HomeMy WebLinkAboutPLANS 725 Castle Mountain Rd PV Solar 2023-01-09Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
VICINITY MAP
SCALE: NTS
PV SOLAR SYSTEM DETAILS
BUILDING INFORMATION:
CONSTRUCTION TYPE: V-B
OCCUPANCY: R3
ROOF:
SYSTEM SIZE: DC STC: 9.250 KW
SYSTEM SIZE: AC CEC: 8.437 KW
SOLAR MODULES: ( )
SATELLITE VIEW
SCALE: NTS
25 Silfab 370 watt
Truss: 2 X 4 @ 24'' O.C.
ELECTRICAL INFORMATION:
NEW UPGRADED
SPAN PANEL BUS SIZE: 225A
SPAN BREAKER SIZE: 200A
MOUNTING SYSTEM:IRONRIDGE XR-100
MAIN
3. ALL METALLIC EQUIPMENT SHALL BE GROUNDED
4. CONTRACTOR SHALL OBTAIN ELECTRICAL PERMITS PRIOR TO
INSTALLATION AND SHALL COORDINATE ALL INSPECTIONS, TESTING
COMMISSIONING AND ACCEPTANCE WITH THE CLIENT,
UTILITY CO. AND CITY INSPECTORS AS NEEDED.
5. THE ELECTRICAL CONTRACTOR SHALL VERIFY THE EXACT LOCATIONS OF
SERVICE POINTS AND SERVICE SIZES WITH THE SERVING UTILITY COMPANY
AND COMPLY WITH ALL UTILITY COMPANIES REQUIREMENTS.
6. DRAWINGS ARE DIAGRAMMATIC ONLY, ROUTING OF RACEWAYS SHALL
BE OPTION OF THE CONTRACTOR UNLESS OTHERWISE NOTED AND SHALL
BE COORDINATED WITH OTHER TRADES.
7. IF THE ROOF MATERIAL OR ROOF STRUCTURE NOT ADEQUATE FOR PV
INSTALLATION, CALL ENGINEER PRIOR TO INSTALL. THE CONTRACTOR IS
RESPONSIBLE TO VERIFY THAT THE ROOF IS CAPABLE OF WITHSTANDING
THE EXTRA WEIGHT.
8. IF THE DISTANCES FOR CABLE RUNS ARE DIFFERENT THAN SHOWN, THE
CONTRACTOR SHALL NOTIFY THE ELECTRICAL ENGINEER TO VALIDATE THE
WIRE SIZE. FINAL DRAWINGS WILL BE RED-LINED AND UPDATED AS
APPROPRIATE.
9. WHENEVER A DISCREPANCY IN QUALITY OF EQUIPMENT ARISES ON THE
DRAWING OR SPECIFICATIONS, THE CONTRACTOR SHALL BE RESPONSIBLE
FOR PROVIDING AND INSTALLING ALL MATERIAL AND SERVICES REQUIRED
BY THE STRICTEST CONDITIONS NOTED ON THE DRAWINGS OR IN THE
SPECIFICATIONS TO ENSURE COMPLETE COMPLIANCE AND LONGEVITY OF
THE OPERABLE SYSTEM REQUIRED BY THE ARCHITECT/ENGINEERS.
10. ALL BROCHURES, OPERATION MANUALS, CATALOGS, SHOP DRAWINGS,
ETC. SHALL BE HANDED OVER TO OWNER'S REPRESENTATIVE AT THE
COMPLETION OF WORK
PHOTOVOLTAIC NOTES:
1. ROOFTOP MOUNTED PHOTOVOLTAIC PANELS AND MODULES SHALL
BE TESTED, LISTED AND IDENTIFIED BY RECOGNIZED ELECTRICAL
TESTING LABORATORY
2. SOLAR SYSTEM SHALL NOT COVER ANY PLUMBING OR MECHANICAL
VENTS
3. MODULES AND SUPPORT STRUCTURES SHALL BE GROUNDED.
5. REMOVAL OF AN INTERACTIVE INVERTER OR OTHER EQUIPMENT SHALL
NOT DISCONNECT THE BONDING CONNECTION BETWEEN THE GROUNDING
ELECTRODE CONDUCTOR AND THE PHOTOVOLTAIC SOURCE AND/OR
OUTPUT CIRCUIT GROUNDED CONDUCTORS.
4. SOLAR INVERTER SHALL BE LISTED TO UL1741.
6. ALL PV MODULES AND ASSOCIATED EQUIPMENT AND
WIRING SHALL BE PROTECTED FROM PHYSICAL DAMAGE.
7. LIVE PARTS OF PV SOURCE CIRCUITS AND PV OUTPUT
CIRCUITS OVER 150V TO GROUND SHALL NOT BE
ACCESSIBLE TO OTHER THAN QUALIFIED PERSONS WHILE
ENERGIZED.
8. INVERTER IS EQUIPED WITH INTEGRATED GFDI, THUS
PROVIDING GROUND FAULT PROTECTION
9. ALL CONDUCTORS SHALL BE COPPER AND 90 DEG
RATED
10. ALL ELECTRICAL EQUIPMENT SHALL BE LISTED BY A
RECOGNIZED ELECTRICAL TESTING LABORATORY.
11. A SINGLE CONDUCTOR SHALL BE PERMITTED TO BE
USED TO PERFORM THE MULTIPLE FUNCTIONS OF DC
GROUNDING, AC GROUNDING AND BONDING BETWEEN
AC AND DC SYSTEMS.
12. NON-CURRENT CARRYING METAL PARTS OF
EQUIPMENT SHALL BE EFFECTIVELY BONDED TOGETHER.
BOND BOTH ENDS OF RACEWAYS.
GENERAL NOTES
1. ALL ELECTRICAL MATERIALS SHALL BE NEW AND LISTED BY RECOGNIZED
ELECTRICAL TESTING LABORATORY
CUSTOM MADE EQUIPMENT SHALL HAVE COMPLETE TEST DATA SUBMITTED
BY THE MANUFACTURER ATTESTING TO ITS SAFETY
2. OUTDOOR EQUIPMENT SHALL BE NEMA 3R RATED OR BETTER
ROOF PLAN
SINGLE LINE DIAGRAM
ATTACHMENT LAYOUT
SIGNAGE
1
INDEX
2
3
4
5
6.1
7
8
9
SITE PLAN
MODULE DATA SHEET
RACKING DATA SHEET
THE INSTALLATION OF SOLAR ARRAYS AND
PHOTOVOLTAIC POWER SYSTEMS SHALL COMPLY
WITH THE FOLLOWING CODES:
NATIONAL ELECTRICAL CODE 2020
INTERNATIONAL RESIDENTIAL CODE 2015
INTERNATIONAL BUILDING CODE 2015
INTERNATIONAL FIRE CODE 2015
AS ADOPTED BY THE STATE OF COLORADO
ALL OTHER ORDINANCE ADOPTED BY THE LOCAL
GOVERNING AGENCIES
COMP SHINGLE
GATEWAY DATA SHEET
(1) POWERWALL+
PHOTOVOLTAIC (PV) AND BATTERY ENERGY
STORAGE SYSTEM (BESS)
(1) TESLA POWERWALL BATTERY
6.2
POWERWALL+ DATA SHEET
POWERWALL+ DATA SHEET
10 ATTACHMENT DATA SHEET
11 SPAN PANEL DATA SHEET
ELEV = 7880 FT
Sealed For
Existing Roof and
Attachment Only
Brandon
R. Little
Digitally signed by
Brandon R. Little
Date: 2023.01.06
12:35:01 -07'00'
SAFEbuilt
APPROVED
Subject to inspection and
compliance to all relevant
Adopted Building and Municipal
codes.
Changes in Plans MUST be
approved.
D.GRAHAM
01/09/2023
I-CODES 2015
PRINT PLANS IN
COLOR AND HAVE
FOR INSPECTOR
AT TIME OF
INSPECTION
INSTALLATION
INSTRUCTIONS AND
MANUALS MUST BE
ON JOB FOR THE
INSPECTOR AT THE
TIME OF
INSPECTION FOR
ALL EQUIPMENT.
PLAN REVIEW IS FOR
STRUCTURAL ONLY
NOTES TO BE
TYPICAL ON ALL
PAGES AND
ELEVATIONS
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
ROOF PLAN1
Conduit
Solar Module
INDEX
(N) Junction Box
Setback
JB
Total Roof Area: 1909
Total Module Area: 550
28.81% of Coverage
(N) Gateway 2GT
(N) PowerWall+PW+
(N) BatteryBT
(N) Span PanelSP
(N) AC DisconnectAC
(N) Main MeterMM
18''
f
i
r
e
s
e
t
b
a
c
k
18
'
'
f
i
r
e
s
e
t
b
a
c
k
Cas
t
l
e
M
o
u
n
t
a
i
n
R
d
GT
SP
AC
PW+
MM
Solar PV Array 1
11 - Silfab 370 W Modules
Pitch: 26 Deg
Orientation: 205 Deg
Solar PV Array 2
14 - Silfab 370W Modules
Pitch: 26 Deg
Orientation:115 Deg
a
a
a
a
a
a
a
a
a
a
a
c
c
c
b
b
JB
c
c
c c
b
b
b
b
b SCALE: 1/8" = 1'-0"
S
180 °
E
90 °W
270 °
N
0°
01/06/2023
Sealed For
Existing Roof and
Attachment Only
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
SINGLE LINE
DIAGRAM2
PERCENT
OF VALUES
NUMBER OF CURRENT
CARRYING CONDUCTORS IN EMT
.80 4-6
.70 7-9
.50 10-20
#ITEM DESCRIPTION QTY
1 PV MODULE
2 PVC JUNCTION BOX
4"x4"x2" UL LISTED WATER TIGHT
NEMA TYPE 3 1
3
...1
2
1
String a: (11) Modules
AC SYSTEM SIZE CALCULATION
Module PTC
Rating (W)x NO. of
Modules x Average Inverter
CEC Efficiency =AC System Size
x x 98%= 8.437 kW AC25
WIRE CHART
#
MODULE QTY x NEC MULT
x MICROINV. OUTPUT
AMPS = DESIGN AMPS
BREAKER
SIZE (A)WIRE TYPE EGC
WIRE RATING X TEMP
DERATE X CONDUCTOR
DERATE = DERATED WIRE
CONDUIT SIZE
1
32 X 1.25 = 40A 503
344.4
10.33 X 1.25 = 12.91A 20 (2) #10 PV-WIRE (1) #6 BARE SOLID COPPER GEC 40 X .71 X 1 = 28.4 >= 12.91 FREE IN THE AIR
20 (6) #10 AWG, CU-THWN-2 40 X .71 X .8 =12.72>=12.91 3/4" EMT2(1) #8 AWG, CU-THWN-2
25
600V CALCULATION
MAX NUMBER MODULES PER STRING: 11
Voc:44.76 V
CORRECTION FACTOR:1.12
MAX SYSTEM VOLTAGE 11 x 44.76x 1.12 = 551.4V
4 INVERTER
10.33 X 1.25 = 12.91A
1
SILFAB 370 WATT
SIL-370 BK
Voc =44.76V, Vmp = 38.34V
Isc = 10.33A, Imp = 9.69A
...1
1
String b: (7) Modules
...1
1
String c: (7) Modules
2 3
6
50A
4
AC DISCONNECT 60A 2P BLADE TYPE 240V
NON-FUSIBLE AC DISCONNECT 15
6
7
1BACKUP GATEWAY 200A TESLA BACKUP GATEWAY 2
(1) #4 AWG, CU-THWN-2200(3) #3/0 AWG, CU-THWN-2 225 X .91 X 1= 204.75>=200
NOTE:AC DISCONNECT VISIBLE AND LOCKABLE
ALL DC CONNECTORS TO MODULES OR INVERTERS
MUST BE OF MATCHING MANUFACTURE BRAND AND
STYLE. DO NOT USE 'COMPATIBLE' CONNECTORS
WHICH HAVE NOT BEEN UL TESTED FOR
COMPATIBILITY.PERFORMANCE AND FIRE DAMAGE
MAY RESULT FROM MIS-MATCHED CONNECTOR
USEAGE
7
1MAIN METER UTILITY METER
4
KEY NOTES:
·SOLID BARE G.E.C (FREE-AIR) MOUNTED UNDER ARRAY
·PER NEC 250.120(C): WHERE CONDUCTORS & GROUND WIRE ARE RUN
EXPOSED ON FROM ARRAY TO J-BOX, CONDUCTORS & BARE GROUND
WIRE SHALL BE CONCEALED INSTALL IN CONDUIT
·PER NEC ARTICLE 690.35 INVERTER GROUND FAULT PROTECTION
PROVIDED
·ALL GROUNDS AND NEUTRALS BONDED TO EXISTING GROUNDING
CONDUCTOR W/IRREVERSIBLE CRIP CONNECTOR,
·BACKFED BREAKERS MUST BE LOCATED @ OPPOSITE END OF BUS BAR
FROM MAIN BREAKER OR MAIN LUG ON GRID SIDE. WHEN A BACKFED
BREAKER IS THE METHOD OF UTILITY INTERCONNECTION, BREAKER
SHALL NOT READ ' LINE OR LOAD'.
·PER CEC 250.65(C): CONDUCTOR SPLICES ONLY ALLOWED WITH
COMPRESSION CONNECTORS OR EXOTHERMIC WELDING
·ALL GROUNDS AND NEUTRALS BONDED TO EXISTING GROUNDING
CONDUCTOR W/IRREVERSIBLE CRIP CONNECTOR,
·VERIFY (E) UFER GROUND NEAR MSP. IF (E) UFER IS NOT ACCESSIBLE
259(5,),$%/(,167$//$1(:;
/21**5281',1*52'$1'
BOND SOLAR SYSTEM EQUIPMENT GROUNDING ACCORDINGLY.
TESLA POWERWALL +
Model 1850000-xx-y
98% CEC EFFICIENCY
NOMINAL BATTERY ENERGY 13.5 KW
MAXIMUM CONTINUOUS POWER 7.6 KW
MAX OUTPUT CURRENT 32Aac
MAX INPUT VOLTAGE 600VDC
MPPT TRACKERS: 4
SPAN
PANEL
SPAN 01-00200 MAX MAIN OCPD,
225A BUSSING, 200 FED THROUGH
RATED NEMA 3R
Communication wire
5
3
20
0
A
3
SPAN 01-00200
Max Main OCPD,
225A Bussing, 200 Fed
Through Rated NEMA 3R
TO (E) HOME
LOADS
3/4" EMT
2" EMT
(3) #8 AWG, CU-THWN-2 (1) #8 AWG, CU-THWN-2 55 X .91 X 1= 50.05>=50
4
4
THIS ELECTRICAL INSTALLATION
MUST CONFORM TO THE 2020
NEC
NEW SERVICE CHANGE
REVIEWED
BY SAFEBUILT
01/09/2023
INSPECTION PER THE STATE
OF COLORADO
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
SIGNAGE3
Permanent directory or plaque providing
location of service disconnecting means
and photovoltaic system disconnecting
means, if not located at the same location.
(Plaques shall be metal or plastic, with
engraved or machine printed letters, or
electro-photo plating, in a contrasting color to
the plaque. Plaques shall be permanently
attached to the equipmenq or in the required
location using an approved method that is
suitable to withstand the environment to which
it is exposed. Plaques and signage shall meet
legibility, defacemet, exposure and adhesion
requirements of Underwriters Laboratories
marking and labeling system 969(UL969).
MARKINGS, LABELS AND WIRING SIGNS
A. Purpose: Provide emergency responders with appropriate warning and guidance with
respect to isolating solar electric system.
This can facilitate identifying energized electrical lines that connect solar panels to the
inverter, as these should not be cut when venting for smoke removal
B. Main Service Disconnect.
1. Residential buildings - The marking main be placed within the main service
disconnect. The marking shall be placed
outside cover if the main service disconnect is operable with the service panel closed.
2. Commercial buildings - Tha marking shall be placed adjacent to the main service
disconnect clearly visible from the location where the level is operated
3. Markings: Verbiage, Format and Type of Material.
a. Verbiage: CAUTION: SOLAR ELECTRIC SYSTEM CONNECTED
b. Format: White lettering on a red background. Minimum 3/8 inches letter height. All
letters shall be capitalized. Arial or similar font, non bold.
c. Material: Reflective, weather resistant material suitable for the environment (use UL -
969 as standard for weather rating). Durable adhesive materials meet this requirement.
C.Marking Requirements on DC conduit, raceways, enclosures, cable assemblies, DC
combiners and junction boxes:
1. Markings: Verbiage, Format and Type of Material.
a. Placement : Markings shall be placed every 10 feet on all interior and exterior DC
conduits, raceways, enclosures, and cable assemblies,
at turns, above and for below penetrations, all DC combiners and junction boxes
b. Verbiage: CAUTION: SOLAR CIRCUIT Note: The format and type of material shall
adhere to "V. V-3b, c" of this requirement.
c. Inverters are not required to have caution markings
1.Marking is required on all interior and exterior DC conduit raceways,enclosures,cable
assemblies,and junction boxes,combiner boxes and disconnects.
2.The materials used for marking shall be reflective,weather resistant material suitable
for the environment.
Minimum 3/8 "letter height; all upper case letters Arial or similar font; Red background
with white lettering.
3.Marcking shall contain the words: WARNING : PHOTOVOLTAIC POWER SOURCE.
4.Marking shall be placed adjacent to the main service disconnect in a location clearly
visible from the location where the disconnect is operated
1
2
(STICKER TO BE LOCATED ON
CONDUIT WITH DC CURRENT
EVERY 4' HORIZONTALLY OR
10' VERTICALLY AND 1' FROM
EACH SIDE OF A BEND)
3
4
5
(TO BE LOCATED ON
SUB-PANEL ONLY
WHEN SUB-PANEL IS
DEDICATED FOR PV ONLY)
6
7
8
9
(STICKER LOCATED
INSIDE PANEL
NEXT TO SOLAR BREAKER)
10
(STICKER LOCATED
INSIDE PANEL
BELOW PV BREAKER)
PV ARRAY
J BOX
INVERTER
INTEGRATED
DC DISCONNECT
PV SUB-PANEL
* if applicable
SUB-PANEL
* if applicable
AC
DISCONNECT
* if applicable
METER
MAIN SERVICE
PANEL
2
1
3
4 5
6
7
9
8
10
7
9
8
10
7
7
9
8
10
*if applicable
11
(STICKER LOCATED
ON THE PV SUB PANEL)
11
12
(STICKER LOCATED
ON THE MAIN SERVICE PANEL)
12
CAUTION
AUTHORIZED SOLAR
PERSONNAL ONLY!
CAUTION
SOLAR DC CURRENT PRESENT
DURING DAYLIGHT HOURS
WARNING!
ELECTRIC SHOCK HAZARD.
IF GROUND FAULT IS INDICATED,
NORMALLY GROUNDED
CONDUCTORS MAY BE
UNGROUNDED AND ENERGIZED.
DC DISCONNECT
DC PHOTOVOLTAIC POWER SOURCE
RATED MAX POWER POINT CURRENT- AMPS
RATED MAX POWER POINT VOLTAGE- VOLTS
MAXIMUM SYSTEM VOLTAGE- VOLTS
SHORT CIRCUIT CURRENT- AMPS
WARNING!
ELECTRIC SHOCK HAZARD.
DO NOT TOUCH THE TERMINALS.
TERMINALS ON BOTH THE LINE AND
LOAD SIDES MAY BE ENERGIZED IN
THE OPEN POSITION.
PV LOAD CENTER SIZED FOR PV
BREAKERS ONLY OR RENDERED UNABLE
TO ACCEPT ANY ADDITIONAL LOADS.
PV SUB-PANEL ONLY
AC DISCONNECT
AC PHOTOVOLTAIC POWER SOURCE
RATED AC OUTPUT CURRENT: A MAX
NOMINAL AC OPERATING VOLTAGE: 240 Vac
THIS PANEL FED BY
MULTIPLE SOURCES
(UTILITY & SOLAR)
SOLAR
WARNING!
INVERTER OUTPUT CONNECTION. DO NOT
RELOCATE THIS OVERCURRENT DEVICE
PHOTOVOLTAIC SYSTEM
EQUIPPED WITH
RAPID SHUT DOWN
40
13
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRIC
PV PANELS
REVIEWED
BY SAFEBUILT
01/09/2023
INSPECTION PER THE STATE
OF COLORADO
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
SITE PLAN4
Solar Module
INDEX
(N) Gateway 2GT
(N) PowerWall+PW+
(N) BatteryBT
(N) Span PanelSP
(N) AC DisconnectAC
(N) Main MeterMM
Cas
t
l
e
M
o
u
n
t
a
i
n
R
d
GT
SP
AC
PW+
MM
384'-1"
155'-3"
57'-6"
193'-10"
228'-9"
707'-7"
203'-8"
389'-4"
D
R
I
V
E
W
A
Y
PROPERTY LINE
96'-11"
67'-9"
SCALE: 1/64" = 1'-0"
S
180 °
E
90 °W
270 °
N
0°
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
ATTACHMENT
LAYOUT5
MODULE WEIGHT (lbs)
# OF MODULES
TOTAL MODULE WEIGHT (lbs)
RACK WEIGHT (lbs)
TOTAL SYSTEM WEIGHT (lbs)
# OF STANDOFFS
MAX SPAN BETWEEN STANDOFFS (in)
LOADING PER STANDOFF (lbs)
TOTAL AREA (sq.ft.)
LOADING (PSF)
1047.5
209.5
1257
88
24
14.28
2.28
550
25
41.9
SOLAR MODULE
BlockingMaximum 6"
Truss: 2 X 4 @ 24'' O.C.
1.
2.
3. Roof attachment hardware to be mounted to existing structure
( ) with 24" O.C. rail spans or less.
4. Lag bolts are 5/16" X 3.5" stainless steel with 2.5" minimum embedment into the center of the roof
5. Roof sheathed with 1/2" plywood and upper surface is faced with felt paper.
Finished roof surface is One layer of .
Truss: 2 X 4 @ 24'' O.C.
COMP SHINGLE
IronRidge FlashFoot 2 Attachments
IronRidge XR-100 Racking System
RAIL
ATTACHMENT
TRUSS
PV MODULE FRAME
IRONRIDGE RAIL
DETAIL, END CLAMP FRONTB
IRONRIDGE STOPPER SLEEVE
IRONRIDGE UNIVERSAL
FASTENING OBJECTPV MODULE FRAME
IRONRIDGE RAIL
DETAIL, END CLAMP PLANB
IRONRIDGE STOPPER
SLEEVE
IRONRIDGE UNIVERSAL
FASTENING OBJECT
PV MODULE FRAME
IRONRIDGE RAIL
DETAIL, MID CLAMP FRONTC
IRONRIDGE UNIVERSAL
FASTENING OBJECTPV MODULE FRAME
DETAIL, MID CLAMP PLANC
IRONRIDGE UNIVERSAL
FASTENING OBJECT
IRONRIDGE RAIL
IRONRIDGE FLASHFOOT2
A
IRONRIDGE RAIL
PV MODULE
0.4xL MAX.
CB D
IRONRIDGE STOPPER SLEEVE
IRONRIDGE UNIVERSAL
FASTENING OBJECT
IRONRIDGE FLASHFOOT2
IRONRIDGE UNIVERSAL
FASTENING OBJECT
(E) ROOF
MEMBRANE
IRONRIDGE
FLASHFOOT2
IRONRIDGE
RAIL
PV MODULE,
BY OTHERS
(E) BUILDING
STRUCTURE
(E) ROOF
MEMBRANE
IRONRIDGE
FLASHFOOT2
IRONRIDGE
RAIL
PV MODULE,
BY OTHERS
(E) BUILDING
STRUCTURE
DETAIL, FLASHFOOT2 SIDEA DETAIL, FLASHFOOT2 FRONTD
5/16" STAINLESS STEEL LAG SCREW
MIN. 2.5" EMBED INTO FRAMING MEMBER
FRONT VIEW
SIDE VIEW
(E) Truss
3.0
12.0
4.50
9.0
3.67
3.56 1.02
IRONRIDGE ATTACHMENT AND RACKING DETAILS
01/06/2023
Sealed For
Existing Roof and
Attachment Only
REVIEWED
BY SAFEBUILT
01/09/2023
PROVIDE ALL RACKING
INSTALLATION INSTRUCTIONS
AND DOCUMENTATION TO THE
INSPECTOR AT THE TIME OF
INSPECTION
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
6.1 POWERWALL+
DATA SHEET
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
POWERWALL+
DATA SHEET6.2
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
MODULE
DATA SHEET7
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
8 GATEWAY
DATA SHEET
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
9 RACKING
DATA SHEET
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
10 ATTACHMENT
DATA SHEET
REVIEWED
BY SAFEBUILT
01/09/2023
Project Name:
Terry Caldwell - Summit
Property address:
725 Castle Mountain Rd
Estes Park, CO 80517
DATE: 12/15/2022
Elevated Independent
Energy
Address:7000 Broadway #104
Denver, CO 80221
License Number:EC.0101394
Phone:970-460-4970
SPAN PANEL
DATA SHEET11
REVIEWED
BY SAFEBUILT
01/09/2023