HomeMy WebLinkAboutPERMIT Info 10 Unit Bldg 800 MacGregor Ave 200608/14/2006 15:41 9705862459
CORNERSTONE ENG PAGE 02
CONTRACTOR/ SUBCONTRACTOR TOWN BUSINESS LICENSE AFFIDAVIT
Applicant Name: Black Canyon Inn
Business Name; Cornerstone Eraineering ctSurveying, Inc...
,Aling Address; 1,692 Big Thompson Axe. Suite 200 .Est.es Park CO 80517
Phone Number: (970) 586-2458
Address of Project: Bldg F 800 MacGregor Ave. Estes Park CO 80517
Type of Project: Residential.
Please list the required information for all contractor/subcontractor, who performed work/services for the above
Plumbing & Heating Specialists
Thermal concepts
2649 East Mulberry, Unit 19
Fort Collins, CO 80524
P.O. Box 1374, Lyons CO 80540 - 8262
131 Pleasant Ave. Joluistowa, CO 80534
P.O, Box 270066, Fort Collins CO 80527
1023 S. Lincoln Ave. Loveland, CO 80537
2416 Donella et 4A - Fort Collins, CO 80524
430 Olympus Road, Estes Park CO 80517
certify that this Affidavit represents a complete list of contractors/subcontractors who provided work/services
on the project described above, and I understand that Final Inspection or Certificate of Occupancy will not be
issued until all contractors/subcontractors listed above have acquired a current Town of Estes Park Business
License/
Vjpplicant's Signature; Date:
RETURN COMPLETED FORM TO:
TOWN CLERK'S OFFICE, TOWN OF ESTES PARK, P,O. BOX 1200, ESTES PARK, CO 80517
Initialed By: Town Clerkl:(,,OA,„,'"") Date; c. Building Official: Xe)--/Y Date: D 8--/‘ -06
6/14/02
08/14/2006 15:41 9705862459 CORNERSTONE ENG
PAGE 03
CONTRACTOR/ SUBCONTRACTOR TOWN BUSINESS LICENSE AFFIDAVIT
Applicant Name: Blackn ign
Business Name: Cornerstone Engineering & Surveying,_Inc,
.ailing Address: 1692_Big Thompson Ave. Suite. 200 Etes Park CO 80517
Phone Number: (970) 586-2458
Address ofProject:Bldg F 800
Type ofProject: Residential
Ave. Estes Par.
80517
Please list the required information for all contractor/subcontractor, who performed work/services for the above
ro'ect,
certify that this Affidavit represents a complete list of contractors/subcontractors who provided work/services
on the project described above, and I understand that Final Inspection or Certificate of Occupancy will not be
issued until all contractors/subcontractors listed above have acquired a current Town of Estes Park Business
License.
Applicant's Signature:
Date:
RETURN COMPLETED FORM TO:
TOWN CLERK'S OFFICE, TOWN OF ESTES PARK, P.O. BOX 1200, ESTES PARK, CO 80517
1, ‹2
Initialed By; Town Clerk: vi Date:
Building Official:)73
Date: 0876 796
6/14/02
08/14/2006 15:41 9705862459 CORNERSTONE ENG PAGE 01
CORNE I STO11E
SURVEYING. INC.
1692 Big Thompson- Suite 200
Estes Park, CO 80517
970.586.2458 Phone
970.5862459 Fax
TRANSMITTAL
Name : cONNIE
Organization: BUILDING DEPARTMENT
From: JUSTIN SPROUSr
Date; 8/3.4/06
Subject; CONCTRACT AFFIDAVIT
Pages:
Documents Transmitted:
For Approval As Requested
For Your Use X For Review X
Hard Copy mailed For Signature
Comments:
Comic;
here is another copy of the contractor affidavit for Black Canyon tun as you requested.
in Sp use
erston ngineering and Surveying
rou : @Ce5 ccc.com
CONTRACTOR/ SUBCONTRACTOR TOWN BUSINESS LICENSE AFFIDAVIT
Applicant Name: Black Canyon Inn
Business Name: Cornerstone Engineering & Surveying, Inc.
Mailing Address: 1692 Big Thompson Ave. Suite 200 Estes Park CO 80517
Phone Number: (970) 586-2458
Address of Project: Bldg F 800 MacGregor Ave. Estes Park CO 80517
Type of Project: Residential
Please list the required information for all contractor/subcontractor, who performed work/services for the above
roiect.
Business Name
Contact Name
Complete Address
Business
License #
Kearney & Son's Excavating
Mike Kearney
P.O. Box 3623, Estes Park CO 80517
20
Phillips Carpentry
Pat Phillips
2649 East Mulberry, Unit 19
Fort Collins, CO 80524
713
All Surfaces
Brian Wicen
P.O. Box 1374, Lyons CO 80540 - 8262
1167
Plumbing & Heating Specialists
Jim Sampson
131 Pleasant Ave. Johnstown, CO 80534
1182
Thermal Concepts
Mike Brown
P.O. Box 270066, Fort Collins CO 80527
16
Fiske Electric
Rob Denney
1023 S. Lincoln Ave. Loveland, CO 80537
239
Poudre Valley Air
Craig Larson
2416 Donella Ct #A - Fort Collins, CO 80524
125
Gold Roofing
Bill Goldsbury
1424 E. Eisenhower Blvd, Loveland CO 80537
559
Estes Park Painting & Decorating
Roger Ping
430 Olympus Road, Estes Park CO 80517
1031
Coulson Excavating
Jim Abbott
3609 N. County Rd 13, Loveland CO 80538
159
Performance Fire Protection
Ray Lawson
PMB #325, 453 E. Wonderview Ave
Estes Park CO 80517
616
I certify that this Affidavit represents a complete list of contractors/subcontractors who provided work/services
on the project described above, and I understand that Final Inspection or Certificate of Occupancy will not be
issued until all contractors/subcontractors listed above have acquired a current Town of Estes Park Business
License.
Applicant's Signature: Date:
RETURN COMPLE1ED FORM TO:
TOWN CLERK'S OFFICE, TOWN OF ESTES PARK, P.O. BOX 1200, ESTES PARK, CO 80517
Initialed By: Town Clerk: Date: Building Official: Date:
6/14/02
CONTRACTOR/ SUBCONTRACTOR TOWN BUSINESS LICENSE AFFIDAVIT
Applicant Name: Black Canyon Inn
Business Name: Cornerstone Engineering & Surveying, Inc.
Mailing Address: 1692 Big Thompson Ave. Suite 200 Estes Park CO 80517
Phone Number: (970) 586-2458
Address of Project: Bldg F 800 MacGregor Ave. Estes Park CO 80517
Type of Project: Residential
Please list the required information for all contractor/subcontractor, who performed work/services for the above
roiect.
Business Name
Contact Name
Complete Address
Business
License #
Superior Siding, LLC
Randy Schmidt
6408 Orbit Way, Fort Collins, CO 80525
1019
Garrett Schafmann Construction
Paul Garrett
P.O. Box 2293, Estes Park, CO 80517
529
Ed's Drywall Inc.
Ed Lewis
P.O. Box 1686, Estes Park CO 80517
234
Colorado Rose Red
Michaela Sigler
P.O. Box 2116, Estes Park CO 80517
1321
Estes Park Glass
Jeff Sessler
P.O. Box 33, Drake, CO 80515
335
Resolution Surfaces
Glen Pettet
14252 W. 44th Ave. Unit 13, Golden CO 80403
667
Garage Door
Pat Street
1059-B N. Colorado Ave. Loveland, CO 80537
633
Cornerstone Concrete
Bob Pavlish
P.O. Box 2494, Estes Park CO 80517
153
I certify that this Affidavit represents a complete list of contractors/subcontractors who provided work/services
on the project described above, and I understand that Final Inspection or Certificate of Occupancy will not be
issued until all contractors/subcontractors listed above have acquired a current Town of Estes Park Business
License.
Applicant's Signature:
Date:
RETURN COMPLE'I'ED FORM TO:
TOWN CLERK'S OFFICE, TOWN OF ESTES PARK, P.O. BOX 1200, ESTES PARK, CO 80517
Initialed By: Town Clerk: Date: Building Official: Date:
6/14/02
TOWN OF ESTES PARK
7f
I I • 4 ,
DATE: —So,ne, 0,2 / .2006
Town of Estes Park
Building Division
170 MacGregor Avenue
Estes Park, Co. 80517
47\
Re: Foundation Setback and Elevation Certification for LOT •
BLOCK — , B(&c- yoft.- otr SUBDIVISI8N;
ADRESS eoo Mar-- Ore-yr Ave. ,PERMIT # 77/ 1
To Whom It May Concern
Ts E.
On Mo,rc,k ,,act A006 , a field crew from this office the foundation
setbacks and elevations for the above -referenced lot, and found them to be in substantial
Compliance with the Drainage, Final Grading and Development Plan approved by the
Town of Estes Park.
Sincerely,
BY:
seal
http://www.estesnet,com
(970) 586-533'1 P.O. BOX 1200 170 MAC GREGOR AVENUE ESTES PARK, CO 8051 7 FAX (970) 586-0249
Calculations And Submittals:
Black Canyon Inn
10 Unit Lodge
800 McGregor Ave
Estes Park, CO
WIIIIM61101.uumapammMilm
!VISION OFEEI 3 E SAFE
14S REVIEW
PAWNED
S PPROVE
PPROV ED, AS C. FERECITE
ATE
clzifiTiitimsEm
11011011,
HYDRAULIC CALCULATIONS
FOR
Black Canyon Inn
10 Unit Lodge
Estes Park, CO
-DESIGN DATA -
OCCUPANCY CLASSIFICATION: NFPA 13R
DENSITY: Residential
AREA OF APPLICATION: 540 sqft
COVERAGE PER SPRINKLER: 320 Max sqft For Sidewall (16'x20')
400 Max sqft For Pendent (20'x20')
NUMBER OF SPRINKLERS CALCULATED: 4 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 108.5 gpm
TOTAL WATER REQUIRED (including hose): 108.5 gpm
FLOW AND PRESSURE (@ BOR): 108.5 gpm @ 98.9 psi
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 158.0 140.0 1500.0 157.9 108.5 115.4
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE
TOTAL HOSE STREAM ALLOWANCE AT SOURCE
OTHER HOSE STREAM ALLOWANCES
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS
NODE ANALYSIS DATA
108.5 GPM
0.0 GPM
0.0 GPM
108.5 GPM
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 7681.0 K= 4.90 30.3 27.0
2 7681.0 K= 4.90 31.2 27.4
3 7681.0 - - - - 40.1 - - -
4 7681.0 K= 4.90 33.0 28.1
5 7677.0 K= 4.20 38.3 26.0
6 7668.0 - - - - 45.7
7 7668.0 45.7
8 7668.0 44.1
9 7668.0 45.7
10 7668.0 44.6
11 7668.0 45.8
12 7668.0 44.9
13 7668.0 45.7
14 7668.0 48.3
15 7668.0 - - 54.7
16 7666.0 a - 73.0
17 7658.0 79.2
18 7658.0 80.1
TOR 7649.0 84.9
BOR 7649.0 98.9
U1 7645.0 104.3
U2 7670.0 - - - - 93.5
SOURCE 7620.0 SOURCE 115.4 108.5
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
PIPE DATA
PIPE TAG
END ELEV.
NODES (FT)
Pipe: 1
1 7681.0
2 7681.0
Pipe: 2
2 7681.0
12 7668.0
Pipe: 3
3 7681.0
6 7668.0
Pipe: 4
4 7681.0
8 7668.0
Pipe: 5
5 7677.0
10 7668.0
NOZ. PT DISC.
(K) (PSI) (GPM)
Q(GPM) DIA(IN) LENGTH
VEL(FPS) HW(C) (FT)
FL/FT
-27.0 1.101
4.9 30.3 27.0 9.1 150
4.9 31.2 27.4 0.118
PL
FTG
TL
8.00
8.00
PRESS.
SUM.
(PSI)
PF
PE
PV
- 54.3 1.394 PL 23.00 PF
4.9 31.2 27.4 11.4 150 FTG 5ET PE
0.0 44.9 0.0 0.137 TL 59.00 PV
0.0 1.101 PL 16.50 PF
0.0 40.1 0.0 0.0 150 FTG 3ET PE
0.0 45.7 0.0 0.000 TL 37.50 PV
-28.1 1.101 PL 22.00 PF
4.9 33.0 28.1 9.5 150 FTG 3ET PE
0.0 44.1 0.0 0.128 TL 43.00 PV
- 26.0 1.101 PL 10.25 PF
4.2 38.3 26.0 8.8 150 FTG ET PE
0.0 44.6 0.0 0.111 TL 21.25 PV
Pipe: 6
6 7668.0 0.0
7 7668.0 0.0
Pipe: 7
8 7668.0
9 7668.0
Pipe: 7A
10 7668.0
11 7668.0
Pipe: 8
12 7668.0
13 7668.0
Pipe: 9
13 7668.0
14 7668.0
Pipe: 10
7 7668.0
9 7668.0
Pipe: 11
9 7668.0
11 7668.0
Pipe: 11A
11 7668.0
14 7668.0
0.0 1.101 PL 10.25 PF
45.7 0.0 0.0 150 FTG T PE
45.7 0.0 0.000 TL 16.25 PV
- 28.1 1.101 PL 6.90 PF
0.0 44.1 0.0 9.5 150 FTG T PE
0.0 45.7 0.0 0.128 TL 12.90 PV
- 26.0 1.101 PL 5.00 PF
0.0 44.6 0.0 8.8 150 FTG T PE
0.0 45.8 0.0 0.111 TL 11.00 PV
-54.3 1.394 PL 5.50 PF
0.0 44.9 0.0 11.4 150 FTG ---- PE
0.0 45.7 0.0 0.137 TL 5.50 PV
- 54.3 1.394 PL 13.12 PF
0.0 45.7 0.0 11.4 150 FTG T PE
0.0 48.3 0.0 0.137 TL 19.12 PV
0.0 1.394 PL 7.90 PF
0.0 45.7 0.0 0.0 150 FTG ---- PE
0.0 45.7 0.0 0.000 TL 7.90 PV
-28.1 1.394 PL 1.00 PF
0.0 45.7 0.0 5.9 150 FTG ---- PE
0.0 45.8 0.0 0.041 TL 1.00 PV
- 54.1 1.394 PL 12.33 PF
0.0 45.8 0.0 11.4 150 FTG T PE
0.0 48.3 0.0 0.136 TL 18.33 PV
0.9
0.0
0.6
8.1
5.6
0.9
0.0
5.6
0.0
5.5
5.6
0.6
2.3
3.9
0.5
0.0
0.0
0.0
1.6
0.0
0.6
1.2
0.0
0.5
0.8
0.0
0.9
2.6
0.0
0.9
0.0
0.0
0.0
0.0
0.0
0.2
2.5
0.0
0.9
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
• DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
PIPE TAG
END ELEV. NOZ. PT DISC.
NODES (FT) (K) (PSI) (GPM)
Pipe: 12
14 7668.0 0.0 48.3
15 7668.0 0.0 54.7
Pipe: 13
15 7668.0 0.0 54.7
16 7666.0 0.0 73.0
Pipe: 13A
16 7666.0 0.0
17 7658.0 0.0
Pipe: 14
17 7658.0
18 7658.0
Q(GPM) DIA(IN) LENGTH
VEL(FPS) HW(C) (FT)
FL/FT
- 108.5 1.394
0.0 22.8 150
0.0 0.492
- 108.5
0.0 22.8
0.0
PL 7.00
FTG E
TL 13.00
PRESS.
SUM.
(PSI)
PF
PE
PV
6.4
0.0
3.5
1.394 PL 17.50 PF 17.5
150 FTG 2ET PE 0.9
0.492 TL 35.50 PV 3.5
- 108.5 2.003 PL 13.50 PF
73.0 0.0 11.0 150 FTG ET PE
79.2 0.0 0.084 TL 32.50 PV
0.0 79.2
0.0 80.1
Pipe: 15
18 7658.0 0.0 80.1
TOR 7649.0 0.0 84.9
Pipe: 16
BOR 7649.0
TOR 7649.0
Pipe: 17
BOR 7649.0
U1 7645.0
Pipe: 18
U1 7645.0
U2 7670.0
- 108.5 2.003 PL 2.00 PF
0.0 11.0 150 FTG E PE
0.0 0.084 TL 11.00 PV
- 108.5
0.0 11.0
0.0
2.003 PL 9.00 PF
150 FTG G PE
0.084 TL 10.51 PV
FIXED PRESSURE LOSS DEVICE
0.0 98.9 0.0 14.0 psi, 108.5 gpm
0.0 84.9 0.0
0.0 98.9
0.0 104.3
0.0 104.3
0.0 93.5
- 108.5
0.0 11.1
0.0
2.000 PL 25.00 PF
140 FTG 2EG PE
0.096 TL 37.46 PV
2.7
3.5
0.8
0.9
0.0
0.8
0.9
3.9
0.8
3.6
1.7
0.8
-108.5 8.390 PL 425.00 PF 0.1
0.0 0.6 140 FTG 5E PE -10.8
0.0 0.000 TL 580.00 PV 0.0
Pipe: 19 -108.5 6.280 PL 600.00 PF 0.3
U2 7670.0 0.0 93.5 0.0 1.1 140 FTG 4E PE 21.7
SOURCE 7620.0 SRCE 115.4 (N/A) 0.000 TL 696.00 PV 0.0
NOTES:
(1) Calculations were performed by the HASS 7.3
under license no. 49011032 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
computer program
(2) The system has been calculated to provide an average
imbalance at each node of 0.005 gpm and a maximum
imbalance at any node of 0.101 gpm.
(3) Velocity pressures are printed for information only and are
not used in balancing the system. Maximum water velocity
is 22.8 ft/sec at pipe 13.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: *
Diameter
(in)
2.067
PAGE: D
Diameter
(in)
6.280
8.390
PAGE: P
Diameter
(in)
1.101
1.394
2.003
MATERIAL: S40 HWC: 120
Equivalent Fitting Lengths in Feet
E T L C B G A
Ell Tee LngEll ChkVly BfyVly GatVly AlmChk
5.00 10.00 3.00 11.00 6.00 1.00 10.00
MATERIAL: DIRON HWC: 140
Equivalent Fitting
E T L C
E11 Tee LngEll ChkV1v
24.00 52.00 16.00 55.00
31.00 60.00 22.00 78.00
MATERIAL: CPVC HWC: 150
Equivalent Fitting
E T L G
Ell Tee LngEll GatVly
5.00 6.00 0.00 1.51
6.00 6.00 0.00 1.51
9.00 10.00 0.00 1.51
Lengths in Feet
B G N
BfyVly GatVly NPTee
17.00 5.00 52.00
21.00 7.00 60.00
Lengths in Feet
C B
ChkVly BtyV1v
7.55 9.06
10.57 9.06
16.61 9.06
D
DPV1v
10.00
N
NPTee
10.00
° D���z 4/I8/20O6C �\208gBI0KLER SYSTEM HYDRAULIC ANALYSIS gage 5
06 CALCG\BIACK CANYON INN\BIACK CANYON I00 SIDOWALL m PENDENTSDF
JOB TITLE: Black Canyon Inn
'
WATER SUPPLY ANALYSIS
0,0
-14,7
,
-
-
-
-
_
_
I
�
=
2
I I | I . ! I I I
400600 800 1000 1200 I400 1600 l800 2000
FLOW (GPM)
LEGEND
Available pressure
157'86 psi @ I08'5 gpm
� Required pressure
II5'40 psi @ I08'5 gpm
HYDRAULIC CALCULATIONS
FOR
Black Canyon Inn
10 Unit Lodge
Estes Park, CO
-DESIGN DATA -
OCCUPANCY CLASSIFICATION: NFPA 13R
DENSITY: Residential
AREA OF APPLICATION: 540 sqft
COVERAGE PER SPRINKLER: 320 Max sqft For Sidewall (16'x20')
400 Max sqft For Pendent (20'x20')
NUMBER OF SPRINKLERS CALCULATED: 4 sprinklers
TOTAL SPRINKLER WATER FLOW REQUIRED: 86.1 gpm
TOTAL WATER REQUIRED (including hose): 86.1 gpm
FLOW AND PRESSURE (0 BOR): 86.1 gpm @ 72.6 psi
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 1
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
WATER SUPPLY DATA
SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D
NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS.
TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI)
SOURCE 158.0 140.0 1500.0 157.9 86.1 87.7
AGGREGATE FLOW ANALYSIS:
TOTAL FLOW AT SOURCE
TOTAL HOSE STREAM ALLOWANCE AT SOURCE
OTHER HOSE STREAM ALLOWANCES
TOTAL DISCHARGE FROM ACTIVE SPRINKLERS
NODE ANALYSIS DATA
86.1 GPM
0.0 GPM
0.0 GPM
86.1 GPM
NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE
(FT) (PSI) (GPM)
1 7681.0 K= 4.90 18.4 21.0
2 7681.0 K= 4.90 19.0 21.3
3 7681.0 K= 4.90 19.9 21.9
4 7681.0 K= 4.90 19.9 21.9
5 7677.0 - - - - 26.2
6 7668.0 28.5
7 7668.0 29.8
8 7668.0 29.0
9 7668.0 30.0
10 7668.0 30.1
11 7668.0 30.1
12 7668.0 29.7
13 7668.0 30.2
14 7668.0 31.8
15 7668.0 36.0
16 7666.0 98.2
17 7658.0 53.5
18 7658.0 - 54.1
TOR 7649.0 - - _ 58.6
BOR 7649.0 72.6
Ul 7645.0 76.7
U2 7670.0 - - - - 65.9
SOURCE 7620.0 SOURCE 87.7 86.1
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
PIPE DATA
PIPE TAG
END
NODES
ELEV.
(FT)
Pipe: 1
1 7681.0
2 7681.0
Pipe: 2
2 7681.0
12 7668.0
NOZ. PT DISC.
(K) (PSI) (GPM)
Q(GPM) DIA(IN) LENGTH
VEL(FPS) HW(C) (FT)
FL/FT
- 21.0
4.9 18.4 21.0 7.1
4.9 19.0 21.3
4.9 19.0
0.0 29.7
1.101 PL
150 FTG
0.074 TL
8.00
8.00
PRESS.
SUM.
(PSI)
PF
PE
PV
- 42.3 1.394 PL 23.00 PF
21.3 8.9 150 FTG 5ET PE
0.0 0.086 TL 59.00 PV
Pipe: 3 -21.9
3 7681.0 4.9 19.9 21.9 7.4
6 7668.0 0.0 28.5 0.0
Pipe: 4 -21.9
4 7681.0 4.9 19.9 21.9 7.4
8 7668.0 0.0 29.0 0.0
Pipe: 5
5 7677.0 0.0 26.2
10 7668.0 0.0 30.1
Pipe: 6
6 7668.0 0.0 28.5
7 7668.0 0.0 29.8
Pipe: 7
8 7668.0
9 7668.0
0.0 29.0
0.0 30.0
Pipe: 7A
10 7668.0 0.0 30.1
11 7668.0 0.0 30.1
Pipe: 8
12 7668.0
13 7668.0
1.101 PL 16.50 PF
150 FTG 3ET PE
0.080 TL 37.50 PV
1.101 PL 22.00 PF
150 FTG 3ET PE
0.080 TL 43.00 PV
0.0 1.101 PL 10.25 PF
0.0 0.0 150 FTG ET PE
0.0 0.000 TL 21.25 PV
- 21.9 1.101 PL 10.25 PF
0.0 7.4 150 FTG T PE
0.0 0.080 TL 16.25 PV
-21.9 1.101 PL 6.90 PF
0.0 7.4 150 FTG T PE
0.0 0.080 TL 12.90 PV
0.0 1.101 PL 5.00 PF
0.0 0.0 150 FTG T PE
0.0 0.000 TL 11.00 PV
- 42.3 1.394 PL 5.50 PF
0.0 29.7 0.0 8.9 150 FTG ---- PE
0.0 30.2 0.0 0.086 TL 5.50 PV
Pipe: 9
13 7668.0 0.0
14 7668.0 0.0
Pipe: 10
7 7668.0
9 7668.0
Pipe: 11
9 7668.0
11 7668.0
Pipe: 11A
11 7668.0
14 7668.0
- 42.3 1.394 PL 13.12 PF
30.2 0.0 8.9 150 FTG T PE
31.8 0.0 0.086 TL 19.12 PV
- 21.9
0.0 29.8 0.0 4.6
0.0 30.0 0.0
1.394 PL 7.90 PF
150 FTG ---- PE
0.025 TL 7.90 PV
- 43.7 1.394 PL 1.00 PF
0.0 30.0 0.0 9.2 150 FTG ---- PE
0.0 30.1 0.0 0.092 TL 1.00 PV
- 43.7 1.394 PL 12.33 PF
0.0 30.1 0.0 9.2 150 FTG T PE
0.0 31.8 0.0 0.092 TL 18.33 PV
0.6
0.0
0.3
5.1
5.6
0.5
3.0
5.6
0.4
3.5
5.6
0.4
0.0
3.9
0.0
1.3
0.0
0.4
1.0
0.0
0.4
0.0
0.0
0.0
0.5
0.0
0.5
1.7
0.0
0.5
0.2
0.0
0.1
0.1
0.0
0.6
1.7
0.0
0.6
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
PIPE TAG Q(GPM) DIA(IN) LENGTH PRESS.
END ELEV. NOZ. PT DISC. VEL(FPS) HW(C) (FT) SUM.
NODES (FT) (K) (PSI) (GPM) FL/FT (PSI)
Pipe: 12 -86.1 1.394 PL 7.00 PF 4.2
14 7668.0 0.0 31.8 0.0 18.1 150 FTG E PE 0.0
15 7668.0 0.0 36.0 0.0 0.321 TL 13.00 PV 2.2
Pipe: 13 -86.1 1.394 PL 17.50 PF 11.4
15 7668.0 0.0 36.0 0.0 18.1 150 FTG 2ET PE 0.9
16 7666.0 0.0 48.2 0.0 0.321 TL 35.50 PV 2.2
Pipe: 13A -86.1 2.003 PL 13.50 PF 1.8
16 7666.0 0.0 48.2 0.0 8.8 150 FTG ET PE 3.5
17 7658.0 0.0 53.5 0.0 0.055 TL 32.50 PV 0.5
Pipe: 14 -86.1 2.003 PL 2.00 PF 0.6
17 7658.0 0.0 53.5 0.0 8.8 150 FTG E PE 0.0
18 7658.0 0.0 54.1 0.0 0.055 TL 11.00 PV 0.5
Pipe: 15 -86.1 2.003 PL 9.00 PF 0.6
18 7658.0 0.0 54.1 0.0 8.8 150 FTG G PE 3.9
TOR 7649.0 0.0 58.6 0.0 0.055 TL 10.51 PV 0.5
Pipe: 16 FIXED PRESSURE LOSS DEVICE
BOR 7649.0 0.0 72.6 0.0 14.0 psi, 86.1 gpm
TOR 7649.0 0.0 58.6 0.0
Pipe: 17 -86.1 2.000 PL 25.00 PF 2.4
BOR 7649.0 0.0 72.6 0.0 8.8 140 FTG 2EG PE 1.7
U1 7645.0 0.0 76.7 0.0 0.063 TL 37.46 PV 0.5
Pipe: 18 -86.1 8.390 PL 425.00 PF 0.0
U1 7645.0 0.0 76.7 0.0 0.5 140 FTG 5E PE -10.8
U2 7670.0 0.0 65.9 0.0 0.000 TL 580.00 PV 0.0
Pipe: 19 -86.1 6.280 PL 600.00 PF 0.2
U2 7670.0 0.0 65.9 0.0 0.9 140 FTG 4E PE 21.7
SOURCE 7620.0 SRCE 87.7 (N/A) 0.000 TL 696.00 PV 0.0
NOTES:
(1) Calculations were performed by the HASS 7.3 computer program
under license no. 49011032 granted by
HRS Systems, Inc.
4792 LaVista Road
Tucker, GA 30084
(2) The system has been calculated to provide an average
imbalance at each node of 0.004 gpm and a maximum
imbalance at any node of 0.092 gpm.
(3) Velocity pressures are printed for information only and are
not used in balancing the system. Maximum water velocity
is 18.1 ft/sec at pipe 12.
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
(4) PIPE FITTINGS TABLE
Pipe Table Name: STANDARD.PIP
PAGE: *
Diameter
(in)
MATERIAL: S40 HWC: 120
Equivalent Fitting
E T L C
Ell Tee LngEll ChkVly
2.067 5.00 10.00 3.00 11.00
PAGE: D
Diameter
(in)
MATERIAL: DIRON HWC: 140
Equivalent Fitting
E T L C
Ell Tee LngEll ChkVly
6.280 24.00 52.00 16.00 55.00
8.390 31.00 60.00 22.00 78.00
PAGE: P
Diameter
(in)
1.101
1.394
2.003
MATERIAL: CPVC HWC: 150
Equivalent Fitting
E T L G
Ell Tee LngEll GatVly
5.00 6.00 0.00 1.51
6.00 6.00 0.00 1.51
9.00 10.00 0.00 1.51
Lengths in Feet
B G A
BfyVly GatVly AlmChk
6.00 1.00 10.00
Lengths in Feet
B G N
BfyVly GatVly NPTee
17.00 5.00 52.00
21.00 7.00 60.00
Lengths in Feet
C B
ChkVly BtyVly
7.55 9.06
10.57 9.06
16.61 9.06
D
DPV1v
10.00
N
NPTee
10.00
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 5
DATE: 4/18/2006C:\2006 CALCS\BLACK CANYON INN\BLACK CANYON INN SIDEWALL & PENDENT.SDF
JOB TITLE: Black Canyon Inn
WATER SUPPLY ANALYSIS
160.1
140.0
G120.0
A
U
G
E100.0
P 2
R 3
E 80.0
S
S
U
R 60.0
E
(
p 40.0
s
i
20.0
Static: 158.00 psi Resid: 140.00 psi Flow: 1500.0 gpm
4
1
1
2
0.0
-14.7
I I I I I I 1 1
400600 800 1000 1200 1400 1600 1800 2000
FLOW (GPM)
LEGEND
Available pressure
157.91 psi @ 86.1 gpm
1 Required pressure
87.69 psi @ 86.1 gpm
'NCO/Fire & Building
Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB — Z8, 4.2, 5.6, and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Quick Response, Standard Coverage
General
Description
The Series TY FRB, 2.8, 4.2, 5.6, and
8.0 K-factor, Upright and Pendent
Sprinklers described in this data sheet
are quick response - standard cover-
age, decorative 3 mm glass bulb type
spray sprinklers designed for use in
light or ordinary hazard, commercial
occupancies such as banks, hotels,
shopping malls, etc.
The recessed version of the Series
TY FRB Pendent Sprinkler, where ap-
plicable, is intended for use in areas
with a finished ceiling. It uses either a
two-piece Style 10 (1/2 inch NPT) or
Style 40 (3/4 inch NPT) Recessed Es-
cutcheon with 1/2 inch (12,7 mm) of
recessed adjustment or up to 3/4 inch
(19,1 mm) of total adjustment from the
flush pendent position, or a two-piece
Style 20 (1/2 inch NPT) or Style 30 (3/4
inch NPT) Recessed Escutcheon with
1/4 inch (6,4 mm) of recessed adjust-
ment or up to 1/2 inch (12,7 mm) of
total adjustment from the flush pen-
dent position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the fixed pipe
drops to the sprinklers must be cut.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at -
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
An intermediate level versions of the
Series TY FRB Pendent Sprinklers are
detailed in Technical Data Sheet
TFP356, and Sprinkler Guards are de-
tailed in Technical Data Sheet TFP780
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner Is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY1131 -
TY1231 -
TY2131 -
TY2231 -
TY3131 -
Upright 2.8K, 1/2"NPT
Pendent 2.8K, 1/2"NPT
Upright 4.2K, 1/2"NPT
Pendent 4.2K, 1/2"NPT
Upright 5.6K, 1/2"NPT
TY3231 - Pendent 5.6K, 1/2"NPT
TY4131 - Upright 8.0K, 3/4"NPT
TY4231 - Pendent 8.0K, 3/4"NPT
Technical
Data
Approvals
UL and C-UL Listed.
FM, LPCB, and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K = 2.8 GPM/psi1/2 (40,3 LPM/barli2)
K = 4.2 GPM/psili2 (60,5 LPM/barli2)
K = 5.6 GPM/psis/2 (80,6 LPM/barli2)
K = 8.0 GPM/psin2 (115,2 LPM/barl/2)
Temperature Ratings
Refer to Table A and B
Page 1 of 8
JULY, 2004 TFP171
Page 2 of 8
TFP171
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING ** NOMINAL
SURFACE 1/2 MAKE -IN
NPT
2-1/4"
(57,2 mm) 1
1-9/16"
(39,7 mm)
SSP DEFLECTOR *
PENDENT
1 - Frame 3 - Sealing
2 - Button Assembly
STYLE 10 or 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
2-7/8" (73,0 mm) DIA. --,-]
SSU*
DEFLECTOR
7/16"
(11,1 mm)
NOMINAL
MAKE -IN
2-3/16"
(55,6 mm)
1/2" NPT** f +
RECESSED PENDENT UPRIGHT
CROSS SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 1
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY1131) AND PENDENT (TY1231) SPRINKLERS
2.8 K-FACTOR, 1/2 INCH NPT
4 - Bulb
5 - Compression
Screw
6 - Deflector
7 - Bushing
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING ** NOMINAL
SURFACE 1/2" MAKE -IN
NPT
1
2-3/16"
(55,6 mm)
SSP DEFLECTOR *
PENDENT
1-Frame
2-Button
STYLE 10 or 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
2-7/8" (73,0 mm) DIA, --4'
SSU*
DEFLECTOR
7/16"
(11,1 mm)
NOMINAL
MAKE -IN
i l
1/2" NPT **
RECESSED PENDENT UPRIGHT
3 - Sealing 4 - Bulb
Assembly 5 - Compression
Screw
6 - Deflector
1
2-3/16"
(55,6 mm)
CROSS SECTION
*
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 2
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY2131) AND PENDENT (TY2231) SPRINKLERS
4.2 K-FACTOR, 1/2 INCH NPT
Finishes
Sprinkler: Refer to Table A and B
Recessed Escutcheon: White Coated,
Chrome Plated, or Brass Plated
Physical Characteristics
Frame Bronze
Button Brass/Copper
Sealing Assembly
Beryllium Nickel w/Teflont
Glass
Compression Screw Bronze
Deflector ....... Copper/Bronze
Bushing (K=2.8) Bronze
Bulb
Operation
The glass Bulb contains a fluid which
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb, allowing the sprinkler to
activate and water to flow.
t DuPont Registered Trademark
1/2" (12,7 mm)
3/4" ** NOMINAL
NPT MAKE -IN
TFP171
Page 3 of 8
ESCUTCHEON 7/16" (11,1 mm)
PLATE SEATING 1/2" ** NOMINAL
SURFACE NPT MAKE -IN
2-3/16°
(55,6 mm) I
1-1/2'
(38,1 mm)
SSP DEFLECTOR*
1 - Frame
2-Button
STYLE 10 or 20
RECESSED
ESCUTCHEON
WRENCH
FLATS
2-7/8" (73,0 mm) DIA. --•--1
PENDENT RECESSED PENDENT
3 - Sealing 4 - Bulb 6 - Deflector
Assembly 5 - Compression
Screw
SSU*
DEFLECTOR
7/16"
(11,1 mm)
NOMINAL
MAKE -IN
1/2" NPT**
UPRIGHT CROSS SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
** Pipe thread connections per ISO 7/1 can be provided on
special request.
2-3/16"
(55,6 mm)
*
t
QUICK RESPONSE SERIES TY-FRB UPRIFIGURE 3
GHT (TY3131) AND PENDENT (TY3231) SPRINKLERS
5.6 K-FACTOR, 1/2 INCH NPT
ESCUTCHEON
PLATE SEATING
SURFACE
2-5/16"
(58,7 mm)
1-9/16"
(39,7 mm)
SSP DEFLECTOR *
PENDENT
1 - Frame 3 = Sealing
2 - Button Assembly
STYLE 30 or 40
RECESSED
ESCUTCHEON
Vir
-"-- 2-7/8" (73,0 mm) DIA.
RECESSED PENDENT
WRENCH
F
LATS
FLATS
4 - Bulb
5 - Compression
Screw
6 Deflector
SSU*
DEFLECTOR
1/2"
(12,7 mm)
NOMINAL
MAKE -IN
2- /4°
(57,2 mm)
3/4" NPT**
UPRIGHT
CROSS SECTION
* Temperature rating is indicated on deflector or adjacent to
orifice seat on frame.
**Pipe thread connections per ISO 7/1 can be provided on
special request.
FIGURE 4
QUICK RESPONSE SERIES TY-FRB UPRIGHT (TY431) AND PENDENT (TY4231) SPRINKLERS
8.0 K-FACTOR, 3/4 INCH NPT
*
Design
Criteria
The Series TY-FRB Pendent and Up-
right Sprinklers are intended for fire
protection systems designed in ac-
cordance with the standard installation
rules recognized by the applicable
Listing or Approval agency (e.g., UL
Listing is based on the requirements of
NFPA 13, and FM Approval is based
on the requirements of FM's Loss Pre-
vention Data Sheets ). Only the Style
10, 20, 30, or 40 Recessed Escutch-
eon, as applicable, is to be used for
recessed pendent installations.
Installation
The Series TY-FRB Sprinklers must be
installed in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
Page 4 of 8
SPRINKLER
FINISH (See
CHROME
I PLATED
1, 2, 3, 5
Note 7)
WHITE""
(POLYESTER
K
TYPE
TEMP.
BULB
LIQUID
NATURAL
BRASS
2.8
1/2"
PENDENT
(TY1231)
and
UPRIGHT
(TY1131)
135°F/57°C
Orange
155"F/68°C
Red
175°F/79°C
Yellow
200°F/93°C
Green
286°F/141°C
Blue
NPT
135°F/57°C
Orange
RECESSED
PENDENT
155°F/68°C
Red
(TY1231)*
175°F/79°C
Yellow
Figure 5
200°F/93°C
Green
1, 2, 5
135"F/57°C
Orange
RECESSED
PENDENT
155°F/68°C
Red
(TY1231)**
175°F/79°C
Yellow
Figure 6
200°F/93°C
Green
135°F/57°C
Orange
P(n2231;
155°F/68°C
Red
and
175°F/79°C
Yellow
UPRIGHT
200°F/93°C
Green
4.2
(TY2131)
1/2"
286°F/141°C
Blue
1,2
135°F/57°C
Orange
NPT
RECESSED
PENDENT
155°F/68°C
Red
(TY2231)*
175°F/79°C
Yellow
Figure 7
200°F/93°C
Green
135°F/57°C
Orange
RECESSED
PENDENT
155°F/68°C
Red
(TY2231)"
175°F/79°C
Yellow
Figure 8
200°F/93°C
Green
NOTES
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response
Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprin-
klers.
5. Approved by the City of New York under MEA 354-01-E.
7. Where Polyester Coated Sprinklers are noted to be UL and C-UL Listed, the sprin-
klers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment
Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment
Recessed Escutcheon, as applicable.
"" Frame and Deflector only. Listings and approvals apply to color (Special Order).
N/A: Not Available
TABLE A
LABORATORY LISTINGS AND APPROVALS
2.8 AND 4.2 K-FACTOR SPRINKLERS
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm) for the 135°F/57°C to 3/32
inch (2,4 mm) for the 286°F/141°C
temperature ratings.
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm), A maxi-
mum of 21 ft. lbs. (28,5 Nm) of torque
may be used to install sprinklers with
1/2 NPT connections. A leak tight 3/4
TFP171
inch NPT sprinkler joint should be ob-
tained with a torque of 10 to 20 ft.lbs.
(13,4 to 26,8 Nm). A maximum of 30
ft.lbs. (40,7 Nm) of torque is to be used
to install sprinklers with 3/4 NPT con-
nections. Higher levels of torque may
distort the sprinkler inlet and cause
leakage or impairment of the sprinkler.
Do not attempt to make-up for insuffi-
cient adjustment in the escutcheon
plate by under- or over -tightening the
sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series TY-FRB Pendent and Up-
right Sprinklers must be installed in
accordance with the following instruc-
tions.
Step 1. Pendent sprinklers are to be
installed in the pendent position, and
upright sprinklers are to be installed in
the upright position.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 13).
With reference to Figures 1, 2, 3, and
4, the W-Type 6 Sprinkler Wrench is to
be applied to the sprinkler wrench
flats.
The Series TY-FRB Recessed Pen-
dent Sprinklers must be installed in
accordance with the following instruc-
tions.
Step A. After installing the Style 10.
20, 30, or 40 Mounting Plate, as appli-
cable, over the sprinkler threads and
with pipe thread sealant applied to the
pipe threads, hand tighten the sprin-
kler into the sprinkler fitting.
Step B. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 14). With reference to Figure 1,
2, 3, and 4, the W-Type 7 Recessed
Sprinkler Wrench is to be applied to
the sprinkler wrench flats.
Step C. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 10, 20, 30, or
40 Closure over the Series TY-FRB
Sprinkler and push the Closure over
the Mounting Plate until its flange
comes in contact with the ceiling.
TFP171
Page 5 of 8
SPRINKLER FINISH (See Note 8)
K
TYPE
TEMP.
BULB
LIQUID
NATURAL
BRASS
CHROME
PLATED
WHITE*
POLYESTER
LEAD
COATED
5.6
1/2"
NPT
PENDENT
(TY3231)
and
UPRIGHT
(TY3 31)
135°F/57°C
Orange
1,2,3,5
155°F/68°C
Red
1,2,3,4,5,6,7
175°F/79°C
Yellow
200°F/93°C
Green
286F/141°C
Blue
RECESSED
PENDENT
(TY3231)*
Figure 9
135°F/57°C
Orange
1, 2, 4, S
N/A
155°F/68°C
Red
175°F/79°C
Yellow
200°F/93°C
Green
RECESSED
PENDENT
(TY3231p•
Figure 10
135°F/57°C
Orange
1, 2, 3, 4, 5
1, 2, 4, 5
N/A
155°F/68°C
Red
175F/79°C
Yellow
200°F/93°C
Green
8.0UPR
NPT
PENDENT
(TY4231)
and
4131)
(TY3/4"
135F/57°C
Orange
1,2,3,4,5,6,7
1, 2, 5
155°F/68°C
Red
175°F/79°C
Yellow
200°F/93°C
Green
286°F/141°C
Blue
RECESSED
PENDENT
(TY4231)*
Figure 11
135°F/57°C
Green
1, 2, 4, 5
N/A
155°F/68°C
Orange
175°F/79°C
Red
200F/93°C
Yellow
RECESSED
PENDENT
135°F/57°C
Orange
1, 2, 3, 4, 5
N/A
155F/68°C
Red
(TY4231)**
Figure 12
175°F/79°C
Yellow
200°F/93°C
Green
NOTES:
1. Listed by Underwriters Laboratories, Inc. (UL) as Quick Response Sprinklers.
2. Listed by Underwriters Laboratories, Inc. for use in Canada (C-UL) as Quick Response Sprinklers.
3. Approved by Factory Mutual Research Corporation (FM) as Quick Response Sprinklers.
4. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 007k/04) as Quick Response Sprinklers; however, the
LPCB does not rate the thermal sensitivity of recessed sprinklers.
5. Approved by the City of New York under MEA 354-01-E.
6. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53,428•3377).
7. Approved by the Loss Prevention Certification Board (LPCB Ref. No. 094a/06) as Quick Response Sprinklers.
8. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as
Corrosion Resistant Sprinklers. Where Lead Coated Sprinklers are noted to be FM Approved, the sprinklers are FM Approved as a
Corrosion Resistant Sprinklers.
* Installed with Style 10 (1/2" NPT) or Style 40 (3/4" NPT) 3/4" Total Adjustment Recessed Escutcheon, as applicable.
Installed with Style 20 (1/2" NPT) or Style 30 (3/4" NPT) 1/2" Total Adjustment Recessed Escutcheon, as applicable,
"' Frame and Deflector only. Listings and approvals apply to color (Special Order)..
N/A: Not Available
TABLE B
LABORATORY LISTINGS AND APPROVALS
5.6 AND 8.0 K-FACTOR SPRINKLERS
Page 6 of 8
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4' DIA.
(57,2 mm)
MOUNTING
SURFACE
CLOSURE
3/4" (19,1 mm)
1/4' (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
SERIES
TY-FRB
1-5/16" (33,3 mm)
13/16° (20,6 mm)
FIGURE 5
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
5/8±1/4"
(15,91-6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8' DIA.
(73,0 mm)
2-1/4' DIA.,
(57,2 mm)
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
MOUNTING
SURFACE
CLOSURE
SERIES
TY-FRB
1-1/4' (31,8 mm)
3/4"(19,1 mm)
FIGURE 7
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
Care and
Maintenance
The Series TY-FRB Sprinklers must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down the
affected fire protection system must be
obtained from the proper authorities
and all personnel who may be affected
by this action must be notified.
Absence of an escutcheon, which is
TFP171
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
CLOSURE
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
SERIES
TY-FRB
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-5/16" (33,3 mm)
1-1/16" (27,0 mm)
FIGURE 6
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
2.8 K-FACTOR, 1/2 INCH NPT
1/2±1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
SURFACE
CLOSURE
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
SERIES
TY-FRB
1-1/4" (31,8 mm)
1" (25,4 mm)
FIGURE 8
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
4.2 K-FACTOR, 1/2 INCH NPT
used to cover a clearance hole, may
delay the time to sprinkler operation in
a fire situation.
Sprinklers that are found to be leaking
or exhibiting visible signs of corrosion
must be replaced.
Automatic sprinklers must never be
painted, plated, coated or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
Frequent visual inspections are rec-
ommended to be initially performed for
corrosion resistant coated sprinklers,
after the installation has been com•
pleted, to verify the integrity of the cor-
rosion resistant coating. Thereafter,
annual inspections per NFPA 25
should suffice; however, instead of in-
specting from the floor level, a random
sampling of close-up visual inspec-
tions should be made, so as to better
determine the exact sprinkler condi-
TFP171
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4° DIA.
(57,2 mm)
MOUNTING
SURFACE
CLOSURE
II lir
Rir
lflf
1
SERIES
TY-FRB
3/4" (19,1 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1_
1-1/4" (31,8 mm)
3/4" (19,1 mm)
FIGURE 9
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 10 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
5/8±1/4"
(15,9±6,4 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4° DIA.
(57,2 mm)
MOUNTING
SURFACE
3/4" (19,1 mm)
1/4' (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
CLOSURE SERIES
TY-FRB
1-5/16" (33,3 mm)
13/16" (20,6 mm)
FIGURE 11
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 3/4 INCH TOTAL ADJUSTMENT
STYLE 40 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
tion and the long term integrity of the
corrosion resistant coating, as it may
be affected by the corrosive conditions
present.
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative to
any questions.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
Page 7 of 8
1/2t1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
MOUNTING
SURFACE
CLOSURE
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8°
(3,2 mm)
SERIES
TY-FRB
1-1/4" (31,8 mm)
1" (25,4 mm)
FIGURE 10
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 20 RECESSED ESCUTCHEON
5.6 K-FACTOR, 1/2 INCH NPT
1/2t1/8"
(12,7±3,2 mm)
FACE OF
SPRINKLER
FITTING
\
MOUNTING
SURFACE
2-7/8' DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
CLOSURE SERIES
TY-FRB
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1/8"
(3,2 mm)
1-5/16' (33,3 mm)
1-1/16" (27,0 mm)
FIGURE 12
SERIES TY-FRB RECESSED PENDENT
WITH TWO-PIECE 1/2 INCH TOTAL ADJUSTMENT
STYLE 30 RECESSED ESCUTCHEON
8.0 K-FACTOR, 3/4 INCH NPT
WRENCH RECESS
(END "A' USED FOR
1/2" NPT MODELS)
WRENCH RECESS
(END "B" USED FOR
3/4' NPT MODELS)
FIGURE 13
W-TYPE 6 SPRINKLER
WRENCH
ocal requirements and/or national
codes.
WRENCH
RECESS
f\f
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 14
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 8 of 8
P/N 57 - XXX - X - XXX
I I
MODEUSIN
330
2.8K UPRIGHT (1/2"NPT)
TY1131
331
2.8K PENDENT (1/2"NPT)
TY1231
340
4.2K UPRIGHT (1/2"NPT)
TY2131
341
4.2K PENDENT (1/2"NPT)
TY2231
370
5.6K UPRIGHT (1/2"NPT)
TY3131
371
5.6K PENDENT (1/2"NPT)
TY3231
390
8.0K UPRIGHT (3/4"NPT)
TY4131
391
8.0K PENDENT (3/4"NPT)
TY4231
SPRINKLER
1
NATURAL BRASS
4
WHITE POLYESTER
3
WHITE (RAL9010)*
9
CHROME PLATED
7
LEAD COATED
TFP171
TEMPERATURE
RATING
135
135F/57°C
155
155°F/68°C
175
175°F/79°C
200
200°F/93°C
286
286°F/141°C
* Eastem Hemisphere sales only..
TABLE C
PART NUMBER SELECTION
SERIES TY-FRB PENDENT AND UPRIGHT SPRINKLERS
Limited
Warranty
Products manufactured by Tyco Fire
Products are warranted solely to the
original Buyer for ten (10) years
against defects in material and work-
manship when paid for and properly
installed and maintained under normal
use and service. This warranty will ex-
pire ten (10) years from date of ship-
ment by Tyco Fire Products. No war-
ranty is given for products or
components manufactured by compa-
nies not affiliated by ownership with
Tyco Fire Products or for products and
components which have been subject
to misuse, improper installation, corro-
sion, or which have not been installed,
maintained, modified or repaired in ac-
cordance with applicable Standards of
the National Fire Protection Associa-
tion, and/or the standards of any other
Authorities Having Jurisdiction. Mate-
rials found by Tyco Fire Products to be
defective shall be either repaired or
replaced, at Tyco Fire Products' sole
option. Tyco Fire Products neither as-
sumes, nor authorizes any person to
assume for it, any other obligation in
connection with the sale of products or
parts of products. Tyco Fire Products
shall not be responsible for sprinkler
system design errors or inaccurate or
incomplete information supplied by
Buyer or Buyer's representatives.
IN NO EVENT SHALL TYCO FIRE
PRODUCTS BE LIABLE, IN CON-
TRACT, TORT, STRICT LIABILITY OR
UNDER ANY OTHER LEGAL THE-
ORY, FOR INCIDENTAL, INDIRECT,
SPECIAL OR CONSEQUENTIAL
DAMAGES, INCLUDING BUT NOT
LIMITED TO LABOR CHARGES, RE-
GARDLESS OF WHETHER TYCO
FIRE PRODUCTS WAS INFORMED
ABOUT THE POSSIBILITY OF SUCH
DAMAGES, AND IN NO EVENT
SHALL TYCO FIRE PRODUCTS' LI-
ABILITY EXCEED AN AMOUNT
EQUAL TO THE SALES PRICE.
THE FOREGOING WARRANTY IS
MADE IN LIEU OF ANY AND ALL
DRIER WARRANTIES EXPRESS OR
IMPLIED. INCLUDING WARRANTIES
OF MERCHANTABILITY AND FIT-
NESS. R. FOR A PARTICULAJR-
Ordering
Procedure
0tsatteakvon tecaI distributor for avail-
abtlimindicale the
fulrproduct
name. Refer to
the Price List for
complete listing
of Part Numbers.
Sprinkler Assemblies with NPT
Thread Connections:
Specify: (Specify Model/SIN), Quick
Response, (specify K-factor), (specify
temperature rating), Series TY-FRB
(specify Pendent or Upright) Sprinkler
with (specify type of finish or coating),
P/N (specify from Table C).
Recessed Escutcheon:
Specify: Style (specify) Recessed Es-
cutcheon with (specify finish), P/N
(specify).
1/2" (15 mm)
Style 10
Chrome Plated . , ..
While Coated .......
White RAL9010"
Brass Plated
P/N 56-701-9-010
P/N 56-701.4.010
P/N 56-701-3-010
P/N 56-701.2M010
1/2" (15 mm)
Style 20
Chrome Plated P/N 56-705-9-010
White Coated P/N 56-705-4-010
White RAL9010• P/N 56-705-3-010
Brass Plated P/N 56-705-2-010
3/4' (20 mm)
Style 30
Chrome Plated P/N 56-705-9-011
White Coated P/N 56-705-4-011
White RAL9010" P/N 56-705.3 011
Brass Plated P/N 56-705-2-011
3/4" (20 mm)
Style 40
Chrome Plated P/N 56-700-9-010
White Coated P/N 56-700-4-010
White RAL9010' P/N 56-700-3.010
Brass Plated P/N 56-700-2.010
" Eastern Hemisphere sales only.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
two IFire & Bui/ding
Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
la
rapid response
HOME FIRE SPRINKLER SYSTEM
Series LFII Residential
Pendent Sprinklers
4.9 K-factor
General
Description
The Series LFII (TY2234) Residential
Pendent Sprinklers are decorative,
fast response, frangible bulb sprin-
klers designed for use in residential
occupancies such as homes, apart-
ments, dormitories, and hotels. When
aesthetics and optimized flow charac-
teristics are the major consideration,
the Series LFII (TY2234) should be the
first choice.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 13D; wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFII (TY2234) has a 4.9
(70,6) K-factor that provides the re-
quired residential flow rates at reduced
pressures, enabling smaller pipe sizes
and water supply requirements.
The recessed version of the Series
LFII (TY2234) is intended for use in
areas with finished ceilings. It employs
a two-piece Style 20 Recessed Es-
cutcheon. The Recessed Escutcheon
provides 1/4 inch (6,4 mm) of recessed
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
adjustment or up to 1/2 inch (12,7 mm)
of total adjustment from the flush ceil-
ing position. The adjustment provided
by the Recessed Escutcheon reduces
the accuracy to which the pipe nipples
to the sprinklers must be cut.
The Series LFII (TY2234) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
WARNINGS
The Series LFII (TY2234) Residential
Pendent Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the National Fire Protection Asso-
ciation, in addition to the standards of
any other authorities having jurisdic-
tion. Failure to do so may impair the
performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler/Model
Identification
Number
SIN TY2234
Page 1 of 8
JANUARY, 2006 TFP400
Page 2 of 8
TFP400
Maximum
Coverage
Area (a)
Ft. x Ft.
(m x m)
Maximum
Spacing
Ft.
(m)
Minimum Flow (b) and
Residual Pressure
For Horizontal Ceiling
(Max. 2 Inch Rise
for 12 Inch Run)
Minimum Flow lb) and
Residual Pressure
For Sloped Ceiling
(Greater Than 2 Inch Rise
Up To Max. 4 Inch Rise for 12 Inch Run)
Minimum Flow (b) and
Residual Pressure
For Sloped Ceiling
(Greater Than 4 Inch Rise
Up To Max. 8 Inch Rise for 12 Inch Run)
155°F/68°C or
175°F/79°C
155°F/68°C
175°F/79°C
155F/68°C
175°F/79°C
12 x 12
(3,7 x 3,7)
12
(3,7)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
14 x 14
(4,3 x 4,3)
14
(4,3)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
16 x 16
(4,9 x 4,9)
16
(4,9)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
13 GPM (49,2 LPM)
7.0 psi (0,48 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
18 x 18
(5,5 x 5,5)
18
(5,5)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
17 GPM (64,3 LPM)
12.0 psi (0,83 bar)
20 x 20
(6,1 x 6,1)
20
(6,1)
20 GPM (75,7 LPM)
16.7 psi (1,15 bar)
20 GPM (75,7 LPM)
16.7 psi (1,15 bar)
20 GPM (75,7 LPM)
16.7 psi (1,15 bar)
21 GPM (79,5 LPM)
18.4 psi (1,27 bar)
22 GPM (83,3 LPM)
20.2 psi (1,39 bar)
(a) For coverage area dimensions less than o between those indicated, it is necessary to use the minimum required
highest coverage area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures
using the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
TABLE A
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA FOR THE SERIES LFII
RESIDENTIAL PENDENT AND RECESSED PENDENT SPRINKLERS
flow for the next
are calculated
(TY2234)
Technical
Data
Approvals:
UL and C-UL Listed. NYC Approved
under MEA 44-03-E.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
K = 4.9 GPM/psi1/2 (70,6 LPM/bar1/2)
Temperature Rating:
155FI68°C or 175°F/79°C
Finishes:
White Polyester Coated,
Chrome Plated, or Natural Brass
Physical Characteristics:
Frame Brass
Button Bronze
Sealing Assembly .
Beryllium Nickel w/Teflont
Bulb 3 mm dia. Glass
Compression Screw .....Bronze
Deflector Bronze
Ejection Spring ... . Stainless Steel
tDuPont Registered Trademark
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series LFII (TY2234) Residential
Pendent Sprinklers are UL and C-UL
Listed for installation in accordance
with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the local Authority having Juris-
diction.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A as a function of
temperature rating and the maximum
allowable coverage areas. The sprin-
kler flow rate is the minimum required
discharge from each of the total
number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
• The flow rates given in Table A for
NFPA 13D and 13R as a function of
temperature rating and the maxi-
mum allowable coverage area.
• A minimum discharge of 0.1 gpm/sq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity.
• For "Horizontal Ceilings" (maximum
2 inch rise for 12 inch run), the sprin-
klers are to be installed with a deflec-
tor to ceiling distance of 1-3/8 to 4
inches or in the recessed position
using only the Style 20 Recessed
Escutcheon as shown in Figure 2.
NOTES
The Beam Ceiling Design Criteria"
section starting on Page 4 permits de-
flector to ceiling distances up to 15-3/4
inches.
So as to help avoid obstructions to
water distribution, a maximum 12 inch
deflector -to -ceiling distance is permit-
ted forNFPA 13D and NFPA 13R appli-
cations where the sprinklers are located
in closets.
• For "Sloped Ceilings" (greater than
2 inch rise up to 8 inch rise for 12
inch run), the sprinklers are to be
installed with a deflector to ceiling
TFP400
Page 3 of 8
Components:
1 - Frame
2 - Button
3 - Sealing Assembly
4 - Bulb
5 - Compression
Screw
6 - Deflector *
* Temperature
rating is
indicated on
Deflector.
7/16" (11,1 mm) 1/2" ESCUTCHEON
NOMINAL NPT PLATE SEATING
MAKE -IN SURFACE
CROSS SECTION
PENDENT
2-1/4"
(57,2 mm)
1-5/8"
(41,3 mm)
2-7/8" DIA.
(73,0 mm)
STYLE 20
RECESSED
ESCUTCHEON
RECESSED PENDENT
FIGURE 1
SERIES LFII (TY2234) RESIDENTIAL
PENDENT AND RECESSED PENDENT SPRINKLERS
7/16±1/8"
(11,1±3,2 mm)
FACE OF
SPRINKLER
FITTING
MOUNTING
SURFACE
2-7/8" DIA.
(73,0 mm)
2-1/4" DIA.
(57,2 mm)
CLOSURE TY2234
1/2" (12,7 mm)
1/4" (6,4 mm)
MOUNTING
PLATE
1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON
FOR USE WITH THE SERIES LFII (TY2234)
RESIDENTIAL PENDENT SPRINKLER
distance of 1-3/8 to 4 inches or in
the recessed position using only the
Style 20 Recessed Escutcheon as
shown in Figure 2
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
length of the coverage area (Ref. Ta-
ble A) being hydraulically calculated
(e.g., maximum 12 feet for a 12 ft.. x
12 ft. coverage area, or 20 feet for a 20
ft. x 20 ft. coverage area).
WRENCH RECESS
(END "A" USED
FOR TY2234)
FIGURE 3
W-TYPE 6
SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
Page 4 of 8
Beam Ceiling
Design Criteria
The Series LFII (TY2234) Residential
Pendent Sprinklers are UL and C-UL
Listed for installation in residential oc-
cupancies with horizontal ceilings (Le.,
slopes up to a 2 inch rise over a 12 inch
run) with beams when installed in ac-
cordance with the following criteria:
General Information. The basic con-
cept of this protection scheme is to
locate the sprinklers on the underside
of the beams, Ref. Figure 5, (not in the
beam pockets); to identify the main
beams that principally run in one direc-
tion as "primary beams"; and, to iden-
tify the beams that run principally per-
pendicular to the main beams, as may
be present (or in some cases may be
necessary for proper sprinkler protec-
tion), as "secondary beams".
Primary and Secondary Beam
Types. Solid surface, solid or hollow
core, combustible or non-combustible.
Primary and Secondary Beam Posi-
tioning. Directly attached to the un-
derside of a combustible or non-com-
bustible smooth ceiling at any
elevation.
Primary Beam Cross -Section: Maxi-
mum depth of 14 inches and the maxi-
mum width is unlimited. The cross -
sectional shape of the primary beam
may be rectangular to circular.
Secondary Beam Cross -Section.
Maximum depth to be no greater than
the primary beam and the maximum
width is unlimited. The cross -sectional
shape of the secondary beam may be
rectangular to circular.
Primary Beam Spacing. The primary
beams (Fig. 6A) are to be 3 ft. - 4 in. to
6 ft. from the compartment wall to cen-
ter of the nearest beam and from cen-
ter to center between beams.
Secondary Beam Spacing. The sec-
ondary beams principally run perpen-
dicular to the primary beams.
Secondary beams of a depth equal to
the primary beam must be placed so
that the beam pockets created by the
primary beams do not exceed 20 feet
in length (Fig. 6B).
NOTE
When the beam pockets created by
the primary beams exceed 20 feet in
length, the installation will require the
use of secondary beams as described
above. Otherwise, secondary beams
need not be present.
Secondary beams of a cross -sectional
depth greater than one -quarter the
depth of the primary beams are to be
a minimum of 3 ft. - 4 in. from the
compartment wall to center of the
nearest beam and from center to cen-
ter between beams (Fig. 6C).
Secondary beams of a cross -sectional
depth no greater than one -quarter the
depth of the primary beams may be
placed at any compartment wall to
center of the nearest beam distance
and from any center to center distance
between beams (Fig. 6C).
Lintels. Lintels over doorways exiting
the compartment must be present. The
minimum height for the lintels is 8
inches or no less than the depth of the
Primary Beams, whichever is greater.
Sprinkler Types. Series LFII
(TY2234), 155F and 175F, Pendent
and Recessed Pendent Residential
Sprinklers.
Sprinkler Coverage Area and Hy-
draulic Design. The sprinkler cover-
age areas and hydraulic design criteria
as presented in the Table A for "Hori-
zontal Ceilings" are to be applied.
Sprinkler Position. The deflector to
bottom of primary beams for the Series
LFII (TY2234) Pendent Sprinklers or
Series LFII (TY2234) Recessed Pen-
dent Sprinklers is to be 1-1/4 to 1-3/4
inches (Fig. 5A). The vertical center-
line of the Series LFII (TY2234) Pen-
dent Sprinklers is to be no greater than
half the primary beam cross -sectional
width plus 2 inches from the centerline
of the primary beam (Fig 5B).
NOTES
Core drilling of beams to allow the in-
stallation of sprinkler drops requires
consulting with a structural engineer.
Where core drilling is not permitted,
the previously stated sprinkler position
criteria for the Series LFII (TY2234)
Pendent Sprinklers allows for the
sprinkler drop to be placed adjacent to
the primary beam.
Beam and Soffit Arrangements. A
soffit is permitted to be placed around
the perimeter of a compartment with
the beam arrangement within the sof-
fited area (Fig.7).
The cross-section of the soffit may be
any size as long as it does not create
an obstruction to water distribution per
the obstruction rules of NFPA 13 for
residential sprinklers.
When soffits are present, the pre-
viously provided 3 ft. - 4 in, to 6 ft.
"compartment wall to adjacent beam"
distance for the primary and secon-
dary beams is to be measured from the
face of the soffit as opposed to the
compartment wall.
TFP400
B
Eg
z
E E
m
MAXIMUM
ONE-HALF BEAM
WIDTH PLUS
2" (50,8 mm)
TY2234
TY2234
FIGURE 5
SPRINKLER POSITIONING
UNDER PRIMARY BEAMS
(Refer to the "Beam Ceiling
Design Criteria" section)
NOTE
Although the distance to the beams is
measured from the face of the soffit,
the sprinkler coverage area is to be
measured from the compartment wall.
*REFER TO
FIGURE 68 COMPARTMEN
FOR SPANS WALLS
EXCEEDING
20'-0" (6,1 m)
TFP400
Page 5 of 8
ALL FIGURES:
DISTANCES ARE
MEASURED TO
COMPARTMENT
WALL FACES AND
TO CENTERL
OF BEAMS
A AA
14" (356 mm)
MAXIMUM
INES
/SA
FPRIMARY
BEAM
COMPARTMENTWALLS wm=m)iNsm)mi
O
FIGURE 6A
PRIMARY BEAM SPANS UP TO 20'-0" (6,1 m)
R
A=3'-4"to6'-0"(1,0to1,8m)
PRIMARY BEAMS HAV-
ING A 14" (356 mm) MAXIMUM
DEPTH
20'-0" (6,1 m)
MAXIMUM
ATq�q--.1
SECONDARY
BEAM
PRIMARY
BEAM
COMPARTMENT
WALLS
FIGURE 6B
PRIMARY BEAM SPANS GREATER THAN 20'-0" (6,1 m)
A = 3'-4" to 6'-0" (1,0 to 1,8 m)
FOR PRIMARY BEAMS HAV-
INGA 14" (356 mm) MAXIMUM
DEPTH
B = 20'-0" (6,1 m) MAXIMUM
FOR SECONDARY BEAMS
THAT ARE TO BE EQUAL IN
DEPTH TO PRIMARY BEAMS
AND THAT MUST BE IN PLACE
SO THAT PRIMARY BEAM
POCKETS DO NOT EXCEED
20'-0" (6,1 m)
A A A--.1
T
SECONDARY -1_1_1111K
BEAM 114W—k\t\NI\Tilk
PRIMARY* —,
BEAM
FIGURE 6C
COMBINATIONS OF PRIMARY AND SECONDARY BEAMS
A = 3'-0" to 6'-0" (1,0 to 1,8 m)
FOR PRIMARY BEAMS HAV-
ING A 14" (356 mm) MAXIMUM
DEPTH
C = 3'-4" (1,0 m) MINIMUM FOR
SECONDARY BEAMS HAVING
DEPTHS GREATER THAN 25%
OF PRIMARY BEAMS
— or—
C = ANY DISTANCE FOR SEC
ONDARY BEAMS HAVING
DEPTHS UP TO 25% OF
PRIMARY BEAMS
FIGURE 6
BEAM ARRANGEMENTS
(Refer to the "Beam Ceiling Design Criteria" section)
Page 6 of 8
TFP400
SECONDARY
BEAM
PRIMARY
BEAM
FACE OF
SOFFIT
* USE DISTANCES SHOWN
IN FIGURES 6A, 6B 8 6C,
EXCEPT MEASUREMENTS
ARE TAKEN FROM FACES
OF SOFFITS INSTEAD OF
FROM COMPARTMENT
WALL SURFACES
COMPARTMENT
WALLS
FIGURE 7
BEAM AND SOFFIT ARRANGEMENTS
(Refer to the "Beam Ceiling Design Criteria" section)
Installation
The Series LFII (TY2234) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over -tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series LFII Pendent Sprinklers
must be installed in accordance with
the following instructions,
Step 1. Pendent sprinklers are to be
installed in the pendent position with
the deflector parallel to the ceiling.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref, Figure 3).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats,
The Series LFII Recessed Pendent
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step A. Recessed pendent sprinklers
are to be installed in the pendent posi-
tion with the deflector parallel to the
ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step D. After the ceiling has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 20 Closure
over the Series LFII Sprinkler and
push the Closure over the Mounting
Plate until its flange comes in contact
with the ceiling.
Care and
Maintenance
The Series LFII (TY2234) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
TFP400
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb. (Ref. Installation
Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
NOTE
The owner must assure that the sprin-
klers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non -
operation in the event of a fire or inad-
vertent operation may result.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties. ex-
press or implied. including warranties
of merchantability and fitness for a par-
ticular purpose.
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder..
Page 7 of 8
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability..
Sprinkler Assembly:
Series LFII (TY2234), K=4.9, Residen-
tial Pendent Sprinkler with (specify)
temperature rating and (specify) fin-
ish, P/N (specify).
155°F/68°C or
Chrome Plated P/N 51-201-9-155
155°F/68°C
White Polyester P/N 51-201-4-155
155°F/68°C
White
(RAL9010)* P/N 51-201-3-155
155°F/68°C
Natural Brass P/N 51-201-1-155
175°F/79°C or
Chrome Plated P/N 51-201-9-175
175°F/79°C
White Polyester P/N 51-201-4-175
175°F/79°C
White
(RAL9010)• P/N 51-201-3-175
175°F/79°C
Natural Brass P/N 51-201-1-175
`Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (spec-
ify').
*Refer to Technical Data Sheet TFP770.
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
Page 8 of 8
TFP400
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
tqcci I Fire &Building
Products
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
ist
rapid response
HOME FIRE SPRINKLER SYSTEM
Series LFII Residential
Horizontal Sidewall Sprinklers
4.2 K-factor
General
Description
The Series LFII (TY1334) Residential
Horizontal Sidewall Sprinklers are
decorative, fast response, frangible
bulb sprinklers designed for use in
residential occupancies such as
homes, apartments, dormitories, and
hotels. When aesthetics and optimized
flow characteristics are the major con-
sideration, the Series LFII (TY1334)
should be the first choice.
The Series LFII are to be used in wet
pipe residential sprinkler systems for
one- and two-family dwellings and mo-
bile homes per NFPA 13D; wet pipe
residential sprinkler systems for resi-
dential occupancies up to and includ-
ing four stories in height per NFPA
13R; or, wet pipe sprinkler systems for
the residential portions of any occu-
pancy per NFPA 13.
The Series LFII (TY1334) has a 4.2
(60,5) K-factor that provides the re-
quired residential flow rates at reduced
pressures, enabling smaller pipe sizes
and water supply requirements.
The recessed version of the Series
LFII (TY1334) is intended for use in
areas with finished walls. It employs a
two-piece Style 20 Recessed Escutch-
eon. The Recessed Escutcheon pro-
vides 1/4 inch (6,4 mm) of recessed
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
adjustment or up to 1/2 inch (12,7 mm)
of total adjustment from the flush
mounting surface position. The adjust-
ment provided by the Recessed Es-
cutcheon reduces the accuracy to
which the pipe nipples to the sprinklers
must be cut.
The Series LFII (TY1334) has been
designed with heat sensitivity and
water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
WARNINGS
The Series LFII (TY1334) Residential
Horizontal Sidewall Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner Is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler/Model
Identification
Number
SIN TY1334
oh
11111111
Page 1 of 8
JANUARY, 2006 TFP410
Page 2 of 8
TFP41O
Components:
1 - Frame
2 - Button Assembly
3 - Sealing Assembly
4 - Bulb
5 - Compression Screw
6 - Deflector* TOP -OF -
DEFLECTOR
* Temperature rating
is indicated on top
of Deflector.
7/ 6"
(11,1 mm)
END -OF -
DEFLECTOR
BOSS
*
APWRIi
1..:C841113.11111111111111
1 11IIIIIIIIIIIM
1-5/8"
7/16" (11,1 mm)
NOMINAL
MAKE -IN
CENTERLINE
OF WATERWAY
1/2" NPT
(41,3 mm) ESCUTCHEON
2-1/4" PLATE SEATING
(57,2 mm) SURFACE
WRENCH
FLATS
STYLE 20
RECESSED
ESCUTCHEON
RECESSED
FIGURE 1
SERIES LFII (TY1334) RESIDENTIAL
HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
2-7/8" DIA.
(73,0 mm)
MOUNTING
SURFACE
TOP -OF- CLOSURE
DEFLECTOR
\
MOUNTING
PLATE
END -OF -
DEFLECTOR
BOSS
1-3/8" (34,9 mm)
1-1/8" (28,6 mm)
7/16t1/8"
(11,1±3,2 mm)
FACE OF
SPRINKLER
FITTING
2.7/8 DIA.
(73,0 mm)
2-1/4 DIA.
(57,2 mm)
1/8"
(3,2 mm)
1/2" (12,7 mm)
1/4" (6,4 mm)
FIGURE 2
STYLE 20 RECESSED ESCUTCHEON
FOR USE WITH THE SERIES LFII (TY1334)
RESIDENTIAL HORIZONTAL SIDEWALL SPRINKLER
WRENCH RECESS
(END "A" USED
FOR TY1334)
FIGURE 3
W-TYPE 6 SPRINKLER WRENCH
WRENCH
RECESS
PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
WITH SPRINKLER
WRENCHING AREA
FIGURE 4
W-TYPE 7 RECESSED
SPRINKLER WRENCH
TFP41O Page 3 of 8
Technical
Data
Approvals:
UL and C-UL Listed. NYC Approved
under MEA 44-03-E.
Maximum Working Pressure:
175 psi (12,1 bar)
Discharge Coefficient:
K = 4.2 GPM/psi1/2 (60,5 LPM/bars/2)
Temperature Rating:
155°F/68°C or 175°F/79°C
Finishes:
White Polyester Coated,
Chrome Plated, or Natural Brass
Physical Characteristics:
Frame Brass
Button Bronze
Sealing Assembly
Beryllium Nickel w/Teflont
Bulb 3 mm dia. Glass
Compression Screw Bronze
Deflector ... Copper
tDupont Registered Trademark
Operation
The glass Bulb contains a fluid that
expands when exposed to heat. When
the rated temperature is reached, the
fluid expands sufficiently to shatter the
glass Bulb allowing the sprinkler to
activate and flow water.
Design
Criteria
The Series LFII (TY1334) Residential
Horizontal Sidewall Sprinklers are UL
and C-UL Listed for installation in ac-
cordance with the following criteria.
NOTE
When conditions exist that are outside
the scope of the provided criteria, refer
to the Residential Sprinkler Design
Guide TFP490 for the manufacturer's
recommendations that may be accept-
able to the local Authority Having Ju-
risdiction.
System Type. Only wet pipe systems
may be utilized.
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
designed to NFPA 13D or NFPA 13R
are given in Table A, B, C, and D as a
function of temperature rating and the
maximum allowable coverage areas.
The sprinkler flow rate is the minimum
required discharge from each of the
total number of "design sprinklers" as
specified in NFPA 13D or NFPA 13R.
For systems designed to NFPA 13, the
number of design sprinklers is to be
the four most hydraulically demanding
sprinklers. The minimum required dis-
charge from each of the four sprinklers
is to be the greater of the following:
• The flow rates given in Tables A, B,
C, and D for NFPA 13D and 13R as
a function of temperature rating and
the maximum allowable coverage
area.
• A minimum discharge of 0.1 gpm/sq.
ft. over the "design area" comprised
of the four most hydraulically de-
manding sprinklers for the actual
coverage areas being protected by
the four sprinklers.
Obstruction To Water Distribution.
Locations of sprinklers are to be in
accordance with the obstruction rules
of NFPA 13 for residential sprinklers.
Operational Sensitivity. The sprin-
klers are to be installed with an end -of -
deflector -boss to wall distance of 1-
3/8 to 6 inches or in the recessed po-
sition using only the Style 20 Re-
cessed Escutcheon as shown in
Figure 2.
In addition the top -of -deflector -to -ceil-
ing distance is to be within the range
(Ref. Table A, B, C, or D) being hy-
draulically calculated.
Sprinkler Spacing. The minimum
spacing between sprinklers is 8 feet
(2,4 m). The maximum spacing be-
tween sprinklers cannot exceed the
width of the coverage area (Ref. Table
A) being hydraulically calculated (e.g.,
maximum 12 feet for a 12 ft. x 12 ft.
coverage area, or 16 feet for a 16 ft. x
20 ft. coverage area).
Installation
The Series LFII (TY1334) must be in-
stalled in accordance with the follow-
ing instructions:
NOTES
Do not install any bulb type sprinkler if
the bulb is cracked or there is a loss of
liquid from the bulb. With the sprinkler
held horizontally, a small air bubble
should be present. The diameter of the
air bubble is approximately 1/16 inch
(1,6 mm).
A leak tight 1/2 inch NPT sprinkler joint
should be obtained with a torque of 7
to 14 ft.lbs. (9,5 to 19,0 Nm). A maxi-
mum of 21 ft.lbs. (28,5 Nm) of torque
is to be used to install sprinklers.
Higher levels of torque may distort the
sprinkler inlet with consequent leak-
age or impairment of the sprinkler.
Do not attempt to compensate for in-
sufficient adjustment in an Escutcheon
Plate by under- or over -tightening the
Sprinkler. Readjust the position of the
sprinkler fitting to suit.
The Series LFII Horizontal Sidewall
Sprinklers must be installed in ac-
cordance with the following instruc-
tions.
Step 1. Horizontal sidewall sprinklers
are to be installed in the horizontal
position with their centerline of water-
way perpendicular to the back wall and
parallel to the ceiling. The word "TOP"
on the Deflector is to face towards the
ceiling with the front edge of the De-
flector parallel to the ceiling.
Step 2. With pipe thread sealant ap-
plied to the pipe threads, hand tighten
the sprinkler into the sprinkler fitting.
Step 3. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
6 Sprinkler Wrench (Ref. Figure 3).
With reference to Figure 1, the W-Type
6 Sprinkler Wrench is to be applied to
the wrench flats.
The Series LFII Recessed Horizontal
Sidewall Sprinklers must be installed
in accordance with the following in-
structions.
Step A. Recessed horizontal sidewall
sprinklers are to be installed in the
horizontal position with their centerline
of waterway perpendicular to the back
wall and parallel to the ceiling. The
word "TOP" on the Deflector is to face
towards the ceiling.
Step B. After installing the Style 20
Mounting Plate over the sprinkler
threads and with pipe thread sealant
applied to the pipe threads, hand
tighten the sprinkler into the sprinkler
fitting.
Step C. Tighten the sprinkler into the
sprinkler fitting using only the W-Type
7 Recessed Sprinkler Wrench (Ref.
Figure 4). With reference to Figure 1,
the W-Type 7 Recessed Sprinkler
Wrench is to be applied to the sprinkler
wrench flats.
Step C. After the wall has been in-
stalled or the finish coat has been ap-
plied, slide on the Style 20 Closure
over the Series LFII Sprinkler and
push the Closure over the Mounting
Plate until its flange comes in contact
with the wall.
(Continued on Page 8)
Page 4 of 8
TFP41O
ELEVATION
Maximum
Coverage
Area (a)
Width x Length (b)
Ft. x Ft.
(m x m)
12 x 12
Maximum
Spacing
Ft.
(m)
Minimum Flow (c) and Residual Pressure
Top -Of -Deflector- To- Ceiling:
4 to 6 Inches (100 to 150 mm)
Top -Of -Deflector- To- Ceiling:
6 to 12 Inches (150 to 300 mm)
155F/68°C
175°F/79°C
155°F/68°C
175F/79°C
(3,7 x 3,7)
14 x 14
(4,3 x 4,3)
16 x 16
(4,9 x 4,9)
16 x 18
(4,9 x 5,5)
16x20
(4,9 x 6,1)
12
(3,7)
14
(4,3)
16
(4,9)
16
(4,9)
16
(4,9)
12 GPM (45,4 LPM)
8.2 psi (0,57 bar)
14 GPM (53,0 LPM)
11.1 psi (0,77 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
19 GPM (71,9 LPM)
20.5 psi (1,41 bar)
23 GPM (87,1 LPM)
30.0 psi (2,07 bar)
12 GPM (45,4 LPM)
8.2 psi (0,57 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
19 GPM (71,9 LPM)
20.5 psi (1,41 bar)
23 GPM (87,1 LPM)
30.0 psi (2,07 bar)
13 GPM (49,2 LPM)
9.6 psi (0,66 bar)
17 GPM (64,3 LPM)
16.4 psi (1,13 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
21 GPM (79,5 LPM)
25.0 psi (1,72 bar)
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
13 GPM (49,2 LPM)
9.6 psi (0,66 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
21 GPM (79,5 LPM)
25.0 psi (1,72 bar)
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
(a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
(b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler).
(c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.
(d) Sidewall sprinklers, where installed under a ceiling with a slope greater than 0 inch rise for a 12 inch run to a slope up to 2 inch
rise for 12 inch run, must be located per one of the following:
• Locate the sprinklers at the high point of the slope and positioned to discharge down the slope.
• Locate the sprinklers along the slope and positioned to discharge across the slope.
TABLE A
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR SERIES RESIDENTIAL HORIZONTAL SIDEWALLHE AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
FOR HORIZONTAL CEILING (Maximum 2 Inch Rise for 12 Inch Run)
TFP41O
Page 5 of 8
12"
8" MAXIMUM
ELEVATION
Maximum
Coverage
Area la)
Width x Length lb)
Ft. x Ft.
(m x m)
Maximum
Spacing
Ft.
(m)
Minimum Flow (o) and Residual Pressure
(I) Two sprinkler design with the sprinklers at the high point of the slope and positioned
to discharge down the slope.
Top -Of -Deflector- To- Ceiling:
4 to 6 Inches (100 to 150 mm)
Top -Of -Deflector- To- Ceiling:
6 to 12 Inches (150 to 300 mm)
155°F/68°C
175°F/79°C
155°F/68°C
175°F/79°C
12 x 12
(3,7 x 3,7)
12
(3,7)
1
12 GPM (45,4 LPM)
8.2 psi(0,57 bar)
1
12 GPM (45,4 LPM)
8.2 psi (0,57 bar)
1
13 GPM (49,2 LPM)
9.6 psi (0,66 bar)
1
13 GPM (49,2 LPM)
9.6 psi (0,66 bar)
14 x 14
(4,3 x 4,3)
14
(4,3)
1
14 GPM (53,0 LPM)
11.1 psi (0,77 bar)
1
14 GPM (53,0 LPM)
11.1 psi (0,77 bar)
1
17 GPM (64.3 LPM)
16.4 psi (1,13 bar)
1
17 GPM (64.3 LPM)
16.4 psi (1,13 bar)
16 x 16
(4,9 x 4,9)
16
(4,9)
1
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
I
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
1
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
I
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
16 x 18
(4,9 x 5,5)
16
(4,9)
1
19 GPM (71,9 LPM)
20.5 psi (1,41 bar)
1
19 GPM (71,9 LPM)
20.5 psi (1,41 bar)
1
21 GPM (79,5 LPM)
25.0 psi (1,72 bar)
1
21 GPM (79,5 LPM)
25.0 psi (1,72 bar)
16 x 20
(4,9 x 6,1)
16
(4,9)
I
24 GPM (90,8 LPM)
32.7 psi (2,25 bar)
I
24 GPM (90,8 LPM)
32.7 psi (2,25 bar)
I
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
1
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
(a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
(b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler).
(c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details,
TABLE B
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY1334)
RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
FOR SPRINKLERS AT THE HIGH POINT OF THE SLOPE AND DISCHARGING DOWN THE SLOPE
(Greater Than 2 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run)
Page 6 of 8
TFP41O
ELEVATION
Maximum
Coverage
Area (a)
Width x Length (b)
Ft. x Ft.
(m x m)
12 x 12
Maximum
Spacing
Ft.
(m)
Minimum Flow Ic) and Residual Pressure
(II) Two sprinkler design with the sprinklers located along the slope and positioned to
discharge across the slope.
(111) Three sprinkler design when there are more than two sprinklers in a compartment and
with the sprinklers located along the siope.and positioned to discharge across the slope.
Top -Of -Deflector- To- Ceiling:
4 to 6 Inches (100 to 150 mm)
Top -Of -Deflector- To- Ceiling:
6 to 12 Inches (150 to 300 mm)
155°F/68°C
175°F/79°C
155°F/68°C
175°F/79°C
(3,7 x 3,7)
14 x 14
(4,3 x 4,3)
16 x 16
(4,9 x 4,9)
16 x 18
(4,9 x 5,5)
16 x 20
(4,9 x 6,1)
12
(3,7)
14
(4,3)
16
(4,9)
16
(4,9)
16
(4,9)
11
11
11
11
111
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
22 GPM (83,3 LPM)
27.4 psi (1,89 bar)
23 GPM (87,1 LPM)
30.0 psi (2,07 bar)
11
11
11
11
111
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
22 GPM (83,3 LPM)
27.4 psi (1,89 bar)
23 GPM (87,1 LPM)
30.0 psi (2,07 bar)
11
11
11
11
111
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
22 GPM (83,3 LPM)
27.4 psi (1,89 bar)
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
11
11
11
11
111
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
18 GPM (68,1 LPM)
18.4 psi (1,27 bar)
22 GPM (83,3 LPM)
27.4 psi (1,89 bar)
26 GPM (98,4 LPM)
38.3 psi (2,64 bar)
(a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
(b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler).
(c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details..
TABLE C
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY1334)
RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE
(Greater Than 2 Inch Rise for 12 Inch Run Up To 4 Inch Rise for 12 Inch Run)
TFP41O
Page 7 of 8
ELEVATION
Maximum
Coverage
Area fa)
Width x Length (b)
Ft. x Ft.
(m x m)
Maximum
Spacing
Ft.
(m)
Minimum Flow lc) and Residual Pressure
(Ill) Three sprinkler design when there are more than two sprinklers In a compartment and
with the sprinklers located along the siope.and positioned to discharge across the slope.
Top -Of -Deflector- To- Ceiling:
4 to 6 Inches (100 to 150 mm)
155°F/68°C
175°F/79°C
12 x 12
(3,7 x 3,7)
12
(3,7)
11I
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
III
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
14 x 14
(4,3 x 4,3)
14
(4,3)
I11
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
11I
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 x 16
(4,9 x 4,9)
16
(4,9)
III
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
III
16 GPM (60,6 LPM)
14.5 psi (1,00 bar)
16 x 18
(4,9 x 5,5)
16
(4,9)
N/A
N/A
16 x 20
(4,9 x 6,1)
16
(4,9)
N/A
N/A
(a) For coverage area dimensions Tess than or between those indicated, it is necessary to use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
(b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler).
(c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details..
TABLE D
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS
FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE
(Greater Than 4 Inch Rise for 12 Inch Run Up To 8 Inch Rise for 12 Inch Run)
Page 8 of 8
Care and
Maintenance
The Series LFII (TY1334) must be
maintained and serviced in accord-
ance with the following instructions:
NOTES
Absence of an Escutcheon Plate may
delay the sprinkler operation in a fire
situation.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system
which it controls, permission to shut
down the affected fire protection sys-
tem must be obtained from the proper
authorities and all personnel who may
be affected by this action must be no-
tified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
Automatic sprinklers must never be
painted, plated, coated, or otherwise
altered after leaving the factory. Modi-
fied sprinklers must be replaced.
Sprinklers that have been exposed to
corrosive products of combustion, but
have not operated, should be replaced
if they cannot be completely cleaned
by wiping the sprinkler with a cloth or
by brushing it with a soft bristle brush.
Care must be exercised to avoid dam-
age to the sprinklers - before, during,
and after installation. Sprinklers dam-
aged by dropping, striking, wrench
twist/slippage, or the like, must be re-
placed. Also, replace any sprinkler that
has a cracked bulb or that has lost
liquid from its bulb, (Ref. Installation
Section).
The owner is responsible for the in-
spection, testing, and maintenance of
their fire protection system and de-
vices in compliance with this docu-
ment, as well as with the applicable
standards of the National Fire Protec-
tion Association (e.g., NFPA 25), in
addition to the standards of any other
authorities having jurisdiction. The in-
stalling contractor or sprinkler manu-
facturer should be contacted relative
to any questions.
NOTE
The owner must assure that the sprin-
klers are not used for hanging of any
objects and that the sprinklers are only
cleaned by means of gently dusting
with a feather duster; otherwise, non -
operation in the event of a fire or inad-
vertent operation may result.
It is recommended that automatic
sprinkler systems be inspected,
tested, and maintained by a qualified
Inspection Service in accordance with
local requirements and/or national
codes.
Limited
Warranty
Products manufactured by Tyco Fire &
Building Products (TFBP) are war-
ranted solely to the original Buyer for
ten (10) years against defects in mate-
rial and workmanship when paid for
and properly installed and maintained
under normal use and service. This
warranty will expire ten (10) years
from date of shipment by TFBP. No
warranty is given for products or com-
ponents manufactured by companies
not affiliated by ownership with TFBP
or for products and components which
have been subject to misuse, improper
installation, corrosion, or which have
not been installed, maintained, modi-
fied or repaired in accordance with ap-
plicable Standards of the National Fire
Protection Association, and/or the
standards of any other Authorities
Having Jurisdiction. Materials found
by TFBP to be defective shall be either
repaired or replaced, at TFBP's sole
option. TFBP neither assumes, nor
authorizes any person to assume for it,
any other obligation in connection with
the sale of products or parts of prod-
ucts. TFBP shall not be responsible for
sprinkler system design errors or inac-
curate or incomplete information sup-
plied by Buyer or Buyer's repre-
sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam-
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP's liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties. ex-
press or implied. including warranties
of merchantability and fitness for a par-
ticular purpose
This limited warranty sets forth the ex-
clusive remedy for claims based on
failure of or defect in products, materi-
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex-
tent permitted by law. The invalidity, in
whole or part, of any portion of this
warranty will not affect the remainder.
TFP41O
Ordering
Procedure
When placing an order, indicate the
full product name. Contact your local
distributor for availability..
Sprinkler Assembly:
Series LFII (TY1334), K=4.2, Residen-
tial Horizontal Sidewall Sprinkler with
(specify) temperature rating and
(specify) finish, P/N (specify).
155°F/68°C or
Chrome Plated P/N 51-211-9-155
155°F/68°C
White Polyester P/N 51-211-4-155
155°F/68°C
White
(RAL9010)* P/N 51-211-3-155
155°F/68°C
Natural Brass P/N 51-211-1-155
175°F/79°C or
Chrome Plated P/N 51-211-9-175
175°F/79°C
White Polyester P/N 51-211-4-175
175°F/79°C
White
(RAL9010)* P/N 51-211-3-175
175°F/79°C
Natural Brass P/N 51-211-1-175
*Eastern Hemisphere sales only.
Recessed Escutcheon:
Specify: Style 20 Recessed Escutch-
eon with (specify*) finish, P/N (spec-
ify*).
*Refer to Technical Data Sheet TFP770
Sprinkler Wrench:
Specify: W-Type 6 Sprinkler Wrench,
P/N 56-000-6-387.
Specify: W-Type 7 Sprinkler Wrench,
P/N 56-850-4-001.
TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446
WIL KINS
a ZURN company
FEATURES
Sizes: ❑ 3/4" ❑ 1" 0 1 %4" ❑ 1'/" 0 2"
Maximum working water pressure
Maximum working water temperature
Hydrostatic test pressure
End connections Threaded
OPTIONS
(Suffixes can be combined)
❑ - with full port QT ball valves (standard)
❑ L - less ball valves
❑ U - with union ball valves
O MS - with integral relief valve monitor switch
❑ P - for reclaimed water systems
❑ S - with bronze "Y" type strainer
❑ BMS - with battery operated monitor switch
❑ FDC - with fire hydrant connection; 2" only
❑ TCU - with test cocks up
O V - with union swivel elbows
❑ SE - with street elbows
❑ FT - with integral male 45° flare SAE test fitting
175 PSI
180°F
350 PSI
ANSI B1.20.1
ACCESSORIES
Cl Air gap (ModelAG)
O Repair kit (rubber only)
O Thermal expansion tank (Model WXTP)
O Soft seated check valve (Model 40)
O Shock arrester (Model 1250)
❑ QT-SET Quick Test Fitting Set
O Ball valve handle locks
❑ Test Cock Lock (Model TCL24)
DIMENSIONS & WEIGHTS (do not include pkg.)
r
M «11» del 975XL
Reduced Pressure Principle Assembly
0
s
11
111
BP
-t 1:7 ..T
APPLICATION
Designed for installation on potable water lines to protect
against both backsiphonage and backpressure of contami-
nated water into the potable water supply. Assembly shall
provide protection where a potential health hazard exists.
STANDARDS COMPLIANCE
• ASSE® Listed 1013
• IAPMO® Listed
• UL® Classified (less shut-off valves orwith OS&Yvalves)
• C-UL® Classified
• CSA® Certified
• AVINVA Compliant C511
• Approved by the Foundation for Cross Connection
Control and Hydraulic Research at the University of
Southem California
MATERIALS
Main valve body
Access covers
Fasteners
Elastomers
Polymers
Springs
Cast Bronze ASTM B 584
Cast Bronze ASTM B 584
Stainless Steel, 300 Series
Silicone (FDAApproved)
Buna Nitrite (FDAApproved)
Noryi , NSF Listed
Stainless steel, 300 series
Relief Valve discharge port
3/4" - 1" - 0.63 sq.
11/4"-2" - 1.19sq. in.
MODEL
SIZE
in. mm
3/4
1
1 1/4
1 1/2
2
20
25
32
40
50
A
in.
12
13
17
17 3/8
18 1/2
Page 1 of 2
mm
305
330
432
441
470
A UNION
BALL
VALVES
in mm
14
14 1/4
19
20
21 1/4
356
362
483
508
540
DIMENSIONS approximate)
B LESS BALL
VALVES
in.
7 3/4
7 3/4
10 15/16
10 15/16
10 15/16
mm
197
197
278
278
278
in. mm
2 1/8
2 1/8
2 3/4
2 3/4
2 3/4
54
54
70
70
70
in. mm
3
3
3 1/2
3 1/2
3 1/2
76
76
89
89
89
in.
3 1/2
3 1/2
5
5
5
WEIGHT
mm
F
in.
mm
in.
G
LESS
VALVES
BALL
WITH
VALVES
BALL
89
5
127
15 3/4
mm
400
lbs.
kg
lbs.
kg
89
5
127
17 3/4
451
10
4.5
12
5.5
127
6 3/4
171
22
559
10
22
4.5
10
14
28
6.4
12.7
127
6 3/4
171
23 1/8
587
127
6 3/4
171
25 1/2
648
22
22
10
28
12.7
10
34
15.4
DOCUMENT St:
BF-975XL lc
REVISION:
1/06
GU
15
10
50
3/4" (20mm)
1" (25mm)
r
20 MI An a,
FLOW CHARACTERISTICS
MODEL 975XL 3/4", 1", 1 1/4", 1 1/2" & 2" (STANDARD & METRIC)
FLOW RATES (Us)
1.26 2.52 3.8 5.0
20
15
10
3.2
6.3
9.5
12.6 15.8
137
1 1 4" (32mm)
1 h"
(40mm
2" (50mm)
5 50
FLOW RATES (GPM)
O Rated Flow (Established by approval agencies)
100
150
200
35
250
TYPICAL INSTALLATION
Local codes shall govern installation re-
quirements. To be installed in accor-
dance with the manufacturers' instruc-
tions and the latest edition of the Uni-
form Plumbing Code. Unless otherwise
specified, the assembly shall be mounted
at a minimum of 12" (305mm) and a
maximum of 30" (762mm) above ad-
equate drains with sufficient side clear-
ance for testing and maintenance. The
installation shall be made so that no part
of the unit can be submerged.
1 i►�r, ►r:■
CENTRAL
STATION
ALARM
PANEL
BATTERY
MONITOR
SWITCH
AIR GAP
FITTING
DIRECTION OF FLOW
INDOOR INSTALLATION
(Shown w/optional BMS)
Capacity thru
Schedule 40 Pipe
P ip a size
5 ft/sec
7 .5
ft/sec
10 ft/sec
1 5
ft/s e c
1 /8"
1
1
2
3
1 /4"
2
2
3
5
3/8"
3
4
6
9
1/2"
5
7
9
14
3/4"
8
12
17
25
1"
13
20
27
40
1 1/4"
23
35
47
70
1 1/2"
32
48
63
95
2"
52
78
105
167
OPT ONAL
WATER METER
PROTECTIVE
ENCLOSURE
DIRECTION OF FLOW
INLET SHUT-OFF
OUTDOOR INSTALLATION
SPECIFICATIONS
The Reduced Pressure Principle Backflow Preventer shall be ASSE® Listed 1013, rated to 180°F and supplied with
full port ball valves. The main body and access covers shall be bronze (ASTM B 584), the seat ring and all internal
polymers shall be NSF® Listed NorylIm and the seat disc elastomers shall be silicone. The first and second checks
shall be accessible for maintenance without removing the relief valve or the entire device from the line. If installed
indoors, the installation shall be supplied with an air gap adapter and integral monitor switch. The Reduced Pressure
Principle Backflow Preventer shall be a WILKINS Model 975XL.
Page 2 of 2
WILKINS a Zum company, 1747 Commerce Way, Paso Robles, CA 93446 Phone:805/238-7100 Fax 805/238-5766
IN CANADA: ZURN INDUSTRIES LIMITED, 3544 Nashua Dr., Mississauga, Ontario L4V 1L2 Phone:905/405-8272 Fax 905/405-1292
Product Support Help Line: 1-877-BACKFLOW (1-877-222-5356) • Webslte: http•//www.zurn.com
TOLCO
(,+NIBCO
WWW,toIco,com
Revision 3/31/2003
Fig. 22 - Hanger for CPVC Plastic Pipe
Single Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre -Galvanized
Function — Intended to perform as a hanger to support only CPVC piping
used in automatic fire sprinkler systems. The product acts as a hanger when
tab is upward and the fastener screw is in the horizontal position. Figure 22
can be installed on the top of a beam, but in this situation acts as a guide to
the piping which is supported by the beam itself. It is not intended to support
CPVC pipe from under a flat horizontal surface, such as a ceiling. For this
type of installation, use the TOLCOTM Fig. 23, Double Fastener Strap for
CPVC Piping. Fig. 22, when inverted, with the hanger tab downward, can
function as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL) and Canada
(cUL) to support fire sprinkler piping. Meets and exceeds the requirements of
NFPA 13, 13R and 13D.
Features — Fig. 22 incorporates features which protect the pipe and ease installation. The flared edge design* pro-
tects CPVC pipe from any rough surface. It is easily attached to the building structure using the special UL Listed hex
head self threading screw furnished with the product, this is the minimum size fastener acceptable. It is recommended
that rechargeable electric drills fitted with a hex socket attachment to be used as installation tools. No impact tools
(such as a hammer) or impact fasteners (such as drive screws or nails) are allowed. Damage has been know to result
from installations using impact type tools. No pre -drilling of a pilot hole in wood is required.
Finish — Pre -Galvanized
Note — Fastener into light gauge metal may be ordered separately. Minimum acceptable: #10 x 1" Hardened Self
Threading Screw with 5/16" hex washer head.
Order By — Figure number and CPVC pipe size.
* Patent Pending
@c®
CPVC
Max. Hanger Fastener Hex Ap
Dimensions • Weights
Pipe Size AB C ,__ ___.
Spacing (Ft.) Head Size Wt./1o0
3/�4 23/4e 1e/,e 13/,6 5'/z 5/16
2"/,e 1'/,a 13/,e 9
' 6 5/169
1 /< 3'/,e 15/a 13/,e 6,/2
1 /z
2 3a/,e 5/16 11
1 /4 13/4e 7 5/16 12
33/4 2'/e 13/1e 8 5/16 15
38
Office/Manufacturing Facility • 1375 Sampson Ave • Corona. CA 92879 • Plir 95 5;,
Customer Service • 800 786 5266
wwwtolco.eom
TOLCO
i>ntim rI NIBCO
www.tolco,com
Revision 5/24/2001
Fig. 22C - Combination
Hanger & Restrainer Application
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre -Galvanized
Function — Designed to support a CPVC pipe away
from the corner of a beam. This position allows for easy
installation of drops or risers without adding additional
wood blocks.
Approvals — Underwriters' Laboratories Listed in the USA
(UL) and Canada (cUL) for use as a combination hanger and
restrainer.
Finish — Pre -Galvanized
Note — Approved UL Listed fastener into wood is furnished
with the product. A fastener into light gauge metal may be
ordered separately. Minimum acceptable #10 x 1" hardened
self threading screw with 5/16" hex washer head.
Order By — Fig. 22C application is composed of two
standard Fig. 22 models — order two singles for each hanger
and restrainer application required.
TRUSS HEADER
OR
TRUSS JOIST
(TYP)
5195
Office/Manufacturing Facility • 1375 Sampson Ave • Corona. CA 92879 • Ph: 951.737.5599 • fax: 951.737 0330
Customer Service • 800.786.5266
www.toleo.com
TOLCO
NIBCO
WWW,tolco.com
Revision 5/24/2001
Fig. 23 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre -Galvanized
Function — Intended to perform as a hanger/restrainer to support
only CPVC piping used in automatic fire sprinkler systems. Can be
installed on the top or on the bottom of a beam. The Fig. 23 can also
be installed on the side of a beam. The Fig. 23 can also function as
a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds
the requirements of NFPA 13, 13R and 13D.
Features — Fig. 23 incorporates features which protect the pipe and
ease installation. The flared edge design` protects the CPVC pipe
from any rough surface. It also incorporates snap restrainers allow-
ing easier and faster installation. Easily attaches to the building
structure using the two UL Listed hex head self threading screws**
furnished with the product. It is recommended that rechargeable
electric drills fitted with a hex socket attachment be used as installa-
tion tools. No impact tools (such as a hammer) or impact fasteners
(such as drive screws or nails) are allowed. Damage has been
known to result from installations using impact type tools.
No pre -drilling of a pilot hole in wood is required.
Finish — Pre -Galvanized
Order By — Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
Dimensions • Weights
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4
3 /e 19/+e 13/+e 51/2 5/16 9
1 Y, 3% 1 �/+a 13/1e 6 5/16
2 /az 1'/+e 6+/2 5/16 11
2 4'/8 27/+e 13/+e 8 5/16 15
8 5/16 15
CPVC
Max. Hanger Fastener Hex Approx.
Office/Manufacturing Facility • 1375 Sampson Ave • Corona. CA 92879 • Ph
Customer Service • 800, 786 5266
www.tolco.com
Dimensions • Weights
Pipe Size A B C Spacing (Ft.) Head Size Wt./100
3/4 25/ie 15/32 13/,e 572 5/16 9
1 25/e 15/,e 13/,5 6 5/16 9
1'/, 3 11/2 13/,e 6'/2 5/16 11
11/2 3'/% 15/e 1/m 7 3
„ 5/16 12
2 3 /,e 1s'/32 13/,e 8 5/16 15
br nil nl NIBCC]
www.tolco.com
Revision 5/24/2001
Fig. 24 - Hanger for CPVC Plastic Pipe
Double Fastener Strap Type - Side Mount
Size Range — 3/4" thru 2" CPVC pipe
Material — Carbon Steel, Pre -Galvanized
Function — Intended to perform as a hanger/restrainer to support only
CPVC piping used in automatic fire sprinkler systems. Can be installed
on the top or on the bottom of a beam. The Fig. 24 can also function
as a restrainer to prevent the upward movement of the sprinkler head
during activation.
Approvals — Underwriters' Laboratories Listed in the USA (UL) and
Canada (cUL) to support fire sprinkler piping. Meets and exceeds the
requirements of NFPA 13, 13R and 13D.
Features — Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design* protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the two
UL Listed hex head self threading screws** furnished with the product. It
is recommended that rechargeable electric drills fitted with a hex socket
attachment be used as installation tools. No impact tools (such as a hammer)
or impact fasteners (such as drive screws or nails) are allowed. Damage has
been known to result from installations using impact type tools. No pre -drilling
of a pilot hole in wood is required.
Finish — Pre -Galvanized
Order By — Figure number and pipe size
* Patent Pending
** Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
CPVC Max. Hanger Fastener Hex Approx.
Office/Manufacturing Facility • 1375 Sampson Ave • Corona. CA 92879 • Ph: 951.737.5599 • Fax: 951.737 0330
Customer Service • 800 786 5266
www.tolco.com