HomeMy WebLinkAbout1119 Morgan St Loads
Gillam Addition
HVAC Load Calculations
for
Glacier Creek Const.
Prepared By:
Rexs Allen
Air-City Heating And A/C LLC
Friday, July 9, 2021
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 2
Project Report
General Project Information
Project Title:Gillam Addition
Designed By:Glacier Creeki Cont.
Project Date:Friday, July 9, 2021
Client Name:Glacier Creek Const.
Company Name:Air-City Heating And A/C LLC
Company Representative:Rexs Allen
Design Data
Reference City:Estes Park, Colorado
Building Orientation:Front door faces North
Daily Temperature Range:High
Latitude:40Degrees
Elevation:4935ft.
Altitude Factor:0.834
Elevation Heating Adj. Factor:0.760
OutdoorOutdoorOutdoorIndoorIndoorGrains
Dry BulbWet BulbRel.HumRel.HumDry BulbDifference
Winter:40.21n/a30%7240.39
Summer:896223%50%75-21
Check Figures
Total Building Supply CFM:228CFM Per Square ft.:0.327
Square ft. of Room Area:699Square ft. Per Ton:1,986
Volume (ft³):5,592
Building Loads
Total Heating Required Including Ventilation Air:20,094Btuh20.094MBH (Based On 0.760 Derating)
Total Sensible Gain:4,504Btuh100%
Total Latent Gain:-280Btuh0%
Total Cooling Required Including Ventilation Air:4,504Btuh0.38Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 3
Miscellaneous Report
System 1 OutdoorOutdoorOutdoorIndoorIndoorGrains
Input DataDry BulbWet BulbRel.HumRel.HumDry BulbDifference
Winter:40.2118%30%7240.39
Summer:896223%50%75-21.20
Duct Sizing Inputs
Main TrunkRunouts
Calculate:YesYes
Use Schedule:YesYes
Roughness Factor:0.003000.01000
Pressure Drop:0.1000in.wg./100 ft.0.1000in.wg./100 ft.
Minimum Velocity:0ft./min0ft./min
Maximum Velocity:900ft./min750ft./min
Minimum Height:5in.5in.
Maximum Height:8in.8in.
Outside Air Data
WinterSummer
Infiltration Specified:0.210AC/hr0.110AC/hr
20CFM10CFM
Infiltration Actual:0.168AC/hr0.000AC/hr
Above Grade Volume:X 5,592Cu.ft.X 5,592Cu.ft.
937Cu.ft./hr0Cu.ft./hr
X 0.0167X 0.0167
Total Building Infiltration:16CFM0CFM
Total Building Ventilation:12CFM12CFM
---System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 12.85 = (1.10 X 0.834 X 14.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: -12.02 = (0.68 X 0.834 X -21.20 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 62.39 = (1.10 X 0.834 X 68.00 Winter Temp. Difference)
Winter Infiltration Specified:0.210 AC/hr (20 CFM), Construction: Tight
Summer Infiltration Specified:0.110 AC/hr (10 CFM), Construction: Tight
Duct Load Factor Scenarios for System 1
AtticDuctDuctSurfaceFrom
No.TypeDescriptionLocationCeilingLeakageInsulationArea\[T\]MDD
1SupplyOpen Crawl-0.128184No
1ReturnOpen Crawl-0.12868No
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 4
Load Preview Report
SysSysSys
Netft.²SenLatNetSenDuct
HtgClgAct
ScopeTon/TonAreaGainGainGainLossSize
CFMCFMCFM
Building0.381,9866994,504-2804,50415,271214228228
System 10.381,9866994,504-2804,50415,2712142282287x8
Ventilation152-142152736
Supply Duct Latent-600
Return Duct163-7885796
Humidification719
Zone 16994,19004,19013,0212142282287x8
1-Closet327207290015441--5
2-Bedr4oom13261306131,7802933331--5
3-Desk4419001905971010101--5
4-Bath/Laundry9925302531,8103014141--5
5-Living Room1691,68201,6823,8656392921--6
6-Kitchen14338103811,7142821211--5
7-Landing3625102518611414141--5
8-Stairs4474807481,4932541411--5
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 5
Duct Size Preview
Room or MinimumMaximumRough.DesignSPDuctDuctReg
HtgClgAct.Duct
Source
Duct NameVelocityVelocityFactorL/100LossVelocityLengthSize
FlowFlowFlowSize
System 1
Supply Runouts
Zone 1
1-ClosetBuilt-In07500.010.128.815441--5
2-Bedr4oomBuilt-In07500.010.1244.92933331--5
3-DeskBuilt-In07500.010.175.91010101--5
4-Bath/LaundryBuilt-In07500.010.11013014141--5
5-Living RoomBuilt-In07500.010.1466.96392921--6
6-KitchenBuilt-In07500.010.1152.32821211--5
7-LandingBuilt-In07500.010.1100.51414141--5
8-StairsBuilt-In07500.010.1298.82541411--5
Other Ducts in System 1
Supply Main TrunkBuilt-In09000.0030.1587.12142282287x8
SummarySummarySummarySummarySummarySummarySummarySummary
System 1
Heating Flow:214
Cooling Flow:228
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 6
Total Building Summary Loads
ComponentAreaSenLatSenTotal
DescriptionQuanLossGainGainGain
4A-6-d: Glazing-Double pane low-e (e = 0.20 or less), 1372,88702,4322,432
high performance, sliding glass door, e=0.05 on
surface 2, any frame, U-value 0.31, SHGC 0.31
12F-0bw: Wall-Frame, R-21 insulation in 2 x 6 stud 6993,0900210210
cavity, no board insulation, brick finish, wood studs,
U-value 0.065
16C-50: Roof/Ceiling-Under Attic with Insulation on Attic 6999520475475
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, White or
Light Color Shingles, Any Wood Shake, Light Metal,
Tar and Gravel or Membrane, R-50 insulation, U-
value 0.02
20P-38: Floor-Over open crawl space or garage, Passive, 6991,42608383
R-38 blanket insulation, any cover, U-value 0.03
Subtotals for structure:8,35503,2003,200
People:0000
Equipment:000
Lighting:000
Ductwork:4,488-1381,1531,014
Infiltration: Winter CFM: 16, Summer CFM: 0974000
Ventilation: Winter CFM: 12, Summer CFM: 12736-14215210
Humidification (Winter) 1.96 gal/day :719000
Total Building Load Totals:15,271-2804,5044,224
Check Figures
Total Building Supply CFM:228CFM Per Square ft.:0.327
Square ft. of Room Area:699Square ft. Per Ton:1,986
Volume (ft³):5,592
Building Loads
Total Heating Required Including Ventilation Air:20,094Btuh20.094MBH (Based On 0.760 Derating)
Total Sensible Gain:4,504Btuh100%
Total Latent Gain:-280Btuh0%
Total Cooling Required Including Ventilation Air:4,504Btuh0.38Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 7
System 1 Summary Loads
ComponentAreaSenLatSenTotal
DescriptionQuanLossGainGainGain
4A-6-d: Glazing-Double pane low-e (e = 0.20 or less), 1372,88702,4322,432
high performance, sliding glass door, e=0.05 on
surface 2, any frame, U-value 0.31, SHGC 0.31
12F-0bw: Wall-Frame, R-21 insulation in 2 x 6 stud 6993,0900210210
cavity, no board insulation, brick finish, wood studs,
U-value 0.065
16C-50: Roof/Ceiling-Under Attic with Insulation on Attic 6999520475475
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, White or
Light Color Shingles, Any Wood Shake, Light Metal,
Tar and Gravel or Membrane, R-50 insulation, U-
value 0.02
20P-38: Floor-Over open crawl space or garage, Passive, 6991,42608383
R-38 blanket insulation, any cover, U-value 0.03
Subtotals for structure:8,35503,2003,200
People:0000
Equipment:000
Lighting:000
Ductwork:4,488-1381,1531,014
Infiltration: Winter CFM: 16, Summer CFM: 0974000
Ventilation: Winter CFM: 12, Summer CFM: 12736-14215210
Humidification (Winter) 1.96 gal/day :719000
System 1 Load Totals:15,271-2804,5044,224
Check Figures
Supply CFM:228CFM Per Square ft.:0.327
Square ft. of Room Area:699Square ft. Per Ton:1,986
Volume (ft³):5,592
System Loads
Total Heating Required Including Ventilation Air:20,094Btuh20.094MBH (Based On 0.760 Derating)
Total Sensible Gain:4,504Btuh100%
Total Latent Gain:-280Btuh0%
Total Cooling Required Including Ventilation Air:4,504Btuh0.38Tons (Based On Sensible + Latent)
Notes
Rhvac is an ACCA approved Manual J, D and S computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 8
Equipment Data - System 1
Heating
System Type:Natural Gas Furnace
Model:GMEC960302BNA
Tradename:Kenmore
Manufacturer:GOODMAN MANUFACTURING COMPANY
Description:Natural Gas or Propane Furnace
Comment:2 stage
Capacity:28,800
Efficiency:96 AFUE
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 9
Manual S Performance Data - System 1
Loads and Design Conditions
Cooling:
Outdoor Dry Bulb:0Sensible Gain:4.504
Outdoor Wet Bulb:62Latent Gain:-0.280
Indoor Dry Bulb:75Total Gain:4.224
Indoor RH:50Load SHR:1.07
Supply Airflow:0Entering Dry Bulb:0
Entering Wet Bulb:0
Heating:
Outdoor Dry Bulb:4Sensible Loss:15.271
Indoor Dry Bulb:72Entering Dry Bulb:64.4
Indoor RH:30Supply Airflow:214
Equipment Performance Data at System Design Conditions
Cooling:
Model Type: Standard Air Conditioner,
Manufacturer:
Interpolation Results:
Percent
Loadof Load
Sensible Capacity:0.0004.5040%
Latent Capacity:0.000-0.2800%
Total Capacity:0.0004.2240%
Heating:
Model Type: Natural Gas Furnace, Model: GMEC960302BNA, Nominal Capacity: 28.800, Manufacturer: GOODMAN
MANUFACTURING COMPANY
Results:
Percent
Loadof Load
Heating Capacity:28.80015.271189%
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 10
Detailed Room Loads - Room 1 - Closet (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:4.0ft.System Number:1
Room Width:8.0ft.Zone Number:1
Area:32.0sq.ft.Supply Air:4CFM
Ceiling Height:8.0ft.Supply Air Changes:0.9AC/hr
Volume:256cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:1CFM
Runout Air:4CFMPercent of Supply.:21%
Runout Duct Size:5in.Actual Summer Vent.:0CFM
Runout Air Velocity:29ft./min.Percent of Supply:5%
Runout Air Velocity:29ft./min.Actual Winter Infil.:2CFM
Actual Loss:0.001in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
S -Wall-12F-0bw 8 X 8640.0654.42830.3019
W -Wall-12F-0bw 4 X 8320.0654.41410.3010
UP-Ceil-16C-50 4 X 8320.0201.4440.7022
Floor-20P-38 8 X 4320.0302.0650.104
Subtotals for Structure:533055
Infil.: Win.: 1.8, Sum.: 0.0961.1671120.00000
Ductwork:25517
Room Totals:900072
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 11
Detailed Room Loads - Room 2 - Bedr4oom (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:12.0ft.System Number:1
Room Width:11.0ft.Zone Number:1
Area:132.0sq.ft.Supply Air:33CFM
Ceiling Height:8.0ft.Supply Air Changes:1.9AC/hr
Volume:1,056cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:2CFM
Runout Air:33CFMPercent of Supply.:5%
Runout Duct Size:5in.Actual Summer Vent.:2CFM
Runout Air Velocity:245ft./min.Percent of Supply:5%
Runout Air Velocity:245ft./min.Actual Winter Infil.:2CFM
Actual Loss:0.043in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
S -Wall-12F-0bw 11 X 8680.0654.43010.3020
S -Gls-4A-6-d shgc-0.31 0%S200.31021.142217.10342
UP-Ceil-16C-50 12 X 111320.0201.41800.7090
Floor-20P-38 11 X 121320.0302.02690.1016
Subtotals for Structure:1,1720468
Infil.: Win.: 1.6, Sum.: 0.0881.1701030.00000
Ductwork:505145
Room Totals:1,7800613
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 12
Detailed Room Loads - Room 3 - Desk (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:11.0ft.System Number:1
Room Width:4.0ft.Zone Number:1
Area:44.0sq.ft.Supply Air:10CFM
Ceiling Height:8.0ft.Supply Air Changes:1.8AC/hr
Volume:352cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:1CFM
Runout Air:10CFMPercent of Supply.:5%
Runout Duct Size:5in.Actual Summer Vent.:1CFM
Runout Air Velocity:76ft./min.Percent of Supply:5%
Runout Air Velocity:76ft./min.Actual Winter Infil.:1CFM
Actual Loss:0.005in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
S -Wall-12F-0bw 4 X 8260.0654.41150.308
S -Gls-4A-6-d shgc-0.31 0%S60.31021.112617.00102
UP-Ceil-16C-50 11 X 4440.0201.4600.7030
Floor-20P-38 4 X 11440.0302.0900.105
Subtotals for Structure:3910145
Infil.: Win.: 0.6, Sum.: 0.0321.156370.00000
Ductwork:16945
Room Totals:5970190
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 13
Detailed Room Loads - Room 4 - Bath/Laundry (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:11.0ft.System Number:1
Room Width:9.0ft.Zone Number:1
Area:99.0sq.ft.Supply Air:14CFM
Ceiling Height:8.0ft.Supply Air Changes:1.0AC/hr
Volume:792cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:2CFM
Runout Air:14CFMPercent of Supply.:12%
Runout Duct Size:5in.Actual Summer Vent.:1CFM
Runout Air Velocity:101ft./min.Percent of Supply:5%
Runout Air Velocity:101ft./min.Actual Winter Infil.:3CFM
Actual Loss:0.008in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
S -Wall-12F-0bw 9 X 8680.0654.43010.3020
E -Wall-12F-0bw 11 X 8880.0654.43890.3026
S -Gls-4A-6-d shgc-0.31 0%S40.31021.18417.0068
UP-Ceil-16C-50 11 X 9990.0201.41350.7067
Floor-20P-38 9 X 11990.0302.02020.1012
Subtotals for Structure:1,1110193
Infil.: Win.: 3.0, Sum.: 0.01601.1631860.00000
Ductwork:51360
Room Totals:1,8100253
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 14
Detailed Room Loads - Room 5 - Living Room (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:13.0ft.System Number:1
Room Width:13.0ft.Zone Number:1
Area:169.0sq.ft.Supply Air:92CFM
Ceiling Height:8.0ft.Supply Air Changes:4.1AC/hr
Volume:1,352cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:4CFM
Runout Air:92CFMPercent of Supply.:4%
Runout Duct Size:6in.Actual Summer Vent.:5CFM
Runout Air Velocity:467ft./min.Percent of Supply:5%
Runout Air Velocity:467ft./min.Actual Winter Infil.:4CFM
Actual Loss:0.118in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
N -Wall-12F-0bw 13 X 8620.0654.42740.3019
E -Wall-12F-0bw 13 X 8840.0654.43710.3025
N -Gls-4A-6-d shgc-0.31 100%S420.31021.188510.30434
E -Gls-4A-6-d shgc-0.31 0%S200.31021.142233.60672
UP-Ceil-16C-50 13 X 131690.0201.42300.70115
Floor-20P-38 13 X 131690.0302.03450.1020
Subtotals for Structure:2,52701,285
Infil.: Win.: 3.9, Sum.: 0.02081.1632420.00000
Ductwork:1,096397
Room Totals:3,86501,682
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 15
Detailed Room Loads - Room 6 - Kitchen (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:13.0ft.System Number:1
Room Width:11.0ft.Zone Number:1
Area:143.0sq.ft.Supply Air:21CFM
Ceiling Height:8.0ft.Supply Air Changes:1.1AC/hr
Volume:1,144cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:2CFM
Runout Air:21CFMPercent of Supply.:7%
Runout Duct Size:5in.Actual Summer Vent.:1CFM
Runout Air Velocity:152ft./min.Percent of Supply:5%
Runout Air Velocity:152ft./min.Actual Winter Infil.:2CFM
Actual Loss:0.017in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
N -Wall-12F-0bw 11 X 8730.0654.43230.3022
N -Gls-4A-6-d shgc-0.31 100%S150.31021.131610.30155
UP-Ceil-16C-50 13 X 111430.0201.41940.7097
Floor-20P-38 11 X 131430.0302.02920.1017
Subtotals for Structure:1,1250291
Infil.: Win.: 1.6, Sum.: 0.0881.1701030.00000
Ductwork:48690
Room Totals:1,7140381
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 16
Detailed Room Loads - Room 7 - Landing (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:6.0ft.System Number:1
Room Width:6.0ft.Zone Number:1
Area:36.0sq.ft.Supply Air:14CFM
Ceiling Height:8.0ft.Supply Air Changes:2.9AC/hr
Volume:288cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:1CFM
Runout Air:14CFMPercent of Supply.:6%
Runout Duct Size:5in.Actual Summer Vent.:1CFM
Runout Air Velocity:100ft./min.Percent of Supply:5%
Runout Air Velocity:100ft./min.Actual Winter Infil.:1CFM
Actual Loss:0.008in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
N -Wall-12F-0bw 5.5 X 8290.0654.41280.309
N -Gls-4A-6-d shgc-0.31 100%S150.31021.131610.30155
UP-Ceil-16C-50 6 X 6360.0201.4490.7024
Floor-20P-38 6 X 6360.0302.0730.104
Subtotals for Structure:5660192
Infil.: Win.: 0.8, Sum.: 0.0441.159510.00000
Ductwork:24459
Room Totals:8610251
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 17
Detailed Room Loads - Room 8 - Stairs (Average Load Procedure)
General
Calculation Mode:Htg. & clg.Occurrences:1
Room Length:11.0ft.System Number:1
Room Width:4.0ft.Zone Number:1
Area:44.0sq.ft.Supply Air:41CFM
Ceiling Height:8.0ft.Supply Air Changes:6.9AC/hr
Volume:352cu.ft.Req. Vent. Clg:0CFM
Number of Registers:1Actual Winter Vent.:1CFM
Runout Air:41CFMPercent of Supply.:3%
Runout Duct Size:5in.Actual Summer Vent.:2CFM
Runout Air Velocity:299ft./min.Percent of Supply:5%
Runout Air Velocity:299ft./min.Actual Winter Infil.:2CFM
Actual Loss:0.063in.wg./100 ft.Actual Summer Infil.:0CFM
ItemArea-U-HtgSenClgLatSen
DescriptionQuantityValueHTMLossHTMGainGain
W -Wall-12F-0bw 11 X 8730.0654.43230.3022
N -Wall-12F-0bw 4 X 8320.0654.41410.3010
W -Gls-4A-6-d shgc-0.31 0%S150.31021.131633.60504
UP-Ceil-16C-50 11 X 4440.0201.4600.7030
Floor-20P-38 4 X 11440.0302.0900.105
Subtotals for Structure:9300571
Infil.: Win.: 2.2, Sum.: 0.01201.1671400.00000
Ductwork:423177
Room Totals:1,4930748
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Rhvac - Residential & Light Commercial HVAC LoadsElite Software Development, Inc.
Air-City Heating & A/C LLCGillam Addition
Loveland, CO 80538Page 18
System 1 Room Load Summary
HtgMinRunRunClgClgMinAct
RoomAreaSensHtgDuctDuctSensLatClgSys
NoNameSFBtuhCFMSizeVelBtuhBtuhCFMCFM
---Zone 1---
1Closet32900151-52972044
2Bedr4oom1321,780291-524561303333
3Desk44597101-57619001010
4Bath/Laundry991,810301-510125301414
5Living Room1693,865631-64671,68209292
6Kitchen1431,714281-515238102121
7Landing36861141-510025101414
8Stairs441,493251-529974804141
Ventilation736152-142
Humidification719
Duct Latent-60
Return Duct796163-78
System 1 total69915,2712144,504-280228228
System 1 Main Trunk Size:7x8in.
Velocity:587ft./min
Loss per 100 ft.:0.097in.wg
Cooling System Summary
CoolingSensible/LatentSensibleLatentTotal
TonsSplitBtuhBtuhBtuh
Net Required:0.38107% / -7%4,504-2804,504
Equipment Data
Heating SystemCooling System
Type:Natural Gas FurnaceStandard Air Conditioner
Model:GMEC960302BNA
Indoor Model:
Brand:Kenmore
Description:Natural Gas or Propane Furnace
Efficiency:96 AFUE0 SEER
Comment :2 stage
Sound:00
Capacity:28,800 Btuh0 Btuh
Sensible Capacity:n/a0 Btuh
Latent Capacity:n/a0 Btuh
C:\\ ...\\Gallam Addition.rh9Friday, July 9, 2021, 5:15 PM
Form
Residential Plans Examiner Review Form
RPER 1.01
for HVAC System Design (Loads, Equipment, Ducts)
8 Mar 10
County, Town, Municipality, Jurisdiction
Header Information
REQUIRED ATTACHMENTS¹ATTACHED
Contractor
Manual J1 Form (and supporting worksheets):
YesNo
or MJ1AE Form² (and supporting worksheets):
YesNo
Mechanical License #
OEM performance data (heating, cooling, blower):
YesNo
Manual D Friction Rate Worksheet:
YesNo
Building Plan #
Duct distribution system sketch:
YesNo
Home Address (Street or Lot#, Block, Subdivision)
HVAC LOAD CALCULATION (IRC M1401.3)
Design Conditions
Building Construction Information
Winter Design ConditionsBuilding
Orientation (Front door faces)
°F
Outdoor temperature
North
4
North, East, West, South, Northeast, Northwest, Southeast, Southwest
°F
Indoor temperature
72
Number of bedrooms
1
Btu/h
Total heat loss
15271
Sq Ft
Conditioned floor area
699
Summer Design Conditions
°F
Outdoor temperature
Number of occupants
89
0
°F
Indoor temperature
Windows
75
Gr @% Rh
Eave overhang depth
Grains difference Ft
-21
50
0
Btu/h
Sensible heat gain
4504
Internal shade
Blinds, drapes, etc
Btu/h
Latent heat gain
-280
Number of skylights
Btu/h
Total heat gain
0
4224
HVAC EQUIPMENT SELECTION (IRC M1401.3)
Heating Equipment DataCooling Equipment DataBlower Data
Equipment typeEquipment type
Furnace
Standard Air Conditioner
CFM
Heating CFM
228
Air Conditioner, Heat pump, etc
Furnace, Heat pump, Boiler, etc.
Model
Model
GMEC960302BNA
CFM
Cooling CFM
228
Sensible cooling capacity
Heating output capacity
Btu/h
Btu/h
28800
Heat pumps - capacity at winter design outdoor conditions
Latent cooling capacity
Btu/h
Auxiliary heat output capacityTotal cooling capacity Btu/h
Btu/h
HVAC DUCT DISTRIBUTION SYSTEM DESIGN (IRC M1601.1)
Duct Materials Used (circle)
Design airflow CFM Longest supply duct:
Ft
Trunk Duct: Duct board, Flex, Sheet metal,
Lined sheet metal, Other (specify)
External Static Pressure (ESP)
IWC Longest return duct:
Ft
Component Pressure Losses (CPL)IWC Total Effective Length (TEL)
Ft
Branch Duct: Duct board, Flex, Sheet metal,
Lined sheet metal, Other (specify)
IWC
Friction Rate:
Available Static Pressure (ASP)
IWC
ASP = ESP - CPLFriction Rate = (ASP × 100) ÷ TEL
I declare the load calculation, equipment selection, and duct system design were rigorously performed based on the building plan listed
above, I understand the claims made on these forms will be subject to review and verification.
Contractor's Printed NameDate
Contractor's Signature
Reserved for use by County, Town, Municipality, or Authority having jurisdiction.
¹ The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions.
² If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions.
Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.
Form
Residential Plans Examiner Review Form
RPER 1.01
for HVAC System Design (Loads, Equipment, Ducts)
8 Mar 10
County, Town, Municipality, Jurisdiction
Header Information
REQUIRED ATTACHMENTS¹ATTACHED
Contractor
Manual J1 Form (and supporting worksheets):
YesNo
or MJ1AE Form² (and supporting worksheets):
YesNo
Mechanical License #
OEM performance data (heating, cooling, blower):
YesNo
Manual D Friction Rate Worksheet:
YesNo
Building Plan #
Duct distribution system sketch:
YesNo
Home Address (Street or Lot#, Block, Subdivision)
HVAC LOAD CALCULATION (UMC 1106.1)
Design Conditions
Building Construction Information
Winter Design ConditionsBuilding
Orientation (Front door faces)
°F
Outdoor temperature
North
4
North, East, West, South, Northeast, Northwest, Southeast, Southwest
°F
Indoor temperature
72
Number of bedrooms
1
Btu/h
Total heat loss
15271
Sq Ft
Conditioned floor area
699
Summer Design Conditions
°F
Outdoor temperature
Number of occupants
89
0
°F
Indoor temperature
Windows
75
Gr @% Rh
Eave overhang depth
Grains difference Ft
-21
50
0
Btu/h
Sensible heat gain
4504
Internal shade
Blinds, drapes, etc
Btu/h
Latent heat gain
-280
Number of skylights
Btu/h
Total heat gain
0
4224
HVAC EQUIPMENT SELECTION
Heating Equipment DataCooling Equipment DataBlower Data
Equipment typeEquipment type
Furnace
Standard Air Conditioner
CFM
Heating CFM
228
Air Conditioner, Heat pump, etc
Furnace, Heat pump, Boiler, etc.
Model
Model
GMEC960302BNA
CFM
Cooling CFM
228
Sensible cooling capacity
Heating output capacity
Btu/h
Btu/h
28800
Heat pumps - capacity at winter design outdoor conditions
Latent cooling capacity
Btu/h
Auxiliary heat output capacityTotal cooling capacity Btu/h
Btu/h
HVAC DUCT DISTRIBUTION SYSTEM DESIGN (UMC 601.2)
Duct Materials Used (circle)
Design airflow CFM Longest supply duct:
Ft
Trunk Duct: Duct board, Flex, Sheet metal,
Lined sheet metal, Other (specify)
External Static Pressure (ESP)
IWC Longest return duct:
Ft
Component Pressure Losses (CPL)IWC Total Effective Length (TEL)
Ft
Branch Duct: Duct board, Flex, Sheet metal,
Lined sheet metal, Other (specify)
IWC
Friction Rate:
Available Static Pressure (ASP)
IWC
ASP = ESP - CPLFriction Rate = (ASP × 100) ÷ TEL
I declare the load calculation, equipment selection, and duct system design were rigorously performed based on the building plan listed
above, I understand the claims made on these forms will be subject to review and verification.
Contractor's Printed NameDate
Contractor's Signature
Reserved for use by County, Town, Municipality, or Authority having jurisdiction.
¹ The AHJ shall have the discretion to accept Required Attachments printed from approved ACCA software vendors, see list on page 2 of instructions.
² If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition Checklist on page 13 of instructions.
Form generated by ACCA-approved Manual J Eighth Edition Version 2 Elite Software Rhvac program.