANICAL NOTES AND OUTLINE SPECIFICATIONS 1. ALL SUPPLY AND RETURN DUCTWORK UNLESS SPECIFICALLY INDICATED IS TO BE IN ASTM A527 LOCK FORMING QUALITY GALVANIZED SHEET METAL WITH ASTM A525 G90 ZINC COATING INSTALLED IN ACCORDANCE WITH CHAPTER 6 OF THE CURRENT ADOPTED VERSION OF IMC AND THE SMACNA DUCT CONSTRUCTION STANDARDS, FOR PRESSURE CLASS "A" FOR 3" SP AND ABOVE, CLASS "B" FOR 2" TO 3" SP AND CLASS "C" FOR 1/4" TO 2" SP, WITH "HARD CAST" SEALED JOINTS. THE USE OF PRESSURE SENSITIVE TAPE WILL NOT BE ACCEPTABLE. DIMENSIONS SHOWN ARE AIRWAY (INSIDE CLEAR) DIMENSIONS. M.C. IS RESPONSIBLE FOR MAKING ALLOWANCES FOR LINER THICKNESS (WHERE APPLICABLE) FOR SHEET METAL DIMENSIONS. 2. INSTALL FULL SIZE CONDENSATE DRAIN WITH TRAP SEAL DEPTH EQUAL TO 1.5 x UNIT TOTAL STATIC PRESSURE FOR EACH COOLING COIL. 3. ALL TYPE "B" VENTS ARE TO HAVE JOINTS SEALED WITH "HARD CAST". THE USE OF PRESSURE SENSITIVE TAPE TO SEAL JOINTS WILL NOT BE ACCEPTABLE. 4. INTERNALLY INSULATE ALL NEW SUPPLY AIR AND RETURN AIR DUCTS THAT ARE INSTALLED OUTSIDE OF THE BUILDING OR IN UN-CONDITIONED SPACES WITH INSULATION HAVING A MINIMUM "R" VALUE OF 8.0. INTERNALLY INSULATE ALL NEW SUPPLY AIR AND RETURN AIR DUCT MAINS THAT ARE INSTALLED IN A CONDITIONED SPACE WITH MINIMUM 1" THICK FLEXIBLE FIBERGLASS, EQUAL TO JOHNS MANSVILLE (LINEACOUSTIC RC). ALL INSULATION IS TO HAVE MINIMUM INSTALLED "R" VALUE OF 5.0, FLAME SPREAD RATING OF 25 OR LESS, SMOKE DEVELOPED RATING OF 50 OR LESS AND BE RATED FOR OPERATING TEMPERATURES UP TO 250° F. DUCT LINERS ARE TO HAVE AN ACRYLIC COATING ON SURFACE IN CONTACT WITH THE AIR STREAM AND AN ANTI-MICROBIAL COATING TO PROHIBIT THE GROWTH OF FUNGUS AND BACTERIA. WRAP ALL ROUND SUPPLY DUCTS. DUCT WRAP IS TO HAVE AN ALUMINUM FOIL FACING. EXTERNALLY INSULATE ALL ENVIRONMENTAL EXHAUST AND CLOTHES DRYER EXHAUST DUCTS IN UNHEATED SPACES WITH MIN. R-8 INSULATION 5. ALL DUCT PENETRATIONS THRU FIRE RATED WALLS, FLOORS, DEMISING WALLS TO HAVE APPROVED AUTOMATIC FIRE DAMPERS OR TO PROVIDE APPROPRIATE FIRE RATED SHAFTS FOR ALL SUCH PENETRATIONS. VERIFY WITH IBC / IMC AND RESPECTIVE CITY. 6. ALL CONCEALED, ROUND SUPPLY AIR DUCTS 12" AND SMALLER ARE TO BE GALVANIZED SHEET METAL SNAP-LOCK. ROUND SUPPLY DUCT GREATER THAN 12" IS TO BE GALVANIZED SHEETMETAL SPIRAL. PROVIDE 1" FIBERGLASS INSULATION WRAP. INSULATED FLEXIBLE DUCT MAY BE USED FOR THE CONNECTION TO THE AIR OUTLET PROVIDED THE LENGTH OF THE FLEXIBLE DUCT DOES NOT EXCEED 6 LINEAR FEET. 7. ALL BRANCH DUCT CONNECTIONS TO AIR OUTLETS AND AIR INLETS ARE TO BE THE SAME SIZE AS THE DEVICE NECK UNLESS SHOWN OTHERWISE ON THE DRAWINGS. 8. ALL GENERAL EXHAUST AND OUTSIDE AIR DUCTWORK IS TO BE GALVANIZED SHEET METAL WITH NO DUCT LINERS. 9. DISH WASHING AND POT WASHING EXHAUST DUCT SYSTEMS ARE TO BE ALUMINUM SHEET METAL WITH ALL JOINTS CAULKED WATERTIGHT WITH SILICONE. PITCH DUCTWORK BACK TOWARD INLET AT 1" PER 10 LINEAR FEET. 10. ALL EXHAUST DUCTWORK CONNECTED TO TYPE I HOODS IS TO BE 16 GAUGE BLACK STEEL WITH ALL WELDED JOINTS. INSTALL DUCTWORK IN A U.L. LISTED (1) HOUR FIRE RATED ENCLOSURE FROM TOP OF HOOD TO THE EXTERIOR OF BUILDING. PITCH DUCTWORK IN ACCORDANCE WITH CODE. MAINTAIN ACCORDANCE WITH CODE. MAINTAIN MINIMUM OF 3" FROM ENCLOSURE TO COMBUSTIBLES. PROVIDE ACCESS DOORS EVERY 12'-0" AND WITHIN 2'-0" OF EVERY ELBOW USE ALL LONG RADIUS ELBOWS WITHOUT VANES. SQUARE ELBOWS WILL NOT BE PERMITTED. DUCT SUPPORTS ARE TO BE SIZED TO SUPPORT THE WEIGHT OF (1) HOUR FIRE RATED ENCLOSURE. 11. ALL EXHAUST DUCTWORK CONNECTED TO TYPE 2 HOODS USED FOR VAPOR, MOISTURE OR STEAM REMOVAL IS TO BE ALUMINUM SHEET METAL WITH ALL JOINTS CAULKED WATERTIGHT WITH SILICON. PITCH DUCTWORK BACK TOWARD INLET AT 1" PER 10 LINEAR FEET. DUCTWORK FROM TYPE 2 HOODS THAT IS VISIBLE IN KITCHENS IS TO BE TYPE 304 STAINLESS STEEL WITH MILL FINISH. 12. ALL CONDENSING UNITS SERVING THE FOOD SERVICE EQUIPMENT REFRIGERATION EQUIPMENT ARE TO BE LOCATED OUTSIDE THE CONDITIONED SPACE. NONE OF THIS EQUIPMENT IS TO REJECT HEAT TO THE SPACE. GENERAL DUCTWORK NOTES AND OUTLINE SPECIFICATIONS Page 53 of 61 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: SCHEDULES M0.1 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 ROOF TOP UNIT SCHEDULE RTU-1 TAG QTY TRANE YHD210 MANUFAC.MODEL CENTIF. FC---1 7,875 TYPESIZE CFM MAX OA 3,1001" 2.9 ECON. MIN OA SUPPLY FAN DATA ESP TSP 5.0 BELT 3,450 NAT. GAS DRIVEHP RPM TYPE FUEL 283350 MBH OUTPUT HEATING COIL DATA @ 7,522 FT. ELEVATION MBH INPUT ( F) EAT 3/4" DX. 200 ( F) LAT CONN. GAS TYPE COIL TOTAL COMPRESSORS LAT 55198 ROWS/FINS COOLING COIL DATA @ 7,522 FT. ELEVATION SENS.EAT 410a95 SCROLL REFG. TYPE°F AMB TYPE 2 TAW 20x20x2/ 4/4 QTY. FILTERS TYPEQTY SIZE 1 THRU 18208/3 101 125 V/PH UNIT MCA MOCP UNIT 102,500 MIN. UNIT EER(LBS) OP. WEIGHT NOTES RTU-1 TAG 44 4/15 A THRU P OPTIONS @S.L.125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz MAX. DISCHARGE SOUND POWER LEVELS (dB) AT HIGH CFM WITH ACOUSTICAL CURB 83 83 83 85 79 78 8377 20x25x2 O. 38" TALL ACOUSTICAL ROOF CURB (BAYCURB FIELD INSTALLED OPTIONS: 027B RC-3) SIDE DISCHARGE S.A. W/TURNING VANES, DOWN DISCH. RETURN. ACOUSTIC VIBRATION ISOLATION RAILS. HP. 5 UNITCFM S.P. 6000 0.50 TYPE MANUF. MODEL DESCRIPTION NOTES A TITUS OMNI SUPPLY DIFFUSER 24"x24" FACE WITH FIXED SQUARE PANEL, STEEL CONSTRUCTION, RADIAL DAMPER. 1,2,3 B TITUS OMNI SUPPLY DIFFUSER 12"x12" FACE WITH FIXED SQUARE PANEL, STEEL CONSTRUCTION, RADIAL DAMPER. 1,2,3 C ACUTHERM TF-HC SUPPLY DIFFUSER 24"x24" THERMALLY POWERED VAV, INDIVIDUAL SETPOINT FOR HEATING & COOLING. 1,2,3 D TITUS 50 F EXHAUST GRILLE, 1/2"x1/2" ALUMINUM CORE GRID, ALUMINUM FRAME, OPPOSED BLADE DAMPER. E TITUS 50 F RETURN GRILLE, 12"x24", 1/2"x1/2" ALUMINUM CORE GRID, ALUMINUM FRAME, OPPOSED BLADE DAMPER. 1,2,3 F TITUS 50 F RETURN GRILLE, 24"x24", 1/2"x1/2" ALUMINUM CORE GRID, ALUMINUM FRAME, OPPOSED BLADE DAMPER. 1,2,3 G TITUS 272 RL SUPPLY REGISTER, DOUBLE DEFLECTION, 3/4" BLADE SPACING, STEEL CONSTRUCTION, OPPOSED BLADE DAMPER. 1,2 H TITUS PAS SUPPLY DIFFUSER 24"x24" FACE WITH PERFORATED GRILLE, STEEL CONSTRCUTION, SLIDING BLADE DAMPER. 1,2,3 I TITUS 23 RL RETURN REGISTER, 3/4" BLADE SPACING, STEEL CONSTRUCTION. 1,2,3 WALL CABINET UNIT HEATER SCHEDULE TAG NOTES: 1. 18 GAUGE STEEL HOUSING. 2. STEEL SHEATHED FINNED ELEMENT. 3. FAN OFF DELAY. 4. HIGH TEMPERATURE CUT OUT SWITCH WITH MANUAL RESET. 5. 16 GAUGE FRONT BAR GRILLE. FACTORY INSTALLED OPTIONS: A. BUILT-IN SNAP ACTING THERMOSTAT. B. BUILT-IN DISCONNECT SWITCH. FIELD INSTALLED OPTIONS: C. FULL RECESSED MOUNTING FRAME. D. 4" SURFACE MOUNTING FRAME. LOCATION MANUF. MODEL TYPE CFM MBH VOLTS/PH NOTES OPTIONS CUH-1 MISC. MARKEL F3422 RECESSED 245 6.8 2.0 --- 208/1 9.6 1 THRU 5 A, B, C, D TAG CUH-1 KW HP AMPS MOUNTING VERTICAL 41 OP. WT. (LBS) FAN SCHEDULE TAG NOTES: 1. BACKWARD INCLINED ALUMINUM FAN WHEEL. 2. NEMA 1 DISCONNECT SWITCH. 3. INTERNAL CONDUIT CHASE. 4. ADJUSTABLE MOTOR PULLEY. 5. MOTOR VIBRATION ISOLATORS. 6. ALUMINUM MOTOR COVER 7. HEAVY GAUGE GALVANIZED STEEL HOUSING. 8. NEOPRENE HANGING ISOLATORS. 9. ELECTRONICALLY COMMUTATED MOTOR (CONTROL SIGNAL FROM BAS). 10. INLET/ OUTLET GUARD. 11. DIRECT DRIVE MOTOR. LOCATION SERVICE MANUF. MODEL TOTAL CFM E.S.P. (IN W.C.)TYPE DIA. (IN) MAX RPM MAX SONES MOUNT DRIVE H.P. VOLTS/PH OP. WT. (LBS) EMERG. POWER NOTES OPTIONS FAN DATA MOTOR DATA TAG EF-1 MECH. WELL GREENHECK CUE-101-B 800 0.25 CENTRIFUGAL --- 1140 6.2 CURB DIRECT 1/6 115/1 60 N 1 THRU 7 B, C, D, H EF-1 FACTORY INSTALLED OPTIONS: A. ALL ALUMINUM CONSTRUCTION. B. BIRDSCREEN. C. ALUMINUM BACKDRAFT DAMPER. FIELD INSTALLED OPTIONS: D. 14" PRE-FABRICATED ROOF CURB E. EXTENDED BASE SOUND CURB WITH INTERNAL BAFFLES. F. SOLID STATE SPEED CONTROLLER INSTALLED DOWNSTREAM OF DISCONNECT SWITCH UNDER MOTOR COVER. G. ECM MOTOR FOR 2-SPEED OPERATION FROM BAS. H. WALL MOUNTED OCC. SENSOR WITH 15 MINUTE DELAY OFF. I. WALL MOUNTED 0-60 MIN. MECHANICAL TWIST TIMER. J. WALL CAP K. HIGH LIMIT STAT ELECTRIC UNIT HEATER SCHEDULE TAG NOTES: 1. STEEL CABINET WITH BAKED ENAMEL FINISH. 2. ADJUSTABLE DISCHARGE LOUVERS. 3. ALUMINUM TUBULAR FINNED ELEMENT. 4.. HIGH TEMPERATURE CUT OUT SWITCH WITH AUTO RESET. LOCATION SERVICE MANUF. MODEL TYPE KW VOLTS/PH NOTES OPTIONS TAG 5. 24 V CONTROL TRANSFORMER. 6. FAN OFF DELAY. MBHSIZE UH-1 MECH MARKEL F2F5103N SUSPENDED 400 11.2 3.3 208/1 1 THRU 6 A, B, C UH-1MECH FACTORY INSTALLED OPTIONS: A. DISCONNECT SWITCH. MOUNTING VERTICAL 30 FEILD INSTALLED OPTIONS: B. 24 V. WALL MOUNTED THERMOSTAT. C. CEILING/WALL MOUNTING BRACKETS. OP. WT. (LBS) EMERG. POWER N MENS/WOMENS RESTROOMS EF-2 MECH. WELL MISC. GREENHECK CUE-090-VG 400/200 0.375 CENTRIFUGAL --- 1725 8.6 CURB DIRECT 1/6 115/1 50 N 1 THRU 7 EF-2 EF-3 MECH. WELL POT WASH GREENHECK CUE-80-D 300 0.25 CENTRIFUGAL --- 1550 7.3 CRUB DIRECT 1/20 115/1 30 N 1 THRU 7 EF-3 ELECTRIC BASEBOARD HEATER SCHEDULE B. INTEGRAL DISCONNECT SWITCH. WATTS FACTORY INSTALLED OPTIONS: A. INTEGRAL UNIT MOUNTED LINE VOLTAGE THERMOSTAT. MANUFACTURER 6. PRE-WIRED J-BOX. 4. STEEL TUBULAR ELEMENT. LOCATIONTAG SERVICE 3. HEAVY DUTY CONSTRUCTION. 2. 12 GAUGE FRONT COVER. 1. FLOOR MOUNTED.NOTES: 5. ALUMINUM FINS. MODEL TYPE LENGTH 8. AUTOMATIC HIGH TEMP. CUT OUT SWITCH. 7. BUILT-IN WIREWAY. OPTIONSEMERG.VOLTS/PH BTU/H NOTESPWR.TAG EBB-1 EBB-1A, B, CN1 TO 84262125010'-0"DBF-10 FLOOR MOUNTEDMARKEL 208/1VARIES VARIES C. BRONZE ANODIZED GRILLE, REGISTER AND DIFFUSER SCHEDULE NOTES: 1. FACTORY STANDARD WHITE FINISH. 2. REFER TO DRAWINGS FOR NECK SIZE AND AIR QUANTITY. 3. REFER TO ARCHITECTURAL DRAWING FOR CEILING TYPE AND LOCATION OF ALL GRD'S. B, C, D, G B, C, D, I FIXED LOUVER SCHEDULE TAG NOTES: 1. EXTRUDED ALUMINUM FRAME. 2. EXTRUDED ALUMINUM BLADES. 3. DRAINABLE HEAD. FACTORY INSTALLED OPTIONS: A. INTERNAL MOUNTED EXPANDED ALUMINUM REMOVABLE BIRDSCREEN. B. FLANGED FRAME. FIELD INSTALLED OPTIONS: C. FACTORY APPLIED COATING TO MATCH EXTERIOR. VERIFY COLOR WITH ARCHITECT. LOCATION MANUF. MODEL W (IN.) H (IN.) D (IN.) BLADE TYPE NOTES OPTIONS L-1 MECH WELL GREENHECK EDJ-601 60" 8.53 7,875 715 0.085 STATIONARY DRAIN HEAD 45° 1, 2, 3 A, B, C TAG L-1 FREE AREA (FT2) MAX. CFM MAX BLADE ANGLE 40" 6" MAX. VEL. MAX. AIR P.D. (IN. W.C.) SERVICE INTAKE 12. CRANKCASE HEATERS ON SCROLL COMPRESSORS. 14. THERMAL EXPANSION VALVE ON 6 TON AND LARGER UNITS. 15. SOLID-CORE LIQUID LINE FILTER-DRIERS. 13. REFRIGERANT LOW PRESS. SWITCHES ON RECIP. COMPRESSORS. 11. VIBRATION ISOLATORS ON SCROLL COMPRESSORS 7. SLOPED NON-CORROSIVE CONDENSATE DRAIN PAN 10. INDEPENDENT REFRIGERANT CIRCUITS 9. COMPRESSOR ANTI-SHORT CYCLE TIMER. 6. BELT DRIVE FAN WITH ADJUSTABLE MOTOR SHEAVE 8. COMPRESSOR AND FAN MOTOR OVERLOAD PROTECTION 1. SINGLE POINT POWER CONNECTION. 4. MICROPROCESSOR CONTROLS. 5. SIDE ACCESS MOTOR AND BLOWER ASSEMBLY. 3. INSULATED (FOIL FACED, 1/2", 1 LB DENSITY) CABINET 2. LOW AMBIENT (0°) COOLING. NOTES: I. LAT CONTROLS WITH ROOM RESET B. TRANE STATICTRAC POWER RELIEF FAN, WITH SEPERATE ELEC. CONNECTION. D. ALTERNATE HIGH STATIC MOTOR AND DRIVE. C. TROUGH BASE ELECTRICAL CONNECTIONS. A. FACTORY INSTALLED INTEGRATED DRY BULB FACTORY INSTALLED OPTIONS: 18. FLAME PROVING CONTROLS 16. DIRECT ELECTRONIC SPARK IGNITION 17. HIGH TEMPERATURE LIMIT SWITCH 100% OA ECONOMIZER. E. CONDENSER COIL HAIL GUARDS. P. ECONOMIZER OA HOOD WITH BIRD SCREEN. F. SMOKE DETECTOR IN RETURN AIR STREAM. G. ASHRAE 52 - MERV 13 FILTERS H. HOT GAS BYPASS TO EVAPORATOR INLET OF EACH COMPRESSOR. Q. FLUE EXTENSION KIT K. INDUCED DRAFT DIRECT DRIVE MOD. GAS J. VFD DUTY RATED SUPPLY FAN MOTOR. L. 120V CONVENIENCE OUTLET (WIRED BY E.C.) M. CO2 SENSOR IN MAIN R.A. DUCT. (5:1 TURN DOWN). STAINLESS STEEL BURNER. L-2 MECH WELL GREENHECK EDJ-601 60" 8.53 7,875 715 0.085 STATIONARY DRAIN HEAD 45° 1, 2, 3 A, B, C L-240" 6"INTAKE EF-4 MECH ROOM MECH ROOM GREENHECK EF-4SQ-65-VG 150 0.25 CENTRIFUGAL --- 1725 5.0 INLINE DIRECT 1/6 115/1 40 N B, C, D, J, K1 THRU 8 N. PRESSURE SWITCH ACROSS FILTER. Page 54 of 61 1 CUH 1 CUH 1 EBB 1 EBB 1 EBB 1 EBB 1 EBB 1 EBB 1 EBB 1 CUH 1 CUH 3 H 12"ØA450 (16) 12"x12"I 200 (2) 8"ØA200 8"ØA200 MECH/ SPRK ELEC STORAGE MEN'S RESTROOM WOMEN'S RESTROOM COOLER FREEZER FOOD SERVICE DIRECTOR STAFF RESTROOM STAFF LOCKERS DISH DINING HALL HOT BUFFET/ SOUPS/ SALAD BAR BEVERAGE CENTER BREAKFAST LINE TRAYS/ TRASH ENTRY COATS COATS ENTRY DRY STORAGE KITCHEN M101 1 12"x12"I 200 (2) 1 1 A B C D E F G 1 2 3 4 5 6 7 6.7 1.1 2 2 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: FIRST FLOOR HVAC PLAN M100 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 4' 16'2' 8' 1/8" = 1'-0" FIRST FLOOR HVAC PLAN KEY NOTES 1 PROVIDE 12" VERTICAL OFFSET BETWEEN TRANSFER GRILLES IN STUD CAVITY. 2 GANG REMOTE ACTUATOR FLEX CABLE TERMINATION MOUNTING BRACKETS SERVING WEST/EAST SIDE OF DINING HALL AT THIS APPROX LCOATION (VERIFY WITH ARCH). PLAN NORTH Page 55 of 61 1 CUH 36 " x 2 2 " 8" x 8 " 8" x 8 " EUH 1 28"x12" 8"ØA100 24 " x 8 " 12 " x 1 2 " 10"ø 10"ø 8"x8" 8"x8" 1 H 2 H 30"x16" 12"ø 12"ø 16 " x 1 4 " 8"ØB200 (2) E E F F 8"ØA200 8"ØA200 (2,950) 12"ØH400 12"ØH400 8"ØA200 10"ø 8"ø 10"ØA275 6"ØB50 6"ØB50 TAHU-1 8"x8"D 100 (2) E 8"ØC125 3 H 48"x24" 34"x34"I 3925 30 " x 2 2 " 36"x22" 8" x 8 " (BY FSC)(BY FSC) (BY FSC) 28 " x 1 2 " 24"x48" 20"x76" 8"x6"G 150 10"x10"D 300 8"x8"D 200 12"x12" 1 2 2 3 4 5 3 4 B C D E F 1 2 3 1.1 6 6 12 " x 1 2 " T MAU-1 7 8 9 910 10 11 12 13 13 14 15 16 16 16 12"x10"G 400 36 " x 2 2 " 34"x34"I 3950 MVD MVD 17 14 " x 8 " 8"x6"G 200 18 19 20 16 " x 1 4 " 2121 MVD 22 4 EF 8"x6" 8"x6" T(80°) 6 23 UP NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: HVAC ENLARGED PLAN M101 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 2' 8'1' 4' 1/4" = 1'-0" FIRST FLOOR HVAC ENLARGED PLAN KEY NOTES 1 PROVIDE AIRFOIL TYPE TURNING VANES IS S.A. ELBOW. 2 PACK END OF DUCT WITH 4" LINACOUSTIC INSULATION. 3 TRANSITION TO S.A./R.A. DISCHARGE SIZE OF UNIT. 4 PROVIDE FLEX AT CONNECTION TO UNIT. 5 PROVIDE SPLTTER TEE WITH AIRFOIL TYPE TURNING VANES AT S.A. DISCHARGE. 6 PROVIDE MINIMUM 1" DOOR UNDERCUT AT THIS LOCATION. 7 10"X10"X10" DEEP ALUMINUM PLENUM AT EXHAUST GRILLE. EXTEND 8"X8" ALUMINUM EA. DUCT UP TO EF-3. 8 12"X12" ALUMINUM E.A. DUCT TO HOOD (H-3 - BY FSC). VERIFY FINAL CONNECTION SIZE. 9 WELD 22"X10" GREASE DUCT RISER TO DUCT COLLAR OF HOOD (H-1/2 BY FSC). 22"X10" UP TO KEF-1/2 ON ROOF, TRANSITION TO EXHAUST FAN CONNECTION. 10 INSTALL GREASE DUCT WRAP (2-HOUR) AROUND GREASE DUCT FROM DUCT COLLAR OF HOOD TO ROOF PENETRATION. INSTALL PER MANUFACTURERS INSTRUCTIONS 11 HOOD TO BE PROVIDED WITH FACTORY LINER ALLOWING ZERO CLEARANCE TO COMBUSTIBLES. 12 LOCATION OF REMOTE STATUS PANEL FOR MAU-1 13 R.A. DUCT DOWN FROM ABOVE. 14 MANUAL OPPOSED BLADE LOW LEAKAGE AIRFOIL TYPE VOLUME CONTROL DAMPER, BALANCE TO CFM INDICATED ON PLANS. 15 24"X12" 1/2" FIBERGLASS DUCT BOARD TRANSFER BOOT THRU WALL. TURN UPWARD AT BOTH ENDS. 16 E.A. DUCT UP TO EF-1/2/3 ON ROOF. PROVIDE FLEX AT CONNECTION TO UNIT AND TRANSITION TO DISCHARGE SIZE OF UNIT. 17 OFFSET EXHAUST DUCT DOWN TO ALIGN MZEOUNTING HEIGHT TO MATCH ADJACENT RETURN AND SA GRILLES (APPROX. 10'-0" A.F.F), RE: ARCH. 18 OFFSET DUCT UP. 19 OFFSET DUCT DOWN BELOW BEAM. 20 LOCATION OF DDC CONTROL PANEL. 21 COORDINATE DUCT INSTALLATION WITH P.C. TO ALLOW INSTALLATION OF ROOF DRAINS ABOVE DUCTWORK. 22 24"X16" S.A. TAP (TYP. 6) TO FRONT DISCHARGE PLENUM PROVIDED WITH HOOD, HOOD, DISCHARGE PLENUM AND VOLUMNE DAMPERS BY FSC. 23 TERMINATE DUCT OPEN ENDED. PLAN NORTH Page 56 of 61 INTAKE MAU 1 EF 1 1 KEF 2 KEF KEF 3 EF 2 EF 3 1 RTU M500M200 1 M500 M200 2M500 M200 3 18 " x 1 8 " 18 " x 1 8 " 22"x22" 44 " x 2 4 " 10 " ø (BY FSC) (BY FSC)(BY FSC) A B C D E F G 1 2 3 4 5 6 7 6.7 1.1 1 2 34 5 64 7 8 9 10 10 11 11 11 11 11 11 11 11 11 11 11 11 60"x40" INTAKE 66"x44" 1 L 2 L EQ.EQ. 12 12 3 443 13 22 " x 2 2 " 24 " x 2 4 " NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: MECHANICAL ROOF PLAN M200 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 KEY NOTES 1 45° SHOE TAP FITTING. 2 PROVIDE AIRFOIL TYPE TURNING VANES IS S.A. ELBOW. 3 PROVIDE FLEX CONNECTION AT UNIT. COVER FLEX WITH SHEETMETAL SHROUD CONNECTED TO DUCT ONLY. 4 TRANSITION TO S.A./R.A. DISCHARGE SIZE OF UNIT. 5 R.A. DUCT TO OFFSET HORIZONTALLY WITHIN MAU CURB. COORDINATE WITH CAPTIVEAIRE TO ENSURE 36" CURB IS PROVIDED. 6 PROVIDE FLEX AT CONNECTION TO UNIT. 7 INSULATE EXTERIOR DUCTWORK WITH 2" THICK OUTDOOR INSULATION WITH ALUMINUM JACKETING. SEAL ALL JOINTS OF EXPOSED DUCT. 8 PROVIDE ALUMINUM SHEETMETAL ESCUTCHEON AT DUCT PENETRATION OF EXTERIOR WALL. CAULK AROUND DUCT AND RENDER WEATHER TIGHT. 9 OFFSET DUCT AS NECESSARY TO TRANSITION BETWEEN ROOF CONDITIONS. 10 ROUTE DUCTWORK WITHIN WEB OF SCISSOR TRUSS. COORDINATE WITH G.C. AND TRUSS MANUFACTURER. 11 PROVIDE REMOTE CABLE CONTROLLER TO BALANCE DIFFUSERS AT INACCESSIBLE CEILING, YOUNG REGULATOR MODEL 270-275 OR EQUAL. TRIM BALANCING TO BE COMPLETED BY RADIAL DAMPER AT DIFFUSER. 12 ENSURE LOUVERS ARE CENTERED SYMMETRICALLY ABOUT COLUMN LINE "D". 13 PACK END OF DUCT WITH 4" LINACOUSTIC INSULATION. PLAN NORTH 4' 16'2' 8' 1/8" = 1'-0" MECHANICAL ROOF PLAN Page 57 of 61 UNION 1 2 3 1 2 3 DISTANCE EQUAL TO A NEGATIVE STATIC PRESSURE (IN. W .C.) +1" OR POSITIVE STATIC PRESSURE (IN. W.C.) +1". SEE MECH. SCHEDULES FOR STATIC PRESSURE INFORMATION. MINIMUM DISTANCE EQUAL TO NEGATIVE STATIC PRESSURE (IN. W.C.) +1". OR A POSITIVE STATIC PRESSURE (IN. W.C.) +1". MINIMUM DRAIN PIPE SIZE EQUAL TO CONNECTION PROVIDED WITH EQUIPMENT. EQUIPMENT PAD UNIT CASING TO APPROVED LOCATION 1" AIR GAP FULL SIZE VENT/PRIMER OPENING CLEANOUT WITH PLUG DRAIN CONNECTION NOTES:1. DUCT WRAP TO EXTEND FROM TOP OF HOOD TO UNDERSIDE OF STRUCTURE. 16 GAUGE BLACK STEEL DUCT WITH ALL WELDED JOINTS FROM HOOD TO EXHAUST FAN. ALUMINUM FOIL COVER. PROVIDE ACCESS OPENINGS IN DUCT WRAP AT GREASE CLEAN- OUT LOCATIONS. FOLLOW DUCT WRAP MANUFACTURER'S INSTRUCTIONS. U.L. LISTED DUCT WRAP EQUAL TO FYREMASTER. CONTRACTOR TO INSTALL PER MANUFACTURER'S INSTRUCTIONS. TAKE CARE TO NOT OVER-TIGHTEN CLAMP BANDING. MEMBRANE 2 HR. DUCTWRAP. 2X BLOCKING INSULATION RE: ARCH. PREFAB ROOF CURB MIN. 40" MIN. 18" MOTOR HOUSING INLET NOTE:EXHAUST FAN SHALL BE U.L. LISTED FOR GREASE REMOVAL WOOD DECKING ROOF OPENING FRAMING (SEE STRUCTURAL) WELDED BLACK STEEL DUCTWORK VENTILATED EXTENDED CURB BASE APPROVED GREASE RECEPTOR KITCHEN HOOD MA X . 2' - 0 " BOTTOM OF JOISTS. 112'-00" 16" 16 GAUGE BLACK STEEL TOP OF HOOD @ 8'-6" A.F.F. (MAX) TYPE 1 HOOD BY FSEC 22"x10" 16 GAUGE BLACK STEEL THRU ROOF/FLOOR ABOVE. 2 HOUR U.L. LISTED DUCT WRAP EQUAL TO FYREMASTER. CEILING 8'-0" A.F.F. BOTTOM OF HOOD 6"-6" A.F.F. (MAX) 6" RTU'S STEEL ANGLE AT PERIMETER OF OPENING. RE: STRUCT. CONCRETE PAD COORD. LOCATION OF OPENING W/ G.C. METAL CURB. FURNISHED WITH UNIT WRAP CURB WITH RIGID BOARD INSULATION SCREWED INTO CURB SEALANT & BACKER ROD MEMBRANE FLASHING FULLY ADHERED TO INSULATION W/ BONDING ADHESIVE LAP SEALANT. WOOD DECK PRESSURE TREATED 2X WOOD BLOCKING AS REQ'D TO LEVEL CURB. NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: DIAGRAMS M300 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 SCALE: 12" = 1'-0" 4 COIL DRAIN PAN PIPING SCALE: 12" = 1'-0" 2 GREASE EXHAUST DUCT WRAP SCALE: 12" = 1'-0" 3 KITCHEN EXHAUST FAN SCALE: 12" = 1'-0" 1 EXHAUST DUCT CONNECTION - STRAIGHT DUCT SCALE: 12" = 1'-0" 5 CONCRETE PAD ROOF CURB2 Page 58 of 61 MAU-1 5,762 KEF-1 KEF-2EF-1 E.A. SUMMARY KEF-1 2,406 KEF-2 2,306 KEF-3 1,050 EF-1 800 EF-2 400 EF-3 300 EF-4 150 7,412 BUILDING AIR BALANCE - MAU-1 O.A.5,762 RTU-1 O.A. (MIN)3,100 -TOTAL EXHASUT AIR 7,412 1,450 BUILDING PRESSURIZATION APPROX 8,160 FT2 @ 0.05 CFM/FT =408 CFM. EF-2 KITCHENDINING KEF-3EF-3 RTU-1 3,100 EF-4 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: CONTROLS M400 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 MISC. CONTROL SEQUENCES *ELECTRIC BASEBOARD HEATER : INTEGRAL LINE VOLTAGE STATS. EBB-1 SERVING DINING SET AT 65° ADJ. *CABINET UNIT HEATERS : INTEGRAL LINE VOLTAGE STATS. CUH-1 SERVING ENTRY VESTIBULES SET AT 65° *EXHAUST FANS : EF-2 RUN CONTINUOUSLY ON HIGH CFM BETWEEN 8AM AND 8PM AND ON LOW CFM FROM 8:01PM TO 7:59AM. SCHEDULE TIMES WITH OWNER. : EF-1 OCC. SENSORS START/STOP. FAN TO DELAY "OFF" FOR 15 MINUTES. OCC. SENSORS FOR MULTIPLE ROOMS TO BE WIRED IN PARALLEL. SCALE:NOT TO SCALE1BUILDING AIR BALANCE EF-3 SERVING THE 3-COMPARTMENT POT SINK AREA TO BE STARTED AND STOPPED VIA TWIST TIMER WALL SWITCH, (0-60 MIN.) FURNISHED WITH FAN. *HOOD GAS SHUT OFF: INTERLOCK WIRING TO GAS SOLENOID VALVE FROM ANSUL PANEL. COORDINATE WITH HOOD ANSUL PANEL BY FSEC. UNOCCUPIED SCHEDULE OVERRIDE. TEMPERATURE/PRESSURE TRENDING CAPABILITY FOR ALL SUITES SINGLE ZONE VAV CONTROL SEQUENCES (RTU-1) * ALL DAMPER POSITIONS REFERENCED AS % RELATE TO % OF FULL LOAD/MAX FAN CFM.* ALL TEMPERATURE SET POINTS TO BE ADJUSTABLE.* ALL TIME DURATIONS TO BE ADJUSTABLE.* ALL PRESSURE SET POINTS TO BE ADJUSTABLE* AN OUTSIDE AIR TEMPERATURE SENSOR TO LIMIT THE VENTILATION AIR TO "MINIMUM" AS SCHEDULED AT TEMPERATURES HIGHER THAN 90 DEGREES AND LOWER THAN 0 DEGREES. * * * * * * * * * * THE VARIABLE AIR VOLUME PACKAGED ROOF TOP AIR HANDLING UNIT IS DESIGNED FOR COOLING AND HEATING AS WELL AS FOR TEMPERING THE REQUIRED OUTSIDE AIR VIA DEMAND CONTROLLED VENTILATION AND NIGHT SET BACK. COOLING - VIA THE SPACE TEMPERATUR SENSOR, FIRST STAGE OF COOLING IS ECONOMIZER MODE, SECOND STAGE WILL MODULATE FAN SPEED AND INITIATE COMPRESSOR OUTPUTS TO MEET SPACE TEMPERATURE SETPOINT. *RTU-1 TO PROVIDE 7,875 CFM. *A UNIT MOUNTED SMOKE DETECTOR IN THE RETURN AIR SECTION FOR RTU-1 TO SHUT DOWN THE SUPPLY FAN UPON DETECTION OF SMOKE / PRODUCTS OF COMBUSTION. DIRECT DIGITAL CONTROL (DDC) TECHNOLOGY TO BE USED TO PROVIDE FUNCTIONS NECESSARY FOR CONTROL OF MECHANICAL SYSTEMS ON THIS PROJECT AS INDICATED ON THE DRAWINGS, SPECIFICATIONS, AND SEQUENCE OF OPERATION. FURNISH AND INSTALL REQUIRED DDC ELEMENTS AND ALL ASSOCIATED INTERLOCKS COMMUNICATION AND 24 VOLT WIRING INCLUDING STEP DOWN TRANSFORMERS AND 120V WIRING WHERE NOT COVERED BY ELECTRICAL CONTRACTOR. THE RTU VARIABLE AIR VOLUME CONTROL SYSTEM IS AN INTEGRATED DIRECT DIGITAL CONTROL SYSTEM WITH THE REMOTE CONTROL PANEL LOCATED IN DETOX BUILDING. THIS CONTROL PANEL COMMUNICATES WITH LOCAL MICROPROCESSOR BASED CONTROLLERS AT THE RTU. BUILT-IN FEATURES INCLUDE: * * * * * * * OUTSIDE AIR, SUPPLY AND RETURN AIR TEMPERATURE FOR THE RTU DISCHARGE AIR TEMPERATURE MIXED AIR TEMPERATURE SUPPLY DUCT DISCHARGE HIGH STATIC PRESSURE SUPPLY FAN STATUS HIGH FILTER PRESSURE ALARM VIA ON/OFF PRESSURE SWITCH. NOTE: COORDINATE WITH OWNERS REPRESENTATIVE/BUILDING OPERATOR TO PROVIDE ALL REQUESTED MAPPABLE MONITORING AND CONTROL POINTS DDC CONTROLLER WITH LCD DISPLAY TO DISPLAY THE FOLLOWING (LOCATED IN THE DETOX BUILDING): SETPOINT AND CONTROL PARAMETERS FULLY ADJUSTABLE EITHER FROM THE REMOTE CONTROL PANEL, OR FROM A REMOTE LOCATION VIA AN ETHERNET CONNECTION. GENERAL APPLICATION CONTROLLER, NETWORK CONTROLLER COMMUNICATION AND SYSTEM FAILURES ARE DISPLAYED AT THE CENTRAL PANEL AS AN ALARM. THESE ALARMS/ALERTS CAN BE SENT TO A REMOTE SUPERVISOR LOCATION AT THE OWNER'S DIRECTION. A SINGLE CO2 SENSOR LOCATED IN THE MAIN RETURN AIR DUCT AT THE RTU TO MAINTAIN A 400 PPM DIFFERENTIAL BETWEEN THE O.A. AND R.A. O.A DAMPER TO MODULATE BETWEEN THE MINIMUM AND VENT POSITIONS IN CONJUNCTION WITH THE RETURN AIR DAMPER AT LEVELS ABOVE THE DIFFERENTIAL. * * * * BUILDING STATIC PRESSURE TO BE SENSED AT THE RETURN AIR CEILING CAVITY WITH RESPECT TO THE OUTSIDE. *THE RELIEF/EXHAUST FAN TO REMAIN OFF AND ITS ASSOCIATED DAMPER TO REMAIN FULLY CLOSED UNTIL THE BUILDING STATIC PRESSURE RAISES ABOVE THE 0.025" W.C. SET POINT AT WHICH POINT, MODULATE THE RELIEF DAMPER FULLY OPEN TO MAINTAIN THE SET POINT. IF DAMPER IS FULLY OPEN AND THE BUILDING PRESSURE IS ABOVE SET POINT FOR MORE THAN 15 MINUETS, START EXHAUST/RELIEF FAN. THE OSA AIR VOLUME CONTROLLER TO MODULATE THE DAMPERS TO MAINTAIN THE MINIMUM OSA AIR VOLUME SET POINT AS WELL AS TO MAINTAIN THE BUILDING PRESSURE SET POINT (0.025" W.C.) * * LOW TEMP ALARM FROM MIXED AIR TEMP SUPPLY FAN FAIL HIGH SUPPLY AIR DUCT PRESSURE ALL SAFETY ALARMS TO HAVE AUTOMATIC RESET. SAFETY ALARMS TO BE DISPLAYED AT THE CONTROLLER: PROGRAMMABLE TIME CLOCK TO SCHEDULE OCCUPIED/UNOCCUPIED HOURS. 100% AIR ECONOMIZER FOR FREE COOLING. SET UP/SET BACK TEMPERATURES. ADAPTIVE OPTIMAL START/STOP. BUILDING STATIC PRESSURE CONTROL DAMPER NORMAL (AKA FAIL) POSITIONS: OUTSIDE AIR DAMPER: CLOSED (NC) RETURN AIR DAMPER: OPEN (NO) NOTES: DESIGN INTENT: GENERAL: THE SCHEDULED OPERATION TIME IS 12 HOUR, VERIFY WITH OWNER. WHEN THE SUPPLY FAN IS OFF, ALL DAMPERS TO GO TO "NORMAL" POSITIONS. DISCHARGE AIR TEMPERATURE CONTROL: OSA VOLUME CONTROL: A. RELIEF/EXHAUST FAN DAMPER SEQUENCE: *RELIEF AIR/ POWER EXHAUST DAMPER: CLOSED (NC) * * * * * * * * * * FIELD CONTROLLER(S) RTU-1 SF F A N T R A C K I N G EF-2 START/STOP HI/LO STATUS EF-1 START/STOP OA / R A D A M P E R S COMM BUILDING PRESSURE OWNER PC/TABLET (WEB BASED BROWSING AND CONTROL) CONTROL SYSTEM CONCEPT ARCHITECTURE P OCC PO W E R E X H *GENERAL STANDBY - DURING THE OCCUPIED CYCLE, WHEN THERE ARE NO HEATING/COOLING DEMANDS, THE UNITS FAN TO OPERATE AT 50% OF MAX. (ADJ.) *HEATING - VIA THE SPACE TEMPERATURE SENSOR THE UNIT WILL MODUALTE FAN SPEED AND ( XXX MAX) AND BEGIN TO STAGE HEATING OUTPUTS TO MEET THE SPACE DEMAND. EF-3 STATUS S STATUS EF-4 SERVING THE MECHANICAL ROOM TO BE STARTED AND STOPPED VIA HIGH LIMIT STAT FURNISHED WITH FAN. T EF-4 START/STOP STATUS COMM TO BAS CONTROLLER AT DETOX BUILDING. Page 59 of 61 NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: CONTROLS M401 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 MAU VENTILATION CONTROL SEQUENCES O .A .M FI L T E R 17 % - 1 0 0 % E L E C T R O N I C MO D U L A T I N G G A S BU R N E R FAN S/SS DP O. A . D A M P E R R.A. R. A . S M O K E DE T E C T O R FI L T E R D P GA S V A L V E FA N S / S FR E E Z E S T A T PACKAGED STAND ALONE CONTROLS BY CAPTIVEAIRE SPACE TEMP T NOTE: ALL TEMPERATURE SET POINTS TO BE ADJUSTABLE. ALL CONTROL WIRING TO BE PLENUM RATED CABLE. THE MAKEUP AIR UNIT TO BE INTERLOCKED TO RUN CONTINUOUSLY WHENEVER THE KITCHEN HOOD EXHAUST FAN KEF-1/2 IS STARTED FROM THE HOOD STAT OR MANUAL START/STOP SWITCH AT THE HOOD. A RELAY FROM THE HOOD START/STOP SWITCH TO INITIATE THE MAU START/STOP AND CONTROL SEQUENCE. A PUSH BUTTON SELECTION SWITCH WILL DICTATE WEATHER THE SYSTEM IS IN SUMMER VENT MODE OR WINTER HEAT MODE. THE O.A. DAMPER AND DISCHARGE DAMPER TO FULLY OPEN AND RETURN AIR DAMPER TO FULLY CLOSE ONLY WHEN UNIT IS COMMANDED "ON". HEATING OR EVAPORATIVE COOLING TO BE MANUALLY SELECTED BY THE AREA OCCUPANT VIA THE SUMMER/WINTER SELECTOR SWITCH AT THE CONTROL PANEL. A TEMPERATURE SENSOR IN THE HOOD OVERRIDES THE MANUAL START/STOP SWITCH AT THE HOOD AND STARTS THE EF-3 AND MAU. A DISCHARGE AIR TEMPERATURE TRANSMITTER TO OPEN A TIMED FILL VALVE, CLOSE DRAIN VALVE TO WET THE EVAP. MEDIA AT 80° AND ABOVE. COORDINATE "FILL" VALVE "ON/OFF" TIME TO BE ADEQUATE TO SOAK THE EVAP. MEDIA AND MITIGATE WATER WASTE. AT 50° AND BELOW THE FULLY MODULATING (17% TO 100%) HEATING SECTION TO BE ENERGIZED AND MAINTAIN A 80° DISCHARGE AIR TEMPERATURE. A REMOTE SET POINT ADJUSTER ALLOWS THE USER TO ADJUST THE DISCHARGE AIR SET POINT. A SPACE TEMPERATURE TRANSMITTER TO OVERRIDE THE HEATING CONTROL AT 80°F. AN O.A. TEMPERATURE SENSOR TO CLOSE THE WATER MAKE UP VALVE AND OPEN THE RESERVOIR DRAIN VALVE AT 40°F ON THE EVAPORATIVE COOL MODULE AND ALL WATER TO DRAIN FROM THE UNIT (THIS TO ALSO OCCUR WHENEVER THE UNIT IS OFF). FREEZE STAT AND FIRE STAT SAFETIES TO SHUT DOWN THE UNIT. SMOKE DETECTOR IN RETURN AIR DUCT IS TO SHUT DOWN UNIT UPON DETECTION OF PRODUCTS OF COMBUSTION. IN "UNOCCUPIED" SCHEDULE UNIT TO START AND CIRCULATE HEATED AIR TO MAINTAIN MINIMUM 60° DB SPACE TEMP. O.A. DAMPER TO REMAIN FULLY CLOSED. R.A. AND DISCHARGE DAMPER TO FULLY OPEN. WHEN THE SUPPLY FAN HAS BEEN SHUT DOWN FOR SERVICING OR A LOSS IN ELECTRICAL POWER ALL CONTROL FUNCTIONS TO BE DEACTIVATED AND O.A. DAMPER TO FULLY CLOSE. FILTER DIFFERENTIAL PRESSURE SWITCH SET AT 0.5" WC. TO ALARM AT BAS. FIRE AND FREEZE STAT SIGNALS TO ALARM AT BAS. LAT DI S C H . T E M P FI R E S T A T M DI S C H A R G E D A M P E R M R. A . D A M P E R EV A P . C O O L ME D I A S C NO NC SNO DRAIN VALVE AI R F L O W S W I T C H DP FI L L V A L V E M NC WINTER HEAT SUMMER VENT FA N S / S EF-3 EF-3 CONTROL PANEL AT HOOD *BLOWER "ON" LIGHT EF-3 S/S HOOD STAT O.A. SENSOR REMOTE SET POINT SPACE TEMP. OVERRIDETT Page 60 of 61 FIRST FLOOR 100' - 0" MECH WELL 113' - 1 3/4" MAU 1 2 H 1 H (BY FSC) EF 1 1 KEF 2 KEF EF 2 EF 3 22 " x 1 0 " 10"ø6"ø 10"ø36"x22"16"x14" 12"x12"8"x8" 44"x24" 30"x22"10"ø 8"x8" 22 " x 1 0 " B C D E F 36"x22" FIRST FLOOR 100' - 0" MECH WELL 113' - 1 3/4" 2 KEF1 RTU 44"x24" 2 H KEF 3 (BY FSC) (BY FSC) 8"x8" 10 " x 2 2 " 30"x16"36"x22" 20 " x 7 6 " 22"x22" 1 21.1 44"x66" FIRST FLOOR 100' - 0" MECH WELL 113' - 1 3/4" MAU 1 EF 1 12"x28"22"x30" 8"x24" 24"x48" R.A. 22"x22" S.A. 1 21.1 40"x60" 7' - 9 " (BY FSC) 36"x22" 24 " x 4 8 " NOTE: DRAWINGS AND SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND SHALL REMAIN THE PROPERTY OF THE CONSULTING ENGINEERING GROUP L.L.C. ( A.K.A. THE CE GROUP ). COPIES OF THESE DOCUMENTS RETAINED BY THE CLIENT ARE FOR THE CLIENTS USE IN THE CONSTRUCTION OF THE PROJECT FOR WHICH THESE DOCUMENTS WERE PREPARED. ANY USE OF THESE DOCUMENTS, IN WHOLE OR IN PART, BY ANY MEANS WHATSOEVER TO CONSTRUCT ANY OTHER PROJECT OR FOR USE AS STOCK PLANS OR PROTOTYPE DESIGN FOR MULTIPLE BUILDING PROJECTS IS STRICTLY PROHIBITED, EXCEPT WITH THE SPECIFIC WRITTEN CONSENT OF THE CONSULTING ENGINEERING GROUP L.L.C. Prepared for BASIS Architecture P.C. Sheet Title: Sheet No: Issue: Date: SECTIONS M500 Ha r m o n y F o u n d a t i o n , I n c Di n i n g H a l l 16 0 0 F i s h H a t c h e r y R o a d Es t e s P a r k , C o l o r a d o 8 0 5 1 7 100% CD 03/28/14 4' 16'2' 8' 1/4" = 1'-0" EAST/WEST SECTION AT MECH. WELL 4' 16'2' 8' 1/4" = 1'-0" SECTION AT AHU 4' 16'2' 8' 1/4" = 1'-0" SECTION AT MAU Page 61 of 61